DEEP SEA ELECTRONICS

DSE45xx Series
Configuration Suite Software Manual

Document Number 057-172


Author: Fady Atallah

DSE4500 Series PC Software Manual ISSUE 2


DSE4500 Series PC Software Manual

DEEP SEA ELECTRONICS PLC


Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND

Sales Tel: +44 (0) 1723 890099


Sales Fax: +44 (0) 1723 893303

E-mail : sales@Deepseaplc.com
Website : www.deepseaplc.com

DSE45xx Series Configuration Suite Software Manual

© Deep Sea Electronics Plc


All rights reserved. No part of this publication may be reproduced in any material form (including photocopying
or storing in any medium by electronic means or other) without the written permission of the copyright holder
except in accordance with the provisions of the Copyright, Designs and Patents Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be
addressed to Deep Sea Electronics Plc at the address above.

The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC.

Any reference to trademarked product names used within this publication is owned by their respective
companies.

Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.

Amendments List

Issue Comments Minimum Minimum


Module Configuration Suite
version Version required
required
1 Initial release V1.0.0 2012.27 v1.44.6
2 Added Instrumentation Suppression V1.7.76 2014.109 V1.221.3
Fuel Analogue Input updated
Added: Additional Output Functions
Added CT location for AMF modules
Added CAN Options
Added Over Speed Overshoot feature
Added Monthly Scheduler

Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The
numeral 1 has a top serif to avoid this confusion.

2
DSE4500 Series PC Software Manual

TABLE OF CONTENTS

1 BIBLIOGRAPHY .............................................................................................. 4
1.1 INSTALLATION INSTRUCTIONS ..................................................................................................... 4
1.2 MANUALS ......................................................................................................................................... 4
1.3 OTHER .............................................................................................................................................. 4
2 DESCRIPTION ................................................................................................. 4
3 INSTALLATION AND USING THE DSE CONFIGURATION SUITE ............... 4
4 EDIT CONFIG .................................................................................................. 5
4.1 SCREEN LAYOUT ............................................................................................................................ 5
4.2 MODULE ........................................................................................................................................... 6
4.2.1 MODULE OPTIONS................................................................................................................... 6
4.3 APPLICATION ................................................................................................................................... 8
4.4 INPUTS .............................................................................................................................................. 9
4.4.1 OIL PRESSURE......................................................................................................................... 9
4.4.2 COOLANT TEMPERATURE ...................................................................................................... 9
4.4.3 FUEL SENSOR ........................................................................................................................ 10
4.4.4 EDITING THE SENSOR CURVE ............................................................................................. 11
4.4.5 DIGITAL INPUTS ..................................................................................................................... 12
4.4.6 INPUT FUNCTIONS ................................................................................................................ 13
4.5 DIGITAL OUTPUTS......................................................................................................................... 15
4.5.1 OUTPUT SOURCES................................................................................................................ 16
4.6 TIMERS ........................................................................................................................................... 20
4.6.1 START TIMERS ....................................................................................................................... 20
4.6.2 LOAD / STOPPING TIMERS ................................................................................................... 21
4.6.3 MODULE TIMERS ................................................................................................................... 22
4.7 GENERATOR .................................................................................................................................. 23
4.7.1 GENERATOR OPTIONS ......................................................................................................... 23
4.7.2 GENERATOR VOLTAGE ALARMS ......................................................................................... 24
4.7.3 GENERATOR FREQUENCY ALARMS ................................................................................... 25
4.7.4 GENERATOR CURRENT ........................................................................................................ 26
4.8 MAINS ............................................................................................................................................. 27
4.8.1 MAINS OPTIONS..................................................................................................................... 27
4.8.2 MAINS ALARMS ...................................................................................................................... 28
4.9 ENGINE ........................................................................................................................................... 29
4.9.1 ENGINE PROTECTION ........................................................................................................... 29
4.9.2 CAN OPTIONS ........................................................................................................................ 30
4.9.3 ENGINE OPTIONS .................................................................................................................. 31
4.9.4 CRANK DISCONNECT ............................................................................................................ 32
4.9.5 SPEED ALARMS ..................................................................................................................... 33
4.9.6 PLANT BATTERY .................................................................................................................... 34
4.10 SCHEDULER ................................................................................................................................... 35
4.11 MAINTENANCE ALARM ................................................................................................................. 36
4.12 ALTERNATIVE CONFIGURATION ................................................................................................. 37
4.12.1 CONFIGURATION OPTIONS .................................................................................................. 37
4.12.2 ALTERNATIVE CONFIGURATIONS EDITOR ......................................................................... 38
5 SCADA ........................................................................................................... 39
5.1 MIMIC .............................................................................................................................................. 40
5.2 DIGITAL INPUTS ............................................................................................................................ 41
5.3 DIGITAL OUTPUTS......................................................................................................................... 41
5.4 MAINS ............................................................................................................................................. 42
5.5 GENERATOR .................................................................................................................................. 43
5.5.1 FREQUENCY, VOLTAGES AND CURRENT .......................................................................... 43
5.5.2 POWER ................................................................................................................................... 44
5.6 ENGINE ........................................................................................................................................... 45
5.7 FLEXIBLE SENSOR........................................................................................................................ 45
5.8 ALARMS.......................................................................................................................................... 45
5.9 STATUS........................................................................................................................................... 46
5.10 EVENT LOG .................................................................................................................................... 46
5.10.1 MAINTENANCE ....................................................................................................................... 47
5.10.2 HOURS RUN AND NUMBER OF STARTS ............................................................................. 47
5.10.3 HOURS RUN AND NUMBER OF STARTS ............................................................................. 48
5.10.4 DAY AND TIME........................................................................................................................ 49
5.10.5 MODULE PIN ........................................................................................................................... 50
6 ALARM TYPES .............................................................................................. 51
3
Bibliography

1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained from the
DSE website www.deepseaplc.com:

1.1 INSTALLATION INSTRUCTIONS


DSE PART DESCRIPTION
053-145 4500 installation instructions sheet

1.2 MANUALS

DSE PART DESCRIPTION


057-151 DSE Configuration Suite PC Software Installation & Operation Manual
057-004 Electronic Engines and DSE wiring
057-171 DSE45xx Operator Manual

1.3 OTHER
The following third party documents are also referred to:

ISBN DESCRIPTION
1-55937-879-4 IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device Function Numbers
and Contact Designations. Published by Institute of Electrical and Electronics Engineers
Inc

2 DESCRIPTION
The DSE4500 Series configuration suite allows the 4500 family of modules to be connected to a PC via
USB ‘A –USB B’ cable. Once connected the various operating parameters within the module can be viewed or
edited as required by the engineer. This software allows easy controlled access to these values.

This manual details the configuration of the DSE45xx series controllers

The configuration suite should only be used by competent, qualified personnel, as changes to the operation of
the module may have safety implications on the panel / generating set to which it is fitted. Access to critical
operational sequences and settings for use by qualified engineers, may be barred by a security code set by
the generator provider.
The information contained in this manual should be read in conjunction with the information contained in the
appropriate module documentation. This manual only details which settings are available and how they may
be used.
A separate manual deals with the operation of the individual module (See section entitled Bibliography
elsewhere in this document).

3 INSTALLATION AND USING THE DSE CONFIGURATION SUITE


SOFTWARE

For information in regards to instating and using the DSE Configuration Suite Software please refer to DSE
publication: 057-151 DSE Configuration Suite PC Software Installation & Operation Manual which can
be found on our website: www.deepseaplc.com

4
Edit Config

4 EDIT CONFIG
This menu allows module configuration, to change the function of Inputs, Outputs and LED’s, system timers
and level settings to suit a particular application.

4.1 SCREEN LAYOUT

Move to the
The type of Previous or Next
configuration configuration page
file being edited

The coloured
shading shows
the currently Close this
selected page. configuration file

Click + or – to
show or hide
the sub settings
within each
sections.

Click to return
Step forward or to this page at
backward through any time
previously viewed pages

Click to select
the subsection
to view / edit

5
Edit Config

4.2 MODULE
The module page is subdivided into smaller sections.
Select the required section with the mouse.

This section allows the user to change the options related to the module itself.

4.2.1 MODULE OPTIONS

Tick to hide the


parameter on the
module display

Miscellaneous Options
Lamp Test At Power  = Feature disabled
Up  = All the LEDs on the module’s fascia illuminate when the DC power is applied
as a ‘lamp test’ feature.
Protected Start Mode If enabled, the start button must be pressed twice to confirm manual start request
Power Save Mode  =Normal operation
Enable  = Module goes into power save (low current) mode after 1m of inactivity in STOP
mode. Press any button to ‘wake’ the module.
Deep Sleep Mode (Available only if Power Save Mode is Enabled)
Enable When enabled, the module will go into a deeper sleep state with maximum power
saving
Power Up in Mode Select the mode that the module enters when DC power is applied.
Available modes to select from: Auto, Manual, Stop mode
Display SPN Strings  =The module displays CAN messages in manufacturer numerical code.
(CAN only)  = The module displays CAN messages in ENGLISH text alongside the
manufacturer numerical code.
Event log in Hours Run  = The engine run hours is added to the recorded event in the event log

More descriptions of parameters overleaf...

6
Edit Config

Miscellaneous Options
Enable Fast Loading  = Normal Operation, the safety on timer is observed in full. This feature is useful
if the module is to be used with some small engines where pre-mature termination
of the delay timer can lead to overspeed alarms on start up.
 = The module will terminate the safety on timer once all monitored parameters
have reached their normal settings. This feature is useful if the module is to be used
as a standby controller as it allows the generator to start and go on load in the
shortest possible time.

NOTE: - Enabling Fast Loading is only recommended where steps have


been taken to ensure rapid start up of the engine is possible. (For example
when fitted with engine heaters, electronic governors etc.)

Maintenance PIN If enabled, maintenance alarm reset through the front panel editor is PIN protected
Protected Enable
Enable Cool Down in Changes the way the module reacts to the Stop button.
Stop Mode  = if the engine is running on load and the stop button is pressed, the module will
open the breaker and directly shutdown the engine.
 = if the engine is running and the breaker is closed, the module will open the
breaker, wait for the cool down timer to expire, then shutdown the engine.

NOTE: - If the engine is running with the breaker open, the module will
always shutdown the engine directly even if this option is enabled.
All Warnings are  = Normal Operation, the warnings and pre-alarms will automatically reset once
Latched the triggering condition has cleared.
 = Warning and pre-alarms latch when triggered. Resetting the alarm is performed
by an input configured for Alarm Reset or pressing the Stop/Reset button (once the
triggering condition has been cleared).

7
Edit Config

4.3 APPLICATION

Allows selection of the Engine type


being used (ie Conventional Diesel
Engine, Gas Engine or Electronic
Engine)

Instructs electronic engines to run


at their ‘alternative speed’
(supported CAN engines only)

Configuration of the CAN data fail


alarm, providing protection against
the failure of the engine ECU data
link.

8
Edit Config

4.4 INPUTS
The inputs page is subdivided into smaller sections.
Select the required section with the mouse.

4.4.1 OIL PRESSURE


If a CAN Engine File is selected – Most engines give oil pressure from CAN link. In these cases, Input A is
fixed as Digital Input. Configuration is the same as for Digital Inputs, detailed elsewhere in this document.
Where the CAN engine does not support oil pressure over CAN link, Analogue input A is selectable as either
digital input, or as analogue oil pressure sensor.

When enabled the


Select the analogue input is used for
input type the measurement instead of
using the value measured
by the engine ECU

Click to edit the


‘sensor curve’.
See section
entitled Editing
the sensor curve.

Enable or disable
the alarms.
4.4.2 COOLANT TEMPERATURE
If a CAN Engine File is selected – Engines give temperature measurements from CAN link. Input A is fixed
as Digital Input. Configuration is the same as for Digital Inputs, detailed elsewhere in this document.

When enabled the


analogue input is used for
the measurement instead of
Select the using the value measured
sensor type by the engine ECU

Click to edit the


‘sensor curve’.
See section
entitled Editing
the sensor curve.

9
Edit Config

4.4.3 FUEL SENSOR


The fuel analogue input can be used as Fuel Level Sensor or Flexible Sensor.

Click to edit the


‘sensor curve’. See
Select the
section entitled
sender type
Editing the sensor
curve.
Select the
Input Type Click to enable or
disable the alarms.
The relevant values
below will appear
greyed out if the
alarm is disabled.

Click and drag


to alter the
time delay

Type the value or


click the up and
down arrows to
change the settings

Select the type of


alarm required.
For details of these,
see the section
entitled Alarm
Types elsewhere in
this document.

10
Edit Config

4.4.4 EDITING THE SENSOR CURVE


While the configuration suite holds sensor specification for the most commonly used resistive sensors,
occasionally it is required that the 4500 Series module be connected to a sensor not listed by the
configuration suite. To aid this process, a sensor editor has been provided.

In this example, the closest match to the sensor


in use is the VDO 10-180Ω fuel level sensor.

Click to edit the


‘sensor curve’.

Click and drag the


points on the
graphs to change
the settings
Click Interpolate then select
two points as prompted to
draw a straight line between
them. Or use the mouse
to select the graph
point, then enter the
value in the box or
click up/down to Click CANCEL to
change the value ignore and lose any
changes you have
made

Click OK to accept
the changes and
return to the
Click SAVE AS, you are prompted to name configuration editor
your curve....

Hint: Deleting, renaming or


editing custom sensor curves
that have been added is
performed in the main menu,
select Tools | Curve Manager.
.
Click OK to save the curve.

Any saved curves become selectable in the


Input Type selection list.

11
Edit Config

4.4.5 DIGITAL INPUTS


The digital inputs page is subdivided into smaller sections.
Select the required section with the mouse.

Input function. See section


entitled Input functions for
details of all available functions

As this example shows a


predefined function,
these parameters are
greyed out as they are
not applicable

Configures when
the input is active:
Never, always, Example of a user configured
active from input
starting, active
from the end of the
safety timer Close or open to activate

Select the type of


alarm required.
For details of these,
Click and drag to change see the section
the setting. This is used to entitled Alarm
give a delay on acceptance Types elsewhere in
of the input. Useful for liquid this document.
level switches or to mask
short term operations of the
external switch device.

12
Edit Config

4.4.6 INPUT FUNCTIONS


Where a digital input is NOT configured as “user configured”, a selection can be made from a list of
predefined functions. The selections are as follows:

Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor
devices and software programs. Where the DSE input functions can be represented by IEEE 37.2, the
function number is listed below.

= Only applicable to DSE4520 AMF Modules


Function Description
Alarm Mute This input is used to silence the audible alarm from an external source,
such as a remote mute switch.
Alarm Reset This input is used to reset any latched alarms from a remote location. It
is also used to clear any latched warnings which may have occurred (if
configured) without having to stop the generator.
Alternative Configuration These inputs are used to instruct the module to follow one of the
alternative configuration settings instead of the main configuration
settings.
Auto Restore Inhibit In the event of a remote start/mains failure, the generator will be
IEEE 37.2 - 3 checking or instructed to start and take load. On removal of the remote start
interlocking relay signal/mains return the module will continue to run the generator on
load until the Auto Restore Inhibit input is removed. This input allows
the controller to be fitted as part of a system where the restoration to
mains is controlled remotely or by an automated system.
Auto start Inhibit This input is used to provide an over-ride function to prevent the
IEEE 37.2 - 3 checking or controller from starting the generator in the event of a remote
interlocking relay start/mains out of limits condition occurring. If this input is active and a
remote start signal/mains failure occurs the module will not give a start
command to the generator. If this input signal is then removed, the
controller will operate as if a remote start/mains failure has occurred,
starting and loading the generator. This function can be used to give an
‘AND’ function so that a generator will only be called to start if the
mains fails and another condition exists which requires the generator to
run. If the ‘Auto start Inhibit’ signal becomes active once more it will be
ignored until the module has returned the mains supply on load and
shutdown.
This input does not prevent starting of the engine in MANUAL or TEST
modes.
Auxiliary Mains Fail The module will monitor the incoming single or three phase supply for
Over voltage, Under Voltage, Over Frequency or Under frequency. It
may be required to monitor a different mains supply or some aspect of
the incoming mains not monitored by the controller. If the devices
providing this additional monitoring are connected to operate this input,
the controller will operate as if the incoming mains supply has fallen
outside of limits, the generator will be instructed to start and take the
load. Removal of the input signal will cause the module to act if the
mains has returned to within limits providing that the mains sensing also
indicates that the mains is within limits.
Coolant Temperature Switch This input is used to give a Coolant Temperature High shutdown from a
digital normally open or closed switch. It allows coolant temperature
protection using the switch and the analogue input can be used in
parallel to give protection or configured to be used for indication only.
Emergency Stop Provides an immediate engine hot shutdown, used in emergency
situations
External Panel Lock Locks the module into the current operating mode.
Generator Load Inhibit This input is used to prevent the module from loading the generator. If
IEEE 37.2 - 52 AC circuit the generator is already on load, activating this input will cause the
breaker module to unload the generator. Removing the input will allow the
generator to be loaded again.

NOTE: -This input only operates to control the generator-


switching device if the module load switching logic is attempting
to load the generator. It will not control the generator-switching
device when the mains supply is on load.

13
Edit Config

Function Description
Lamp Test This input is used to provide a test facility for the front panel indicators
fitted to the module. When the input is activated all LED’s should
illuminate.
Low Fuel Level Switch Used to give a digital input function to provide a low fuel level alarm
Mains Load Inhibit This input is used to prevent the module from loading the mains supply.
IEEE 37.2 - 3 checking or If the mains supply is already on load activating this input will cause the
interlocking relay module to unload the mains supply. Removing the input will allow the
mains to be loaded again.

NOTE: -This input only operates to control the mains


switching device if the module load switching logic is attempting
to load the mains. It will not control the mains switching device
when the generator is on load.
Maintenance Reset Alarm Air Provides an external digital input to reset the maintenance alarm
Maintenance Reset Alarm Fuel Provides an external digital input to reset the maintenance alarm
Maintenance Reset Alarm Oil Provides an external digital input to reset the maintenance alarm
Oil Pressure Switch A digital normally open or closed oil pressure switch gives this input. It
allows oil pressure protection using the switch and the analogue input to
be used in parallel to give protection or to be used for oil pressure
indication only.
Remote Start off load If this input is active, operation will be similar to the ‘Remote Start on
load’ function except that the generator will not be instructed to take the
load. This function can be used where an engine only run is required
e.g. for exercise.
Remote Start on load (Only applicable to Digital Input A)
When in auto mode, the module will perform the start sequence and
transfer load to the generator.
In Manual mode, the load will be transferred to the generator if the
engine is already running, however in manual mode, this input will not
generate start/stop requests of the engine.
Simulate Auto Button
NOTE: - If a call to start is present when AUTO MODE is
entered, the starting sequence will begin. Call to Start can come
from a number of sources depending upon module type and
configuration and includes (but is not limited to) : Remote start
input present, Mains failure, Scheduled run, Auxiliary mains failure
input present, Telemetry start signal from remote locations.
This input mimic’s the operation of the ‘Auto’ button and is used to
provide a remotely located Auto mode push button.
Simulate Mains available This function is provided to override the module’s internal monitoring
function. If this input is active, the module will not respond to the state of
the incoming AC mains supply.
Simulate Start Button This input mimic’s the operation of the ‘Start’ button and is used to
provide a remotely located start push button.
Simulate Stop Button This input mimic’s the operation of the ‘Stop’ button and is used to
provide a remotely located stop/reset push button.
Smoke limit This input instructs the module to give a run at idle speed command to
IEEE 37.2 – 18 accelerating or the engine either via an output configured to smoke limit or by data
decelerating device commands when used with supported electronic engines.
Transfer to generator/Open This input is used to transfer the load to the generator when running in
Mains MANUAL MODE
IEEE 37.2 - 52 AC circuit
breaker
Transfer to Mains/ Open This input is used to transfer the load to the mains supply (AMF
Generator module) when running in MANUAL MODE or provide the ‘Open
IEEE 37.2-52 AC circuit breaker Generator’ signal in a non AMF Module.)

14
Edit Config

4.5 DIGITAL OUTPUTS

These are greyed out as


they are fixed, not
Select what the adjustable unless a CAN
output is to be engine has been
Select if the relay is to
used to control selected energise or de-energise
upon activation of the
source

These labels
match the
typical wiring
diagram

15
Edit Config

4.5.1 OUTPUT SOURCES


The list of output sources available for configuration of the module relay.

Under the scope of IEEE 37.2, function numbers can also be used to represent functions in microprocessor
devices and software programs. Where the DSE output functions can be represented by IEEE 37.2, the
function number is listed below.

The outputs are in alphabetical


order with the parameter first. For
instance for overspeed output, it’s
listed as Engine Overspeed.

= Only available on DSE4520 AMF Modules


Output source Activates… Is not active….
Not Used The output will not change state (Unused)
Air Filter Maintenance Indicates that the air filter maintenance alarm is due
Air Flap Relay Normally used to control an air flap, this Inactive when the set has come to
output becomes active upon an rest
Emergency
Stop or Over-speed situation.
Audible Alarm This output indicates that the internal Inactive if the internal sounder is not
IEEE 37.2 – 74 alarm relay sounder is operating to allow it to feed operating.
an external sounder. Operation of the
Mute pushbutton will reset this output
once activated.
Battery High Voltage This output indicates that a Battery Inactive when battery voltage is not
IEEE 37.2 – 59DC overvoltage Over voltage alarm has occurred. High
relay

Battery Low Voltage This output indicates that a Battery Inactive when battery voltage is not
IEEE 37.2 – 27DC undervoltage Under Voltage alarm has occurred. Low
relay

CAN ECU Data Fail Becomes active when no CAN data is Inactive when:
received from the ECU after the safety • CAN data is being received
delay timer has expired • The set is at rest
• During the starting sequence
before the safety delay timer
has expired
CAN ECU WARNING Becomes active when a ‘Yellow lamp’ – Warning alarm is signalled by the
CAN ECU
CAN ECU SHUTDOWN Becomes active when a ‘Red lamp’ – Shutdown alarm is signalled by the CAN
ECU
CAN ECU Power Used to switch an external relay to power the CAN ECU. Exact timing of this
output is dependent upon the type of the engine ECU
CAN ECU Stop Active when the DSE controller is requesting that the CAN ECU stops the
engine.
Charge alternator Active when the charge alternator alarm is active
warning/shutdown

Close Gen Output Used to control the load switching Inactive whenever the generator is
IEEE 37.2 – 52 ac circuit breaker device. Whenever the 4500 module not required to be on load
selects the generator to be on load this
control source will be active.
Close Gen Output Pulse Used to control the load switching device. Whenever the 4500 module selects
IEEE 37.2 – 52 ac circuit breaker the generator to be on load this control source will be active for the duration of
the Breaker Close Pulse timer, after which it will become inactive again.
Close Mains Output Used to control the load switching device. The output is inactive
IEEE 37.2 – 52 ac circuit breaker Whenever the 4500 module selects the whenever the mains is not
mains to be on load this control source will required to be on load
be active.
Close Mains Output Pulse Used to control the load switching device. Whenever the 4500 module selects
IEEE 37.2 – 52 ac circuit breaker the mains to be on load this control source will be active for the duration of the
Breaker Close Pulse timer, after which it will become inactive again.

16
Edit Config

Output source Activates… Is not active….


Combined Mains Failure Active when the mains supply is out of limits OR the input for Auxiliary Mains
Failure is active
Common Alarm Active when one or more alarms (of any The output is inactive when no
type) are active alarms are present
Common Electrical Trip Active when one or more Electrical Trip The output is inactive when no
alarms are active shutdown alarms are present
Common Shutdown Active when one or more Shutdown The output is inactive when no
alarms are active shutdown alarms are present
Common Warning Active when one or more Warning The output is inactive when no
alarms are active warning alarms are present
Cooling Down Active when the Cooling timer is in The output is inactive at all other
progress times
Delayed Load Output 1, 2, 3 & 4 Provide delayed outputs for controlling load switching devices
Digital Input A, B, C & D Active when the relevant digital input is active
Digital Input E – Oil Pressure Active when a low oil pressure alarm is triggered
Sensor
Digital Input F – Temperature Active when a high coolant temperature alarm is triggered
Sensor
Digital Input G – Flexible Sensor Active when a flexible sensor alarm is triggered
Display Heater Fitted and ON (Available in RTH modules only) Activates when the ambient temperature falls
below -10 °C (14 °F) and deactivates when the ambient temperature rises
above -5 °C (23 °F).
Emergency Stop Active when the Emergency Stop alarm is active.
Energise to Stop Normally used to control an Energise to Becomes inactive a configurable
Stop solenoid, this output becomes amount of time after the set has
active when the controller wants the set stopped. This is the ETS hold time.
to stop running.
Fail to Start Becomes active if the set is not seen to be running after the configurable
IEEE 37.2 - 48 Incomplete number of start
Sequence attempts
Relay
Fail to Stop Becomes active when the number of start attempts has been exceeded.
IEEE 37.2 - 48 Incomplete
Sequence
Relay
Flexible Sensor Low/High – Active when the relevant flexible sensor alarm is active
Warning/Shutdown
Fuel Filter Maintenance Indicates that the fuel filter maintenance alarm is due
Fuel Level High Alarm/Pre-Alarm Active when the relevant High Fuel Level alarm is active
Fuel Level Low Alarm/Pre-Alarm Active when the relevant Low Fuel Level alarm is active
Fuel Relay Becomes active when the controller Becomes inactive whenever the
requires the governor/fuel system to be set should be stopped, including
active. between crank attempts, upon
controlled stops and upon fault
shutdowns.
Gas Choke On Becomes active during starting for the Inactive at all other times
duration of the Gas Choke timer.
Normally used to choke a gas engine.
Gas Ignition Becomes active during starting. Becomes inactive a configurable
amount of time after the fuel relay
becomes inactive. This is the Gas
ignition off timer.
Generator Available Becomes active when the generator is Inactive when
available to take load. • Loading voltage and loading
frequency have not been
reached
• After electrical trip alarm
• During the starting sequence
before the end of the warming
timer.
Generator High Voltage Alarm Active when the generator voltage exceeds the trip level.
Generator Low Voltage Alarm Active when the generator voltage falls below the trip level during normal
running.
Generator Over Frequency Activates when the generator frequency exceeds the overshoot setting during
Overshoot Alarm the overshoot time.

17
Edit Config

Output source Activates… Is not active….


High Coolant Temperature Active when the high coolant temperature shutdown alarm is active
Shutdown
kW Overload Alarm (Available in current sensing modules only) Activates when the kW produced
by the generator exceeds the kW Overload Alarm trip setting
Low Fuel Level Active when the digital input configured to Low Fuel Level is active.
IEEE 37.2 – 71 level switch
Low Oil Pressure Shutdown Active when the Low Oil Pressure Shutdown alarm is activate
Mains Low/High Frequency Active when the relevant Mains Frequency alarm is active
Mains Low/High Voltage Active when the relevant Mains Voltage alarm is active
Oil Filter Maintenance Indicates that the oil filter maintenance alarm is due
Oil Pressure Sender Open Circuit Active when the Oil Pressure Sensor is detected as being open circuit.
Open Gen Output Used to control the load switching Inactive whenever the generator is
IEEE 37.2 – 52 ac circuit breaker device. Whenever the 4500 module required to be on load
selects the generator to be off load
this control source will be active.
Open Gen Output Pulse Used to control the load switching device. Whenever the 4500 module selects
IEEE 37.2 – 52 ac circuit breaker the generator to be off load this control source will be active for the duration of
the Breaker Open Pulse timer, after which it will become inactive again.
Open Mains Output Used to control the load switching The output is inactive whenever the
IEEE 37.2 – 52 ac circuit breaker device. Whenever the 4500 module mains is required to be on load
selects the mains to be off load this
control source will be active.
Open Mains Output Pulse Used to control the load switching device. Whenever the 4500 module selects
IEEE 37.2 – 52 ac circuit breaker the mains to be off load this control source will be active for the duration of the
Breaker Open Pulse timer, after which it will become inactive again.
Over Current Delayed Alarm Activates when an overcurrent condition exceeds the Overcurrent Alarm Trip
Setting for the configured delay time
Over Current Immediate Warning Activates when an overcurrent condition exceeds the Overcurrent Alarm Trip
IEEE 37.2 – 50 instantaneous Setting
overcurrent relay
Over Frequency Shutdown Active when the generator frequency exceeds the High Frequency Shutdown
IEEE 37.2 - 81 frequency relay setting
Over Speed Shutdown Active if the engine speed exceeds the Over Speed Shutdown setting
IEEE 37.2 – 12 over speed device
Overspeed Overshoot Alarm Activates when the engine speed exceeds the overshoot setting during the
overshoot time
Preheat during preheat timer Becomes active when the preheat Inactive when :
timer begins. • The set is stopped
Normally used to control the engine • The preheat timer has expired
preheat glow-plugs.
Preheat until end of crank Becomes active when the preheat Inactive when :
timer begins. • The set is stopped
Normally used to control the engine • The set has reached crank
preheat glow-plugs. disconnect conditions
Preheat until end of safety timer Becomes active when the preheat Inactive when :
timer begins. • The set is stopped
Normally used to control the engine • The set has reached the end of
preheat glow-plugs. the safety delay timer
Preheat until end of warming timer Becomes active when the preheat Inactive when :
timer begins. • The set is stopped
Normally used to control the engine • The set has reached the end of
preheat glow-plugs. the warming timer
Smoke Limiting Becomes active when the controller Becomes inactive when the controller
requests that the engine runs at idle requests that the engine runs at rated
speed. speed.
As an output, this can be used to give
a signal to the Idle input of an engine
speed governor (if available)
Start Relay Active when the controller requires the cranking of the engine.
IEEE 37.2 – 54 turning gear
engaging device

18
Edit Config

Output source Activates… Is not active….


System in Auto Mode Active when Auto mode is selected
System in Manual Mode Active when Manual mode is selected
System in Stop Mode Active when Stop mode is selected
Temperature Sensor Open Circuit Active when the Temperature Sensor is detected as being open circuit.
Under Frequency Shutdown Active when the generator frequency falls below the low frequency Shutdown
setting
Under Speed Shutdown Active when the engine speed falls below the under speed Shutdown setting
Waiting for Manual Restore Becomes active when the generator is on load and the mains supply is healthy
but an input configured to Manual Restore is active.
This can be used to signal to an operator that action is required before the set
can transfer back to the mains supply.

19
Edit Config

4.6 TIMERS
Many timers are associated with alarms. Where this occurs, the timer for the alarm is located on the same
page as the alarm setting. Timers not associated with an alarm are located on the timers page.
The timers page is subdivided into smaller sections. Select the required section with the mouse.

4.6.1 START TIMERS


Click and drag to change the setting.
Timers increment in steps of 1 second up to
one minute, then in steps of 30 seconds up
to 30minutes, then in steps of 30 minutes
thereafter (where allowed by the limits of the
timer).

= Only available on DSE4520 AMF Modules


Timer Description
Mains Transient Delay Used to give a delay between sensing mains failure and acting upon it. This is used to
prevent dropouts of the mains breaker and operation of the system due to mains
supply transient conditions.
Start delay Used to give a delay before starting in AUTO mode. This timer is activated upon a
remote start signal being applied, or upon a start due to mains failure, scheduled run
or any other automatic start.
Typically this timer is applied to prevent starting upon fleeting remote start signals or
short term mains failures.
Pre-heat Give a ‘pre start’ time during which the Preheat output will become active (if
configured)
Cranking time The length of each crank attempt
Crank rest time The time between multiple crank attempts.
Smoke limit The amount of time that the engine will be requested to run at idle speed upon
starting. This is typically used to limit emissions at startup.
Smoke limit off This should be set to a little longer than the amout of time that the set takes to run up
to rated speed after removal of the command to run at idle speed. If this time is too
short, the set could be stopped due to underspeed failure. If the time is too long,
underspeed protection is disabled until the Smoke limit time off time has expired.
Safety on delay The amount of time at startup that the controller will ignore oil pressure, engine speed,
alternator voltage and other delayed alarms. This is used to allow the engine to run up
to speed before protections are activated.
Warming up time The amount of time that the set will run BEFORE being allowed to take load. This is
used to warm the engine to prevent excessive wear.

20
Edit Config

4.6.2 LOAD / STOPPING TIMERS Click and drag to change the


setting.
Timers increment in steps of
1second up to one minute, then in
steps of 30seconds up to
30minutes, then in steps of
30minutes thereafter (where
allowed by the limits of the timer).

Respective digital outputs, if


configured, will become energised
after a load delay timer expires.

= Only available on DSE4520 AMF Modules


Timer Description
Transfer Time The time between one load switch opening and the other closing. Used during
transfer to and from the generator.
Breaker close pulse The amount of time that Breaker Close Pulse signals will be present when the
request to close a breaker is given.
Breaker Trip pulse The amount of time that Breaker Open Pulse signals will be present when the
request to open a breaker is given.
Load Delay Timers Delay Load Output 1, 2, 3 & 4
Determine the time delay before energising the configured “Delayed Load” outputs.
These outputs are used to control additional load breakers to provide five stage
loading. After the generator load switch is closed, the remaining four outputs are
closed after the configurable time delay. This allows for additional loads to be
energised in sequence, minimising the size of step loading of the generator
Return delay A delay, used in auto mode only, that allows for short term removal of the request
to stop the set before action is taken. This is usually used to ensure the set remains
on load before accepting that the start request has been removed.
Cooling time The amount of time that the set will be made to run OFF LOAD before being
stopped. This is to allow the set to cool down and is particularly important for
engines with turbo chargers.
Cooling Time at Idle The amount of time the generator runs at an idle speed after the Cooling Time has
expired
ETS Solenoid hold The amount of time the Energise to stop solenoid will be kept energised after the
engine has come to rest. This is used to ensure the set has fully stopped before
removal of the stop solenoid control signal.
Fail to stop delay If the set is called to stop and is still running after the fail to stop delay, a Fail to
Stop alarm is generated.
Generator transient Used to delay the generator under/over volts/frequency alarms. Typically this is
delay used to prevent spurious shutdown alarms caused by large changes in load levels.

21
Edit Config

4.6.3 MODULE TIMERS

Timer Description
Power Save Mode If the module is left unattended in STOP mode for the duration of the Power Save
Delay Mode Delay it will enter low power consumption mode (Power Save Mode).
Deep Sleep Mode When the module is in Power Save Mode, if left unattended for the duration of the
Delay Deep Sleep Mode Delay timer it will enter a lower power consumption mode (Deep
Sleep Mode)
Page Delay If the module is left unattended for the duration of the Page Delay Timer it will revert
to show
the Status page.

22
Edit Config

4.7 GENERATOR
The generator page is subdivided into smaller sections.
Select the required section with the mouse.

4.7.1 GENERATOR OPTIONS


Click to enable or
disable alternator
functions.

Parameter Description
Alternator fitted  = There is no alternator in the system, it is an engine only application
 = An alternator is fitted to the engine, it is a generator application.
AC System Allows a number of AC systems to be catered for.

Selecting the AC system shows the connections required for that particular system,
along with the relevant connection numbers on the controller.

23
Edit Config

4.7.2 GENERATOR VOLTAGE ALARMS


Click to enable or
disable the alarms.
The relevant values
below will appear
greyed out if the
alarm is disabled.

Click and drag to change


the setting.

Type the
value or click
the up and
down arrows
to change the
settings

Alarm IEEE designation


Generator Under voltage IEEE 37.2 - 27AC Undervoltage relay
Loading Voltage Determines the alternator voltage at which the generator becomes available and
ready to take load
Generator Over voltage IEEE 37.2 - 59AC Overvoltage relay

24
Edit Config

4.7.3 GENERATOR FREQUENCY ALARMS


Click to enable or
disable the alarms.
The relevant values
below will appear
greyed out if the
alarm is disabled.

Type the value


or click the up
and down Click and drag to change
arrows to the setting.
change the
settings

Overfrequency Shutdown
can only be disabled if
another method of speed
protection is available (ie
CAN or Magnetic Pickup).
Hence the checkbox is
greyed out

Alarm IEEE designation


Generator Under Frequency IEEE 37.2 -81 Frequency relay
Loading Voltage Determines the alternator frequency at which the generator becomes available
and ready to take load
Generator Over Frequency IEEE 37.2 -81 Frequency relay

25
Edit Config

4.7.4 GENERATOR CURRENT


This is the CT primary value as fitted
to the set (CT secondary must be
5A). The full load rating is the 100%
rating of the set in Amps.

Select CT location, Generator


or Load side. Avalibale for
AMF modules, allows Mains
Current measurement.

Click to enable or disable the


option. The relevant values
below will appear greyed out if
the alarm is disabled.

Type the value or click the up


and down arrows to change
the Settings.

Click to enable or disable the


option. The relevant values
below will appear greyed out
if the Overload Protection is
disabled.

Setting Description
CT Primary Primary rating of the Current Transformers
Full Load Rating The maximum current per phase
CT Location Gen : The CTs are located in the feed from the generator, to provide generator
(Available in AMF current and power only.
modules only) Load: The CTs are in the feed to the load, to display load current and power in
addition, when mains is available.
Overcurrent Alarm Trip The current percentage of the Full Load Rating at which the Alarm Action is
activated after the Delay.
Generator kW rating The Generator kW rating must be set in order for the Generator Power functions to
be correctly utilised.
Overload Protection  = Overload Protection function is disabled.
 = The module will monitor the kW load level and provide an alarm function if the
level exceeds the Trip setting for the configured amount of time in the Delay setting.

Action
Electrical Trip: The generator is taken off load and the set stopped after the Cooling
timer. Any output or LCD display set to kW Overload Protection is energised.
Indication: No alarm is generated; however any output or LCD display set to kW
Overload Protection is energised. The kW load must fall below the Return level in
order to cancel the output source.
Shutdown: The generator is taken off load and the set stopped immediately.
Warning: An alarm is generated but the set continues to run. Any output or LCD
display set to kW Overload Protection is energised. The kW load must fall below
the Return level in order to cancel the output source.

26
Edit Config

4.8 MAINS

= Only available on DSE4520 AMF Modules

The mains page is subdivided into smaller sections.


Select the required section with the mouse.

If three phase loads are


present, it is usually desirable
4.8.1 MAINS OPTIONS to set this parameter to  to
enable Immediate Mains
Dropout.

This is ‘read only’ for


information purposes.
The AC system is
configured in the
‘Generator Options’
page.

Timer Description
Mains failure  = The module will ignore the status of the mains supply.
detection  = The module will monitor the mains supply and use this status for automatically starting
and stopping the set in auto mode.
Immediate  = Upon mains failure, the mains load switch will be kept closed until the generator is up
Mains Dropout to speed and volts.
 = Upon mains failure, the mains load switch will be opened immediately, subject to the
setting of the mains transient timer.
AC System These settings are used to detail the type of AC system to which the module is connected:
3 phase 4 wire, 1 phase 2 wire, 2 phase 3 wire – L1-L2, 2 phase 3 wire – L1-L3, 3 phase 3
wire, 3 phase 4 wire delta

This list is not exhaustive. DSE reserve the right to add to this list as part of our policy of
continual development

27
Edit Config

4.8.2 MAINS ALARMS Click to enable or


disable the alarms.
The relevant values
below will appear
greyed out if the
alarm is disabled.

Type the
value or click
the up and
down arrows
to change the
settings Click and drag to
change the setting.

Alarm IEEE designation


Mains Under voltage IEEE 37.2 - 27AC Undervoltage relay

Mains Over voltage IEEE 37.2 - 59AC Overvoltage relay

Mains Under Frequency IEEE 37.2 -81 Frequency relay

Mains Over Frequency IEEE 37.2 -81 Frequency relay

28
Edit Config

4.9 ENGINE
The engine page is subdivided into smaller sections.
Select the required section with the mouse.

4.9.1 ENGINE PROTECTION

Enable or disable
the alarms. The
Click and drag to
relevant values
change the settings
below will appear
greyed out if the
alarm is disabled.

Type the value or


click the up and
down arrows to
change the settings

29
Edit Config

4.9.2 CAN OPTIONS

These options are greyed out if Conventional Engine is selected from the Application.

CAN Options Description


Module To Measure Oil Pressure  = Oil Pressure is provided by the ECU
 = The DSE module measures the Oil Pressure
Module To Measure Coolant  = Coolant Temperature is provided by the ECU
Temperature  = The DSE module measures the Coolant Temperature
Module To Record Engine Hours  = Engine Run Time is provided by the ECU
 = The DSE module counts the Engine Run Time
Module To Use Engine Speed  = Engine Speed is provided by the ECU
 = The DSE module measures the Engine Speed
Module To Use Charge Alt Voltage  = Engine Run Time is provided by the ECU
 = The DSE module counts the Engine Run Time
Disable ECM Speed  = Engine Speed is controlled by the ECU, this disables the command
from the DSE module to run at nominal speed
 = The DSE module commands the ECU to run the engine at the
configured speed

30
Edit Config

4.9.3 ENGINE OPTIONS


This item is not adjustable
here, it’s read only. To change
this item, visit the module
menu.

Controls the amount


of time that the Gas
Choke output will be
active during the
starting sequence.

Controls the amount of time


between energising the Gas
Ignition and energising the Fuel
output. Used in the starting
sequence to purge old gas from
the engine.

For these timers to


have any meaning,
outputs are required
for Gas Choke, Gas Controls the amount of time between de-energising
Ignition and Fuel. the Fuel output and de-energising the Gas Ignition
output. Used in the stopping sequence to purge
unburnt gas from the engine before it is stopped.

Raises the overspeed and over frequency shutdown settings by


the configured percentage & duration at the start of the Safety on
Delay Time. It is used to prevent overspeed and over frequency
shutdowns caused by slow acting speed governing systems at
start up.

31
Edit Config

4.9.4 CRANK DISCONNECT


Crank disconnect settings are used to detect when the set fires during the starting sequence.
As the set is cranked, the first parameter that passes it’s crank disconnect setting will result in the cessation of
the cranking signal.

Having more than one crank disconnect source allows for a much faster crank disconnect response leading to
less wear on the engine and starter components, and provides added safety in case one source is lost, by a
blown or tripped fuse for example.

If check oil pressure prior to


starting is enabled, the cranking
will not be allowed if the oil
pressure is not seen as being
low. This used as a double
check that the engine is stopped
before the starter is engaged

Click and drag to change


the setting.

Type the value


or click the up
and down
arrows to
change the
settings

32
Edit Config

4.9.5 SPEED ALARMS

Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.

Type the value


or click the up
and down
arrows to
change the
settings
Overspeed shutdown
cannot be disabled.

Click and drag to change the


setting.

33
Edit Config

4.9.6 PLANT BATTERY

Click and drag to change


the setting.
Click to enable or
disable the option.
The relevant
values below will Type the value or
appear greyed out click the up and
if the alarm is down arrows to
disabled. change the settings

Select to enable autostart upon


the battery voltage falling to the
threshold level.
The engine will start and run for
the specified Engine Run Time.

Alarm IEEE designation


Plant Battery Undervolts IEEE 37.2 -27 DC Undervoltage relay
Plant Battery Overvolts IEEE 37.2 -59 DC Overvoltage relay
Start on Low Battery  = Start on Low Battery is disabled.
 = Select to enable autostart upon the battery voltage falling to the threshold
level. The engine will start and run for the specified Engine Run Time. This will
occur only if the module is in AUTO mode
Charge Alternator Alarm If the voltage measured at the charge alternator output drops below the
configured value the respective alarm will be triggered.
Start Delay Start delay timer for the Start on Low Battery function.

34
Edit Config

4.10 SCHEDULER
The scheduler is used to automatically start the set at on a configured day and time and run for the set
duration.
The generator is made to run on load or off load depending upon the configuration :

Function Description
Enabled  = Scheduled runs are disabled
 = Enables the Scheduler
Scheduled run is On Load  = The module will run the generator on schedule with the breaker open
 = The module will run the generator on schedule and will close the breaker
Scheduled Period Determines the repeat interval for the scheduled run.
Options available are: Weekly, Monthly
Week Determines the week of the month when the Scheduled Period is configured to
Monthly
Options available are: First, Second, Third, Fourth, Last
Day Specifies the day of week, on which the scheduled run should take place
Start Time Determines at what time of day the scheduled run should start
Duration Determines the time duration for the scheduled run
Clear Resets the values for the Day, Start Time and Duration to defaults

35
Edit Config

4.11 MAINTENANCE ALARM

Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.

Maintenance Alarm will occur


when the engine has run for the
specified number of hours.

There are three ways to reset the maintenance alarm:


1) Activate a digital input configured to “Maintenance Reset Alarm”.
2) Use the SCADA | Maintenance | Maintenance Alarm section of this PC Software.
3) Through the Front Panel Editor of the module

36
Edit Config

4.12 ALTERNATIVE CONFIGURATION


An Alternative Configuration is provided to allow the system designer to cater for different AC requirements
utilising the same generator system. Typically this feature is used by Rental Set Manufacturers where the set
is capable of being operated at (for instance) 120V 50Hz and 240V 50Hz using a selector switch.

The Alternative Configuration can be selected using either:

• Configuration Suite Software (Selection for ‘Default Configuration’)


• DSE4500 Series Front Panel Editor
• Via external signal to DSE4500 Series module input configured to “Alternative Configuration” select.

4.12.1 CONFIGURATION OPTIONS

Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.

Select the ‘default’


configuration that will be used
when there is no instruction
to use an ‘alternative
configuration’.

37
Edit Config

4.12.2 ALTERNATIVE CONFIGURATIONS EDITOR


The Alternative Configurations Editor allows for editing of the parameters that will be changed when an
Alternative Configuration is selected.

Alternative configuration options contain a subset of the main configuration. The adjustable parameters are
not discussed here as they are identical to the main configuration options :

Configuration menus for the


Alternative Configuration.
For information about the
configuration items within this section,
you are referred to their description in
the ‘main’ configuration.

38
SCADA

5 SCADA
SCADA stands for Supervisory Control And Data Acquisition and is provided both as a service tool and also
as a means of monitoring / controlling the generator set.
As a service tool, the SCADA pages are to check the operation of the controller’s inputs and outputs as well
as checking the generators operating parameters.

Click to open the connection to the module. If


no module is connected, the SCADA will open
to show the screens for the type of module
currently open in the configuration.

When connection is made…


Click to close the
connection to the
module

The Module’s
firmware revision
number

The SCADA page is subdivided into smaller sections.


Select the required section with the mouse.

39
SCADA

5.1 MIMIC
This screen provides a mimic of the control module and allows the operator to change the control mode of the
module.

Hint : Buttons may not operate if this


Click the mimic buttons to has been locked out by the Access
control the module remotely Permissions security feature of the
Configuration Suite Software.
Refer to your system supplier for
details.

40
SCADA

5.2 DIGITAL INPUTS

State of the input


(open or closed to
battery negative)

5.3 DIGITAL OUTPUTS

State of the
output
(open or closed)

Shows if the output channel is


active or not.

41
SCADA

5.4 MAINS

DSE4520 AMF MODULES ONLY

Shows the modules measurements of the mains supply (4520 only).

42
SCADA

5.5 GENERATOR
5.5.1 FREQUENCY, VOLTAGES AND CURRENT
Shows the modules measurements of the generator supply.

43
SCADA

5.5.2 POWER
Shows the modules measurements of the generator supply power.

44
SCADA

5.6 ENGINE
Shows the modules measurements of the engine parameters.

Hint : Bad Data appears with a CAN engine file is


selected when the CAN ECU is not communicating
with the 4500 controller. This could mean a fault with
the CAN link, or simply that the ECU is currently not
powered.

5.7 FLEXIBLE SENSOR


Shows the measurement of the Flexible Sensor (If configured)

5.8 ALARMS
Shows any present alarm conditions.

45
SCADA

5.9 STATUS
Shows the module’s current status.

5.10 EVENT LOG


Shows the contents of the module’s event log.

46
SCADA

5.10.1 MAINTENANCE
The Maintenance section is subdivided into smaller sections.
Select the required section with the mouse.

5.10.2 HOURS RUN AND NUMBER OF STARTS

Reset the maintenance


alarm based upon the
module’s configuration.

47
SCADA

5.10.3 HOURS RUN AND NUMBER OF STARTS


This section allows the Hours Run and Number of Starts to be customised on the controller.
Typically, this is used when fitting a new controller to an older generator so that the controller display matches
the amount of work previously done by the system.
Type the value
or click the up
and down
arrows to
change the
settings

Click to perform the


adjustment in the module.
Note that this is not visible on
the module itself. It is
included in the PC SCADA
for diagnostic purposes.

48
SCADA

5.10.4 DAY AND TIME


This section allows the day and time to be set and changed on the controller.

Display of the
module’s
current date
and time

Type the new


date / time or
click the up and
down arrows to
change the
settings

Click Set to
adjust the
module to the
selected
date/time.

Click Set to adjust


the module to the
date/time that
your PC is set to.

49
SCADA

5.10.5 MODULE PIN

NOTE : If the PIN is lost of forgotten, it will not be possible to access the module!

Allows a PIN (Personal Identification Number) to be set in the controller. This PIN must be entered to either
access the front panel configuration editor or before a configuration file can be sent to the controller from the
PC software.

Enter the desired PIN


number and reconfirm.

Click to set the


PIN number in
the module.

50
Alarm Types

6 ALARM TYPES
The protection included with the DSE control modules provides increasing levels of notification, depending
upon the severity of the situation:

Alarm type Description


Indication No audible alarm or common warning signal occurs.
Indication alarms are only used to illuminate indicators or to activate outputs.
Warning Audible alarm and common alarm signal is generated. The set continues to
run.
Warning alarms are used to draw the operator’s attention to a minor issue or
to a problem that may escalate to an Electrical Trip or Shutdown Alarm if left
untreated.
Electrical Trip Audible alarm and common alarm signal is generated. The set is taken off
load and the cooling timer begins, after which the set is stopped.
Electrical Trip alarms are series issues that require the set to be taken off
load. As the name implies, this is often electrical faults that occur ‘after’ the
load breaker. The set is allowed to cool before stopping.
Shutdown Audible alarm and common alarm signal is generated. The set is taken off
load and immediately stopped.
Shutdown alarms are serious issues that demand immediate stopping of the
generator. For instance Emergency Stop or Overspeed alarms require
immediate shutdown.

51
This Page Intentionally Blank.

52