19000 1675 5990 3250 5990 1520

1675 725 550 3440 550 725 725 550 3440 550 725

B
12mm ISOLATION JOINT
- C
-
10mm ISOLATION JOINT 10mm ISOLATION JOINT
AGAINST PLINTH AGAINST PLINTH

650 200 650


750
I.J.

1500

2235
750
A A

735

735
1675 1200 1130 1330 1130 1200 1620 1620 1200 1130 1330 1130 1200 1520

19300
BUND WALL CONCRETE LAYOUT
SCALE 1:50

18420

1675 725 550 3440 550 725 3250 725 550 3440 550 725 1520
EXISTING

560
1
NEW -
R16-02 DOWELS AT 200 c/c

710
500 400 300
A

500 400
35200

1200
-

900
HILTI-HIT RE-500 OR SIMILAR KUNISEAL OR SIMILAR APPROVED WATER STOP

2400
APPROVED SLEEVE COMPOUND SEAL PLACED ALL AROUND WHERE NEW CONCRETE
SECTION A GET INTO CONTACT WITH EXISTING SURFACES
1:50 -

550
650 200 650
1425 200 375 CONCRETE NOTES

50
3440
1. CONCRETE CONSTRUCTION SHALL BE PERFORMED TO SANS 2001-CC1

30
DRILLED AND EPOXY BARS 200mm LONG 2. ALL CONCRETE SHALL BE 30 MPa AT 28 DAYS U.O.N.

600 LONG DOWELS


400
HOLES FOR Y10 STARTER BARS

R16-02 @ 200c/c
3. BLINDING CONCRETE TO BE MINIMUM 10 MPa

BARS = 570 LONG


Y10-01@200 c/c
HILTI-HIT RE-500 OR SIMILAR
APPROVED EPOXY ADHESIVE

400
4. ALL EXPOSED CORNERS TO HAVE 25mm CHAMFER

370
550

900

70
5. ALL REINFORCEMENT TO HAVE (UNLESS STATED OTHERWISE):-

900
500

360
50mm COVER - BASES AND CONCRETE IN CONTACT WITH THE GROUND

200
30mm COVER - R.C. WALL
585

500
70
6. ALL REINFORCEMENT TO LAP WITH MIN 50 DIAMETERS U.O.N.
4700

200

70
7. REINFORCEMENT DIMENSIONS ARE ACCORDING TO SANS 282
ROUGHEN SURFACE TO
EXPOSE AGGREGATE 8. ALL CONCRETE SHALL BE PROPERLY CURED FOR AT LEAST 7 DAYS U.O.N.
9. FINISHES ON CONCRETE FLOOR MUST CONFORM TO SANS 10109-2:2013
DOWEL SLEEVES WITH HILTI-HIT
70 180 250 250 250 250 180 70 RE-500 OR SIMILAR APPROVED 10. AT LEAST 6 CONCRETE TEST CUBES MUST BE SAMPLED FROM EACH TRUCK OF READY
550

SLEEVE COMPOUND MIX FOR TESTING (3 FOR CRUSHING AT 7 DAYS AND 3 FOR CRUSHING AT 28 DAYS)
750 750
1525 475 11. THE CONTRACTOR SHALL ENSURE THAT ALL REINFORCEMENT IS PROPERLY HELD IN
1500
2000 POSITION AND SHALL ALSO MAINTAIN THE CORRECT CONCRETE COVER UTILIZING
3440

APPROVED SPACERS (NOT STONES, OFF-CUT REINFORCEMENT, ETC) AT ALL TIMES


SECTION B SECTION C
- 12. CONCRETE SHALL BE COMPACTED MECHANICALLY THROUGH THE USE OF VIBRATORS
1:20 1:20 -
13. STOOLS TO SIT ON TOP OF B1 AND NOT ON FORMWORK OF BLINDING LAYER
550

14. ALL EXPOSED SURFACES OF THE NEW CONCRETE WALL AND BASES TO BE COATED

305 295 WITH ABE-COTE SF 217 OR SIMILAR APPROVED


2245

12mm ISOLATION JOINT


38
00

400
16140

900
BUND WALL CONCRETE LAYOUT

500
SCALE 1:100

R16-02 DOWELS AT 200 c/c DOWEL SLEEVE


FOR 16mm BARS
DETAIL 1
1:20 -

REFERENCE DRAWINGS APPROVER: Q.M.S CHECKING SYSTEM No. 11 MALOKIBA INDUSTRIAL PARK
SCALE
BUND WALL REINFORCEMENT LAYOUT NAME: 1 BRUNEL ROAD
RE-MP-21070-STR-002
DRAWN BY: SB SOHUMA EVANDER, MPUMALANGA
DRAWING No.
Pr. No. 2280 PROPOSED BUND WALL
DRAWING CHECK: G TLAAMELA RE-MP-21070-STR-001
P.O. Box 3211
For: ROBUST CONSULTING SECUNDA EVANDER, MPUMALANGA
ENGINEERS (PTY) LTD DRAWING REVIEW: M WAYITI 2302 CLIENT DRAWING No.
BUND WALL CONCRETE
Revisions

Sign: DESIGN ENG.: G TLAAMELA Tell: 086 117 7726


A1 2021/11/02 ISSUE FOR TENDER SB Fax: 086 535 3817 LAYOUT, SECTIONS AND DETAILS
Date:
No. Date Description Initial
DESIGN REVIEW: M WAYITI E-mail: info@robustengineers.co.za REVISION No. A1