You are on page 1of 4

edcon

UPS
MST Series 30-200KVA
The MST series is ideal for protecting data center, telecommunications systems, IT networks, and critical systems in
general, where the risks connected with poor energy supply can compromise the continuity of activities and services.
MST is available in 20-30-40-60-80-100-125-160-200 KVA models with three-phase input and output and ON LINE double
conversion technology in accordance with VFI-SS-111 classification (as set out in standard IEC EN 62040-3).

SWMB
Maintenance by-pass
MST is designed and built using state-of-the -art
switch
technology and components. It has a fully controlled
IGBT rectifier to minimize the impact on the grid.
PFC
CONVERTER INVERTER
Automatic
static by-pass It is controlled by a DSP (Digital Signal Processor) to
Line in Line out
provide maximum protection to the powered loads with
Input Stand-by
SWIN
Input
relay switch SWOUT
Output
no impact on downstream systems, and optimized
breaker breaker
Battery
charger energy savings.

SWBATT

Battery

Main features
Reliable, filtered, stabilized and regulated sine wave output (double on-line conversion technology VFI according
to EN50091-3 standard) with filters for atmospheric disturbance suppression
High reliability
IGBT Technology in rectifier and inverter, high frequency PWM, fully digital control with microprocessor, no break
static and manual transferring
Cleaned source
Power factor correction for unitary power factor and very low input THDI%
First class in efficiency
High operation efficiency up to 96.5% in normal mode, up to 99% in eco mode operation
Low noise levels
The high frequency PWM for rectifier and inverter allows very low audible noise
Flexibility
Can be set for several configurations as normal mode, smart mode, and standby off
High availability
Distributed parallel configuration of up to 8 units per redundant (N+1) or power parallel system. The UPS continue
to operate in parallel even if the connection cable is interrupted (Closed Loop).
Battery care system
Sealed VRLA, AGM, GEL or open-vented load acid batteries, Ni-Cd batteries
Temperature voltage compensation
Deep discharging controlled by microprocessor with load and main levels (sharing power mode suitable within
- 40% Vin)
High power availability
The output factor 0.9 providing up to 15% more active power than a traditional UPS and more load
expansiononnection cable is interrupted (Closed Loop).
edcon
UPS
MST Series 30-200KVA
Low management cost
The transformer less technology allows the lowest footprint in this category. The MST design allows front, top,
and sides access
Zero impact source
The superior technology of MST allows it be used where the site mains power supply is limited in capacity, or
has an on-site generator and/or loads that generate current harmonic problems. It is designed to have a
zero-impact on its upstream power supply (mains or generator).

Main source

SNMP HP

Router
Power
Messaging

Hub

RS232/USB

Server Local monitoring Remote monitoring


UPS

Cost Saving in Efficiency Communication and power management solutions


MST is the first class in cost saving due to efficiency MST provides solutions for remote monitoring and
up to 96.5% providing a 50% saving in energy usage power management. With optional SNMP card, UPS
per annum compared to traditional UPS products can be easily integrated into any medium and large-size
(92% standard). This exceptional performance can Data Center. UPS status can be monitored by ModBus
lead to a full initial investment recovery within TCP/IP; Profibus DP Network; BACnet/IP and GSM/
hree years. WIFT ready by means of customized RTG1 00 dongle.
Large LCD display
MST is equipped with a graphic display that provides information, measures, states and alarms regarding the UPS
in 9 different languages

Menu
1. LED for mains operation
2. LED for battery operation
3. LED for load on bypass
4. LED for standby/alarm
5. LED for replacing batteries
6. LED for ECO mode
7. Graphical Display
F1, F2, F3, F4 = Function Keys
Messages are available in the following languages: English, Italian,
French, German, Spanish, Polish, Turkish, Chinese and Russian.
edcon
UPS
MST Series 30-200KVA

MST30 MST40 MST60 MST80 MST100 MST125 MST160 MST200


MODELS
Bat Bat
INPUT
Nominal voltage 380-400-415 VAC 3-phase + N
Rated frequency 50/60 Hz
Voltage tolerance 400V ± 20% @ full load
Frequency 45-72 Hz
Power factor @full load 0,99
Harmonic current distor on ≤ 3% THDi ≤ 2.5% THDi
BYPASS
Nominal voltage 380-400-415 VAC 3-phase + N
Voltage tolerance (Ph-N) 180 - 264 VAC (selectable)
Nominal frequency 50/60Hz (selectable)
Frequency tolerance ±5% (selectable)
OUTPUT
Nominal power (kVA) 30 40 60 80 100 125 160 200
Ac ve power (kW) 27 36 54 72 90 112,5 160 200
Power factor 0,9 1
Nominal voltage 380-400-415 VAC 3-phase + N (selectable)
Sta c stability; Dynamic stability ±1%; ±3%
Crest factor 3:1
Voltage distor on ≤ 1% with linear load; ≤3% with non-linear load
Wave form sine wave
Frequency stability on ba ery 0,01%
Frequency 50/60 Hz (selectable)
Overload 125% for 60 minutes; 150% for 10 minutes
BATTERIES
Type Maintenance-free sealed lead acid; VRLA AGM/ GEL; NiCD; Supercaps; Li-on
Voltage (Vdc) 480
Recharges me 6 hours
ENVIRONMENTAL
Weight w/i ba ery (kg) 135 145 190 200 220 250 450 460
Dimension (WxDxH) (mm) 650x840
440x850x1320 500x850x1600 x1600 850x1050x1900
Communica ons 3 slots communica on interface/ USB/ RS232
Opera ng temperature 0 °C - 40 °C
Rela ve humidity 90% non-condensing
Colour Dark grey
Noise level at 1m (dBA) < 40 < 63 < 50
IP ra ng IP20
Efficiency up to 99%
Direc ves LV 2006/95/CE low voltage; EMC 2004/108/CE electromagne c compa bility;
Standards Standard: Safety IEC EN 62040-1; EMC IEC EN 62040-2; Classifica on in accordance with
IEC 62040-3 (VFI) VFI-SS-111
*) UPS specifica on and data may subject to change for improvement without prior no ce V.2020.07