You are on page 1of 3

www.repuestosgruposelectrogenos.

es

AUTOMATIC VOLTAGE REGULATOR (AVR)


AVR7
Overview Technical specifications
AVR7 is a half-wave AVR with a IGBT SENSING INPUT
control and a DC link that performs the Voltage 110-300Vac
excitation control of brushless AC Frequency 50-60Hz nominal
alternators.
POWER INPUT
The DC link allows the system to store a Voltage 171-300Vac
power reseve and use it to overcome a Frequency 50-60Hz nominal
shock load with better response.
POWER OUTPUT
The power input and the sensing input are Voltage 110VDC @ 220Vac
separated, allowing a auxiliary winding 7A continuous current
excitation. 12A transitional
Resistance 15 ohms o more
AVR7 can sense directly from the output
main stator winding, allowing a closed loop REGULATION
control with an accuracy of + / -1%. AVR7 +/- 1.0%
allows the possibility of single phase or
three-phase sensing. RESPONSE SYSTEM
20ms response AVR
This AVR allows a potentiometer remote 92% Time 50ms Iexc
connection to perform the output voltage 90% Vout time 180ms
adjustment.
EXTERNAL VOLTAGE ADJUSTMENT
It has an analog voltage input for the +/- 10% with an external potentiometer 22K
variation of the output voltage in the range of +/- 20% with an analog signal of + /-9V
+ / -10%.
AVR POWER DISSIPATION
AVR7 has a low frequency protection. The 15W @ 100 º C
low frequency threshold is adjustable by a
potentiometer. STARTING VOLTAGE
AVR7 has an operating frequency selector 3 Vac
interchangeable to 50 or 60Hz.
LOW FREQUENCY PROTECCTION
AVR7 has an overexcitation protection too, 100% to 78% (for 50Hz and 60Hz)
which can be configured to cut the excitation
when reach 4, 5 or 7A FREQUENCY SELECTOR
50Hz or 60Hz
Output voltage stability can be adjusted by
the stability potentiometer.
www.repuestosgruposelectrogenos.es

DISTRIBUTION OF CONTROLS AND CONNECTORS

SUMMARY OF CONTROLS AVR


CONTROLS FUNCTION OPERATION
VOLTS Adjust the output voltage Clockwise increases the output voltage
V / F FREQ Adjust the threshold of detection of low frequency protection Clockwise increases the frequency of detection
V / F GAIN Adjust the gain of low frequency protection Clockwise increases the gain
BRIDGE 50/60Hz Setting the operating frequency With bridge 50Hz. Without bridge 60Hz
STAB Adjusting the stability Clockwise increases the output voltage
OVEREXCITEMENT Adjust the trigger level of overexcitement Position 1 maximum current level
SELECTOR Position 2 middle current level
Position 3 minimum current level

CONNECTIONS
Wiring Diagram Trifasic Sensing
CONNECTOR FUNCTIONALITY
3 Power Input Middle Phase Sensing Complete Phase Sensing
4 Power and sensing reference
F+ Positive excitation field
F- Negative excitation field
E1 Sensing input E1 (**)
E2 Sensing input E2 (**)
E3 Sensing input E3 (**)
POT+ Input external potentiometer (*)
POT- Input external potentiometer (*)
A+ Analog signal input
A- Analog signal input

(**) For single-phase sensing bridge E1-E2-E3


(*) If the potentiometer input is not used must be bridged
www.repuestosgruposelectrogenos.es

DIMENSIONS

*All the dimensions are in mm

You might also like