InteliConfig

PC Configuration and
Monitoring Tool

SW version 2.17.0
1 Document information 4
2 Getting started 8
3 Communication links 14
4 Connection menu 21
5 Monitoring 27
6 Configuration 37
7 Multicontroller features 145
8 Other features 150
9 Appendix 157

Copyright © 2021 ComAp a.s.


Written by Jan Donát, Jakub Šafanda, Jakub Váňa
Prague, Czech Republic
ComAp a.s., U Uranie 1612/14a,
170 00 Prague 7, Czech Republic
Tel: +420 246 012 111
E-mail: info@comap-control.com, www.comap-control.com Global Guide
Table of contents
1 Document information 4 3.6.2 Offline archive 20
1.1 Document information 4
4 Connection menu 21
1.1.1 Document history 4
4.1 Connection in general 21
1.2 Clarification of Notation 4
4.2 Create new site 22
1.3 About this guide 4
4.3 Add controller to site 22
1.4 Legal notice 5
4.3.1 Add new controller to site 22
2 Getting started 8 4.3.2 Add detected controller to site 23
2.1 Welcome 8 4.4 Context menu 24
2.2 Help and Manuals 8 4.4.1 Functions of context menu 24
2.3 Supported controllers 9 4.5 Export of site 24
2.3.1 Supported communication modules 10 4.6 Connection bookmarks 25
2.3.2 Supported extension modules 10 4.6.1 Default Connection 25
2.4 Installing InteliConfig 11 4.6.2 Alternative Connection 25
2.4.1 Requirements 11 4.6.3 Offline Mode 25
2.4.2 Installation procedure 11
5 Monitoring 27
3 Communication links 14 5.1 General information 27
3.1 Link types 14 5.2 Ribbon bar 27
3.1.1 Online connections 14 5.2.1 Control bookmark 27
3.1.2 Offline connections 14 5.2.2 Tools bookmark 28
3.2 AirGate 14 5.3 Control window 29
3.2.1 To obtain an AirGate 15 5.3.1 Control window features 29
3.2.2 To make an AirGate connection 15 5.3.2 Color highlights in the Control window 30
3.2.3 To end an AirGate connection 16 5.3.3 Control Window Customization 31
3.3 Direct connection 16 5.4 Right Dock Panel 32
3.3.1 To make a Direct connection 16 5.4.1 To open a window from RDP 32
3.3.2 To end a Direct connection 17 5.4.2 To pin a window to RDP 33
3.4 Detected controllers 17 5.5 Statistics 34
3.4.1 To make a connection with Detected 5.5.1 To set Statistics 34
controllers 17 5.5.2 To view Statistics 35
3.5 Internet / Ethernet connection 18
3.5.1 To make an Internet / Ethernet 6 Configuration 37
connection 18 6.1 General information 37
3.5.2 To end an Internet / Ethernet 6.2 Configuration window 38
connection 18 6.2.1 To open the Configuration window 38
3.6 Offline connection 19 6.2.2 Configuration window description 39
3.6.1 New Configuration 19

InteliConfig 2.17.0 Global Guide 2


6.2.3 Setpoints 40 6.9.4 Instrument / Screen properties panel 99
6.2.4 User Setpoints 40 6.9.5 Toolbar 100
6.2.5 User Protections 41 6.9.6 Virtual screen 101
6.2.6 Controller Inputs and Outputs 42 6.9.7 Instrument palette panel 102
6.2.7 Sensors 51 6.9.8 ICD (Integrated color display) and
6.2.8 Modules 52 InteliVision 5.2 screen types and structures 104

6.2.9 Logical Binary Inputs (LBI) / Logical 6.9.9 Working with the editor 105
Analog Inputs (LAI) 55 6.9.10 ICD and IV5.2 Instruments 107
6.2.10 PLC 56 6.9.11 Consistency check of Screens
6.2.11 Others 63 definiton 144

6.2.12 Consistency check 70


7 Multicontroller features 145
6.2.13 Value selection window 71
7.1 General information 145
6.3 Configuration import 73
7.2 View 145
6.4 Access 73
7.2.1 Site view 145
6.4.1 Enter password 73
7.2.2 Detail view 146
6.4.2 Deactivate password 73
7.3 Setpoints 146
6.4.3 Production mode 73
7.3.1 Multiwrite 147
6.5 Monitoring 74
7.4 Values 147
6.5.1 Setpoints 74
7.5 Login manager 148
6.5.2 Values 80
7.6 Saving archive(s) 149
6.5.3 History 84
6.5.4 PLC Monitor 86 8 Other features 150
6.6 Language 87 8.1 Help section 150
6.7 Firmware upgrade 87 8.2 Reporting problems 150
6.7.1 Default configuration 88 8.2.1 Steps 150
6.7.2 Current configuration 88 8.3 Cloning 150
6.7.3 Module FW 89 8.3.1 Create clone 150
6.7.4 Bulk / offlline update 89 8.3.2 Save the clone 151
6.8 Security 90 8.3.3 Manage clones 152
6.8.1 Change password (ver. 1) 90 8.4 Data export 154
6.8.2 Change access code 91 8.4.1 Exporting Setpoints, Values or Inputs
6.8.3 User management (ver. 2) 91 and Outputs 155
6.8.4 Change password (ver. 2) 92
9 Appendix 157
6.8.5 Change PIN (ver. 2) 93
9.1 PLC 157
6.8.6 Password reset 94
9.1.1 List of PLC blocks 157
6.9 ScreenEditor 96
9.1.2 Group: Basic Logical functions 157
6.9.1 ScreenEditor page layout 96
9.1.3 Group: Comparison of Analog inputs 160
6.9.2 Screens structure panel 97
9.1.4 Group: Time functions 162
6.9.3 Screen content panel 98
9.1.5 Group: Other functions 166

InteliConfig 2.17.0 Global Guide 3


1 Document information
1.1 Document information
1.1.1 Document history
Number Related SW version Date
11 2.17.0 26.2.2021
10 2.14.0 6.7.2020
9 2.13.0 30.6.2020
8 2.8.0 30.1.2020
7 2.4.0 30.8.2019
6 2.2.0 30.6.2019
5 2.1.0 31.5.2019
4 1.5.2 28.3.2019
3 1.3.0 7.1.2019
2 1.2.1 24.7.2018
1 1.0.0 9.1.2018

1.2 Clarification of Notation


Note: This type of paragraph calls the reader’s attention to a notice or related theme.

IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.

Example: This type of paragraph contains information that is used to illustrate how a specific function
works.

1.3 About this guide


This manual contains important instructions for InteliConfig PC monitoring and configuration tool. It provides
general information how to:
Install InteliConfig to user PC
Connect to supported controllers
Configure supported controllers
Monitor and control supported controllers

InteliConfig 2.17.0 Global Guide 4


1.4 Legal notice
This End User's Guide/Manual as part of the Documentation is an inseparable part of ComAp’s Product and
may be used exclusively according to the conditions defined in the “END USER or Distributor LICENSE
AGREEMENT CONDITIONS – COMAP CONTROL SYSTEMS SOFTWARE” (License Agreement) and/or in
the “ComAp a.s. Global terms and conditions for sale of Products and provision of Services” (Terms) and/or in
the “Standardní podmínky projektů komplexního řešení ke smlouvě o dílo, Standard Conditions for Supply of
Complete Solutions” (Conditions) as applicable.
ComAp’s License Agreement is governed by the Czech Civil Code 89/2012 Col., by the Authorship Act
121/2000 Col., by international treaties and by other relevant legal documents regulating protection of the
intellectual properties (TRIPS).
The End User and/or ComAp’s Distributor shall only be permitted to use this End User's Guide/Manual with
ComAp Control System Registered Products. The Documentation is not intended and applicable for any other
purpose.
Official version of the ComAp’s End User's Guide/Manual is the version published in English. ComAp reserves
the right to update this End User's Guide/Manual at any time. ComAp does not assume any responsibility for its
use outside of the scope of the Terms or the Conditions and the License Agreement.
Licensed End User is entitled to make only necessary number of copies of the End User's Guide/Manual. Any
translation of this End User's Guide/Manual without the prior written consent of ComAp is expressly prohibited!
Even if the prior written consent from ComAp is acquired, ComAp does not take any responsibility for the
content, trustworthiness and quality of any such translation. ComAp will deem a translation equal to this End
User's Guide/Manual only if it agrees to verify such translation. The terms and conditions of such verification
must be agreed in the written form and in advance.
Some components of open source software are being used in ComAp’s Software and Documentation to
InteliConfig. Their use is associated with obligation to disclose conditions for further distribution and use of the
herein listed open source software.ComAp notifies that no changes were made to the used version of the
software source code.
By quoting references to the provisions of any licenses for open source software, ComAp fulfils the obligations
arising from license agreement conditions on the individual open source software. Individual components may
not be used to modify or otherwise intervene to the Software and Documentation for ComAp’s Product
InteliConfig by the Distributor, End User or any other person.
Used open source software:
AutoMapper - https://automapper.codeplex.com/license
Copyright © 2010 Jimmy Bogard
AvalonDock - https://avalondock.codeplex.com/license
Copyright © 2007-2013, Xceed Software Inc. All rights reserved
cefsharp - https://github.com/cefsharp/CefSharp/blob/master/LICENSE
Copyright © 2010-2014 The CefSharp Authors

InteliConfig 2.17.0 Global Guide 5


Log4net - http://www.apache.org/licenses/ 1
Copyright © 2014 The Apache Software Foundation
1
Microsoft Prism - http://compositewpf.codeplex.com/license
Copyright © 2008-2012 Microsoft Corporation
1
NPOI - https://npoi.codeplex.com/license
Copyright © 2014 Neuzilla
SharpZipLib - http://icsharpcode.github.io/SharpZipLib/
Copyright © 2001-2010 Mike Krueger, John Reilly
1
Google Fonts Roboto Mono - https://fonts.google.com/specimen/Roboto+Mono
Copyright © 2015 Google Inc. All Rights Reserved
The full license text are available in an electronic form at ComAp and also may be sent to you upon your request
in a hardcopy against payment of the shipping charge and costs.

For more details relating to the Ownership, Extent of Permitted Reproductions Term of Use of the
Documentation and to the Confidentiality rules please review and comply with the ComAp’s License
Agreement, Terms and Conditions available on www.comap-control.com.
Security Risk Disclaimer
Pay attention to the following recommendations and measures to increase the level of security of ComAp
products and services.
Please note that possible cyber-attacks cannot be fully avoided by the below mentioned recommendations and
set of measures already performed by ComAp, but by following them the cyber-attacks can be considerably
reduced and thereby to reduce the risk of damage. ComAp does not take any responsibility for the actions of
persons responsible for cyber-attacks, nor for any damage caused by the cyber-attack. However, ComAp is
prepared to provide technical support to resolve problems arising from such actions, including but not limited to
restoring settings prior to the cyber-attacks, backing up data, recommending other preventive measures against
any further attacks.
Warning: Some forms of technical support may be provided against payment. There is no legal or factual
entitlement for technical services provided in connection to resolving problems arising from cyber-attack or
other unauthorized accesses to ComAp's Products or Services.
General security recommendations and set of measures
1. AccessCode
• Change the AccessCode BEFORE the device is connected to a network.
• Use a secure AccessCode – ideally a random string of 8 characters containing lowercase, uppercase letters
and digits.
• For each device use a different AccessCode.
2. Password
• Change the password BEFORE the device enters a regular operation.

1Licensed under the Apache License, Version 2.0 (the "License"); you may not use this file except in compliance
with the License. You may obtain a copy of the License at http://www.apache.org/licenses/LICENSE-2.0. Unless
required by applicable law or agreed to in writing, software distributed under the License is distributed on an "AS IS"
BASIS, WITHOUT WARRANTIES OR CONDITIONS OF ANY KIND, either express or implied.

InteliConfig 2.17.0 Global Guide 6


• Do not leave displays or PC tools unattended if an user, especially administrator, is logged in.
3. Controller Web interface
• The controller web interface at port TCP/80 is based on http, not https, and thus it is intended to be used only
in closed private network infrastructures.
• Avoid exposing the port TCP/80 to the public Internet.
4. MODBUS/TCP
• The MODBUS/TCP protocol (port TCP/502) is an instrumentation protocol designed to exchange data
between locally connected devices like sensors, I/O modules, controllers etc. From it’s nature it does not
contain any kind of security – neither encryption nor authentication. Thus it is intended to be used only in closed
private network infrastructures.
• Avoid exposing the port TCP/502 to the public Internet.
5. SNMP
• The SNMP protocol (port UDP/161) version 1,2 is not encrypted. Thus it is intended to be used only in closed
private network infrastructures.
• Avoid exposing the port UDP/161 to the public Internet.

InteliConfig 2.17.0 Global Guide 7


2 Getting started
2.1 Welcome 8
2.2 Help and Manuals 8
2.3 Supported controllers 9
2.4 Installing InteliConfig 11
6 back to Table of contents

2.1 Welcome
Welcome to InteliConfig from ComAp a.s.
InteliConfig is an on-line/off-line monitoring and configuration tool for use with various ComAp controllers, see
Supported controllers on page 9.
®
InteliConfig runs on various versions of Microsoft Windows™, see Installing InteliConfig on page 11.
The main four chapters of this guide reflect the primary functions of InteliConfig:
Communication links (page 14) – making the connection to the controller.
Monitoring (page 27) – viewing real-time operation and making setpoint adjustments.
Configuration (page 37) – making fundamental hardware, software settings, language changes and
firmware upgrades

2.2 Help and Manuals


Within InteliConfig you can access content Help and Manuals in several ways:
Latest Manuals for InteliConfig or Supported controllers (page 9) are available in main menu: click at
Home, choose the bookmark of Manuals and pick the required manual from the list of supported controllers.

Image 2.1 Manuals in InteliConfig

InteliConfig 2.17.0 Global Guide 8


Note: Chosen manual is automatically displayed in built-in PDF viewer. It is also possible to open the manual in
your own PDF viewer in separated window by clicking at Open full Reference Guide.

For general information about the InteliConfig application itself, go to Control bookmark in ribbon and in the
Help category click at

InteliConfig manual icon for opening the latest manual in external PDF viewer

About icon to open the About window containing basic information about InteliConfig version.
For general information about the connected controller, go to to Control bookmark in ribbon and in the Help
category click at

Controller manual icon for opening the latest relevant manual in external PDF viewer.

Controller help icon for opening the relevant controller Help file.

Controller info icon for opening the Controller info window containing information about the
controller (Serial Number, Type of Application, version of HW and FW etc.).
For further information about Setpoints, Values and Input/Output functions listings for the currently
connected controller select the required Setpoint, Value or Input / Output within the InteliConfig
Controller configuration window:
Basic information will appear automatically in the right Info panel.
More detailed information can be shown by clicking at Controller help button in Info panel or just by
pressing F1 key on your keyboard.

Image 2.2 Configuration of Setpoints with basic description in Info panel

2.3 Supported controllers


InteliConfig can be used with the following controllers:

Supported controller Description


InteliLite AMF25 Advanced Gen-set controller for single stand-by applications
InteliLite AMF20 Standard Gen-set controller for single stand-by applications
InteliLite MRS16 Advanced Gen-set controller for single prime move applications
InteliLite MRS11 Standard Gen-set controller for single prime move applications

InteliConfig 2.17.0 Global Guide 9


InteliLite 9 AMF Single Gen-set controller for stand-by and prime power applications
InteliLite 9 MRS Single Gen-set controller for prime power applications
InteliLite4 AMF8 Single Gen-set controller for stand-by and prime power applications
InteliLite4 AMF9 Single Gen-set controller for stand-by and prime power applications
InteliLite4 AMF25 Advanced single Gen-set controller for stand-by and prime power applications
InteliLite4 AMF20 Advanced single Gen-set controller for stand-by and prime power applications
InteliLite4 MRS16 Advanced single Gen-set controller for prime power applications
InteliGen 200 GC New generation of Parallel Gen-set Controller
InteliMains 210 MC New generation of Mains Controller
InteliMains 210 BTB New generation of Bus Tie Breaker Controller
InteliGen 500 New generation of Parallel Gen-set Controller with color display

2.3.1 Supported communication modules


Module Type Order code Description
Ethernet plug-in communication
CM-Ethernet Plug-in CM2ETHERXBX module for TCP/IP, TCP Modbus
or SNMP connection.

Support of AirGate connection.


CM3 - Ethernet Plug-in CM3ETHERXBX

GSM/GPRS plug-in
communication module for GPRS
CM-GPRS Plug-in CM2GPRSXXBX connection and SMS/E-Mail
notification.

Support of AirGate connection.


Combined module that offers fast
CM-4G-GPS Plug-in CM14GGPSXBX speed 4G communication
capability, including active SMS /
Emails alerts and control. Module
CM2-4G-GPS Plug-in CM24GGPSXBX also tracks GPS location and
supports AirGate.
Serial link communication module
CM-RS232-485 Plug-in CM223248XBX with RS232 and RS485 for Direct,
Modbus or ECU connection.

2.3.2 Supported extension modules


Module Type Order code Description
Combined extension plug-in module with 8
EM-BIO8-EFCP Plug-in EM2BIO8EXBX configurable terminals for binary inputs / outputs
and CT input for Earth Fault Current Protection.

InteliConfig 2.17.0 Global Guide 10


2.4 Installing InteliConfig
2.4.1 Requirements
Software requirements
®
InteliConfig can run on PCs equipped with any of the following versions of Microsoft Windows™ and
®
Microsoft  .NET Framework.

®
Operating System Version of Microsoft .NET Framework
Windows 8 and 8.1 4.7.1 or newer
Windows 10 (version 1607 and newer) 4.7.1 or newer

Hardware requirements

Component Minimum Recommended


Processor Intel Celeron 2.0GHz (Quad-core) Intel Core i5 2.9GHz (Quad-Core)
Memory (RAM) 4GB 8GB
Free disk space 1GB 1GB
Display 1280x768 1600x900

PC has to be equipped with USB 2.0 and other suitable communication interfaces (e.g. Internet connection).

2.4.2 Installation procedure


1. Download the ComAp PC Suite installation package from the ComAp website (www.comap-control.com).
2. Execute the downloaded file and follow the on-screen instructions.

InteliConfig 2.17.0 Global Guide 11


3. Read license agreement and accept them for continuing in installation.

4. Select components to install. It is recommended to use Full installation, but there is possibility of installing
only components you want.

5. Select additional tasks before the installation. Click 2x to Next and Install.

InteliConfig 2.17.0 Global Guide 12


Note: If your system already has InteliConfig installed, the installation program will offer an upgrade (if your
current version is older) or re-installation (if your current version is identical). If your current version is older, then
it is recommended to perform the upgrade because the controller firmware that you are about to install may not
be compatible with older InteliConfig versions.

6 back to Getting started

InteliConfig 2.17.0 Global Guide 13


3 Communication links
3.1 Link types 14
3.2 AirGate 14
3.3 Direct connection 16
3.4 Detected controllers 17
3.5 Internet / Ethernet connection 18
3.6 Offline connection 19
6 back to Table of contents

3.1 Link types


The following links can be used to connect InteliConfig together with a supported controller:

3.1.1 Online connections


Online connection with the supported controller allowing configuration, parameter setting and on-line monitoring
and control of the controlled device.

AirGate – ComAp proprietary protocol connection, for more information see AirGate on page
14
Internet / Ethernet – Internet or Ethernet connection, for more information see Internet /
Ethernet connection on page 18
Direct - Direct cable connection via RS232, RS485, for more information see Direct
connection on page 16
Detected controllers – Connection to automatically detected controllers via USB or Ethernet.
or
For more information see Detected controllers on page 17

3.1.2 Offline connections


Offline connection allows to open the saved offline archive or prepare any configuration for the further usage.

New configuration – Creating of new offline configuration, for more information see New
Configuration on page 19
Offline Archives – Open an archived configuration file, for more information see Offline archive
on page 20

3.2 AirGate
AirGate connection technology makes access to the ComAp controller via internet as simple as possible.
AirGate technology was designed to overcome the issues commonly faced when trying to connect remote
equipment using internet based communications.
AirGate allows ComAp’s controllers to connect to the internet using the existing network infrastructure,
negotiating firewalls and VPN systems and removing the requirement for static and public IP address.

InteliConfig 2.17.0 Global Guide 14


Image 3.1 Scheme of AirGate connection

3.2.1 To obtain an AirGate


1. Connect the communication module (CM-Ethernet or CM-GPRS) to the controller including the cable or
antenna.
2. Turn on the controller and configure the communication modules according to their relevant guides.
3. Ensure the AirGate function is ENABLED and AirGate IP is set to airgate.comap.cz.

4. By using of and buttons on the controller get to AirGate screen and note the displayed AirGate ID.

3.2.2 To make an AirGate connection


1. On supported controller fit a suitable communication module (CM-Ethernet, CM-4G-GPS or CM-GPRS).
2. Power on the controller with 8-36 V DC power terminal.
3. Connect the controller and the PC. How to make direct connection see Direct connection on page 16
4. In the InteliConfig go to Home menu → Connection bookmark → Online Connection and in section of
Controller connection click at AirGate, other parameter fields will roll down.
5. Enter the AirGate ID, AirGate server (enter "airgate.comap.cz" as standard), Port (use port "44445" as
standard), Access code and optionally even the controller Password.

InteliConfig 2.17.0 Global Guide 15


Image 3.2 Field for AirGate connection

6. Click at Open button to let the InteliConfig to establish the connection.

3.2.3 To end an AirGate connection


1. In the InteliConfig application click the Close connection icon to terminate the connection.

2. You will be asked whether you really wish to close the connection. Click at Yes button to close the
connection.

IMPORTANT: Archive is not saved automatically. If you want to save the archive, click at Save
archive icon before closing the connection.

3.3 Direct connection


The following direct cable connections are supported by InteliConfig:

Image 3.3 Scheme of Direct connection

3.3.1 To make a Direct connection


1. Fit a suitable communication module to supported controller or use the built-in USB.
Note: While plugging-in the communication module, the controller has to be switched off (8 - 36 V DC Power
terminals has to be disconnected).

2. Power on the controller with 8 - 36 V DC power terminal.


3. Connect an RS232 or RS485 cable between the controller and PC.
4. In the InteliConfig application on the PC go to Home menu → Connection bookmark → Online
Connection and in Controller connection click at Direct, other parameter fields will roll down.

InteliConfig 2.17.0 Global Guide 16


5. Choose the COM port, Controller address and optionally enter even the Password.
Note: Only COM ports that are actually installed and present in the computer will be displayed. If the USB
connection is used (either external USB to RS232 converter or USB on board), the USB must be handled as a
virtual COM port of your computer, which is created by the USB module driver.

6. Click to Open to let the InteliConfig to establish the connection.

3.3.2 To end a Direct connection


1. In the InteliConfig application click the Close connection icon to terminate the connection.

2. You will be asked whether you really wish to close the connection. Click at Yes button to close the
connection.

IMPORTANT: Archive is not saved automatically. If you want to save the archive, click at Save
archive icon before closing the connection.

3.4 Detected controllers


InteliConfig is able to automatically detect available supported controllers which are connected via:
USB - controllers needs to be equipped with USB-HID driver.
LAN - controllers needs to be connected to the same Local Area Network as the PC.
The following connections can be automatically detected by InteliConfig.

Image 3.4 Scheme of connections available for automatic detection

3.4.1 To make a connection with Detected controllers


1. On supported controller fit a suitable communication module.
2. Power on the controller with 8-36 V DC power terminal.
3. Make the required network links between the controller and the PC via a suitable network, USB or LAN.
4. In the InteliConfig go to Home menu → Connection bookmark and in section of Detected controllers in
the right part of the screen double click at the chosen controller.

Note: Controllers available via USB are marked with the icon. Controllers available via LAN are marked
with icon. In case of connection via LAN the question of Access code will appear.

Note: In case there are no Detected controllers showed click at icon for refreshing the list.

InteliConfig 2.17.0 Global Guide 17


3.5 Internet / Ethernet connection
The following network connections are supported by InteliConfig:

Image 3.5 Scheme of Internet / Ethernet connection

3.5.1 To make an Internet / Ethernet connection


1. Fit a suitable communication module to supported controller.
2. Power on the controller with 8-36 V DC power terminal.
3. Make the required network link(s) between the controller and the PC, either directly via a cross-over cable or
via suitable network switches.
4. In the InteliConfig application on the PC go to Home menu → Connection bookmark → Online
Connection and in Controller connection click at Internet / Ethernet, other parameter fields will roll
down.
5. In the roll-down fields enter the Controller address, IP address, the Access code and optionally enter
even the Password.
6. Click to Open to let the InteliConfig to establish the connection.
Note: The final (separated) IP address is a public address dedicated for testing connection to controller situated
in ComAp office. Feel free to try it.

3.5.2 To end an Internet / Ethernet connection


1. In the InteliConfig application click the Close connection icon to terminate the connection.

2. You will be asked whether you really wish to close the connection. Click at Yes button to close the
connection.

IMPORTANT: Archive is not saved automatically. If you want to save the archive, click at Save
archive icon before closing the connection.

InteliConfig 2.17.0 Global Guide 18


3.6 Offline connection
The Offline connection option allows you to open, inspect and edit previously saved archive. Archive is a file
which contain:
Configuration of the controller
History of the controller
Offline connection means any opened archive of the controller which is not directly connected to the controller.
It is used for preparing own configuration before using it in the controller, or just for an inspection of the archive
from the real site.
It is possible to open such offline archive in several different ways:
A. Creating of New configuration
B. Opening of Offline Archives

3.6.1 New Configuration


Use New configuration option whenever you want to create brand new archive based on the default one.
ComAp's default archives have timer proved settings which can be used on most Gen-sets.
To open the New configuration:
1. Go to Home bookmark in the main Ribbon menu.
2. Choose New configuration in left menu.

3. In the Default bookmark choose the required type of the controller and click at Create new
configuration icon.

Note: The Create new configuration icon is not active when other offline archive is already opened.

Note: In case you want to create a New configuration based on any earlier saved archive, go to the My
configurations bookmark and choose any of earlier saved archives.

Image 3.6 Create New Configuration

InteliConfig 2.17.0 Global Guide 19


3.6.2 Offline archive
For opening of offline archive:
1. Go to Home bookmark in the main Ribbon menu.
2. Choose Connection in left menu.
3. Choose the bookmark Offline Archives and here you can:

a. Open any archive from your PC by using of Open archive icon.


b. Open any recently opened archive from the lists of Recent archives or Recent used places.

Note: The Open archive icon is not active when other offline archive is already opened.

Note: Another way how to open the offline archive is just do double-click at the archive file in your PC equipped
with InteliConfig PC SW.

6 back to Communication links

InteliConfig 2.17.0 Global Guide 20


4 Connection menu
4.1 Connection in general 21
4.2 Create new site 22
4.3 Add controller to site 22
4.4 Context menu 24
4.5 Export of site 24
4.6 Connection bookmarks 25
6 back to Table of contents

4.1 Connection in general


InteliConfig can be connected with the supported controller via required link type from the Home overlay menu
directly. Connection is limited to ten controllers.
Options are following:

1. To connect to the controller online use Connection bookmark and in Online Connection tab you can:

a. Connect to the controller via AirGate.

b. Connect to the controller via Internet / Ethernet connection.

c. Connect to the controller via Direct connection.

d. Connect to the Detected controller via USB or LAN.

2. To create new configuration of the selected controller use New configuration bookmark and here you
can:
a. Create new configuration based on imported default archive in Default tab.
b. Create new configuration based on your previously created archive in My configurations tab.
Note: In the case there is imported any beta version of the controller firmware including its default beta
archives, these archives appears in special Beta versions tab.

3. To open offline archived configuration use Connection bookmark and in Offline Archives tab you can:

a. Open archive from selected place in your PC.


b. Choose from Recent archives.
c. Find the archive in Recent used places.

InteliConfig 2.17.0 Global Guide 21


4.2 Create new site
To create new site go through Connection bookmark and in Connections tab click on button Create new
site

Image 4.1 Create new site

4.3 Add controller to site


4.3.1 Add new controller to site
To add new controller to site go through Connection bookmark and in Connections tab click on button
Add new controller
Controller will be added always to selected site or to site, where is some controller selected
To site can be added unlimited number of controllers (connection is possible only to ten at the same time)

InteliConfig 2.17.0 Global Guide 22


Image 4.2 Add new controller to site

4.3.2 Add detected controller to site


To site can be added controller from panel Detected controllers by click on button in the top right corner
of bookmark Default Connection.

Image 4.3 Add detected controller to site

InteliConfig 2.17.0 Global Guide 23


4.4 Context menu
The context menu is available by right click on name of a site in the column Connections.

4.4.1 Functions of context menu


Open - open connection for selected site
New Controller - add new controller to selected site
New Site - create new site
Delete - delete selected item (site or controller)
Copy - copy selected item (site or controller)
Paste - paste (site or controller)
Import - import (site)
Export - export selected site (with connection parameters of all controllers in site)
Rename - rename selected item (site or controller)

Image 4.4 Context menu

4.5 Export of site


Created site can be exported from InteliConfig to your computer. Exported are by default connections
parameters of all controllers in site. Additional components may be added in the bottom of window. Exported
site can be easily imported to InteliConfig by opening exported file or by import button in Context menu.
To export site right click on the site in Connections column and select required data, which will be site exported.
It will be exported one file (exported_site.psi) to selected location.
Components to export:
1. AST's (Archive Sets)
a. Sets of archives will be exported with site (if some archive set is for selected site saved in database)

InteliConfig 2.17.0 Global Guide 24


2. Archives
a. Archives, which are not connected with any AST will be exported with site (if some archives is for
selected site saved in database)
3. Access Codes

Image 4.5 Export of site window

4.6 Connection bookmarks


4.6.1 Default Connection
Default Connection defines the primary set of connection parameters for defined controllers in sites. By click on
OPEN SELECTED button will be opened connection with default connection parameters (default connection
tab must be selected).

4.6.2 Alternative Connection


Alternative Connection is the secondary set of connection parameters. Connection parameters are by default
the same for each controller as in Default Connection until any change is done. By click on OPEN SELECTED
button will be opened connection with alternative connection parameters (alternative connection tab must be
selected).

4.6.3 Offline Mode


All archives
In bookmark All archives are stored all archives, which are connected with controllers in selected site.

To export archive, click on export archive icon

To rename archive, click on rename icon

To delete archive, click on delete icon

InteliConfig 2.17.0 Global Guide 25


Image 4.6 All archives bookmark

Archive sets
In bookmark Archive sets are stored all archive sets, which were saved in connection with selected site.
Archive set is folder containing all archives, which were available during save (possibility Save all archives to
database).
Opening archive set give you possibility to visualize offline image of the whole site.

InteliConfig 2.17.0 Global Guide 26


5 Monitoring
5.1 General information 27
5.2 Ribbon bar 27
5.3 Control window 29
5.4 Right Dock Panel 32
5.5 Statistics 34
6 back to Table of contents

5.1 General information


InteliConfig can be used to monitor and adjust one of supported controllers:
Online real-time monitoring via the Controlbookmark.
View and adjust Setpoints.
View Values and History logs.
View and setup Statistics.
Export data for use within spreadsheets.

5.2 Ribbon bar


Most of InteliConfig's functions are accessible by clicking the various icons arranged along its main Ribbon bar:

Image 5.1 Ribbon bar

Note: Ribbon bar can be hidden or displayed if necessary by clicking at "arrow" icon in the right upper corner.

5.2.1 Control bookmark


Icon Name Category Function Link to Topic

Close connection Connection Close the opened connection. -

Save archive Save Save configuration into the archive. -

Open the Controller configuration Configuration window


Controller configuration Configuration
window. description (page 39)
Open the window for Configuration
Configuration import Configuration Configuration import (page 73)
import.
Enter password / Enter password (page 73)
/ Access Enter / Deactivate password.
Deactivate password Deactivate password (page 73)
Setpoints window description
Setpoints Monitoring Open the Setpoints window.
(page 76)
Values window description
Values Monitoring Open the Values window.
(page 82)

InteliConfig 2.17.0 Global Guide 27


History window description
History Monitoring Open the History window.
(page 85)

PLC Monitor Monitoring Open the PLC Monitor window. PLC Monitor (page 86)

Controllers Monitoring Open the Controllers window. -

Language change - icon shows the name


Language Language Language (page 87)
of the chosen language directly.

Controller info Help Open the Controller info window.

Controller help Help Open theController help window.

Open the window with Controller manual


Controller manual Help -
in PDF.
Open the InteliConfig manual help
InteliConfig manual Help
window.

About Help Open the About window.

5.2.2 Tools bookmark


Icon Name Category Function

Create clone Cloning Open the Cloning window.

Save clone Cloning Save connected controller for future cloning.

Manage Clones Cloning Open the Import / Export clone window.

Firmware upgrade Firmware Open the window for controller or plug-in module firmware upgrade.

Open the Display Screens window, where can be changed screens of controller
Display Screens Configuration
display(not available for controllers with monochromatic display).

Set statistics Statistics Open the Set statistics window.

Control Window
Customization Open window for Control Window Customization.
Customization

Change password Security Open the Change password window.

Change access code Security Open the Change access code window.

Open Export data window. Data can be selected by type and exported to .csv or
Export to CSV/XLS Data export
.xls(x) format.
Generate Cfg image
Data export Generate configuration image of communication objects.
(COM)
Generate Cfg image
Data export Generate configuration image of Modbus objects.
(MODBUS)
Generate SNMP MIB
Data export Generate SNMP MIB table.
table

USB Flash Export Data export Export data from controller or InteliConfig to flash disk.

Reset from init


Reset Reset the controller from Init state.
state

InteliConfig 2.17.0 Global Guide 28


5.3 Control window
The Control window is available whenever a valid link is made to a controller or when an offline connection to an
archive files is open. The Control window provides a mixed overview of certain front panel items as well as key
values and alarms.

5.3.1 Control window features

Image 5.2 Description of Control window

# Description

Mode indicator – directly mimics the current setting of the controller's mode indicator.

Basic controller info – shows controller's name and serial number.

Diagram panel – mimics the diagram of the application and allows to control some of controller
buttons remotely.
Mains and Generator output values – provides voltage, current and general power factor
readings.
Analogue measuring panel – shows current values and protection limits of configured analog
inputs. This area could be for some controllers customized in Control Window Customization
(page 31)
Generator total output meter – provides an overall generator output meter reading for quick visual
confirmation.

InteliConfig 2.17.0 Global Guide 29


# Description
Statistic counters panel – shows a selection of important statistic values as Maintenance,
Running hours, Gen-set kWh and kVArh. This area could be for some controllers customized in
Control Window Customization (page 31)

Binary outputs panel – displays the current values of the various Binary outputs.

Binary inputs panel – displays the current values of the various binary inputs.

Status message area – mimics status messages of the engine and generator auto-mat related to
status of breakers, generator and engine. It mimics also the controller's current process timer.

Alarm list – display a list of current alarms as issued by the controller or ECU.

5.3.2 Color highlights in the Control window


Color highlights are used in various areas of the Control window to provide quick visual feedback. The meanings
of the highlights used differ slightly between areas, as follows:

Alarm list
Item color Meaning
*Alarm event Active and unconfirmed Yellow alarm (Warning)
Alarm event Active but confirmed Yellow alarm (Warning)
*Alarm event Inactivate but unconfirmed Yellow alarm (Warning)
*Alarm event Active and unconfirmed Red alarm (Shutdown or BOC)
Alarm event Active but confirmed Red alarm (Shutdown or BOC)
*Alarm event Inactivate but unconfirmed Red alarm (Shutdown or BOC)
*Alarm event Active and unconfirmed ECU alarm
Alarm event Active but confirmed ECU alarm
*Alarm event Inactivate but unconfirmed ECU alarm
*Alarm event Active and unconfirmed Sensor fail
Alarm event Active but confirmed Sensor fail
*Alarm event Inactive but unconfirmed Sensor fail

Diagram panel
Symbol / Color Meaning

Mains is OK.

Mains failed.

Generator is stopped and Ready.

Generator is running. There are no Red alarms at generator side.

Shutdown or BOC alarm at generator side. Generator is stopped or it is just


stopping.

InteliConfig 2.17.0 Global Guide 30


Bus indicator. Green = Bus voltage is present. Red = Bus failure occurred. Off =
Bus voltage is not present

Load is not powered up.

Load is powered from the Mains or Generator.

Breaker is opened.

Breaker is closed.

Measuring gauges
Symbol color Meaning
Green Value is in preset limit
Yellow Value is out of Yellow alarm limit. The Yellow alarm is announced also.
Red Value is out of Red alarm limit. The Red alarm is announced also.
White No values.
Table above is valid for following areas:
Mains and Generator output values.
Generator total output meter.
Analog measuring panel.

5.3.3 Control Window Customization


In the Control Window Customization you can easily define for analog inputs and statistics, which values will be
displayed in the control window. The window is accessible from the Ribbon menu in Tools category under icon
. Selected values are the same for every type of controller (e.g. for two InteliLite4 MRS16 are displayed the
same selected values). If the value is not available in the current configuration, it is displayed as "Value not
available".

InteliConfig 2.17.0 Global Guide 31


Image 5.3 Control Window Settings

Buttons description:
... – Opens the selection window with available values.

– Removes the currently selected value.

– Restores the default value.

5.4 Right Dock Panel


The Right Dock Panel (RDP) is here to help to monitor and set the controller more effectively. Through the RDP
it is possible to open following windows:
Setpoints
Values
History
PLC Monitor

Note: All of these windows have a possibility to be pinned-in by clicking at Pin button.

5.4.1 To open a window from RDP


1. Initiate online or offline connection with the supported controller.
2. Select the bookmark Control or Tools and in the Right Dock Panel (page 32) click at the bookmark
Setpoints or ValuesHistory to open the selected window.
3. The selected window will roll over the Control window.

InteliConfig 2.17.0 Global Guide 32


5.4.2 To pin a window to RDP
1. Open the supported window:
a. Setpoints
b. Values
c. History

2. Click at Pin icon.


The window will be pinned to the Right Dock Panel. The Control window will automatically adapt its size to the
screen.

Image 5.4 Setpoints window pinned to the Right Dock Panel

Size of the Control window can be controller by changing of the width of the pinned window or by using of
Control window zooming functions:

Fit the height of the Control window.

Fit the width of the Control window.

Zoom in the Control window.

Zoom out the Control window.

3. To unpin click at Unpin icon.


It is possible to pin-in more windows at once and to arrange them according to your needs by drag&drop
function.

InteliConfig 2.17.0 Global Guide 33


Image 5.5 Setpoints, Values and History windows pinned to the Right Dock Panel

5.5 Statistics
Statistic values (counters) are one of groups available in the Values (page 80). The difference from other values
is that statistics can be reset to zero or be preset to some value and they are also retained in the controller even
when the power is off.

5.5.1 To set Statistics


1. Initiate online or offline connection with the supported controller.

2. Select the Control bookmark and in the category of Access click at Enter password icon. Enter the
Administrator password for the full access to the controller.

3. Select the Tools bookmark and in the category of Statistics click at Set statistics icon to display the
Statistics setup window.

InteliConfig 2.17.0 Global Guide 34


Image 5.6 Statistics setup window

4. For each parameter enter your new required value and either:
a. Click the Set button, or
b. Continue changing all required values and after that click the Set all button.
5. When finished, close the window.
IMPORTANT: All statistic values can be reset to zero using Clear all button.

5.5.2 To view Statistics


1. Initiate online or offline connection with the supported controller.
2. For opening the Values window you can either:

a. Select the Control bookmark and in the category of Monitoring click at Values icon to open the
Values window.
b. Select the bookmark Control or Tools and in the Right Dock Panel (page 32) click at the bookmark
Values to open the Values window.
3. Select the group of Statistics.

InteliConfig 2.17.0 Global Guide 35


Image 5.7 Statistics in Values window

6 back to Monitoring

InteliConfig 2.17.0 Global Guide 36


6 Configuration
6.1 General information 37
6.2 Configuration window 38
6.3 Configuration import 73
6.4 Access 73
6.5 Monitoring 74
6.6 Language 87
6.7 Firmware upgrade 87
6.8 Security 90
6.9 ScreenEditor 96
6 back to Table of contents

6.1 General information


InteliConfig can be used to full configuration up to ten supported controllers:
Basic configuration of the controller in Configuration window.
Configuration of Setpoints.
Configuration of controller Inputs and Outputs.
Configuration of extension modules, CAN modules and ECU.
Configuration of additional functions – Languages, Access Rules etc.
Import of the configuration.
Upgrade of the controller firmware.
Cloning of one controller configuration to another controller.

InteliConfig 2.17.0 Global Guide 37


6.2 Configuration window
Configuration window enables you to view and adjust all parameters of configuration related to the supported
controller from one place.

6.2.1 To open the Configuration window 38


6.2.2 Configuration window description 39
6.2.3 Setpoints 40
6.2.4 User Setpoints 40
6.2.5 User Protections 41
6.2.6 Controller Inputs and Outputs 42
6.2.7 Sensors 51
6.2.8 Modules 52
6.2.9 Logical Binary Inputs (LBI) / Logical Analog Inputs (LAI) 55
6.2.10 PLC 56
6.2.11 Others 63
6.2.12 Consistency check 70
6.2.13 Value selection window 71
6 back to Configuration

6.2.1 To open the Configuration window


1. Initiate online or offline connection with the supported controller.

2. Select the Control bookmark and in the category of Configuration click at Controller configuration
icon to open the Configuration window.

Image 6.1 Configuration window

InteliConfig 2.17.0 Global Guide 38


6.2.2 Configuration window description

Image 6.2 Configuration window description

A. Configuration bookmarks – bookmarks sort out the controller configuration to few categories:
Setpoints – configuration of Setpoints.
Controller I/O – configuration of binary and analog inputs or outputs.
Sensors – adjusting analog sensor curves.
Modules – configuration of extension modules, CAN modules and ECU.
PLC Editor – allows to add control logic, additional alarm functions or even new features to meet
complex or unique requirements
Others – configuration of controller's additional functions: Init screen, Languages, Access rules,
Units/Power format, Modbus and Firewall.
B. Configuration window – main configuration window. The content may vary according to chosen
bookmark.
C. Info panel – contains basic information about the selected setpoint or Input / Output. Content and visibility
of the panel may vary according to chosen bookmark.
D. Tool bar – bar with handy tool while configuring setpoints. For more information see the chapter of
Setpoints (page 40)

InteliConfig 2.17.0 Global Guide 39


6.2.3 Setpoints
The Setpoints bookmark enables you to view and adjust each Setpoint present in the controller.
The Setpoints bookmark in Configuration window shows the same parameters as main Setpoints window
described in the separated chapter, see Setpoints on page 74.
IMPORTANT: The difference in both Setpoints windows is in the approach of parameter changing.
In case of separated Setpoints window the change of the parameter is immediately written into the
controller. Contrary to that any changes in parameters in Setpoints as a part of Configuration
window are written into the controller after pressing of OK and Restart button only.

6.2.4 User Setpoints


User Setpoints are setpoints, which can be created by user. Maximal number of User Setpoints depends on
controller type and its version.
User Setpoints are created as 32b signed numbers (int32).
User Setpoints could be used in any part of configuration where numeric setpoint can be used (PLC, Forced
value definitions, Protections...).
Parameters defined for User Setpoint:
Name (up to 32 characters)
Dimension (it is possible define new dimension)
Resolution (number of decimal places)
Allowed range
Default value (this value is stored in configuration and user can set typical value. This value can be changed
in Configuration window only)
Group/Subgroup – Setpoint is placed at the end of selected group/subgroup.
There is a flag for which the User Setpoint was created automatically or manually. When User Setpoint was
created automatically (for example when it created with protection), it is automatically deleted when this
protection is deleted and User Setpoint is not used on another place of configuration.

InteliConfig 2.17.0 Global Guide 40


Image 6.3 User setpoint definition window

6.2.5 User Protections


It is possible (when supported in controller) create protection on any binary or analog value (numeric data type
only). Protected value is not limited only to analog/binary inputs.
There are 2 ways how to create User Protection:

1. On card for I/O configuration, click on button in section Protections for selected input. Window for
protection definition is automatically opened and protected value is selected (cannot be changed in this
situation).

2. On tab Protections, select type of protected value (binary or analog). Click on button to open window
with definition of new protection.

InteliConfig 2.17.0 Global Guide 41


Image 6.4 Analog protection definition window.

Configuring protection
1. Select protected value (source)
a. When value is selected, setpoints for Limit and Delay are automatically created with correct format
2. Select Protection type, Active when, Block type, History record , Evaluation period.
3. Define protection name. This name is also used as text displayed in Alarmlist. Prefix is automatically
defined based on Protection type and cannot be changed.
4. Change objects for Limit and Delay if needed. It is possible use different object with correct format or change
properties of automatically created setpoints (change name, range, group/subgroup).
5. If you need binary information that this protection was evaluated as active, check "Use User Protection
State". This will create binary value with the same name as protection in Values - User Protection States.

6.2.6 Controller Inputs and Outputs


Controller I/O bookmark enables to configure Binary inputs, Binary outputs and Analog inputs available at the
supported controller.

To configure Inputs and Outputs:


1. In the Configuration window select the bookmark Controller I/O.
2. In displayed window choose what do you want to configure:
a. Binary inputs (page 45)
b. Binary outputs (page 46)
c. Analog inputs (page 47)
3. Configure the controller according to required wiring.

4. Once all changes within the Configuration window have been made click the OK and Restart button to
write the configuration to the controller. Once the configuration is uploaded the controller will automatically
restart and new connection will be automatically established.

InteliConfig 2.17.0 Global Guide 42


Inputs and Outputs configuration (ver. 1)

Image 6.5 Controller I/O window description

A. Configuration bookmarks – bookmarks sort out the controller configuration to few categories.
B. I/O Group panel – contains groups of inputs and outputs available in control unit itself.
C. Configuration panel – main configuration window with available inputs / outputs.
D. Info panel – contains basic information about the selected parameter. It shows:
Inputs / Outputs overview – overview of all available inputs / outputs including their description and type.
It contains following symbols:
Terminal is used for the function without any protection.

Terminal is used for the function including the Warning protection.

Terminal is used for the function including the Shutdown protection.

Terminal is not used.


Normally open binary input.
Normally close binary input.
Normally open binary output.
Normally close binary output.
Short description of the selected parameter.
Controller help button for opening full context help for the selected parameter.

InteliConfig 2.17.0 Global Guide 43


E. Tool bar

Save as... button – Saves the current configuration to the archive file.

OK and Restart button – Confirms the configuration and writes it to the controller. While the
configuration is written properly the controller will restart.

Cancel button – Closes the Configuration window without any change.

Inputs and Outputs configuration (ver. 2)

Image 6.6 Controller I/O window description

A. Configuration bookmarks – bookmarks sort out the controller configuration to few categories.
B. I/O Group panel – contains groups of inputs and outputs available in control unit itself.
C. Configuration panel – main configuration window with available inputs / outputs.
It is possible select more functions assigned to the specific input.

Add new function to the input. Normally open/close parameter could be set for each function
independently .

Remove function from the input.


It is possible add one or more protections to the specific input or binary output.

Create new protection on the input/output


Each input/output can have more than one protection configured.
List of all protections is on Protections tab.
It is possible move configuration from one I/O to another.

Configuration of this I/O is transferred to another I/O of the same type. For more information see
Transfer IO Configuration on page 49.

InteliConfig 2.17.0 Global Guide 44


It is possible remove configuration of I/O.

Remove configuration from I/O. For more information see Remove IO Configuration on page
50.
Select Normally open / Normally closed functionality for Binary input and Binary output

Binary input

Binary output
D. Info panel – contains basic information about the selected parameter. It shows:
Inputs / Outputs overview – overview of all available inputs / outputs including their description and type.
It contains following symbols:
Terminal is used for the function.
Terminal is not used.
Short description of the selected parameter.
Controller help button for opening full context help for the selected parameter.
E. Tool bar

Save as... button – Saves the current configuration to the archive file.
Consistency check button - Check whole configuration and display problems.

OK and Restart button – Confirms the configuration and writes it to the controller. While the
configuration is written properly the controller will restart.

Cancel button – Closes the Configuration window without any change.

Binary inputs
While configuring Binary inputs there are available 3 different options – in the field of Function choose:
A. Not Used – for the case that the Binary input is not wired or you don't want to use it.
B. Controller function – prepared functions directly in the controller as breaker feedbacks, external buttons
etc.. In this case it is possible in advanced to configure only:
Contact type as Normally close or Normally open.
C. General protection – in case you choose the general protection (as a default named as "BIN Protection #) it
is possible to predefined other values such as:
Name – Filled name will appear in case of activation in the Alarm list or History.
Contact type – Normally close or Normally open.
Protection type of the activated binary input:
Monitoring - it is possible to see the value in the Controller, in SCADA or in LE Values window but
no action is executed.
HistRecOnly – activating of such a binary input will cause the record to the History (including all
other values) but no alarm will be announced in Alarm list.
Wrn – Warning, activating of the binary input will cause the Warning alarm which is visible at the
controller and InteliConfig side too. Warning alarm is immediately written to the History.
Sd – Shutdown, activating of the binary input will cause the Shutdown alarm (immediate stop of the
engine). This alarm is visible at the controller and InteliConfig side too. Shutdown alarm is
immediately written to the History.

InteliConfig 2.17.0 Global Guide 45


BOC – Breaker Open and Cool Down, activating of the binary input will cause the BOC alarm
(immediate opening of the GCB, cooling of the engine and shutting down). This alarm is visible at the
controller and InteliConfig side too. Shutdown alarm is immediately written to the History.
Delay of the protection.
Engine running only means that the protection is active only after proper engine start.

Image 6.7 Binary inputs configuration

Binary outputs
While configuring Binary outputs it is possible to configure the Function as:
A. Not Used – for the case that the Binary input is not wired or you don't want to use it.
B. Controller function – prepared functions directly in the controller as Starter, Fuel Solenoid, breaker control
signals etc. In this case it is possible in advanced to configure:
Contact type as Normally close or Normally open.

InteliConfig 2.17.0 Global Guide 46


Image 6.8 Binary outputs configuration

Analog inputs
While configuring Analog inputs there are available 3 different options – in the field of Function choose:
A. Not Used – for the case that the Analog input is not wired or you don't want to use it.
B. Controller function – prepared functions directly in the controller as Oil Pressure, Coolant Temp and Fuel
Level. In this case it is possible in advanced to configure:
History abbreviation – shortcut of the function in the History
Sensor – choice of the curve for used analog sensor. For more information about sensors and theirs
configuration see Sensors on page 51.
Protection type of the activated analog input:
Monitoring – it is possible to see the value in the Controller, in SCADA or in InteliConfigValues
window but no action is executed.
HistRecOnly – exceeding of preset Hst value will cause the record to the History (including all other
values) but no alarm will be announced in Alarm list.
Wrn – Warning, exceeding of preset Wrn value will cause the Warning alarm which is visible at the
controller and InteliConfig side too. Warning alarm is immediately written to the History.
Wrn+BOC – Warning and Breaker Open and Cool Down, exceeding of preset Wrn value will cause
the Warning alarm and exceeding of preset BOC value will cause the BOC alarm. Both are visible at
the controller and InteliConfig side too. Both alarms are immediately written to the History.

InteliConfig 2.17.0 Global Guide 47


BOC – Breaker Open and Cool Down, exceeding of preset BOC value will cause the BOC alarm
(immediate opening of the GCB, cooling of the engine and shutting down). This alarm is visible at the
controller and InteliConfig side too. BOC alarm is immediately written to the History.
Wrn+Sd – Warning and Shutdown, exceeding of preset Wrn value will cause the Warning alarm and
exceeding of preset Sd value will cause the Shutdown alarm. Both are visible at the controller and
InteliConfig side too. Both alarms are immediately written to the History.
Sd – Shutdown, exceeding of preset Sd value will cause the Shutdown alarm (immediate stop of the
engine). This alarm is visible at the controller and InteliConfig side too. Shutdown alarm is
immediately written to the History.
"AI Name" Delay – delay of the protection.

Note: Parameter visibility depends on the setting of Protection type

Setpoint values of:


"AI Name" Hst – limitation value for History Record.
"AI Name" Wrn – limitation value for Warning.
"AI Name" BOC – limitation value for BOC.
"AI Name" Sd – limitation value for Shutdown.

Note: Setpoints visibility depends on the setting of Protection type.

Alarm parameter describes the condition of the alarm. It is visible only when the protection is activated:
Under Limit: alarm is activated if the value is lower than the preset setpoint.
Under Limit+Fls: alarm is activated if the value is lower than the preset setpoint or when the value is
out of sensor range.
Over Limit: alarm is activated if the value is higher than the preset setpoint.
Over Limit+Fls: alarm is activated if the value is higher than the preset setpoint or when the value is
out of sensor range.
Note: Parameter visibility depends on the setting of Protecton type.

Engine running only means that the protection is active only after proper engine start.

Note: Parameter visibility depends on the setting of Protection type.

C. AIN Switch – this Analog input controls logical bianry output Analog Switch. In case of Analog switch it is
possible to configure:
History abbreviation – shortcut of the function in the History.
Sensor – choice of the curve for used analog sensor. For more information about sensors and theirs
configuration see Sensors on page 51.
IMPORTANT: Value for activation and deactivation of the logical binary output is done by the
relevant setpoint of Analog Switch in the group of General Analog inputs.

D. AIN Protec – Analog input is used for any protection based on analog value. It is possible to configure:
Name – Filled name will appear in case of activation in the Alarm list or History.
History abbreviation – shortcut of the function in the History.
Sensor – choice of the curve for used analog sensor. For more information about sensors and theirs
configuration see Sensors on page 51.

InteliConfig 2.17.0 Global Guide 48


Protection type of the activated analog input. Same protection types as in Controller functions
described above.
Limitation setpoints, Alarm type and Engine running only option are the same as in Controller function
described above.
Note: Parameters visibility depends on the setting of Protection type.

Image 6.9 Analog inputs configuration

Transfer IO Configuration
This functionality offers to transfer the whole input/output configuration to another compatible input/output in the
same category. The icon for transfer is available in the top right corner of every input/output (if the
input/output supports transfer).

Image 6.10 Binary input with the possibility of transferring the configuration.

InteliConfig 2.17.0 Global Guide 49


Note: The configuration is transferred completely (functions, protections, sensor, PLC configuration) except
Modbus definition.

After clicking on the transfer icon is displayed window for selecting the destination input/output. Offered are only
compatible inputs/outputs of the same category. When the required input/output is selected and confirmed by
the OK button the transfer operation starts.

Image 6.11 The window for selecting the destination input/output.

Remove IO Configuration
This functionality offers to remove the whole input/output configuration. The icon for remove is available in
the top right corner of every input/output (if the input/output supports removing). The name of input/output is
after remove set to "Not Used".

Image 6.12 Binary input with the possibility of removing the configuration.

Note: The configuration is removed completely (functions, protections, sensor, PLC configuration) except
Modbus definition.

InteliConfig 2.17.0 Global Guide 50


6.2.7 Sensors
Curves in the Sensors bookmark are used to accurately determine how external analog electrical signal should
be converted to internal numerical values. By adjusting the curve you can ensure that the controller behaves
correctly across the range of values.

To adjust an analog sensor curve


1. In Configuration window select the bookmark Sensors.
2. In the left panel choose which sensor curve you want to adjust. It is possible to choose from the list of
typical (default) curves – e.g. VDO, or from the list of general curves.

Image 6.13 Sensor curve configuration

3. Use options within the Sensor window to make necessary adjustments:


Add line – to add new row in the table.
Order – to automatically arrange rows in the table from the lowest to highest number.
Delete line – to delete the chosen row in the table.
Open – to open saved curve.
Save – to save the current curve.
HW configuration – select physical (HW) configuration of Analog input
Sensor Name – customizable name of the sensor curve.
Resolution and Dimension of the curve.

4. Once all changes within the Configuration window have been made click the OK and Restart button to
write the configuration to the controller. Once the configuration is uploaded the controller will automatically
restart and new connection will be automatically established.

InteliConfig 2.17.0 Global Guide 51


6.2.8 Modules
Plug-in modules
There are two different approaches in configuration of Supported communication modules (page 10).
Communication plug-in modules – while assembled in the controller there appear relevant Group in Setpoints
window.
Extension plug-in modules – configuration should be made via the Configuration window:
1. Open the online / offline connection with the controller.

2. Go to Controller configuration and choose the bookmark of Modules.


3. Choose the relevant slot (A or B).

4. Pick the wanted plug-in module from the list and click at Add module icon.
5. Set required Plug-in module properties.
6. Go to I/O Configuration for added Plug-in module and set I/O configuration for this module.

7. Click at OK and Restart to take the configuration into effect.

Engine Control Unit – ECU


In case your engine is using ECU, it is necessary to configure it properly in the controller:
1. Open the online / offline connection with the controller.

2. Go to Controller configuration and choose the bookmark of Modules.


3. Click on ECU field in left column.
4. Select right ECU list from the list.

5. From the shown list of ECUs choose the same ECU as is used by your engine and click at Add module
icon.
6. Set proper ECU settings.
7. If necessary, go to I/O Configuration or Fault Codes Configuration for ECU and change configuration

8. Click at OK and Restart to take the configuration into effect.

Note: In case there is no ECU listed choose the used ECU list in the field of Electronic Control Unit.

ECU Fault Codes Configuration


Tab Fault Codes Configuration allows user to customize indication of ECU incoming messages.

Customization Possibilities:
1. Define own set of fault codes sent by ECU
2. Modify predefined set of fault codes sent by ECU
3. Setting own user messages
4. Changing the visibility of some messages

InteliConfig 2.17.0 Global Guide 52


Image 6.14 ECU Fault Codes Table

Add new definable item.

Remove existing item.

Export set of defined fault codes.

Import set of defined fault codes.

Restore default list of fault codes.

Fault Code Definition


Diagnostic Code SPN (Suspect Parameter Number)
Number identifying message from ECU

InteliConfig 2.17.0 Global Guide 53


FMI (Failure Mode Identifier)
Provides possibility to specify only selected diagnostic states (not available on all controllers)

States can be selected through the button , which opens FMI Numbers window

Image 6.15 FMI Numbers window

Message
Definition of the displayed message
Visibility
Visibility of the specific item

CAN modules
In case your controller supports CAN modules (external modules connected via CAN link), you can add
supported modules to offered CAN slots. Number of slots and list of supported modules depends on default
configuration provided by ComAp.
To add CAN module(s):
1. Open the online / offline connection with the controller.

2. Go to Controller configuration and choose the bookmark of Modules.


3. Choose the relevant CAN slot.

4. Select wanted CAN module from the list and click at button.
5. Set required CAN module properties. Pay attention to correct settings on module itself, usually described on
picture of module.
6. Go to I/O Configuration for added CAN module and set I/O configuration for this module.

7. Click at button to take the configuration into effect.

InteliConfig 2.17.0 Global Guide 54


6.2.9 Logical Binary Inputs (LBI) / Logical Analog Inputs (LAI)
This tab allow define source for any LBI/LAI.
For each LBI, it is possible use any binary signal available in controller. This signal could be inverted if needed.
For each LAI, it is possible use any analog value with numeric data format. Note, that LAI expects correct
format of value, it means right number of decimal places. If number of decimal places is different than expected,
controller functionality could be incorrect. See controller manual for details.

Image 6.16 Logical binary inputs tab.

InteliConfig 2.17.0 Global Guide 55


6.2.10 PLC
PLC Editor is powerful tool which helps you to create your own PLC scheme. It has graphical interface to have
user interface easy to use.

Image 6.17 PLC Editor main page

Working with the editor


If the currently opened archive does not contain any PLC program, then an empty drawing is created
automatically when you select the PLC Editor. The procedure of creation of a PLC drawing (program) contains
following essential steps:
Adjust the sheet to your needs. See Working with sheets (page 56) for more information.
Add PLC blocks into the sheets. See Adding PLC blocks (page 58) for more information.
Define inputs and outputs of the PLC program. See Define inputs and outputs (page 59) for more
information.
Create connections between inputs, blocks and outputs. See Creating wires (page 61) for more
information.
Adjust properties of the blocks. See List of PLC blocks (page 157) for more information about blocks.

Working with sheets

Change size of sheets


Drag the sheet edges to re-size the sheet according to your needs.

InteliConfig 2.17.0 Global Guide 56


Image 6.18 Adjusting PLC sheet

Multisheet
There is support of Multisheet functionality. It is possible create more sheets, for example each sheet for
specific functionality.
Each sheet could have user editable name and note. Just doubleclick on header of sheet. When Hints are
enabled, by place mouse cursor to header, name and note is displayed.
It is possible add new PLC Sheet, Delete selected PLC sheet (including its content) and move PLC Sheet up
and down.
When there is need to use value representing output of PLC block located on another PLC Sheet, it is not
necessary connect this output to right ladder to be able use it in different PLC Sheet. On any PLC Sheet it is
possible use any existing value with supported data type.

InteliConfig 2.17.0 Global Guide 57


Image 6.19 Management of PLC sheets

Note: Multisheet functionality is connected only with right version of InteliConfig. It is not conditioned by the
controller version.

IMPORTANT: You can get unexpected error message when connecting to controller or opening
configuration with more PLC sheets in configuration from older version of InteliConfig (without
support of PLC Multisheet). In this case download and install latest version of InteliConfig (PLC
Multisheet is supported from version 2.17.0).

Adding PLC blocks


Adding PLC block is simple and intuitive. Follow the procedure below to add PLC block.
Select required block from the list of available PLC blocks at the left and drag it into the sheet
Double-click on the block and adjust properties of the block. See List of PLC blocks (page 157) for more
information about blocks.
Connect the block inputs and outputs by drawing wires in the sheet. See Define inputs and outputs (page
59) for more information. It is also possible to connected inputs and outputs via properties of selected PLC
block.

InteliConfig 2.17.0 Global Guide 58


Image 6.20 Adding PLC blocks

Note: To delete PLC block just click on it and press delete button. Also delete selection function can by used.

Note: To see context help for selected PLC block just press F1 button.

Define inputs and outputs

Image 6.21 Blank sheet of PLC editor

InteliConfig 2.17.0 Global Guide 59


Inputs
Sheet inputs are located at the left side of a sheet. Follow the procedure below to add or edit an input.
Double-click on a free input position or existing input to add new input or edit the existing one.
Select the source for the input.
If you create a Binary input, you can select a source from following categories:
Bin. Values – this category contains all binary values available in the controller as binary inputs,
logical binary outputs etc.
PLC Outputs – this category contains all PLC blocks binary outputs available in the controller
If you create an Analog input, you can select a source from following categories:
Ana. Values – this category contains all analog values available in the controller as analog inputs,
electrical values, values from ECU etc.
All Setpoints – this category contains all setpoints of the controller except the dedicated PLC
setpoints. Names, resolutions and dimensions of these setpoints can not be modified
PLC Setpoints – this category contains a group of setpoints which are dedicated for using in the PLC
program. PLC setpoints can be renamed, their dimension, resolution and limits can be modified
according to need of PLC blocks where they are used

Image 6.22 PLC inputs

InteliConfig 2.17.0 Global Guide 60


Outputs
Sheet outputs are located at the right side of a sheet. Follow the procedure below to add or edit an input.
Doubleclick on a free output position to add new sheet output
Doubleclick on an already created output to configure the output onto a controller output terminal or a logical
Binary input (first of all some PLC block output has to be connected to this output to enable configuration of
output)

Image 6.23 PLC outputs

IMPORTANT: It is necessary to click on Connect button after selecting the output. Otherwise PLC
output is not connected to output.

Creating wires
Wires can be created between PLC inputs and PLC blocks and between PLC blocks and PLC outputs.
IMPORTANT: Keep the order of starting and finishing connection points. Wires between inputs and
blocks have to start from inputs. Wires between blocks and outputs have to start from blocks.

Follow the procedure below to create wire.

InteliConfig 2.17.0 Global Guide 61


Locate the mouse pointer over the starting point of the wire. If the area under the mouse pointer is a
connection point, the pointer will change the color (fill of pointer will be white).
Press and hold the left mouse button and drag the wire to the destination of required connection point. If you
point over a valid connection point, the connection point will be marked with a red circle.
Release the left mouse button to create a wire between the two points. The wire is routed automatically.

Note: It is possible to make connection only between the outputs and inputs with the same type of value (binary
or analog). Binary values are marker by black pointer, analog values are marked with green pointer.

Note: To delete wire just click on it and press delete button on your keyboard. Also delete selection function
can by used by selecting more objects and clicking on the delete selection button

PLC logic execution rules


The PLC program is executed every 100 ms. The blocks are executed in order according to block numbers (item
numbers), which are indicated in each block. The block numbers are assigned automatically according to
position on sheet.

Image 6.24 PLC execution logic

IMPORTANT: Please always check that the blocks are ordered correctly, especially if you use direct
feedbacks from outputs to inputs within one sheet. Wrong order may lead to incorrect results!!!

InteliConfig 2.17.0 Global Guide 62


Other functions
Delete whole content of sheet
Use this function to delete the whole content of sheet (including blocks, wires, inputs, outputs, etc...).

Hints
Use this function to enable or disable quick hints for blocks (controller help is not affected by this function).

PLC monitor
PLC monitor is a powerful tool for monitoring your PLC . Just click on PLC monitor button on main InteliConfig
page to see your PLC. Active inputs and outputs have blue color. Also wires with active signals have blue color.
IMPORTANT: It is not possible to edit PLC in PLC monitor tool.

6.2.11 Others
In the Configuration window use the bookmark of Controller for the advanced configuration, you can either:
Change the Init screen. For more information see Init screen on page 63.
Change the Languages of the controller. For more information see Languages on page 64.
Change the Access rules. For more information see Access rules on page 66.
Change the Units/Power format. For more information see Units / Power format on page 68.

Init screen
Init screen is shown each time when the controller is started up when enabled. Here you can change the
message you want to be shown during the controller start up.
1. Open the online / offline connection with the controller.

2. Go to Controller configuration and choose the bookmark of Control


3. Go to the group of Init screen.
4. Enable Init screen by ticking off the Enable Init screen field.
5. Choose the language.

InteliConfig 2.17.0 Global Guide 63


6. Enter the content of Init screen.

7. Click at OK and Restart to take the configuration into effect.

Languages tab
In this tab it is possible to manage list of languages in configuration and make own translations.

Languages
ComAp controllers support different languages. For their configuration:
1. Open the online / offline connection with the controller.

2. Go to Controller configuration and choose the bookmark of Control


3. Go to the group of Languages.
4. Left column shows Available languages, Right column shows Languages presented in the controller (in the
configuration). By using Add or Remove buttons or by drag&drop functionality choose those languages
which you want to have presented in the controller.

5. Click at OK and Restart to take the configuration into effect.

Note: First language, English, is a basic language of the controller and can't be removed.

Image 6.25 Adding / Removing Languages to the Controller

Translator
Translator allows user translation of any text in controller configuration.
1. Open the online / offline connection with the controller.

2. Go to Controller configuration and choose the bookmark of Control


3. Go to the group of Languages.

InteliConfig 2.17.0 Global Guide 64


4. Go to the tab Translator. Update translations for languages in configuration.

5. Click at OK and Restart to take the configuration into effect.

Image 6.26 Translator

Each available language has its own Default dictionary with translations prepared by ComAp. If there is no
translation in this dictionary or user wants to use different translation, automatically is created User dictionary
for specific language to store all user translations. The User dictionary takes precedence over the Default
dictionary. The User dictionary can be exported to disk and imported on another PC. But only one User
dictionary for each language can exists on PC.

Translator use color indication for each text to indicate different states
Text not translated. It is possible to use user translation.
Text in specific language is the same as in English and does not exist in User or Default
dictionary.
Text has been translated earlier but there is no translation in current dictionaries. It is possible to
add this text to user dictionary.
Text in specific language is different from English (text was translated earlier by different user) and
there is no translation in User or Default dictionary.

Text translated using user dictionary. It is possible to remove this text from user dictionary.

Text translated using default dictionary. It is possible to use user translation.

Text has been translated earlier, but there is a different translation in the current dictionaries. It is
possible to add / update translations in user dictionary.
Text cannot be translated. This is default language or default dictionary for this language is missing.
Because User dictionary is connected with Default dictionary for specific language, it cannot exist when there is no Default
dictionary.

InteliConfig 2.17.0 Global Guide 65


Operations with texts available in translator

Add selected text to the user dictionary.

Add all yellow-marked texts to the user dictionary.

Add all red-marked texts to the user dictionary.

Delete selected translation from the user dictionary.


Text is automatically translated using Default dictionary. If there is no translation, text is replaced by
English text.

Translate all texts in all languages.

Operations with User dictionaries

Export dictionaries to file.

Import dictionaries from file.

It is possible to export dictionaries to the disk as package (extension is .psidict). User can select which
dictionaries will be included into package. Displayed are only languages where User dictionary exists. Exported
is always pair of dictionaries (User nad Default) – It is usefull, if it is required to copy Used dictionaries from one
PC to another.
During import (allowed are only packages with extension .psidict) can user select which dictionaries will be
imported. It is not necessarry to import all dictionaries contained in package.
Note: When importing dictionaries, existing dictionaries are rewrited by imported ones.

Access rules
ComAp controllers support at least 2 different user approaches to the controller – without the password and with
the password. Protected approach can be differentiated to another 3 different groups. Setting of access rules:

InteliConfig 2.17.0 Global Guide 66


1. Open the online / offline connection with the controller.

2. Go to Controller configuration and choose the bookmark of Control


3. Go to the group of Access rules.
4. Within all setpoints, organized by groups, select the access right for each user:
No password – User 0
User 0 can be allowed to either read only or read and write the setpoint
User 0 can be disallowed to perform selected commands
Password level 1 – User 1
User 1 can be allowed to either read only or read and write the setpoint
User 1 can be disallowed to perform selected commands
Password level 2 User 2
User 2 can be allowed to either read only or read and write the setpoint
User 2 can be disallowed to perform selected commands
Password level 3 – Administrator
Administrator is allowed to change any setpoint without any limitation
Administrator has the full access to all commands

Image 6.27 Access rules window - description

It is possible to set following rights:


Read Only
The user is able to see the value of the setpoint but he is not allowed to change it
Read and Write
The user is allowed to see and change the value of the setpoint
In addition it is possible to choose the visibility of the Setpoint, it can be either:
Standard
The setpoint is visible all the time
Advanced only
The setpoint is visible at the controller only when switched to Advanced mode

InteliConfig 2.17.0 Global Guide 67


5. Click at OK and Restart to take the configuration into effect.
For the information how to set up Password and define user levels see Change access code on page 91.
IMPORTANT: InteliConfig PC SW is in the group of Basics Settings showing in the fact some of
Setpoints from the group of Alternate Configuration - e.g. Nominal frequency, Nominal current,
Nominal voltage etc. Please consider this fact during configuration of Access rules.

Units / Power format


InteliConfig supports both Metric and US Units/Power format. In this tab you can also define required Power
format.

Image 6.28 Units / Power format setting

Modbus
InteliConfig supports create user definition of Modbus registers

Image 6.29 Modbus definition

InteliConfig 2.17.0 Global Guide 68


Controller supports access to most its objects using Modbus protocol. This window allows to define list of
Modbus registers and its meaning (connection Modbus register <->controller object).
In configuration are three groups of objects. Each group has assigned range of Modbus registers.
Binary objects: <0...999>
Values: <1000...2999>
Setpoints: <3000...3999>
Default controller configuration may contain some Modbus definition. This definition can be modified based on
user needs. If there is no definition (group is empty), definition could be created.
Available operations:

– Add new Modbus register. Free Modbus register is predefined as default, can be changed in allowed range.
Controller object is selected from the list.

– Delete selected Modbus register.

– Edit already defined Modbus register

– Export Modbus definition to file

– Import Modbus definition from file. This replaces while Modbus definition in configuration (remove all
defined Modbus registers and import Modbus registers from file).
Each Modbus register can contain 2 bytes of data. In controller exist objects, which are bigger than 2 bytes
(statistics values, text setpoints...). It is necessary to use more Modbus registers for this objects. When
configuring Modbus register for this object, only first Modbus register is chosen by user. System automatically
use following registers for other bytes (Modbus register is increased by +1). There must be enough free space in
Modbus table definition to allow create appropriate number of Modbus registers. Othervise Modbus register
cannot be added. This Modbus registers are in gray, it means cannot be edited or deleted separately.
There is example of Modbus definition for setpoint Gen-set name:

It is allowed to have more different Modbus registers for the same object.
Modbus registers definition table is automatically sorted by Modbus column.
In window is available Search functionality. This will find any text in definition table in selected group.

InteliConfig 2.17.0 Global Guide 69


Firewall
Firewall rules are used to explicitly define parameters of incoming TCP/UDP communication, which will be
accepted by the controller. All other communication will be dropped. Firewall is by default disabled on
controllers, which support this functionality.
A firewall rule definition consists of:
1. IP address
2. Address mask
3. Port

Image 6.30 Firewall window

To add new firewall rule, click on add new row icon and fill in all required values

To remove firewall rule, click on delete row icon

6.2.12 Consistency check


There may be various inconsistencies in the configuration. It is very hard to allow only consistent changes
during configuration process and it is also very limiting to user, in some situation temporary inconsistency is
required.
To have final configuration without inconsistencies, Consistency check functionality is available to user.

Consistency check could be manually started by user by click on button located near
OK and Restart button. Consistency check is also automatically started when "OK and Restart" is clicked and
during "Save As" from Configuration window. Consistency check is available in Configuration.
User is noticed about all inconsistencies in configuration in separate window. This window can be kept

displayed as long as the Configuration window is open. To refresh data, click on button in this

window or on button in Configuration window.

InteliConfig 2.17.0 Global Guide 70


More than one inconsistencies (individual reports) could have the same season (for example incompatible
resolution of User Setpoint).

Image 6.31 Configuration window with Consistency check

Image 6.32 Consistency check resul window

Note: ScreenEditor Consistency check must be performed separately.

6.2.13 Value selection window


The window is used in situations, where object from configuration can be assigned (PLC, protection source
value, LAI, LBI etc.). Items in the window are organized to categories which are displayed at the top of the
window. Each category has its own table with items, which can be assigned to the object, from which was a
window opened (displayed items are compatible for destination area).

InteliConfig 2.17.0 Global Guide 71


Image 6.33 Value selection window

Window functionalities
Filter panel
Filter panel is displayed under main categories at the top of the window. It allows you to easily start writing
name of required value and during this operation are items dynamically filtered. After two characters are entered,
the entire table with items is expanded.

Collapse All / Expand All


In the top left corner of the items table is placed icon for Collapsing / Expanding all groups and subgroups.

Control from keyboard


If the focus is placed inside the items table it is possible to use standard table control as tabulator, arrows,
select by the enter (double click on item possible too).

InteliConfig 2.17.0 Global Guide 72


6.3 Configuration import
In case of opened online connection it is possible to write into the controller other configuration from the
prepared archive – import of the configuration:
1. Open the online connection with the controller.
Note: Not every type of online connection needs to be supported , e.g. AirGate via GPRS module...

2. Go to Control bookmark and in the category of Configuration click at Configuration import icon.
3. In the opened Explorer window find the wanted archive and click at Open.
4. The new Configuration window will appear. Now you can check the needed configuration and in the case
you want to use it click at OK and Restart to take the configuration into effect.

6.4 Access
Access bookmark allows users activate or deactivate password. InteliConfig contains 4 Access levels. For
more information about Access rules see Access rules on page 66.

6.4.1 Enter password


If is Password activated, Access tab indicates red lock icon and it is a need to Enter password.

Note: How to Change password see Change password (ver. 1) on page 90.

6.4.2 Deactivate password


If is Password deactivated, Access tab indicates green unlock icon. After required configuration user can
Deactivate password and lock the Configuration.
InteliConfig contains 4 user levels. Access tab can displays this levels.

Image 6.34 Unlocked access level

Note: How to Change passwordsee Change password (ver. 1) on page 90.

6.4.3 Production mode


Production mode allows you to work with the controller without the need to log in as an administrator. All
operations for which an administrator account is usually required are enabled even without logging in. It means
that until the production mode is turned off you have fully access as administrator. This mode could be helpful
during the commissioning when is not necessary to verify logged user. If this mode is on, it is signalized by the
different icon in the section, where level of logged user is displayed.

InteliConfig 2.17.0 Global Guide 73


Production mode setting
Production mode can be set in the right part of the user management window. The setting is by a check-box
(turned on/turned off). If the production mode is turned on, the changes are applied immediately, but to use it is
necessary to log out.

Image 6.35 The window for setting production mode.

6.5 Monitoring
6.5.1 Setpoints
The Setpoint window enables you to view and adjust each Setpoint present in the controller. It is possible to
choose whether some or all Setpoints require password protection from unauthorized changes. When displayed
within the window, any password protected Setpoint will be shown with a gray background and will remain
uneditable until a password of proper level is entered. In off-line mode, Setpoints can be altered without a
password, however, a password will be required later when the modified archive is written into the controller.
In cases where you need to copy across one or more Setpoint values from an archive file, use the Alternative
setpoints feature to provide assistance Control window (page 29).
Note: For AirGate connections, when retrieving the history from the controller, the Setpoint window will be
disabled until the History has been fully downloaded.

InteliConfig 2.17.0 Global Guide 74


To open the Setpoints window
1. Initiate online or offline connection with the supported controller.
2. For opening the Setpoints window you can either:

a. Select the Control bookmark and in the category of Configuration click at Controller
configuration icon to open the Configuration window. Now select the bookmark Setpoints.

b. Select the Control bookmark and in the category of Monitoring click at Setpoints icon to open the
Setpoints window.
c. Select the bookmark Control or Tools and in the Right Dock Panel (page 32) click at the bookmark
Setpoints to open the Setpoints window.

Image 6.36 Setpoints window

IMPORTANT: For opening of Controller configuration window for the online connected
controller it is necessary to enter the password. To enter the password select the Control bookmark
and in Access category click at Enter password.

Note: In case of changing parameters in the Setpoints window (opened by clicking at Setpoints icon or at
Setpoints bookmark in Right Dock Panel) the effect is immediate after confirmation of the change by Enter key
or by clicking to another parameter. In case of changing parameters in the Configuration window (opened by
clicking at Controller configuration icon) it is necessary to confirm all changes by pressing the OK and
Restart button.

InteliConfig 2.17.0 Global Guide 75


Setpoints window description

Image 6.37 Setpoints window description

A. Setpoint group panel – contains all visible groups for the current type of controller.
B. Setpoints panel – contains all visible setpoints (parameters) within the selected group. This panel can
contain following parts of parameters:
Name of the Setpoint.
Value of the Setpoint and unit.

Numbers of the alternative –  or ‚. Some setpoints have two different alternatives which are
switchable by the configured Logical Binary input.
C. Info panel – contains basic information about the selected Setpoint. It shows:
Parameter range.
Parameter units.
Original value of the setpoint – this value resets always after the new connection.
Default value of the setpoint – value of the default configuration prepared by ComAp.
Short description of the setpoint – basic information about the purpose of the setpoint.
Controller help button for opening full context help for the selected setpoint.

InteliConfig 2.17.0 Global Guide 76


D. Tool bar - bar with handy tool while configuring setpoints. It contains following functions:
Search

Search panel.

Go to previous occurrence.

Go to next occurrence.

Cancel search.
View

Turn on/off hiding functionality – setpoints are appeared / hidden


Operations

Set all setpoints to default value – this option will reset all made changes and will set all Setpoints
to default values.

Reset original values – this option will reset all made changes back to original values.
Alternative setpoints

Show alternatve setpoints – this icon will open the explorer window where it is possible to find the
configuration for the Setpoint comparison.

Hide alternative setpoints – in case of opened Alternative Setpoints this option will close it.

Show/Hide alternative setpoint names – this option will show or hide names of alternative
Setpoints to show possible differences.

Import all alternative values – this option will rewrite all Setpoints of the openned connection by
those from the alternative configuration.

Import selected alternative value – this option will rewrite the selected Setpoint of the openned
connection by the relevant value from the alternative configuration.
Hide panel

Hide panel – this option will hide the whole Tool bar. In case of hidden Tool bar only the icon of
is shown in the right bottom corner of the Setpoints window. After click at this icon the Tool bar will
appear again.

Note: The separate Setpoints window is possible to pin to the Right Dock Panel (page 32) by using of Pin
icon.

To edit a Setpoint
1. In the Setpoint window, click the required Group name to display all related setpoints.
2. In the Setpoint value column, click the cell adjacent to the required setpoint in order to highlight it (in light
blue).
Note: If the cell has a dark gray highlight then it is password protected and you'll first need to enter a valid
password.

3. Change the setpoint by writing new value, increasing or decreasing the value by using of arrows or just by
choosing from the offered list.

InteliConfig 2.17.0 Global Guide 77


Note: In cases where you need to copy across one or more setpoint values from an archive file, use the
Alternative setpoints feature to provide assistance.

Note: In cases where you need to use the Original or Default value just double-click at this value in the info
panel and it will be automatically written in the required setpoint. If the Original or Default value differs from the
actual value of the Setpoint it is highlighted with bold font.

4. Continue with other changes. Setpoints are written to the controller immediately after pressing of Enter key
or right after choosing another setpoint.

IMPORTANT: In case of changing Setpoints in Configuration window all changes will take
affect after pressing OK and Restart button only.

Additional functions of Setpoints window


Setpoints window of InteliConfig offers different highlighting of groups, parameters or values to help the user to
find all needed information.

Image 6.38 Functions of Setpoints window

# Meaning
1 Active group of Setpoints.
2 Active setpoint. Basic info about the Active Setpoint available in the Information panel on the right.
3a Changed setpoint from its original value.
3b Indication of the group which contains any changed Setpoint.

InteliConfig 2.17.0 Global Guide 78


4a Searched word via the Search panel in the Tool bar.
4b Indication of the group which contains any searched words.
Indication of setpoints which have its alternate option. Green number indicates the active value. See
5
Alternate Configuration chapter.

Table 6.1 Functions of Setpoints window

Alternative setpoints
Alternative setpoints is a InteliConfig feature that can help to compare two different configurations and to import
one or more setpoint values from another archive.

Image 6.39 Setpoints window with Alternative setpoints

To open Alternative setpoints


1. Establish the online connection with the controller or open the offline archive.
2. Open the Setpoint window.

3. In the bottom Tool bar in the Setpoints window click at Show/Hide alternative setpoints icon.
4. Open the chosen configuration archive and click at Open.

InteliConfig 2.17.0 Global Guide 79


Advanced functions of Alternative setpoints

= Double-click at the relevant value of Alternative


To copy the value from Alternative setpoints
setpoints.
= Select the value which you want to change and click at
Import selected alternative value icon.

To copy all values from Alternative setpoints = Click at Import all alternative values icon.

= Click at Show/Hide alternative setpoint names


To show Alternative setpoints names
icon.

To close Alternative setpoints = Click at Show/Hide alternative setpoints icon.

6.5.2 Values
The Values window allows you to view current measured and computed values. The values are separated into
groups according to their meaning.

To open the Values window


1. Initiate online or offline connection with the supported controller.
2. For opening the Values window you can either:

a. Select the Control bookmark and in the category of Monitoring click at Values icon to open the
Values window.
b. Select the bookmark Control or Tools and in the Right Dock Panel (page 32) click at the bookmark
Values to open the Values window.

InteliConfig 2.17.0 Global Guide 80


Image 6.40 Values window

InteliConfig 2.17.0 Global Guide 81


Values window description

Image 6.41 Values window description

A. Values group panel – contains all visible groups for the current type of controller.
B. Values panel – contains all visible values within the selected group. This panel can contain following parts
of values:
Value Name.
Value, including the unit if available.
C. Info panel – contains basic information about the selected value. It shows:
Value range, if available.
Value unit, if available.
Short description of the value.
Controller help button for opening full context help for the selected value.
D. Tool bar – it contains following functions:
Search

Search panel.

Go to previous occurrence.

Go to next occurrence.

Cancel search.

InteliConfig 2.17.0 Global Guide 82


Hide panel

Hide panel – this option will hide the whole Tool bar. In case of hidden Tool bar only the icon of
is shown in the right bottom corner of the Setpoints window. After click at this icon the Tool bar will
appear again.

Note: The Values window is possible to pin to the Right Dock Panel (page 32) by using of Pin icon.

Additional functions of the Values window


Values window of InteliConfig offers different highlighting of groups or values to help the user to find all needed
information.

Image 6.42 Functions of Values window

# Meaning
1a Value which is out of warning limit.
1b Indication of the group which contains any value which is out of warning limit.
Indication of the group which contains any value which is out of shutdown limit. Value which is out of
2
shutdown limit is colored with red background.
3a Searched word via the Search panel in the Tool bar.
3b Indication of the group which contains any searched words.
4 Chosen value. Basic info about the chosen value available in the Information panel on the right.
Rolled down field of Binary Inputs / Outputs which contains detailed info about the status of
5
configured inputs / outputs.

Table 6.2 Functions of Values window

InteliConfig 2.17.0 Global Guide 83


6.5.3 History
The History window displays the history log held within the controller. The history log is displayed as a table,
where each row contains one record (event) and the columns contain data values recorded in the moment that
the event occurred.
Columns of history are partially customizable. It is possible to add or delete some of columns associated with
ECU , External or Plug-in modules. This can be done by ticking the 'Add to history' option when configuring
ECU , External or Plug-in modules in Configuration window.

To open the History window


1. Initiate online or offline connection with the supported controller.
2. For opening the History window you can either:

a. Select the Control bookmark and in the category of Monitoring click at History icon to open the
History window.
b. Select the bookmark Control or Tools and in the Right Dock Panel (page 32) click at the bookmark
History to open the History window.

Image 6.43 History window

InteliConfig 2.17.0 Global Guide 84


History window description

Image 6.44 History window description

A. Fixed history columns – basic columns of the history log which are fixed
B. History columns – logged values which belong to specific events. All values are arranged to columns
helping easy orientation in it.
C. Tool bar – bar with handy tool while configuring Setpoints. It contains following functions:
Search

Search panel.

Go to previous occurrence.

Go to next occurrence.

Cancel search.
History

Move to first column.

Move to last column.

Edit columns – this option opens the window with additional functions of history columns.

Export the history to MS Excel (.XLS) file.


Hide panel

Hide panel – this option will hide the whole Tool bar. In case of hidden Tool bar only the icon of
is shown in the right bottom corner of the Setpoints window. After click at this icon the Tool bar will
appear again.

InteliConfig 2.17.0 Global Guide 85


Note: The separate Setpoints window is possible to pin to the Right Dock Panel (page 32) by using of Pin
icon.

Additional functions of the History window

Image 6.45 Functions of History window

# Meaning
1 Searched word via the Search panel in the Tool bar.

Selected column. When any column is selected buttons of Move to first column and Move
2
to last column are activated.

3 History column edit window opened by Edit columns button.


3a Selecting of columns which will be fixed.
3b Selecting of columns which will be visible.

Control buttons for changing of the selected column position: Move to the top, Move up,
3c
Move down and Move to the bottom.

Table 6.3 Functions of History window

6.5.4 PLC Monitor


PLC Monitor displays PLC Monitor window. How configure PLC see PLC on page 56.

InteliConfig 2.17.0 Global Guide 86


6.6 Language
To configure language is possible directly from Ribbon bar. Click on Language button and select required
language.
Other way of changing Language is from Home bookmark
1. Go to Home bookmark

2. Click on Settings button → InteliConfig – Settings window appears


3. Select Language panel
4. Choose both InteliConfig Language and Control Language

Image 6.46 Language Settings

6.7 Firmware upgrade


InteliConfig can be used for upgrading firmware in controller and Plug-in modules.
There are several ways to upgrade a firmware.
Firmware update is accessible via Firmware upgrade icon in Tools:

InteliConfig 2.17.0 Global Guide 87


6.7.1 Default configuration
This option upload selected firmware into the controller with default configuration.
Note: User configuration is replaced with default configuration.

1. Open the online connection with the controller.


Note: Not every type of online connection needs to be supported for firmware upgrade, e.g. AirGate via GPRS
module...

1. Go to Control bookmark and in the category of Access set the administrator password (Password level 3).

2. Go to Tools bookmark and in the category of Firmware click at Firmware upgrade icon and select
Default configuration.
3. The Controller firmware upgrade – default configuration window will appear with the list of supported
firmwares available in your PC.
4. Pick desired firmware and click at Upgrade.
Note: You will be asked to save the original configuration. It is recommended to do that.

Note: Default configuration is uploaded to the controller during Firmware upgrade.

IMPORTANT: In case there is no required firmware available in the list it is necessary to import this
to your computer. Download the relevant .PSI file (on our website -> Products -> your controller ->
Software -> Product Upgrade .PSI) and after successful download execute it with double click. The
import procedure will begin. After the successful firmware import try the Firmware upgrade
procedure once again.

6.7.2 Current configuration


This option is used to update controller with configuration to newer version. Controller configuration is not
replaced by default but is imported into new archive. After upgrading process the controller has new version of
firmware and archive with user settings from old archive.
1. Open the online connection with the controller.
Note: Not every type of online connection needs to be supported for firmware upgrade, e.g. AirGate via GPRS
module...

5. Go to Control bookmark and in the category of Access set the administrator password (Password level 3).

6. Go to Tools bookmark and in the category of Firmware click at Firmware upgrade icon and select
Current configuration.
7. The Controller firmware upgrade – existing configuration window will appear with the list of supported
firmwares available in your PC.
8. Pick the desired firmware and click at Upgrade.
9. If source version is different from target version, you can see report from upgrade configuration process. If
everything is OK, press Next button to write new firmware and configuration into controller.
Note: You will be asked to save the original configuration. It is recommended to do that.

Note: Updated configuration is uploaded to the controller during Firmware upgrade.

InteliConfig 2.17.0 Global Guide 88


Note: It is possible to upgrade configuration to newer version only. This utility unable to downgrade
configuration to older version.

IMPORTANT: In case there is no required firmware available in the list it is necessary to import this
to your computer. Download the relevant .PSI file and execute it with double click. The import
procedure will begin. After the successful firmware import try the Firmware upgrade procedure
once again.

6.7.3 Module FW
This option allow user upgrade firmware in Plug-in modules.
1. Open the online connection with the controller.
2. Go to Control bookmark and in the category of Access set the administrator password (Password level 3).

3. Go to Tools bookmark and in the category of Firmware click at Firmware upgrade icon and select
Module FW.
4. The Plug-in modules firmware update window will appear with the list of supported firmwares available in
your PC. On the bottom there is a list of installed modules and current firmware displayed.
5. Pick the wanted firmware and click at OK.

6.7.4 Bulk / offlline update


This option allow user to upgrade archives offline. Source is list of archives selected by user, target is set
archives in new version with user configuration.There is no need to have any configuration opened or connected
to any controller.

1. Go to Tools bookmark and in the category of Firmware click at Firmware upgrade icon and select Bulk /
offline update.
10. The Configuration upgrade – stored configurations window will appear.
11. Add archive from disk to be upgraded.It is possible to add more archives.
12. For each selected archive there is a target automatically assigned to the newest compatible default archive.
You can change this target archive for each user separatelly.
13. Select output folder.
14. Click OK to proceed upgrade.
15. Final report is displayed after finish. If there is any problem, you can see it in report.
Note: Upgraded archives are automatically saved into selected folder. The name of archives consists from
name of source archive + "_m.n.p.b" where m.n.p.b is version of target (final) archive.

Configuration upgrade between different controllers


In some cases is possible to upgrade configuration for future use in another controller. This type of upgrade is
possible only from specific version of configuration. In case of needing the newer version of the target archive, it
is necessary to do upgrade twice. The first upgrade is from specific version and the second upgrade could be
from previous output to any higher available version.

InteliConfig 2.17.0 Global Guide 89


Specific upgrades description
Source controller Configuration version (source) Target controller
InteliLite MRS16 1.13.0.5 InteliLite4 MRS16
InteliLite AMF20 1.13.0.5 InteliLite4 AMF20
InteliLite AMF25 1.13.0.5 InteliLite4 AMF25
InteliLite 9 AMF 1.4.0.4 InteliLite4 AMF8

6.8 Security
Security bookmark allows to Change password (ver. 1) (page 90)Change access code (page 91)
Note: For the information how to activate password see Enter password on page 73 or how to deactivate
password see Deactivate password on page 73.

Note: List of security functions depends on Controller type and Firmware version.

6.8.1 Change password (ver. 1)


InteliConfig allows to Change password, to set up user passwords and to assign Passwords level.
The Password set is saved in the controller. Can be changed or set from the front panel or InteliConfig. It is not
changed with upload of configuration.
For configuration in InteliConfig go to Tools bookmark and in section Security click on Change password icon
. A window Change password appears.

IMPORTANT: Box with email address in change Password window is visible only if controller
support Password reset function. We strongly recommend to set up email address for
administrator account if your controller supports Password reset. This email address is necessary
for Password reset function.

Image 6.47 Change password window

InteliConfig 2.17.0 Global Guide 90


1. Fill in Administrator Password.
a. Default value of Admin. Password is 0 (zero).
b. Password consists of 4 numbers 0-9999
2. Select the level to be changed
3. Insert required new Password
4. Repeat required new Password again
Note: The Admin Password is required for change any Password of the Password set.

6.8.2 Change access code


Access code is required for remote access to the Controller.
For configuration in InteliConfig go to Tools bookmark and in section Security click on Change access code
icon . A window Change access code appears.

Note: Default Access code is 0 (zero)

Image 6.48 Change access codewindow

6.8.3 User management (ver. 2)


User management ver. 2 is new type of user management used in new controllers. User verification is not
based on 4digit password only but each user has defined Username and Password. When logging-in, user must
fill both fields.
In some situations, like login on displays, it is not comfortable type long strings for username and password. for
this, each user account can have defined also UID and PIN. Both is 4digit number. This type of login is more
comfortable for user but due to worse security, list of actions available with this login type is limited. For
example, it is not possible change password or manage users (add, delete) etc. For details, see Controller
manual.
InteliConfig allows to manage users.
Each user must/can have defined:
Username (mandatory). Consists of 6-15 characters (a..z, A..Z, 0..9).
Password (mandatory). Consists of 6-15 characters (a..z, A..Z, 0..9), at least one must be alphabetical and
at least one must be number.
UID (optional). Consist of 4 numbers (0..9).
PIN (optional). Consist of 4 numbers (0..9).
Access level (0..3). Level 3 has Administrator rights.
Maximal number of users depends on controller type.
For configuration in InteliConfig go to Tools bookmark and in section Security click on User Administration
(icon ) - User management. A window user management appears.

InteliConfig 2.17.0 Global Guide 91


Image 6.49 User management window

1. Click on to add new user.


a. Fill Username (mandatory, must be unique in the controller)
b. Fill Password (mandatory)
c. Fill UID (optional, must be unique in the controller)
d. Fill PIN (mandatory if UID is used)
e. Select required Access level

2. Click on to delete selected user


a. At least one user with administrator rights must exists in the controller.
b. Actually logged-in user cannot be deleted.

3. Click on to edit selected user


a. It is possible change password or PIN (if used) and Access level.
b. It is not possible edit actually logged-in user.

6.8.4 Change password (ver. 2)


InteliConfig allows to Change password, to change password for actually logged user.
The Password set is saved in the controller. Can be changed or set from the front panel or InteliConfig. It is not
changed with upload of configuration.
For configuration in InteliConfig go to Tools bookmark and in section Security click on User Administration
(icon ) – Change password. A window Change password appears.

InteliConfig 2.17.0 Global Guide 92


IMPORTANT: Box with email address in change Password window is visible only if controller
support Password reset function. We strongly recommend to set up email address for
administrator account if your controller supports Password reset. This email address is necessary
for Password reset function.

Image 6.50 Change password window

1. Fill in Password for actual user.


a. Default value of Administrator. Password is serial number of controller.
b. Password consists of 6-15 characters (a..z, A..Z, 0..9), at least one must be alphabetical and at least
one must be number
2. Insert required new Password
3. Repeat required new Password again

6.8.5 Change PIN (ver. 2)


InteliConfig allows to Change PIN for actually logged user.
The PIN is saved in the controller. Can be changed or set from the front panel or InteliConfig. It is not changed
with upload of configuration.
To change PIN, user must be logged in using Username/Password.
For configuration in InteliConfig go to Tools bookmark and in section Security click on User Administration
(icon ) – Change PIN. A window Change PIN appears.

InteliConfig 2.17.0 Global Guide 93


Image 6.51 Change password window

1. Fill in Password for actual user.


a. PIN consists of 4 numbers (0..9).
2. Insert required new PIN
3. Repeat required new PIN again

6.8.6 Password reset


Password reset is function for reset administrator Password. Necessary prerequisite is to set recovery email in
change Password window. If the email address has not been set before the Password was lost, it will not be
possible to use this function.

For using this function go to Tools bookmark and in section Security click on Password reset icon .

InteliConfig 2.17.0 Global Guide 94


Table 6.4 Password reset window

Note: How to set up recovery email see Change password (ver. 1) on page 90.

6 back to Configuration

InteliConfig 2.17.0 Global Guide 95


6.9 ScreenEditor
6.9.1 ScreenEditor page layout 96
6.9.2 Screens structure panel 97
6.9.3 Screen content panel 98
6.9.4 Instrument / Screen properties panel 99
6.9.5 Toolbar 100
6.9.6 Virtual screen 101
6.9.7 Instrument palette panel 102
6.9.8 ICD (Integrated color display) and InteliVision 5.2 screen types and structures 104
6.9.9 Working with the editor 105
6.9.10 ICD and IV5.2 Instruments 107
6.9.11 Consistency check of Screens definiton 144
6 back to Configuration
The ScreenEditor is an integrated tool which allows the user to modify the layout of the screens in the internal
and external displays.
The default layout of the screens is given in the default archive of the respective firmware and InteliConfig
modifies it automatically when extension modules are added into/removed from the configuration. However,
some users may want to rearrange the information on the screens in a different way to fit better their needs. The
ScreenEditor allows adding of new screens, modifying of present screens as well as removing unneeded
screens. Also exporting screens to XML files and reimporting them back (e.g. into another archive) is possible.

6.9.1 ScreenEditor page layout

InteliConfig 2.17.0 Global Guide 96


Panels
1. Screens structure panel.
2. Screen content panel.
3. Instrument or screen properties
4. Toolbar
5. Virtual screen
6. Instrument palette

6.9.2 Screens structure panel


This panel shows all the screens contained in the configuration. Each tab contains the screens for the
respective display type.
The tabs (1) contain screens for display types which are supported by configuration. Select the appropriate
tab to see and edit the screens for the respective display type.
The tree shows the screens organized into groups according to their types. There is a tree node for metering
screens (2), status screens (3).
The grey or blue background (4) indicates that these screens are currently displayed in the virtual screen.
The green "arrow" icon indicates that this screen is actually selected for editing and its content (instruments)
is listed in the panel Screen content.

Click to a screen to select it.


Drag the screen up or down within the list to change the screen order.
Right-click on a screen in the structure to show the screen context menu.
The screen context menu can be activated by right-click on a screen in the structure panel. The menu allows
the user to add/remove screens of the particular type, clipboard operations with the screens and
import/export of a screen(s) from/to an XML file.
The screen structure context menu can be activated by right-click in the area of the structure panel outside
the screens tree. The menu allows the user to add screens of all types and paste screen from the clipboard.

InteliConfig 2.17.0 Global Guide 97


6.9.3 Screen content panel
This panel displays the content (instruments) of the currently selected screen. If there are some instruments
selected in the screen, they are highlighted.
The order, in which the instruments are listed in the screen content panel, defines the z-order of the instruments,
i.e. the order in which the instruments are drawn on the screen. The most upper instrument is drawn on the
bottom. If some instruments overlap each other, then the upper one in the list will be overridden by the one
below.

Click to the instrument to select it. Hold "CTRL" key while clicking to select more than one instrument.
Drag the instrument up or down within the list to change the z-order.
Press DEL key to delete the selected instrument(s).
Right-click on a screen in the structure to show the context menu.
The context menu contains operations with selected instruments and the clipboard.

InteliConfig 2.17.0 Global Guide 98


6.9.4 Instrument / Screen properties panel
This panel is intended for adjusting the properties of selected instrument. The properties (2) are associated into
groups (1) according to their meaning. The properties are not identical in the scope of all instruments.

Position properties are updated automatically while the instrument is being moved in the virtual screen. It is
also possible to modify them manually.
All other properties are to be modified manually if the original value does not fit.
If multiple instruments are selected it is possible to modify all properties that are common for all selected
instruments. If a text <multi select> is displayed in a property, it means the value is different for the selected
instruments.

InteliConfig 2.17.0 Global Guide 99


6.9.5 Toolbar

Shows and hides the grid. Click to the arrow on the right of the icon to select the grid density.
Options available: (None - Low - Medium - High).

Activates and deactivates the function "snap to grid". If this function is active the objects (their
reference points) can be placed only onto the grid points when they are being dragged or moved by
arrow keys. The snap to grid function is overridden if CTRL + arrow keys are used to move the object
as well as if the position properties are edited directly.

Cuts the active selection into the clipboard.

Copies the active selection into the clipboard.

Pastes the content of the clipboard into the screens. If the clipboard contains a whole screen(s) the
screens are inserted to the existing screens before the active screen. If the clipboard contains
instrument(s) it is appended to the active screen.

Performs undo operation of the last user action.

Cancels the last undo operation and returns back to the original state before undo was performed.

Zooms in or out of the virtual screen.


Options available: 75 %, 100 % and 200 %
Activates and deactivates the alignment lines. The alignment lines are displayed while an instrument
is being moved and its position is actually aligned with some other instrument. It helps to create
screen layout with aligned instruments.

Shows and hides instrument borders. This function helps to prevent overlapping of instruments,
which might not be clearly visible if the instruments have the same color as the background.

Validates a consistency of screen definitions. When the consistency check finds any problem then
the application shows window with list of inconsistencies.

InteliConfig 2.17.0 Global Guide 100


6.9.6 Virtual screen
The virtual screen represents the selected real InteliVision display for the purpose of editing screen content in
the metering mode.
Note: Archives contain separate screens descriptions (screens descriptions are depended on type of
controller). Select the appropriate tab to see and edit the screens for the respective display type.

The display consists of following areas:

1. Metering screen (editable)


2. Status bar (editable)
3. Disabled area (non-editable)
Selected instrument(s) are marked with gray dashed box with hooks in the corners (4) and are also highlighted in
the panel Screen content.

Note: Some instruments are not re-sizable!

InteliConfig 2.17.0 Global Guide 101


6.9.7 Instrument palette panel
This panel contains the list of all available instruments that can be used on the screens. The instruments are
grouped according to their common function such as meters, bargraphs, active elements, etc.

1. Pull-down menu with fast access to instrument groups.


2. Deactivate selected instrument in the instrument palette and activate cursor for selecting instruments in the
virtual screen.
3. Instrument search field.
4. Instrument groups.
5. Instruments. Click to select desired instrument and then click to the virtual screen to place it there.

InteliConfig 2.17.0 Global Guide 102


Note: Some of the instruments may not be supported in a particular archive. The set of supported instruments
for each InteliVision type depend on version of screens definition used in this archive.

Note: Some of the instruments are intended for use in specific screen types only. E.g. ButtonCMD are to be
used only in Status bar screens as their function is linked to the position on the screen and to the hardware
buttons. On the other hand pointer meters are intended for using only on the metering screens as they are too
big to fit anywhere else.

InteliConfig 2.17.0 Global Guide 103


6.9.8 ICD (Integrated color display) and InteliVision 5.2 screen
types and structures
ICD (Integrated color display) and InteliVision 5.2 contain one or more metering screen(s) and one or more
bottom status bar(s) screen. Each metering screen is connected with one status bar bottom. See the image in
the chapter Virtual screen.

Metering screens are editable, can be also added and removed. always at least one screen must remain in
the configuration. These screens contain measured and/or computed values, texts, simple drawings etc.
Status bar bottom screens are editable and can be added and removed. Status bar bottom screens are
linked to metering screens (i.e. together create pairs) and are displayed together. The pairs need not to be
1:1, it is possible to link one Status bar bottom screen to multiple metering screens (or even to all).

InteliConfig 2.17.0 Global Guide 104


6.9.9 Working with the editor
Add and remove screens
Right click to a screen in the screens structure panel to activate the screen context menu. Then select desired
operation.

Add screen will insert a blank screen before the currently selected one.
Delete screen will remove the currently selected screen.
Cut screen will remove the currently selected screen and place it into the clipboard.
Copy screen will copy the currently selected screen into the clipboard.
Paste screen will insert the screen stored in the clipboard (if there i s any) before the currently selected one.
Import screen function will import the screen from an XML file and replaces the currently selected screen.
Export screen function will export the currently selected screen into an XML file.

Editing screens
First select the screen, which you want to edit. To do so, click on the desired screen in the screens structure
panel. The content of the screen will appear in the screen content panel. Then you can edit the screen.

InteliConfig 2.17.0 Global Guide 105


Click to an instrument in the virtual screen or in the screen content panel to select/deselect
it. By clicking to another instrument while holding CTRL key you can add/remove further
Select
instruments to/from the current selection. If you want to select items that are adjacent, you
can use the SHIFT key.
Drag the selected instrument(s) in the virtual screen to move it. Use arrow keys to move
the objects from keyboard or use CTRL + arrow keys for fine position adjustment
(overrides the snap to grid function). It is also possible to edit directly the position properties.
Move SHIFT + arrow keys can resize instruments.
Note: If the alignment lines are displayed you will see magenta lines whenever the
moving instrument is horizontally or vertically aligned with any other instrument.
If you want to add an instrument to the screen, then select the desired instrument in the
instrument palette panel and then click to the desired position on the screen to place the
Add instrument there. Click to the button 3 in the instrument palette panel to deselect the
instrument and return the cursor to edit mode.
Note: Some instruments may not be supported in the respective display type/version.
Properties of the selected instrument can be modified in the instrument properties panel. If
the selection contains multiple instruments the instrument properties panel contains only
Properties properties that are present in all of the selected instruments.
Example: This is useful e.g. if you want to adjust the same text color for all texts in the
particular screen.
The order in which the instruments are drawn on the screen is given by the order in which
Drawing the instruments are listed in the screen structure panel. The instruments are drawn from the
order most upper one to the lowest one. The order can be changed by dragging the instruments in
the screen structure panel.

InteliConfig 2.17.0 Global Guide 106


6.9.10 ICD and IV5.2 Instruments
Group of instruments Instrument
Line (page 125)
Graphic elements
Rectangle (page 133)
Internal Picture (page 124)
Pictures
Aftertreatment (page 108)
Text Screen (page 142)
Text Fixed (page 140)
Static texts Text Dim (page 139)
Text Label (page 141)
Text Bit Name (page 138)
Char (page 122)
String (page 135)
Dynamic texts
MultiLabel (page 131)
AlterMultiLabel (page 110)
MultiBar V (page 129)
Bargraphs
MultiBar H (page 127)
Analog Meter 1 (page 111)
Meters Analog Meter 3 (page 113)
Synchroscope (page 136)
BinRow (page 116)
Binary indicators BinList (page 115)
Bit (page 117)
Numeric (page 132)
Numeric analog indicators Date (page 123)
Time (page 143)
ButtonCMD (page 118)
Active elements
ButtonLink (page 120)

InteliConfig 2.17.0 Global Guide 107


Aftertreatment

This instrument supports aftertreatment. In Automatic mode user can simply choose one of predefined
functionalities. Pictograms and blinking are set automatically.

Properties
Default Value
Category Name Note
value range
"Mode = Custom" -> all properties under Source
Custom / value & Pictograms are enabled "Mode =
General Mode Automatic
Automatic Automatic" -> all properties under Source value
& Pictograms are disabled
This property is enabled only if "Mode =
Automatic" in the automatic mode combobox
shows list of all Aftertreatment functions (from
XML definiton). Once the functionality is
selected, all the properties under Source value &
First item None, ... Pictograms are pre-selected based on the XML
Functionality
(Amber lamp) N definition. If "Mode = Custom" and Source value
& Pictograms settings fit to any of defined
functionality, the functionality name is displayed
(in the disabled field). If settings doesn't fit to any
of the functionalities (user has chaned any value),
"Functionality = None" is set.
X 0 0-799
Position
Y 0 0-399
Picture state is defined by this bit State bit = 1:
Picture active, blinking depends on Period bit 0
State bit DPF°status 1
and Period bit 1 State bit = 0: Picture inactive, no
blinking
Picture blinking period is defined by these 2
bits State bit = 1:
Source Period bit 0 DPF°status 2
Period bit 0 Period bit 1 Blinking
value
0 0 no blinking
0 1 fast blinking
1 0 slow blinking
Period bit 1 DPF°status 3 1 1 reserve

(State bit = 0: no blinking)

InteliConfig 2.17.0 Global Guide 108


Display Bg color Default
attributes Border ON ON/OFF
Pictogram Exclamation None, ...
Active mark Yellow N
Pictograms
Pictogram Exclamation None, ...
Inactive mark Inactive N
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 109


AlterMultiLabel

This instrument displays one of a set of text strings according to the index contained in the assigned value. The
value must be "stringlist" type. The selection window in the Com object property automatically filters the objects
so that only "stringlist" type objects are displayed.

Properties
Value
Category Name Default value Note
range
X 0 0-799
Position Y 0 0-399
Width 100 30-799
If the communication object doesn't exist the value
of None (0) is used. Required field (None is not
Value ControllerMode
allowed - red background in Instrument properties
Source
panel).
value
If the communication object doesn't exist the
Setpoint ControllerMode setpoint of None (0) is used. The list is limited to
setpoints only. Optional field (None is allowed).
Display Bg color Default
attributes Border ON ON/OFF
(Default),
Text Font
(Default) Small, FontSize Small = 24px; Large = 36px.
attributes size
Large
Label
Default
color
Value
Default
color
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 110


Analog Meter 1

Represents circular (270°) meter with needle for displaying the value of the given communication object. User
can defined 4 different warning limits.
It has ability to display variety of visual decoration like scale limit, scale bar, warning limits, needle, border, etc.
The meter has two size - small and large.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position
Y 0 0-399
Source Com Selection limited to values only (Setpoint option is
None
value object disabled).

InteliConfig 2.17.0 Global Guide 111


Size Small Small/Large
Bg color Default
Border ON ON/OFF
Label ON ON/OFF
Value ON ON/OFF
Units ON ON/OFF
Limits ON ON/OFF
Expand
ON ON/OFF
scale
Scale
ON ON/OFF
bar
Display
attributes Editable combobox
shows list of all names from table of 'screen texts'
allows user to type & use a new text
Label
Default Default item is the first in the list. Meter displays
text
selected com object name as default.
user texts are available in <screentexts> section of
screen definition xml
Low scale limit it represented by com. obj. number or
Scale
Default constant value. Its meaning is given by connected range
0%
attributes which are set in Scale limit dialog
Scale If Low limit is >= High limit, then default limit values from
Default
100% the configuration are used.
Text
Color Default
attributes
Com. obj., which determines Hi limit (100%) for relative
Limits %
Default warning limits. Default - defined hi limit of Source Value /
base
Com object is taken as default.
Warning limit is represented by com. obj. number or
Warning
None constant value. Its meaning is given by connected range
limit 1
Warning attributes which are set in Warning limit dialog
limits Warning
None See 'Warning limit 1' above
limit 2
Warning
None See 'Warning limit 1' above
limit 3
Warning
None See 'Warning limit 1' above
limit 4
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 112


Analog Meter 3

Represents circular (90°) instrument (meter) for displaying the value of the given communication object. User
can defined 4 different warning limits.
It has ability to display variety of visual decoration like scale limit, scale bar, warning limits, needle, border, etc.
The meter has two size - small and large.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position
Y 0 0-399
Source Com Selection limited to values only (Setpoint option is
None
value object disabled).

InteliConfig 2.17.0 Global Guide 113


Size Small Small/Large
Bg color Default
Border ON ON/OFF
Label ON ON/OFF
Value ON ON/OFF
Units ON ON/OFF
Limits ON ON/OFF
Expand
ON ON/OFF
scale
Scale
ON ON/OFF
bar
Display
attributes Editable combobox
shows list of all names from table of 'screen texts'
allows user to type & use a new text
Label
Default Default item is the first in the list. Meter displays
text
selected com object name as default.
user texts are available in <screentexts> section of
screen definition xml
Low scale limit it represented by com. obj. number or
Scale
Default constant value. Its meaning is given by connected range
0%
attributes which are set in Scale limit dialog
Scale If Low limit is >= High limit, then default limit values from
Default
100% the configuration are used.
Text
Color Default
attributes
Com. obj., which determines Hi limit (100%) for relative
Limits %
Default warning limits. Default - defined hi limit of Source Value /
base
Com object is taken as default.
Warning limit is represented by com. obj. number or
Warning
None constant value. Its meaning is given by connected range
limit 1
Warning attributes which are set in Warning limit dialog
limits Warning
None See 'Warning limit 1' above
limit 2
Warning
None See 'Warning limit 1' above
limit 3
Warning
None See 'Warning limit 1' above
limit 4
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 114


BinList

This instrument displays group of consequent bits with their names below each other.

Properties
Value
Category Name Default value Note
range
X 0 0-799
Position Y 0 0-399
Width 54 30-799
BIN
Com
Source value (com object: 8235 and mask: .
object
255/0xFF)
Bg color Default
Display Border ON ON/OFF
attributes Label ON ON/OFF
Bit order ON ON/OFF
(Default),
Font FontSize Small = 24px; Large =
(Default) Small,
size 36px.
Large
Text
Label
attributes Default
color
Value
Default
Color
This instrument supports mask
Visibility
dynamic visibility

InteliConfig 2.17.0 Global Guide 115


BinRow

This instrument displays a group of consequent bits as a string of "0" and "1" characters. First bit is on the left.
Binary value name (label) can be displayed as well as hidden.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 127 30-799
Source value Com object None .
Bg color Default
Display
Border ON ON/OFF
attributes
Label ON ON/OFF
(Default),
Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Text attributes
Label color Default
Value
Default
Color
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 116


Bit

This instrument displays bit name and its value.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 127 30-799
Source value Com object None .
Bg color Default
Display
Border ON ON/OFF
attributes
Label ON ON/OFF
(Default),
Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Text attributes
Label color Default
Value
Default
Color
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 117


ButtonCMD

Special meter – button for capturing press hardware button and convert it to the sending argument and
command to the controller. Meter can color its face regarding to RED and GREEN bit. Meter can also show pre-
selected internal picture regarding to RED and GREEN bit. Meter can also show text, there is special text for
ON and OFF button state regarding to on/off text bit value.
Typically used commands:
1 = EngineCommand
2 = BreakersCommand
Typically used arguments ID:
0x01FE … StartEngine (EngineCommand 1)
0x02FD … StopEngine (EngineCommand 1)
0x04FB … HotrnReset (EngineCommand 1)
0x08F7 … FaultReset (EngineCommand 1)
0x11EE … GCB ON/OFF (BreakersCommand 2)
0x12ED … MCB ON/OFF (BreakersCommand 2)
There is also option to display the pictogram based on the bit combination

Properties
Default Value
Category Name Note
value range
0 - HW button F1
1 - HW button F2
(Inserted
Position Key index 0-4 2 - HW button F3
position)
3 - HW button F4
4 - HW button F5
Display
Bg color Default
attributes
(Default),
Text Font size (Default) Small, FontSize Small = 24px; Large = 36px.
attributes Large
Color Default
Red None .
Source Green None
value Text If Text switch = 1, Active text is displayed.
None
switch If Text switch = 0, Inactive text is displayed.

InteliConfig 2.17.0 Global Guide 118


Red ON OFF / ON
Show colors Green ON OFF / ON User sets enabled colors
Yellow ON OFF / ON
Combobox shows list of available commands.

If other then "Custom" command is selected, the


properties "Cmd number", "Cmd argument", "Source
value", "Show colors" and "Texts" are pre-configured
Custom, with real values. Properties "Cmd number" and "Cmd
Command Custom
... N argument" are disabled.

Commands If "Custom" is selected, the properties "Cmd number"


and "Cmd argument" are enabled and user can change
it. There is no automatic command recognition (if user
settings fits any existing command).
Cmd
0 0-255
number This property is enabled only if "Command =
Cmd Custom"
0 0-65535
argument
Pictogram None, ... None variant is included (on the top of the list).
None
00 N
Pictogram None, ... Pictogram GREEN RED
None
01 N Pictogram 00 0 0
Pictograms
Pictogram None, ... Pictogram 01 0 1
None
10 N Pictogram 10 1 0
Pictogram None, ... Pictogram 11 1 1
None
11 N
Editable combobox
shows list of all names from table of 'screen
<No text
Inactive texts'
specified>
allows user to type & use a new text

Texts <No text specified> item is the first in the list. It


means no text is displayed on the button.
user texts are available in <screentexts>
<No text
Active section of screen definition xml
specified>
If Active or Inactive text is displayed depends on
Source value / Text switch.
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 119


ButtonLink

Special meter – button for capturing touch press hardware button and convert it to the changing the displaying
mode. It is also possible to specify preferred screen of selected target screen.

Properties
Default
Category Name Value range Note
value
0 - HW button F1
1 - HW button F2
(Inserted
Position Key index 0-4 2 - HW button F3
position)
3 - HW button F4
4 - HW button F5
Display
Bg color Default
attributes
FontSize Small = 24px; Large =
Text Font size (Default) (Default), Small, Large
36px.
attributes
Color Default
Metering
Trends
Selected value affects if other
Setpoints comboboxes (Metering screen,
Target screen Metering
AlarmList Setpoint group and Administration
History tab) are enabled or disabled.

Administration
This property is enabled only if
Metering <1st "Target screen= Metering"
screen screen> Combobox shows list of all metering
screen names
This property is enabled only if
Link target <1st
"Target screen= Setpoints"
Setpoint group setpoints
Combobox shows list of all
group>
setpoints group names
Users &
Passwords
Communication
This property is enabled only if
Users & Languages "Target screen= Administration"
Administration
Passwords InteliVision Info Combobox shows list of all
Controller info administration tab names

InteliVision
Settings

InteliConfig 2.17.0 Global Guide 120


Export & Import
Service Screen
Combobox with internal icon list.
Pictograms Pictogram None 0-255 None variant is included (on the top
of the list).
Editable combobox
shows list of all names from
table of 'screen texts'
allows user to type & use a
new text
<No text <No text specified> item is
Texts Text
specified> the first in the list. It means
no text is displayed on the
button.
user texts are available in
<screentexts> section of
screen definition xml
This instrument supports mask
Visibility
dynamic visibility

InteliConfig 2.17.0 Global Guide 121


Char
This instrument displays one character according to the ASCII code contained in the assigned "char-type"
value. This instrument is typically used for displaying the AC load character (i.e. "R", "L", "C") next to the power
factor value.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 54 30-799
Source value Com object None List is limited to character values only.
Display Bg color Default
attributes Border ON ON/OFF
(Default),
Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Text attributes Left /
Alignment Center Right /
Center
Color Default
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 122


Date

This instrument displays a date-type object, e.g. current date from the controller RTC clock. The format is given
by the language, which is currently selected in the display.
Respects US/EU format based on the actually selected language in entire GUI:
EU Date : DD/MM/YYYY (fullyear)
EU Date : DD/MM/YY
US Date : MM/DD/YYYY (fullyear)
US Date : MM/DD/YY

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 150 50-799
By default, the Date (24553) is pre-configured. If the
Source Com communication object doesn't exist the default value of
Date
value object None (0) is pre-configured. Only communication objects
of td_fdate are allowed for configuration.
Bg color Default
Display
Border ON ON/OFF
attributes
Full year ON ON/OFF
(Default),
Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Text
Left /
attributes
Alignment Left Right /
Center
Color Default
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 123


Internal Picture

This instrument displays a static image. Internal picture is placed to the position [X, Y] (left top corner
coordinates) and is drawn from top-left to the bottom-right direction.
Supports 3 sizes (24 × 24 px; 40 × 40 px; 64 × 64 px)

Properties
Value
Category Name Default value Note
range
X 0 0-799
Position
Y 0 0-399
Source Bit 0 None
value Bit 1 None
Bg color Default
Border ON ON/OFF
Display Icon sizes:
attributes Small/Large/Very 0 = small (24 x 24)
Size
large 1 = large (40 x 40)
2 = very large (64 x 64)
Combo box with internal icon list. None variant
is included (1st item) Picture set: internal
Pictogram None, ...
None (External = 0) N ... number of internal pictures
00 N
Pictogram 00 is displayed if Bit 0 = 0 and Bit 1
= 0.
Pictograms Pictogram None, ... Pictogram 01 is displayed if Bit 0 = 1, Bit 1 = 0
None
01 N for details see Pictogram 00 Note
Pictogram None, ... Pictogram 10 is displayed if Bit 0 = 0, Bit 1 = 1
None
10 N for details see Pictogram 00 Note
Pictogram None, ... Pictogram 11 is displayed if Bit 0 = 1 and Bit 1
None
11 N = 1 for details see Pictogram 00 Note
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 124


Line

Draws a line from point [X1,Y1] to point [X2,Y2]. Line width, color are adjustable.

Properties
Value
Category Name Default value Note
range
X1 0 0-799
Y1 0 0-399
Position Minimal line length is 0 px.
X2 75 0-799
Y2 75 0-399
Line attributes Color Default Attribute Style is not supported, line is always solid.
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 125


MaskDynamicVisibility
Non-visual instrument allowing you to show/hide target instrument. Based on the 32bit mask mechanism.

Properties
Default Value
Category Name Note
value range
None /
Mask
Visibility None Dynamic
mechanism
mask
Hide /
Mask type Hide This property is hidden if 'Mask mechanism = None'
Show
This property is hidden if 'Mask mechanism = None'

Com object None


If Mask mode is set on 'One or more' then ComObjBit
dialog must allow to select bits.
This property is hidden if 'Mask mechanism = None'.
Mask mode "One or more" means that at least one of the
bits selected in Comm obj has to be true (value 1) to
One or One or
Mask mode activate masking. Mask mode "All" means that all the bits
more more / All
selected in Comm obj have to be true (value 1) to activate
masking. If the mask type is "Hide", then the screen is
hidden, if it is "Show" then the screen is shown.

InteliConfig 2.17.0 Global Guide 126


MultiBar H

This instrument shows N horizontal bars (Nmax = 6). Each bar represents value of given communication object.
It expects all the communication objects are of the same data type and resolution as the first one.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position
Y 0 0-399
Maximum is 6 communication objects. It is limited to
values only.
At least 1 comobj has to be selected. Number of selected
Com items displays in Instrument properties window (e.g. "list
Source Generator
object 1-6 of 4 values")
value kW (8202)
list If any of selected com objects has a different format
(units) a message ("... Continue? Yes/No") is displayed.
Each bar represents one com object (relevant label). Only
the unit of the first selected com object is displayed.

InteliConfig 2.17.0 Global Guide 127


Bg color Default
Border ON ON/OFF
Label ON ON/OFF
Value ON ON/OFF
Units ON ON/OFF
Grid ON ON/OFF
Warn
limit ON ON/OFF
labels
Warn
limit ON ON/OFF
direction
Limits ON ON/OFF
Display
attributes Expand
OFF ON/OFF Expand high limit to 125%
scale
Editable combobox
shows list of all names from table of 'screen texts'
allows user to type & use a new text
Label
Default Default item is the first in the list. Meter displays
text
selected com object name as default.
user texts are available in <screentexts> section of
screen definition xml
Low scale limit it represented by com. obj. number or
Scale
Default constant value. Its meaning is given by connected range
0%
attributes which are set in Scale limit dialog
Scale If Low limit is >= High limit, then default limit values from
Default
100% the configuration are used.
Text
Color Default
attributes
Com. obj., which determines Hi limit (100%) for relative
Limits %
Default warning limits. Default - defined hi limit of the 1st item in
base
Source Value / Com object list is taken as default.
Warning limit is represented by com. obj. number or
Warning
None constant value. Its meaning is given by connected range
limit 1
Warning attributes which are set in Warning limit dialog
limits Warning
None See 'Warning limit 1' above
limit 2
Warning
None See 'Warning limit 1' above
limit 3
Warning
None See 'Warning limit 1' above
limit 4
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 128


MultiBar V

This instrument shows N vertical bars (Nmax = 6). Each bar represents value of given
communication object. It expects all the communication objects are of the same data
type and resolution as the first one.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position
Y 0 0-399
Maximum is 6 communication objects. It is limited to
values only.
At least 1 comobj has to be selected. Number of selected
Com items displays in Instrument properties window (e.g. "list
Source Generator
object 1-6 of 4 values")
value kW (8202)
list If any of selected com objects has a different format
(units) a message ("... Continue? Yes/No") is displayed.
Each bar represents one com object (relevant label). Only
the unit of the first selected com object is displayed.

InteliConfig 2.17.0 Global Guide 129


Bg color Default
Border ON ON/OFF
Label ON ON/OFF
Value ON ON/OFF
Units ON ON/OFF
Grid ON ON/OFF
Warn
limit ON ON/OFF
labels
Warn
limit ON ON/OFF
direction
Limits ON ON/OFF
Display
attributes Expand
OFF ON/OFF Expand high limit to 125%
scale
Editable combobox
shows list of all names from table of 'screen texts'
allows user to type & use a new text
Label
Default Default item is the first in the list. Meter displays
text
selected com object name as default.
user texts are available in <screentexts> section of
screen definition xml
Low scale limit it represented by com. obj. number or
Scale
Default constant value. Its meaning is given by connected range
0%
attributes which are set in Scale limit dialog
Scale If Low limit is >= High limit, then default limit values from
Default
100% the configuration are used.
Text
Color Default
attributes
Com. obj., which determines Hi limit (100%) for relative
Limits %
Default warning limits. Default - defined hi limit of the 1st item in
base
Source Value / Com object list is taken as default.
Warning limit is represented by com. obj. number or
Warning
None constant value. Its meaning is given by connected range
limit 1
Warning attributes which are set in Warning limit dialog
limits Warning
None See 'Warning limit 1' above
limit 2
Warning
None See 'Warning limit 1' above
limit 3
Warning
None See 'Warning limit 1' above
limit 4
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 130


MultiLabel

This instrument displays one of a set of text strings according to the index contained in the assigned value. The
value must be "stringlist" type. The selection window in the Com object property automatically filters the objects
so that only "stringlist" type objects are displayed.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 150 30-799
List is limited to values and setpoints of
Source value Com object None
stringlist type.
Display Bg color Default
attributes Border ON ON/OFF
(Default),
Text attributes Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Left /
Alignment Left Right /
Center
Color Default
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 131


Numeric

This instrument is intended for displaying numeric-type values or setpoints.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Y 0 0-399
Position Width 388 30-799
Value
300 0-799
offset
Source value Com object None
Bg color Default
Border ON ON/OFF
Display
Label ON ON/OFF
attributes
Value ON ON/OFF
Units ON ON/OFF
(Default),
Text attributes Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Label color Default
Value color Default
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 132


Rectangle

Draws a rectangle with upper-left corner at point [X,Y]. Line width, color and style are adjustable, as well as the
fill color. Fill color can be also Default.

Properties
Value
Category Name Default value Note
range
X 0 0-799 X coordinate of the left top corner
Y 0 0-399 Y coordinate of the left top corner
Position
Width 100 20-799
Height 100 20-399
Attribute Style is not supported, line is always
Line attributes Color Default
solid.
Fill attributes Fill color Default
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 133


ScreenMaskDynamicVisibility
Non-visual instrument allowing you to show/hide target screen. Based on the 32bit mask mechanism.

Properties
Default Value
Category Name Note
value range
None /
Mask
Visibility None Dynamic
mechanism
mask
Hide /
Mask type Hide This property is hidden if 'Mask mechanism = None'
Show
This property is hidden if 'Mask mechanism = None'

Com object None


If Mask mode is set on 'One or more' then ComObjBit
dialog must allow to select bits.
This property is hidden if 'Mask mechanism = None'.
Mask mode "One or more" means that at least one of the
bits selected in Comm obj has to be true (value 1) to
One or One or
Mask mode activate masking. Mask mode "All" means that all the bits
more more / All
selected in Comm obj have to be true (value 1) to activate
masking. If the mask type is "Hide", then the screen is
hidden, if it is "Show" then the screen is shown.

InteliConfig 2.17.0 Global Guide 134


String

This instrument is intended for displaying string-type values or setpoints.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Y 0 0-399
Position Width 388 30-799
Value
300 0-799
offset
Source value Com object None
Bg color Default
Border ON ON/OFF
Display
Label ON ON/OFF
attributes
Value ON ON/OFF
Units ON ON/OFF
(Default),
Text attributes Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Label color Default
Value color Default
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 135


Synchroscope

This instrument represents circular instrument (meter) for displaying the value of given communication object.
The scale covers angle value of range -180.0° -> +180.0°
Phase window is graphicaly represented as the range of the mirrored value around the phase angle
Meter expects all the communication objects have the same resolution, ie. 0.1°.
There are a communication objects for the synchroscope settings
Angle - current phase angle
Shift - phase shift - the window is shifted about the value specified in this com obj
Window - phase window (acceptable range where the phasing is still allowed)

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position
Y 0 0-399
By default, the Angle (8225) is pre-configured. If the
Slip
communication object doesn't exist the default value of
Angle Angle
None (0) is used. 'Angle' comobj selection is filtered, only
(8225)
values of dimension '°' are allowed.
By default, the Voltage Meas Phase Shift (9578) is pre-
Source configured. If the communication object doesn't exist the
Voltage default value of None (0) is used. 'Shift' comobj selection
value
Meas is filtered, only values or parameters of dimension '°'
Shift Phase are allowed.
Shift
Note: ComObj 9578 is not visible and available for
(9578)
user in some older versions of configuration (e.g. for
IG500 and IG1000)

InteliConfig 2.17.0 Global Guide 136


Phase By default, the Phase window (8652) is pre-configured.
Window window If the communication object doesn't exist the default
(8652) value of None (0) is used.
Size Small Small/Large
Bg color Default
Border ON ON/OFF
Label ON ON/OFF
Value ON ON/OFF
Units ON ON/OFF
Animated ON ON/OFF
Inner
Display scale ON ON/OFF
attributes labels
Scale bar ON ON/OFF
Editable combobox
shows list of all names from table of 'screen texts'
allows user to type & use a new text
Label text Default Default item is the first in the list. Meter displays
selected com object name as default.
user texts are available in <screentexts> section
of screen definition xml
Text
Text color Default
attributes
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 137


Text Bit Name

This instrument displays the Bit name of the selected communication object

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 150 50-799
Bin com
Source value None Variant LED status disabled
object
Display Bg color Default
attributes Border ON ON/OFF
(Default),
Text attributes Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Left /
Alignment Left Right /
Center
Color Default
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 138


Text Dim

This instrument displays the dimension of the assigned value or setpoint separately. In combination with Text
label it allows customization of the layout of various other instruments.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 150 50-799
In case of invalid value meter displays
Source value Com object None
„####“.
Display Bg color Default
attributes Border ON ON/OFF
(Default),
Text attributes Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Left /
Alignment Left Right /
Center
Color Default
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 139


Text Fixed

This is a static text string, which can be selected from the predefined system strings. If you need a custom
string use the instrument Text screen instead.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 150 50-799
The combobox
shows list of all names from table of 'fixed
names'
list can differ depending on archive (structure is
Texts Text Default
the same, eg. index 10 = Applictaion name)
Default item is the first in the list. Meter displays
„####“ as default.
In case of invalid value meter displays „####“.
Display Bg color Default
attributes Border ON ON/OFF
(Default),
Text
Font size (Default) Small, FontSize Small = 24px; Large = 36px.
attributes
Large
Left /
Alignment Left Right /
Center
Color Default
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 140


Text Label

This instrument displays the name (label) of the assigned value or setpoint separately. In combination with Text
dimension it allows customization of the layout of various other instruments.

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 150 50-799
In case of invalid value meter displays
Source value Com object None
„####“.
Display Bg color Default
attributes Border ON ON/OFF
(Default),
Text attributes Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Left /
Alignment Left Right /
Center
Color Default
This instrument supports mask dynamic
Visibility
visibility

InteliConfig 2.17.0 Global Guide 141


Text Screen

This is a static text string of max. 14 characters. It is possible to use one of already existing strings in the
configuration or add a new string. New string is added into all languages that exist in the configuration and must
be translated later using the translator function. The string is located in the group "Screen text names".

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 150 50-799
The combobox
shows list of all names from table of 'screen
texts'
allows user to type & use a new text
Texts Text Default Default item is the first in the list. Meter
displays „####“ as default.
user texts are available in <screentexts>
section of screen definition xml
In case of invalid value meter displays „####“.
Display Bg color Default
attributes Border ON ON/OFF
(Default),
Text
Font size (Default) Small, FontSize Small = 24px; Large = 36px.
attributes
Large
Left /
Alignment Left Right /
Center
Color Default
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 142


Time

This instrument displays a time-type object, e.g. current time from the controller RTC clock. The format is given
by the language, which is currently selected in the display.
Respects US/EU format based on the actually selected language in entire GUI:
EU Time : HH:MM:SS (HH 0-24)
US Time : HH:MM:SS AM/PM (HH 0-12)

Properties
Default Value
Category Name Note
value range
X 0 0-799
Position Y 0 0-399
Width 150 50-799
By default, the Time (24554) is pre-configured. If the
Source Com communication object doesn't exist the default value of
Time
value object None (0) is pre-configured. Only communication objects
of td_ftime are allowed for configuration.
Bg color Default
Display
Border ON ON/OFF
attributes
Full year ON ON/OFF
(Default),
Font size (Default) Small, FontSize Small = 24px; Large = 36px.
Large
Text
Left /
attributes
Alignment Left Right /
Center
Color Default
Visibility This instrument supports mask dynamic visibility

InteliConfig 2.17.0 Global Guide 143


6.9.11 Consistency check of Screens definiton
Consistency check shows warnings which can be in screen definition. Consistency check is shown by
Consistency check button in group Validation on Toolbar (page 100).
The warnings are shown as list in table. Each item contains description about a problem.

Properties
Supported
Name Description
displays
The warning is displayed when any property is set on an invalid
Invalid property value.
All
value The warning message shows information about a display, a screen,
an instrument and a property which contains invalid value.
The warning is displayed when screen definition contains
Invalid communication object which is not existed in configuration table.
communication The warning message shows information about a display, a screen, All
objects an instrument and a property which contains invalid communication
object.
The warning is displayed when screen doesn't contain any
instrument.
Empty screen All
The warning message shows information about a display, a screen,
which doesn't contain any instrument.
The warning is displayed when screen contains too many non-
dynamic instruments.
Too many Total limit for ICD metering screen and status bar screen is 50 non-
ICD/InteliVision
instruments on dynamic instruments and the limit only for ICD statusbar screen is
5.2
screen 10 non-dynamic instruments.
The warning message shows information about a display and a
screen, which contains too many instruments.
The warning is displayed when display configuration contains too
Too many many dynamic instruments (for ICD is limit 50
dynamic ScreenMaskDynamicVisibility instruments or 150 ICD/InteliVision
instruments in MaskDynamicVisibility instruments). 5.2
configuration The warning message shows information, which display contains
too many instruments.
The warning is displayed when instrument which contains property
Wrong scale Scale 0% and Scale 100% has invalid value. ICD/InteliVision
range The warning message shows information about a display, a screen 5.2
and an instrument which contains invalid Scale value(s).

6 back to Table of contents

InteliConfig 2.17.0 Global Guide 144


7 Multicontroller features
7.1 General information 145
7.2 View 145
7.3 Setpoints 146
7.4 Values 147
7.5 Login manager 148
7.6 Saving archive(s) 149
6 back to Table of contents

7.1 General information


In chapter Multicontroller features will be described functions, which are available only if connection to site is
opened.

7.2 View
By clicking in window Controllers can be switched view between controllers and between the view of the whole
site.

7.2.1 Site view


After connection to site is established, by default is displayed view of the whole site. Functionalities in Ribbon
are connected with controller, which is selected by green border of SCADA column template.

Image 7.1 View of the whole site

InteliConfig 2.17.0 Global Guide 145


Note: By click to some controller on the right side in Controllers window, view will be switched to detail view of
selected controller.

7.2.2 Detail view


Detail view for controller is visible if in Controllers window is selected some controller (not site). If detail view for
controller is opened, functionalities in Ribbon are connected with this selected controller (some windows have
possibility to monitor the whole site).

Image 7.2 View of the selected controller in site

7.3 Setpoints
If the connection to more than one controller is opened, setpoints window is extended by possibility to see
setpoints on all controllers (if the setpoint is on controller available) in site. By checkboxes in Control tree
section you can define from which controllers will be value of setpoint displayed.

InteliConfig 2.17.0 Global Guide 146


Image 7.3 Extended setpoints window

7.3.1 Multiwrite
Multiwrite mode allows you to rewrite setpoint value on more than one controller at the same time.
Conditions:
1. Setpoint can be rewritten only in controllers, where is setpoint available
2. You must have access rules for modifying setpoint

Steps to rewrite setpoint on more than one controller:


1. Open setpoints window and by checkboxes in Control treesection choose controllers, where you would like
to rewrite setpoint value
2. Choose setpoint you would like to change
3. Click on multiwrite icon at the bottom tab of window

7.4 Values
If the connection to more than one controller is opened, Values window is extended by possibility to see values
on all controllers (if the value is on controller available) in site. By checkboxes in Control tree section you can
define from which controllers will be values displayed.

InteliConfig 2.17.0 Global Guide 147


Image 7.4 Extended Values window

7.5 Login manager


Login manager allows user to login to more than one controller at the same time.
By checkboxes on the left side it can be selected to which controllers will be password entered. Checkboxes
have same significance for Logout button.

Image 7.5 Login manager window

InteliConfig 2.17.0 Global Guide 148


7.6 Saving archive(s)
Archive(s) may be saved to local drive or to database of InteliConfig. These functions can be found in
Ribbonunder Save icon .
Save archive
Save archive of selected controller to disk of your computer
Save archive as
Save archive of selected controller to disk as new file without any connection to possibly existing
archives, which were saved before
Save archive to database as
Save archive of selected controller to database of InteliConfig
To archive you will have access through Offline Mode bookmark
Save all archives to database
Save all available archives of controllers in site to database of InteliConfig
To these archives you will have access through Offline Mode bookmark
Save all archives to database as
Save all available archives of controllers in site as new file to database of InteliConfig
To these archives you will have access through Offline Mode bookmark

InteliConfig 2.17.0 Global Guide 149


8 Other features
8.1 Help section 150
8.2 Reporting problems 150
8.3 Cloning 150
8.4 Data export 154
6 back to Table of contents

8.1 Help section


The Help section includes:

Controller info – detail information about Controller

Controller help – full help of Controller in HTML5 format


External web browser is needed

Controller manual – PDF full Controller manual

InteliConfig manual – PDF full InteliConfig manual

About – detail information about InteliConfig version

8.2 Reporting problems


8.2.1 Steps
1. Save application logs to your computer
a. By click on report button if some error message appears

b. By click on Collect logs under Troubleshooter icon


2. Send these logs with description of problem to our technical support by email

Note: If you click on Enable detailed logging under Troubleshooter icon the application will log every single
action you make, so that the logs are more precise and helpful in case of reporting problem

8.3 Cloning
Cloning feature allows user to clone one controller or Plug-in modules configuration and firmware to another
controller.

8.3.1 Create clone


To create new clone slick on Create clone icon. Following window appears.

InteliConfig 2.17.0 Global Guide 150


Image 8.1 Create clone

1. Select required clone and click on Next button


2. Following window appears

Image 8.2 Create clone

3. Select required Connection type


4. Fill in Password
5. Click on Clone button

8.3.2 Save the clone


To save controller configuration as clone click on Save clone icon. The following window appears.

InteliConfig 2.17.0 Global Guide 151


Image 8.3 Save the clone

Plug-in Module FW bookmark


If is required to clone firmware of connected plug-in modules, click to checkbox "Include Plug-in Modules
FW"
User Management bookmark
If is required to clone user management, it can be set there all sing-in parameters, which will be saved to
clone file
If your credentials will be saved to clone file, we recommend protect this clone file by password, which
can be set up in Package protection bookmark
Init screen bookmark (not available for controllers with monochromatic display)
If is required to change Init screen of controller, it can be selected there default or custom user picture
Service screen bookmark (not available for controllers with monochromatic display)
If is required to change Service screen of controller, it can be selected there default or custom user
picture
Package protection
Set up password for clone file

8.3.3 Manage clones


Click on Manage Clones icon for managing clones. Following window appears.

InteliConfig 2.17.0 Global Guide 152


Image 8.4 Manage Clones

Exporting clone
It is possible to export clone from InteliConfig software into any location. To export the clone click on Export
clone icon. Following window appears.

Image 8.5 Save as clone

1. Type required clone name into File name bar


2. Choose required folder
3. Click on Save button

Importing clone
It is possible to import clone from any location. For importing the clone click on Import clone icon. Following
window appears.

InteliConfig 2.17.0 Global Guide 153


Image 8.6 Open clone

1. Go to location where is required clone saved


2. Select the clone
3. Click on Open button

8.4 Data export


InteliConfig allows user to export following data:
History

To export History go to History and in the bottom panel click on Export history to xls button
For more information see Exporting Setpoints, Values or Inputs and Outputs on page 155
Setpoints, values, inputs and outputs

To export Setpoints or Values click on Export to CSV/XLS icon


For more information see Exporting Setpoints, Values or Inputs and Outputs on page 155
Generate Configuration image

(COM) – To generate configuration image click on Generate Cfg image (COM) icon

(Modbus) – To generate configuration image click on Generate Cfg image (MODBUS) icon
Generate SNMP MIB table

To Generate SNMP MIB table click on icon


Archive, Firmware and Display Screens
To export archive, firmware or display screens (export of display screens is not available only for
controllers with monochromatic display) click on USB Flash Export icon and in Export manager you

InteliConfig 2.17.0 Global Guide 154


can choose required data for export
After exporting the file in .pcg3 format you can check which components are stored in the package by
clicking on Package information under USB Flash Export

8.4.1 Exporting Setpoints, Values or Inputs and Outputs


To export Setpoints, Values or Inputs and Outputs click on Export to CSV/XLS icon. Following window
appears.

1. Select required Data type


2. Click on Save button

InteliConfig 2.17.0 Global Guide 155


3. Following window appears

4. Type required exported file name and click on Save button


Note: Exported data are saved in *.csv or *.xls(x) format.

6 back to Other features

InteliConfig 2.17.0 Global Guide 156


9 Appendix
9.1 PLC
9.1.1 List of PLC blocks
Group: Basic logical functions
OR/AND 157
XOR/RS 159

Group: Comparison of analog inputs


Comparator With Hysteresis 160
Comparator With Delay 161

Group: Time functions


Timer 162
Delay 164

Group: Other functions


Force History Record 166
Force Protection 166
Counter 167

6 back to Table of contents

9.1.2 Group: Basic Logical functions


OR/AND
PLC group Basic logical functions

Related FW x.x.x

Related applications AMF, MRS MINT, SPtM

Inputs

Input Type Negation Range Function


Input 1..8 Binary Yes 0/1 Inputs 1..8
Outputs

InteliConfig 2.17.0 Global Guide 157


Output Type Negation Range Function
Output Binary Yes 0/1 Result of the logical operation
Description
The block performs logical operation OR / AND of 2-8 binary operands. The inputs as well as the output can be
inverted.

Function OR
Input 1 Input 2 Output
0 0 0
0 1 1
1 0 1
1 1 1

Function AND
Input 1 Input 2 Output
0 0 0
0 1 0
1 0 0
1 1 1

There have to be at least 2 inputs every time. There may be up to 8 inputs configured.

Image 9.1 Configuration of OR / AND block

InteliConfig 2.17.0 Global Guide 158


XOR/RS
PLC group Basic logical functions

Related FW x.x.x

Related applications AMF, MRS MINT, SPtM

Inputs

Input Type Negation Range Function


Input 1..2 Binary Yes 0/1 Inputs 1..2
Outputs

Output Type Negation Range Function


Output Binary Yes 0/1 Result of the logical operation
Description
The block provides logical function of two values – XOR or RS flip-flop. Both inputs and output can be
inverted.

Function XOR
Input 1 Input 2 Output
0 0 0
0 1 1
1 0 1
1 1 0

Function RS
R S Qn+1
0 0 Qn
0 1 1
1 0 0
1 1 0

Image 9.2 Configuration of XOR / RS block

InteliConfig 2.17.0 Global Guide 159


9.1.3 Group: Comparison of Analog inputs
Comparator With Hysteresis
PLC group Comparison of analog
inputs
Related FW x.x.x
Related applications AMF, MRS MINT, SPtM
Inputs

Input Type Negation Range Function


Input Analog No Any Compared value
Input ON Analog No Same as Input Comparative level for switching on
Input OFF Analog No Same as Input Comparative level for switching off
Outputs

Output Type Negation Range Function


Output Binary No 0/1 Comparator output
Description
The block compares the input value with the comparative levels. The behavior depends on whether the ON
level is higher than OFF level or vice versa.

Image 9.3 Different On and Off levels

InteliConfig 2.17.0 Global Guide 160


Image 9.4 Configuration of Comp Hyst block

Note: Level On and Level Off can be constants or values from controller.

IMPORTANT: In case that values on inputs have different decimal numbers than the values
are converted and the name of block is red. It is strongly recommended to use values with
the same decimal numbers.

Comparator With Delay


PLC group Comparison of analog
inputs
Related FW x.x.x
Related applications AMF, MRS MINT, SPtM
Inputs

Input Type Negation Range Function


Input 1 Analog No Any Compared value
Input 2 Analog No Same as Input 1 Comparative level
Delay Analog No 0.0..3000.0 [s] Comparative delay
Outputs

InteliConfig 2.17.0 Global Guide 161


Output Type Negation Range Function
Output Binary No 0/1 Comparator output
Description
The block works as an analog switch. It compares the input value with the comparative level. The output will
switch on if the input is equal or higher than the comparative level for time longer than the delay.

Image 9.5 Principle of delay

Image 9.6 Configuration of Comp Time block

Note: Input 2 and Delay can be constants or values from controller.

9.1.4 Group: Time functions


Timer
PLC group Time functions

Related FW x.x.x

Related applications AMF, MRS MINT, SPtM

Inputs

Input Type Negation Range Function


The timer runs only if this input is
Run Binary No 0/1
active or not connected
Reload Binary No 0/1 This input reloads the timer to the

InteliConfig 2.17.0 Global Guide 162


initial value
Reload
Analog No 0.0..3276.7 [s] Initial value of the timer
value
Outputs

Output Type Negation Range Function


Output Binary No 0/1 Timer output
Description
The block works as a countdown timer which is decreased by 1 every PLC cycle. The timer initial value is
adjustable by the "Reload value" input. The timer is automatically reloaded with the initial value when it
reaches zero or it can be reloaded in any other moment using the "reload" input. The timer is held at reload
value until the reload input is deactivated. The timer output is inverted always when the timer is reloaded.

Image 9.7 Principle of timer

Image 9.8 Configuration of Timer block

Note: Input reload value can be constant or value from controller.

Note: If you want the output to start at logical 0, tick First down option. Otherwise the output will start at
logical 1.

IMPORTANT: In case that inputs are not connected and First down option isn’t tick, then
output is active.

InteliConfig 2.17.0 Global Guide 163


Delay
PLC group Time functions

Related FW x.x.x

Related applications AMF, MRS MINT, SPtM

Inputs

Input Type Negation Range Function


Input Binary No 0/1 Input signal to be delayed
Delay of the rising edge resp. pulse
Input time -3200.0 .. 3200.0
Analog No length generated by rising edge of the
up [s, m, h]
input
Delay of the falling edge resp. pulse
Input time -3200.0 .. 3200.0
Analog No length generated by falling edge of the
down [s, m, h]
input
Resets the output to logical 0. The
output remains in logical 0 until new
Input reset Binary No 0/1
rising edge appears on Input (when
Input reset is deactivated already)
Outputs

Output Type Negation Range Function


Output Binary No 0/1 Output signal
Description
This block can work in two modes of operation:
Delay mode – the rising edge at the output is generated with delay of "input time up" when a rising
edge at the input is detected. The falling edge at the output is generated with delay of "input time
down" when a falling edge at the input is detected. If the delayed falling edge at the output came
earlier than the delayed rising edge, then no pulse would be generated at the output.
Pulse mode – a pulse of "input time up" length is generated at the output when a rising edge is
detected, a pulse of "input time down" length is generated at the output when a falling edge is
detected.

InteliConfig 2.17.0 Global Guide 164


Image 9.9 Delay modes principles

Image 9.10 Configuration of Delay block

Note: If Input time up or Input time down value is <0, this input is internally set to zero.

Note: Input time up and Input time down values can be constants or values from controller.

Note: Use Pulse on edge option to choose between delay and pulse mode.

InteliConfig 2.17.0 Global Guide 165


9.1.5 Group: Other functions
Force History Record
PLC group Other functions

Related FW x.x.x

Related applications AMF, MRS MINT, SPtM

Inputs

Input Type Negation Range Function


A record with configured text is
Input Binary No 0/1 recorded into the controller history
when the input is activated.
Outputs
No outputs.
Description
This block writes a record with defined text into the history when the input is activated.

Image 9.11 Configuration of Force Hist block

Note: Maximal number of characters for history message is 15.

Force Protection
PLC group Other functions

Related FW x.x.x

Related applications AMF, MRS MINT, SPtM

Inputs

Input Type Negation Range Function


The input activates yellow level of the
Lvl 1 Binary No 0/1
configured protection if it is configured
The input activates red level of the
Lvl 2 Binary No 0/1 configured protection if a red level
protection is configured
The input activates sensor fail if a fls
Fls Binary No 0/1
protection is configured
Outputs

InteliConfig 2.17.0 Global Guide 166


No outputs.
Description
This block issues alarms of configured type and text when appropriate binary input is activated.

Image 9.12 Configuration of Force Prot block

Available protections are:


Monitoring
HistRecOnl
AL Indic
Wrn
Wrn+BOC
BOC
Wrn+Sd
Sd

Note: Maximal number of characters for alarmlist message is 15.

Note: Prefix of protection (e.g. Wrn, Sd, BOC) is added automatically into alarmlist message.

Counter
PLC group Other functions

Related FW x.x.x

Related applications AMF, MRS MINT, SPtM

Inputs

Input Type Negation Range Function


Input (source) of the counted edges,
Input Count
Binary No 0/1 Edge on this Input increase the value
Up
of the counter
Input
Counter value limit for activation of the
Preset Analog No 0-32767 [-]
output.
Limit
Input Clear Binary No 0/1 Reset input.

InteliConfig 2.17.0 Global Guide 167


Outputs

Output Type Negation Range Function


Output is activated when the counter
Output Binary No 0/1
value >= Input "Preset Limit".
Description
The block works as a counter of edges (selectable rising, falling or both) with reset input and adjustable
counting limit. The maximal counter value is 32767. The counter value is lost when the controller is switched
off. The output is activated when the counter value reaches equal or higher value than the adjusted limit and
remain active until the block is reset. Activating of the reset input resets the counter value to 0, deactivates
the output. The counter is kept stopped until the "Input Clear" is active.

Image 9.13 Configuration of Counter block

6 back to Appendix

InteliConfig 2.17.0 Global Guide 168