You are on page 1of 5

PT SUCOFINDO

Specification of Stack

Client : PT. HM SAMPOERNA PLANT SUKOREJO


Unit : GENSET 03 (213378-28)
Date of sampling : MAY 29,2021 11.00 WIB
Technician : SJD/WY/MMA
Type of stack : CIRCULAR
Fuel : DIESEL OIL
Number of sampling hole : 2
Engine Capacity : 60%
Diameter of stack (m) : 0.5
Height of stack (m) : 9.425
Upstream (B) : 0.65
Downstream (A) : 1.2
Number of traverse point : 8
o
Coordinate S 07 42' 06.75"
o
E 112 41' 34.66"
PT SUCOFINDO
Determination of Gas Concentration Using Gas Analyzer

Client : PT. HM SAMPOERNA PLANT SUKOREJO


Unit : GENSET 03 (213378-28)
Date of sampling : MAY 29,2021 11.00 WIB
Technician : SJD/WY/MMA
Lab No :

O2 Correction O2 CO2 CO NO NO2 NOx as NO2 SO2


Meas
Reference % % ppm ppm ppm ppm ppm
1 13 14.75 6.68 82 349 1.2 350.2 24
2 14.72 6.68 82 364 1.2 365.2 27
3 14.48 6.95 84 386 1.4 387.4 29
4 14.91 6.56 80 363 1.2 364.2 26
5 15.02 6.45 82 369 1.1 370.1 28
6 -
7 -
8 -
9 -
10 -

Summary
Parameters %O2 % CO2 CO NO NO2 NOx as NO2 SO2 %CE
Average of (ppm) 14.8 6.7 82.0 366.2 1.2 367.4 26.8
Concentrations (mg/Nm³) - - 93.9 449.3 2.3 691.3 70.2 99.88
Oxygen correction result (mg/Nm³) - - 120.7 577.5 3.0 888.5 90.2
*) %CE : Combustion Efficiency

Test Personnel Supervisor ppm CO2


#REF!
Signature Signature
PT SUCOFINDO
Determination of Water Content

Client : PT. HM SAMPOERNA PLANT SUKOREJO


Unit : GENSET 03 (213378-28)
Date of sampling : MAY 29,2021 11.00 WIB
Technician : SJD/WY/MMA
Lab No : 0
Metode : SNI 7117.16-2009

Impinger No Wo (g) W1 (g) (W1-Wo)


1 752.00 782.00 30.00 g
2 702.00 705.00 3.00 g
3 607.00 610.00 3.00 g
4
5
6
Volume of condensed water vapor 36.00 g
Silica Gel 745.00 750.00
Volume of condensed water vapor in silica gel 5.00 g

Component
Volume of gas sampled through dry gas meter (Vm) 1.324 m³
Dry gas meter (DGM) calibration factor (Y) 0.9965
DGM temperature in Celsius (tm) 33.4 °C
DGM temperature in Kelvin (Tm) 306.4 K
Temperature Standard (Tstd) 298.0 K
DGM orifice pressure differential (dH) 48.25 mmH2O
Barometric pressure actual (Pbar) 759 mmHg
Barometric pressure standard (Pstd) 760 mmHg
Gas Ideal a Constant (R) 0.06236 mmHg.m³/g-mol.K
Weight Molecular of Water M 18 g/mol

Component
Volume of dry gas sampled convert to STD Condition Vm(std) 1.2956 Nm³
Volume of condensed water vapor convert to STD Condition Vwc(std) 0.05 Nm³
Volume of condensed water vapor in silica gel convert to STD Condition Vwsg(std) 0.00679 Nm³
Mole Fraction of water vapor condensed Bws 0.041 (v/v)
Water Content %H2O 4.1 %(v/v)
METRIC UNITS
PT SUCOFINDO
Determination of Linier Velocity, Molecullar Mass of Dry Gas and Total Particulate
Client PT. HM SAMPOERNA PLANT SUKOREJO Technician SJD/WY/MMA
Unit GENSET 03 (213378-28) Start Time 11:35
Date of sampling MAY 29,2021 11.00 WIB End Time 12:35
Metode SNI 7117.14-2009 (Linier Velocity) Lab No 0
SNI 7117.15-2009 (Molecullar Mass of Dry Gas)
SNI 7117.17-2009(Total Particulate)
STACK DATA EQUIPMENT ESTIMATES FILTERS
% H2O est (%)O₂
% Moisture est: 5 METER BOX: Est. Tm: 32.0 °C Main Filter (g) Recovery (g)
CORRECTION
Barometric: 759.0 mm Hg Y: 0.9965 Est. Ts: 441.0 °C W1 0.3352 1.327 REFERENCE
Static Press: 40.0 mm H2O DH@: 47.30 mm H2O Est. dP: 86.5 mm H2O Wo 0.3256 1.321
Stack Press: 761.9 mm Hg PITOT: Est. Dn: 4.76 mm W1-Wo 0.0096 0.006 13
%CO2: 6.66 % Cp: 0.84 LEAK CHECKS K FACTOR
%O2: 14.78 % NOZZLE: DGM initial ______ ______ ______ liters
0.56
%N2/CO: 78.56 % Dn: 4.80 mm DGM final ______ ______ ______ liters
Md: 29.66 g/g-mole Diameter Stack 0.5 m Leak Rate ______ ______ ______ lpm Particulate Mass (mg)
Ms: 29.07 g/g-mole Traverse Point 8 Vacuum ______ ______ ______ in. Hg 15.6

Sample Time Pitot Gas Temperatures (°C) Orifice Press. Pump Gas Temps
Sample

Dry Gas Meter Imp Vs


Point

(minutes) DP DGM DH (mm H20) Vac. (°C) % ISO


Reading (liters) (°C) (m/s)
Begin End (mm H2O) Inlet Outlet Stack Ideal Actual (in Hg) Probe Filter
A1 0 7.50 120763.00 84.00 32.0 32.0 442 46.8 48.0 3 120 120 19.0 101.2 48.37
2 7.5 15.00 120925.00 86.00 32.0 32.0 446 47.6 48.0 3 120 120 19.0 100.3 49.08
3 15 22.50 121087.00 88.00 33.0 33.0 448 48.7 50.0 3 120 120 19.0 103.9 49.71
4 22.5 30.00 121257.00 86.00 34.0 34.0 449 47.7 48.0 3 121 121 19.0 103.0 49.18
5 30 37.50 121424.00 84.00 34.0 34.0 449 46.6 48.0 3 121 121 19.0 103.5 48.60
6 37.5 45.00 121590.00 84.00 34.0 34.0 448 46.7 48.0 3 120 121 19.0 103.5 48.57
7 45 52.50 121756.00 86.00 34.0 34.0 448 47.8 48.0 4 121 120 19.0 102.3 49.14
8 52.5 60.00 121922.00 84.00 34.0 34.0 449 46.6 48.0 4 120 120 19.0 102.9 48.60
9 60 122087.00 - -
10 0 - -
11 0 - -
12 0 - -
13 0 - -
14 0 - -
15 0 - -
16 0 - -
17 0 - -
18 0 - -
19 0 - -
20 0 - -
21 0 - -
22 0 - -
23 0 - -
24 0 - -
Final DGM:

DP (H2O) DH (H2O)
RESULTS

Run Time Vm Tm Ts Max. Vac %ISO Vs


3
60.00 min 1.324 m 85.25 mm 33.4 °C 447.4 °C 4 48.25 mm 101.7 48.9 m/s
##### #####
Vmstd Stack Area Qsd Qa Concentration Concentration Corr O₂ Emission Rate
1.2876 Nm3 0.196 m² 3.8 m³/s 9.6 m³/s 12.1 mg/Nm³ 15.6 mg/Nm³ 0.166 kg/hr
Test Personnel : Supervisor : Abdul Muis Karim

Signature : Signature :

METRIC UNITS
REPORT OF ANALYSIS

Client : PT. HM SAMPOERNA TBK PLANT SUKOREJO


Jl. Raya Surabaya-Malang, Km.51.4 , Pandaan, Jerukuwik
Ngadimulyo, Kec.Sukorejo, Kab.Pasuruan , Jawa Timur 67161
Type Of Sample : Emission Air
Tested for : Environment Minister Regulatory No.13/2009 . Appendix I 1.a2 (>570 Kwth , oil)
Date Of Sampling : MAY 29,2021 11.00 WIB
Sample Identification : Unit GENSET 03 (213378-28)
: Fuel DIESEL OIL
: Engine Capacity (kVa) 0.6
: Inside Diameter (m) 0.5
: Height (m) 9.425
: Upstream 0.65
: Downstream 1.2
: Number Of Traverse Point 8
: Coordinate S 07o 42' 06.75"
E 112o 41' 34.66"

Test Result
Threshold Limit
Parameter Unit Measurement Corrected Methods
Value
Concentration Concentration
Total Particulate mg/Nm³ 12.1 15.6 150 SNI 7117.17:2009
SO₂ (Sulfur Dioxide) mg/Nm³ 70.2 90.2 800 PO/ENV-EMS/02
Nitrogen Oxide (NOx) as NO₂ mg/Nm³ 691 889 1000 PO/ENV-EMS/03
CO (carbon Monoxide) mg/Nm³ 93.9 121 600 SNI 19-7117.10-2005
CO₂ (Carbon Dioxide) % 6.7 - - SNI 19-7117.10-2005
O₂ (Oxygen) % 14.8 - - SNI 19-7117.10-2005
Isokinetic % 102 90 - 110 Calculated
Linear Velocity m/s 48.9 - SNI 7117.14:2009
Flow Rate (ACT) m³/s 9.6 - SNI 7117.14:2009
Flow Rate (STD) m³/s 3.8 - SNI 7117.14:2009
Note : The result of parameter concentration were corrected 13% oxygen rate on condition normally air (25°C and 760 mmHg) and dry basis