Professional Documents
Culture Documents
2
2
Thermal Magnetic Breakers
3
3
UL 489
Molded Case Circuit Breakers
• Calibration
• 135% - Trip within 1 hr for
ratings less than 50A
• 200%
• 2 min – 0-30A
• 4 min – 31-50A
• Endurance (below 100A)
• 6,000 operations w/ current
• 4,000 operations w/o current
• Overload
• Must break 600 percent of
its rated current
4
4
5
5
Overcurrent Protection
• Overcurrent protection is
provided by bi-metal
Bi-metal
6
6
Short Circuit Protection
7
7
UL 943 / UL 1053
Ground Fault Circuit Interrupters /
Ground-Fault Sensing and Relaying Equipment
UL 943
• Leakage < 6 mA
• Trip time ~15 mS
• Temperature Cycle Testing
• Room Temp, -35ºC, Room
Temp, 60ºC, Room Temp
• Humidity Condition
• 60hrs – 92% Humidity / 85ºF
• Surge Testing
UL 1053
• Leakage within 10% of level
defined by manufacturer
• Humidity Condition
• 60hrs – 92% Humidity / 85ºF
• Surge Testing
8
8
Ground Fault Circuit Interrupters
4.993A
5.000A
X
OK
5.000A
9
9
Arcing Faults
• Unintentional Arcing
Condition
• Temperatures In
Excess Of 10,000
degrees Fahrenheit
• Not persistent
enough to heat the
bimetal in Thermal
Magnetic Breakers
10
10
History of Arc Fault Detection
2001 2002 2003 2004 2005 2008 2011 2014
Product Development
Branch-Feeder AFCI
120VAC 60 Hz
Combination Type
High Current Arc Aircraft AFCI Receptacle AFCI
Detection 28 VDC 120VAC, 60 Hz
(not mandated)
12
12
High Current vs Low Current Arcing
High Current Level Arc Low Current Level Arc
“Parallel Arc” “Series Arc”
• Spikes within the AC Waveform • Current may not rise above handle rating
• Current Spikes above handle rating but… • Arcing evident by high frequency noise being
• Current level of spike are not big enough to generated (pink trace)
trip short circuit mechanism
• Thermal mechanism would not trip in time
to mitigate a fire
2
Breaker
Handle -2
Rating
13
13
Classifying An Arc Fault
• Operational Arcs - occur in a properly functioning
electrical system
• Switching loads on/off
• Contact closure/opening
14
14
Operational Arcs
15
15
Hazardous Arcs
16
16
Wiring Degradation Drivers
• Temperature
• Humidity
• Mechanical Stress
• Voltage Stress
• Time
• Loose connections
• Stranded Aluminum wiring
• Nails through the wall
• Corrosion
• Do-it-yourselfers
• Rodents
17
17
CPSC Recalls
Shock and Fire Hazards
18
18
CPSC Recalls
Shock and Fire Hazard
19
19
Life Phases of the Home
20
20
Case Study
Location:
Fort Mill, SC
Age of Home:
Home Built in 2005
Background:
An arc fault breaker began
tripping intermittently on a
bedroom lighting circuit when
turning on fan or lights.
21
21
Case Study
22
22
Case Study
23
23
Codes And Standards
2008 NEC
“Dwelling Units. All 120-volt, single-phase, 15- and 20-
ampere branch circuits supplying outlets installed in
dwelling unit
25
25
National Electrical Code
Article 210.12
Introduction of Branch Feeder AFCI to the National Electrical Code.
Protection of branch circuits supplying bedroom receptacle outlets as of
January 1, 2002.
26
26
2011 NEC – AFCI Requirements
210.12
• No expanded use of AFCI
• No removal of conduit requirement
(A) Dwelling Units. All 120-volt, single phase, 15- and 20-ampere branch circuits
supplying outlets or devices installed in dwelling unit kitchens, family rooms, dining rooms,
living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets,
hallways, laundry areas, or similar rooms or areas shall be protected by any of the means
described in (1) through (6) [P2-85] [P2-82a] [P2-80] [C2-52]
(1) A listed combination type arc-fault circuit interrupter, installed to provide protection
of the entire branch circuit.
28
28
2014 NEC – AFCI Requirements
Receptacle Requirements
(2) A listed branch/feeder type AFCI installed at the origin of the branch circuit in
combination with a listed outlet branch circuit type arc-fault circuit interrupter installed at
the first outlet box on the branch circuit. The first outlet box in the branch circuit shall be
marked to indicate that it is the first outlet of the circuit. [C2-59]
(3) A listed supplemental arc protection circuit breaker installed at the origin of the
branch circuit in combination with a listed outlet branch circuit type arc-fault circuit
interrupter installed at the first outlet box on the branch circuit where all of the following
conditions are met:
(a) The branch circuit wiring shall be continuous from the branch circuit overcurrent device
to the outlet branch circuit arc-fault circuit interrupter.
(b) The maximum length of the branch circuit wiring from the branch circuit overcurrent
device to the first outlet shall not exceed 15.2 m (50 ft) for a 14 AWG or 21.3 m (70 ft)
for a 12 AWG conductor.
(c) The first outlet box in the branch circuit shall be marked to indicate that it is the first
outlet of the circuit. [C2-59]
29
29
2014 NEC – AFCI Requirements
Receptacle Requirements
(4) A listed outlet branch circuit type arc-fault circuit interrupter installed at the first
outlet on the branch circuit in combination with a listed branch circuit overcurrent
protective device where all of the following conditions are met:
(a) The branch circuit wiring shall be continuous from the branch circuit overcurrent device
to the outlet branch circuit arc-fault circuit interrupter.
(b) The maximum length of the branch circuit wiring from the branch circuit overcurrent
device to the first outlet shall not exceed 15.2 m (50 ft) for a 14 AWG or 21.3 m (70 ft) for
a 12 AWG conductor.
(c) The first outlet box in the branch circuit shall be marked to indicate that it is the first
outlet of the circuit. [C2-59]
(d) The combination of the branch circuit overcurrent device and outlet branch circuit AFCI
is identified as meeting the requirements for a "System Combination" type AFCI and is listed
as such.
(5) If RMC, IMC, EMT, Type MC, or steel armored Type AC cables meeting the
requirements of 250.118, metal wireways, metal auxiliary gutters and metal outlet and
junction boxes are installed for the portion of the branch circuit between the branch-circuit
overcurrent device and the first outlet, it shall be permitted to install a listed outlet branch-
circuit type AFCI at the first outlet to provide protection for the remaining30portion of the 30
2014 NEC – AFCI Requirements
Receptacle Requirements
(6) Where a listed metal or nonmetallic conduit or tubing or Type MC Cable is encased
in not less than 50mm (2 in.) of concrete for the portion of the branch circuit between the
branch circuit overcurrent device and the first outlet, it shall be permitted to install a listed
outlet branch circuit type AFCI at the first outlet to provide protection for the remaining
portion of the branch circuit. [C2-46] [P2-103]
31
31
Introducing AFCI
32
32
Introducing AFCI
Operating Handle Push To Test Button
Latch Piece
Load Terminal
Mechanism Spring
33
33
Installation
• Basic Installation Notes
• Circuit Breaker Pigtail Termination To Neutral Bar
• Load Hot (black) AND Neutral (white) Landed To
The Circuit Breaker
• Press The Test Button
• Plug A Load Into The Circuit To Ensure No
Shared Neutral Mistakes
Grounded
• Common Mistakes Neutral
35
35
36
36
FCC Regulations
Conducted Emissions
§ 15.107 Conducted limits.
(a) Except for Class A digital devices, for equipment that is designed to be connected to the public utility
(AC) power line, the radio frequency voltage that is conducted back onto the AC power line on any
frequency or frequencies within the band 150 kHz to 30 MHz shall not exceed the limits in the following
table, as measured using a 50 μH/50 ohms line impedance stabilization network (LISN). Compliance with
the provisions of this paragraph shall be based on the measurement of the radio frequency voltage between
each power line and ground at the power terminal. The lower limit applies at the band edges.
Eaton’s Options
1) Contact the Manufacturer
2) Enter a Complaint with FCC / UL
3) Make a Better Product!
37
37
Case Study
Manmade vs Hazardous Arcs
Common electronic
stepdown transformer
(low voltage lighting)
dB scale: 20 dB = 10X
SPEED
650
LIMIT MPH!
65
38
38
Case Study
Manmade vs Hazardous Arcs
High Frequency Noise Arc Signature
Electronic Transformer Series Arc Test per UL 1699
(low voltage lighting)
39
39
Troubleshooting
Basic Troubleshooting Techniques
1. Is the breaker functioning properly?
• Disconnect the load wire and the neutral, leave the pigtail connected
• Turning the breaker on.
• Press the Test Button.
2. Check For Grounded Neutrals
3. Is there a load creating the issue?
• Disconnect All Loads From The Receptacles . . . Including Surge Strips
4. Narrow down the wiring issue
• Break The Circuit Into Smaller Chunks – disconnect wire at every junction
• Add sections back until the issue is found
40
40
Trip Codes We Capture…
(Eaton Only)
41
41
5A Threshold
42
42
Solutions
Universal Solutions
• Surge Device
• Filters noise via capacitor to ground
• Must be installed on the device or
between the device and the breaker.
• Ferrite Beads
• Can become saturated if too much
noise is present
Eaton Solutions
• Next Generation
• Reduced unwanted tripping through
software changes creating tolerance
for non-compliant devices
43
43
Case Study
Surge on a Vacuum
High Frequency Noise Reduced Interference with
Conducted by a 12A Vacuum Surge Device
44
44
Next Generation BR (1”)
Compact Footprint
Feature
Compact as a Standard
Benefit
Better access to
conductors and neutral
bars in wireway
45
45
Next Generation BR (1”) and CH (3/4”)
Updated Electronics
Feature
Redesigned Electronic
Hardware and Software
Benefit
Highly resistant to
unwanted tripping due to
non-compliant devices
46
46
Next Generation BR (1”) and CH (3/4”)
Diagnostic LED
Feature
Diagnostic LED Signals
up to 7 Trip Codes
Benefit
Immediate feedback to
diagnose and resolve
tripping
• Standard Feature in CH
• Optional Feature in BR
47
47
A Word On Handheld Testers…
UL Says…
• The Button Rules
AFCI / Tester Compatibility
• Not every tester will not trip every breaker
• Eaton Handheld tester is approved for
use with Eaton Breakers
So…What is the Value?
• Is receptacle on AFCI/GFCI?
• Confirm wiring
• Visual for Home owner
48
48
Thank You