You are on page 1of 5

PT SUCOFINDO

Specification of Stack

Client : PT. HM SAMPOERNA PLANT SUKOREJO


Unit : GENSET 01 (213378-26)
Date of sampling : MAY 29,2021 14.00 wib
Technician : SJD/WY/MMA
Type of stack : CIRCULAR
Fuel : DIESEL OIL
Number of sampling hole : 2
Engine Capacity : 100%
Diameter of stack (m) : 0.5
Height of stack (m) : 9.425
Upstream (B) : 0.65
Downstream (A) : 1.2
Number of traverse point : 8
o
Coordinate S 07 42' 07.24"
o
E 112 41' 34.36"
PT SUCOFINDO
Determination of Gas Concentration Using Gas Analyzer

Client : PT. HM SAMPOERNA PLANT SUKOREJO


Unit : GENSET 01 (213378-26)
Date of sampling : MAY 29,2021 14.00 wib
Technician : SJD/WY/MMA
Lab No :

O2 Correction O2 CO2 CO NO NO2 NOx as NO2 SO2


Meas
Reference % % ppm ppm ppm ppm ppm
1 13 14.14 6.77 70 509 5.2 514.2 0
2 14.35 7.33 75 549 5.3 554.3 0
3 14.39 6.75 72 521 5 526 0
4 13.97 6.86 74 533 12.7 545.7 0
5 -
6 -
7 -
8 -
9 -
10 -

Summary
Parameters %O2 % CO2 CO NO NO2 NOx as NO2 SO2 %CE
Average of (ppm) 14.2 6.9 72.8 528.0 7.1 535.1 0.0
Concentrations (mg/Nm³) - - 83.3 647.9 13.3 1006.6 0.0 99.90
Oxygen correction result (mg/Nm³) - - 98.2 763.6 15.6 1186.5 0.0
*) %CE : Combustion Efficiency

Test Personnel Supervisor ppm CO2


#REF!
Signature Signature
PT SUCOFINDO
Determination of Water Content

Client : PT. HM SAMPOERNA PLANT SUKOREJO


Unit : GENSET 01 (213378-26)
Date of sampling : MAY 29,2021 14.00 wib
Technician : SJD/WY/MMA
Lab No : 0
Metode : SNI 7117.16-2009

Impinger No Wo (g) W1 (g) (W1-Wo)


1 725.00 752.00 27.00 g
2 702.00 727.00 25.00 g
3 603.00 607.00 4.00 g
4
5
6
Volume of condensed water vapor 56.00 g
Silica Gel 740.00 745.00
Volume of condensed water vapor in silica gel 5.00 g

Component
Volume of gas sampled through dry gas meter (Vm) 0.865 m³
Dry gas meter (DGM) calibration factor (Y) 0.9965
DGM temperature in Celsius (tm) 35.0 °C
DGM temperature in Kelvin (Tm) 308.0 K
Temperature Standard (Tstd) 298.0 K
DGM orifice pressure differential (dH) 49.25 mmH2O
Barometric pressure actual (Pbar) 758 mmHg
Barometric pressure standard (Pstd) 760 mmHg
Gas Ideal a Constant (R) 0.06236 mmHg.m³/g-mol.K
Weight Molecular of Water M 18 g/mol

Component
Volume of dry gas sampled convert to STD Condition Vm(std) 0.8410 Nm³
Volume of condensed water vapor convert to STD Condition Vwc(std) 0.08 Nm³
Volume of condensed water vapor in silica gel convert to STD Condition Vwsg(std) 0.00679 Nm³
Mole Fraction of water vapor condensed Bws 0.090 (v/v)
Water Content %H2O 9.0 %(v/v)
METRIC UNITS
PT SUCOFINDO
Determination of Linier Velocity, Molecullar Mass of Dry Gas and Total Particulate
Client PT. HM SAMPOERNA PLANT SUKOREJO Technician SJD/WY/MMA
Unit GENSET 01 (213378-26) Start Time 14:00
Date of sampling MAY 29,2021 14.00 wib End Time 15:00
Metode SNI 7117.14-2009 (Linier Velocity) Lab No 0
SNI 7117.15-2009 (Molecullar Mass of Dry Gas)
SNI 7117.17-2009(Total Particulate)
STACK DATA EQUIPMENT ESTIMATES FILTERS
% H2O est (%)O₂
% Moisture est: 5 METER BOX: Est. Tm: 35.0 °C Main Filter (g) Recovery (g)
CORRECTION
Barometric: 758.0 mm Hg Y: 0.9965 Est. Ts: 394.0 °C W1 0.3372 1.4034 REFERENCE
Static Press: 42.8 mm H2O DH@: 47.30 mm H2O Est. dP: 76.5 mm H2O Wo 0.3262 1.401
Stack Press: 761.1 mm Hg PITOT: Est. Dn: 4.80 mm W1-Wo 0.011 0.0024 13
%CO2: 6.93 % Cp: 0.84 LEAK CHECKS K FACTOR
%O2: 14.21 % NOZZLE: DGM initial ______ ______ ______ liters
0.61
%N2/CO: 78.86 % Dn: 4.80 mm DGM final ______ ______ ______ liters
Md: 29.68 g/g-mole Diameter Stack 0.5 m Leak Rate ______ ______ ______ lpm Particulate Mass (mg)
Ms: 29.09 g/g-mole Traverse Point 8 Vacuum ______ ______ ______ in. Hg 13.4

Sample Time Pitot Gas Temperatures (°C) Orifice Press. Pump Gas Temps
Sample

Dry Gas Meter Imp Vs


Point

(minutes) DP DGM DH (mm H20) Vac. (°C) % ISO


Reading (liters) (°C) (m/s)
Begin End (mm H2O) Inlet Outlet Stack Ideal Actual (in Hg) Probe Filter
A1 0 5.00 119114.00 80.00 35.0 35.0 438 45.2 48.0 3 120 120 18.0 101.4 47.08
2 5 10.00 119221.00 80.00 35.0 35.0 439 45.2 48.0 4 120 120 18.0 103.4 47.11
3 10 15.00 119330.00 78.00 35.0 35.0 439 44.1 48.0 4 120 120 18.0 105.7 46.52
4 15 20.00 119440.00 80.00 35.0 35.0 439 45.2 48.0 4 120 120 18.0 100.6 47.11
5 20 25.00 119546.00 84.00 35.0 35.0 439 47.4 52.0 5 120 120 18.0 103.7 48.28
6 25 30.00 119658.00 84.00 35.0 35.0 441 47.3 52.0 5 120 120 18.0 97.4 48.34
7 30 35.00 119763.00 80.00 35.0 35.0 441 45.1 48.0 5 120 120 18.0 105.4 47.18
8 35 40.00 119874.00 82.00 35.0 35.0 441 46.2 50.0 5 120 120 19.0 98.5 47.76
9 40 45.00 119979.00 - -
10 45 - -
11 0 - -
12 0 - -
13 0 - -
14 0 - -
15 0 - -
16 0 - -
17 0 - -
18 0 - -
19 0 - -
20 0 - -
21 0 - -
22 0 - -
23 0 - -
24 0 - -
Final DGM:

DP (H2O) DH (H2O)
RESULTS

Run Time Vm Tm Ts Max. Vac %ISO Vs


3
45.00 min 0.865 m 81.00 mm 35.0 °C 439.6 °C 5 49.25 mm 94.7 47.4 m/s
##### #####
Vmstd Stack Area Qsd Qa Concentration Concentration Corr O₂ Emission Rate
0.8358 Nm3 0.196 m² 3.5 m³/s 9.3 m³/s 16.0 mg/Nm³ 18.9 mg/Nm³ 0.205 kg/hr
Test Personnel : Supervisor : Abdul Muis Karim

Signature : Signature :

METRIC UNITS
REPORT OF ANALYSIS

Client : PT. HM SAMPOERNA TBK PLANT SUKOREJO


Jl. Raya Surabaya-Malang, Km.51.4 , Pandaan, Jerukuwik
Ngadimulyo, Kec.Sukorejo, Kab.Pasuruan , Jawa Timur 67161
Type Of Sample : Emission Air
Tested for : Environment Minister Regulatory No.13/2009 . Appendix I 1.a2 (>570 Kwth , oil)
Date Of Sampling : MAY 29,2021 14.00 wib
Sample Identification : Unit GENSET 01 (213378-26)
: Fuel DIESEL OIL
: Engine Capacity (kVa) 1
: Inside Diameter (m) 0.5
: Height (m) 9.425
: Upstream 0.65
: Downstream 1.2
: Number Of Traverse Point 8
: Coordinate S 07o 42' 07.24"
E 112o 41' 34.36"

Test Result
Threshold Limit
Parameter Unit Measurement Corrected Methods
Value
Concentration Concentration
mg/Nm³ 16.0 18.9 150 SNI 7117.17:2009
Total Particulate
SO₂ (Sulfur Dioxide) mg/Nm³ <0.26 <0.26 800 PO/ENV-EMS/02
Nitrogen Oxide (NOx) as NO₂ mg/Nm³ 1007 1186 1000 PO/ENV-EMS/03
CO (carbon Monoxide) mg/Nm³ 83.3 98.2 600 SNI 19-7117.10-2005
CO₂ (Carbon Dioxide) % 6.93 - - SNI 19-7117.10-2005
O₂ (Oxygen) % 14.21 - - SNI 19-7117.10-2005
Isokinetic % 94.7 90 - 110 Calculated
Linear Velocity m/s 47.4 - SNI 7117.14:2009
Flow Rate (ACT) m³/s 9.3 - SNI 7117.14:2009
Flow Rate (STD) m³/s 3.5 - SNI 7117.14:2009
Note : The result of parameter concentration were corrected 13% oxygen rate on condition normally air (25°C and 1 atm) and dry basis