68 ※ Dev Type AC
address

instance
point Name
number

26625 1 On/Off (Setting)


26626 2 On/Off (Status)
26627 3 Lock (Setting)
26628 4 Lock (Status)
26629 5 Filter Sign
26630 6 Filter Sign reset
26631 7 Operation Mode (Setting)
26632 8 Operation Mode (Status)
26633 9 Swing (Setting)
26634 10 Swing (Status)
26635 11 Fan Speed (Setting)
26636 12 Fan Speed (Status)
26637 13 Set Room Temperature
26638 14 Room Temperature
26639 15 Alarm
26640 16 Error Code
26643 19 Set Temperature (Status)
26644 20 Accumulated Power Distribution (Status)
26651 27 Set Upper Temperature (Setting)
26652 28 Set Lower Temperature (Setting)
26653 29 Set Upper Tempaerature (Status)
26654 30 Set Lower Temperature (Status)
26655 31 Mode Lock (Setting)
26656 32 Mode Lock (Status)
26657 33 Fan Lock (Setting)
26658 34 Fan Lock (Status)
26659 35 Occupancy (Setting)
26660 36 Occupancy (Status)
26661 37 2Set Cooling Set Temperature (Setting)
26662 38 2Set Cooling Set Temperature (Status)
26663 39 2Set Heating Set Temperature (Setting)
26664 40 2Set Heating Set Temperature (Status)
26665 41 2Set Cooling Upper Temperature (Setting)
26666 42 2Set Cooling Upper Temperature (Status)
26667 43 2Set Heating Upper Temperature (Setting)
26668 44 2Set Heating Upper Temperature (Status)
26669 45 2Set Cooling Lower Temperature (Setting)
26670 46 2Set Cooling Lower Temperature (Status)
26671 47 2Set Heating Lower Temperature (Setting)
26672 48 2Set Heating Lower Temperature (Status)
26673 49 Thermo Status (Status)
26674 50 Accumulated Gas Distribution (Status)
26675 51 Dust Sensor Available (Status)
26676 52 Air Cleaning Opereration (Setting)
26677 53 Air Cleaning Opereration (Status)
26678 54 Fine Dust (Status)
26679 55 Ultra Fine Dust (Status)
26680 56 Super Ultra Fine Dust (Status)
26681 57 Humidity (Status)
26682 58 Comfort Cooling Available (Status)
26683 59 Comfort Cooling Opereration (Setting)
26684 60 Comfort Cooling Opereration (Status)
26685 61 Comfort Cooling Step (Setting)
26686 62 Comfort Cooling Step (Status)
26687 63 Human Detection Available (Status)
26688 64 Human Detection Opereration (Setting)
26689 65 Human Detection Opereration (Status)
26690 66 Human Detection Wind (Setting)
26691 67 Human Detection Wind (Status)
26692 68 Human Detection Time (Setting)
26693 69 Human Detection Time (Status)
26694 70 Hotel Checkin (Setting)
26695 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_68 BO Stop(0) Start(1)
StartStopStatus_68 BI Stop(0) Start(1)
LockCommand_68 BO Permit(0) Prohibit(1)
LockStatus_68 BI Permit(0) Prohibit(1)
FilterSign_68 BI Off(0) On(1)
FilterSignReset_68 BV - Reset(1)
AirConModeCommand_68 MO Cool(1)
AirConModeStatus_68 MI Cool(1)
SwingCommand_68 BO Stop(0) Run(1)
SwingStatus_68 BI Stop(0) Run(1)
FanSpeedCommand_68 MO Low(1)
FanSpeedStatus_68 MI Low(1)
SetRoomTemp_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_68 AI ℃
Alarm_68 BI Normal(0) Abnormal(1)
MalfunctionCode_68 AI Refer to the
SetTempStatus_68 AI ℃
Accumulated power(100 Watt)_68 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_68 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_68 AI ℃
TempRangeLowerLimitStatus_68 AI ℃
ModeLockCommand_68 BO Permit(0) Prohibit(1)
ModeLockStatus_68 BI Permit(0) Prohibit(1)
FanLockCommand_68 BO Permit(0) Prohibit(1)
FanLockStatus_68 BI Permit(0) Prohibit(1)
OccupancyCommand_68 BO Unoccupied(0) Occupied(1)
OccupancyStatus_68 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_68 BI Off(0) On(1)
AccumulatedGas(100 Watt)_68 AI Wattage values (Unit : 100Watt)
DustSensorAvail_68 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_68 BO Stop(0) Run(1)
AirCleaningOperStatus_68 BI Stop(0) Run(1)
FineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_68 AI %
ComfortCoolingAvail_68 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_68 BO Stop(0) Run(1)
ComfortCoolingOperStatus_68 BI Stop(0) Run(1)
ComfortCoolingStepCommand_68 AV 1~3 step
ComfortCoolingStepStatus_68 AI 1~3 step
HumanDetectionAvail_68 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_68 MO Off(1)
HumanDetectionOperStatus_68 MI Off(1)
HumanDetectionWindCommand_68 MO Off(1)
HumanDetectionWindStatus_68 MI Off(1)
HumanDetectionTimeCommand_68 MO 5min(1)
HumanDetectionTimeStatus_68 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4e ※ Dev Type AC
address

instance
point Name
number

19969 1 On/Off (Setting)


19970 2 On/Off (Status)
19971 3 Lock (Setting)
19972 4 Lock (Status)
19973 5 Filter Sign
19974 6 Filter Sign reset
19975 7 Operation Mode (Setting)
19976 8 Operation Mode (Status)
19977 9 Swing (Setting)
19978 10 Swing (Status)
19979 11 Fan Speed (Setting)
19980 12 Fan Speed (Status)
19981 13 Set Room Temperature
19982 14 Room Temperature
19983 15 Alarm
19984 16 Error Code
19987 19 Set Temperature (Status)
19988 20 Accumulated Power Distribution (Status)
19995 27 Set Upper Temperature (Setting)
19996 28 Set Lower Temperature (Setting)
19997 29 Set Upper Tempaerature (Status)
19998 30 Set Lower Temperature (Status)
19999 31 Mode Lock (Setting)
20000 32 Mode Lock (Status)
20001 33 Fan Lock (Setting)
20002 34 Fan Lock (Status)
20003 35 Occupancy (Setting)
20004 36 Occupancy (Status)
20005 37 2Set Cooling Set Temperature (Setting)
20006 38 2Set Cooling Set Temperature (Status)
20007 39 2Set Heating Set Temperature (Setting)
20008 40 2Set Heating Set Temperature (Status)
20009 41 2Set Cooling Upper Temperature (Setting)
20010 42 2Set Cooling Upper Temperature (Status)
20011 43 2Set Heating Upper Temperature (Setting)
20012 44 2Set Heating Upper Temperature (Status)
20013 45 2Set Cooling Lower Temperature (Setting)
20014 46 2Set Cooling Lower Temperature (Status)
20015 47 2Set Heating Lower Temperature (Setting)
20016 48 2Set Heating Lower Temperature (Status)
20017 49 Thermo Status (Status)
20018 50 Accumulated Gas Distribution (Status)
20019 51 Dust Sensor Available (Status)
20020 52 Air Cleaning Opereration (Setting)
20021 53 Air Cleaning Opereration (Status)
20022 54 Fine Dust (Status)
20023 55 Ultra Fine Dust (Status)
20024 56 Super Ultra Fine Dust (Status)
20025 57 Humidity (Status)
20026 58 Comfort Cooling Available (Status)
20027 59 Comfort Cooling Opereration (Setting)
20028 60 Comfort Cooling Opereration (Status)
20029 61 Comfort Cooling Step (Setting)
20030 62 Comfort Cooling Step (Status)
20031 63 Human Detection Available (Status)
20032 64 Human Detection Opereration (Setting)
20033 65 Human Detection Opereration (Status)
20034 66 Human Detection Wind (Setting)
20035 67 Human Detection Wind (Status)
20036 68 Human Detection Time (Setting)
20037 69 Human Detection Time (Status)
20038 70 Hotel Checkin (Setting)
20039 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4e BO Stop(0) Start(1)
StartStopStatus_4e BI Stop(0) Start(1)
LockCommand_4e BO Permit(0) Prohibit(1)
LockStatus_4e BI Permit(0) Prohibit(1)
FilterSign_4e BI Off(0) On(1)
FilterSignReset_4e BV - Reset(1)
AirConModeCommand_4e MO Cool(1)
AirConModeStatus_4e MI Cool(1)
SwingCommand_4e BO Stop(0) Run(1)
SwingStatus_4e BI Stop(0) Run(1)
FanSpeedCommand_4e MO Low(1)
FanSpeedStatus_4e MI Low(1)
SetRoomTemp_4e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4e AI ℃
Alarm_4e BI Normal(0) Abnormal(1)
MalfunctionCode_4e AI Refer to the
SetTempStatus_4e AI ℃
Accumulated power(100 Watt)_4e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4e AI ℃
TempRangeLowerLimitStatus_4e AI ℃
ModeLockCommand_4e BO Permit(0) Prohibit(1)
ModeLockStatus_4e BI Permit(0) Prohibit(1)
FanLockCommand_4e BO Permit(0) Prohibit(1)
FanLockStatus_4e BI Permit(0) Prohibit(1)
OccupancyCommand_4e BO Unoccupied(0) Occupied(1)
OccupancyStatus_4e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4e BI Off(0) On(1)
AccumulatedGas(100 Watt)_4e AI Wattage values (Unit : 100Watt)
DustSensorAvail_4e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4e BO Stop(0) Run(1)
AirCleaningOperStatus_4e BI Stop(0) Run(1)
FineDustStatus_4e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4e AI %
ComfortCoolingAvail_4e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4e BO Stop(0) Run(1)
ComfortCoolingOperStatus_4e BI Stop(0) Run(1)
ComfortCoolingStepCommand_4e AV 1~3 step
ComfortCoolingStepStatus_4e AI 1~3 step
HumanDetectionAvail_4e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4e MO Off(1)
HumanDetectionOperStatus_4e MI Off(1)
HumanDetectionWindCommand_4e MO Off(1)
HumanDetectionWindStatus_4e MI Off(1)
HumanDetectionTimeCommand_4e MO 5min(1)
HumanDetectionTimeStatus_4e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1 ※ Dev Type AC
address

instance
point Name
number

257 1 On/Off (Setting)


258 2 On/Off (Status)
259 3 Lock (Setting)
260 4 Lock (Status)
261 5 Filter Sign
262 6 Filter Sign reset
263 7 Operation Mode (Setting)
264 8 Operation Mode (Status)
265 9 Swing (Setting)
266 10 Swing (Status)
267 11 Fan Speed (Setting)
268 12 Fan Speed (Status)
269 13 Set Room Temperature
270 14 Room Temperature
271 15 Alarm
272 16 Error Code
275 19 Set Temperature (Status)
276 20 Accumulated Power Distribution (Status)
283 27 Set Upper Temperature (Setting)
284 28 Set Lower Temperature (Setting)
285 29 Set Upper Tempaerature (Status)
286 30 Set Lower Temperature (Status)
287 31 Mode Lock (Setting)
288 32 Mode Lock (Status)
289 33 Fan Lock (Setting)
290 34 Fan Lock (Status)
291 35 Occupancy (Setting)
292 36 Occupancy (Status)
293 37 2Set Cooling Set Temperature (Setting)
294 38 2Set Cooling Set Temperature (Status)
295 39 2Set Heating Set Temperature (Setting)
296 40 2Set Heating Set Temperature (Status)
297 41 2Set Cooling Upper Temperature (Setting)
298 42 2Set Cooling Upper Temperature (Status)
299 43 2Set Heating Upper Temperature (Setting)
300 44 2Set Heating Upper Temperature (Status)
301 45 2Set Cooling Lower Temperature (Setting)
302 46 2Set Cooling Lower Temperature (Status)
303 47 2Set Heating Lower Temperature (Setting)
304 48 2Set Heating Lower Temperature (Status)
305 49 Thermo Status (Status)
306 50 Accumulated Gas Distribution (Status)
307 51 Dust Sensor Available (Status)
308 52 Air Cleaning Opereration (Setting)
309 53 Air Cleaning Opereration (Status)
310 54 Fine Dust (Status)
311 55 Ultra Fine Dust (Status)
312 56 Super Ultra Fine Dust (Status)
313 57 Humidity (Status)
314 58 Comfort Cooling Available (Status)
315 59 Comfort Cooling Opereration (Setting)
316 60 Comfort Cooling Opereration (Status)
317 61 Comfort Cooling Step (Setting)
318 62 Comfort Cooling Step (Status)
319 63 Human Detection Available (Status)
320 64 Human Detection Opereration (Setting)
321 65 Human Detection Opereration (Status)
322 66 Human Detection Wind (Setting)
323 67 Human Detection Wind (Status)
324 68 Human Detection Time (Setting)
325 69 Human Detection Time (Status)
326 70 Hotel Checkin (Setting)
327 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1 BO Stop(0) Start(1)
StartStopStatus_1 BI Stop(0) Start(1)
LockCommand_1 BO Permit(0) Prohibit(1)
LockStatus_1 BI Permit(0) Prohibit(1)
FilterSign_1 BI Off(0) On(1)
FilterSignReset_1 BV - Reset(1)
AirConModeCommand_1 MO Cool(1)
AirConModeStatus_1 MI Cool(1)
SwingCommand_1 BO Stop(0) Run(1)
SwingStatus_1 BI Stop(0) Run(1)
FanSpeedCommand_1 MO Low(1)
FanSpeedStatus_1 MI Low(1)
SetRoomTemp_1 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1 AI ℃
Alarm_1 BI Normal(0) Abnormal(1)
MalfunctionCode_1 AI Refer to the
SetTempStatus_1 AI ℃
Accumulated power(100 Watt)_1 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1 AI ℃
TempRangeLowerLimitStatus_1 AI ℃
ModeLockCommand_1 BO Permit(0) Prohibit(1)
ModeLockStatus_1 BI Permit(0) Prohibit(1)
FanLockCommand_1 BO Permit(0) Prohibit(1)
FanLockStatus_1 BI Permit(0) Prohibit(1)
OccupancyCommand_1 BO Unoccupied(0) Occupied(1)
OccupancyStatus_1 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1 BI Off(0) On(1)
AccumulatedGas(100 Watt)_1 AI Wattage values (Unit : 100Watt)
DustSensorAvail_1 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1 BO Stop(0) Run(1)
AirCleaningOperStatus_1 BI Stop(0) Run(1)
FineDustStatus_1 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1 AI %
ComfortCoolingAvail_1 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1 BO Stop(0) Run(1)
ComfortCoolingOperStatus_1 BI Stop(0) Run(1)
ComfortCoolingStepCommand_1 AV 1~3 step
ComfortCoolingStepStatus_1 AI 1~3 step
HumanDetectionAvail_1 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1 MO Off(1)
HumanDetectionOperStatus_1 MI Off(1)
HumanDetectionWindCommand_1 MO Off(1)
HumanDetectionWindStatus_1 MI Off(1)
HumanDetectionTimeCommand_1 MO 5min(1)
HumanDetectionTimeStatus_1 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2 ※ Dev Type AC
address

instance
point Name
number

513 1 On/Off (Setting)


514 2 On/Off (Status)
515 3 Lock (Setting)
516 4 Lock (Status)
517 5 Filter Sign
518 6 Filter Sign reset
519 7 Operation Mode (Setting)
520 8 Operation Mode (Status)
521 9 Swing (Setting)
522 10 Swing (Status)
523 11 Fan Speed (Setting)
524 12 Fan Speed (Status)
525 13 Set Room Temperature
526 14 Room Temperature
527 15 Alarm
528 16 Error Code
531 19 Set Temperature (Status)
532 20 Accumulated Power Distribution (Status)
539 27 Set Upper Temperature (Setting)
540 28 Set Lower Temperature (Setting)
541 29 Set Upper Tempaerature (Status)
542 30 Set Lower Temperature (Status)
543 31 Mode Lock (Setting)
544 32 Mode Lock (Status)
545 33 Fan Lock (Setting)
546 34 Fan Lock (Status)
547 35 Occupancy (Setting)
548 36 Occupancy (Status)
549 37 2Set Cooling Set Temperature (Setting)
550 38 2Set Cooling Set Temperature (Status)
551 39 2Set Heating Set Temperature (Setting)
552 40 2Set Heating Set Temperature (Status)
553 41 2Set Cooling Upper Temperature (Setting)
554 42 2Set Cooling Upper Temperature (Status)
555 43 2Set Heating Upper Temperature (Setting)
556 44 2Set Heating Upper Temperature (Status)
557 45 2Set Cooling Lower Temperature (Setting)
558 46 2Set Cooling Lower Temperature (Status)
559 47 2Set Heating Lower Temperature (Setting)
560 48 2Set Heating Lower Temperature (Status)
561 49 Thermo Status (Status)
562 50 Accumulated Gas Distribution (Status)
563 51 Dust Sensor Available (Status)
564 52 Air Cleaning Opereration (Setting)
565 53 Air Cleaning Opereration (Status)
566 54 Fine Dust (Status)
567 55 Ultra Fine Dust (Status)
568 56 Super Ultra Fine Dust (Status)
569 57 Humidity (Status)
570 58 Comfort Cooling Available (Status)
571 59 Comfort Cooling Opereration (Setting)
572 60 Comfort Cooling Opereration (Status)
573 61 Comfort Cooling Step (Setting)
574 62 Comfort Cooling Step (Status)
575 63 Human Detection Available (Status)
576 64 Human Detection Opereration (Setting)
577 65 Human Detection Opereration (Status)
578 66 Human Detection Wind (Setting)
579 67 Human Detection Wind (Status)
580 68 Human Detection Time (Setting)
581 69 Human Detection Time (Status)
582 70 Hotel Checkin (Setting)
583 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2 BO Stop(0) Start(1)
StartStopStatus_2 BI Stop(0) Start(1)
LockCommand_2 BO Permit(0) Prohibit(1)
LockStatus_2 BI Permit(0) Prohibit(1)
FilterSign_2 BI Off(0) On(1)
FilterSignReset_2 BV - Reset(1)
AirConModeCommand_2 MO Cool(1)
AirConModeStatus_2 MI Cool(1)
SwingCommand_2 BO Stop(0) Run(1)
SwingStatus_2 BI Stop(0) Run(1)
FanSpeedCommand_2 MO Low(1)
FanSpeedStatus_2 MI Low(1)
SetRoomTemp_2 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2 AI ℃
Alarm_2 BI Normal(0) Abnormal(1)
MalfunctionCode_2 AI Refer to the
SetTempStatus_2 AI ℃
Accumulated power(100 Watt)_2 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2 AI ℃
TempRangeLowerLimitStatus_2 AI ℃
ModeLockCommand_2 BO Permit(0) Prohibit(1)
ModeLockStatus_2 BI Permit(0) Prohibit(1)
FanLockCommand_2 BO Permit(0) Prohibit(1)
FanLockStatus_2 BI Permit(0) Prohibit(1)
OccupancyCommand_2 BO Unoccupied(0) Occupied(1)
OccupancyStatus_2 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2 BI Off(0) On(1)
AccumulatedGas(100 Watt)_2 AI Wattage values (Unit : 100Watt)
DustSensorAvail_2 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2 BO Stop(0) Run(1)
AirCleaningOperStatus_2 BI Stop(0) Run(1)
FineDustStatus_2 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2 AI %
ComfortCoolingAvail_2 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2 BO Stop(0) Run(1)
ComfortCoolingOperStatus_2 BI Stop(0) Run(1)
ComfortCoolingStepCommand_2 AV 1~3 step
ComfortCoolingStepStatus_2 AI 1~3 step
HumanDetectionAvail_2 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2 MO Off(1)
HumanDetectionOperStatus_2 MI Off(1)
HumanDetectionWindCommand_2 MO Off(1)
HumanDetectionWindStatus_2 MI Off(1)
HumanDetectionTimeCommand_2 MO 5min(1)
HumanDetectionTimeStatus_2 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3 ※ Dev Type AC
address

instance
point Name
number

769 1 On/Off (Setting)


770 2 On/Off (Status)
771 3 Lock (Setting)
772 4 Lock (Status)
773 5 Filter Sign
774 6 Filter Sign reset
775 7 Operation Mode (Setting)
776 8 Operation Mode (Status)
777 9 Swing (Setting)
778 10 Swing (Status)
779 11 Fan Speed (Setting)
780 12 Fan Speed (Status)
781 13 Set Room Temperature
782 14 Room Temperature
783 15 Alarm
784 16 Error Code
787 19 Set Temperature (Status)
788 20 Accumulated Power Distribution (Status)
795 27 Set Upper Temperature (Setting)
796 28 Set Lower Temperature (Setting)
797 29 Set Upper Tempaerature (Status)
798 30 Set Lower Temperature (Status)
799 31 Mode Lock (Setting)
800 32 Mode Lock (Status)
801 33 Fan Lock (Setting)
802 34 Fan Lock (Status)
803 35 Occupancy (Setting)
804 36 Occupancy (Status)
805 37 2Set Cooling Set Temperature (Setting)
806 38 2Set Cooling Set Temperature (Status)
807 39 2Set Heating Set Temperature (Setting)
808 40 2Set Heating Set Temperature (Status)
809 41 2Set Cooling Upper Temperature (Setting)
810 42 2Set Cooling Upper Temperature (Status)
811 43 2Set Heating Upper Temperature (Setting)
812 44 2Set Heating Upper Temperature (Status)
813 45 2Set Cooling Lower Temperature (Setting)
814 46 2Set Cooling Lower Temperature (Status)
815 47 2Set Heating Lower Temperature (Setting)
816 48 2Set Heating Lower Temperature (Status)
817 49 Thermo Status (Status)
818 50 Accumulated Gas Distribution (Status)
819 51 Dust Sensor Available (Status)
820 52 Air Cleaning Opereration (Setting)
821 53 Air Cleaning Opereration (Status)
822 54 Fine Dust (Status)
823 55 Ultra Fine Dust (Status)
824 56 Super Ultra Fine Dust (Status)
825 57 Humidity (Status)
826 58 Comfort Cooling Available (Status)
827 59 Comfort Cooling Opereration (Setting)
828 60 Comfort Cooling Opereration (Status)
829 61 Comfort Cooling Step (Setting)
830 62 Comfort Cooling Step (Status)
831 63 Human Detection Available (Status)
832 64 Human Detection Opereration (Setting)
833 65 Human Detection Opereration (Status)
834 66 Human Detection Wind (Setting)
835 67 Human Detection Wind (Status)
836 68 Human Detection Time (Setting)
837 69 Human Detection Time (Status)
838 70 Hotel Checkin (Setting)
839 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3 BO Stop(0) Start(1)
StartStopStatus_3 BI Stop(0) Start(1)
LockCommand_3 BO Permit(0) Prohibit(1)
LockStatus_3 BI Permit(0) Prohibit(1)
FilterSign_3 BI Off(0) On(1)
FilterSignReset_3 BV - Reset(1)
AirConModeCommand_3 MO Cool(1)
AirConModeStatus_3 MI Cool(1)
SwingCommand_3 BO Stop(0) Run(1)
SwingStatus_3 BI Stop(0) Run(1)
FanSpeedCommand_3 MO Low(1)
FanSpeedStatus_3 MI Low(1)
SetRoomTemp_3 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3 AI ℃
Alarm_3 BI Normal(0) Abnormal(1)
MalfunctionCode_3 AI Refer to the
SetTempStatus_3 AI ℃
Accumulated power(100 Watt)_3 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3 AI ℃
TempRangeLowerLimitStatus_3 AI ℃
ModeLockCommand_3 BO Permit(0) Prohibit(1)
ModeLockStatus_3 BI Permit(0) Prohibit(1)
FanLockCommand_3 BO Permit(0) Prohibit(1)
FanLockStatus_3 BI Permit(0) Prohibit(1)
OccupancyCommand_3 BO Unoccupied(0) Occupied(1)
OccupancyStatus_3 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3 BI Off(0) On(1)
AccumulatedGas(100 Watt)_3 AI Wattage values (Unit : 100Watt)
DustSensorAvail_3 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3 BO Stop(0) Run(1)
AirCleaningOperStatus_3 BI Stop(0) Run(1)
FineDustStatus_3 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3 AI %
ComfortCoolingAvail_3 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3 BO Stop(0) Run(1)
ComfortCoolingOperStatus_3 BI Stop(0) Run(1)
ComfortCoolingStepCommand_3 AV 1~3 step
ComfortCoolingStepStatus_3 AI 1~3 step
HumanDetectionAvail_3 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3 MO Off(1)
HumanDetectionOperStatus_3 MI Off(1)
HumanDetectionWindCommand_3 MO Off(1)
HumanDetectionWindStatus_3 MI Off(1)
HumanDetectionTimeCommand_3 MO 5min(1)
HumanDetectionTimeStatus_3 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4 ※ Dev Type AC
address

instance
point Name
number

1025 1 On/Off (Setting)


1026 2 On/Off (Status)
1027 3 Lock (Setting)
1028 4 Lock (Status)
1029 5 Filter Sign
1030 6 Filter Sign reset
1031 7 Operation Mode (Setting)
1032 8 Operation Mode (Status)
1033 9 Swing (Setting)
1034 10 Swing (Status)
1035 11 Fan Speed (Setting)
1036 12 Fan Speed (Status)
1037 13 Set Room Temperature
1038 14 Room Temperature
1039 15 Alarm
1040 16 Error Code
1043 19 Set Temperature (Status)
1044 20 Accumulated Power Distribution (Status)
1051 27 Set Upper Temperature (Setting)
1052 28 Set Lower Temperature (Setting)
1053 29 Set Upper Tempaerature (Status)
1054 30 Set Lower Temperature (Status)
1055 31 Mode Lock (Setting)
1056 32 Mode Lock (Status)
1057 33 Fan Lock (Setting)
1058 34 Fan Lock (Status)
1059 35 Occupancy (Setting)
1060 36 Occupancy (Status)
1061 37 2Set Cooling Set Temperature (Setting)
1062 38 2Set Cooling Set Temperature (Status)
1063 39 2Set Heating Set Temperature (Setting)
1064 40 2Set Heating Set Temperature (Status)
1065 41 2Set Cooling Upper Temperature (Setting)
1066 42 2Set Cooling Upper Temperature (Status)
1067 43 2Set Heating Upper Temperature (Setting)
1068 44 2Set Heating Upper Temperature (Status)
1069 45 2Set Cooling Lower Temperature (Setting)
1070 46 2Set Cooling Lower Temperature (Status)
1071 47 2Set Heating Lower Temperature (Setting)
1072 48 2Set Heating Lower Temperature (Status)
1073 49 Thermo Status (Status)
1074 50 Accumulated Gas Distribution (Status)
1075 51 Dust Sensor Available (Status)
1076 52 Air Cleaning Opereration (Setting)
1077 53 Air Cleaning Opereration (Status)
1078 54 Fine Dust (Status)
1079 55 Ultra Fine Dust (Status)
1080 56 Super Ultra Fine Dust (Status)
1081 57 Humidity (Status)
1082 58 Comfort Cooling Available (Status)
1083 59 Comfort Cooling Opereration (Setting)
1084 60 Comfort Cooling Opereration (Status)
1085 61 Comfort Cooling Step (Setting)
1086 62 Comfort Cooling Step (Status)
1087 63 Human Detection Available (Status)
1088 64 Human Detection Opereration (Setting)
1089 65 Human Detection Opereration (Status)
1090 66 Human Detection Wind (Setting)
1091 67 Human Detection Wind (Status)
1092 68 Human Detection Time (Setting)
1093 69 Human Detection Time (Status)
1094 70 Hotel Checkin (Setting)
1095 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4 BO Stop(0) Start(1)
StartStopStatus_4 BI Stop(0) Start(1)
LockCommand_4 BO Permit(0) Prohibit(1)
LockStatus_4 BI Permit(0) Prohibit(1)
FilterSign_4 BI Off(0) On(1)
FilterSignReset_4 BV - Reset(1)
AirConModeCommand_4 MO Cool(1)
AirConModeStatus_4 MI Cool(1)
SwingCommand_4 BO Stop(0) Run(1)
SwingStatus_4 BI Stop(0) Run(1)
FanSpeedCommand_4 MO Low(1)
FanSpeedStatus_4 MI Low(1)
SetRoomTemp_4 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4 AI ℃
Alarm_4 BI Normal(0) Abnormal(1)
MalfunctionCode_4 AI Refer to the
SetTempStatus_4 AI ℃
Accumulated power(100 Watt)_4 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4 AI ℃
TempRangeLowerLimitStatus_4 AI ℃
ModeLockCommand_4 BO Permit(0) Prohibit(1)
ModeLockStatus_4 BI Permit(0) Prohibit(1)
FanLockCommand_4 BO Permit(0) Prohibit(1)
FanLockStatus_4 BI Permit(0) Prohibit(1)
OccupancyCommand_4 BO Unoccupied(0) Occupied(1)
OccupancyStatus_4 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4 BI Off(0) On(1)
AccumulatedGas(100 Watt)_4 AI Wattage values (Unit : 100Watt)
DustSensorAvail_4 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4 BO Stop(0) Run(1)
AirCleaningOperStatus_4 BI Stop(0) Run(1)
FineDustStatus_4 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4 AI %
ComfortCoolingAvail_4 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4 BO Stop(0) Run(1)
ComfortCoolingOperStatus_4 BI Stop(0) Run(1)
ComfortCoolingStepCommand_4 AV 1~3 step
ComfortCoolingStepStatus_4 AI 1~3 step
HumanDetectionAvail_4 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4 MO Off(1)
HumanDetectionOperStatus_4 MI Off(1)
HumanDetectionWindCommand_4 MO Off(1)
HumanDetectionWindStatus_4 MI Off(1)
HumanDetectionTimeCommand_4 MO 5min(1)
HumanDetectionTimeStatus_4 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5 ※ Dev Type AC
address

instance
point Name
number

1281 1 On/Off (Setting)


1282 2 On/Off (Status)
1283 3 Lock (Setting)
1284 4 Lock (Status)
1285 5 Filter Sign
1286 6 Filter Sign reset
1287 7 Operation Mode (Setting)
1288 8 Operation Mode (Status)
1289 9 Swing (Setting)
1290 10 Swing (Status)
1291 11 Fan Speed (Setting)
1292 12 Fan Speed (Status)
1293 13 Set Room Temperature
1294 14 Room Temperature
1295 15 Alarm
1296 16 Error Code
1299 19 Set Temperature (Status)
1300 20 Accumulated Power Distribution (Status)
1307 27 Set Upper Temperature (Setting)
1308 28 Set Lower Temperature (Setting)
1309 29 Set Upper Tempaerature (Status)
1310 30 Set Lower Temperature (Status)
1311 31 Mode Lock (Setting)
1312 32 Mode Lock (Status)
1313 33 Fan Lock (Setting)
1314 34 Fan Lock (Status)
1315 35 Occupancy (Setting)
1316 36 Occupancy (Status)
1317 37 2Set Cooling Set Temperature (Setting)
1318 38 2Set Cooling Set Temperature (Status)
1319 39 2Set Heating Set Temperature (Setting)
1320 40 2Set Heating Set Temperature (Status)
1321 41 2Set Cooling Upper Temperature (Setting)
1322 42 2Set Cooling Upper Temperature (Status)
1323 43 2Set Heating Upper Temperature (Setting)
1324 44 2Set Heating Upper Temperature (Status)
1325 45 2Set Cooling Lower Temperature (Setting)
1326 46 2Set Cooling Lower Temperature (Status)
1327 47 2Set Heating Lower Temperature (Setting)
1328 48 2Set Heating Lower Temperature (Status)
1329 49 Thermo Status (Status)
1330 50 Accumulated Gas Distribution (Status)
1331 51 Dust Sensor Available (Status)
1332 52 Air Cleaning Opereration (Setting)
1333 53 Air Cleaning Opereration (Status)
1334 54 Fine Dust (Status)
1335 55 Ultra Fine Dust (Status)
1336 56 Super Ultra Fine Dust (Status)
1337 57 Humidity (Status)
1338 58 Comfort Cooling Available (Status)
1339 59 Comfort Cooling Opereration (Setting)
1340 60 Comfort Cooling Opereration (Status)
1341 61 Comfort Cooling Step (Setting)
1342 62 Comfort Cooling Step (Status)
1343 63 Human Detection Available (Status)
1344 64 Human Detection Opereration (Setting)
1345 65 Human Detection Opereration (Status)
1346 66 Human Detection Wind (Setting)
1347 67 Human Detection Wind (Status)
1348 68 Human Detection Time (Setting)
1349 69 Human Detection Time (Status)
1350 70 Hotel Checkin (Setting)
1351 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5 BO Stop(0) Start(1)
StartStopStatus_5 BI Stop(0) Start(1)
LockCommand_5 BO Permit(0) Prohibit(1)
LockStatus_5 BI Permit(0) Prohibit(1)
FilterSign_5 BI Off(0) On(1)
FilterSignReset_5 BV - Reset(1)
AirConModeCommand_5 MO Cool(1)
AirConModeStatus_5 MI Cool(1)
SwingCommand_5 BO Stop(0) Run(1)
SwingStatus_5 BI Stop(0) Run(1)
FanSpeedCommand_5 MO Low(1)
FanSpeedStatus_5 MI Low(1)
SetRoomTemp_5 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5 AI ℃
Alarm_5 BI Normal(0) Abnormal(1)
MalfunctionCode_5 AI Refer to the
SetTempStatus_5 AI ℃
Accumulated power(100 Watt)_5 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5 AI ℃
TempRangeLowerLimitStatus_5 AI ℃
ModeLockCommand_5 BO Permit(0) Prohibit(1)
ModeLockStatus_5 BI Permit(0) Prohibit(1)
FanLockCommand_5 BO Permit(0) Prohibit(1)
FanLockStatus_5 BI Permit(0) Prohibit(1)
OccupancyCommand_5 BO Unoccupied(0) Occupied(1)
OccupancyStatus_5 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5 BI Off(0) On(1)
AccumulatedGas(100 Watt)_5 AI Wattage values (Unit : 100Watt)
DustSensorAvail_5 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5 BO Stop(0) Run(1)
AirCleaningOperStatus_5 BI Stop(0) Run(1)
FineDustStatus_5 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5 AI %
ComfortCoolingAvail_5 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5 BO Stop(0) Run(1)
ComfortCoolingOperStatus_5 BI Stop(0) Run(1)
ComfortCoolingStepCommand_5 AV 1~3 step
ComfortCoolingStepStatus_5 AI 1~3 step
HumanDetectionAvail_5 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5 MO Off(1)
HumanDetectionOperStatus_5 MI Off(1)
HumanDetectionWindCommand_5 MO Off(1)
HumanDetectionWindStatus_5 MI Off(1)
HumanDetectionTimeCommand_5 MO 5min(1)
HumanDetectionTimeStatus_5 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
6 ※ Dev Type AC
address

instance
point Name
number

1537 1 On/Off (Setting)


1538 2 On/Off (Status)
1539 3 Lock (Setting)
1540 4 Lock (Status)
1541 5 Filter Sign
1542 6 Filter Sign reset
1543 7 Operation Mode (Setting)
1544 8 Operation Mode (Status)
1545 9 Swing (Setting)
1546 10 Swing (Status)
1547 11 Fan Speed (Setting)
1548 12 Fan Speed (Status)
1549 13 Set Room Temperature
1550 14 Room Temperature
1551 15 Alarm
1552 16 Error Code
1555 19 Set Temperature (Status)
1556 20 Accumulated Power Distribution (Status)
1563 27 Set Upper Temperature (Setting)
1564 28 Set Lower Temperature (Setting)
1565 29 Set Upper Tempaerature (Status)
1566 30 Set Lower Temperature (Status)
1567 31 Mode Lock (Setting)
1568 32 Mode Lock (Status)
1569 33 Fan Lock (Setting)
1570 34 Fan Lock (Status)
1571 35 Occupancy (Setting)
1572 36 Occupancy (Status)
1573 37 2Set Cooling Set Temperature (Setting)
1574 38 2Set Cooling Set Temperature (Status)
1575 39 2Set Heating Set Temperature (Setting)
1576 40 2Set Heating Set Temperature (Status)
1577 41 2Set Cooling Upper Temperature (Setting)
1578 42 2Set Cooling Upper Temperature (Status)
1579 43 2Set Heating Upper Temperature (Setting)
1580 44 2Set Heating Upper Temperature (Status)
1581 45 2Set Cooling Lower Temperature (Setting)
1582 46 2Set Cooling Lower Temperature (Status)
1583 47 2Set Heating Lower Temperature (Setting)
1584 48 2Set Heating Lower Temperature (Status)
1585 49 Thermo Status (Status)
1586 50 Accumulated Gas Distribution (Status)
1587 51 Dust Sensor Available (Status)
1588 52 Air Cleaning Opereration (Setting)
1589 53 Air Cleaning Opereration (Status)
1590 54 Fine Dust (Status)
1591 55 Ultra Fine Dust (Status)
1592 56 Super Ultra Fine Dust (Status)
1593 57 Humidity (Status)
1594 58 Comfort Cooling Available (Status)
1595 59 Comfort Cooling Opereration (Setting)
1596 60 Comfort Cooling Opereration (Status)
1597 61 Comfort Cooling Step (Setting)
1598 62 Comfort Cooling Step (Status)
1599 63 Human Detection Available (Status)
1600 64 Human Detection Opereration (Setting)
1601 65 Human Detection Opereration (Status)
1602 66 Human Detection Wind (Setting)
1603 67 Human Detection Wind (Status)
1604 68 Human Detection Time (Setting)
1605 69 Human Detection Time (Status)
1606 70 Hotel Checkin (Setting)
1607 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_6 BO Stop(0) Start(1)
StartStopStatus_6 BI Stop(0) Start(1)
LockCommand_6 BO Permit(0) Prohibit(1)
LockStatus_6 BI Permit(0) Prohibit(1)
FilterSign_6 BI Off(0) On(1)
FilterSignReset_6 BV - Reset(1)
AirConModeCommand_6 MO Cool(1)
AirConModeStatus_6 MI Cool(1)
SwingCommand_6 BO Stop(0) Run(1)
SwingStatus_6 BI Stop(0) Run(1)
FanSpeedCommand_6 MO Low(1)
FanSpeedStatus_6 MI Low(1)
SetRoomTemp_6 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_6 AI ℃
Alarm_6 BI Normal(0) Abnormal(1)
MalfunctionCode_6 AI Refer to the
SetTempStatus_6 AI ℃
Accumulated power(100 Watt)_6 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_6 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_6 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_6 AI ℃
TempRangeLowerLimitStatus_6 AI ℃
ModeLockCommand_6 BO Permit(0) Prohibit(1)
ModeLockStatus_6 BI Permit(0) Prohibit(1)
FanLockCommand_6 BO Permit(0) Prohibit(1)
FanLockStatus_6 BI Permit(0) Prohibit(1)
OccupancyCommand_6 BO Unoccupied(0) Occupied(1)
OccupancyStatus_6 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_6 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_6 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_6 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_6 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_6 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_6 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_6 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_6 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_6 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_6 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_6 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_6 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_6 BI Off(0) On(1)
AccumulatedGas(100 Watt)_6 AI Wattage values (Unit : 100Watt)
DustSensorAvail_6 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_6 BO Stop(0) Run(1)
AirCleaningOperStatus_6 BI Stop(0) Run(1)
FineDustStatus_6 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_6 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_6 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_6 AI %
ComfortCoolingAvail_6 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_6 BO Stop(0) Run(1)
ComfortCoolingOperStatus_6 BI Stop(0) Run(1)
ComfortCoolingStepCommand_6 AV 1~3 step
ComfortCoolingStepStatus_6 AI 1~3 step
HumanDetectionAvail_6 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_6 MO Off(1)
HumanDetectionOperStatus_6 MI Off(1)
HumanDetectionWindCommand_6 MO Off(1)
HumanDetectionWindStatus_6 MI Off(1)
HumanDetectionTimeCommand_6 MO 5min(1)
HumanDetectionTimeStatus_6 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
7 ※ Dev Type AC
address

instance
point Name
number

1793 1 On/Off (Setting)


1794 2 On/Off (Status)
1795 3 Lock (Setting)
1796 4 Lock (Status)
1797 5 Filter Sign
1798 6 Filter Sign reset
1799 7 Operation Mode (Setting)
1800 8 Operation Mode (Status)
1801 9 Swing (Setting)
1802 10 Swing (Status)
1803 11 Fan Speed (Setting)
1804 12 Fan Speed (Status)
1805 13 Set Room Temperature
1806 14 Room Temperature
1807 15 Alarm
1808 16 Error Code
1811 19 Set Temperature (Status)
1812 20 Accumulated Power Distribution (Status)
1819 27 Set Upper Temperature (Setting)
1820 28 Set Lower Temperature (Setting)
1821 29 Set Upper Tempaerature (Status)
1822 30 Set Lower Temperature (Status)
1823 31 Mode Lock (Setting)
1824 32 Mode Lock (Status)
1825 33 Fan Lock (Setting)
1826 34 Fan Lock (Status)
1827 35 Occupancy (Setting)
1828 36 Occupancy (Status)
1829 37 2Set Cooling Set Temperature (Setting)
1830 38 2Set Cooling Set Temperature (Status)
1831 39 2Set Heating Set Temperature (Setting)
1832 40 2Set Heating Set Temperature (Status)
1833 41 2Set Cooling Upper Temperature (Setting)
1834 42 2Set Cooling Upper Temperature (Status)
1835 43 2Set Heating Upper Temperature (Setting)
1836 44 2Set Heating Upper Temperature (Status)
1837 45 2Set Cooling Lower Temperature (Setting)
1838 46 2Set Cooling Lower Temperature (Status)
1839 47 2Set Heating Lower Temperature (Setting)
1840 48 2Set Heating Lower Temperature (Status)
1841 49 Thermo Status (Status)
1842 50 Accumulated Gas Distribution (Status)
1843 51 Dust Sensor Available (Status)
1844 52 Air Cleaning Opereration (Setting)
1845 53 Air Cleaning Opereration (Status)
1846 54 Fine Dust (Status)
1847 55 Ultra Fine Dust (Status)
1848 56 Super Ultra Fine Dust (Status)
1849 57 Humidity (Status)
1850 58 Comfort Cooling Available (Status)
1851 59 Comfort Cooling Opereration (Setting)
1852 60 Comfort Cooling Opereration (Status)
1853 61 Comfort Cooling Step (Setting)
1854 62 Comfort Cooling Step (Status)
1855 63 Human Detection Available (Status)
1856 64 Human Detection Opereration (Setting)
1857 65 Human Detection Opereration (Status)
1858 66 Human Detection Wind (Setting)
1859 67 Human Detection Wind (Status)
1860 68 Human Detection Time (Setting)
1861 69 Human Detection Time (Status)
1862 70 Hotel Checkin (Setting)
1863 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_7 BO Stop(0) Start(1)
StartStopStatus_7 BI Stop(0) Start(1)
LockCommand_7 BO Permit(0) Prohibit(1)
LockStatus_7 BI Permit(0) Prohibit(1)
FilterSign_7 BI Off(0) On(1)
FilterSignReset_7 BV - Reset(1)
AirConModeCommand_7 MO Cool(1)
AirConModeStatus_7 MI Cool(1)
SwingCommand_7 BO Stop(0) Run(1)
SwingStatus_7 BI Stop(0) Run(1)
FanSpeedCommand_7 MO Low(1)
FanSpeedStatus_7 MI Low(1)
SetRoomTemp_7 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_7 AI ℃
Alarm_7 BI Normal(0) Abnormal(1)
MalfunctionCode_7 AI Refer to the
SetTempStatus_7 AI ℃
Accumulated power(100 Watt)_7 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_7 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_7 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_7 AI ℃
TempRangeLowerLimitStatus_7 AI ℃
ModeLockCommand_7 BO Permit(0) Prohibit(1)
ModeLockStatus_7 BI Permit(0) Prohibit(1)
FanLockCommand_7 BO Permit(0) Prohibit(1)
FanLockStatus_7 BI Permit(0) Prohibit(1)
OccupancyCommand_7 BO Unoccupied(0) Occupied(1)
OccupancyStatus_7 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_7 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_7 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_7 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_7 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_7 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_7 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_7 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_7 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_7 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_7 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_7 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_7 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_7 BI Off(0) On(1)
AccumulatedGas(100 Watt)_7 AI Wattage values (Unit : 100Watt)
DustSensorAvail_7 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_7 BO Stop(0) Run(1)
AirCleaningOperStatus_7 BI Stop(0) Run(1)
FineDustStatus_7 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_7 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_7 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_7 AI %
ComfortCoolingAvail_7 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_7 BO Stop(0) Run(1)
ComfortCoolingOperStatus_7 BI Stop(0) Run(1)
ComfortCoolingStepCommand_7 AV 1~3 step
ComfortCoolingStepStatus_7 AI 1~3 step
HumanDetectionAvail_7 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_7 MO Off(1)
HumanDetectionOperStatus_7 MI Off(1)
HumanDetectionWindCommand_7 MO Off(1)
HumanDetectionWindStatus_7 MI Off(1)
HumanDetectionTimeCommand_7 MO 5min(1)
HumanDetectionTimeStatus_7 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
8 ※ Dev Type AC
address

instance
point Name
number

2049 1 On/Off (Setting)


2050 2 On/Off (Status)
2051 3 Lock (Setting)
2052 4 Lock (Status)
2053 5 Filter Sign
2054 6 Filter Sign reset
2055 7 Operation Mode (Setting)
2056 8 Operation Mode (Status)
2057 9 Swing (Setting)
2058 10 Swing (Status)
2059 11 Fan Speed (Setting)
2060 12 Fan Speed (Status)
2061 13 Set Room Temperature
2062 14 Room Temperature
2063 15 Alarm
2064 16 Error Code
2067 19 Set Temperature (Status)
2068 20 Accumulated Power Distribution (Status)
2075 27 Set Upper Temperature (Setting)
2076 28 Set Lower Temperature (Setting)
2077 29 Set Upper Tempaerature (Status)
2078 30 Set Lower Temperature (Status)
2079 31 Mode Lock (Setting)
2080 32 Mode Lock (Status)
2081 33 Fan Lock (Setting)
2082 34 Fan Lock (Status)
2083 35 Occupancy (Setting)
2084 36 Occupancy (Status)
2085 37 2Set Cooling Set Temperature (Setting)
2086 38 2Set Cooling Set Temperature (Status)
2087 39 2Set Heating Set Temperature (Setting)
2088 40 2Set Heating Set Temperature (Status)
2089 41 2Set Cooling Upper Temperature (Setting)
2090 42 2Set Cooling Upper Temperature (Status)
2091 43 2Set Heating Upper Temperature (Setting)
2092 44 2Set Heating Upper Temperature (Status)
2093 45 2Set Cooling Lower Temperature (Setting)
2094 46 2Set Cooling Lower Temperature (Status)
2095 47 2Set Heating Lower Temperature (Setting)
2096 48 2Set Heating Lower Temperature (Status)
2097 49 Thermo Status (Status)
2098 50 Accumulated Gas Distribution (Status)
2099 51 Dust Sensor Available (Status)
2100 52 Air Cleaning Opereration (Setting)
2101 53 Air Cleaning Opereration (Status)
2102 54 Fine Dust (Status)
2103 55 Ultra Fine Dust (Status)
2104 56 Super Ultra Fine Dust (Status)
2105 57 Humidity (Status)
2106 58 Comfort Cooling Available (Status)
2107 59 Comfort Cooling Opereration (Setting)
2108 60 Comfort Cooling Opereration (Status)
2109 61 Comfort Cooling Step (Setting)
2110 62 Comfort Cooling Step (Status)
2111 63 Human Detection Available (Status)
2112 64 Human Detection Opereration (Setting)
2113 65 Human Detection Opereration (Status)
2114 66 Human Detection Wind (Setting)
2115 67 Human Detection Wind (Status)
2116 68 Human Detection Time (Setting)
2117 69 Human Detection Time (Status)
2118 70 Hotel Checkin (Setting)
2119 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_8 BO Stop(0) Start(1)
StartStopStatus_8 BI Stop(0) Start(1)
LockCommand_8 BO Permit(0) Prohibit(1)
LockStatus_8 BI Permit(0) Prohibit(1)
FilterSign_8 BI Off(0) On(1)
FilterSignReset_8 BV - Reset(1)
AirConModeCommand_8 MO Cool(1)
AirConModeStatus_8 MI Cool(1)
SwingCommand_8 BO Stop(0) Run(1)
SwingStatus_8 BI Stop(0) Run(1)
FanSpeedCommand_8 MO Low(1)
FanSpeedStatus_8 MI Low(1)
SetRoomTemp_8 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_8 AI ℃
Alarm_8 BI Normal(0) Abnormal(1)
MalfunctionCode_8 AI Refer to the
SetTempStatus_8 AI ℃
Accumulated power(100 Watt)_8 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_8 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_8 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_8 AI ℃
TempRangeLowerLimitStatus_8 AI ℃
ModeLockCommand_8 BO Permit(0) Prohibit(1)
ModeLockStatus_8 BI Permit(0) Prohibit(1)
FanLockCommand_8 BO Permit(0) Prohibit(1)
FanLockStatus_8 BI Permit(0) Prohibit(1)
OccupancyCommand_8 BO Unoccupied(0) Occupied(1)
OccupancyStatus_8 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_8 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_8 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_8 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_8 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_8 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_8 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_8 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_8 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_8 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_8 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_8 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_8 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_8 BI Off(0) On(1)
AccumulatedGas(100 Watt)_8 AI Wattage values (Unit : 100Watt)
DustSensorAvail_8 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_8 BO Stop(0) Run(1)
AirCleaningOperStatus_8 BI Stop(0) Run(1)
FineDustStatus_8 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_8 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_8 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_8 AI %
ComfortCoolingAvail_8 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_8 BO Stop(0) Run(1)
ComfortCoolingOperStatus_8 BI Stop(0) Run(1)
ComfortCoolingStepCommand_8 AV 1~3 step
ComfortCoolingStepStatus_8 AI 1~3 step
HumanDetectionAvail_8 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_8 MO Off(1)
HumanDetectionOperStatus_8 MI Off(1)
HumanDetectionWindCommand_8 MO Off(1)
HumanDetectionWindStatus_8 MI Off(1)
HumanDetectionTimeCommand_8 MO 5min(1)
HumanDetectionTimeStatus_8 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
9 ※ Dev Type AC
address

instance
point Name
number

2305 1 On/Off (Setting)


2306 2 On/Off (Status)
2307 3 Lock (Setting)
2308 4 Lock (Status)
2309 5 Filter Sign
2310 6 Filter Sign reset
2311 7 Operation Mode (Setting)
2312 8 Operation Mode (Status)
2313 9 Swing (Setting)
2314 10 Swing (Status)
2315 11 Fan Speed (Setting)
2316 12 Fan Speed (Status)
2317 13 Set Room Temperature
2318 14 Room Temperature
2319 15 Alarm
2320 16 Error Code
2323 19 Set Temperature (Status)
2324 20 Accumulated Power Distribution (Status)
2331 27 Set Upper Temperature (Setting)
2332 28 Set Lower Temperature (Setting)
2333 29 Set Upper Tempaerature (Status)
2334 30 Set Lower Temperature (Status)
2335 31 Mode Lock (Setting)
2336 32 Mode Lock (Status)
2337 33 Fan Lock (Setting)
2338 34 Fan Lock (Status)
2339 35 Occupancy (Setting)
2340 36 Occupancy (Status)
2341 37 2Set Cooling Set Temperature (Setting)
2342 38 2Set Cooling Set Temperature (Status)
2343 39 2Set Heating Set Temperature (Setting)
2344 40 2Set Heating Set Temperature (Status)
2345 41 2Set Cooling Upper Temperature (Setting)
2346 42 2Set Cooling Upper Temperature (Status)
2347 43 2Set Heating Upper Temperature (Setting)
2348 44 2Set Heating Upper Temperature (Status)
2349 45 2Set Cooling Lower Temperature (Setting)
2350 46 2Set Cooling Lower Temperature (Status)
2351 47 2Set Heating Lower Temperature (Setting)
2352 48 2Set Heating Lower Temperature (Status)
2353 49 Thermo Status (Status)
2354 50 Accumulated Gas Distribution (Status)
2355 51 Dust Sensor Available (Status)
2356 52 Air Cleaning Opereration (Setting)
2357 53 Air Cleaning Opereration (Status)
2358 54 Fine Dust (Status)
2359 55 Ultra Fine Dust (Status)
2360 56 Super Ultra Fine Dust (Status)
2361 57 Humidity (Status)
2362 58 Comfort Cooling Available (Status)
2363 59 Comfort Cooling Opereration (Setting)
2364 60 Comfort Cooling Opereration (Status)
2365 61 Comfort Cooling Step (Setting)
2366 62 Comfort Cooling Step (Status)
2367 63 Human Detection Available (Status)
2368 64 Human Detection Opereration (Setting)
2369 65 Human Detection Opereration (Status)
2370 66 Human Detection Wind (Setting)
2371 67 Human Detection Wind (Status)
2372 68 Human Detection Time (Setting)
2373 69 Human Detection Time (Status)
2374 70 Hotel Checkin (Setting)
2375 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_9 BO Stop(0) Start(1)
StartStopStatus_9 BI Stop(0) Start(1)
LockCommand_9 BO Permit(0) Prohibit(1)
LockStatus_9 BI Permit(0) Prohibit(1)
FilterSign_9 BI Off(0) On(1)
FilterSignReset_9 BV - Reset(1)
AirConModeCommand_9 MO Cool(1)
AirConModeStatus_9 MI Cool(1)
SwingCommand_9 BO Stop(0) Run(1)
SwingStatus_9 BI Stop(0) Run(1)
FanSpeedCommand_9 MO Low(1)
FanSpeedStatus_9 MI Low(1)
SetRoomTemp_9 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_9 AI ℃
Alarm_9 BI Normal(0) Abnormal(1)
MalfunctionCode_9 AI Refer to the
SetTempStatus_9 AI ℃
Accumulated power(100 Watt)_9 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_9 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_9 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_9 AI ℃
TempRangeLowerLimitStatus_9 AI ℃
ModeLockCommand_9 BO Permit(0) Prohibit(1)
ModeLockStatus_9 BI Permit(0) Prohibit(1)
FanLockCommand_9 BO Permit(0) Prohibit(1)
FanLockStatus_9 BI Permit(0) Prohibit(1)
OccupancyCommand_9 BO Unoccupied(0) Occupied(1)
OccupancyStatus_9 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_9 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_9 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_9 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_9 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_9 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_9 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_9 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_9 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_9 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_9 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_9 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_9 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_9 BI Off(0) On(1)
AccumulatedGas(100 Watt)_9 AI Wattage values (Unit : 100Watt)
DustSensorAvail_9 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_9 BO Stop(0) Run(1)
AirCleaningOperStatus_9 BI Stop(0) Run(1)
FineDustStatus_9 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_9 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_9 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_9 AI %
ComfortCoolingAvail_9 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_9 BO Stop(0) Run(1)
ComfortCoolingOperStatus_9 BI Stop(0) Run(1)
ComfortCoolingStepCommand_9 AV 1~3 step
ComfortCoolingStepStatus_9 AI 1~3 step
HumanDetectionAvail_9 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_9 MO Off(1)
HumanDetectionOperStatus_9 MI Off(1)
HumanDetectionWindCommand_9 MO Off(1)
HumanDetectionWindStatus_9 MI Off(1)
HumanDetectionTimeCommand_9 MO 5min(1)
HumanDetectionTimeStatus_9 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
a ※ Dev Type AC
address

instance
point Name
number

2561 1 On/Off (Setting)


2562 2 On/Off (Status)
2563 3 Lock (Setting)
2564 4 Lock (Status)
2565 5 Filter Sign
2566 6 Filter Sign reset
2567 7 Operation Mode (Setting)
2568 8 Operation Mode (Status)
2569 9 Swing (Setting)
2570 10 Swing (Status)
2571 11 Fan Speed (Setting)
2572 12 Fan Speed (Status)
2573 13 Set Room Temperature
2574 14 Room Temperature
2575 15 Alarm
2576 16 Error Code
2579 19 Set Temperature (Status)
2580 20 Accumulated Power Distribution (Status)
2587 27 Set Upper Temperature (Setting)
2588 28 Set Lower Temperature (Setting)
2589 29 Set Upper Tempaerature (Status)
2590 30 Set Lower Temperature (Status)
2591 31 Mode Lock (Setting)
2592 32 Mode Lock (Status)
2593 33 Fan Lock (Setting)
2594 34 Fan Lock (Status)
2595 35 Occupancy (Setting)
2596 36 Occupancy (Status)
2597 37 2Set Cooling Set Temperature (Setting)
2598 38 2Set Cooling Set Temperature (Status)
2599 39 2Set Heating Set Temperature (Setting)
2600 40 2Set Heating Set Temperature (Status)
2601 41 2Set Cooling Upper Temperature (Setting)
2602 42 2Set Cooling Upper Temperature (Status)
2603 43 2Set Heating Upper Temperature (Setting)
2604 44 2Set Heating Upper Temperature (Status)
2605 45 2Set Cooling Lower Temperature (Setting)
2606 46 2Set Cooling Lower Temperature (Status)
2607 47 2Set Heating Lower Temperature (Setting)
2608 48 2Set Heating Lower Temperature (Status)
2609 49 Thermo Status (Status)
2610 50 Accumulated Gas Distribution (Status)
2611 51 Dust Sensor Available (Status)
2612 52 Air Cleaning Opereration (Setting)
2613 53 Air Cleaning Opereration (Status)
2614 54 Fine Dust (Status)
2615 55 Ultra Fine Dust (Status)
2616 56 Super Ultra Fine Dust (Status)
2617 57 Humidity (Status)
2618 58 Comfort Cooling Available (Status)
2619 59 Comfort Cooling Opereration (Setting)
2620 60 Comfort Cooling Opereration (Status)
2621 61 Comfort Cooling Step (Setting)
2622 62 Comfort Cooling Step (Status)
2623 63 Human Detection Available (Status)
2624 64 Human Detection Opereration (Setting)
2625 65 Human Detection Opereration (Status)
2626 66 Human Detection Wind (Setting)
2627 67 Human Detection Wind (Status)
2628 68 Human Detection Time (Setting)
2629 69 Human Detection Time (Status)
2630 70 Hotel Checkin (Setting)
2631 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_a BO Stop(0) Start(1)
StartStopStatus_a BI Stop(0) Start(1)
LockCommand_a BO Permit(0) Prohibit(1)
LockStatus_a BI Permit(0) Prohibit(1)
FilterSign_a BI Off(0) On(1)
FilterSignReset_a BV - Reset(1)
AirConModeCommand_a MO Cool(1)
AirConModeStatus_a MI Cool(1)
SwingCommand_a BO Stop(0) Run(1)
SwingStatus_a BI Stop(0) Run(1)
FanSpeedCommand_a MO Low(1)
FanSpeedStatus_a MI Low(1)
SetRoomTemp_a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_a AI ℃
Alarm_a BI Normal(0) Abnormal(1)
MalfunctionCode_a AI Refer to the
SetTempStatus_a AI ℃
Accumulated power(100 Watt)_a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_a AI ℃
TempRangeLowerLimitStatus_a AI ℃
ModeLockCommand_a BO Permit(0) Prohibit(1)
ModeLockStatus_a BI Permit(0) Prohibit(1)
FanLockCommand_a BO Permit(0) Prohibit(1)
FanLockStatus_a BI Permit(0) Prohibit(1)
OccupancyCommand_a BO Unoccupied(0) Occupied(1)
OccupancyStatus_a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_a BI Off(0) On(1)
AccumulatedGas(100 Watt)_a AI Wattage values (Unit : 100Watt)
DustSensorAvail_a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_a BO Stop(0) Run(1)
AirCleaningOperStatus_a BI Stop(0) Run(1)
FineDustStatus_a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_a AI %
ComfortCoolingAvail_a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_a BO Stop(0) Run(1)
ComfortCoolingOperStatus_a BI Stop(0) Run(1)
ComfortCoolingStepCommand_a AV 1~3 step
ComfortCoolingStepStatus_a AI 1~3 step
HumanDetectionAvail_a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_a MO Off(1)
HumanDetectionOperStatus_a MI Off(1)
HumanDetectionWindCommand_a MO Off(1)
HumanDetectionWindStatus_a MI Off(1)
HumanDetectionTimeCommand_a MO 5min(1)
HumanDetectionTimeStatus_a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
b ※ Dev Type AC
address

instance
point Name
number

2817 1 On/Off (Setting)


2818 2 On/Off (Status)
2819 3 Lock (Setting)
2820 4 Lock (Status)
2821 5 Filter Sign
2822 6 Filter Sign reset
2823 7 Operation Mode (Setting)
2824 8 Operation Mode (Status)
2825 9 Swing (Setting)
2826 10 Swing (Status)
2827 11 Fan Speed (Setting)
2828 12 Fan Speed (Status)
2829 13 Set Room Temperature
2830 14 Room Temperature
2831 15 Alarm
2832 16 Error Code
2835 19 Set Temperature (Status)
2836 20 Accumulated Power Distribution (Status)
2843 27 Set Upper Temperature (Setting)
2844 28 Set Lower Temperature (Setting)
2845 29 Set Upper Tempaerature (Status)
2846 30 Set Lower Temperature (Status)
2847 31 Mode Lock (Setting)
2848 32 Mode Lock (Status)
2849 33 Fan Lock (Setting)
2850 34 Fan Lock (Status)
2851 35 Occupancy (Setting)
2852 36 Occupancy (Status)
2853 37 2Set Cooling Set Temperature (Setting)
2854 38 2Set Cooling Set Temperature (Status)
2855 39 2Set Heating Set Temperature (Setting)
2856 40 2Set Heating Set Temperature (Status)
2857 41 2Set Cooling Upper Temperature (Setting)
2858 42 2Set Cooling Upper Temperature (Status)
2859 43 2Set Heating Upper Temperature (Setting)
2860 44 2Set Heating Upper Temperature (Status)
2861 45 2Set Cooling Lower Temperature (Setting)
2862 46 2Set Cooling Lower Temperature (Status)
2863 47 2Set Heating Lower Temperature (Setting)
2864 48 2Set Heating Lower Temperature (Status)
2865 49 Thermo Status (Status)
2866 50 Accumulated Gas Distribution (Status)
2867 51 Dust Sensor Available (Status)
2868 52 Air Cleaning Opereration (Setting)
2869 53 Air Cleaning Opereration (Status)
2870 54 Fine Dust (Status)
2871 55 Ultra Fine Dust (Status)
2872 56 Super Ultra Fine Dust (Status)
2873 57 Humidity (Status)
2874 58 Comfort Cooling Available (Status)
2875 59 Comfort Cooling Opereration (Setting)
2876 60 Comfort Cooling Opereration (Status)
2877 61 Comfort Cooling Step (Setting)
2878 62 Comfort Cooling Step (Status)
2879 63 Human Detection Available (Status)
2880 64 Human Detection Opereration (Setting)
2881 65 Human Detection Opereration (Status)
2882 66 Human Detection Wind (Setting)
2883 67 Human Detection Wind (Status)
2884 68 Human Detection Time (Setting)
2885 69 Human Detection Time (Status)
2886 70 Hotel Checkin (Setting)
2887 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_b BO Stop(0) Start(1)
StartStopStatus_b BI Stop(0) Start(1)
LockCommand_b BO Permit(0) Prohibit(1)
LockStatus_b BI Permit(0) Prohibit(1)
FilterSign_b BI Off(0) On(1)
FilterSignReset_b BV - Reset(1)
AirConModeCommand_b MO Cool(1)
AirConModeStatus_b MI Cool(1)
SwingCommand_b BO Stop(0) Run(1)
SwingStatus_b BI Stop(0) Run(1)
FanSpeedCommand_b MO Low(1)
FanSpeedStatus_b MI Low(1)
SetRoomTemp_b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_b AI ℃
Alarm_b BI Normal(0) Abnormal(1)
MalfunctionCode_b AI Refer to the
SetTempStatus_b AI ℃
Accumulated power(100 Watt)_b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_b AI ℃
TempRangeLowerLimitStatus_b AI ℃
ModeLockCommand_b BO Permit(0) Prohibit(1)
ModeLockStatus_b BI Permit(0) Prohibit(1)
FanLockCommand_b BO Permit(0) Prohibit(1)
FanLockStatus_b BI Permit(0) Prohibit(1)
OccupancyCommand_b BO Unoccupied(0) Occupied(1)
OccupancyStatus_b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_b BI Off(0) On(1)
AccumulatedGas(100 Watt)_b AI Wattage values (Unit : 100Watt)
DustSensorAvail_b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_b BO Stop(0) Run(1)
AirCleaningOperStatus_b BI Stop(0) Run(1)
FineDustStatus_b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_b AI %
ComfortCoolingAvail_b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_b BO Stop(0) Run(1)
ComfortCoolingOperStatus_b BI Stop(0) Run(1)
ComfortCoolingStepCommand_b AV 1~3 step
ComfortCoolingStepStatus_b AI 1~3 step
HumanDetectionAvail_b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_b MO Off(1)
HumanDetectionOperStatus_b MI Off(1)
HumanDetectionWindCommand_b MO Off(1)
HumanDetectionWindStatus_b MI Off(1)
HumanDetectionTimeCommand_b MO 5min(1)
HumanDetectionTimeStatus_b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
d ※ Dev Type AC
address

instance
point Name
number

3329 1 On/Off (Setting)


3330 2 On/Off (Status)
3331 3 Lock (Setting)
3332 4 Lock (Status)
3333 5 Filter Sign
3334 6 Filter Sign reset
3335 7 Operation Mode (Setting)
3336 8 Operation Mode (Status)
3337 9 Swing (Setting)
3338 10 Swing (Status)
3339 11 Fan Speed (Setting)
3340 12 Fan Speed (Status)
3341 13 Set Room Temperature
3342 14 Room Temperature
3343 15 Alarm
3344 16 Error Code
3347 19 Set Temperature (Status)
3348 20 Accumulated Power Distribution (Status)
3355 27 Set Upper Temperature (Setting)
3356 28 Set Lower Temperature (Setting)
3357 29 Set Upper Tempaerature (Status)
3358 30 Set Lower Temperature (Status)
3359 31 Mode Lock (Setting)
3360 32 Mode Lock (Status)
3361 33 Fan Lock (Setting)
3362 34 Fan Lock (Status)
3363 35 Occupancy (Setting)
3364 36 Occupancy (Status)
3365 37 2Set Cooling Set Temperature (Setting)
3366 38 2Set Cooling Set Temperature (Status)
3367 39 2Set Heating Set Temperature (Setting)
3368 40 2Set Heating Set Temperature (Status)
3369 41 2Set Cooling Upper Temperature (Setting)
3370 42 2Set Cooling Upper Temperature (Status)
3371 43 2Set Heating Upper Temperature (Setting)
3372 44 2Set Heating Upper Temperature (Status)
3373 45 2Set Cooling Lower Temperature (Setting)
3374 46 2Set Cooling Lower Temperature (Status)
3375 47 2Set Heating Lower Temperature (Setting)
3376 48 2Set Heating Lower Temperature (Status)
3377 49 Thermo Status (Status)
3378 50 Accumulated Gas Distribution (Status)
3379 51 Dust Sensor Available (Status)
3380 52 Air Cleaning Opereration (Setting)
3381 53 Air Cleaning Opereration (Status)
3382 54 Fine Dust (Status)
3383 55 Ultra Fine Dust (Status)
3384 56 Super Ultra Fine Dust (Status)
3385 57 Humidity (Status)
3386 58 Comfort Cooling Available (Status)
3387 59 Comfort Cooling Opereration (Setting)
3388 60 Comfort Cooling Opereration (Status)
3389 61 Comfort Cooling Step (Setting)
3390 62 Comfort Cooling Step (Status)
3391 63 Human Detection Available (Status)
3392 64 Human Detection Opereration (Setting)
3393 65 Human Detection Opereration (Status)
3394 66 Human Detection Wind (Setting)
3395 67 Human Detection Wind (Status)
3396 68 Human Detection Time (Setting)
3397 69 Human Detection Time (Status)
3398 70 Hotel Checkin (Setting)
3399 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_d BO Stop(0) Start(1)
StartStopStatus_d BI Stop(0) Start(1)
LockCommand_d BO Permit(0) Prohibit(1)
LockStatus_d BI Permit(0) Prohibit(1)
FilterSign_d BI Off(0) On(1)
FilterSignReset_d BV - Reset(1)
AirConModeCommand_d MO Cool(1)
AirConModeStatus_d MI Cool(1)
SwingCommand_d BO Stop(0) Run(1)
SwingStatus_d BI Stop(0) Run(1)
FanSpeedCommand_d MO Low(1)
FanSpeedStatus_d MI Low(1)
SetRoomTemp_d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_d AI ℃
Alarm_d BI Normal(0) Abnormal(1)
MalfunctionCode_d AI Refer to the
SetTempStatus_d AI ℃
Accumulated power(100 Watt)_d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_d AI ℃
TempRangeLowerLimitStatus_d AI ℃
ModeLockCommand_d BO Permit(0) Prohibit(1)
ModeLockStatus_d BI Permit(0) Prohibit(1)
FanLockCommand_d BO Permit(0) Prohibit(1)
FanLockStatus_d BI Permit(0) Prohibit(1)
OccupancyCommand_d BO Unoccupied(0) Occupied(1)
OccupancyStatus_d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_d BI Off(0) On(1)
AccumulatedGas(100 Watt)_d AI Wattage values (Unit : 100Watt)
DustSensorAvail_d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_d BO Stop(0) Run(1)
AirCleaningOperStatus_d BI Stop(0) Run(1)
FineDustStatus_d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_d AI %
ComfortCoolingAvail_d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_d BO Stop(0) Run(1)
ComfortCoolingOperStatus_d BI Stop(0) Run(1)
ComfortCoolingStepCommand_d AV 1~3 step
ComfortCoolingStepStatus_d AI 1~3 step
HumanDetectionAvail_d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_d MO Off(1)
HumanDetectionOperStatus_d MI Off(1)
HumanDetectionWindCommand_d MO Off(1)
HumanDetectionWindStatus_d MI Off(1)
HumanDetectionTimeCommand_d MO 5min(1)
HumanDetectionTimeStatus_d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
e ※ Dev Type AC
address

instance
point Name
number

3585 1 On/Off (Setting)


3586 2 On/Off (Status)
3587 3 Lock (Setting)
3588 4 Lock (Status)
3589 5 Filter Sign
3590 6 Filter Sign reset
3591 7 Operation Mode (Setting)
3592 8 Operation Mode (Status)
3593 9 Swing (Setting)
3594 10 Swing (Status)
3595 11 Fan Speed (Setting)
3596 12 Fan Speed (Status)
3597 13 Set Room Temperature
3598 14 Room Temperature
3599 15 Alarm
3600 16 Error Code
3603 19 Set Temperature (Status)
3604 20 Accumulated Power Distribution (Status)
3611 27 Set Upper Temperature (Setting)
3612 28 Set Lower Temperature (Setting)
3613 29 Set Upper Tempaerature (Status)
3614 30 Set Lower Temperature (Status)
3615 31 Mode Lock (Setting)
3616 32 Mode Lock (Status)
3617 33 Fan Lock (Setting)
3618 34 Fan Lock (Status)
3619 35 Occupancy (Setting)
3620 36 Occupancy (Status)
3621 37 2Set Cooling Set Temperature (Setting)
3622 38 2Set Cooling Set Temperature (Status)
3623 39 2Set Heating Set Temperature (Setting)
3624 40 2Set Heating Set Temperature (Status)
3625 41 2Set Cooling Upper Temperature (Setting)
3626 42 2Set Cooling Upper Temperature (Status)
3627 43 2Set Heating Upper Temperature (Setting)
3628 44 2Set Heating Upper Temperature (Status)
3629 45 2Set Cooling Lower Temperature (Setting)
3630 46 2Set Cooling Lower Temperature (Status)
3631 47 2Set Heating Lower Temperature (Setting)
3632 48 2Set Heating Lower Temperature (Status)
3633 49 Thermo Status (Status)
3634 50 Accumulated Gas Distribution (Status)
3635 51 Dust Sensor Available (Status)
3636 52 Air Cleaning Opereration (Setting)
3637 53 Air Cleaning Opereration (Status)
3638 54 Fine Dust (Status)
3639 55 Ultra Fine Dust (Status)
3640 56 Super Ultra Fine Dust (Status)
3641 57 Humidity (Status)
3642 58 Comfort Cooling Available (Status)
3643 59 Comfort Cooling Opereration (Setting)
3644 60 Comfort Cooling Opereration (Status)
3645 61 Comfort Cooling Step (Setting)
3646 62 Comfort Cooling Step (Status)
3647 63 Human Detection Available (Status)
3648 64 Human Detection Opereration (Setting)
3649 65 Human Detection Opereration (Status)
3650 66 Human Detection Wind (Setting)
3651 67 Human Detection Wind (Status)
3652 68 Human Detection Time (Setting)
3653 69 Human Detection Time (Status)
3654 70 Hotel Checkin (Setting)
3655 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_e BO Stop(0) Start(1)
StartStopStatus_e BI Stop(0) Start(1)
LockCommand_e BO Permit(0) Prohibit(1)
LockStatus_e BI Permit(0) Prohibit(1)
FilterSign_e BI Off(0) On(1)
FilterSignReset_e BV - Reset(1)
AirConModeCommand_e MO Cool(1)
AirConModeStatus_e MI Cool(1)
SwingCommand_e BO Stop(0) Run(1)
SwingStatus_e BI Stop(0) Run(1)
FanSpeedCommand_e MO Low(1)
FanSpeedStatus_e MI Low(1)
SetRoomTemp_e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_e AI ℃
Alarm_e BI Normal(0) Abnormal(1)
MalfunctionCode_e AI Refer to the
SetTempStatus_e AI ℃
Accumulated power(100 Watt)_e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_e AI ℃
TempRangeLowerLimitStatus_e AI ℃
ModeLockCommand_e BO Permit(0) Prohibit(1)
ModeLockStatus_e BI Permit(0) Prohibit(1)
FanLockCommand_e BO Permit(0) Prohibit(1)
FanLockStatus_e BI Permit(0) Prohibit(1)
OccupancyCommand_e BO Unoccupied(0) Occupied(1)
OccupancyStatus_e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_e BI Off(0) On(1)
AccumulatedGas(100 Watt)_e AI Wattage values (Unit : 100Watt)
DustSensorAvail_e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_e BO Stop(0) Run(1)
AirCleaningOperStatus_e BI Stop(0) Run(1)
FineDustStatus_e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_e AI %
ComfortCoolingAvail_e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_e BO Stop(0) Run(1)
ComfortCoolingOperStatus_e BI Stop(0) Run(1)
ComfortCoolingStepCommand_e AV 1~3 step
ComfortCoolingStepStatus_e AI 1~3 step
HumanDetectionAvail_e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_e MO Off(1)
HumanDetectionOperStatus_e MI Off(1)
HumanDetectionWindCommand_e MO Off(1)
HumanDetectionWindStatus_e MI Off(1)
HumanDetectionTimeCommand_e MO 5min(1)
HumanDetectionTimeStatus_e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
f ※ Dev Type AC
address

instance
point Name
number

3841 1 On/Off (Setting)


3842 2 On/Off (Status)
3843 3 Lock (Setting)
3844 4 Lock (Status)
3845 5 Filter Sign
3846 6 Filter Sign reset
3847 7 Operation Mode (Setting)
3848 8 Operation Mode (Status)
3849 9 Swing (Setting)
3850 10 Swing (Status)
3851 11 Fan Speed (Setting)
3852 12 Fan Speed (Status)
3853 13 Set Room Temperature
3854 14 Room Temperature
3855 15 Alarm
3856 16 Error Code
3859 19 Set Temperature (Status)
3860 20 Accumulated Power Distribution (Status)
3867 27 Set Upper Temperature (Setting)
3868 28 Set Lower Temperature (Setting)
3869 29 Set Upper Tempaerature (Status)
3870 30 Set Lower Temperature (Status)
3871 31 Mode Lock (Setting)
3872 32 Mode Lock (Status)
3873 33 Fan Lock (Setting)
3874 34 Fan Lock (Status)
3875 35 Occupancy (Setting)
3876 36 Occupancy (Status)
3877 37 2Set Cooling Set Temperature (Setting)
3878 38 2Set Cooling Set Temperature (Status)
3879 39 2Set Heating Set Temperature (Setting)
3880 40 2Set Heating Set Temperature (Status)
3881 41 2Set Cooling Upper Temperature (Setting)
3882 42 2Set Cooling Upper Temperature (Status)
3883 43 2Set Heating Upper Temperature (Setting)
3884 44 2Set Heating Upper Temperature (Status)
3885 45 2Set Cooling Lower Temperature (Setting)
3886 46 2Set Cooling Lower Temperature (Status)
3887 47 2Set Heating Lower Temperature (Setting)
3888 48 2Set Heating Lower Temperature (Status)
3889 49 Thermo Status (Status)
3890 50 Accumulated Gas Distribution (Status)
3891 51 Dust Sensor Available (Status)
3892 52 Air Cleaning Opereration (Setting)
3893 53 Air Cleaning Opereration (Status)
3894 54 Fine Dust (Status)
3895 55 Ultra Fine Dust (Status)
3896 56 Super Ultra Fine Dust (Status)
3897 57 Humidity (Status)
3898 58 Comfort Cooling Available (Status)
3899 59 Comfort Cooling Opereration (Setting)
3900 60 Comfort Cooling Opereration (Status)
3901 61 Comfort Cooling Step (Setting)
3902 62 Comfort Cooling Step (Status)
3903 63 Human Detection Available (Status)
3904 64 Human Detection Opereration (Setting)
3905 65 Human Detection Opereration (Status)
3906 66 Human Detection Wind (Setting)
3907 67 Human Detection Wind (Status)
3908 68 Human Detection Time (Setting)
3909 69 Human Detection Time (Status)
3910 70 Hotel Checkin (Setting)
3911 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_f BO Stop(0) Start(1)
StartStopStatus_f BI Stop(0) Start(1)
LockCommand_f BO Permit(0) Prohibit(1)
LockStatus_f BI Permit(0) Prohibit(1)
FilterSign_f BI Off(0) On(1)
FilterSignReset_f BV - Reset(1)
AirConModeCommand_f MO Cool(1)
AirConModeStatus_f MI Cool(1)
SwingCommand_f BO Stop(0) Run(1)
SwingStatus_f BI Stop(0) Run(1)
FanSpeedCommand_f MO Low(1)
FanSpeedStatus_f MI Low(1)
SetRoomTemp_f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_f AI ℃
Alarm_f BI Normal(0) Abnormal(1)
MalfunctionCode_f AI Refer to the
SetTempStatus_f AI ℃
Accumulated power(100 Watt)_f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_f AI ℃
TempRangeLowerLimitStatus_f AI ℃
ModeLockCommand_f BO Permit(0) Prohibit(1)
ModeLockStatus_f BI Permit(0) Prohibit(1)
FanLockCommand_f BO Permit(0) Prohibit(1)
FanLockStatus_f BI Permit(0) Prohibit(1)
OccupancyCommand_f BO Unoccupied(0) Occupied(1)
OccupancyStatus_f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_f BI Off(0) On(1)
AccumulatedGas(100 Watt)_f AI Wattage values (Unit : 100Watt)
DustSensorAvail_f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_f BO Stop(0) Run(1)
AirCleaningOperStatus_f BI Stop(0) Run(1)
FineDustStatus_f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_f AI %
ComfortCoolingAvail_f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_f BO Stop(0) Run(1)
ComfortCoolingOperStatus_f BI Stop(0) Run(1)
ComfortCoolingStepCommand_f AV 1~3 step
ComfortCoolingStepStatus_f AI 1~3 step
HumanDetectionAvail_f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_f MO Off(1)
HumanDetectionOperStatus_f MI Off(1)
HumanDetectionWindCommand_f MO Off(1)
HumanDetectionWindStatus_f MI Off(1)
HumanDetectionTimeCommand_f MO 5min(1)
HumanDetectionTimeStatus_f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
10 ※ Dev Type AC
address

instance
point Name
number

4097 1 On/Off (Setting)


4098 2 On/Off (Status)
4099 3 Lock (Setting)
4100 4 Lock (Status)
4101 5 Filter Sign
4102 6 Filter Sign reset
4103 7 Operation Mode (Setting)
4104 8 Operation Mode (Status)
4105 9 Swing (Setting)
4106 10 Swing (Status)
4107 11 Fan Speed (Setting)
4108 12 Fan Speed (Status)
4109 13 Set Room Temperature
4110 14 Room Temperature
4111 15 Alarm
4112 16 Error Code
4115 19 Set Temperature (Status)
4116 20 Accumulated Power Distribution (Status)
4123 27 Set Upper Temperature (Setting)
4124 28 Set Lower Temperature (Setting)
4125 29 Set Upper Tempaerature (Status)
4126 30 Set Lower Temperature (Status)
4127 31 Mode Lock (Setting)
4128 32 Mode Lock (Status)
4129 33 Fan Lock (Setting)
4130 34 Fan Lock (Status)
4131 35 Occupancy (Setting)
4132 36 Occupancy (Status)
4133 37 2Set Cooling Set Temperature (Setting)
4134 38 2Set Cooling Set Temperature (Status)
4135 39 2Set Heating Set Temperature (Setting)
4136 40 2Set Heating Set Temperature (Status)
4137 41 2Set Cooling Upper Temperature (Setting)
4138 42 2Set Cooling Upper Temperature (Status)
4139 43 2Set Heating Upper Temperature (Setting)
4140 44 2Set Heating Upper Temperature (Status)
4141 45 2Set Cooling Lower Temperature (Setting)
4142 46 2Set Cooling Lower Temperature (Status)
4143 47 2Set Heating Lower Temperature (Setting)
4144 48 2Set Heating Lower Temperature (Status)
4145 49 Thermo Status (Status)
4146 50 Accumulated Gas Distribution (Status)
4147 51 Dust Sensor Available (Status)
4148 52 Air Cleaning Opereration (Setting)
4149 53 Air Cleaning Opereration (Status)
4150 54 Fine Dust (Status)
4151 55 Ultra Fine Dust (Status)
4152 56 Super Ultra Fine Dust (Status)
4153 57 Humidity (Status)
4154 58 Comfort Cooling Available (Status)
4155 59 Comfort Cooling Opereration (Setting)
4156 60 Comfort Cooling Opereration (Status)
4157 61 Comfort Cooling Step (Setting)
4158 62 Comfort Cooling Step (Status)
4159 63 Human Detection Available (Status)
4160 64 Human Detection Opereration (Setting)
4161 65 Human Detection Opereration (Status)
4162 66 Human Detection Wind (Setting)
4163 67 Human Detection Wind (Status)
4164 68 Human Detection Time (Setting)
4165 69 Human Detection Time (Status)
4166 70 Hotel Checkin (Setting)
4167 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_10 BO Stop(0) Start(1)
StartStopStatus_10 BI Stop(0) Start(1)
LockCommand_10 BO Permit(0) Prohibit(1)
LockStatus_10 BI Permit(0) Prohibit(1)
FilterSign_10 BI Off(0) On(1)
FilterSignReset_10 BV - Reset(1)
AirConModeCommand_10 MO Cool(1)
AirConModeStatus_10 MI Cool(1)
SwingCommand_10 BO Stop(0) Run(1)
SwingStatus_10 BI Stop(0) Run(1)
FanSpeedCommand_10 MO Low(1)
FanSpeedStatus_10 MI Low(1)
SetRoomTemp_10 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_10 AI ℃
Alarm_10 BI Normal(0) Abnormal(1)
MalfunctionCode_10 AI Refer to the
SetTempStatus_10 AI ℃
Accumulated power(100 Watt)_10 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_10 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_10 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_10 AI ℃
TempRangeLowerLimitStatus_10 AI ℃
ModeLockCommand_10 BO Permit(0) Prohibit(1)
ModeLockStatus_10 BI Permit(0) Prohibit(1)
FanLockCommand_10 BO Permit(0) Prohibit(1)
FanLockStatus_10 BI Permit(0) Prohibit(1)
OccupancyCommand_10 BO Unoccupied(0) Occupied(1)
OccupancyStatus_10 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_10 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_10 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_10 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_10 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_10 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_10 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_10 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_10 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_10 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_10 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_10 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_10 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_10 BI Off(0) On(1)
AccumulatedGas(100 Watt)_10 AI Wattage values (Unit : 100Watt)
DustSensorAvail_10 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_10 BO Stop(0) Run(1)
AirCleaningOperStatus_10 BI Stop(0) Run(1)
FineDustStatus_10 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_10 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_10 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_10 AI %
ComfortCoolingAvail_10 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_10 BO Stop(0) Run(1)
ComfortCoolingOperStatus_10 BI Stop(0) Run(1)
ComfortCoolingStepCommand_10 AV 1~3 step
ComfortCoolingStepStatus_10 AI 1~3 step
HumanDetectionAvail_10 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_10 MO Off(1)
HumanDetectionOperStatus_10 MI Off(1)
HumanDetectionWindCommand_10 MO Off(1)
HumanDetectionWindStatus_10 MI Off(1)
HumanDetectionTimeCommand_10 MO 5min(1)
HumanDetectionTimeStatus_10 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
11 ※ Dev Type AC
address

instance
point Name
number

4353 1 On/Off (Setting)


4354 2 On/Off (Status)
4355 3 Lock (Setting)
4356 4 Lock (Status)
4357 5 Filter Sign
4358 6 Filter Sign reset
4359 7 Operation Mode (Setting)
4360 8 Operation Mode (Status)
4361 9 Swing (Setting)
4362 10 Swing (Status)
4363 11 Fan Speed (Setting)
4364 12 Fan Speed (Status)
4365 13 Set Room Temperature
4366 14 Room Temperature
4367 15 Alarm
4368 16 Error Code
4371 19 Set Temperature (Status)
4372 20 Accumulated Power Distribution (Status)
4379 27 Set Upper Temperature (Setting)
4380 28 Set Lower Temperature (Setting)
4381 29 Set Upper Tempaerature (Status)
4382 30 Set Lower Temperature (Status)
4383 31 Mode Lock (Setting)
4384 32 Mode Lock (Status)
4385 33 Fan Lock (Setting)
4386 34 Fan Lock (Status)
4387 35 Occupancy (Setting)
4388 36 Occupancy (Status)
4389 37 2Set Cooling Set Temperature (Setting)
4390 38 2Set Cooling Set Temperature (Status)
4391 39 2Set Heating Set Temperature (Setting)
4392 40 2Set Heating Set Temperature (Status)
4393 41 2Set Cooling Upper Temperature (Setting)
4394 42 2Set Cooling Upper Temperature (Status)
4395 43 2Set Heating Upper Temperature (Setting)
4396 44 2Set Heating Upper Temperature (Status)
4397 45 2Set Cooling Lower Temperature (Setting)
4398 46 2Set Cooling Lower Temperature (Status)
4399 47 2Set Heating Lower Temperature (Setting)
4400 48 2Set Heating Lower Temperature (Status)
4401 49 Thermo Status (Status)
4402 50 Accumulated Gas Distribution (Status)
4403 51 Dust Sensor Available (Status)
4404 52 Air Cleaning Opereration (Setting)
4405 53 Air Cleaning Opereration (Status)
4406 54 Fine Dust (Status)
4407 55 Ultra Fine Dust (Status)
4408 56 Super Ultra Fine Dust (Status)
4409 57 Humidity (Status)
4410 58 Comfort Cooling Available (Status)
4411 59 Comfort Cooling Opereration (Setting)
4412 60 Comfort Cooling Opereration (Status)
4413 61 Comfort Cooling Step (Setting)
4414 62 Comfort Cooling Step (Status)
4415 63 Human Detection Available (Status)
4416 64 Human Detection Opereration (Setting)
4417 65 Human Detection Opereration (Status)
4418 66 Human Detection Wind (Setting)
4419 67 Human Detection Wind (Status)
4420 68 Human Detection Time (Setting)
4421 69 Human Detection Time (Status)
4422 70 Hotel Checkin (Setting)
4423 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_11 BO Stop(0) Start(1)
StartStopStatus_11 BI Stop(0) Start(1)
LockCommand_11 BO Permit(0) Prohibit(1)
LockStatus_11 BI Permit(0) Prohibit(1)
FilterSign_11 BI Off(0) On(1)
FilterSignReset_11 BV - Reset(1)
AirConModeCommand_11 MO Cool(1)
AirConModeStatus_11 MI Cool(1)
SwingCommand_11 BO Stop(0) Run(1)
SwingStatus_11 BI Stop(0) Run(1)
FanSpeedCommand_11 MO Low(1)
FanSpeedStatus_11 MI Low(1)
SetRoomTemp_11 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_11 AI ℃
Alarm_11 BI Normal(0) Abnormal(1)
MalfunctionCode_11 AI Refer to the
SetTempStatus_11 AI ℃
Accumulated power(100 Watt)_11 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_11 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_11 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_11 AI ℃
TempRangeLowerLimitStatus_11 AI ℃
ModeLockCommand_11 BO Permit(0) Prohibit(1)
ModeLockStatus_11 BI Permit(0) Prohibit(1)
FanLockCommand_11 BO Permit(0) Prohibit(1)
FanLockStatus_11 BI Permit(0) Prohibit(1)
OccupancyCommand_11 BO Unoccupied(0) Occupied(1)
OccupancyStatus_11 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_11 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_11 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_11 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_11 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_11 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_11 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_11 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_11 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_11 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_11 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_11 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_11 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_11 BI Off(0) On(1)
AccumulatedGas(100 Watt)_11 AI Wattage values (Unit : 100Watt)
DustSensorAvail_11 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_11 BO Stop(0) Run(1)
AirCleaningOperStatus_11 BI Stop(0) Run(1)
FineDustStatus_11 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_11 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_11 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_11 AI %
ComfortCoolingAvail_11 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_11 BO Stop(0) Run(1)
ComfortCoolingOperStatus_11 BI Stop(0) Run(1)
ComfortCoolingStepCommand_11 AV 1~3 step
ComfortCoolingStepStatus_11 AI 1~3 step
HumanDetectionAvail_11 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_11 MO Off(1)
HumanDetectionOperStatus_11 MI Off(1)
HumanDetectionWindCommand_11 MO Off(1)
HumanDetectionWindStatus_11 MI Off(1)
HumanDetectionTimeCommand_11 MO 5min(1)
HumanDetectionTimeStatus_11 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
12 ※ Dev Type AC
address

instance
point Name
number

4609 1 On/Off (Setting)


4610 2 On/Off (Status)
4611 3 Lock (Setting)
4612 4 Lock (Status)
4613 5 Filter Sign
4614 6 Filter Sign reset
4615 7 Operation Mode (Setting)
4616 8 Operation Mode (Status)
4617 9 Swing (Setting)
4618 10 Swing (Status)
4619 11 Fan Speed (Setting)
4620 12 Fan Speed (Status)
4621 13 Set Room Temperature
4622 14 Room Temperature
4623 15 Alarm
4624 16 Error Code
4627 19 Set Temperature (Status)
4628 20 Accumulated Power Distribution (Status)
4635 27 Set Upper Temperature (Setting)
4636 28 Set Lower Temperature (Setting)
4637 29 Set Upper Tempaerature (Status)
4638 30 Set Lower Temperature (Status)
4639 31 Mode Lock (Setting)
4640 32 Mode Lock (Status)
4641 33 Fan Lock (Setting)
4642 34 Fan Lock (Status)
4643 35 Occupancy (Setting)
4644 36 Occupancy (Status)
4645 37 2Set Cooling Set Temperature (Setting)
4646 38 2Set Cooling Set Temperature (Status)
4647 39 2Set Heating Set Temperature (Setting)
4648 40 2Set Heating Set Temperature (Status)
4649 41 2Set Cooling Upper Temperature (Setting)
4650 42 2Set Cooling Upper Temperature (Status)
4651 43 2Set Heating Upper Temperature (Setting)
4652 44 2Set Heating Upper Temperature (Status)
4653 45 2Set Cooling Lower Temperature (Setting)
4654 46 2Set Cooling Lower Temperature (Status)
4655 47 2Set Heating Lower Temperature (Setting)
4656 48 2Set Heating Lower Temperature (Status)
4657 49 Thermo Status (Status)
4658 50 Accumulated Gas Distribution (Status)
4659 51 Dust Sensor Available (Status)
4660 52 Air Cleaning Opereration (Setting)
4661 53 Air Cleaning Opereration (Status)
4662 54 Fine Dust (Status)
4663 55 Ultra Fine Dust (Status)
4664 56 Super Ultra Fine Dust (Status)
4665 57 Humidity (Status)
4666 58 Comfort Cooling Available (Status)
4667 59 Comfort Cooling Opereration (Setting)
4668 60 Comfort Cooling Opereration (Status)
4669 61 Comfort Cooling Step (Setting)
4670 62 Comfort Cooling Step (Status)
4671 63 Human Detection Available (Status)
4672 64 Human Detection Opereration (Setting)
4673 65 Human Detection Opereration (Status)
4674 66 Human Detection Wind (Setting)
4675 67 Human Detection Wind (Status)
4676 68 Human Detection Time (Setting)
4677 69 Human Detection Time (Status)
4678 70 Hotel Checkin (Setting)
4679 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_12 BO Stop(0) Start(1)
StartStopStatus_12 BI Stop(0) Start(1)
LockCommand_12 BO Permit(0) Prohibit(1)
LockStatus_12 BI Permit(0) Prohibit(1)
FilterSign_12 BI Off(0) On(1)
FilterSignReset_12 BV - Reset(1)
AirConModeCommand_12 MO Cool(1)
AirConModeStatus_12 MI Cool(1)
SwingCommand_12 BO Stop(0) Run(1)
SwingStatus_12 BI Stop(0) Run(1)
FanSpeedCommand_12 MO Low(1)
FanSpeedStatus_12 MI Low(1)
SetRoomTemp_12 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_12 AI ℃
Alarm_12 BI Normal(0) Abnormal(1)
MalfunctionCode_12 AI Refer to the
SetTempStatus_12 AI ℃
Accumulated power(100 Watt)_12 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_12 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_12 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_12 AI ℃
TempRangeLowerLimitStatus_12 AI ℃
ModeLockCommand_12 BO Permit(0) Prohibit(1)
ModeLockStatus_12 BI Permit(0) Prohibit(1)
FanLockCommand_12 BO Permit(0) Prohibit(1)
FanLockStatus_12 BI Permit(0) Prohibit(1)
OccupancyCommand_12 BO Unoccupied(0) Occupied(1)
OccupancyStatus_12 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_12 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_12 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_12 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_12 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_12 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_12 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_12 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_12 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_12 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_12 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_12 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_12 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_12 BI Off(0) On(1)
AccumulatedGas(100 Watt)_12 AI Wattage values (Unit : 100Watt)
DustSensorAvail_12 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_12 BO Stop(0) Run(1)
AirCleaningOperStatus_12 BI Stop(0) Run(1)
FineDustStatus_12 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_12 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_12 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_12 AI %
ComfortCoolingAvail_12 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_12 BO Stop(0) Run(1)
ComfortCoolingOperStatus_12 BI Stop(0) Run(1)
ComfortCoolingStepCommand_12 AV 1~3 step
ComfortCoolingStepStatus_12 AI 1~3 step
HumanDetectionAvail_12 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_12 MO Off(1)
HumanDetectionOperStatus_12 MI Off(1)
HumanDetectionWindCommand_12 MO Off(1)
HumanDetectionWindStatus_12 MI Off(1)
HumanDetectionTimeCommand_12 MO 5min(1)
HumanDetectionTimeStatus_12 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
13 ※ Dev Type AC
address

instance
point Name
number

4865 1 On/Off (Setting)


4866 2 On/Off (Status)
4867 3 Lock (Setting)
4868 4 Lock (Status)
4869 5 Filter Sign
4870 6 Filter Sign reset
4871 7 Operation Mode (Setting)
4872 8 Operation Mode (Status)
4873 9 Swing (Setting)
4874 10 Swing (Status)
4875 11 Fan Speed (Setting)
4876 12 Fan Speed (Status)
4877 13 Set Room Temperature
4878 14 Room Temperature
4879 15 Alarm
4880 16 Error Code
4883 19 Set Temperature (Status)
4884 20 Accumulated Power Distribution (Status)
4891 27 Set Upper Temperature (Setting)
4892 28 Set Lower Temperature (Setting)
4893 29 Set Upper Tempaerature (Status)
4894 30 Set Lower Temperature (Status)
4895 31 Mode Lock (Setting)
4896 32 Mode Lock (Status)
4897 33 Fan Lock (Setting)
4898 34 Fan Lock (Status)
4899 35 Occupancy (Setting)
4900 36 Occupancy (Status)
4901 37 2Set Cooling Set Temperature (Setting)
4902 38 2Set Cooling Set Temperature (Status)
4903 39 2Set Heating Set Temperature (Setting)
4904 40 2Set Heating Set Temperature (Status)
4905 41 2Set Cooling Upper Temperature (Setting)
4906 42 2Set Cooling Upper Temperature (Status)
4907 43 2Set Heating Upper Temperature (Setting)
4908 44 2Set Heating Upper Temperature (Status)
4909 45 2Set Cooling Lower Temperature (Setting)
4910 46 2Set Cooling Lower Temperature (Status)
4911 47 2Set Heating Lower Temperature (Setting)
4912 48 2Set Heating Lower Temperature (Status)
4913 49 Thermo Status (Status)
4914 50 Accumulated Gas Distribution (Status)
4915 51 Dust Sensor Available (Status)
4916 52 Air Cleaning Opereration (Setting)
4917 53 Air Cleaning Opereration (Status)
4918 54 Fine Dust (Status)
4919 55 Ultra Fine Dust (Status)
4920 56 Super Ultra Fine Dust (Status)
4921 57 Humidity (Status)
4922 58 Comfort Cooling Available (Status)
4923 59 Comfort Cooling Opereration (Setting)
4924 60 Comfort Cooling Opereration (Status)
4925 61 Comfort Cooling Step (Setting)
4926 62 Comfort Cooling Step (Status)
4927 63 Human Detection Available (Status)
4928 64 Human Detection Opereration (Setting)
4929 65 Human Detection Opereration (Status)
4930 66 Human Detection Wind (Setting)
4931 67 Human Detection Wind (Status)
4932 68 Human Detection Time (Setting)
4933 69 Human Detection Time (Status)
4934 70 Hotel Checkin (Setting)
4935 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_13 BO Stop(0) Start(1)
StartStopStatus_13 BI Stop(0) Start(1)
LockCommand_13 BO Permit(0) Prohibit(1)
LockStatus_13 BI Permit(0) Prohibit(1)
FilterSign_13 BI Off(0) On(1)
FilterSignReset_13 BV - Reset(1)
AirConModeCommand_13 MO Cool(1)
AirConModeStatus_13 MI Cool(1)
SwingCommand_13 BO Stop(0) Run(1)
SwingStatus_13 BI Stop(0) Run(1)
FanSpeedCommand_13 MO Low(1)
FanSpeedStatus_13 MI Low(1)
SetRoomTemp_13 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_13 AI ℃
Alarm_13 BI Normal(0) Abnormal(1)
MalfunctionCode_13 AI Refer to the
SetTempStatus_13 AI ℃
Accumulated power(100 Watt)_13 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_13 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_13 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_13 AI ℃
TempRangeLowerLimitStatus_13 AI ℃
ModeLockCommand_13 BO Permit(0) Prohibit(1)
ModeLockStatus_13 BI Permit(0) Prohibit(1)
FanLockCommand_13 BO Permit(0) Prohibit(1)
FanLockStatus_13 BI Permit(0) Prohibit(1)
OccupancyCommand_13 BO Unoccupied(0) Occupied(1)
OccupancyStatus_13 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_13 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_13 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_13 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_13 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_13 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_13 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_13 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_13 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_13 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_13 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_13 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_13 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_13 BI Off(0) On(1)
AccumulatedGas(100 Watt)_13 AI Wattage values (Unit : 100Watt)
DustSensorAvail_13 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_13 BO Stop(0) Run(1)
AirCleaningOperStatus_13 BI Stop(0) Run(1)
FineDustStatus_13 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_13 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_13 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_13 AI %
ComfortCoolingAvail_13 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_13 BO Stop(0) Run(1)
ComfortCoolingOperStatus_13 BI Stop(0) Run(1)
ComfortCoolingStepCommand_13 AV 1~3 step
ComfortCoolingStepStatus_13 AI 1~3 step
HumanDetectionAvail_13 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_13 MO Off(1)
HumanDetectionOperStatus_13 MI Off(1)
HumanDetectionWindCommand_13 MO Off(1)
HumanDetectionWindStatus_13 MI Off(1)
HumanDetectionTimeCommand_13 MO 5min(1)
HumanDetectionTimeStatus_13 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
14 ※ Dev Type AC
address

instance
point Name
number

5121 1 On/Off (Setting)


5122 2 On/Off (Status)
5123 3 Lock (Setting)
5124 4 Lock (Status)
5125 5 Filter Sign
5126 6 Filter Sign reset
5127 7 Operation Mode (Setting)
5128 8 Operation Mode (Status)
5129 9 Swing (Setting)
5130 10 Swing (Status)
5131 11 Fan Speed (Setting)
5132 12 Fan Speed (Status)
5133 13 Set Room Temperature
5134 14 Room Temperature
5135 15 Alarm
5136 16 Error Code
5139 19 Set Temperature (Status)
5140 20 Accumulated Power Distribution (Status)
5147 27 Set Upper Temperature (Setting)
5148 28 Set Lower Temperature (Setting)
5149 29 Set Upper Tempaerature (Status)
5150 30 Set Lower Temperature (Status)
5151 31 Mode Lock (Setting)
5152 32 Mode Lock (Status)
5153 33 Fan Lock (Setting)
5154 34 Fan Lock (Status)
5155 35 Occupancy (Setting)
5156 36 Occupancy (Status)
5157 37 2Set Cooling Set Temperature (Setting)
5158 38 2Set Cooling Set Temperature (Status)
5159 39 2Set Heating Set Temperature (Setting)
5160 40 2Set Heating Set Temperature (Status)
5161 41 2Set Cooling Upper Temperature (Setting)
5162 42 2Set Cooling Upper Temperature (Status)
5163 43 2Set Heating Upper Temperature (Setting)
5164 44 2Set Heating Upper Temperature (Status)
5165 45 2Set Cooling Lower Temperature (Setting)
5166 46 2Set Cooling Lower Temperature (Status)
5167 47 2Set Heating Lower Temperature (Setting)
5168 48 2Set Heating Lower Temperature (Status)
5169 49 Thermo Status (Status)
5170 50 Accumulated Gas Distribution (Status)
5171 51 Dust Sensor Available (Status)
5172 52 Air Cleaning Opereration (Setting)
5173 53 Air Cleaning Opereration (Status)
5174 54 Fine Dust (Status)
5175 55 Ultra Fine Dust (Status)
5176 56 Super Ultra Fine Dust (Status)
5177 57 Humidity (Status)
5178 58 Comfort Cooling Available (Status)
5179 59 Comfort Cooling Opereration (Setting)
5180 60 Comfort Cooling Opereration (Status)
5181 61 Comfort Cooling Step (Setting)
5182 62 Comfort Cooling Step (Status)
5183 63 Human Detection Available (Status)
5184 64 Human Detection Opereration (Setting)
5185 65 Human Detection Opereration (Status)
5186 66 Human Detection Wind (Setting)
5187 67 Human Detection Wind (Status)
5188 68 Human Detection Time (Setting)
5189 69 Human Detection Time (Status)
5190 70 Hotel Checkin (Setting)
5191 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_14 BO Stop(0) Start(1)
StartStopStatus_14 BI Stop(0) Start(1)
LockCommand_14 BO Permit(0) Prohibit(1)
LockStatus_14 BI Permit(0) Prohibit(1)
FilterSign_14 BI Off(0) On(1)
FilterSignReset_14 BV - Reset(1)
AirConModeCommand_14 MO Cool(1)
AirConModeStatus_14 MI Cool(1)
SwingCommand_14 BO Stop(0) Run(1)
SwingStatus_14 BI Stop(0) Run(1)
FanSpeedCommand_14 MO Low(1)
FanSpeedStatus_14 MI Low(1)
SetRoomTemp_14 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_14 AI ℃
Alarm_14 BI Normal(0) Abnormal(1)
MalfunctionCode_14 AI Refer to the
SetTempStatus_14 AI ℃
Accumulated power(100 Watt)_14 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_14 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_14 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_14 AI ℃
TempRangeLowerLimitStatus_14 AI ℃
ModeLockCommand_14 BO Permit(0) Prohibit(1)
ModeLockStatus_14 BI Permit(0) Prohibit(1)
FanLockCommand_14 BO Permit(0) Prohibit(1)
FanLockStatus_14 BI Permit(0) Prohibit(1)
OccupancyCommand_14 BO Unoccupied(0) Occupied(1)
OccupancyStatus_14 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_14 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_14 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_14 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_14 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_14 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_14 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_14 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_14 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_14 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_14 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_14 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_14 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_14 BI Off(0) On(1)
AccumulatedGas(100 Watt)_14 AI Wattage values (Unit : 100Watt)
DustSensorAvail_14 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_14 BO Stop(0) Run(1)
AirCleaningOperStatus_14 BI Stop(0) Run(1)
FineDustStatus_14 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_14 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_14 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_14 AI %
ComfortCoolingAvail_14 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_14 BO Stop(0) Run(1)
ComfortCoolingOperStatus_14 BI Stop(0) Run(1)
ComfortCoolingStepCommand_14 AV 1~3 step
ComfortCoolingStepStatus_14 AI 1~3 step
HumanDetectionAvail_14 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_14 MO Off(1)
HumanDetectionOperStatus_14 MI Off(1)
HumanDetectionWindCommand_14 MO Off(1)
HumanDetectionWindStatus_14 MI Off(1)
HumanDetectionTimeCommand_14 MO 5min(1)
HumanDetectionTimeStatus_14 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
15 ※ Dev Type AC
address

instance
point Name
number

5377 1 On/Off (Setting)


5378 2 On/Off (Status)
5379 3 Lock (Setting)
5380 4 Lock (Status)
5381 5 Filter Sign
5382 6 Filter Sign reset
5383 7 Operation Mode (Setting)
5384 8 Operation Mode (Status)
5385 9 Swing (Setting)
5386 10 Swing (Status)
5387 11 Fan Speed (Setting)
5388 12 Fan Speed (Status)
5389 13 Set Room Temperature
5390 14 Room Temperature
5391 15 Alarm
5392 16 Error Code
5395 19 Set Temperature (Status)
5396 20 Accumulated Power Distribution (Status)
5403 27 Set Upper Temperature (Setting)
5404 28 Set Lower Temperature (Setting)
5405 29 Set Upper Tempaerature (Status)
5406 30 Set Lower Temperature (Status)
5407 31 Mode Lock (Setting)
5408 32 Mode Lock (Status)
5409 33 Fan Lock (Setting)
5410 34 Fan Lock (Status)
5411 35 Occupancy (Setting)
5412 36 Occupancy (Status)
5413 37 2Set Cooling Set Temperature (Setting)
5414 38 2Set Cooling Set Temperature (Status)
5415 39 2Set Heating Set Temperature (Setting)
5416 40 2Set Heating Set Temperature (Status)
5417 41 2Set Cooling Upper Temperature (Setting)
5418 42 2Set Cooling Upper Temperature (Status)
5419 43 2Set Heating Upper Temperature (Setting)
5420 44 2Set Heating Upper Temperature (Status)
5421 45 2Set Cooling Lower Temperature (Setting)
5422 46 2Set Cooling Lower Temperature (Status)
5423 47 2Set Heating Lower Temperature (Setting)
5424 48 2Set Heating Lower Temperature (Status)
5425 49 Thermo Status (Status)
5426 50 Accumulated Gas Distribution (Status)
5427 51 Dust Sensor Available (Status)
5428 52 Air Cleaning Opereration (Setting)
5429 53 Air Cleaning Opereration (Status)
5430 54 Fine Dust (Status)
5431 55 Ultra Fine Dust (Status)
5432 56 Super Ultra Fine Dust (Status)
5433 57 Humidity (Status)
5434 58 Comfort Cooling Available (Status)
5435 59 Comfort Cooling Opereration (Setting)
5436 60 Comfort Cooling Opereration (Status)
5437 61 Comfort Cooling Step (Setting)
5438 62 Comfort Cooling Step (Status)
5439 63 Human Detection Available (Status)
5440 64 Human Detection Opereration (Setting)
5441 65 Human Detection Opereration (Status)
5442 66 Human Detection Wind (Setting)
5443 67 Human Detection Wind (Status)
5444 68 Human Detection Time (Setting)
5445 69 Human Detection Time (Status)
5446 70 Hotel Checkin (Setting)
5447 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_15 BO Stop(0) Start(1)
StartStopStatus_15 BI Stop(0) Start(1)
LockCommand_15 BO Permit(0) Prohibit(1)
LockStatus_15 BI Permit(0) Prohibit(1)
FilterSign_15 BI Off(0) On(1)
FilterSignReset_15 BV - Reset(1)
AirConModeCommand_15 MO Cool(1)
AirConModeStatus_15 MI Cool(1)
SwingCommand_15 BO Stop(0) Run(1)
SwingStatus_15 BI Stop(0) Run(1)
FanSpeedCommand_15 MO Low(1)
FanSpeedStatus_15 MI Low(1)
SetRoomTemp_15 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_15 AI ℃
Alarm_15 BI Normal(0) Abnormal(1)
MalfunctionCode_15 AI Refer to the
SetTempStatus_15 AI ℃
Accumulated power(100 Watt)_15 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_15 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_15 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_15 AI ℃
TempRangeLowerLimitStatus_15 AI ℃
ModeLockCommand_15 BO Permit(0) Prohibit(1)
ModeLockStatus_15 BI Permit(0) Prohibit(1)
FanLockCommand_15 BO Permit(0) Prohibit(1)
FanLockStatus_15 BI Permit(0) Prohibit(1)
OccupancyCommand_15 BO Unoccupied(0) Occupied(1)
OccupancyStatus_15 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_15 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_15 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_15 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_15 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_15 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_15 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_15 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_15 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_15 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_15 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_15 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_15 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_15 BI Off(0) On(1)
AccumulatedGas(100 Watt)_15 AI Wattage values (Unit : 100Watt)
DustSensorAvail_15 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_15 BO Stop(0) Run(1)
AirCleaningOperStatus_15 BI Stop(0) Run(1)
FineDustStatus_15 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_15 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_15 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_15 AI %
ComfortCoolingAvail_15 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_15 BO Stop(0) Run(1)
ComfortCoolingOperStatus_15 BI Stop(0) Run(1)
ComfortCoolingStepCommand_15 AV 1~3 step
ComfortCoolingStepStatus_15 AI 1~3 step
HumanDetectionAvail_15 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_15 MO Off(1)
HumanDetectionOperStatus_15 MI Off(1)
HumanDetectionWindCommand_15 MO Off(1)
HumanDetectionWindStatus_15 MI Off(1)
HumanDetectionTimeCommand_15 MO 5min(1)
HumanDetectionTimeStatus_15 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
16 ※ Dev Type AC
address

instance
point Name
number

5633 1 On/Off (Setting)


5634 2 On/Off (Status)
5635 3 Lock (Setting)
5636 4 Lock (Status)
5637 5 Filter Sign
5638 6 Filter Sign reset
5639 7 Operation Mode (Setting)
5640 8 Operation Mode (Status)
5641 9 Swing (Setting)
5642 10 Swing (Status)
5643 11 Fan Speed (Setting)
5644 12 Fan Speed (Status)
5645 13 Set Room Temperature
5646 14 Room Temperature
5647 15 Alarm
5648 16 Error Code
5651 19 Set Temperature (Status)
5652 20 Accumulated Power Distribution (Status)
5659 27 Set Upper Temperature (Setting)
5660 28 Set Lower Temperature (Setting)
5661 29 Set Upper Tempaerature (Status)
5662 30 Set Lower Temperature (Status)
5663 31 Mode Lock (Setting)
5664 32 Mode Lock (Status)
5665 33 Fan Lock (Setting)
5666 34 Fan Lock (Status)
5667 35 Occupancy (Setting)
5668 36 Occupancy (Status)
5669 37 2Set Cooling Set Temperature (Setting)
5670 38 2Set Cooling Set Temperature (Status)
5671 39 2Set Heating Set Temperature (Setting)
5672 40 2Set Heating Set Temperature (Status)
5673 41 2Set Cooling Upper Temperature (Setting)
5674 42 2Set Cooling Upper Temperature (Status)
5675 43 2Set Heating Upper Temperature (Setting)
5676 44 2Set Heating Upper Temperature (Status)
5677 45 2Set Cooling Lower Temperature (Setting)
5678 46 2Set Cooling Lower Temperature (Status)
5679 47 2Set Heating Lower Temperature (Setting)
5680 48 2Set Heating Lower Temperature (Status)
5681 49 Thermo Status (Status)
5682 50 Accumulated Gas Distribution (Status)
5683 51 Dust Sensor Available (Status)
5684 52 Air Cleaning Opereration (Setting)
5685 53 Air Cleaning Opereration (Status)
5686 54 Fine Dust (Status)
5687 55 Ultra Fine Dust (Status)
5688 56 Super Ultra Fine Dust (Status)
5689 57 Humidity (Status)
5690 58 Comfort Cooling Available (Status)
5691 59 Comfort Cooling Opereration (Setting)
5692 60 Comfort Cooling Opereration (Status)
5693 61 Comfort Cooling Step (Setting)
5694 62 Comfort Cooling Step (Status)
5695 63 Human Detection Available (Status)
5696 64 Human Detection Opereration (Setting)
5697 65 Human Detection Opereration (Status)
5698 66 Human Detection Wind (Setting)
5699 67 Human Detection Wind (Status)
5700 68 Human Detection Time (Setting)
5701 69 Human Detection Time (Status)
5702 70 Hotel Checkin (Setting)
5703 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_16 BO Stop(0) Start(1)
StartStopStatus_16 BI Stop(0) Start(1)
LockCommand_16 BO Permit(0) Prohibit(1)
LockStatus_16 BI Permit(0) Prohibit(1)
FilterSign_16 BI Off(0) On(1)
FilterSignReset_16 BV - Reset(1)
AirConModeCommand_16 MO Cool(1)
AirConModeStatus_16 MI Cool(1)
SwingCommand_16 BO Stop(0) Run(1)
SwingStatus_16 BI Stop(0) Run(1)
FanSpeedCommand_16 MO Low(1)
FanSpeedStatus_16 MI Low(1)
SetRoomTemp_16 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_16 AI ℃
Alarm_16 BI Normal(0) Abnormal(1)
MalfunctionCode_16 AI Refer to the
SetTempStatus_16 AI ℃
Accumulated power(100 Watt)_16 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_16 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_16 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_16 AI ℃
TempRangeLowerLimitStatus_16 AI ℃
ModeLockCommand_16 BO Permit(0) Prohibit(1)
ModeLockStatus_16 BI Permit(0) Prohibit(1)
FanLockCommand_16 BO Permit(0) Prohibit(1)
FanLockStatus_16 BI Permit(0) Prohibit(1)
OccupancyCommand_16 BO Unoccupied(0) Occupied(1)
OccupancyStatus_16 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_16 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_16 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_16 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_16 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_16 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_16 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_16 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_16 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_16 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_16 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_16 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_16 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_16 BI Off(0) On(1)
AccumulatedGas(100 Watt)_16 AI Wattage values (Unit : 100Watt)
DustSensorAvail_16 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_16 BO Stop(0) Run(1)
AirCleaningOperStatus_16 BI Stop(0) Run(1)
FineDustStatus_16 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_16 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_16 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_16 AI %
ComfortCoolingAvail_16 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_16 BO Stop(0) Run(1)
ComfortCoolingOperStatus_16 BI Stop(0) Run(1)
ComfortCoolingStepCommand_16 AV 1~3 step
ComfortCoolingStepStatus_16 AI 1~3 step
HumanDetectionAvail_16 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_16 MO Off(1)
HumanDetectionOperStatus_16 MI Off(1)
HumanDetectionWindCommand_16 MO Off(1)
HumanDetectionWindStatus_16 MI Off(1)
HumanDetectionTimeCommand_16 MO 5min(1)
HumanDetectionTimeStatus_16 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
17 ※ Dev Type AC
address

instance
point Name
number

5889 1 On/Off (Setting)


5890 2 On/Off (Status)
5891 3 Lock (Setting)
5892 4 Lock (Status)
5893 5 Filter Sign
5894 6 Filter Sign reset
5895 7 Operation Mode (Setting)
5896 8 Operation Mode (Status)
5897 9 Swing (Setting)
5898 10 Swing (Status)
5899 11 Fan Speed (Setting)
5900 12 Fan Speed (Status)
5901 13 Set Room Temperature
5902 14 Room Temperature
5903 15 Alarm
5904 16 Error Code
5907 19 Set Temperature (Status)
5908 20 Accumulated Power Distribution (Status)
5915 27 Set Upper Temperature (Setting)
5916 28 Set Lower Temperature (Setting)
5917 29 Set Upper Tempaerature (Status)
5918 30 Set Lower Temperature (Status)
5919 31 Mode Lock (Setting)
5920 32 Mode Lock (Status)
5921 33 Fan Lock (Setting)
5922 34 Fan Lock (Status)
5923 35 Occupancy (Setting)
5924 36 Occupancy (Status)
5925 37 2Set Cooling Set Temperature (Setting)
5926 38 2Set Cooling Set Temperature (Status)
5927 39 2Set Heating Set Temperature (Setting)
5928 40 2Set Heating Set Temperature (Status)
5929 41 2Set Cooling Upper Temperature (Setting)
5930 42 2Set Cooling Upper Temperature (Status)
5931 43 2Set Heating Upper Temperature (Setting)
5932 44 2Set Heating Upper Temperature (Status)
5933 45 2Set Cooling Lower Temperature (Setting)
5934 46 2Set Cooling Lower Temperature (Status)
5935 47 2Set Heating Lower Temperature (Setting)
5936 48 2Set Heating Lower Temperature (Status)
5937 49 Thermo Status (Status)
5938 50 Accumulated Gas Distribution (Status)
5939 51 Dust Sensor Available (Status)
5940 52 Air Cleaning Opereration (Setting)
5941 53 Air Cleaning Opereration (Status)
5942 54 Fine Dust (Status)
5943 55 Ultra Fine Dust (Status)
5944 56 Super Ultra Fine Dust (Status)
5945 57 Humidity (Status)
5946 58 Comfort Cooling Available (Status)
5947 59 Comfort Cooling Opereration (Setting)
5948 60 Comfort Cooling Opereration (Status)
5949 61 Comfort Cooling Step (Setting)
5950 62 Comfort Cooling Step (Status)
5951 63 Human Detection Available (Status)
5952 64 Human Detection Opereration (Setting)
5953 65 Human Detection Opereration (Status)
5954 66 Human Detection Wind (Setting)
5955 67 Human Detection Wind (Status)
5956 68 Human Detection Time (Setting)
5957 69 Human Detection Time (Status)
5958 70 Hotel Checkin (Setting)
5959 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_17 BO Stop(0) Start(1)
StartStopStatus_17 BI Stop(0) Start(1)
LockCommand_17 BO Permit(0) Prohibit(1)
LockStatus_17 BI Permit(0) Prohibit(1)
FilterSign_17 BI Off(0) On(1)
FilterSignReset_17 BV - Reset(1)
AirConModeCommand_17 MO Cool(1)
AirConModeStatus_17 MI Cool(1)
SwingCommand_17 BO Stop(0) Run(1)
SwingStatus_17 BI Stop(0) Run(1)
FanSpeedCommand_17 MO Low(1)
FanSpeedStatus_17 MI Low(1)
SetRoomTemp_17 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_17 AI ℃
Alarm_17 BI Normal(0) Abnormal(1)
MalfunctionCode_17 AI Refer to the
SetTempStatus_17 AI ℃
Accumulated power(100 Watt)_17 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_17 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_17 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_17 AI ℃
TempRangeLowerLimitStatus_17 AI ℃
ModeLockCommand_17 BO Permit(0) Prohibit(1)
ModeLockStatus_17 BI Permit(0) Prohibit(1)
FanLockCommand_17 BO Permit(0) Prohibit(1)
FanLockStatus_17 BI Permit(0) Prohibit(1)
OccupancyCommand_17 BO Unoccupied(0) Occupied(1)
OccupancyStatus_17 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_17 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_17 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_17 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_17 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_17 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_17 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_17 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_17 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_17 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_17 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_17 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_17 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_17 BI Off(0) On(1)
AccumulatedGas(100 Watt)_17 AI Wattage values (Unit : 100Watt)
DustSensorAvail_17 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_17 BO Stop(0) Run(1)
AirCleaningOperStatus_17 BI Stop(0) Run(1)
FineDustStatus_17 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_17 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_17 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_17 AI %
ComfortCoolingAvail_17 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_17 BO Stop(0) Run(1)
ComfortCoolingOperStatus_17 BI Stop(0) Run(1)
ComfortCoolingStepCommand_17 AV 1~3 step
ComfortCoolingStepStatus_17 AI 1~3 step
HumanDetectionAvail_17 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_17 MO Off(1)
HumanDetectionOperStatus_17 MI Off(1)
HumanDetectionWindCommand_17 MO Off(1)
HumanDetectionWindStatus_17 MI Off(1)
HumanDetectionTimeCommand_17 MO 5min(1)
HumanDetectionTimeStatus_17 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
18 ※ Dev Type AC
address

instance
point Name
number

6145 1 On/Off (Setting)


6146 2 On/Off (Status)
6147 3 Lock (Setting)
6148 4 Lock (Status)
6149 5 Filter Sign
6150 6 Filter Sign reset
6151 7 Operation Mode (Setting)
6152 8 Operation Mode (Status)
6153 9 Swing (Setting)
6154 10 Swing (Status)
6155 11 Fan Speed (Setting)
6156 12 Fan Speed (Status)
6157 13 Set Room Temperature
6158 14 Room Temperature
6159 15 Alarm
6160 16 Error Code
6163 19 Set Temperature (Status)
6164 20 Accumulated Power Distribution (Status)
6171 27 Set Upper Temperature (Setting)
6172 28 Set Lower Temperature (Setting)
6173 29 Set Upper Tempaerature (Status)
6174 30 Set Lower Temperature (Status)
6175 31 Mode Lock (Setting)
6176 32 Mode Lock (Status)
6177 33 Fan Lock (Setting)
6178 34 Fan Lock (Status)
6179 35 Occupancy (Setting)
6180 36 Occupancy (Status)
6181 37 2Set Cooling Set Temperature (Setting)
6182 38 2Set Cooling Set Temperature (Status)
6183 39 2Set Heating Set Temperature (Setting)
6184 40 2Set Heating Set Temperature (Status)
6185 41 2Set Cooling Upper Temperature (Setting)
6186 42 2Set Cooling Upper Temperature (Status)
6187 43 2Set Heating Upper Temperature (Setting)
6188 44 2Set Heating Upper Temperature (Status)
6189 45 2Set Cooling Lower Temperature (Setting)
6190 46 2Set Cooling Lower Temperature (Status)
6191 47 2Set Heating Lower Temperature (Setting)
6192 48 2Set Heating Lower Temperature (Status)
6193 49 Thermo Status (Status)
6194 50 Accumulated Gas Distribution (Status)
6195 51 Dust Sensor Available (Status)
6196 52 Air Cleaning Opereration (Setting)
6197 53 Air Cleaning Opereration (Status)
6198 54 Fine Dust (Status)
6199 55 Ultra Fine Dust (Status)
6200 56 Super Ultra Fine Dust (Status)
6201 57 Humidity (Status)
6202 58 Comfort Cooling Available (Status)
6203 59 Comfort Cooling Opereration (Setting)
6204 60 Comfort Cooling Opereration (Status)
6205 61 Comfort Cooling Step (Setting)
6206 62 Comfort Cooling Step (Status)
6207 63 Human Detection Available (Status)
6208 64 Human Detection Opereration (Setting)
6209 65 Human Detection Opereration (Status)
6210 66 Human Detection Wind (Setting)
6211 67 Human Detection Wind (Status)
6212 68 Human Detection Time (Setting)
6213 69 Human Detection Time (Status)
6214 70 Hotel Checkin (Setting)
6215 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_18 BO Stop(0) Start(1)
StartStopStatus_18 BI Stop(0) Start(1)
LockCommand_18 BO Permit(0) Prohibit(1)
LockStatus_18 BI Permit(0) Prohibit(1)
FilterSign_18 BI Off(0) On(1)
FilterSignReset_18 BV - Reset(1)
AirConModeCommand_18 MO Cool(1)
AirConModeStatus_18 MI Cool(1)
SwingCommand_18 BO Stop(0) Run(1)
SwingStatus_18 BI Stop(0) Run(1)
FanSpeedCommand_18 MO Low(1)
FanSpeedStatus_18 MI Low(1)
SetRoomTemp_18 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_18 AI ℃
Alarm_18 BI Normal(0) Abnormal(1)
MalfunctionCode_18 AI Refer to the
SetTempStatus_18 AI ℃
Accumulated power(100 Watt)_18 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_18 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_18 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_18 AI ℃
TempRangeLowerLimitStatus_18 AI ℃
ModeLockCommand_18 BO Permit(0) Prohibit(1)
ModeLockStatus_18 BI Permit(0) Prohibit(1)
FanLockCommand_18 BO Permit(0) Prohibit(1)
FanLockStatus_18 BI Permit(0) Prohibit(1)
OccupancyCommand_18 BO Unoccupied(0) Occupied(1)
OccupancyStatus_18 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_18 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_18 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_18 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_18 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_18 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_18 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_18 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_18 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_18 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_18 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_18 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_18 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_18 BI Off(0) On(1)
AccumulatedGas(100 Watt)_18 AI Wattage values (Unit : 100Watt)
DustSensorAvail_18 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_18 BO Stop(0) Run(1)
AirCleaningOperStatus_18 BI Stop(0) Run(1)
FineDustStatus_18 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_18 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_18 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_18 AI %
ComfortCoolingAvail_18 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_18 BO Stop(0) Run(1)
ComfortCoolingOperStatus_18 BI Stop(0) Run(1)
ComfortCoolingStepCommand_18 AV 1~3 step
ComfortCoolingStepStatus_18 AI 1~3 step
HumanDetectionAvail_18 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_18 MO Off(1)
HumanDetectionOperStatus_18 MI Off(1)
HumanDetectionWindCommand_18 MO Off(1)
HumanDetectionWindStatus_18 MI Off(1)
HumanDetectionTimeCommand_18 MO 5min(1)
HumanDetectionTimeStatus_18 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
19 ※ Dev Type AC
address

instance
point Name
number

6401 1 On/Off (Setting)


6402 2 On/Off (Status)
6403 3 Lock (Setting)
6404 4 Lock (Status)
6405 5 Filter Sign
6406 6 Filter Sign reset
6407 7 Operation Mode (Setting)
6408 8 Operation Mode (Status)
6409 9 Swing (Setting)
6410 10 Swing (Status)
6411 11 Fan Speed (Setting)
6412 12 Fan Speed (Status)
6413 13 Set Room Temperature
6414 14 Room Temperature
6415 15 Alarm
6416 16 Error Code
6419 19 Set Temperature (Status)
6420 20 Accumulated Power Distribution (Status)
6427 27 Set Upper Temperature (Setting)
6428 28 Set Lower Temperature (Setting)
6429 29 Set Upper Tempaerature (Status)
6430 30 Set Lower Temperature (Status)
6431 31 Mode Lock (Setting)
6432 32 Mode Lock (Status)
6433 33 Fan Lock (Setting)
6434 34 Fan Lock (Status)
6435 35 Occupancy (Setting)
6436 36 Occupancy (Status)
6437 37 2Set Cooling Set Temperature (Setting)
6438 38 2Set Cooling Set Temperature (Status)
6439 39 2Set Heating Set Temperature (Setting)
6440 40 2Set Heating Set Temperature (Status)
6441 41 2Set Cooling Upper Temperature (Setting)
6442 42 2Set Cooling Upper Temperature (Status)
6443 43 2Set Heating Upper Temperature (Setting)
6444 44 2Set Heating Upper Temperature (Status)
6445 45 2Set Cooling Lower Temperature (Setting)
6446 46 2Set Cooling Lower Temperature (Status)
6447 47 2Set Heating Lower Temperature (Setting)
6448 48 2Set Heating Lower Temperature (Status)
6449 49 Thermo Status (Status)
6450 50 Accumulated Gas Distribution (Status)
6451 51 Dust Sensor Available (Status)
6452 52 Air Cleaning Opereration (Setting)
6453 53 Air Cleaning Opereration (Status)
6454 54 Fine Dust (Status)
6455 55 Ultra Fine Dust (Status)
6456 56 Super Ultra Fine Dust (Status)
6457 57 Humidity (Status)
6458 58 Comfort Cooling Available (Status)
6459 59 Comfort Cooling Opereration (Setting)
6460 60 Comfort Cooling Opereration (Status)
6461 61 Comfort Cooling Step (Setting)
6462 62 Comfort Cooling Step (Status)
6463 63 Human Detection Available (Status)
6464 64 Human Detection Opereration (Setting)
6465 65 Human Detection Opereration (Status)
6466 66 Human Detection Wind (Setting)
6467 67 Human Detection Wind (Status)
6468 68 Human Detection Time (Setting)
6469 69 Human Detection Time (Status)
6470 70 Hotel Checkin (Setting)
6471 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_19 BO Stop(0) Start(1)
StartStopStatus_19 BI Stop(0) Start(1)
LockCommand_19 BO Permit(0) Prohibit(1)
LockStatus_19 BI Permit(0) Prohibit(1)
FilterSign_19 BI Off(0) On(1)
FilterSignReset_19 BV - Reset(1)
AirConModeCommand_19 MO Cool(1)
AirConModeStatus_19 MI Cool(1)
SwingCommand_19 BO Stop(0) Run(1)
SwingStatus_19 BI Stop(0) Run(1)
FanSpeedCommand_19 MO Low(1)
FanSpeedStatus_19 MI Low(1)
SetRoomTemp_19 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_19 AI ℃
Alarm_19 BI Normal(0) Abnormal(1)
MalfunctionCode_19 AI Refer to the
SetTempStatus_19 AI ℃
Accumulated power(100 Watt)_19 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_19 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_19 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_19 AI ℃
TempRangeLowerLimitStatus_19 AI ℃
ModeLockCommand_19 BO Permit(0) Prohibit(1)
ModeLockStatus_19 BI Permit(0) Prohibit(1)
FanLockCommand_19 BO Permit(0) Prohibit(1)
FanLockStatus_19 BI Permit(0) Prohibit(1)
OccupancyCommand_19 BO Unoccupied(0) Occupied(1)
OccupancyStatus_19 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_19 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_19 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_19 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_19 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_19 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_19 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_19 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_19 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_19 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_19 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_19 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_19 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_19 BI Off(0) On(1)
AccumulatedGas(100 Watt)_19 AI Wattage values (Unit : 100Watt)
DustSensorAvail_19 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_19 BO Stop(0) Run(1)
AirCleaningOperStatus_19 BI Stop(0) Run(1)
FineDustStatus_19 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_19 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_19 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_19 AI %
ComfortCoolingAvail_19 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_19 BO Stop(0) Run(1)
ComfortCoolingOperStatus_19 BI Stop(0) Run(1)
ComfortCoolingStepCommand_19 AV 1~3 step
ComfortCoolingStepStatus_19 AI 1~3 step
HumanDetectionAvail_19 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_19 MO Off(1)
HumanDetectionOperStatus_19 MI Off(1)
HumanDetectionWindCommand_19 MO Off(1)
HumanDetectionWindStatus_19 MI Off(1)
HumanDetectionTimeCommand_19 MO 5min(1)
HumanDetectionTimeStatus_19 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1a ※ Dev Type AC
address

instance
point Name
number

6657 1 On/Off (Setting)


6658 2 On/Off (Status)
6659 3 Lock (Setting)
6660 4 Lock (Status)
6661 5 Filter Sign
6662 6 Filter Sign reset
6663 7 Operation Mode (Setting)
6664 8 Operation Mode (Status)
6665 9 Swing (Setting)
6666 10 Swing (Status)
6667 11 Fan Speed (Setting)
6668 12 Fan Speed (Status)
6669 13 Set Room Temperature
6670 14 Room Temperature
6671 15 Alarm
6672 16 Error Code
6675 19 Set Temperature (Status)
6676 20 Accumulated Power Distribution (Status)
6683 27 Set Upper Temperature (Setting)
6684 28 Set Lower Temperature (Setting)
6685 29 Set Upper Tempaerature (Status)
6686 30 Set Lower Temperature (Status)
6687 31 Mode Lock (Setting)
6688 32 Mode Lock (Status)
6689 33 Fan Lock (Setting)
6690 34 Fan Lock (Status)
6691 35 Occupancy (Setting)
6692 36 Occupancy (Status)
6693 37 2Set Cooling Set Temperature (Setting)
6694 38 2Set Cooling Set Temperature (Status)
6695 39 2Set Heating Set Temperature (Setting)
6696 40 2Set Heating Set Temperature (Status)
6697 41 2Set Cooling Upper Temperature (Setting)
6698 42 2Set Cooling Upper Temperature (Status)
6699 43 2Set Heating Upper Temperature (Setting)
6700 44 2Set Heating Upper Temperature (Status)
6701 45 2Set Cooling Lower Temperature (Setting)
6702 46 2Set Cooling Lower Temperature (Status)
6703 47 2Set Heating Lower Temperature (Setting)
6704 48 2Set Heating Lower Temperature (Status)
6705 49 Thermo Status (Status)
6706 50 Accumulated Gas Distribution (Status)
6707 51 Dust Sensor Available (Status)
6708 52 Air Cleaning Opereration (Setting)
6709 53 Air Cleaning Opereration (Status)
6710 54 Fine Dust (Status)
6711 55 Ultra Fine Dust (Status)
6712 56 Super Ultra Fine Dust (Status)
6713 57 Humidity (Status)
6714 58 Comfort Cooling Available (Status)
6715 59 Comfort Cooling Opereration (Setting)
6716 60 Comfort Cooling Opereration (Status)
6717 61 Comfort Cooling Step (Setting)
6718 62 Comfort Cooling Step (Status)
6719 63 Human Detection Available (Status)
6720 64 Human Detection Opereration (Setting)
6721 65 Human Detection Opereration (Status)
6722 66 Human Detection Wind (Setting)
6723 67 Human Detection Wind (Status)
6724 68 Human Detection Time (Setting)
6725 69 Human Detection Time (Status)
6726 70 Hotel Checkin (Setting)
6727 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1a BO Stop(0) Start(1)
StartStopStatus_1a BI Stop(0) Start(1)
LockCommand_1a BO Permit(0) Prohibit(1)
LockStatus_1a BI Permit(0) Prohibit(1)
FilterSign_1a BI Off(0) On(1)
FilterSignReset_1a BV - Reset(1)
AirConModeCommand_1a MO Cool(1)
AirConModeStatus_1a MI Cool(1)
SwingCommand_1a BO Stop(0) Run(1)
SwingStatus_1a BI Stop(0) Run(1)
FanSpeedCommand_1a MO Low(1)
FanSpeedStatus_1a MI Low(1)
SetRoomTemp_1a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1a AI ℃
Alarm_1a BI Normal(0) Abnormal(1)
MalfunctionCode_1a AI Refer to the
SetTempStatus_1a AI ℃
Accumulated power(100 Watt)_1a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1a AI ℃
TempRangeLowerLimitStatus_1a AI ℃
ModeLockCommand_1a BO Permit(0) Prohibit(1)
ModeLockStatus_1a BI Permit(0) Prohibit(1)
FanLockCommand_1a BO Permit(0) Prohibit(1)
FanLockStatus_1a BI Permit(0) Prohibit(1)
OccupancyCommand_1a BO Unoccupied(0) Occupied(1)
OccupancyStatus_1a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1a BI Off(0) On(1)
AccumulatedGas(100 Watt)_1a AI Wattage values (Unit : 100Watt)
DustSensorAvail_1a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1a BO Stop(0) Run(1)
AirCleaningOperStatus_1a BI Stop(0) Run(1)
FineDustStatus_1a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1a AI %
ComfortCoolingAvail_1a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1a BO Stop(0) Run(1)
ComfortCoolingOperStatus_1a BI Stop(0) Run(1)
ComfortCoolingStepCommand_1a AV 1~3 step
ComfortCoolingStepStatus_1a AI 1~3 step
HumanDetectionAvail_1a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1a MO Off(1)
HumanDetectionOperStatus_1a MI Off(1)
HumanDetectionWindCommand_1a MO Off(1)
HumanDetectionWindStatus_1a MI Off(1)
HumanDetectionTimeCommand_1a MO 5min(1)
HumanDetectionTimeStatus_1a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1d ※ Dev Type AC
address

instance
point Name
number

7425 1 On/Off (Setting)


7426 2 On/Off (Status)
7427 3 Lock (Setting)
7428 4 Lock (Status)
7429 5 Filter Sign
7430 6 Filter Sign reset
7431 7 Operation Mode (Setting)
7432 8 Operation Mode (Status)
7433 9 Swing (Setting)
7434 10 Swing (Status)
7435 11 Fan Speed (Setting)
7436 12 Fan Speed (Status)
7437 13 Set Room Temperature
7438 14 Room Temperature
7439 15 Alarm
7440 16 Error Code
7443 19 Set Temperature (Status)
7444 20 Accumulated Power Distribution (Status)
7451 27 Set Upper Temperature (Setting)
7452 28 Set Lower Temperature (Setting)
7453 29 Set Upper Tempaerature (Status)
7454 30 Set Lower Temperature (Status)
7455 31 Mode Lock (Setting)
7456 32 Mode Lock (Status)
7457 33 Fan Lock (Setting)
7458 34 Fan Lock (Status)
7459 35 Occupancy (Setting)
7460 36 Occupancy (Status)
7461 37 2Set Cooling Set Temperature (Setting)
7462 38 2Set Cooling Set Temperature (Status)
7463 39 2Set Heating Set Temperature (Setting)
7464 40 2Set Heating Set Temperature (Status)
7465 41 2Set Cooling Upper Temperature (Setting)
7466 42 2Set Cooling Upper Temperature (Status)
7467 43 2Set Heating Upper Temperature (Setting)
7468 44 2Set Heating Upper Temperature (Status)
7469 45 2Set Cooling Lower Temperature (Setting)
7470 46 2Set Cooling Lower Temperature (Status)
7471 47 2Set Heating Lower Temperature (Setting)
7472 48 2Set Heating Lower Temperature (Status)
7473 49 Thermo Status (Status)
7474 50 Accumulated Gas Distribution (Status)
7475 51 Dust Sensor Available (Status)
7476 52 Air Cleaning Opereration (Setting)
7477 53 Air Cleaning Opereration (Status)
7478 54 Fine Dust (Status)
7479 55 Ultra Fine Dust (Status)
7480 56 Super Ultra Fine Dust (Status)
7481 57 Humidity (Status)
7482 58 Comfort Cooling Available (Status)
7483 59 Comfort Cooling Opereration (Setting)
7484 60 Comfort Cooling Opereration (Status)
7485 61 Comfort Cooling Step (Setting)
7486 62 Comfort Cooling Step (Status)
7487 63 Human Detection Available (Status)
7488 64 Human Detection Opereration (Setting)
7489 65 Human Detection Opereration (Status)
7490 66 Human Detection Wind (Setting)
7491 67 Human Detection Wind (Status)
7492 68 Human Detection Time (Setting)
7493 69 Human Detection Time (Status)
7494 70 Hotel Checkin (Setting)
7495 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1d BO Stop(0) Start(1)
StartStopStatus_1d BI Stop(0) Start(1)
LockCommand_1d BO Permit(0) Prohibit(1)
LockStatus_1d BI Permit(0) Prohibit(1)
FilterSign_1d BI Off(0) On(1)
FilterSignReset_1d BV - Reset(1)
AirConModeCommand_1d MO Cool(1)
AirConModeStatus_1d MI Cool(1)
SwingCommand_1d BO Stop(0) Run(1)
SwingStatus_1d BI Stop(0) Run(1)
FanSpeedCommand_1d MO Low(1)
FanSpeedStatus_1d MI Low(1)
SetRoomTemp_1d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1d AI ℃
Alarm_1d BI Normal(0) Abnormal(1)
MalfunctionCode_1d AI Refer to the
SetTempStatus_1d AI ℃
Accumulated power(100 Watt)_1d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1d AI ℃
TempRangeLowerLimitStatus_1d AI ℃
ModeLockCommand_1d BO Permit(0) Prohibit(1)
ModeLockStatus_1d BI Permit(0) Prohibit(1)
FanLockCommand_1d BO Permit(0) Prohibit(1)
FanLockStatus_1d BI Permit(0) Prohibit(1)
OccupancyCommand_1d BO Unoccupied(0) Occupied(1)
OccupancyStatus_1d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1d BI Off(0) On(1)
AccumulatedGas(100 Watt)_1d AI Wattage values (Unit : 100Watt)
DustSensorAvail_1d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1d BO Stop(0) Run(1)
AirCleaningOperStatus_1d BI Stop(0) Run(1)
FineDustStatus_1d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1d AI %
ComfortCoolingAvail_1d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1d BO Stop(0) Run(1)
ComfortCoolingOperStatus_1d BI Stop(0) Run(1)
ComfortCoolingStepCommand_1d AV 1~3 step
ComfortCoolingStepStatus_1d AI 1~3 step
HumanDetectionAvail_1d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1d MO Off(1)
HumanDetectionOperStatus_1d MI Off(1)
HumanDetectionWindCommand_1d MO Off(1)
HumanDetectionWindStatus_1d MI Off(1)
HumanDetectionTimeCommand_1d MO 5min(1)
HumanDetectionTimeStatus_1d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1e ※ Dev Type AC
address

instance
point Name
number

7681 1 On/Off (Setting)


7682 2 On/Off (Status)
7683 3 Lock (Setting)
7684 4 Lock (Status)
7685 5 Filter Sign
7686 6 Filter Sign reset
7687 7 Operation Mode (Setting)
7688 8 Operation Mode (Status)
7689 9 Swing (Setting)
7690 10 Swing (Status)
7691 11 Fan Speed (Setting)
7692 12 Fan Speed (Status)
7693 13 Set Room Temperature
7694 14 Room Temperature
7695 15 Alarm
7696 16 Error Code
7699 19 Set Temperature (Status)
7700 20 Accumulated Power Distribution (Status)
7707 27 Set Upper Temperature (Setting)
7708 28 Set Lower Temperature (Setting)
7709 29 Set Upper Tempaerature (Status)
7710 30 Set Lower Temperature (Status)
7711 31 Mode Lock (Setting)
7712 32 Mode Lock (Status)
7713 33 Fan Lock (Setting)
7714 34 Fan Lock (Status)
7715 35 Occupancy (Setting)
7716 36 Occupancy (Status)
7717 37 2Set Cooling Set Temperature (Setting)
7718 38 2Set Cooling Set Temperature (Status)
7719 39 2Set Heating Set Temperature (Setting)
7720 40 2Set Heating Set Temperature (Status)
7721 41 2Set Cooling Upper Temperature (Setting)
7722 42 2Set Cooling Upper Temperature (Status)
7723 43 2Set Heating Upper Temperature (Setting)
7724 44 2Set Heating Upper Temperature (Status)
7725 45 2Set Cooling Lower Temperature (Setting)
7726 46 2Set Cooling Lower Temperature (Status)
7727 47 2Set Heating Lower Temperature (Setting)
7728 48 2Set Heating Lower Temperature (Status)
7729 49 Thermo Status (Status)
7730 50 Accumulated Gas Distribution (Status)
7731 51 Dust Sensor Available (Status)
7732 52 Air Cleaning Opereration (Setting)
7733 53 Air Cleaning Opereration (Status)
7734 54 Fine Dust (Status)
7735 55 Ultra Fine Dust (Status)
7736 56 Super Ultra Fine Dust (Status)
7737 57 Humidity (Status)
7738 58 Comfort Cooling Available (Status)
7739 59 Comfort Cooling Opereration (Setting)
7740 60 Comfort Cooling Opereration (Status)
7741 61 Comfort Cooling Step (Setting)
7742 62 Comfort Cooling Step (Status)
7743 63 Human Detection Available (Status)
7744 64 Human Detection Opereration (Setting)
7745 65 Human Detection Opereration (Status)
7746 66 Human Detection Wind (Setting)
7747 67 Human Detection Wind (Status)
7748 68 Human Detection Time (Setting)
7749 69 Human Detection Time (Status)
7750 70 Hotel Checkin (Setting)
7751 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1e BO Stop(0) Start(1)
StartStopStatus_1e BI Stop(0) Start(1)
LockCommand_1e BO Permit(0) Prohibit(1)
LockStatus_1e BI Permit(0) Prohibit(1)
FilterSign_1e BI Off(0) On(1)
FilterSignReset_1e BV - Reset(1)
AirConModeCommand_1e MO Cool(1)
AirConModeStatus_1e MI Cool(1)
SwingCommand_1e BO Stop(0) Run(1)
SwingStatus_1e BI Stop(0) Run(1)
FanSpeedCommand_1e MO Low(1)
FanSpeedStatus_1e MI Low(1)
SetRoomTemp_1e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1e AI ℃
Alarm_1e BI Normal(0) Abnormal(1)
MalfunctionCode_1e AI Refer to the
SetTempStatus_1e AI ℃
Accumulated power(100 Watt)_1e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1e AI ℃
TempRangeLowerLimitStatus_1e AI ℃
ModeLockCommand_1e BO Permit(0) Prohibit(1)
ModeLockStatus_1e BI Permit(0) Prohibit(1)
FanLockCommand_1e BO Permit(0) Prohibit(1)
FanLockStatus_1e BI Permit(0) Prohibit(1)
OccupancyCommand_1e BO Unoccupied(0) Occupied(1)
OccupancyStatus_1e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1e BI Off(0) On(1)
AccumulatedGas(100 Watt)_1e AI Wattage values (Unit : 100Watt)
DustSensorAvail_1e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1e BO Stop(0) Run(1)
AirCleaningOperStatus_1e BI Stop(0) Run(1)
FineDustStatus_1e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1e AI %
ComfortCoolingAvail_1e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1e BO Stop(0) Run(1)
ComfortCoolingOperStatus_1e BI Stop(0) Run(1)
ComfortCoolingStepCommand_1e AV 1~3 step
ComfortCoolingStepStatus_1e AI 1~3 step
HumanDetectionAvail_1e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1e MO Off(1)
HumanDetectionOperStatus_1e MI Off(1)
HumanDetectionWindCommand_1e MO Off(1)
HumanDetectionWindStatus_1e MI Off(1)
HumanDetectionTimeCommand_1e MO 5min(1)
HumanDetectionTimeStatus_1e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1f ※ Dev Type AC
address

instance
point Name
number

7937 1 On/Off (Setting)


7938 2 On/Off (Status)
7939 3 Lock (Setting)
7940 4 Lock (Status)
7941 5 Filter Sign
7942 6 Filter Sign reset
7943 7 Operation Mode (Setting)
7944 8 Operation Mode (Status)
7945 9 Swing (Setting)
7946 10 Swing (Status)
7947 11 Fan Speed (Setting)
7948 12 Fan Speed (Status)
7949 13 Set Room Temperature
7950 14 Room Temperature
7951 15 Alarm
7952 16 Error Code
7955 19 Set Temperature (Status)
7956 20 Accumulated Power Distribution (Status)
7963 27 Set Upper Temperature (Setting)
7964 28 Set Lower Temperature (Setting)
7965 29 Set Upper Tempaerature (Status)
7966 30 Set Lower Temperature (Status)
7967 31 Mode Lock (Setting)
7968 32 Mode Lock (Status)
7969 33 Fan Lock (Setting)
7970 34 Fan Lock (Status)
7971 35 Occupancy (Setting)
7972 36 Occupancy (Status)
7973 37 2Set Cooling Set Temperature (Setting)
7974 38 2Set Cooling Set Temperature (Status)
7975 39 2Set Heating Set Temperature (Setting)
7976 40 2Set Heating Set Temperature (Status)
7977 41 2Set Cooling Upper Temperature (Setting)
7978 42 2Set Cooling Upper Temperature (Status)
7979 43 2Set Heating Upper Temperature (Setting)
7980 44 2Set Heating Upper Temperature (Status)
7981 45 2Set Cooling Lower Temperature (Setting)
7982 46 2Set Cooling Lower Temperature (Status)
7983 47 2Set Heating Lower Temperature (Setting)
7984 48 2Set Heating Lower Temperature (Status)
7985 49 Thermo Status (Status)
7986 50 Accumulated Gas Distribution (Status)
7987 51 Dust Sensor Available (Status)
7988 52 Air Cleaning Opereration (Setting)
7989 53 Air Cleaning Opereration (Status)
7990 54 Fine Dust (Status)
7991 55 Ultra Fine Dust (Status)
7992 56 Super Ultra Fine Dust (Status)
7993 57 Humidity (Status)
7994 58 Comfort Cooling Available (Status)
7995 59 Comfort Cooling Opereration (Setting)
7996 60 Comfort Cooling Opereration (Status)
7997 61 Comfort Cooling Step (Setting)
7998 62 Comfort Cooling Step (Status)
7999 63 Human Detection Available (Status)
8000 64 Human Detection Opereration (Setting)
8001 65 Human Detection Opereration (Status)
8002 66 Human Detection Wind (Setting)
8003 67 Human Detection Wind (Status)
8004 68 Human Detection Time (Setting)
8005 69 Human Detection Time (Status)
8006 70 Hotel Checkin (Setting)
8007 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1f BO Stop(0) Start(1)
StartStopStatus_1f BI Stop(0) Start(1)
LockCommand_1f BO Permit(0) Prohibit(1)
LockStatus_1f BI Permit(0) Prohibit(1)
FilterSign_1f BI Off(0) On(1)
FilterSignReset_1f BV - Reset(1)
AirConModeCommand_1f MO Cool(1)
AirConModeStatus_1f MI Cool(1)
SwingCommand_1f BO Stop(0) Run(1)
SwingStatus_1f BI Stop(0) Run(1)
FanSpeedCommand_1f MO Low(1)
FanSpeedStatus_1f MI Low(1)
SetRoomTemp_1f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1f AI ℃
Alarm_1f BI Normal(0) Abnormal(1)
MalfunctionCode_1f AI Refer to the
SetTempStatus_1f AI ℃
Accumulated power(100 Watt)_1f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1f AI ℃
TempRangeLowerLimitStatus_1f AI ℃
ModeLockCommand_1f BO Permit(0) Prohibit(1)
ModeLockStatus_1f BI Permit(0) Prohibit(1)
FanLockCommand_1f BO Permit(0) Prohibit(1)
FanLockStatus_1f BI Permit(0) Prohibit(1)
OccupancyCommand_1f BO Unoccupied(0) Occupied(1)
OccupancyStatus_1f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1f BI Off(0) On(1)
AccumulatedGas(100 Watt)_1f AI Wattage values (Unit : 100Watt)
DustSensorAvail_1f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1f BO Stop(0) Run(1)
AirCleaningOperStatus_1f BI Stop(0) Run(1)
FineDustStatus_1f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1f AI %
ComfortCoolingAvail_1f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1f BO Stop(0) Run(1)
ComfortCoolingOperStatus_1f BI Stop(0) Run(1)
ComfortCoolingStepCommand_1f AV 1~3 step
ComfortCoolingStepStatus_1f AI 1~3 step
HumanDetectionAvail_1f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1f MO Off(1)
HumanDetectionOperStatus_1f MI Off(1)
HumanDetectionWindCommand_1f MO Off(1)
HumanDetectionWindStatus_1f MI Off(1)
HumanDetectionTimeCommand_1f MO 5min(1)
HumanDetectionTimeStatus_1f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
20 ※ Dev Type AC
address

instance
point Name
number

8193 1 On/Off (Setting)


8194 2 On/Off (Status)
8195 3 Lock (Setting)
8196 4 Lock (Status)
8197 5 Filter Sign
8198 6 Filter Sign reset
8199 7 Operation Mode (Setting)
8200 8 Operation Mode (Status)
8201 9 Swing (Setting)
8202 10 Swing (Status)
8203 11 Fan Speed (Setting)
8204 12 Fan Speed (Status)
8205 13 Set Room Temperature
8206 14 Room Temperature
8207 15 Alarm
8208 16 Error Code
8211 19 Set Temperature (Status)
8212 20 Accumulated Power Distribution (Status)
8219 27 Set Upper Temperature (Setting)
8220 28 Set Lower Temperature (Setting)
8221 29 Set Upper Tempaerature (Status)
8222 30 Set Lower Temperature (Status)
8223 31 Mode Lock (Setting)
8224 32 Mode Lock (Status)
8225 33 Fan Lock (Setting)
8226 34 Fan Lock (Status)
8227 35 Occupancy (Setting)
8228 36 Occupancy (Status)
8229 37 2Set Cooling Set Temperature (Setting)
8230 38 2Set Cooling Set Temperature (Status)
8231 39 2Set Heating Set Temperature (Setting)
8232 40 2Set Heating Set Temperature (Status)
8233 41 2Set Cooling Upper Temperature (Setting)
8234 42 2Set Cooling Upper Temperature (Status)
8235 43 2Set Heating Upper Temperature (Setting)
8236 44 2Set Heating Upper Temperature (Status)
8237 45 2Set Cooling Lower Temperature (Setting)
8238 46 2Set Cooling Lower Temperature (Status)
8239 47 2Set Heating Lower Temperature (Setting)
8240 48 2Set Heating Lower Temperature (Status)
8241 49 Thermo Status (Status)
8242 50 Accumulated Gas Distribution (Status)
8243 51 Dust Sensor Available (Status)
8244 52 Air Cleaning Opereration (Setting)
8245 53 Air Cleaning Opereration (Status)
8246 54 Fine Dust (Status)
8247 55 Ultra Fine Dust (Status)
8248 56 Super Ultra Fine Dust (Status)
8249 57 Humidity (Status)
8250 58 Comfort Cooling Available (Status)
8251 59 Comfort Cooling Opereration (Setting)
8252 60 Comfort Cooling Opereration (Status)
8253 61 Comfort Cooling Step (Setting)
8254 62 Comfort Cooling Step (Status)
8255 63 Human Detection Available (Status)
8256 64 Human Detection Opereration (Setting)
8257 65 Human Detection Opereration (Status)
8258 66 Human Detection Wind (Setting)
8259 67 Human Detection Wind (Status)
8260 68 Human Detection Time (Setting)
8261 69 Human Detection Time (Status)
8262 70 Hotel Checkin (Setting)
8263 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_20 BO Stop(0) Start(1)
StartStopStatus_20 BI Stop(0) Start(1)
LockCommand_20 BO Permit(0) Prohibit(1)
LockStatus_20 BI Permit(0) Prohibit(1)
FilterSign_20 BI Off(0) On(1)
FilterSignReset_20 BV - Reset(1)
AirConModeCommand_20 MO Cool(1)
AirConModeStatus_20 MI Cool(1)
SwingCommand_20 BO Stop(0) Run(1)
SwingStatus_20 BI Stop(0) Run(1)
FanSpeedCommand_20 MO Low(1)
FanSpeedStatus_20 MI Low(1)
SetRoomTemp_20 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_20 AI ℃
Alarm_20 BI Normal(0) Abnormal(1)
MalfunctionCode_20 AI Refer to the
SetTempStatus_20 AI ℃
Accumulated power(100 Watt)_20 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_20 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_20 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_20 AI ℃
TempRangeLowerLimitStatus_20 AI ℃
ModeLockCommand_20 BO Permit(0) Prohibit(1)
ModeLockStatus_20 BI Permit(0) Prohibit(1)
FanLockCommand_20 BO Permit(0) Prohibit(1)
FanLockStatus_20 BI Permit(0) Prohibit(1)
OccupancyCommand_20 BO Unoccupied(0) Occupied(1)
OccupancyStatus_20 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_20 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_20 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_20 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_20 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_20 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_20 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_20 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_20 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_20 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_20 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_20 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_20 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_20 BI Off(0) On(1)
AccumulatedGas(100 Watt)_20 AI Wattage values (Unit : 100Watt)
DustSensorAvail_20 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_20 BO Stop(0) Run(1)
AirCleaningOperStatus_20 BI Stop(0) Run(1)
FineDustStatus_20 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_20 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_20 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_20 AI %
ComfortCoolingAvail_20 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_20 BO Stop(0) Run(1)
ComfortCoolingOperStatus_20 BI Stop(0) Run(1)
ComfortCoolingStepCommand_20 AV 1~3 step
ComfortCoolingStepStatus_20 AI 1~3 step
HumanDetectionAvail_20 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_20 MO Off(1)
HumanDetectionOperStatus_20 MI Off(1)
HumanDetectionWindCommand_20 MO Off(1)
HumanDetectionWindStatus_20 MI Off(1)
HumanDetectionTimeCommand_20 MO 5min(1)
HumanDetectionTimeStatus_20 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
21 ※ Dev Type AC
address

instance
point Name
number

8449 1 On/Off (Setting)


8450 2 On/Off (Status)
8451 3 Lock (Setting)
8452 4 Lock (Status)
8453 5 Filter Sign
8454 6 Filter Sign reset
8455 7 Operation Mode (Setting)
8456 8 Operation Mode (Status)
8457 9 Swing (Setting)
8458 10 Swing (Status)
8459 11 Fan Speed (Setting)
8460 12 Fan Speed (Status)
8461 13 Set Room Temperature
8462 14 Room Temperature
8463 15 Alarm
8464 16 Error Code
8467 19 Set Temperature (Status)
8468 20 Accumulated Power Distribution (Status)
8475 27 Set Upper Temperature (Setting)
8476 28 Set Lower Temperature (Setting)
8477 29 Set Upper Tempaerature (Status)
8478 30 Set Lower Temperature (Status)
8479 31 Mode Lock (Setting)
8480 32 Mode Lock (Status)
8481 33 Fan Lock (Setting)
8482 34 Fan Lock (Status)
8483 35 Occupancy (Setting)
8484 36 Occupancy (Status)
8485 37 2Set Cooling Set Temperature (Setting)
8486 38 2Set Cooling Set Temperature (Status)
8487 39 2Set Heating Set Temperature (Setting)
8488 40 2Set Heating Set Temperature (Status)
8489 41 2Set Cooling Upper Temperature (Setting)
8490 42 2Set Cooling Upper Temperature (Status)
8491 43 2Set Heating Upper Temperature (Setting)
8492 44 2Set Heating Upper Temperature (Status)
8493 45 2Set Cooling Lower Temperature (Setting)
8494 46 2Set Cooling Lower Temperature (Status)
8495 47 2Set Heating Lower Temperature (Setting)
8496 48 2Set Heating Lower Temperature (Status)
8497 49 Thermo Status (Status)
8498 50 Accumulated Gas Distribution (Status)
8499 51 Dust Sensor Available (Status)
8500 52 Air Cleaning Opereration (Setting)
8501 53 Air Cleaning Opereration (Status)
8502 54 Fine Dust (Status)
8503 55 Ultra Fine Dust (Status)
8504 56 Super Ultra Fine Dust (Status)
8505 57 Humidity (Status)
8506 58 Comfort Cooling Available (Status)
8507 59 Comfort Cooling Opereration (Setting)
8508 60 Comfort Cooling Opereration (Status)
8509 61 Comfort Cooling Step (Setting)
8510 62 Comfort Cooling Step (Status)
8511 63 Human Detection Available (Status)
8512 64 Human Detection Opereration (Setting)
8513 65 Human Detection Opereration (Status)
8514 66 Human Detection Wind (Setting)
8515 67 Human Detection Wind (Status)
8516 68 Human Detection Time (Setting)
8517 69 Human Detection Time (Status)
8518 70 Hotel Checkin (Setting)
8519 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_21 BO Stop(0) Start(1)
StartStopStatus_21 BI Stop(0) Start(1)
LockCommand_21 BO Permit(0) Prohibit(1)
LockStatus_21 BI Permit(0) Prohibit(1)
FilterSign_21 BI Off(0) On(1)
FilterSignReset_21 BV - Reset(1)
AirConModeCommand_21 MO Cool(1)
AirConModeStatus_21 MI Cool(1)
SwingCommand_21 BO Stop(0) Run(1)
SwingStatus_21 BI Stop(0) Run(1)
FanSpeedCommand_21 MO Low(1)
FanSpeedStatus_21 MI Low(1)
SetRoomTemp_21 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_21 AI ℃
Alarm_21 BI Normal(0) Abnormal(1)
MalfunctionCode_21 AI Refer to the
SetTempStatus_21 AI ℃
Accumulated power(100 Watt)_21 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_21 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_21 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_21 AI ℃
TempRangeLowerLimitStatus_21 AI ℃
ModeLockCommand_21 BO Permit(0) Prohibit(1)
ModeLockStatus_21 BI Permit(0) Prohibit(1)
FanLockCommand_21 BO Permit(0) Prohibit(1)
FanLockStatus_21 BI Permit(0) Prohibit(1)
OccupancyCommand_21 BO Unoccupied(0) Occupied(1)
OccupancyStatus_21 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_21 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_21 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_21 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_21 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_21 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_21 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_21 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_21 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_21 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_21 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_21 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_21 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_21 BI Off(0) On(1)
AccumulatedGas(100 Watt)_21 AI Wattage values (Unit : 100Watt)
DustSensorAvail_21 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_21 BO Stop(0) Run(1)
AirCleaningOperStatus_21 BI Stop(0) Run(1)
FineDustStatus_21 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_21 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_21 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_21 AI %
ComfortCoolingAvail_21 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_21 BO Stop(0) Run(1)
ComfortCoolingOperStatus_21 BI Stop(0) Run(1)
ComfortCoolingStepCommand_21 AV 1~3 step
ComfortCoolingStepStatus_21 AI 1~3 step
HumanDetectionAvail_21 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_21 MO Off(1)
HumanDetectionOperStatus_21 MI Off(1)
HumanDetectionWindCommand_21 MO Off(1)
HumanDetectionWindStatus_21 MI Off(1)
HumanDetectionTimeCommand_21 MO 5min(1)
HumanDetectionTimeStatus_21 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
22 ※ Dev Type AC
address

instance
point Name
number

8705 1 On/Off (Setting)


8706 2 On/Off (Status)
8707 3 Lock (Setting)
8708 4 Lock (Status)
8709 5 Filter Sign
8710 6 Filter Sign reset
8711 7 Operation Mode (Setting)
8712 8 Operation Mode (Status)
8713 9 Swing (Setting)
8714 10 Swing (Status)
8715 11 Fan Speed (Setting)
8716 12 Fan Speed (Status)
8717 13 Set Room Temperature
8718 14 Room Temperature
8719 15 Alarm
8720 16 Error Code
8723 19 Set Temperature (Status)
8724 20 Accumulated Power Distribution (Status)
8731 27 Set Upper Temperature (Setting)
8732 28 Set Lower Temperature (Setting)
8733 29 Set Upper Tempaerature (Status)
8734 30 Set Lower Temperature (Status)
8735 31 Mode Lock (Setting)
8736 32 Mode Lock (Status)
8737 33 Fan Lock (Setting)
8738 34 Fan Lock (Status)
8739 35 Occupancy (Setting)
8740 36 Occupancy (Status)
8741 37 2Set Cooling Set Temperature (Setting)
8742 38 2Set Cooling Set Temperature (Status)
8743 39 2Set Heating Set Temperature (Setting)
8744 40 2Set Heating Set Temperature (Status)
8745 41 2Set Cooling Upper Temperature (Setting)
8746 42 2Set Cooling Upper Temperature (Status)
8747 43 2Set Heating Upper Temperature (Setting)
8748 44 2Set Heating Upper Temperature (Status)
8749 45 2Set Cooling Lower Temperature (Setting)
8750 46 2Set Cooling Lower Temperature (Status)
8751 47 2Set Heating Lower Temperature (Setting)
8752 48 2Set Heating Lower Temperature (Status)
8753 49 Thermo Status (Status)
8754 50 Accumulated Gas Distribution (Status)
8755 51 Dust Sensor Available (Status)
8756 52 Air Cleaning Opereration (Setting)
8757 53 Air Cleaning Opereration (Status)
8758 54 Fine Dust (Status)
8759 55 Ultra Fine Dust (Status)
8760 56 Super Ultra Fine Dust (Status)
8761 57 Humidity (Status)
8762 58 Comfort Cooling Available (Status)
8763 59 Comfort Cooling Opereration (Setting)
8764 60 Comfort Cooling Opereration (Status)
8765 61 Comfort Cooling Step (Setting)
8766 62 Comfort Cooling Step (Status)
8767 63 Human Detection Available (Status)
8768 64 Human Detection Opereration (Setting)
8769 65 Human Detection Opereration (Status)
8770 66 Human Detection Wind (Setting)
8771 67 Human Detection Wind (Status)
8772 68 Human Detection Time (Setting)
8773 69 Human Detection Time (Status)
8774 70 Hotel Checkin (Setting)
8775 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_22 BO Stop(0) Start(1)
StartStopStatus_22 BI Stop(0) Start(1)
LockCommand_22 BO Permit(0) Prohibit(1)
LockStatus_22 BI Permit(0) Prohibit(1)
FilterSign_22 BI Off(0) On(1)
FilterSignReset_22 BV - Reset(1)
AirConModeCommand_22 MO Cool(1)
AirConModeStatus_22 MI Cool(1)
SwingCommand_22 BO Stop(0) Run(1)
SwingStatus_22 BI Stop(0) Run(1)
FanSpeedCommand_22 MO Low(1)
FanSpeedStatus_22 MI Low(1)
SetRoomTemp_22 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_22 AI ℃
Alarm_22 BI Normal(0) Abnormal(1)
MalfunctionCode_22 AI Refer to the
SetTempStatus_22 AI ℃
Accumulated power(100 Watt)_22 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_22 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_22 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_22 AI ℃
TempRangeLowerLimitStatus_22 AI ℃
ModeLockCommand_22 BO Permit(0) Prohibit(1)
ModeLockStatus_22 BI Permit(0) Prohibit(1)
FanLockCommand_22 BO Permit(0) Prohibit(1)
FanLockStatus_22 BI Permit(0) Prohibit(1)
OccupancyCommand_22 BO Unoccupied(0) Occupied(1)
OccupancyStatus_22 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_22 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_22 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_22 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_22 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_22 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_22 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_22 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_22 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_22 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_22 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_22 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_22 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_22 BI Off(0) On(1)
AccumulatedGas(100 Watt)_22 AI Wattage values (Unit : 100Watt)
DustSensorAvail_22 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_22 BO Stop(0) Run(1)
AirCleaningOperStatus_22 BI Stop(0) Run(1)
FineDustStatus_22 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_22 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_22 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_22 AI %
ComfortCoolingAvail_22 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_22 BO Stop(0) Run(1)
ComfortCoolingOperStatus_22 BI Stop(0) Run(1)
ComfortCoolingStepCommand_22 AV 1~3 step
ComfortCoolingStepStatus_22 AI 1~3 step
HumanDetectionAvail_22 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_22 MO Off(1)
HumanDetectionOperStatus_22 MI Off(1)
HumanDetectionWindCommand_22 MO Off(1)
HumanDetectionWindStatus_22 MI Off(1)
HumanDetectionTimeCommand_22 MO 5min(1)
HumanDetectionTimeStatus_22 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
23 ※ Dev Type AC
address

instance
point Name
number

8961 1 On/Off (Setting)


8962 2 On/Off (Status)
8963 3 Lock (Setting)
8964 4 Lock (Status)
8965 5 Filter Sign
8966 6 Filter Sign reset
8967 7 Operation Mode (Setting)
8968 8 Operation Mode (Status)
8969 9 Swing (Setting)
8970 10 Swing (Status)
8971 11 Fan Speed (Setting)
8972 12 Fan Speed (Status)
8973 13 Set Room Temperature
8974 14 Room Temperature
8975 15 Alarm
8976 16 Error Code
8979 19 Set Temperature (Status)
8980 20 Accumulated Power Distribution (Status)
8987 27 Set Upper Temperature (Setting)
8988 28 Set Lower Temperature (Setting)
8989 29 Set Upper Tempaerature (Status)
8990 30 Set Lower Temperature (Status)
8991 31 Mode Lock (Setting)
8992 32 Mode Lock (Status)
8993 33 Fan Lock (Setting)
8994 34 Fan Lock (Status)
8995 35 Occupancy (Setting)
8996 36 Occupancy (Status)
8997 37 2Set Cooling Set Temperature (Setting)
8998 38 2Set Cooling Set Temperature (Status)
8999 39 2Set Heating Set Temperature (Setting)
9000 40 2Set Heating Set Temperature (Status)
9001 41 2Set Cooling Upper Temperature (Setting)
9002 42 2Set Cooling Upper Temperature (Status)
9003 43 2Set Heating Upper Temperature (Setting)
9004 44 2Set Heating Upper Temperature (Status)
9005 45 2Set Cooling Lower Temperature (Setting)
9006 46 2Set Cooling Lower Temperature (Status)
9007 47 2Set Heating Lower Temperature (Setting)
9008 48 2Set Heating Lower Temperature (Status)
9009 49 Thermo Status (Status)
9010 50 Accumulated Gas Distribution (Status)
9011 51 Dust Sensor Available (Status)
9012 52 Air Cleaning Opereration (Setting)
9013 53 Air Cleaning Opereration (Status)
9014 54 Fine Dust (Status)
9015 55 Ultra Fine Dust (Status)
9016 56 Super Ultra Fine Dust (Status)
9017 57 Humidity (Status)
9018 58 Comfort Cooling Available (Status)
9019 59 Comfort Cooling Opereration (Setting)
9020 60 Comfort Cooling Opereration (Status)
9021 61 Comfort Cooling Step (Setting)
9022 62 Comfort Cooling Step (Status)
9023 63 Human Detection Available (Status)
9024 64 Human Detection Opereration (Setting)
9025 65 Human Detection Opereration (Status)
9026 66 Human Detection Wind (Setting)
9027 67 Human Detection Wind (Status)
9028 68 Human Detection Time (Setting)
9029 69 Human Detection Time (Status)
9030 70 Hotel Checkin (Setting)
9031 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_23 BO Stop(0) Start(1)
StartStopStatus_23 BI Stop(0) Start(1)
LockCommand_23 BO Permit(0) Prohibit(1)
LockStatus_23 BI Permit(0) Prohibit(1)
FilterSign_23 BI Off(0) On(1)
FilterSignReset_23 BV - Reset(1)
AirConModeCommand_23 MO Cool(1)
AirConModeStatus_23 MI Cool(1)
SwingCommand_23 BO Stop(0) Run(1)
SwingStatus_23 BI Stop(0) Run(1)
FanSpeedCommand_23 MO Low(1)
FanSpeedStatus_23 MI Low(1)
SetRoomTemp_23 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_23 AI ℃
Alarm_23 BI Normal(0) Abnormal(1)
MalfunctionCode_23 AI Refer to the
SetTempStatus_23 AI ℃
Accumulated power(100 Watt)_23 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_23 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_23 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_23 AI ℃
TempRangeLowerLimitStatus_23 AI ℃
ModeLockCommand_23 BO Permit(0) Prohibit(1)
ModeLockStatus_23 BI Permit(0) Prohibit(1)
FanLockCommand_23 BO Permit(0) Prohibit(1)
FanLockStatus_23 BI Permit(0) Prohibit(1)
OccupancyCommand_23 BO Unoccupied(0) Occupied(1)
OccupancyStatus_23 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_23 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_23 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_23 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_23 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_23 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_23 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_23 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_23 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_23 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_23 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_23 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_23 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_23 BI Off(0) On(1)
AccumulatedGas(100 Watt)_23 AI Wattage values (Unit : 100Watt)
DustSensorAvail_23 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_23 BO Stop(0) Run(1)
AirCleaningOperStatus_23 BI Stop(0) Run(1)
FineDustStatus_23 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_23 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_23 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_23 AI %
ComfortCoolingAvail_23 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_23 BO Stop(0) Run(1)
ComfortCoolingOperStatus_23 BI Stop(0) Run(1)
ComfortCoolingStepCommand_23 AV 1~3 step
ComfortCoolingStepStatus_23 AI 1~3 step
HumanDetectionAvail_23 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_23 MO Off(1)
HumanDetectionOperStatus_23 MI Off(1)
HumanDetectionWindCommand_23 MO Off(1)
HumanDetectionWindStatus_23 MI Off(1)
HumanDetectionTimeCommand_23 MO 5min(1)
HumanDetectionTimeStatus_23 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
24 ※ Dev Type AC
address

instance
point Name
number

9217 1 On/Off (Setting)


9218 2 On/Off (Status)
9219 3 Lock (Setting)
9220 4 Lock (Status)
9221 5 Filter Sign
9222 6 Filter Sign reset
9223 7 Operation Mode (Setting)
9224 8 Operation Mode (Status)
9225 9 Swing (Setting)
9226 10 Swing (Status)
9227 11 Fan Speed (Setting)
9228 12 Fan Speed (Status)
9229 13 Set Room Temperature
9230 14 Room Temperature
9231 15 Alarm
9232 16 Error Code
9235 19 Set Temperature (Status)
9236 20 Accumulated Power Distribution (Status)
9243 27 Set Upper Temperature (Setting)
9244 28 Set Lower Temperature (Setting)
9245 29 Set Upper Tempaerature (Status)
9246 30 Set Lower Temperature (Status)
9247 31 Mode Lock (Setting)
9248 32 Mode Lock (Status)
9249 33 Fan Lock (Setting)
9250 34 Fan Lock (Status)
9251 35 Occupancy (Setting)
9252 36 Occupancy (Status)
9253 37 2Set Cooling Set Temperature (Setting)
9254 38 2Set Cooling Set Temperature (Status)
9255 39 2Set Heating Set Temperature (Setting)
9256 40 2Set Heating Set Temperature (Status)
9257 41 2Set Cooling Upper Temperature (Setting)
9258 42 2Set Cooling Upper Temperature (Status)
9259 43 2Set Heating Upper Temperature (Setting)
9260 44 2Set Heating Upper Temperature (Status)
9261 45 2Set Cooling Lower Temperature (Setting)
9262 46 2Set Cooling Lower Temperature (Status)
9263 47 2Set Heating Lower Temperature (Setting)
9264 48 2Set Heating Lower Temperature (Status)
9265 49 Thermo Status (Status)
9266 50 Accumulated Gas Distribution (Status)
9267 51 Dust Sensor Available (Status)
9268 52 Air Cleaning Opereration (Setting)
9269 53 Air Cleaning Opereration (Status)
9270 54 Fine Dust (Status)
9271 55 Ultra Fine Dust (Status)
9272 56 Super Ultra Fine Dust (Status)
9273 57 Humidity (Status)
9274 58 Comfort Cooling Available (Status)
9275 59 Comfort Cooling Opereration (Setting)
9276 60 Comfort Cooling Opereration (Status)
9277 61 Comfort Cooling Step (Setting)
9278 62 Comfort Cooling Step (Status)
9279 63 Human Detection Available (Status)
9280 64 Human Detection Opereration (Setting)
9281 65 Human Detection Opereration (Status)
9282 66 Human Detection Wind (Setting)
9283 67 Human Detection Wind (Status)
9284 68 Human Detection Time (Setting)
9285 69 Human Detection Time (Status)
9286 70 Hotel Checkin (Setting)
9287 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_24 BO Stop(0) Start(1)
StartStopStatus_24 BI Stop(0) Start(1)
LockCommand_24 BO Permit(0) Prohibit(1)
LockStatus_24 BI Permit(0) Prohibit(1)
FilterSign_24 BI Off(0) On(1)
FilterSignReset_24 BV - Reset(1)
AirConModeCommand_24 MO Cool(1)
AirConModeStatus_24 MI Cool(1)
SwingCommand_24 BO Stop(0) Run(1)
SwingStatus_24 BI Stop(0) Run(1)
FanSpeedCommand_24 MO Low(1)
FanSpeedStatus_24 MI Low(1)
SetRoomTemp_24 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_24 AI ℃
Alarm_24 BI Normal(0) Abnormal(1)
MalfunctionCode_24 AI Refer to the
SetTempStatus_24 AI ℃
Accumulated power(100 Watt)_24 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_24 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_24 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_24 AI ℃
TempRangeLowerLimitStatus_24 AI ℃
ModeLockCommand_24 BO Permit(0) Prohibit(1)
ModeLockStatus_24 BI Permit(0) Prohibit(1)
FanLockCommand_24 BO Permit(0) Prohibit(1)
FanLockStatus_24 BI Permit(0) Prohibit(1)
OccupancyCommand_24 BO Unoccupied(0) Occupied(1)
OccupancyStatus_24 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_24 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_24 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_24 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_24 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_24 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_24 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_24 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_24 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_24 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_24 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_24 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_24 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_24 BI Off(0) On(1)
AccumulatedGas(100 Watt)_24 AI Wattage values (Unit : 100Watt)
DustSensorAvail_24 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_24 BO Stop(0) Run(1)
AirCleaningOperStatus_24 BI Stop(0) Run(1)
FineDustStatus_24 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_24 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_24 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_24 AI %
ComfortCoolingAvail_24 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_24 BO Stop(0) Run(1)
ComfortCoolingOperStatus_24 BI Stop(0) Run(1)
ComfortCoolingStepCommand_24 AV 1~3 step
ComfortCoolingStepStatus_24 AI 1~3 step
HumanDetectionAvail_24 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_24 MO Off(1)
HumanDetectionOperStatus_24 MI Off(1)
HumanDetectionWindCommand_24 MO Off(1)
HumanDetectionWindStatus_24 MI Off(1)
HumanDetectionTimeCommand_24 MO 5min(1)
HumanDetectionTimeStatus_24 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
25 ※ Dev Type AC
address

instance
point Name
number

9473 1 On/Off (Setting)


9474 2 On/Off (Status)
9475 3 Lock (Setting)
9476 4 Lock (Status)
9477 5 Filter Sign
9478 6 Filter Sign reset
9479 7 Operation Mode (Setting)
9480 8 Operation Mode (Status)
9481 9 Swing (Setting)
9482 10 Swing (Status)
9483 11 Fan Speed (Setting)
9484 12 Fan Speed (Status)
9485 13 Set Room Temperature
9486 14 Room Temperature
9487 15 Alarm
9488 16 Error Code
9491 19 Set Temperature (Status)
9492 20 Accumulated Power Distribution (Status)
9499 27 Set Upper Temperature (Setting)
9500 28 Set Lower Temperature (Setting)
9501 29 Set Upper Tempaerature (Status)
9502 30 Set Lower Temperature (Status)
9503 31 Mode Lock (Setting)
9504 32 Mode Lock (Status)
9505 33 Fan Lock (Setting)
9506 34 Fan Lock (Status)
9507 35 Occupancy (Setting)
9508 36 Occupancy (Status)
9509 37 2Set Cooling Set Temperature (Setting)
9510 38 2Set Cooling Set Temperature (Status)
9511 39 2Set Heating Set Temperature (Setting)
9512 40 2Set Heating Set Temperature (Status)
9513 41 2Set Cooling Upper Temperature (Setting)
9514 42 2Set Cooling Upper Temperature (Status)
9515 43 2Set Heating Upper Temperature (Setting)
9516 44 2Set Heating Upper Temperature (Status)
9517 45 2Set Cooling Lower Temperature (Setting)
9518 46 2Set Cooling Lower Temperature (Status)
9519 47 2Set Heating Lower Temperature (Setting)
9520 48 2Set Heating Lower Temperature (Status)
9521 49 Thermo Status (Status)
9522 50 Accumulated Gas Distribution (Status)
9523 51 Dust Sensor Available (Status)
9524 52 Air Cleaning Opereration (Setting)
9525 53 Air Cleaning Opereration (Status)
9526 54 Fine Dust (Status)
9527 55 Ultra Fine Dust (Status)
9528 56 Super Ultra Fine Dust (Status)
9529 57 Humidity (Status)
9530 58 Comfort Cooling Available (Status)
9531 59 Comfort Cooling Opereration (Setting)
9532 60 Comfort Cooling Opereration (Status)
9533 61 Comfort Cooling Step (Setting)
9534 62 Comfort Cooling Step (Status)
9535 63 Human Detection Available (Status)
9536 64 Human Detection Opereration (Setting)
9537 65 Human Detection Opereration (Status)
9538 66 Human Detection Wind (Setting)
9539 67 Human Detection Wind (Status)
9540 68 Human Detection Time (Setting)
9541 69 Human Detection Time (Status)
9542 70 Hotel Checkin (Setting)
9543 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_25 BO Stop(0) Start(1)
StartStopStatus_25 BI Stop(0) Start(1)
LockCommand_25 BO Permit(0) Prohibit(1)
LockStatus_25 BI Permit(0) Prohibit(1)
FilterSign_25 BI Off(0) On(1)
FilterSignReset_25 BV - Reset(1)
AirConModeCommand_25 MO Cool(1)
AirConModeStatus_25 MI Cool(1)
SwingCommand_25 BO Stop(0) Run(1)
SwingStatus_25 BI Stop(0) Run(1)
FanSpeedCommand_25 MO Low(1)
FanSpeedStatus_25 MI Low(1)
SetRoomTemp_25 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_25 AI ℃
Alarm_25 BI Normal(0) Abnormal(1)
MalfunctionCode_25 AI Refer to the
SetTempStatus_25 AI ℃
Accumulated power(100 Watt)_25 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_25 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_25 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_25 AI ℃
TempRangeLowerLimitStatus_25 AI ℃
ModeLockCommand_25 BO Permit(0) Prohibit(1)
ModeLockStatus_25 BI Permit(0) Prohibit(1)
FanLockCommand_25 BO Permit(0) Prohibit(1)
FanLockStatus_25 BI Permit(0) Prohibit(1)
OccupancyCommand_25 BO Unoccupied(0) Occupied(1)
OccupancyStatus_25 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_25 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_25 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_25 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_25 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_25 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_25 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_25 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_25 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_25 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_25 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_25 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_25 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_25 BI Off(0) On(1)
AccumulatedGas(100 Watt)_25 AI Wattage values (Unit : 100Watt)
DustSensorAvail_25 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_25 BO Stop(0) Run(1)
AirCleaningOperStatus_25 BI Stop(0) Run(1)
FineDustStatus_25 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_25 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_25 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_25 AI %
ComfortCoolingAvail_25 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_25 BO Stop(0) Run(1)
ComfortCoolingOperStatus_25 BI Stop(0) Run(1)
ComfortCoolingStepCommand_25 AV 1~3 step
ComfortCoolingStepStatus_25 AI 1~3 step
HumanDetectionAvail_25 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_25 MO Off(1)
HumanDetectionOperStatus_25 MI Off(1)
HumanDetectionWindCommand_25 MO Off(1)
HumanDetectionWindStatus_25 MI Off(1)
HumanDetectionTimeCommand_25 MO 5min(1)
HumanDetectionTimeStatus_25 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
26 ※ Dev Type AC
address

instance
point Name
number

9729 1 On/Off (Setting)


9730 2 On/Off (Status)
9731 3 Lock (Setting)
9732 4 Lock (Status)
9733 5 Filter Sign
9734 6 Filter Sign reset
9735 7 Operation Mode (Setting)
9736 8 Operation Mode (Status)
9737 9 Swing (Setting)
9738 10 Swing (Status)
9739 11 Fan Speed (Setting)
9740 12 Fan Speed (Status)
9741 13 Set Room Temperature
9742 14 Room Temperature
9743 15 Alarm
9744 16 Error Code
9747 19 Set Temperature (Status)
9748 20 Accumulated Power Distribution (Status)
9755 27 Set Upper Temperature (Setting)
9756 28 Set Lower Temperature (Setting)
9757 29 Set Upper Tempaerature (Status)
9758 30 Set Lower Temperature (Status)
9759 31 Mode Lock (Setting)
9760 32 Mode Lock (Status)
9761 33 Fan Lock (Setting)
9762 34 Fan Lock (Status)
9763 35 Occupancy (Setting)
9764 36 Occupancy (Status)
9765 37 2Set Cooling Set Temperature (Setting)
9766 38 2Set Cooling Set Temperature (Status)
9767 39 2Set Heating Set Temperature (Setting)
9768 40 2Set Heating Set Temperature (Status)
9769 41 2Set Cooling Upper Temperature (Setting)
9770 42 2Set Cooling Upper Temperature (Status)
9771 43 2Set Heating Upper Temperature (Setting)
9772 44 2Set Heating Upper Temperature (Status)
9773 45 2Set Cooling Lower Temperature (Setting)
9774 46 2Set Cooling Lower Temperature (Status)
9775 47 2Set Heating Lower Temperature (Setting)
9776 48 2Set Heating Lower Temperature (Status)
9777 49 Thermo Status (Status)
9778 50 Accumulated Gas Distribution (Status)
9779 51 Dust Sensor Available (Status)
9780 52 Air Cleaning Opereration (Setting)
9781 53 Air Cleaning Opereration (Status)
9782 54 Fine Dust (Status)
9783 55 Ultra Fine Dust (Status)
9784 56 Super Ultra Fine Dust (Status)
9785 57 Humidity (Status)
9786 58 Comfort Cooling Available (Status)
9787 59 Comfort Cooling Opereration (Setting)
9788 60 Comfort Cooling Opereration (Status)
9789 61 Comfort Cooling Step (Setting)
9790 62 Comfort Cooling Step (Status)
9791 63 Human Detection Available (Status)
9792 64 Human Detection Opereration (Setting)
9793 65 Human Detection Opereration (Status)
9794 66 Human Detection Wind (Setting)
9795 67 Human Detection Wind (Status)
9796 68 Human Detection Time (Setting)
9797 69 Human Detection Time (Status)
9798 70 Hotel Checkin (Setting)
9799 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_26 BO Stop(0) Start(1)
StartStopStatus_26 BI Stop(0) Start(1)
LockCommand_26 BO Permit(0) Prohibit(1)
LockStatus_26 BI Permit(0) Prohibit(1)
FilterSign_26 BI Off(0) On(1)
FilterSignReset_26 BV - Reset(1)
AirConModeCommand_26 MO Cool(1)
AirConModeStatus_26 MI Cool(1)
SwingCommand_26 BO Stop(0) Run(1)
SwingStatus_26 BI Stop(0) Run(1)
FanSpeedCommand_26 MO Low(1)
FanSpeedStatus_26 MI Low(1)
SetRoomTemp_26 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_26 AI ℃
Alarm_26 BI Normal(0) Abnormal(1)
MalfunctionCode_26 AI Refer to the
SetTempStatus_26 AI ℃
Accumulated power(100 Watt)_26 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_26 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_26 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_26 AI ℃
TempRangeLowerLimitStatus_26 AI ℃
ModeLockCommand_26 BO Permit(0) Prohibit(1)
ModeLockStatus_26 BI Permit(0) Prohibit(1)
FanLockCommand_26 BO Permit(0) Prohibit(1)
FanLockStatus_26 BI Permit(0) Prohibit(1)
OccupancyCommand_26 BO Unoccupied(0) Occupied(1)
OccupancyStatus_26 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_26 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_26 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_26 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_26 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_26 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_26 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_26 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_26 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_26 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_26 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_26 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_26 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_26 BI Off(0) On(1)
AccumulatedGas(100 Watt)_26 AI Wattage values (Unit : 100Watt)
DustSensorAvail_26 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_26 BO Stop(0) Run(1)
AirCleaningOperStatus_26 BI Stop(0) Run(1)
FineDustStatus_26 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_26 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_26 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_26 AI %
ComfortCoolingAvail_26 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_26 BO Stop(0) Run(1)
ComfortCoolingOperStatus_26 BI Stop(0) Run(1)
ComfortCoolingStepCommand_26 AV 1~3 step
ComfortCoolingStepStatus_26 AI 1~3 step
HumanDetectionAvail_26 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_26 MO Off(1)
HumanDetectionOperStatus_26 MI Off(1)
HumanDetectionWindCommand_26 MO Off(1)
HumanDetectionWindStatus_26 MI Off(1)
HumanDetectionTimeCommand_26 MO 5min(1)
HumanDetectionTimeStatus_26 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
27 ※ Dev Type AC
address

instance
point Name
number

9985 1 On/Off (Setting)


9986 2 On/Off (Status)
9987 3 Lock (Setting)
9988 4 Lock (Status)
9989 5 Filter Sign
9990 6 Filter Sign reset
9991 7 Operation Mode (Setting)
9992 8 Operation Mode (Status)
9993 9 Swing (Setting)
9994 10 Swing (Status)
9995 11 Fan Speed (Setting)
9996 12 Fan Speed (Status)
9997 13 Set Room Temperature
9998 14 Room Temperature
9999 15 Alarm
10000 16 Error Code
10003 19 Set Temperature (Status)
10004 20 Accumulated Power Distribution (Status)
10011 27 Set Upper Temperature (Setting)
10012 28 Set Lower Temperature (Setting)
10013 29 Set Upper Tempaerature (Status)
10014 30 Set Lower Temperature (Status)
10015 31 Mode Lock (Setting)
10016 32 Mode Lock (Status)
10017 33 Fan Lock (Setting)
10018 34 Fan Lock (Status)
10019 35 Occupancy (Setting)
10020 36 Occupancy (Status)
10021 37 2Set Cooling Set Temperature (Setting)
10022 38 2Set Cooling Set Temperature (Status)
10023 39 2Set Heating Set Temperature (Setting)
10024 40 2Set Heating Set Temperature (Status)
10025 41 2Set Cooling Upper Temperature (Setting)
10026 42 2Set Cooling Upper Temperature (Status)
10027 43 2Set Heating Upper Temperature (Setting)
10028 44 2Set Heating Upper Temperature (Status)
10029 45 2Set Cooling Lower Temperature (Setting)
10030 46 2Set Cooling Lower Temperature (Status)
10031 47 2Set Heating Lower Temperature (Setting)
10032 48 2Set Heating Lower Temperature (Status)
10033 49 Thermo Status (Status)
10034 50 Accumulated Gas Distribution (Status)
10035 51 Dust Sensor Available (Status)
10036 52 Air Cleaning Opereration (Setting)
10037 53 Air Cleaning Opereration (Status)
10038 54 Fine Dust (Status)
10039 55 Ultra Fine Dust (Status)
10040 56 Super Ultra Fine Dust (Status)
10041 57 Humidity (Status)
10042 58 Comfort Cooling Available (Status)
10043 59 Comfort Cooling Opereration (Setting)
10044 60 Comfort Cooling Opereration (Status)
10045 61 Comfort Cooling Step (Setting)
10046 62 Comfort Cooling Step (Status)
10047 63 Human Detection Available (Status)
10048 64 Human Detection Opereration (Setting)
10049 65 Human Detection Opereration (Status)
10050 66 Human Detection Wind (Setting)
10051 67 Human Detection Wind (Status)
10052 68 Human Detection Time (Setting)
10053 69 Human Detection Time (Status)
10054 70 Hotel Checkin (Setting)
10055 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_27 BO Stop(0) Start(1)
StartStopStatus_27 BI Stop(0) Start(1)
LockCommand_27 BO Permit(0) Prohibit(1)
LockStatus_27 BI Permit(0) Prohibit(1)
FilterSign_27 BI Off(0) On(1)
FilterSignReset_27 BV - Reset(1)
AirConModeCommand_27 MO Cool(1)
AirConModeStatus_27 MI Cool(1)
SwingCommand_27 BO Stop(0) Run(1)
SwingStatus_27 BI Stop(0) Run(1)
FanSpeedCommand_27 MO Low(1)
FanSpeedStatus_27 MI Low(1)
SetRoomTemp_27 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_27 AI ℃
Alarm_27 BI Normal(0) Abnormal(1)
MalfunctionCode_27 AI Refer to the
SetTempStatus_27 AI ℃
Accumulated power(100 Watt)_27 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_27 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_27 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_27 AI ℃
TempRangeLowerLimitStatus_27 AI ℃
ModeLockCommand_27 BO Permit(0) Prohibit(1)
ModeLockStatus_27 BI Permit(0) Prohibit(1)
FanLockCommand_27 BO Permit(0) Prohibit(1)
FanLockStatus_27 BI Permit(0) Prohibit(1)
OccupancyCommand_27 BO Unoccupied(0) Occupied(1)
OccupancyStatus_27 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_27 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_27 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_27 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_27 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_27 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_27 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_27 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_27 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_27 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_27 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_27 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_27 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_27 BI Off(0) On(1)
AccumulatedGas(100 Watt)_27 AI Wattage values (Unit : 100Watt)
DustSensorAvail_27 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_27 BO Stop(0) Run(1)
AirCleaningOperStatus_27 BI Stop(0) Run(1)
FineDustStatus_27 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_27 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_27 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_27 AI %
ComfortCoolingAvail_27 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_27 BO Stop(0) Run(1)
ComfortCoolingOperStatus_27 BI Stop(0) Run(1)
ComfortCoolingStepCommand_27 AV 1~3 step
ComfortCoolingStepStatus_27 AI 1~3 step
HumanDetectionAvail_27 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_27 MO Off(1)
HumanDetectionOperStatus_27 MI Off(1)
HumanDetectionWindCommand_27 MO Off(1)
HumanDetectionWindStatus_27 MI Off(1)
HumanDetectionTimeCommand_27 MO 5min(1)
HumanDetectionTimeStatus_27 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
28 ※ Dev Type AC
address

instance
point Name
number

10241 1 On/Off (Setting)


10242 2 On/Off (Status)
10243 3 Lock (Setting)
10244 4 Lock (Status)
10245 5 Filter Sign
10246 6 Filter Sign reset
10247 7 Operation Mode (Setting)
10248 8 Operation Mode (Status)
10249 9 Swing (Setting)
10250 10 Swing (Status)
10251 11 Fan Speed (Setting)
10252 12 Fan Speed (Status)
10253 13 Set Room Temperature
10254 14 Room Temperature
10255 15 Alarm
10256 16 Error Code
10259 19 Set Temperature (Status)
10260 20 Accumulated Power Distribution (Status)
10267 27 Set Upper Temperature (Setting)
10268 28 Set Lower Temperature (Setting)
10269 29 Set Upper Tempaerature (Status)
10270 30 Set Lower Temperature (Status)
10271 31 Mode Lock (Setting)
10272 32 Mode Lock (Status)
10273 33 Fan Lock (Setting)
10274 34 Fan Lock (Status)
10275 35 Occupancy (Setting)
10276 36 Occupancy (Status)
10277 37 2Set Cooling Set Temperature (Setting)
10278 38 2Set Cooling Set Temperature (Status)
10279 39 2Set Heating Set Temperature (Setting)
10280 40 2Set Heating Set Temperature (Status)
10281 41 2Set Cooling Upper Temperature (Setting)
10282 42 2Set Cooling Upper Temperature (Status)
10283 43 2Set Heating Upper Temperature (Setting)
10284 44 2Set Heating Upper Temperature (Status)
10285 45 2Set Cooling Lower Temperature (Setting)
10286 46 2Set Cooling Lower Temperature (Status)
10287 47 2Set Heating Lower Temperature (Setting)
10288 48 2Set Heating Lower Temperature (Status)
10289 49 Thermo Status (Status)
10290 50 Accumulated Gas Distribution (Status)
10291 51 Dust Sensor Available (Status)
10292 52 Air Cleaning Opereration (Setting)
10293 53 Air Cleaning Opereration (Status)
10294 54 Fine Dust (Status)
10295 55 Ultra Fine Dust (Status)
10296 56 Super Ultra Fine Dust (Status)
10297 57 Humidity (Status)
10298 58 Comfort Cooling Available (Status)
10299 59 Comfort Cooling Opereration (Setting)
10300 60 Comfort Cooling Opereration (Status)
10301 61 Comfort Cooling Step (Setting)
10302 62 Comfort Cooling Step (Status)
10303 63 Human Detection Available (Status)
10304 64 Human Detection Opereration (Setting)
10305 65 Human Detection Opereration (Status)
10306 66 Human Detection Wind (Setting)
10307 67 Human Detection Wind (Status)
10308 68 Human Detection Time (Setting)
10309 69 Human Detection Time (Status)
10310 70 Hotel Checkin (Setting)
10311 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_28 BO Stop(0) Start(1)
StartStopStatus_28 BI Stop(0) Start(1)
LockCommand_28 BO Permit(0) Prohibit(1)
LockStatus_28 BI Permit(0) Prohibit(1)
FilterSign_28 BI Off(0) On(1)
FilterSignReset_28 BV - Reset(1)
AirConModeCommand_28 MO Cool(1)
AirConModeStatus_28 MI Cool(1)
SwingCommand_28 BO Stop(0) Run(1)
SwingStatus_28 BI Stop(0) Run(1)
FanSpeedCommand_28 MO Low(1)
FanSpeedStatus_28 MI Low(1)
SetRoomTemp_28 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_28 AI ℃
Alarm_28 BI Normal(0) Abnormal(1)
MalfunctionCode_28 AI Refer to the
SetTempStatus_28 AI ℃
Accumulated power(100 Watt)_28 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_28 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_28 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_28 AI ℃
TempRangeLowerLimitStatus_28 AI ℃
ModeLockCommand_28 BO Permit(0) Prohibit(1)
ModeLockStatus_28 BI Permit(0) Prohibit(1)
FanLockCommand_28 BO Permit(0) Prohibit(1)
FanLockStatus_28 BI Permit(0) Prohibit(1)
OccupancyCommand_28 BO Unoccupied(0) Occupied(1)
OccupancyStatus_28 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_28 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_28 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_28 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_28 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_28 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_28 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_28 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_28 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_28 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_28 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_28 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_28 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_28 BI Off(0) On(1)
AccumulatedGas(100 Watt)_28 AI Wattage values (Unit : 100Watt)
DustSensorAvail_28 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_28 BO Stop(0) Run(1)
AirCleaningOperStatus_28 BI Stop(0) Run(1)
FineDustStatus_28 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_28 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_28 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_28 AI %
ComfortCoolingAvail_28 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_28 BO Stop(0) Run(1)
ComfortCoolingOperStatus_28 BI Stop(0) Run(1)
ComfortCoolingStepCommand_28 AV 1~3 step
ComfortCoolingStepStatus_28 AI 1~3 step
HumanDetectionAvail_28 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_28 MO Off(1)
HumanDetectionOperStatus_28 MI Off(1)
HumanDetectionWindCommand_28 MO Off(1)
HumanDetectionWindStatus_28 MI Off(1)
HumanDetectionTimeCommand_28 MO 5min(1)
HumanDetectionTimeStatus_28 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
29 ※ Dev Type AC
address

instance
point Name
number

10497 1 On/Off (Setting)


10498 2 On/Off (Status)
10499 3 Lock (Setting)
10500 4 Lock (Status)
10501 5 Filter Sign
10502 6 Filter Sign reset
10503 7 Operation Mode (Setting)
10504 8 Operation Mode (Status)
10505 9 Swing (Setting)
10506 10 Swing (Status)
10507 11 Fan Speed (Setting)
10508 12 Fan Speed (Status)
10509 13 Set Room Temperature
10510 14 Room Temperature
10511 15 Alarm
10512 16 Error Code
10515 19 Set Temperature (Status)
10516 20 Accumulated Power Distribution (Status)
10523 27 Set Upper Temperature (Setting)
10524 28 Set Lower Temperature (Setting)
10525 29 Set Upper Tempaerature (Status)
10526 30 Set Lower Temperature (Status)
10527 31 Mode Lock (Setting)
10528 32 Mode Lock (Status)
10529 33 Fan Lock (Setting)
10530 34 Fan Lock (Status)
10531 35 Occupancy (Setting)
10532 36 Occupancy (Status)
10533 37 2Set Cooling Set Temperature (Setting)
10534 38 2Set Cooling Set Temperature (Status)
10535 39 2Set Heating Set Temperature (Setting)
10536 40 2Set Heating Set Temperature (Status)
10537 41 2Set Cooling Upper Temperature (Setting)
10538 42 2Set Cooling Upper Temperature (Status)
10539 43 2Set Heating Upper Temperature (Setting)
10540 44 2Set Heating Upper Temperature (Status)
10541 45 2Set Cooling Lower Temperature (Setting)
10542 46 2Set Cooling Lower Temperature (Status)
10543 47 2Set Heating Lower Temperature (Setting)
10544 48 2Set Heating Lower Temperature (Status)
10545 49 Thermo Status (Status)
10546 50 Accumulated Gas Distribution (Status)
10547 51 Dust Sensor Available (Status)
10548 52 Air Cleaning Opereration (Setting)
10549 53 Air Cleaning Opereration (Status)
10550 54 Fine Dust (Status)
10551 55 Ultra Fine Dust (Status)
10552 56 Super Ultra Fine Dust (Status)
10553 57 Humidity (Status)
10554 58 Comfort Cooling Available (Status)
10555 59 Comfort Cooling Opereration (Setting)
10556 60 Comfort Cooling Opereration (Status)
10557 61 Comfort Cooling Step (Setting)
10558 62 Comfort Cooling Step (Status)
10559 63 Human Detection Available (Status)
10560 64 Human Detection Opereration (Setting)
10561 65 Human Detection Opereration (Status)
10562 66 Human Detection Wind (Setting)
10563 67 Human Detection Wind (Status)
10564 68 Human Detection Time (Setting)
10565 69 Human Detection Time (Status)
10566 70 Hotel Checkin (Setting)
10567 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_29 BO Stop(0) Start(1)
StartStopStatus_29 BI Stop(0) Start(1)
LockCommand_29 BO Permit(0) Prohibit(1)
LockStatus_29 BI Permit(0) Prohibit(1)
FilterSign_29 BI Off(0) On(1)
FilterSignReset_29 BV - Reset(1)
AirConModeCommand_29 MO Cool(1)
AirConModeStatus_29 MI Cool(1)
SwingCommand_29 BO Stop(0) Run(1)
SwingStatus_29 BI Stop(0) Run(1)
FanSpeedCommand_29 MO Low(1)
FanSpeedStatus_29 MI Low(1)
SetRoomTemp_29 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_29 AI ℃
Alarm_29 BI Normal(0) Abnormal(1)
MalfunctionCode_29 AI Refer to the
SetTempStatus_29 AI ℃
Accumulated power(100 Watt)_29 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_29 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_29 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_29 AI ℃
TempRangeLowerLimitStatus_29 AI ℃
ModeLockCommand_29 BO Permit(0) Prohibit(1)
ModeLockStatus_29 BI Permit(0) Prohibit(1)
FanLockCommand_29 BO Permit(0) Prohibit(1)
FanLockStatus_29 BI Permit(0) Prohibit(1)
OccupancyCommand_29 BO Unoccupied(0) Occupied(1)
OccupancyStatus_29 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_29 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_29 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_29 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_29 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_29 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_29 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_29 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_29 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_29 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_29 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_29 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_29 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_29 BI Off(0) On(1)
AccumulatedGas(100 Watt)_29 AI Wattage values (Unit : 100Watt)
DustSensorAvail_29 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_29 BO Stop(0) Run(1)
AirCleaningOperStatus_29 BI Stop(0) Run(1)
FineDustStatus_29 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_29 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_29 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_29 AI %
ComfortCoolingAvail_29 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_29 BO Stop(0) Run(1)
ComfortCoolingOperStatus_29 BI Stop(0) Run(1)
ComfortCoolingStepCommand_29 AV 1~3 step
ComfortCoolingStepStatus_29 AI 1~3 step
HumanDetectionAvail_29 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_29 MO Off(1)
HumanDetectionOperStatus_29 MI Off(1)
HumanDetectionWindCommand_29 MO Off(1)
HumanDetectionWindStatus_29 MI Off(1)
HumanDetectionTimeCommand_29 MO 5min(1)
HumanDetectionTimeStatus_29 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2a ※ Dev Type AC
address

instance
point Name
number

10753 1 On/Off (Setting)


10754 2 On/Off (Status)
10755 3 Lock (Setting)
10756 4 Lock (Status)
10757 5 Filter Sign
10758 6 Filter Sign reset
10759 7 Operation Mode (Setting)
10760 8 Operation Mode (Status)
10761 9 Swing (Setting)
10762 10 Swing (Status)
10763 11 Fan Speed (Setting)
10764 12 Fan Speed (Status)
10765 13 Set Room Temperature
10766 14 Room Temperature
10767 15 Alarm
10768 16 Error Code
10771 19 Set Temperature (Status)
10772 20 Accumulated Power Distribution (Status)
10779 27 Set Upper Temperature (Setting)
10780 28 Set Lower Temperature (Setting)
10781 29 Set Upper Tempaerature (Status)
10782 30 Set Lower Temperature (Status)
10783 31 Mode Lock (Setting)
10784 32 Mode Lock (Status)
10785 33 Fan Lock (Setting)
10786 34 Fan Lock (Status)
10787 35 Occupancy (Setting)
10788 36 Occupancy (Status)
10789 37 2Set Cooling Set Temperature (Setting)
10790 38 2Set Cooling Set Temperature (Status)
10791 39 2Set Heating Set Temperature (Setting)
10792 40 2Set Heating Set Temperature (Status)
10793 41 2Set Cooling Upper Temperature (Setting)
10794 42 2Set Cooling Upper Temperature (Status)
10795 43 2Set Heating Upper Temperature (Setting)
10796 44 2Set Heating Upper Temperature (Status)
10797 45 2Set Cooling Lower Temperature (Setting)
10798 46 2Set Cooling Lower Temperature (Status)
10799 47 2Set Heating Lower Temperature (Setting)
10800 48 2Set Heating Lower Temperature (Status)
10801 49 Thermo Status (Status)
10802 50 Accumulated Gas Distribution (Status)
10803 51 Dust Sensor Available (Status)
10804 52 Air Cleaning Opereration (Setting)
10805 53 Air Cleaning Opereration (Status)
10806 54 Fine Dust (Status)
10807 55 Ultra Fine Dust (Status)
10808 56 Super Ultra Fine Dust (Status)
10809 57 Humidity (Status)
10810 58 Comfort Cooling Available (Status)
10811 59 Comfort Cooling Opereration (Setting)
10812 60 Comfort Cooling Opereration (Status)
10813 61 Comfort Cooling Step (Setting)
10814 62 Comfort Cooling Step (Status)
10815 63 Human Detection Available (Status)
10816 64 Human Detection Opereration (Setting)
10817 65 Human Detection Opereration (Status)
10818 66 Human Detection Wind (Setting)
10819 67 Human Detection Wind (Status)
10820 68 Human Detection Time (Setting)
10821 69 Human Detection Time (Status)
10822 70 Hotel Checkin (Setting)
10823 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2a BO Stop(0) Start(1)
StartStopStatus_2a BI Stop(0) Start(1)
LockCommand_2a BO Permit(0) Prohibit(1)
LockStatus_2a BI Permit(0) Prohibit(1)
FilterSign_2a BI Off(0) On(1)
FilterSignReset_2a BV - Reset(1)
AirConModeCommand_2a MO Cool(1)
AirConModeStatus_2a MI Cool(1)
SwingCommand_2a BO Stop(0) Run(1)
SwingStatus_2a BI Stop(0) Run(1)
FanSpeedCommand_2a MO Low(1)
FanSpeedStatus_2a MI Low(1)
SetRoomTemp_2a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2a AI ℃
Alarm_2a BI Normal(0) Abnormal(1)
MalfunctionCode_2a AI Refer to the
SetTempStatus_2a AI ℃
Accumulated power(100 Watt)_2a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2a AI ℃
TempRangeLowerLimitStatus_2a AI ℃
ModeLockCommand_2a BO Permit(0) Prohibit(1)
ModeLockStatus_2a BI Permit(0) Prohibit(1)
FanLockCommand_2a BO Permit(0) Prohibit(1)
FanLockStatus_2a BI Permit(0) Prohibit(1)
OccupancyCommand_2a BO Unoccupied(0) Occupied(1)
OccupancyStatus_2a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2a BI Off(0) On(1)
AccumulatedGas(100 Watt)_2a AI Wattage values (Unit : 100Watt)
DustSensorAvail_2a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2a BO Stop(0) Run(1)
AirCleaningOperStatus_2a BI Stop(0) Run(1)
FineDustStatus_2a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2a AI %
ComfortCoolingAvail_2a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2a BO Stop(0) Run(1)
ComfortCoolingOperStatus_2a BI Stop(0) Run(1)
ComfortCoolingStepCommand_2a AV 1~3 step
ComfortCoolingStepStatus_2a AI 1~3 step
HumanDetectionAvail_2a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2a MO Off(1)
HumanDetectionOperStatus_2a MI Off(1)
HumanDetectionWindCommand_2a MO Off(1)
HumanDetectionWindStatus_2a MI Off(1)
HumanDetectionTimeCommand_2a MO 5min(1)
HumanDetectionTimeStatus_2a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2b ※ Dev Type AC
address

instance
point Name
number

11009 1 On/Off (Setting)


11010 2 On/Off (Status)
11011 3 Lock (Setting)
11012 4 Lock (Status)
11013 5 Filter Sign
11014 6 Filter Sign reset
11015 7 Operation Mode (Setting)
11016 8 Operation Mode (Status)
11017 9 Swing (Setting)
11018 10 Swing (Status)
11019 11 Fan Speed (Setting)
11020 12 Fan Speed (Status)
11021 13 Set Room Temperature
11022 14 Room Temperature
11023 15 Alarm
11024 16 Error Code
11027 19 Set Temperature (Status)
11028 20 Accumulated Power Distribution (Status)
11035 27 Set Upper Temperature (Setting)
11036 28 Set Lower Temperature (Setting)
11037 29 Set Upper Tempaerature (Status)
11038 30 Set Lower Temperature (Status)
11039 31 Mode Lock (Setting)
11040 32 Mode Lock (Status)
11041 33 Fan Lock (Setting)
11042 34 Fan Lock (Status)
11043 35 Occupancy (Setting)
11044 36 Occupancy (Status)
11045 37 2Set Cooling Set Temperature (Setting)
11046 38 2Set Cooling Set Temperature (Status)
11047 39 2Set Heating Set Temperature (Setting)
11048 40 2Set Heating Set Temperature (Status)
11049 41 2Set Cooling Upper Temperature (Setting)
11050 42 2Set Cooling Upper Temperature (Status)
11051 43 2Set Heating Upper Temperature (Setting)
11052 44 2Set Heating Upper Temperature (Status)
11053 45 2Set Cooling Lower Temperature (Setting)
11054 46 2Set Cooling Lower Temperature (Status)
11055 47 2Set Heating Lower Temperature (Setting)
11056 48 2Set Heating Lower Temperature (Status)
11057 49 Thermo Status (Status)
11058 50 Accumulated Gas Distribution (Status)
11059 51 Dust Sensor Available (Status)
11060 52 Air Cleaning Opereration (Setting)
11061 53 Air Cleaning Opereration (Status)
11062 54 Fine Dust (Status)
11063 55 Ultra Fine Dust (Status)
11064 56 Super Ultra Fine Dust (Status)
11065 57 Humidity (Status)
11066 58 Comfort Cooling Available (Status)
11067 59 Comfort Cooling Opereration (Setting)
11068 60 Comfort Cooling Opereration (Status)
11069 61 Comfort Cooling Step (Setting)
11070 62 Comfort Cooling Step (Status)
11071 63 Human Detection Available (Status)
11072 64 Human Detection Opereration (Setting)
11073 65 Human Detection Opereration (Status)
11074 66 Human Detection Wind (Setting)
11075 67 Human Detection Wind (Status)
11076 68 Human Detection Time (Setting)
11077 69 Human Detection Time (Status)
11078 70 Hotel Checkin (Setting)
11079 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2b BO Stop(0) Start(1)
StartStopStatus_2b BI Stop(0) Start(1)
LockCommand_2b BO Permit(0) Prohibit(1)
LockStatus_2b BI Permit(0) Prohibit(1)
FilterSign_2b BI Off(0) On(1)
FilterSignReset_2b BV - Reset(1)
AirConModeCommand_2b MO Cool(1)
AirConModeStatus_2b MI Cool(1)
SwingCommand_2b BO Stop(0) Run(1)
SwingStatus_2b BI Stop(0) Run(1)
FanSpeedCommand_2b MO Low(1)
FanSpeedStatus_2b MI Low(1)
SetRoomTemp_2b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2b AI ℃
Alarm_2b BI Normal(0) Abnormal(1)
MalfunctionCode_2b AI Refer to the
SetTempStatus_2b AI ℃
Accumulated power(100 Watt)_2b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2b AI ℃
TempRangeLowerLimitStatus_2b AI ℃
ModeLockCommand_2b BO Permit(0) Prohibit(1)
ModeLockStatus_2b BI Permit(0) Prohibit(1)
FanLockCommand_2b BO Permit(0) Prohibit(1)
FanLockStatus_2b BI Permit(0) Prohibit(1)
OccupancyCommand_2b BO Unoccupied(0) Occupied(1)
OccupancyStatus_2b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2b BI Off(0) On(1)
AccumulatedGas(100 Watt)_2b AI Wattage values (Unit : 100Watt)
DustSensorAvail_2b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2b BO Stop(0) Run(1)
AirCleaningOperStatus_2b BI Stop(0) Run(1)
FineDustStatus_2b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2b AI %
ComfortCoolingAvail_2b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2b BO Stop(0) Run(1)
ComfortCoolingOperStatus_2b BI Stop(0) Run(1)
ComfortCoolingStepCommand_2b AV 1~3 step
ComfortCoolingStepStatus_2b AI 1~3 step
HumanDetectionAvail_2b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2b MO Off(1)
HumanDetectionOperStatus_2b MI Off(1)
HumanDetectionWindCommand_2b MO Off(1)
HumanDetectionWindStatus_2b MI Off(1)
HumanDetectionTimeCommand_2b MO 5min(1)
HumanDetectionTimeStatus_2b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2c ※ Dev Type AC
address

instance
point Name
number

11265 1 On/Off (Setting)


11266 2 On/Off (Status)
11267 3 Lock (Setting)
11268 4 Lock (Status)
11269 5 Filter Sign
11270 6 Filter Sign reset
11271 7 Operation Mode (Setting)
11272 8 Operation Mode (Status)
11273 9 Swing (Setting)
11274 10 Swing (Status)
11275 11 Fan Speed (Setting)
11276 12 Fan Speed (Status)
11277 13 Set Room Temperature
11278 14 Room Temperature
11279 15 Alarm
11280 16 Error Code
11283 19 Set Temperature (Status)
11284 20 Accumulated Power Distribution (Status)
11291 27 Set Upper Temperature (Setting)
11292 28 Set Lower Temperature (Setting)
11293 29 Set Upper Tempaerature (Status)
11294 30 Set Lower Temperature (Status)
11295 31 Mode Lock (Setting)
11296 32 Mode Lock (Status)
11297 33 Fan Lock (Setting)
11298 34 Fan Lock (Status)
11299 35 Occupancy (Setting)
11300 36 Occupancy (Status)
11301 37 2Set Cooling Set Temperature (Setting)
11302 38 2Set Cooling Set Temperature (Status)
11303 39 2Set Heating Set Temperature (Setting)
11304 40 2Set Heating Set Temperature (Status)
11305 41 2Set Cooling Upper Temperature (Setting)
11306 42 2Set Cooling Upper Temperature (Status)
11307 43 2Set Heating Upper Temperature (Setting)
11308 44 2Set Heating Upper Temperature (Status)
11309 45 2Set Cooling Lower Temperature (Setting)
11310 46 2Set Cooling Lower Temperature (Status)
11311 47 2Set Heating Lower Temperature (Setting)
11312 48 2Set Heating Lower Temperature (Status)
11313 49 Thermo Status (Status)
11314 50 Accumulated Gas Distribution (Status)
11315 51 Dust Sensor Available (Status)
11316 52 Air Cleaning Opereration (Setting)
11317 53 Air Cleaning Opereration (Status)
11318 54 Fine Dust (Status)
11319 55 Ultra Fine Dust (Status)
11320 56 Super Ultra Fine Dust (Status)
11321 57 Humidity (Status)
11322 58 Comfort Cooling Available (Status)
11323 59 Comfort Cooling Opereration (Setting)
11324 60 Comfort Cooling Opereration (Status)
11325 61 Comfort Cooling Step (Setting)
11326 62 Comfort Cooling Step (Status)
11327 63 Human Detection Available (Status)
11328 64 Human Detection Opereration (Setting)
11329 65 Human Detection Opereration (Status)
11330 66 Human Detection Wind (Setting)
11331 67 Human Detection Wind (Status)
11332 68 Human Detection Time (Setting)
11333 69 Human Detection Time (Status)
11334 70 Hotel Checkin (Setting)
11335 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2c BO Stop(0) Start(1)
StartStopStatus_2c BI Stop(0) Start(1)
LockCommand_2c BO Permit(0) Prohibit(1)
LockStatus_2c BI Permit(0) Prohibit(1)
FilterSign_2c BI Off(0) On(1)
FilterSignReset_2c BV - Reset(1)
AirConModeCommand_2c MO Cool(1)
AirConModeStatus_2c MI Cool(1)
SwingCommand_2c BO Stop(0) Run(1)
SwingStatus_2c BI Stop(0) Run(1)
FanSpeedCommand_2c MO Low(1)
FanSpeedStatus_2c MI Low(1)
SetRoomTemp_2c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2c AI ℃
Alarm_2c BI Normal(0) Abnormal(1)
MalfunctionCode_2c AI Refer to the
SetTempStatus_2c AI ℃
Accumulated power(100 Watt)_2c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2c AI ℃
TempRangeLowerLimitStatus_2c AI ℃
ModeLockCommand_2c BO Permit(0) Prohibit(1)
ModeLockStatus_2c BI Permit(0) Prohibit(1)
FanLockCommand_2c BO Permit(0) Prohibit(1)
FanLockStatus_2c BI Permit(0) Prohibit(1)
OccupancyCommand_2c BO Unoccupied(0) Occupied(1)
OccupancyStatus_2c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2c BI Off(0) On(1)
AccumulatedGas(100 Watt)_2c AI Wattage values (Unit : 100Watt)
DustSensorAvail_2c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2c BO Stop(0) Run(1)
AirCleaningOperStatus_2c BI Stop(0) Run(1)
FineDustStatus_2c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2c AI %
ComfortCoolingAvail_2c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2c BO Stop(0) Run(1)
ComfortCoolingOperStatus_2c BI Stop(0) Run(1)
ComfortCoolingStepCommand_2c AV 1~3 step
ComfortCoolingStepStatus_2c AI 1~3 step
HumanDetectionAvail_2c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2c MO Off(1)
HumanDetectionOperStatus_2c MI Off(1)
HumanDetectionWindCommand_2c MO Off(1)
HumanDetectionWindStatus_2c MI Off(1)
HumanDetectionTimeCommand_2c MO 5min(1)
HumanDetectionTimeStatus_2c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2d ※ Dev Type AC
address

instance
point Name
number

11521 1 On/Off (Setting)


11522 2 On/Off (Status)
11523 3 Lock (Setting)
11524 4 Lock (Status)
11525 5 Filter Sign
11526 6 Filter Sign reset
11527 7 Operation Mode (Setting)
11528 8 Operation Mode (Status)
11529 9 Swing (Setting)
11530 10 Swing (Status)
11531 11 Fan Speed (Setting)
11532 12 Fan Speed (Status)
11533 13 Set Room Temperature
11534 14 Room Temperature
11535 15 Alarm
11536 16 Error Code
11539 19 Set Temperature (Status)
11540 20 Accumulated Power Distribution (Status)
11547 27 Set Upper Temperature (Setting)
11548 28 Set Lower Temperature (Setting)
11549 29 Set Upper Tempaerature (Status)
11550 30 Set Lower Temperature (Status)
11551 31 Mode Lock (Setting)
11552 32 Mode Lock (Status)
11553 33 Fan Lock (Setting)
11554 34 Fan Lock (Status)
11555 35 Occupancy (Setting)
11556 36 Occupancy (Status)
11557 37 2Set Cooling Set Temperature (Setting)
11558 38 2Set Cooling Set Temperature (Status)
11559 39 2Set Heating Set Temperature (Setting)
11560 40 2Set Heating Set Temperature (Status)
11561 41 2Set Cooling Upper Temperature (Setting)
11562 42 2Set Cooling Upper Temperature (Status)
11563 43 2Set Heating Upper Temperature (Setting)
11564 44 2Set Heating Upper Temperature (Status)
11565 45 2Set Cooling Lower Temperature (Setting)
11566 46 2Set Cooling Lower Temperature (Status)
11567 47 2Set Heating Lower Temperature (Setting)
11568 48 2Set Heating Lower Temperature (Status)
11569 49 Thermo Status (Status)
11570 50 Accumulated Gas Distribution (Status)
11571 51 Dust Sensor Available (Status)
11572 52 Air Cleaning Opereration (Setting)
11573 53 Air Cleaning Opereration (Status)
11574 54 Fine Dust (Status)
11575 55 Ultra Fine Dust (Status)
11576 56 Super Ultra Fine Dust (Status)
11577 57 Humidity (Status)
11578 58 Comfort Cooling Available (Status)
11579 59 Comfort Cooling Opereration (Setting)
11580 60 Comfort Cooling Opereration (Status)
11581 61 Comfort Cooling Step (Setting)
11582 62 Comfort Cooling Step (Status)
11583 63 Human Detection Available (Status)
11584 64 Human Detection Opereration (Setting)
11585 65 Human Detection Opereration (Status)
11586 66 Human Detection Wind (Setting)
11587 67 Human Detection Wind (Status)
11588 68 Human Detection Time (Setting)
11589 69 Human Detection Time (Status)
11590 70 Hotel Checkin (Setting)
11591 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2d BO Stop(0) Start(1)
StartStopStatus_2d BI Stop(0) Start(1)
LockCommand_2d BO Permit(0) Prohibit(1)
LockStatus_2d BI Permit(0) Prohibit(1)
FilterSign_2d BI Off(0) On(1)
FilterSignReset_2d BV - Reset(1)
AirConModeCommand_2d MO Cool(1)
AirConModeStatus_2d MI Cool(1)
SwingCommand_2d BO Stop(0) Run(1)
SwingStatus_2d BI Stop(0) Run(1)
FanSpeedCommand_2d MO Low(1)
FanSpeedStatus_2d MI Low(1)
SetRoomTemp_2d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2d AI ℃
Alarm_2d BI Normal(0) Abnormal(1)
MalfunctionCode_2d AI Refer to the
SetTempStatus_2d AI ℃
Accumulated power(100 Watt)_2d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2d AI ℃
TempRangeLowerLimitStatus_2d AI ℃
ModeLockCommand_2d BO Permit(0) Prohibit(1)
ModeLockStatus_2d BI Permit(0) Prohibit(1)
FanLockCommand_2d BO Permit(0) Prohibit(1)
FanLockStatus_2d BI Permit(0) Prohibit(1)
OccupancyCommand_2d BO Unoccupied(0) Occupied(1)
OccupancyStatus_2d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2d BI Off(0) On(1)
AccumulatedGas(100 Watt)_2d AI Wattage values (Unit : 100Watt)
DustSensorAvail_2d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2d BO Stop(0) Run(1)
AirCleaningOperStatus_2d BI Stop(0) Run(1)
FineDustStatus_2d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2d AI %
ComfortCoolingAvail_2d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2d BO Stop(0) Run(1)
ComfortCoolingOperStatus_2d BI Stop(0) Run(1)
ComfortCoolingStepCommand_2d AV 1~3 step
ComfortCoolingStepStatus_2d AI 1~3 step
HumanDetectionAvail_2d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2d MO Off(1)
HumanDetectionOperStatus_2d MI Off(1)
HumanDetectionWindCommand_2d MO Off(1)
HumanDetectionWindStatus_2d MI Off(1)
HumanDetectionTimeCommand_2d MO 5min(1)
HumanDetectionTimeStatus_2d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2e ※ Dev Type AC
address

instance
point Name
number

11777 1 On/Off (Setting)


11778 2 On/Off (Status)
11779 3 Lock (Setting)
11780 4 Lock (Status)
11781 5 Filter Sign
11782 6 Filter Sign reset
11783 7 Operation Mode (Setting)
11784 8 Operation Mode (Status)
11785 9 Swing (Setting)
11786 10 Swing (Status)
11787 11 Fan Speed (Setting)
11788 12 Fan Speed (Status)
11789 13 Set Room Temperature
11790 14 Room Temperature
11791 15 Alarm
11792 16 Error Code
11795 19 Set Temperature (Status)
11796 20 Accumulated Power Distribution (Status)
11803 27 Set Upper Temperature (Setting)
11804 28 Set Lower Temperature (Setting)
11805 29 Set Upper Tempaerature (Status)
11806 30 Set Lower Temperature (Status)
11807 31 Mode Lock (Setting)
11808 32 Mode Lock (Status)
11809 33 Fan Lock (Setting)
11810 34 Fan Lock (Status)
11811 35 Occupancy (Setting)
11812 36 Occupancy (Status)
11813 37 2Set Cooling Set Temperature (Setting)
11814 38 2Set Cooling Set Temperature (Status)
11815 39 2Set Heating Set Temperature (Setting)
11816 40 2Set Heating Set Temperature (Status)
11817 41 2Set Cooling Upper Temperature (Setting)
11818 42 2Set Cooling Upper Temperature (Status)
11819 43 2Set Heating Upper Temperature (Setting)
11820 44 2Set Heating Upper Temperature (Status)
11821 45 2Set Cooling Lower Temperature (Setting)
11822 46 2Set Cooling Lower Temperature (Status)
11823 47 2Set Heating Lower Temperature (Setting)
11824 48 2Set Heating Lower Temperature (Status)
11825 49 Thermo Status (Status)
11826 50 Accumulated Gas Distribution (Status)
11827 51 Dust Sensor Available (Status)
11828 52 Air Cleaning Opereration (Setting)
11829 53 Air Cleaning Opereration (Status)
11830 54 Fine Dust (Status)
11831 55 Ultra Fine Dust (Status)
11832 56 Super Ultra Fine Dust (Status)
11833 57 Humidity (Status)
11834 58 Comfort Cooling Available (Status)
11835 59 Comfort Cooling Opereration (Setting)
11836 60 Comfort Cooling Opereration (Status)
11837 61 Comfort Cooling Step (Setting)
11838 62 Comfort Cooling Step (Status)
11839 63 Human Detection Available (Status)
11840 64 Human Detection Opereration (Setting)
11841 65 Human Detection Opereration (Status)
11842 66 Human Detection Wind (Setting)
11843 67 Human Detection Wind (Status)
11844 68 Human Detection Time (Setting)
11845 69 Human Detection Time (Status)
11846 70 Hotel Checkin (Setting)
11847 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2e BO Stop(0) Start(1)
StartStopStatus_2e BI Stop(0) Start(1)
LockCommand_2e BO Permit(0) Prohibit(1)
LockStatus_2e BI Permit(0) Prohibit(1)
FilterSign_2e BI Off(0) On(1)
FilterSignReset_2e BV - Reset(1)
AirConModeCommand_2e MO Cool(1)
AirConModeStatus_2e MI Cool(1)
SwingCommand_2e BO Stop(0) Run(1)
SwingStatus_2e BI Stop(0) Run(1)
FanSpeedCommand_2e MO Low(1)
FanSpeedStatus_2e MI Low(1)
SetRoomTemp_2e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2e AI ℃
Alarm_2e BI Normal(0) Abnormal(1)
MalfunctionCode_2e AI Refer to the
SetTempStatus_2e AI ℃
Accumulated power(100 Watt)_2e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2e AI ℃
TempRangeLowerLimitStatus_2e AI ℃
ModeLockCommand_2e BO Permit(0) Prohibit(1)
ModeLockStatus_2e BI Permit(0) Prohibit(1)
FanLockCommand_2e BO Permit(0) Prohibit(1)
FanLockStatus_2e BI Permit(0) Prohibit(1)
OccupancyCommand_2e BO Unoccupied(0) Occupied(1)
OccupancyStatus_2e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2e BI Off(0) On(1)
AccumulatedGas(100 Watt)_2e AI Wattage values (Unit : 100Watt)
DustSensorAvail_2e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2e BO Stop(0) Run(1)
AirCleaningOperStatus_2e BI Stop(0) Run(1)
FineDustStatus_2e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2e AI %
ComfortCoolingAvail_2e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2e BO Stop(0) Run(1)
ComfortCoolingOperStatus_2e BI Stop(0) Run(1)
ComfortCoolingStepCommand_2e AV 1~3 step
ComfortCoolingStepStatus_2e AI 1~3 step
HumanDetectionAvail_2e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2e MO Off(1)
HumanDetectionOperStatus_2e MI Off(1)
HumanDetectionWindCommand_2e MO Off(1)
HumanDetectionWindStatus_2e MI Off(1)
HumanDetectionTimeCommand_2e MO 5min(1)
HumanDetectionTimeStatus_2e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2f ※ Dev Type AC
address

instance
point Name
number

12033 1 On/Off (Setting)


12034 2 On/Off (Status)
12035 3 Lock (Setting)
12036 4 Lock (Status)
12037 5 Filter Sign
12038 6 Filter Sign reset
12039 7 Operation Mode (Setting)
12040 8 Operation Mode (Status)
12041 9 Swing (Setting)
12042 10 Swing (Status)
12043 11 Fan Speed (Setting)
12044 12 Fan Speed (Status)
12045 13 Set Room Temperature
12046 14 Room Temperature
12047 15 Alarm
12048 16 Error Code
12051 19 Set Temperature (Status)
12052 20 Accumulated Power Distribution (Status)
12059 27 Set Upper Temperature (Setting)
12060 28 Set Lower Temperature (Setting)
12061 29 Set Upper Tempaerature (Status)
12062 30 Set Lower Temperature (Status)
12063 31 Mode Lock (Setting)
12064 32 Mode Lock (Status)
12065 33 Fan Lock (Setting)
12066 34 Fan Lock (Status)
12067 35 Occupancy (Setting)
12068 36 Occupancy (Status)
12069 37 2Set Cooling Set Temperature (Setting)
12070 38 2Set Cooling Set Temperature (Status)
12071 39 2Set Heating Set Temperature (Setting)
12072 40 2Set Heating Set Temperature (Status)
12073 41 2Set Cooling Upper Temperature (Setting)
12074 42 2Set Cooling Upper Temperature (Status)
12075 43 2Set Heating Upper Temperature (Setting)
12076 44 2Set Heating Upper Temperature (Status)
12077 45 2Set Cooling Lower Temperature (Setting)
12078 46 2Set Cooling Lower Temperature (Status)
12079 47 2Set Heating Lower Temperature (Setting)
12080 48 2Set Heating Lower Temperature (Status)
12081 49 Thermo Status (Status)
12082 50 Accumulated Gas Distribution (Status)
12083 51 Dust Sensor Available (Status)
12084 52 Air Cleaning Opereration (Setting)
12085 53 Air Cleaning Opereration (Status)
12086 54 Fine Dust (Status)
12087 55 Ultra Fine Dust (Status)
12088 56 Super Ultra Fine Dust (Status)
12089 57 Humidity (Status)
12090 58 Comfort Cooling Available (Status)
12091 59 Comfort Cooling Opereration (Setting)
12092 60 Comfort Cooling Opereration (Status)
12093 61 Comfort Cooling Step (Setting)
12094 62 Comfort Cooling Step (Status)
12095 63 Human Detection Available (Status)
12096 64 Human Detection Opereration (Setting)
12097 65 Human Detection Opereration (Status)
12098 66 Human Detection Wind (Setting)
12099 67 Human Detection Wind (Status)
12100 68 Human Detection Time (Setting)
12101 69 Human Detection Time (Status)
12102 70 Hotel Checkin (Setting)
12103 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2f BO Stop(0) Start(1)
StartStopStatus_2f BI Stop(0) Start(1)
LockCommand_2f BO Permit(0) Prohibit(1)
LockStatus_2f BI Permit(0) Prohibit(1)
FilterSign_2f BI Off(0) On(1)
FilterSignReset_2f BV - Reset(1)
AirConModeCommand_2f MO Cool(1)
AirConModeStatus_2f MI Cool(1)
SwingCommand_2f BO Stop(0) Run(1)
SwingStatus_2f BI Stop(0) Run(1)
FanSpeedCommand_2f MO Low(1)
FanSpeedStatus_2f MI Low(1)
SetRoomTemp_2f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2f AI ℃
Alarm_2f BI Normal(0) Abnormal(1)
MalfunctionCode_2f AI Refer to the
SetTempStatus_2f AI ℃
Accumulated power(100 Watt)_2f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2f AI ℃
TempRangeLowerLimitStatus_2f AI ℃
ModeLockCommand_2f BO Permit(0) Prohibit(1)
ModeLockStatus_2f BI Permit(0) Prohibit(1)
FanLockCommand_2f BO Permit(0) Prohibit(1)
FanLockStatus_2f BI Permit(0) Prohibit(1)
OccupancyCommand_2f BO Unoccupied(0) Occupied(1)
OccupancyStatus_2f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2f BI Off(0) On(1)
AccumulatedGas(100 Watt)_2f AI Wattage values (Unit : 100Watt)
DustSensorAvail_2f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2f BO Stop(0) Run(1)
AirCleaningOperStatus_2f BI Stop(0) Run(1)
FineDustStatus_2f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2f AI %
ComfortCoolingAvail_2f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2f BO Stop(0) Run(1)
ComfortCoolingOperStatus_2f BI Stop(0) Run(1)
ComfortCoolingStepCommand_2f AV 1~3 step
ComfortCoolingStepStatus_2f AI 1~3 step
HumanDetectionAvail_2f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2f MO Off(1)
HumanDetectionOperStatus_2f MI Off(1)
HumanDetectionWindCommand_2f MO Off(1)
HumanDetectionWindStatus_2f MI Off(1)
HumanDetectionTimeCommand_2f MO 5min(1)
HumanDetectionTimeStatus_2f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
30 ※ Dev Type AC
address

instance
point Name
number

12289 1 On/Off (Setting)


12290 2 On/Off (Status)
12291 3 Lock (Setting)
12292 4 Lock (Status)
12293 5 Filter Sign
12294 6 Filter Sign reset
12295 7 Operation Mode (Setting)
12296 8 Operation Mode (Status)
12297 9 Swing (Setting)
12298 10 Swing (Status)
12299 11 Fan Speed (Setting)
12300 12 Fan Speed (Status)
12301 13 Set Room Temperature
12302 14 Room Temperature
12303 15 Alarm
12304 16 Error Code
12307 19 Set Temperature (Status)
12308 20 Accumulated Power Distribution (Status)
12315 27 Set Upper Temperature (Setting)
12316 28 Set Lower Temperature (Setting)
12317 29 Set Upper Tempaerature (Status)
12318 30 Set Lower Temperature (Status)
12319 31 Mode Lock (Setting)
12320 32 Mode Lock (Status)
12321 33 Fan Lock (Setting)
12322 34 Fan Lock (Status)
12323 35 Occupancy (Setting)
12324 36 Occupancy (Status)
12325 37 2Set Cooling Set Temperature (Setting)
12326 38 2Set Cooling Set Temperature (Status)
12327 39 2Set Heating Set Temperature (Setting)
12328 40 2Set Heating Set Temperature (Status)
12329 41 2Set Cooling Upper Temperature (Setting)
12330 42 2Set Cooling Upper Temperature (Status)
12331 43 2Set Heating Upper Temperature (Setting)
12332 44 2Set Heating Upper Temperature (Status)
12333 45 2Set Cooling Lower Temperature (Setting)
12334 46 2Set Cooling Lower Temperature (Status)
12335 47 2Set Heating Lower Temperature (Setting)
12336 48 2Set Heating Lower Temperature (Status)
12337 49 Thermo Status (Status)
12338 50 Accumulated Gas Distribution (Status)
12339 51 Dust Sensor Available (Status)
12340 52 Air Cleaning Opereration (Setting)
12341 53 Air Cleaning Opereration (Status)
12342 54 Fine Dust (Status)
12343 55 Ultra Fine Dust (Status)
12344 56 Super Ultra Fine Dust (Status)
12345 57 Humidity (Status)
12346 58 Comfort Cooling Available (Status)
12347 59 Comfort Cooling Opereration (Setting)
12348 60 Comfort Cooling Opereration (Status)
12349 61 Comfort Cooling Step (Setting)
12350 62 Comfort Cooling Step (Status)
12351 63 Human Detection Available (Status)
12352 64 Human Detection Opereration (Setting)
12353 65 Human Detection Opereration (Status)
12354 66 Human Detection Wind (Setting)
12355 67 Human Detection Wind (Status)
12356 68 Human Detection Time (Setting)
12357 69 Human Detection Time (Status)
12358 70 Hotel Checkin (Setting)
12359 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_30 BO Stop(0) Start(1)
StartStopStatus_30 BI Stop(0) Start(1)
LockCommand_30 BO Permit(0) Prohibit(1)
LockStatus_30 BI Permit(0) Prohibit(1)
FilterSign_30 BI Off(0) On(1)
FilterSignReset_30 BV - Reset(1)
AirConModeCommand_30 MO Cool(1)
AirConModeStatus_30 MI Cool(1)
SwingCommand_30 BO Stop(0) Run(1)
SwingStatus_30 BI Stop(0) Run(1)
FanSpeedCommand_30 MO Low(1)
FanSpeedStatus_30 MI Low(1)
SetRoomTemp_30 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_30 AI ℃
Alarm_30 BI Normal(0) Abnormal(1)
MalfunctionCode_30 AI Refer to the
SetTempStatus_30 AI ℃
Accumulated power(100 Watt)_30 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_30 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_30 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_30 AI ℃
TempRangeLowerLimitStatus_30 AI ℃
ModeLockCommand_30 BO Permit(0) Prohibit(1)
ModeLockStatus_30 BI Permit(0) Prohibit(1)
FanLockCommand_30 BO Permit(0) Prohibit(1)
FanLockStatus_30 BI Permit(0) Prohibit(1)
OccupancyCommand_30 BO Unoccupied(0) Occupied(1)
OccupancyStatus_30 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_30 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_30 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_30 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_30 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_30 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_30 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_30 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_30 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_30 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_30 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_30 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_30 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_30 BI Off(0) On(1)
AccumulatedGas(100 Watt)_30 AI Wattage values (Unit : 100Watt)
DustSensorAvail_30 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_30 BO Stop(0) Run(1)
AirCleaningOperStatus_30 BI Stop(0) Run(1)
FineDustStatus_30 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_30 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_30 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_30 AI %
ComfortCoolingAvail_30 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_30 BO Stop(0) Run(1)
ComfortCoolingOperStatus_30 BI Stop(0) Run(1)
ComfortCoolingStepCommand_30 AV 1~3 step
ComfortCoolingStepStatus_30 AI 1~3 step
HumanDetectionAvail_30 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_30 MO Off(1)
HumanDetectionOperStatus_30 MI Off(1)
HumanDetectionWindCommand_30 MO Off(1)
HumanDetectionWindStatus_30 MI Off(1)
HumanDetectionTimeCommand_30 MO 5min(1)
HumanDetectionTimeStatus_30 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
31 ※ Dev Type AC
address

instance
point Name
number

12545 1 On/Off (Setting)


12546 2 On/Off (Status)
12547 3 Lock (Setting)
12548 4 Lock (Status)
12549 5 Filter Sign
12550 6 Filter Sign reset
12551 7 Operation Mode (Setting)
12552 8 Operation Mode (Status)
12553 9 Swing (Setting)
12554 10 Swing (Status)
12555 11 Fan Speed (Setting)
12556 12 Fan Speed (Status)
12557 13 Set Room Temperature
12558 14 Room Temperature
12559 15 Alarm
12560 16 Error Code
12563 19 Set Temperature (Status)
12564 20 Accumulated Power Distribution (Status)
12571 27 Set Upper Temperature (Setting)
12572 28 Set Lower Temperature (Setting)
12573 29 Set Upper Tempaerature (Status)
12574 30 Set Lower Temperature (Status)
12575 31 Mode Lock (Setting)
12576 32 Mode Lock (Status)
12577 33 Fan Lock (Setting)
12578 34 Fan Lock (Status)
12579 35 Occupancy (Setting)
12580 36 Occupancy (Status)
12581 37 2Set Cooling Set Temperature (Setting)
12582 38 2Set Cooling Set Temperature (Status)
12583 39 2Set Heating Set Temperature (Setting)
12584 40 2Set Heating Set Temperature (Status)
12585 41 2Set Cooling Upper Temperature (Setting)
12586 42 2Set Cooling Upper Temperature (Status)
12587 43 2Set Heating Upper Temperature (Setting)
12588 44 2Set Heating Upper Temperature (Status)
12589 45 2Set Cooling Lower Temperature (Setting)
12590 46 2Set Cooling Lower Temperature (Status)
12591 47 2Set Heating Lower Temperature (Setting)
12592 48 2Set Heating Lower Temperature (Status)
12593 49 Thermo Status (Status)
12594 50 Accumulated Gas Distribution (Status)
12595 51 Dust Sensor Available (Status)
12596 52 Air Cleaning Opereration (Setting)
12597 53 Air Cleaning Opereration (Status)
12598 54 Fine Dust (Status)
12599 55 Ultra Fine Dust (Status)
12600 56 Super Ultra Fine Dust (Status)
12601 57 Humidity (Status)
12602 58 Comfort Cooling Available (Status)
12603 59 Comfort Cooling Opereration (Setting)
12604 60 Comfort Cooling Opereration (Status)
12605 61 Comfort Cooling Step (Setting)
12606 62 Comfort Cooling Step (Status)
12607 63 Human Detection Available (Status)
12608 64 Human Detection Opereration (Setting)
12609 65 Human Detection Opereration (Status)
12610 66 Human Detection Wind (Setting)
12611 67 Human Detection Wind (Status)
12612 68 Human Detection Time (Setting)
12613 69 Human Detection Time (Status)
12614 70 Hotel Checkin (Setting)
12615 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_31 BO Stop(0) Start(1)
StartStopStatus_31 BI Stop(0) Start(1)
LockCommand_31 BO Permit(0) Prohibit(1)
LockStatus_31 BI Permit(0) Prohibit(1)
FilterSign_31 BI Off(0) On(1)
FilterSignReset_31 BV - Reset(1)
AirConModeCommand_31 MO Cool(1)
AirConModeStatus_31 MI Cool(1)
SwingCommand_31 BO Stop(0) Run(1)
SwingStatus_31 BI Stop(0) Run(1)
FanSpeedCommand_31 MO Low(1)
FanSpeedStatus_31 MI Low(1)
SetRoomTemp_31 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_31 AI ℃
Alarm_31 BI Normal(0) Abnormal(1)
MalfunctionCode_31 AI Refer to the
SetTempStatus_31 AI ℃
Accumulated power(100 Watt)_31 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_31 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_31 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_31 AI ℃
TempRangeLowerLimitStatus_31 AI ℃
ModeLockCommand_31 BO Permit(0) Prohibit(1)
ModeLockStatus_31 BI Permit(0) Prohibit(1)
FanLockCommand_31 BO Permit(0) Prohibit(1)
FanLockStatus_31 BI Permit(0) Prohibit(1)
OccupancyCommand_31 BO Unoccupied(0) Occupied(1)
OccupancyStatus_31 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_31 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_31 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_31 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_31 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_31 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_31 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_31 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_31 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_31 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_31 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_31 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_31 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_31 BI Off(0) On(1)
AccumulatedGas(100 Watt)_31 AI Wattage values (Unit : 100Watt)
DustSensorAvail_31 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_31 BO Stop(0) Run(1)
AirCleaningOperStatus_31 BI Stop(0) Run(1)
FineDustStatus_31 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_31 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_31 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_31 AI %
ComfortCoolingAvail_31 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_31 BO Stop(0) Run(1)
ComfortCoolingOperStatus_31 BI Stop(0) Run(1)
ComfortCoolingStepCommand_31 AV 1~3 step
ComfortCoolingStepStatus_31 AI 1~3 step
HumanDetectionAvail_31 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_31 MO Off(1)
HumanDetectionOperStatus_31 MI Off(1)
HumanDetectionWindCommand_31 MO Off(1)
HumanDetectionWindStatus_31 MI Off(1)
HumanDetectionTimeCommand_31 MO 5min(1)
HumanDetectionTimeStatus_31 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
32 ※ Dev Type AC
address

instance
point Name
number

12801 1 On/Off (Setting)


12802 2 On/Off (Status)
12803 3 Lock (Setting)
12804 4 Lock (Status)
12805 5 Filter Sign
12806 6 Filter Sign reset
12807 7 Operation Mode (Setting)
12808 8 Operation Mode (Status)
12809 9 Swing (Setting)
12810 10 Swing (Status)
12811 11 Fan Speed (Setting)
12812 12 Fan Speed (Status)
12813 13 Set Room Temperature
12814 14 Room Temperature
12815 15 Alarm
12816 16 Error Code
12819 19 Set Temperature (Status)
12820 20 Accumulated Power Distribution (Status)
12827 27 Set Upper Temperature (Setting)
12828 28 Set Lower Temperature (Setting)
12829 29 Set Upper Tempaerature (Status)
12830 30 Set Lower Temperature (Status)
12831 31 Mode Lock (Setting)
12832 32 Mode Lock (Status)
12833 33 Fan Lock (Setting)
12834 34 Fan Lock (Status)
12835 35 Occupancy (Setting)
12836 36 Occupancy (Status)
12837 37 2Set Cooling Set Temperature (Setting)
12838 38 2Set Cooling Set Temperature (Status)
12839 39 2Set Heating Set Temperature (Setting)
12840 40 2Set Heating Set Temperature (Status)
12841 41 2Set Cooling Upper Temperature (Setting)
12842 42 2Set Cooling Upper Temperature (Status)
12843 43 2Set Heating Upper Temperature (Setting)
12844 44 2Set Heating Upper Temperature (Status)
12845 45 2Set Cooling Lower Temperature (Setting)
12846 46 2Set Cooling Lower Temperature (Status)
12847 47 2Set Heating Lower Temperature (Setting)
12848 48 2Set Heating Lower Temperature (Status)
12849 49 Thermo Status (Status)
12850 50 Accumulated Gas Distribution (Status)
12851 51 Dust Sensor Available (Status)
12852 52 Air Cleaning Opereration (Setting)
12853 53 Air Cleaning Opereration (Status)
12854 54 Fine Dust (Status)
12855 55 Ultra Fine Dust (Status)
12856 56 Super Ultra Fine Dust (Status)
12857 57 Humidity (Status)
12858 58 Comfort Cooling Available (Status)
12859 59 Comfort Cooling Opereration (Setting)
12860 60 Comfort Cooling Opereration (Status)
12861 61 Comfort Cooling Step (Setting)
12862 62 Comfort Cooling Step (Status)
12863 63 Human Detection Available (Status)
12864 64 Human Detection Opereration (Setting)
12865 65 Human Detection Opereration (Status)
12866 66 Human Detection Wind (Setting)
12867 67 Human Detection Wind (Status)
12868 68 Human Detection Time (Setting)
12869 69 Human Detection Time (Status)
12870 70 Hotel Checkin (Setting)
12871 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_32 BO Stop(0) Start(1)
StartStopStatus_32 BI Stop(0) Start(1)
LockCommand_32 BO Permit(0) Prohibit(1)
LockStatus_32 BI Permit(0) Prohibit(1)
FilterSign_32 BI Off(0) On(1)
FilterSignReset_32 BV - Reset(1)
AirConModeCommand_32 MO Cool(1)
AirConModeStatus_32 MI Cool(1)
SwingCommand_32 BO Stop(0) Run(1)
SwingStatus_32 BI Stop(0) Run(1)
FanSpeedCommand_32 MO Low(1)
FanSpeedStatus_32 MI Low(1)
SetRoomTemp_32 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_32 AI ℃
Alarm_32 BI Normal(0) Abnormal(1)
MalfunctionCode_32 AI Refer to the
SetTempStatus_32 AI ℃
Accumulated power(100 Watt)_32 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_32 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_32 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_32 AI ℃
TempRangeLowerLimitStatus_32 AI ℃
ModeLockCommand_32 BO Permit(0) Prohibit(1)
ModeLockStatus_32 BI Permit(0) Prohibit(1)
FanLockCommand_32 BO Permit(0) Prohibit(1)
FanLockStatus_32 BI Permit(0) Prohibit(1)
OccupancyCommand_32 BO Unoccupied(0) Occupied(1)
OccupancyStatus_32 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_32 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_32 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_32 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_32 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_32 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_32 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_32 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_32 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_32 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_32 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_32 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_32 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_32 BI Off(0) On(1)
AccumulatedGas(100 Watt)_32 AI Wattage values (Unit : 100Watt)
DustSensorAvail_32 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_32 BO Stop(0) Run(1)
AirCleaningOperStatus_32 BI Stop(0) Run(1)
FineDustStatus_32 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_32 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_32 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_32 AI %
ComfortCoolingAvail_32 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_32 BO Stop(0) Run(1)
ComfortCoolingOperStatus_32 BI Stop(0) Run(1)
ComfortCoolingStepCommand_32 AV 1~3 step
ComfortCoolingStepStatus_32 AI 1~3 step
HumanDetectionAvail_32 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_32 MO Off(1)
HumanDetectionOperStatus_32 MI Off(1)
HumanDetectionWindCommand_32 MO Off(1)
HumanDetectionWindStatus_32 MI Off(1)
HumanDetectionTimeCommand_32 MO 5min(1)
HumanDetectionTimeStatus_32 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
33 ※ Dev Type AC
address

instance
point Name
number

13057 1 On/Off (Setting)


13058 2 On/Off (Status)
13059 3 Lock (Setting)
13060 4 Lock (Status)
13061 5 Filter Sign
13062 6 Filter Sign reset
13063 7 Operation Mode (Setting)
13064 8 Operation Mode (Status)
13065 9 Swing (Setting)
13066 10 Swing (Status)
13067 11 Fan Speed (Setting)
13068 12 Fan Speed (Status)
13069 13 Set Room Temperature
13070 14 Room Temperature
13071 15 Alarm
13072 16 Error Code
13075 19 Set Temperature (Status)
13076 20 Accumulated Power Distribution (Status)
13083 27 Set Upper Temperature (Setting)
13084 28 Set Lower Temperature (Setting)
13085 29 Set Upper Tempaerature (Status)
13086 30 Set Lower Temperature (Status)
13087 31 Mode Lock (Setting)
13088 32 Mode Lock (Status)
13089 33 Fan Lock (Setting)
13090 34 Fan Lock (Status)
13091 35 Occupancy (Setting)
13092 36 Occupancy (Status)
13093 37 2Set Cooling Set Temperature (Setting)
13094 38 2Set Cooling Set Temperature (Status)
13095 39 2Set Heating Set Temperature (Setting)
13096 40 2Set Heating Set Temperature (Status)
13097 41 2Set Cooling Upper Temperature (Setting)
13098 42 2Set Cooling Upper Temperature (Status)
13099 43 2Set Heating Upper Temperature (Setting)
13100 44 2Set Heating Upper Temperature (Status)
13101 45 2Set Cooling Lower Temperature (Setting)
13102 46 2Set Cooling Lower Temperature (Status)
13103 47 2Set Heating Lower Temperature (Setting)
13104 48 2Set Heating Lower Temperature (Status)
13105 49 Thermo Status (Status)
13106 50 Accumulated Gas Distribution (Status)
13107 51 Dust Sensor Available (Status)
13108 52 Air Cleaning Opereration (Setting)
13109 53 Air Cleaning Opereration (Status)
13110 54 Fine Dust (Status)
13111 55 Ultra Fine Dust (Status)
13112 56 Super Ultra Fine Dust (Status)
13113 57 Humidity (Status)
13114 58 Comfort Cooling Available (Status)
13115 59 Comfort Cooling Opereration (Setting)
13116 60 Comfort Cooling Opereration (Status)
13117 61 Comfort Cooling Step (Setting)
13118 62 Comfort Cooling Step (Status)
13119 63 Human Detection Available (Status)
13120 64 Human Detection Opereration (Setting)
13121 65 Human Detection Opereration (Status)
13122 66 Human Detection Wind (Setting)
13123 67 Human Detection Wind (Status)
13124 68 Human Detection Time (Setting)
13125 69 Human Detection Time (Status)
13126 70 Hotel Checkin (Setting)
13127 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_33 BO Stop(0) Start(1)
StartStopStatus_33 BI Stop(0) Start(1)
LockCommand_33 BO Permit(0) Prohibit(1)
LockStatus_33 BI Permit(0) Prohibit(1)
FilterSign_33 BI Off(0) On(1)
FilterSignReset_33 BV - Reset(1)
AirConModeCommand_33 MO Cool(1)
AirConModeStatus_33 MI Cool(1)
SwingCommand_33 BO Stop(0) Run(1)
SwingStatus_33 BI Stop(0) Run(1)
FanSpeedCommand_33 MO Low(1)
FanSpeedStatus_33 MI Low(1)
SetRoomTemp_33 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_33 AI ℃
Alarm_33 BI Normal(0) Abnormal(1)
MalfunctionCode_33 AI Refer to the
SetTempStatus_33 AI ℃
Accumulated power(100 Watt)_33 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_33 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_33 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_33 AI ℃
TempRangeLowerLimitStatus_33 AI ℃
ModeLockCommand_33 BO Permit(0) Prohibit(1)
ModeLockStatus_33 BI Permit(0) Prohibit(1)
FanLockCommand_33 BO Permit(0) Prohibit(1)
FanLockStatus_33 BI Permit(0) Prohibit(1)
OccupancyCommand_33 BO Unoccupied(0) Occupied(1)
OccupancyStatus_33 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_33 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_33 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_33 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_33 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_33 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_33 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_33 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_33 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_33 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_33 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_33 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_33 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_33 BI Off(0) On(1)
AccumulatedGas(100 Watt)_33 AI Wattage values (Unit : 100Watt)
DustSensorAvail_33 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_33 BO Stop(0) Run(1)
AirCleaningOperStatus_33 BI Stop(0) Run(1)
FineDustStatus_33 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_33 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_33 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_33 AI %
ComfortCoolingAvail_33 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_33 BO Stop(0) Run(1)
ComfortCoolingOperStatus_33 BI Stop(0) Run(1)
ComfortCoolingStepCommand_33 AV 1~3 step
ComfortCoolingStepStatus_33 AI 1~3 step
HumanDetectionAvail_33 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_33 MO Off(1)
HumanDetectionOperStatus_33 MI Off(1)
HumanDetectionWindCommand_33 MO Off(1)
HumanDetectionWindStatus_33 MI Off(1)
HumanDetectionTimeCommand_33 MO 5min(1)
HumanDetectionTimeStatus_33 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
34 ※ Dev Type AC
address

instance
point Name
number

13313 1 On/Off (Setting)


13314 2 On/Off (Status)
13315 3 Lock (Setting)
13316 4 Lock (Status)
13317 5 Filter Sign
13318 6 Filter Sign reset
13319 7 Operation Mode (Setting)
13320 8 Operation Mode (Status)
13321 9 Swing (Setting)
13322 10 Swing (Status)
13323 11 Fan Speed (Setting)
13324 12 Fan Speed (Status)
13325 13 Set Room Temperature
13326 14 Room Temperature
13327 15 Alarm
13328 16 Error Code
13331 19 Set Temperature (Status)
13332 20 Accumulated Power Distribution (Status)
13339 27 Set Upper Temperature (Setting)
13340 28 Set Lower Temperature (Setting)
13341 29 Set Upper Tempaerature (Status)
13342 30 Set Lower Temperature (Status)
13343 31 Mode Lock (Setting)
13344 32 Mode Lock (Status)
13345 33 Fan Lock (Setting)
13346 34 Fan Lock (Status)
13347 35 Occupancy (Setting)
13348 36 Occupancy (Status)
13349 37 2Set Cooling Set Temperature (Setting)
13350 38 2Set Cooling Set Temperature (Status)
13351 39 2Set Heating Set Temperature (Setting)
13352 40 2Set Heating Set Temperature (Status)
13353 41 2Set Cooling Upper Temperature (Setting)
13354 42 2Set Cooling Upper Temperature (Status)
13355 43 2Set Heating Upper Temperature (Setting)
13356 44 2Set Heating Upper Temperature (Status)
13357 45 2Set Cooling Lower Temperature (Setting)
13358 46 2Set Cooling Lower Temperature (Status)
13359 47 2Set Heating Lower Temperature (Setting)
13360 48 2Set Heating Lower Temperature (Status)
13361 49 Thermo Status (Status)
13362 50 Accumulated Gas Distribution (Status)
13363 51 Dust Sensor Available (Status)
13364 52 Air Cleaning Opereration (Setting)
13365 53 Air Cleaning Opereration (Status)
13366 54 Fine Dust (Status)
13367 55 Ultra Fine Dust (Status)
13368 56 Super Ultra Fine Dust (Status)
13369 57 Humidity (Status)
13370 58 Comfort Cooling Available (Status)
13371 59 Comfort Cooling Opereration (Setting)
13372 60 Comfort Cooling Opereration (Status)
13373 61 Comfort Cooling Step (Setting)
13374 62 Comfort Cooling Step (Status)
13375 63 Human Detection Available (Status)
13376 64 Human Detection Opereration (Setting)
13377 65 Human Detection Opereration (Status)
13378 66 Human Detection Wind (Setting)
13379 67 Human Detection Wind (Status)
13380 68 Human Detection Time (Setting)
13381 69 Human Detection Time (Status)
13382 70 Hotel Checkin (Setting)
13383 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_34 BO Stop(0) Start(1)
StartStopStatus_34 BI Stop(0) Start(1)
LockCommand_34 BO Permit(0) Prohibit(1)
LockStatus_34 BI Permit(0) Prohibit(1)
FilterSign_34 BI Off(0) On(1)
FilterSignReset_34 BV - Reset(1)
AirConModeCommand_34 MO Cool(1)
AirConModeStatus_34 MI Cool(1)
SwingCommand_34 BO Stop(0) Run(1)
SwingStatus_34 BI Stop(0) Run(1)
FanSpeedCommand_34 MO Low(1)
FanSpeedStatus_34 MI Low(1)
SetRoomTemp_34 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_34 AI ℃
Alarm_34 BI Normal(0) Abnormal(1)
MalfunctionCode_34 AI Refer to the
SetTempStatus_34 AI ℃
Accumulated power(100 Watt)_34 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_34 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_34 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_34 AI ℃
TempRangeLowerLimitStatus_34 AI ℃
ModeLockCommand_34 BO Permit(0) Prohibit(1)
ModeLockStatus_34 BI Permit(0) Prohibit(1)
FanLockCommand_34 BO Permit(0) Prohibit(1)
FanLockStatus_34 BI Permit(0) Prohibit(1)
OccupancyCommand_34 BO Unoccupied(0) Occupied(1)
OccupancyStatus_34 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_34 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_34 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_34 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_34 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_34 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_34 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_34 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_34 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_34 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_34 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_34 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_34 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_34 BI Off(0) On(1)
AccumulatedGas(100 Watt)_34 AI Wattage values (Unit : 100Watt)
DustSensorAvail_34 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_34 BO Stop(0) Run(1)
AirCleaningOperStatus_34 BI Stop(0) Run(1)
FineDustStatus_34 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_34 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_34 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_34 AI %
ComfortCoolingAvail_34 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_34 BO Stop(0) Run(1)
ComfortCoolingOperStatus_34 BI Stop(0) Run(1)
ComfortCoolingStepCommand_34 AV 1~3 step
ComfortCoolingStepStatus_34 AI 1~3 step
HumanDetectionAvail_34 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_34 MO Off(1)
HumanDetectionOperStatus_34 MI Off(1)
HumanDetectionWindCommand_34 MO Off(1)
HumanDetectionWindStatus_34 MI Off(1)
HumanDetectionTimeCommand_34 MO 5min(1)
HumanDetectionTimeStatus_34 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
35 ※ Dev Type AC
address

instance
point Name
number

13569 1 On/Off (Setting)


13570 2 On/Off (Status)
13571 3 Lock (Setting)
13572 4 Lock (Status)
13573 5 Filter Sign
13574 6 Filter Sign reset
13575 7 Operation Mode (Setting)
13576 8 Operation Mode (Status)
13577 9 Swing (Setting)
13578 10 Swing (Status)
13579 11 Fan Speed (Setting)
13580 12 Fan Speed (Status)
13581 13 Set Room Temperature
13582 14 Room Temperature
13583 15 Alarm
13584 16 Error Code
13587 19 Set Temperature (Status)
13588 20 Accumulated Power Distribution (Status)
13595 27 Set Upper Temperature (Setting)
13596 28 Set Lower Temperature (Setting)
13597 29 Set Upper Tempaerature (Status)
13598 30 Set Lower Temperature (Status)
13599 31 Mode Lock (Setting)
13600 32 Mode Lock (Status)
13601 33 Fan Lock (Setting)
13602 34 Fan Lock (Status)
13603 35 Occupancy (Setting)
13604 36 Occupancy (Status)
13605 37 2Set Cooling Set Temperature (Setting)
13606 38 2Set Cooling Set Temperature (Status)
13607 39 2Set Heating Set Temperature (Setting)
13608 40 2Set Heating Set Temperature (Status)
13609 41 2Set Cooling Upper Temperature (Setting)
13610 42 2Set Cooling Upper Temperature (Status)
13611 43 2Set Heating Upper Temperature (Setting)
13612 44 2Set Heating Upper Temperature (Status)
13613 45 2Set Cooling Lower Temperature (Setting)
13614 46 2Set Cooling Lower Temperature (Status)
13615 47 2Set Heating Lower Temperature (Setting)
13616 48 2Set Heating Lower Temperature (Status)
13617 49 Thermo Status (Status)
13618 50 Accumulated Gas Distribution (Status)
13619 51 Dust Sensor Available (Status)
13620 52 Air Cleaning Opereration (Setting)
13621 53 Air Cleaning Opereration (Status)
13622 54 Fine Dust (Status)
13623 55 Ultra Fine Dust (Status)
13624 56 Super Ultra Fine Dust (Status)
13625 57 Humidity (Status)
13626 58 Comfort Cooling Available (Status)
13627 59 Comfort Cooling Opereration (Setting)
13628 60 Comfort Cooling Opereration (Status)
13629 61 Comfort Cooling Step (Setting)
13630 62 Comfort Cooling Step (Status)
13631 63 Human Detection Available (Status)
13632 64 Human Detection Opereration (Setting)
13633 65 Human Detection Opereration (Status)
13634 66 Human Detection Wind (Setting)
13635 67 Human Detection Wind (Status)
13636 68 Human Detection Time (Setting)
13637 69 Human Detection Time (Status)
13638 70 Hotel Checkin (Setting)
13639 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_35 BO Stop(0) Start(1)
StartStopStatus_35 BI Stop(0) Start(1)
LockCommand_35 BO Permit(0) Prohibit(1)
LockStatus_35 BI Permit(0) Prohibit(1)
FilterSign_35 BI Off(0) On(1)
FilterSignReset_35 BV - Reset(1)
AirConModeCommand_35 MO Cool(1)
AirConModeStatus_35 MI Cool(1)
SwingCommand_35 BO Stop(0) Run(1)
SwingStatus_35 BI Stop(0) Run(1)
FanSpeedCommand_35 MO Low(1)
FanSpeedStatus_35 MI Low(1)
SetRoomTemp_35 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_35 AI ℃
Alarm_35 BI Normal(0) Abnormal(1)
MalfunctionCode_35 AI Refer to the
SetTempStatus_35 AI ℃
Accumulated power(100 Watt)_35 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_35 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_35 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_35 AI ℃
TempRangeLowerLimitStatus_35 AI ℃
ModeLockCommand_35 BO Permit(0) Prohibit(1)
ModeLockStatus_35 BI Permit(0) Prohibit(1)
FanLockCommand_35 BO Permit(0) Prohibit(1)
FanLockStatus_35 BI Permit(0) Prohibit(1)
OccupancyCommand_35 BO Unoccupied(0) Occupied(1)
OccupancyStatus_35 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_35 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_35 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_35 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_35 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_35 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_35 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_35 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_35 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_35 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_35 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_35 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_35 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_35 BI Off(0) On(1)
AccumulatedGas(100 Watt)_35 AI Wattage values (Unit : 100Watt)
DustSensorAvail_35 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_35 BO Stop(0) Run(1)
AirCleaningOperStatus_35 BI Stop(0) Run(1)
FineDustStatus_35 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_35 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_35 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_35 AI %
ComfortCoolingAvail_35 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_35 BO Stop(0) Run(1)
ComfortCoolingOperStatus_35 BI Stop(0) Run(1)
ComfortCoolingStepCommand_35 AV 1~3 step
ComfortCoolingStepStatus_35 AI 1~3 step
HumanDetectionAvail_35 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_35 MO Off(1)
HumanDetectionOperStatus_35 MI Off(1)
HumanDetectionWindCommand_35 MO Off(1)
HumanDetectionWindStatus_35 MI Off(1)
HumanDetectionTimeCommand_35 MO 5min(1)
HumanDetectionTimeStatus_35 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
36 ※ Dev Type AC
address

instance
point Name
number

13825 1 On/Off (Setting)


13826 2 On/Off (Status)
13827 3 Lock (Setting)
13828 4 Lock (Status)
13829 5 Filter Sign
13830 6 Filter Sign reset
13831 7 Operation Mode (Setting)
13832 8 Operation Mode (Status)
13833 9 Swing (Setting)
13834 10 Swing (Status)
13835 11 Fan Speed (Setting)
13836 12 Fan Speed (Status)
13837 13 Set Room Temperature
13838 14 Room Temperature
13839 15 Alarm
13840 16 Error Code
13843 19 Set Temperature (Status)
13844 20 Accumulated Power Distribution (Status)
13851 27 Set Upper Temperature (Setting)
13852 28 Set Lower Temperature (Setting)
13853 29 Set Upper Tempaerature (Status)
13854 30 Set Lower Temperature (Status)
13855 31 Mode Lock (Setting)
13856 32 Mode Lock (Status)
13857 33 Fan Lock (Setting)
13858 34 Fan Lock (Status)
13859 35 Occupancy (Setting)
13860 36 Occupancy (Status)
13861 37 2Set Cooling Set Temperature (Setting)
13862 38 2Set Cooling Set Temperature (Status)
13863 39 2Set Heating Set Temperature (Setting)
13864 40 2Set Heating Set Temperature (Status)
13865 41 2Set Cooling Upper Temperature (Setting)
13866 42 2Set Cooling Upper Temperature (Status)
13867 43 2Set Heating Upper Temperature (Setting)
13868 44 2Set Heating Upper Temperature (Status)
13869 45 2Set Cooling Lower Temperature (Setting)
13870 46 2Set Cooling Lower Temperature (Status)
13871 47 2Set Heating Lower Temperature (Setting)
13872 48 2Set Heating Lower Temperature (Status)
13873 49 Thermo Status (Status)
13874 50 Accumulated Gas Distribution (Status)
13875 51 Dust Sensor Available (Status)
13876 52 Air Cleaning Opereration (Setting)
13877 53 Air Cleaning Opereration (Status)
13878 54 Fine Dust (Status)
13879 55 Ultra Fine Dust (Status)
13880 56 Super Ultra Fine Dust (Status)
13881 57 Humidity (Status)
13882 58 Comfort Cooling Available (Status)
13883 59 Comfort Cooling Opereration (Setting)
13884 60 Comfort Cooling Opereration (Status)
13885 61 Comfort Cooling Step (Setting)
13886 62 Comfort Cooling Step (Status)
13887 63 Human Detection Available (Status)
13888 64 Human Detection Opereration (Setting)
13889 65 Human Detection Opereration (Status)
13890 66 Human Detection Wind (Setting)
13891 67 Human Detection Wind (Status)
13892 68 Human Detection Time (Setting)
13893 69 Human Detection Time (Status)
13894 70 Hotel Checkin (Setting)
13895 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_36 BO Stop(0) Start(1)
StartStopStatus_36 BI Stop(0) Start(1)
LockCommand_36 BO Permit(0) Prohibit(1)
LockStatus_36 BI Permit(0) Prohibit(1)
FilterSign_36 BI Off(0) On(1)
FilterSignReset_36 BV - Reset(1)
AirConModeCommand_36 MO Cool(1)
AirConModeStatus_36 MI Cool(1)
SwingCommand_36 BO Stop(0) Run(1)
SwingStatus_36 BI Stop(0) Run(1)
FanSpeedCommand_36 MO Low(1)
FanSpeedStatus_36 MI Low(1)
SetRoomTemp_36 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_36 AI ℃
Alarm_36 BI Normal(0) Abnormal(1)
MalfunctionCode_36 AI Refer to the
SetTempStatus_36 AI ℃
Accumulated power(100 Watt)_36 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_36 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_36 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_36 AI ℃
TempRangeLowerLimitStatus_36 AI ℃
ModeLockCommand_36 BO Permit(0) Prohibit(1)
ModeLockStatus_36 BI Permit(0) Prohibit(1)
FanLockCommand_36 BO Permit(0) Prohibit(1)
FanLockStatus_36 BI Permit(0) Prohibit(1)
OccupancyCommand_36 BO Unoccupied(0) Occupied(1)
OccupancyStatus_36 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_36 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_36 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_36 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_36 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_36 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_36 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_36 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_36 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_36 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_36 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_36 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_36 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_36 BI Off(0) On(1)
AccumulatedGas(100 Watt)_36 AI Wattage values (Unit : 100Watt)
DustSensorAvail_36 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_36 BO Stop(0) Run(1)
AirCleaningOperStatus_36 BI Stop(0) Run(1)
FineDustStatus_36 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_36 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_36 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_36 AI %
ComfortCoolingAvail_36 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_36 BO Stop(0) Run(1)
ComfortCoolingOperStatus_36 BI Stop(0) Run(1)
ComfortCoolingStepCommand_36 AV 1~3 step
ComfortCoolingStepStatus_36 AI 1~3 step
HumanDetectionAvail_36 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_36 MO Off(1)
HumanDetectionOperStatus_36 MI Off(1)
HumanDetectionWindCommand_36 MO Off(1)
HumanDetectionWindStatus_36 MI Off(1)
HumanDetectionTimeCommand_36 MO 5min(1)
HumanDetectionTimeStatus_36 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
37 ※ Dev Type AC
address

instance
point Name
number

14081 1 On/Off (Setting)


14082 2 On/Off (Status)
14083 3 Lock (Setting)
14084 4 Lock (Status)
14085 5 Filter Sign
14086 6 Filter Sign reset
14087 7 Operation Mode (Setting)
14088 8 Operation Mode (Status)
14089 9 Swing (Setting)
14090 10 Swing (Status)
14091 11 Fan Speed (Setting)
14092 12 Fan Speed (Status)
14093 13 Set Room Temperature
14094 14 Room Temperature
14095 15 Alarm
14096 16 Error Code
14099 19 Set Temperature (Status)
14100 20 Accumulated Power Distribution (Status)
14107 27 Set Upper Temperature (Setting)
14108 28 Set Lower Temperature (Setting)
14109 29 Set Upper Tempaerature (Status)
14110 30 Set Lower Temperature (Status)
14111 31 Mode Lock (Setting)
14112 32 Mode Lock (Status)
14113 33 Fan Lock (Setting)
14114 34 Fan Lock (Status)
14115 35 Occupancy (Setting)
14116 36 Occupancy (Status)
14117 37 2Set Cooling Set Temperature (Setting)
14118 38 2Set Cooling Set Temperature (Status)
14119 39 2Set Heating Set Temperature (Setting)
14120 40 2Set Heating Set Temperature (Status)
14121 41 2Set Cooling Upper Temperature (Setting)
14122 42 2Set Cooling Upper Temperature (Status)
14123 43 2Set Heating Upper Temperature (Setting)
14124 44 2Set Heating Upper Temperature (Status)
14125 45 2Set Cooling Lower Temperature (Setting)
14126 46 2Set Cooling Lower Temperature (Status)
14127 47 2Set Heating Lower Temperature (Setting)
14128 48 2Set Heating Lower Temperature (Status)
14129 49 Thermo Status (Status)
14130 50 Accumulated Gas Distribution (Status)
14131 51 Dust Sensor Available (Status)
14132 52 Air Cleaning Opereration (Setting)
14133 53 Air Cleaning Opereration (Status)
14134 54 Fine Dust (Status)
14135 55 Ultra Fine Dust (Status)
14136 56 Super Ultra Fine Dust (Status)
14137 57 Humidity (Status)
14138 58 Comfort Cooling Available (Status)
14139 59 Comfort Cooling Opereration (Setting)
14140 60 Comfort Cooling Opereration (Status)
14141 61 Comfort Cooling Step (Setting)
14142 62 Comfort Cooling Step (Status)
14143 63 Human Detection Available (Status)
14144 64 Human Detection Opereration (Setting)
14145 65 Human Detection Opereration (Status)
14146 66 Human Detection Wind (Setting)
14147 67 Human Detection Wind (Status)
14148 68 Human Detection Time (Setting)
14149 69 Human Detection Time (Status)
14150 70 Hotel Checkin (Setting)
14151 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_37 BO Stop(0) Start(1)
StartStopStatus_37 BI Stop(0) Start(1)
LockCommand_37 BO Permit(0) Prohibit(1)
LockStatus_37 BI Permit(0) Prohibit(1)
FilterSign_37 BI Off(0) On(1)
FilterSignReset_37 BV - Reset(1)
AirConModeCommand_37 MO Cool(1)
AirConModeStatus_37 MI Cool(1)
SwingCommand_37 BO Stop(0) Run(1)
SwingStatus_37 BI Stop(0) Run(1)
FanSpeedCommand_37 MO Low(1)
FanSpeedStatus_37 MI Low(1)
SetRoomTemp_37 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_37 AI ℃
Alarm_37 BI Normal(0) Abnormal(1)
MalfunctionCode_37 AI Refer to the
SetTempStatus_37 AI ℃
Accumulated power(100 Watt)_37 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_37 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_37 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_37 AI ℃
TempRangeLowerLimitStatus_37 AI ℃
ModeLockCommand_37 BO Permit(0) Prohibit(1)
ModeLockStatus_37 BI Permit(0) Prohibit(1)
FanLockCommand_37 BO Permit(0) Prohibit(1)
FanLockStatus_37 BI Permit(0) Prohibit(1)
OccupancyCommand_37 BO Unoccupied(0) Occupied(1)
OccupancyStatus_37 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_37 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_37 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_37 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_37 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_37 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_37 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_37 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_37 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_37 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_37 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_37 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_37 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_37 BI Off(0) On(1)
AccumulatedGas(100 Watt)_37 AI Wattage values (Unit : 100Watt)
DustSensorAvail_37 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_37 BO Stop(0) Run(1)
AirCleaningOperStatus_37 BI Stop(0) Run(1)
FineDustStatus_37 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_37 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_37 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_37 AI %
ComfortCoolingAvail_37 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_37 BO Stop(0) Run(1)
ComfortCoolingOperStatus_37 BI Stop(0) Run(1)
ComfortCoolingStepCommand_37 AV 1~3 step
ComfortCoolingStepStatus_37 AI 1~3 step
HumanDetectionAvail_37 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_37 MO Off(1)
HumanDetectionOperStatus_37 MI Off(1)
HumanDetectionWindCommand_37 MO Off(1)
HumanDetectionWindStatus_37 MI Off(1)
HumanDetectionTimeCommand_37 MO 5min(1)
HumanDetectionTimeStatus_37 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
38 ※ Dev Type AC
address

instance
point Name
number

14337 1 On/Off (Setting)


14338 2 On/Off (Status)
14339 3 Lock (Setting)
14340 4 Lock (Status)
14341 5 Filter Sign
14342 6 Filter Sign reset
14343 7 Operation Mode (Setting)
14344 8 Operation Mode (Status)
14345 9 Swing (Setting)
14346 10 Swing (Status)
14347 11 Fan Speed (Setting)
14348 12 Fan Speed (Status)
14349 13 Set Room Temperature
14350 14 Room Temperature
14351 15 Alarm
14352 16 Error Code
14355 19 Set Temperature (Status)
14356 20 Accumulated Power Distribution (Status)
14363 27 Set Upper Temperature (Setting)
14364 28 Set Lower Temperature (Setting)
14365 29 Set Upper Tempaerature (Status)
14366 30 Set Lower Temperature (Status)
14367 31 Mode Lock (Setting)
14368 32 Mode Lock (Status)
14369 33 Fan Lock (Setting)
14370 34 Fan Lock (Status)
14371 35 Occupancy (Setting)
14372 36 Occupancy (Status)
14373 37 2Set Cooling Set Temperature (Setting)
14374 38 2Set Cooling Set Temperature (Status)
14375 39 2Set Heating Set Temperature (Setting)
14376 40 2Set Heating Set Temperature (Status)
14377 41 2Set Cooling Upper Temperature (Setting)
14378 42 2Set Cooling Upper Temperature (Status)
14379 43 2Set Heating Upper Temperature (Setting)
14380 44 2Set Heating Upper Temperature (Status)
14381 45 2Set Cooling Lower Temperature (Setting)
14382 46 2Set Cooling Lower Temperature (Status)
14383 47 2Set Heating Lower Temperature (Setting)
14384 48 2Set Heating Lower Temperature (Status)
14385 49 Thermo Status (Status)
14386 50 Accumulated Gas Distribution (Status)
14387 51 Dust Sensor Available (Status)
14388 52 Air Cleaning Opereration (Setting)
14389 53 Air Cleaning Opereration (Status)
14390 54 Fine Dust (Status)
14391 55 Ultra Fine Dust (Status)
14392 56 Super Ultra Fine Dust (Status)
14393 57 Humidity (Status)
14394 58 Comfort Cooling Available (Status)
14395 59 Comfort Cooling Opereration (Setting)
14396 60 Comfort Cooling Opereration (Status)
14397 61 Comfort Cooling Step (Setting)
14398 62 Comfort Cooling Step (Status)
14399 63 Human Detection Available (Status)
14400 64 Human Detection Opereration (Setting)
14401 65 Human Detection Opereration (Status)
14402 66 Human Detection Wind (Setting)
14403 67 Human Detection Wind (Status)
14404 68 Human Detection Time (Setting)
14405 69 Human Detection Time (Status)
14406 70 Hotel Checkin (Setting)
14407 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_38 BO Stop(0) Start(1)
StartStopStatus_38 BI Stop(0) Start(1)
LockCommand_38 BO Permit(0) Prohibit(1)
LockStatus_38 BI Permit(0) Prohibit(1)
FilterSign_38 BI Off(0) On(1)
FilterSignReset_38 BV - Reset(1)
AirConModeCommand_38 MO Cool(1)
AirConModeStatus_38 MI Cool(1)
SwingCommand_38 BO Stop(0) Run(1)
SwingStatus_38 BI Stop(0) Run(1)
FanSpeedCommand_38 MO Low(1)
FanSpeedStatus_38 MI Low(1)
SetRoomTemp_38 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_38 AI ℃
Alarm_38 BI Normal(0) Abnormal(1)
MalfunctionCode_38 AI Refer to the
SetTempStatus_38 AI ℃
Accumulated power(100 Watt)_38 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_38 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_38 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_38 AI ℃
TempRangeLowerLimitStatus_38 AI ℃
ModeLockCommand_38 BO Permit(0) Prohibit(1)
ModeLockStatus_38 BI Permit(0) Prohibit(1)
FanLockCommand_38 BO Permit(0) Prohibit(1)
FanLockStatus_38 BI Permit(0) Prohibit(1)
OccupancyCommand_38 BO Unoccupied(0) Occupied(1)
OccupancyStatus_38 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_38 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_38 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_38 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_38 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_38 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_38 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_38 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_38 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_38 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_38 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_38 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_38 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_38 BI Off(0) On(1)
AccumulatedGas(100 Watt)_38 AI Wattage values (Unit : 100Watt)
DustSensorAvail_38 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_38 BO Stop(0) Run(1)
AirCleaningOperStatus_38 BI Stop(0) Run(1)
FineDustStatus_38 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_38 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_38 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_38 AI %
ComfortCoolingAvail_38 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_38 BO Stop(0) Run(1)
ComfortCoolingOperStatus_38 BI Stop(0) Run(1)
ComfortCoolingStepCommand_38 AV 1~3 step
ComfortCoolingStepStatus_38 AI 1~3 step
HumanDetectionAvail_38 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_38 MO Off(1)
HumanDetectionOperStatus_38 MI Off(1)
HumanDetectionWindCommand_38 MO Off(1)
HumanDetectionWindStatus_38 MI Off(1)
HumanDetectionTimeCommand_38 MO 5min(1)
HumanDetectionTimeStatus_38 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
39 ※ Dev Type AC
address

instance
point Name
number

14593 1 On/Off (Setting)


14594 2 On/Off (Status)
14595 3 Lock (Setting)
14596 4 Lock (Status)
14597 5 Filter Sign
14598 6 Filter Sign reset
14599 7 Operation Mode (Setting)
14600 8 Operation Mode (Status)
14601 9 Swing (Setting)
14602 10 Swing (Status)
14603 11 Fan Speed (Setting)
14604 12 Fan Speed (Status)
14605 13 Set Room Temperature
14606 14 Room Temperature
14607 15 Alarm
14608 16 Error Code
14611 19 Set Temperature (Status)
14612 20 Accumulated Power Distribution (Status)
14619 27 Set Upper Temperature (Setting)
14620 28 Set Lower Temperature (Setting)
14621 29 Set Upper Tempaerature (Status)
14622 30 Set Lower Temperature (Status)
14623 31 Mode Lock (Setting)
14624 32 Mode Lock (Status)
14625 33 Fan Lock (Setting)
14626 34 Fan Lock (Status)
14627 35 Occupancy (Setting)
14628 36 Occupancy (Status)
14629 37 2Set Cooling Set Temperature (Setting)
14630 38 2Set Cooling Set Temperature (Status)
14631 39 2Set Heating Set Temperature (Setting)
14632 40 2Set Heating Set Temperature (Status)
14633 41 2Set Cooling Upper Temperature (Setting)
14634 42 2Set Cooling Upper Temperature (Status)
14635 43 2Set Heating Upper Temperature (Setting)
14636 44 2Set Heating Upper Temperature (Status)
14637 45 2Set Cooling Lower Temperature (Setting)
14638 46 2Set Cooling Lower Temperature (Status)
14639 47 2Set Heating Lower Temperature (Setting)
14640 48 2Set Heating Lower Temperature (Status)
14641 49 Thermo Status (Status)
14642 50 Accumulated Gas Distribution (Status)
14643 51 Dust Sensor Available (Status)
14644 52 Air Cleaning Opereration (Setting)
14645 53 Air Cleaning Opereration (Status)
14646 54 Fine Dust (Status)
14647 55 Ultra Fine Dust (Status)
14648 56 Super Ultra Fine Dust (Status)
14649 57 Humidity (Status)
14650 58 Comfort Cooling Available (Status)
14651 59 Comfort Cooling Opereration (Setting)
14652 60 Comfort Cooling Opereration (Status)
14653 61 Comfort Cooling Step (Setting)
14654 62 Comfort Cooling Step (Status)
14655 63 Human Detection Available (Status)
14656 64 Human Detection Opereration (Setting)
14657 65 Human Detection Opereration (Status)
14658 66 Human Detection Wind (Setting)
14659 67 Human Detection Wind (Status)
14660 68 Human Detection Time (Setting)
14661 69 Human Detection Time (Status)
14662 70 Hotel Checkin (Setting)
14663 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_39 BO Stop(0) Start(1)
StartStopStatus_39 BI Stop(0) Start(1)
LockCommand_39 BO Permit(0) Prohibit(1)
LockStatus_39 BI Permit(0) Prohibit(1)
FilterSign_39 BI Off(0) On(1)
FilterSignReset_39 BV - Reset(1)
AirConModeCommand_39 MO Cool(1)
AirConModeStatus_39 MI Cool(1)
SwingCommand_39 BO Stop(0) Run(1)
SwingStatus_39 BI Stop(0) Run(1)
FanSpeedCommand_39 MO Low(1)
FanSpeedStatus_39 MI Low(1)
SetRoomTemp_39 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_39 AI ℃
Alarm_39 BI Normal(0) Abnormal(1)
MalfunctionCode_39 AI Refer to the
SetTempStatus_39 AI ℃
Accumulated power(100 Watt)_39 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_39 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_39 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_39 AI ℃
TempRangeLowerLimitStatus_39 AI ℃
ModeLockCommand_39 BO Permit(0) Prohibit(1)
ModeLockStatus_39 BI Permit(0) Prohibit(1)
FanLockCommand_39 BO Permit(0) Prohibit(1)
FanLockStatus_39 BI Permit(0) Prohibit(1)
OccupancyCommand_39 BO Unoccupied(0) Occupied(1)
OccupancyStatus_39 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_39 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_39 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_39 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_39 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_39 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_39 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_39 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_39 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_39 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_39 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_39 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_39 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_39 BI Off(0) On(1)
AccumulatedGas(100 Watt)_39 AI Wattage values (Unit : 100Watt)
DustSensorAvail_39 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_39 BO Stop(0) Run(1)
AirCleaningOperStatus_39 BI Stop(0) Run(1)
FineDustStatus_39 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_39 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_39 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_39 AI %
ComfortCoolingAvail_39 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_39 BO Stop(0) Run(1)
ComfortCoolingOperStatus_39 BI Stop(0) Run(1)
ComfortCoolingStepCommand_39 AV 1~3 step
ComfortCoolingStepStatus_39 AI 1~3 step
HumanDetectionAvail_39 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_39 MO Off(1)
HumanDetectionOperStatus_39 MI Off(1)
HumanDetectionWindCommand_39 MO Off(1)
HumanDetectionWindStatus_39 MI Off(1)
HumanDetectionTimeCommand_39 MO 5min(1)
HumanDetectionTimeStatus_39 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3a ※ Dev Type AC
address

instance
point Name
number

14849 1 On/Off (Setting)


14850 2 On/Off (Status)
14851 3 Lock (Setting)
14852 4 Lock (Status)
14853 5 Filter Sign
14854 6 Filter Sign reset
14855 7 Operation Mode (Setting)
14856 8 Operation Mode (Status)
14857 9 Swing (Setting)
14858 10 Swing (Status)
14859 11 Fan Speed (Setting)
14860 12 Fan Speed (Status)
14861 13 Set Room Temperature
14862 14 Room Temperature
14863 15 Alarm
14864 16 Error Code
14867 19 Set Temperature (Status)
14868 20 Accumulated Power Distribution (Status)
14875 27 Set Upper Temperature (Setting)
14876 28 Set Lower Temperature (Setting)
14877 29 Set Upper Tempaerature (Status)
14878 30 Set Lower Temperature (Status)
14879 31 Mode Lock (Setting)
14880 32 Mode Lock (Status)
14881 33 Fan Lock (Setting)
14882 34 Fan Lock (Status)
14883 35 Occupancy (Setting)
14884 36 Occupancy (Status)
14885 37 2Set Cooling Set Temperature (Setting)
14886 38 2Set Cooling Set Temperature (Status)
14887 39 2Set Heating Set Temperature (Setting)
14888 40 2Set Heating Set Temperature (Status)
14889 41 2Set Cooling Upper Temperature (Setting)
14890 42 2Set Cooling Upper Temperature (Status)
14891 43 2Set Heating Upper Temperature (Setting)
14892 44 2Set Heating Upper Temperature (Status)
14893 45 2Set Cooling Lower Temperature (Setting)
14894 46 2Set Cooling Lower Temperature (Status)
14895 47 2Set Heating Lower Temperature (Setting)
14896 48 2Set Heating Lower Temperature (Status)
14897 49 Thermo Status (Status)
14898 50 Accumulated Gas Distribution (Status)
14899 51 Dust Sensor Available (Status)
14900 52 Air Cleaning Opereration (Setting)
14901 53 Air Cleaning Opereration (Status)
14902 54 Fine Dust (Status)
14903 55 Ultra Fine Dust (Status)
14904 56 Super Ultra Fine Dust (Status)
14905 57 Humidity (Status)
14906 58 Comfort Cooling Available (Status)
14907 59 Comfort Cooling Opereration (Setting)
14908 60 Comfort Cooling Opereration (Status)
14909 61 Comfort Cooling Step (Setting)
14910 62 Comfort Cooling Step (Status)
14911 63 Human Detection Available (Status)
14912 64 Human Detection Opereration (Setting)
14913 65 Human Detection Opereration (Status)
14914 66 Human Detection Wind (Setting)
14915 67 Human Detection Wind (Status)
14916 68 Human Detection Time (Setting)
14917 69 Human Detection Time (Status)
14918 70 Hotel Checkin (Setting)
14919 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3a BO Stop(0) Start(1)
StartStopStatus_3a BI Stop(0) Start(1)
LockCommand_3a BO Permit(0) Prohibit(1)
LockStatus_3a BI Permit(0) Prohibit(1)
FilterSign_3a BI Off(0) On(1)
FilterSignReset_3a BV - Reset(1)
AirConModeCommand_3a MO Cool(1)
AirConModeStatus_3a MI Cool(1)
SwingCommand_3a BO Stop(0) Run(1)
SwingStatus_3a BI Stop(0) Run(1)
FanSpeedCommand_3a MO Low(1)
FanSpeedStatus_3a MI Low(1)
SetRoomTemp_3a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3a AI ℃
Alarm_3a BI Normal(0) Abnormal(1)
MalfunctionCode_3a AI Refer to the
SetTempStatus_3a AI ℃
Accumulated power(100 Watt)_3a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3a AI ℃
TempRangeLowerLimitStatus_3a AI ℃
ModeLockCommand_3a BO Permit(0) Prohibit(1)
ModeLockStatus_3a BI Permit(0) Prohibit(1)
FanLockCommand_3a BO Permit(0) Prohibit(1)
FanLockStatus_3a BI Permit(0) Prohibit(1)
OccupancyCommand_3a BO Unoccupied(0) Occupied(1)
OccupancyStatus_3a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3a BI Off(0) On(1)
AccumulatedGas(100 Watt)_3a AI Wattage values (Unit : 100Watt)
DustSensorAvail_3a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3a BO Stop(0) Run(1)
AirCleaningOperStatus_3a BI Stop(0) Run(1)
FineDustStatus_3a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3a AI %
ComfortCoolingAvail_3a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3a BO Stop(0) Run(1)
ComfortCoolingOperStatus_3a BI Stop(0) Run(1)
ComfortCoolingStepCommand_3a AV 1~3 step
ComfortCoolingStepStatus_3a AI 1~3 step
HumanDetectionAvail_3a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3a MO Off(1)
HumanDetectionOperStatus_3a MI Off(1)
HumanDetectionWindCommand_3a MO Off(1)
HumanDetectionWindStatus_3a MI Off(1)
HumanDetectionTimeCommand_3a MO 5min(1)
HumanDetectionTimeStatus_3a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3b ※ Dev Type AC
address

instance
point Name
number

15105 1 On/Off (Setting)


15106 2 On/Off (Status)
15107 3 Lock (Setting)
15108 4 Lock (Status)
15109 5 Filter Sign
15110 6 Filter Sign reset
15111 7 Operation Mode (Setting)
15112 8 Operation Mode (Status)
15113 9 Swing (Setting)
15114 10 Swing (Status)
15115 11 Fan Speed (Setting)
15116 12 Fan Speed (Status)
15117 13 Set Room Temperature
15118 14 Room Temperature
15119 15 Alarm
15120 16 Error Code
15123 19 Set Temperature (Status)
15124 20 Accumulated Power Distribution (Status)
15131 27 Set Upper Temperature (Setting)
15132 28 Set Lower Temperature (Setting)
15133 29 Set Upper Tempaerature (Status)
15134 30 Set Lower Temperature (Status)
15135 31 Mode Lock (Setting)
15136 32 Mode Lock (Status)
15137 33 Fan Lock (Setting)
15138 34 Fan Lock (Status)
15139 35 Occupancy (Setting)
15140 36 Occupancy (Status)
15141 37 2Set Cooling Set Temperature (Setting)
15142 38 2Set Cooling Set Temperature (Status)
15143 39 2Set Heating Set Temperature (Setting)
15144 40 2Set Heating Set Temperature (Status)
15145 41 2Set Cooling Upper Temperature (Setting)
15146 42 2Set Cooling Upper Temperature (Status)
15147 43 2Set Heating Upper Temperature (Setting)
15148 44 2Set Heating Upper Temperature (Status)
15149 45 2Set Cooling Lower Temperature (Setting)
15150 46 2Set Cooling Lower Temperature (Status)
15151 47 2Set Heating Lower Temperature (Setting)
15152 48 2Set Heating Lower Temperature (Status)
15153 49 Thermo Status (Status)
15154 50 Accumulated Gas Distribution (Status)
15155 51 Dust Sensor Available (Status)
15156 52 Air Cleaning Opereration (Setting)
15157 53 Air Cleaning Opereration (Status)
15158 54 Fine Dust (Status)
15159 55 Ultra Fine Dust (Status)
15160 56 Super Ultra Fine Dust (Status)
15161 57 Humidity (Status)
15162 58 Comfort Cooling Available (Status)
15163 59 Comfort Cooling Opereration (Setting)
15164 60 Comfort Cooling Opereration (Status)
15165 61 Comfort Cooling Step (Setting)
15166 62 Comfort Cooling Step (Status)
15167 63 Human Detection Available (Status)
15168 64 Human Detection Opereration (Setting)
15169 65 Human Detection Opereration (Status)
15170 66 Human Detection Wind (Setting)
15171 67 Human Detection Wind (Status)
15172 68 Human Detection Time (Setting)
15173 69 Human Detection Time (Status)
15174 70 Hotel Checkin (Setting)
15175 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3b BO Stop(0) Start(1)
StartStopStatus_3b BI Stop(0) Start(1)
LockCommand_3b BO Permit(0) Prohibit(1)
LockStatus_3b BI Permit(0) Prohibit(1)
FilterSign_3b BI Off(0) On(1)
FilterSignReset_3b BV - Reset(1)
AirConModeCommand_3b MO Cool(1)
AirConModeStatus_3b MI Cool(1)
SwingCommand_3b BO Stop(0) Run(1)
SwingStatus_3b BI Stop(0) Run(1)
FanSpeedCommand_3b MO Low(1)
FanSpeedStatus_3b MI Low(1)
SetRoomTemp_3b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3b AI ℃
Alarm_3b BI Normal(0) Abnormal(1)
MalfunctionCode_3b AI Refer to the
SetTempStatus_3b AI ℃
Accumulated power(100 Watt)_3b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3b AI ℃
TempRangeLowerLimitStatus_3b AI ℃
ModeLockCommand_3b BO Permit(0) Prohibit(1)
ModeLockStatus_3b BI Permit(0) Prohibit(1)
FanLockCommand_3b BO Permit(0) Prohibit(1)
FanLockStatus_3b BI Permit(0) Prohibit(1)
OccupancyCommand_3b BO Unoccupied(0) Occupied(1)
OccupancyStatus_3b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3b BI Off(0) On(1)
AccumulatedGas(100 Watt)_3b AI Wattage values (Unit : 100Watt)
DustSensorAvail_3b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3b BO Stop(0) Run(1)
AirCleaningOperStatus_3b BI Stop(0) Run(1)
FineDustStatus_3b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3b AI %
ComfortCoolingAvail_3b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3b BO Stop(0) Run(1)
ComfortCoolingOperStatus_3b BI Stop(0) Run(1)
ComfortCoolingStepCommand_3b AV 1~3 step
ComfortCoolingStepStatus_3b AI 1~3 step
HumanDetectionAvail_3b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3b MO Off(1)
HumanDetectionOperStatus_3b MI Off(1)
HumanDetectionWindCommand_3b MO Off(1)
HumanDetectionWindStatus_3b MI Off(1)
HumanDetectionTimeCommand_3b MO 5min(1)
HumanDetectionTimeStatus_3b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3c ※ Dev Type AC
address

instance
point Name
number

15361 1 On/Off (Setting)


15362 2 On/Off (Status)
15363 3 Lock (Setting)
15364 4 Lock (Status)
15365 5 Filter Sign
15366 6 Filter Sign reset
15367 7 Operation Mode (Setting)
15368 8 Operation Mode (Status)
15369 9 Swing (Setting)
15370 10 Swing (Status)
15371 11 Fan Speed (Setting)
15372 12 Fan Speed (Status)
15373 13 Set Room Temperature
15374 14 Room Temperature
15375 15 Alarm
15376 16 Error Code
15379 19 Set Temperature (Status)
15380 20 Accumulated Power Distribution (Status)
15387 27 Set Upper Temperature (Setting)
15388 28 Set Lower Temperature (Setting)
15389 29 Set Upper Tempaerature (Status)
15390 30 Set Lower Temperature (Status)
15391 31 Mode Lock (Setting)
15392 32 Mode Lock (Status)
15393 33 Fan Lock (Setting)
15394 34 Fan Lock (Status)
15395 35 Occupancy (Setting)
15396 36 Occupancy (Status)
15397 37 2Set Cooling Set Temperature (Setting)
15398 38 2Set Cooling Set Temperature (Status)
15399 39 2Set Heating Set Temperature (Setting)
15400 40 2Set Heating Set Temperature (Status)
15401 41 2Set Cooling Upper Temperature (Setting)
15402 42 2Set Cooling Upper Temperature (Status)
15403 43 2Set Heating Upper Temperature (Setting)
15404 44 2Set Heating Upper Temperature (Status)
15405 45 2Set Cooling Lower Temperature (Setting)
15406 46 2Set Cooling Lower Temperature (Status)
15407 47 2Set Heating Lower Temperature (Setting)
15408 48 2Set Heating Lower Temperature (Status)
15409 49 Thermo Status (Status)
15410 50 Accumulated Gas Distribution (Status)
15411 51 Dust Sensor Available (Status)
15412 52 Air Cleaning Opereration (Setting)
15413 53 Air Cleaning Opereration (Status)
15414 54 Fine Dust (Status)
15415 55 Ultra Fine Dust (Status)
15416 56 Super Ultra Fine Dust (Status)
15417 57 Humidity (Status)
15418 58 Comfort Cooling Available (Status)
15419 59 Comfort Cooling Opereration (Setting)
15420 60 Comfort Cooling Opereration (Status)
15421 61 Comfort Cooling Step (Setting)
15422 62 Comfort Cooling Step (Status)
15423 63 Human Detection Available (Status)
15424 64 Human Detection Opereration (Setting)
15425 65 Human Detection Opereration (Status)
15426 66 Human Detection Wind (Setting)
15427 67 Human Detection Wind (Status)
15428 68 Human Detection Time (Setting)
15429 69 Human Detection Time (Status)
15430 70 Hotel Checkin (Setting)
15431 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3c BO Stop(0) Start(1)
StartStopStatus_3c BI Stop(0) Start(1)
LockCommand_3c BO Permit(0) Prohibit(1)
LockStatus_3c BI Permit(0) Prohibit(1)
FilterSign_3c BI Off(0) On(1)
FilterSignReset_3c BV - Reset(1)
AirConModeCommand_3c MO Cool(1)
AirConModeStatus_3c MI Cool(1)
SwingCommand_3c BO Stop(0) Run(1)
SwingStatus_3c BI Stop(0) Run(1)
FanSpeedCommand_3c MO Low(1)
FanSpeedStatus_3c MI Low(1)
SetRoomTemp_3c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3c AI ℃
Alarm_3c BI Normal(0) Abnormal(1)
MalfunctionCode_3c AI Refer to the
SetTempStatus_3c AI ℃
Accumulated power(100 Watt)_3c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3c AI ℃
TempRangeLowerLimitStatus_3c AI ℃
ModeLockCommand_3c BO Permit(0) Prohibit(1)
ModeLockStatus_3c BI Permit(0) Prohibit(1)
FanLockCommand_3c BO Permit(0) Prohibit(1)
FanLockStatus_3c BI Permit(0) Prohibit(1)
OccupancyCommand_3c BO Unoccupied(0) Occupied(1)
OccupancyStatus_3c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3c BI Off(0) On(1)
AccumulatedGas(100 Watt)_3c AI Wattage values (Unit : 100Watt)
DustSensorAvail_3c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3c BO Stop(0) Run(1)
AirCleaningOperStatus_3c BI Stop(0) Run(1)
FineDustStatus_3c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3c AI %
ComfortCoolingAvail_3c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3c BO Stop(0) Run(1)
ComfortCoolingOperStatus_3c BI Stop(0) Run(1)
ComfortCoolingStepCommand_3c AV 1~3 step
ComfortCoolingStepStatus_3c AI 1~3 step
HumanDetectionAvail_3c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3c MO Off(1)
HumanDetectionOperStatus_3c MI Off(1)
HumanDetectionWindCommand_3c MO Off(1)
HumanDetectionWindStatus_3c MI Off(1)
HumanDetectionTimeCommand_3c MO 5min(1)
HumanDetectionTimeStatus_3c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3d ※ Dev Type AC
address

instance
point Name
number

15617 1 On/Off (Setting)


15618 2 On/Off (Status)
15619 3 Lock (Setting)
15620 4 Lock (Status)
15621 5 Filter Sign
15622 6 Filter Sign reset
15623 7 Operation Mode (Setting)
15624 8 Operation Mode (Status)
15625 9 Swing (Setting)
15626 10 Swing (Status)
15627 11 Fan Speed (Setting)
15628 12 Fan Speed (Status)
15629 13 Set Room Temperature
15630 14 Room Temperature
15631 15 Alarm
15632 16 Error Code
15635 19 Set Temperature (Status)
15636 20 Accumulated Power Distribution (Status)
15643 27 Set Upper Temperature (Setting)
15644 28 Set Lower Temperature (Setting)
15645 29 Set Upper Tempaerature (Status)
15646 30 Set Lower Temperature (Status)
15647 31 Mode Lock (Setting)
15648 32 Mode Lock (Status)
15649 33 Fan Lock (Setting)
15650 34 Fan Lock (Status)
15651 35 Occupancy (Setting)
15652 36 Occupancy (Status)
15653 37 2Set Cooling Set Temperature (Setting)
15654 38 2Set Cooling Set Temperature (Status)
15655 39 2Set Heating Set Temperature (Setting)
15656 40 2Set Heating Set Temperature (Status)
15657 41 2Set Cooling Upper Temperature (Setting)
15658 42 2Set Cooling Upper Temperature (Status)
15659 43 2Set Heating Upper Temperature (Setting)
15660 44 2Set Heating Upper Temperature (Status)
15661 45 2Set Cooling Lower Temperature (Setting)
15662 46 2Set Cooling Lower Temperature (Status)
15663 47 2Set Heating Lower Temperature (Setting)
15664 48 2Set Heating Lower Temperature (Status)
15665 49 Thermo Status (Status)
15666 50 Accumulated Gas Distribution (Status)
15667 51 Dust Sensor Available (Status)
15668 52 Air Cleaning Opereration (Setting)
15669 53 Air Cleaning Opereration (Status)
15670 54 Fine Dust (Status)
15671 55 Ultra Fine Dust (Status)
15672 56 Super Ultra Fine Dust (Status)
15673 57 Humidity (Status)
15674 58 Comfort Cooling Available (Status)
15675 59 Comfort Cooling Opereration (Setting)
15676 60 Comfort Cooling Opereration (Status)
15677 61 Comfort Cooling Step (Setting)
15678 62 Comfort Cooling Step (Status)
15679 63 Human Detection Available (Status)
15680 64 Human Detection Opereration (Setting)
15681 65 Human Detection Opereration (Status)
15682 66 Human Detection Wind (Setting)
15683 67 Human Detection Wind (Status)
15684 68 Human Detection Time (Setting)
15685 69 Human Detection Time (Status)
15686 70 Hotel Checkin (Setting)
15687 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3d BO Stop(0) Start(1)
StartStopStatus_3d BI Stop(0) Start(1)
LockCommand_3d BO Permit(0) Prohibit(1)
LockStatus_3d BI Permit(0) Prohibit(1)
FilterSign_3d BI Off(0) On(1)
FilterSignReset_3d BV - Reset(1)
AirConModeCommand_3d MO Cool(1)
AirConModeStatus_3d MI Cool(1)
SwingCommand_3d BO Stop(0) Run(1)
SwingStatus_3d BI Stop(0) Run(1)
FanSpeedCommand_3d MO Low(1)
FanSpeedStatus_3d MI Low(1)
SetRoomTemp_3d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3d AI ℃
Alarm_3d BI Normal(0) Abnormal(1)
MalfunctionCode_3d AI Refer to the
SetTempStatus_3d AI ℃
Accumulated power(100 Watt)_3d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3d AI ℃
TempRangeLowerLimitStatus_3d AI ℃
ModeLockCommand_3d BO Permit(0) Prohibit(1)
ModeLockStatus_3d BI Permit(0) Prohibit(1)
FanLockCommand_3d BO Permit(0) Prohibit(1)
FanLockStatus_3d BI Permit(0) Prohibit(1)
OccupancyCommand_3d BO Unoccupied(0) Occupied(1)
OccupancyStatus_3d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3d BI Off(0) On(1)
AccumulatedGas(100 Watt)_3d AI Wattage values (Unit : 100Watt)
DustSensorAvail_3d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3d BO Stop(0) Run(1)
AirCleaningOperStatus_3d BI Stop(0) Run(1)
FineDustStatus_3d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3d AI %
ComfortCoolingAvail_3d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3d BO Stop(0) Run(1)
ComfortCoolingOperStatus_3d BI Stop(0) Run(1)
ComfortCoolingStepCommand_3d AV 1~3 step
ComfortCoolingStepStatus_3d AI 1~3 step
HumanDetectionAvail_3d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3d MO Off(1)
HumanDetectionOperStatus_3d MI Off(1)
HumanDetectionWindCommand_3d MO Off(1)
HumanDetectionWindStatus_3d MI Off(1)
HumanDetectionTimeCommand_3d MO 5min(1)
HumanDetectionTimeStatus_3d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3e ※ Dev Type AC
address

instance
point Name
number

15873 1 On/Off (Setting)


15874 2 On/Off (Status)
15875 3 Lock (Setting)
15876 4 Lock (Status)
15877 5 Filter Sign
15878 6 Filter Sign reset
15879 7 Operation Mode (Setting)
15880 8 Operation Mode (Status)
15881 9 Swing (Setting)
15882 10 Swing (Status)
15883 11 Fan Speed (Setting)
15884 12 Fan Speed (Status)
15885 13 Set Room Temperature
15886 14 Room Temperature
15887 15 Alarm
15888 16 Error Code
15891 19 Set Temperature (Status)
15892 20 Accumulated Power Distribution (Status)
15899 27 Set Upper Temperature (Setting)
15900 28 Set Lower Temperature (Setting)
15901 29 Set Upper Tempaerature (Status)
15902 30 Set Lower Temperature (Status)
15903 31 Mode Lock (Setting)
15904 32 Mode Lock (Status)
15905 33 Fan Lock (Setting)
15906 34 Fan Lock (Status)
15907 35 Occupancy (Setting)
15908 36 Occupancy (Status)
15909 37 2Set Cooling Set Temperature (Setting)
15910 38 2Set Cooling Set Temperature (Status)
15911 39 2Set Heating Set Temperature (Setting)
15912 40 2Set Heating Set Temperature (Status)
15913 41 2Set Cooling Upper Temperature (Setting)
15914 42 2Set Cooling Upper Temperature (Status)
15915 43 2Set Heating Upper Temperature (Setting)
15916 44 2Set Heating Upper Temperature (Status)
15917 45 2Set Cooling Lower Temperature (Setting)
15918 46 2Set Cooling Lower Temperature (Status)
15919 47 2Set Heating Lower Temperature (Setting)
15920 48 2Set Heating Lower Temperature (Status)
15921 49 Thermo Status (Status)
15922 50 Accumulated Gas Distribution (Status)
15923 51 Dust Sensor Available (Status)
15924 52 Air Cleaning Opereration (Setting)
15925 53 Air Cleaning Opereration (Status)
15926 54 Fine Dust (Status)
15927 55 Ultra Fine Dust (Status)
15928 56 Super Ultra Fine Dust (Status)
15929 57 Humidity (Status)
15930 58 Comfort Cooling Available (Status)
15931 59 Comfort Cooling Opereration (Setting)
15932 60 Comfort Cooling Opereration (Status)
15933 61 Comfort Cooling Step (Setting)
15934 62 Comfort Cooling Step (Status)
15935 63 Human Detection Available (Status)
15936 64 Human Detection Opereration (Setting)
15937 65 Human Detection Opereration (Status)
15938 66 Human Detection Wind (Setting)
15939 67 Human Detection Wind (Status)
15940 68 Human Detection Time (Setting)
15941 69 Human Detection Time (Status)
15942 70 Hotel Checkin (Setting)
15943 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3e BO Stop(0) Start(1)
StartStopStatus_3e BI Stop(0) Start(1)
LockCommand_3e BO Permit(0) Prohibit(1)
LockStatus_3e BI Permit(0) Prohibit(1)
FilterSign_3e BI Off(0) On(1)
FilterSignReset_3e BV - Reset(1)
AirConModeCommand_3e MO Cool(1)
AirConModeStatus_3e MI Cool(1)
SwingCommand_3e BO Stop(0) Run(1)
SwingStatus_3e BI Stop(0) Run(1)
FanSpeedCommand_3e MO Low(1)
FanSpeedStatus_3e MI Low(1)
SetRoomTemp_3e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3e AI ℃
Alarm_3e BI Normal(0) Abnormal(1)
MalfunctionCode_3e AI Refer to the
SetTempStatus_3e AI ℃
Accumulated power(100 Watt)_3e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3e AI ℃
TempRangeLowerLimitStatus_3e AI ℃
ModeLockCommand_3e BO Permit(0) Prohibit(1)
ModeLockStatus_3e BI Permit(0) Prohibit(1)
FanLockCommand_3e BO Permit(0) Prohibit(1)
FanLockStatus_3e BI Permit(0) Prohibit(1)
OccupancyCommand_3e BO Unoccupied(0) Occupied(1)
OccupancyStatus_3e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3e BI Off(0) On(1)
AccumulatedGas(100 Watt)_3e AI Wattage values (Unit : 100Watt)
DustSensorAvail_3e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3e BO Stop(0) Run(1)
AirCleaningOperStatus_3e BI Stop(0) Run(1)
FineDustStatus_3e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3e AI %
ComfortCoolingAvail_3e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3e BO Stop(0) Run(1)
ComfortCoolingOperStatus_3e BI Stop(0) Run(1)
ComfortCoolingStepCommand_3e AV 1~3 step
ComfortCoolingStepStatus_3e AI 1~3 step
HumanDetectionAvail_3e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3e MO Off(1)
HumanDetectionOperStatus_3e MI Off(1)
HumanDetectionWindCommand_3e MO Off(1)
HumanDetectionWindStatus_3e MI Off(1)
HumanDetectionTimeCommand_3e MO 5min(1)
HumanDetectionTimeStatus_3e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3f ※ Dev Type AC
address

instance
point Name
number

16129 1 On/Off (Setting)


16130 2 On/Off (Status)
16131 3 Lock (Setting)
16132 4 Lock (Status)
16133 5 Filter Sign
16134 6 Filter Sign reset
16135 7 Operation Mode (Setting)
16136 8 Operation Mode (Status)
16137 9 Swing (Setting)
16138 10 Swing (Status)
16139 11 Fan Speed (Setting)
16140 12 Fan Speed (Status)
16141 13 Set Room Temperature
16142 14 Room Temperature
16143 15 Alarm
16144 16 Error Code
16147 19 Set Temperature (Status)
16148 20 Accumulated Power Distribution (Status)
16155 27 Set Upper Temperature (Setting)
16156 28 Set Lower Temperature (Setting)
16157 29 Set Upper Tempaerature (Status)
16158 30 Set Lower Temperature (Status)
16159 31 Mode Lock (Setting)
16160 32 Mode Lock (Status)
16161 33 Fan Lock (Setting)
16162 34 Fan Lock (Status)
16163 35 Occupancy (Setting)
16164 36 Occupancy (Status)
16165 37 2Set Cooling Set Temperature (Setting)
16166 38 2Set Cooling Set Temperature (Status)
16167 39 2Set Heating Set Temperature (Setting)
16168 40 2Set Heating Set Temperature (Status)
16169 41 2Set Cooling Upper Temperature (Setting)
16170 42 2Set Cooling Upper Temperature (Status)
16171 43 2Set Heating Upper Temperature (Setting)
16172 44 2Set Heating Upper Temperature (Status)
16173 45 2Set Cooling Lower Temperature (Setting)
16174 46 2Set Cooling Lower Temperature (Status)
16175 47 2Set Heating Lower Temperature (Setting)
16176 48 2Set Heating Lower Temperature (Status)
16177 49 Thermo Status (Status)
16178 50 Accumulated Gas Distribution (Status)
16179 51 Dust Sensor Available (Status)
16180 52 Air Cleaning Opereration (Setting)
16181 53 Air Cleaning Opereration (Status)
16182 54 Fine Dust (Status)
16183 55 Ultra Fine Dust (Status)
16184 56 Super Ultra Fine Dust (Status)
16185 57 Humidity (Status)
16186 58 Comfort Cooling Available (Status)
16187 59 Comfort Cooling Opereration (Setting)
16188 60 Comfort Cooling Opereration (Status)
16189 61 Comfort Cooling Step (Setting)
16190 62 Comfort Cooling Step (Status)
16191 63 Human Detection Available (Status)
16192 64 Human Detection Opereration (Setting)
16193 65 Human Detection Opereration (Status)
16194 66 Human Detection Wind (Setting)
16195 67 Human Detection Wind (Status)
16196 68 Human Detection Time (Setting)
16197 69 Human Detection Time (Status)
16198 70 Hotel Checkin (Setting)
16199 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3f BO Stop(0) Start(1)
StartStopStatus_3f BI Stop(0) Start(1)
LockCommand_3f BO Permit(0) Prohibit(1)
LockStatus_3f BI Permit(0) Prohibit(1)
FilterSign_3f BI Off(0) On(1)
FilterSignReset_3f BV - Reset(1)
AirConModeCommand_3f MO Cool(1)
AirConModeStatus_3f MI Cool(1)
SwingCommand_3f BO Stop(0) Run(1)
SwingStatus_3f BI Stop(0) Run(1)
FanSpeedCommand_3f MO Low(1)
FanSpeedStatus_3f MI Low(1)
SetRoomTemp_3f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3f AI ℃
Alarm_3f BI Normal(0) Abnormal(1)
MalfunctionCode_3f AI Refer to the
SetTempStatus_3f AI ℃
Accumulated power(100 Watt)_3f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3f AI ℃
TempRangeLowerLimitStatus_3f AI ℃
ModeLockCommand_3f BO Permit(0) Prohibit(1)
ModeLockStatus_3f BI Permit(0) Prohibit(1)
FanLockCommand_3f BO Permit(0) Prohibit(1)
FanLockStatus_3f BI Permit(0) Prohibit(1)
OccupancyCommand_3f BO Unoccupied(0) Occupied(1)
OccupancyStatus_3f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3f BI Off(0) On(1)
AccumulatedGas(100 Watt)_3f AI Wattage values (Unit : 100Watt)
DustSensorAvail_3f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3f BO Stop(0) Run(1)
AirCleaningOperStatus_3f BI Stop(0) Run(1)
FineDustStatus_3f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3f AI %
ComfortCoolingAvail_3f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3f BO Stop(0) Run(1)
ComfortCoolingOperStatus_3f BI Stop(0) Run(1)
ComfortCoolingStepCommand_3f AV 1~3 step
ComfortCoolingStepStatus_3f AI 1~3 step
HumanDetectionAvail_3f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3f MO Off(1)
HumanDetectionOperStatus_3f MI Off(1)
HumanDetectionWindCommand_3f MO Off(1)
HumanDetectionWindStatus_3f MI Off(1)
HumanDetectionTimeCommand_3f MO 5min(1)
HumanDetectionTimeStatus_3f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
40 ※ Dev Type AC
address

instance
point Name
number

16385 1 On/Off (Setting)


16386 2 On/Off (Status)
16387 3 Lock (Setting)
16388 4 Lock (Status)
16389 5 Filter Sign
16390 6 Filter Sign reset
16391 7 Operation Mode (Setting)
16392 8 Operation Mode (Status)
16393 9 Swing (Setting)
16394 10 Swing (Status)
16395 11 Fan Speed (Setting)
16396 12 Fan Speed (Status)
16397 13 Set Room Temperature
16398 14 Room Temperature
16399 15 Alarm
16400 16 Error Code
16403 19 Set Temperature (Status)
16404 20 Accumulated Power Distribution (Status)
16411 27 Set Upper Temperature (Setting)
16412 28 Set Lower Temperature (Setting)
16413 29 Set Upper Tempaerature (Status)
16414 30 Set Lower Temperature (Status)
16415 31 Mode Lock (Setting)
16416 32 Mode Lock (Status)
16417 33 Fan Lock (Setting)
16418 34 Fan Lock (Status)
16419 35 Occupancy (Setting)
16420 36 Occupancy (Status)
16421 37 2Set Cooling Set Temperature (Setting)
16422 38 2Set Cooling Set Temperature (Status)
16423 39 2Set Heating Set Temperature (Setting)
16424 40 2Set Heating Set Temperature (Status)
16425 41 2Set Cooling Upper Temperature (Setting)
16426 42 2Set Cooling Upper Temperature (Status)
16427 43 2Set Heating Upper Temperature (Setting)
16428 44 2Set Heating Upper Temperature (Status)
16429 45 2Set Cooling Lower Temperature (Setting)
16430 46 2Set Cooling Lower Temperature (Status)
16431 47 2Set Heating Lower Temperature (Setting)
16432 48 2Set Heating Lower Temperature (Status)
16433 49 Thermo Status (Status)
16434 50 Accumulated Gas Distribution (Status)
16435 51 Dust Sensor Available (Status)
16436 52 Air Cleaning Opereration (Setting)
16437 53 Air Cleaning Opereration (Status)
16438 54 Fine Dust (Status)
16439 55 Ultra Fine Dust (Status)
16440 56 Super Ultra Fine Dust (Status)
16441 57 Humidity (Status)
16442 58 Comfort Cooling Available (Status)
16443 59 Comfort Cooling Opereration (Setting)
16444 60 Comfort Cooling Opereration (Status)
16445 61 Comfort Cooling Step (Setting)
16446 62 Comfort Cooling Step (Status)
16447 63 Human Detection Available (Status)
16448 64 Human Detection Opereration (Setting)
16449 65 Human Detection Opereration (Status)
16450 66 Human Detection Wind (Setting)
16451 67 Human Detection Wind (Status)
16452 68 Human Detection Time (Setting)
16453 69 Human Detection Time (Status)
16454 70 Hotel Checkin (Setting)
16455 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_40 BO Stop(0) Start(1)
StartStopStatus_40 BI Stop(0) Start(1)
LockCommand_40 BO Permit(0) Prohibit(1)
LockStatus_40 BI Permit(0) Prohibit(1)
FilterSign_40 BI Off(0) On(1)
FilterSignReset_40 BV - Reset(1)
AirConModeCommand_40 MO Cool(1)
AirConModeStatus_40 MI Cool(1)
SwingCommand_40 BO Stop(0) Run(1)
SwingStatus_40 BI Stop(0) Run(1)
FanSpeedCommand_40 MO Low(1)
FanSpeedStatus_40 MI Low(1)
SetRoomTemp_40 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_40 AI ℃
Alarm_40 BI Normal(0) Abnormal(1)
MalfunctionCode_40 AI Refer to the
SetTempStatus_40 AI ℃
Accumulated power(100 Watt)_40 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_40 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_40 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_40 AI ℃
TempRangeLowerLimitStatus_40 AI ℃
ModeLockCommand_40 BO Permit(0) Prohibit(1)
ModeLockStatus_40 BI Permit(0) Prohibit(1)
FanLockCommand_40 BO Permit(0) Prohibit(1)
FanLockStatus_40 BI Permit(0) Prohibit(1)
OccupancyCommand_40 BO Unoccupied(0) Occupied(1)
OccupancyStatus_40 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_40 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_40 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_40 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_40 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_40 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_40 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_40 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_40 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_40 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_40 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_40 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_40 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_40 BI Off(0) On(1)
AccumulatedGas(100 Watt)_40 AI Wattage values (Unit : 100Watt)
DustSensorAvail_40 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_40 BO Stop(0) Run(1)
AirCleaningOperStatus_40 BI Stop(0) Run(1)
FineDustStatus_40 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_40 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_40 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_40 AI %
ComfortCoolingAvail_40 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_40 BO Stop(0) Run(1)
ComfortCoolingOperStatus_40 BI Stop(0) Run(1)
ComfortCoolingStepCommand_40 AV 1~3 step
ComfortCoolingStepStatus_40 AI 1~3 step
HumanDetectionAvail_40 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_40 MO Off(1)
HumanDetectionOperStatus_40 MI Off(1)
HumanDetectionWindCommand_40 MO Off(1)
HumanDetectionWindStatus_40 MI Off(1)
HumanDetectionTimeCommand_40 MO 5min(1)
HumanDetectionTimeStatus_40 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
41 ※ Dev Type AC
address

instance
point Name
number

16641 1 On/Off (Setting)


16642 2 On/Off (Status)
16643 3 Lock (Setting)
16644 4 Lock (Status)
16645 5 Filter Sign
16646 6 Filter Sign reset
16647 7 Operation Mode (Setting)
16648 8 Operation Mode (Status)
16649 9 Swing (Setting)
16650 10 Swing (Status)
16651 11 Fan Speed (Setting)
16652 12 Fan Speed (Status)
16653 13 Set Room Temperature
16654 14 Room Temperature
16655 15 Alarm
16656 16 Error Code
16659 19 Set Temperature (Status)
16660 20 Accumulated Power Distribution (Status)
16667 27 Set Upper Temperature (Setting)
16668 28 Set Lower Temperature (Setting)
16669 29 Set Upper Tempaerature (Status)
16670 30 Set Lower Temperature (Status)
16671 31 Mode Lock (Setting)
16672 32 Mode Lock (Status)
16673 33 Fan Lock (Setting)
16674 34 Fan Lock (Status)
16675 35 Occupancy (Setting)
16676 36 Occupancy (Status)
16677 37 2Set Cooling Set Temperature (Setting)
16678 38 2Set Cooling Set Temperature (Status)
16679 39 2Set Heating Set Temperature (Setting)
16680 40 2Set Heating Set Temperature (Status)
16681 41 2Set Cooling Upper Temperature (Setting)
16682 42 2Set Cooling Upper Temperature (Status)
16683 43 2Set Heating Upper Temperature (Setting)
16684 44 2Set Heating Upper Temperature (Status)
16685 45 2Set Cooling Lower Temperature (Setting)
16686 46 2Set Cooling Lower Temperature (Status)
16687 47 2Set Heating Lower Temperature (Setting)
16688 48 2Set Heating Lower Temperature (Status)
16689 49 Thermo Status (Status)
16690 50 Accumulated Gas Distribution (Status)
16691 51 Dust Sensor Available (Status)
16692 52 Air Cleaning Opereration (Setting)
16693 53 Air Cleaning Opereration (Status)
16694 54 Fine Dust (Status)
16695 55 Ultra Fine Dust (Status)
16696 56 Super Ultra Fine Dust (Status)
16697 57 Humidity (Status)
16698 58 Comfort Cooling Available (Status)
16699 59 Comfort Cooling Opereration (Setting)
16700 60 Comfort Cooling Opereration (Status)
16701 61 Comfort Cooling Step (Setting)
16702 62 Comfort Cooling Step (Status)
16703 63 Human Detection Available (Status)
16704 64 Human Detection Opereration (Setting)
16705 65 Human Detection Opereration (Status)
16706 66 Human Detection Wind (Setting)
16707 67 Human Detection Wind (Status)
16708 68 Human Detection Time (Setting)
16709 69 Human Detection Time (Status)
16710 70 Hotel Checkin (Setting)
16711 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_41 BO Stop(0) Start(1)
StartStopStatus_41 BI Stop(0) Start(1)
LockCommand_41 BO Permit(0) Prohibit(1)
LockStatus_41 BI Permit(0) Prohibit(1)
FilterSign_41 BI Off(0) On(1)
FilterSignReset_41 BV - Reset(1)
AirConModeCommand_41 MO Cool(1)
AirConModeStatus_41 MI Cool(1)
SwingCommand_41 BO Stop(0) Run(1)
SwingStatus_41 BI Stop(0) Run(1)
FanSpeedCommand_41 MO Low(1)
FanSpeedStatus_41 MI Low(1)
SetRoomTemp_41 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_41 AI ℃
Alarm_41 BI Normal(0) Abnormal(1)
MalfunctionCode_41 AI Refer to the
SetTempStatus_41 AI ℃
Accumulated power(100 Watt)_41 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_41 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_41 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_41 AI ℃
TempRangeLowerLimitStatus_41 AI ℃
ModeLockCommand_41 BO Permit(0) Prohibit(1)
ModeLockStatus_41 BI Permit(0) Prohibit(1)
FanLockCommand_41 BO Permit(0) Prohibit(1)
FanLockStatus_41 BI Permit(0) Prohibit(1)
OccupancyCommand_41 BO Unoccupied(0) Occupied(1)
OccupancyStatus_41 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_41 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_41 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_41 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_41 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_41 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_41 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_41 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_41 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_41 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_41 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_41 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_41 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_41 BI Off(0) On(1)
AccumulatedGas(100 Watt)_41 AI Wattage values (Unit : 100Watt)
DustSensorAvail_41 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_41 BO Stop(0) Run(1)
AirCleaningOperStatus_41 BI Stop(0) Run(1)
FineDustStatus_41 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_41 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_41 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_41 AI %
ComfortCoolingAvail_41 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_41 BO Stop(0) Run(1)
ComfortCoolingOperStatus_41 BI Stop(0) Run(1)
ComfortCoolingStepCommand_41 AV 1~3 step
ComfortCoolingStepStatus_41 AI 1~3 step
HumanDetectionAvail_41 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_41 MO Off(1)
HumanDetectionOperStatus_41 MI Off(1)
HumanDetectionWindCommand_41 MO Off(1)
HumanDetectionWindStatus_41 MI Off(1)
HumanDetectionTimeCommand_41 MO 5min(1)
HumanDetectionTimeStatus_41 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
42 ※ Dev Type AC
address

instance
point Name
number

16897 1 On/Off (Setting)


16898 2 On/Off (Status)
16899 3 Lock (Setting)
16900 4 Lock (Status)
16901 5 Filter Sign
16902 6 Filter Sign reset
16903 7 Operation Mode (Setting)
16904 8 Operation Mode (Status)
16905 9 Swing (Setting)
16906 10 Swing (Status)
16907 11 Fan Speed (Setting)
16908 12 Fan Speed (Status)
16909 13 Set Room Temperature
16910 14 Room Temperature
16911 15 Alarm
16912 16 Error Code
16915 19 Set Temperature (Status)
16916 20 Accumulated Power Distribution (Status)
16923 27 Set Upper Temperature (Setting)
16924 28 Set Lower Temperature (Setting)
16925 29 Set Upper Tempaerature (Status)
16926 30 Set Lower Temperature (Status)
16927 31 Mode Lock (Setting)
16928 32 Mode Lock (Status)
16929 33 Fan Lock (Setting)
16930 34 Fan Lock (Status)
16931 35 Occupancy (Setting)
16932 36 Occupancy (Status)
16933 37 2Set Cooling Set Temperature (Setting)
16934 38 2Set Cooling Set Temperature (Status)
16935 39 2Set Heating Set Temperature (Setting)
16936 40 2Set Heating Set Temperature (Status)
16937 41 2Set Cooling Upper Temperature (Setting)
16938 42 2Set Cooling Upper Temperature (Status)
16939 43 2Set Heating Upper Temperature (Setting)
16940 44 2Set Heating Upper Temperature (Status)
16941 45 2Set Cooling Lower Temperature (Setting)
16942 46 2Set Cooling Lower Temperature (Status)
16943 47 2Set Heating Lower Temperature (Setting)
16944 48 2Set Heating Lower Temperature (Status)
16945 49 Thermo Status (Status)
16946 50 Accumulated Gas Distribution (Status)
16947 51 Dust Sensor Available (Status)
16948 52 Air Cleaning Opereration (Setting)
16949 53 Air Cleaning Opereration (Status)
16950 54 Fine Dust (Status)
16951 55 Ultra Fine Dust (Status)
16952 56 Super Ultra Fine Dust (Status)
16953 57 Humidity (Status)
16954 58 Comfort Cooling Available (Status)
16955 59 Comfort Cooling Opereration (Setting)
16956 60 Comfort Cooling Opereration (Status)
16957 61 Comfort Cooling Step (Setting)
16958 62 Comfort Cooling Step (Status)
16959 63 Human Detection Available (Status)
16960 64 Human Detection Opereration (Setting)
16961 65 Human Detection Opereration (Status)
16962 66 Human Detection Wind (Setting)
16963 67 Human Detection Wind (Status)
16964 68 Human Detection Time (Setting)
16965 69 Human Detection Time (Status)
16966 70 Hotel Checkin (Setting)
16967 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_42 BO Stop(0) Start(1)
StartStopStatus_42 BI Stop(0) Start(1)
LockCommand_42 BO Permit(0) Prohibit(1)
LockStatus_42 BI Permit(0) Prohibit(1)
FilterSign_42 BI Off(0) On(1)
FilterSignReset_42 BV - Reset(1)
AirConModeCommand_42 MO Cool(1)
AirConModeStatus_42 MI Cool(1)
SwingCommand_42 BO Stop(0) Run(1)
SwingStatus_42 BI Stop(0) Run(1)
FanSpeedCommand_42 MO Low(1)
FanSpeedStatus_42 MI Low(1)
SetRoomTemp_42 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_42 AI ℃
Alarm_42 BI Normal(0) Abnormal(1)
MalfunctionCode_42 AI Refer to the
SetTempStatus_42 AI ℃
Accumulated power(100 Watt)_42 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_42 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_42 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_42 AI ℃
TempRangeLowerLimitStatus_42 AI ℃
ModeLockCommand_42 BO Permit(0) Prohibit(1)
ModeLockStatus_42 BI Permit(0) Prohibit(1)
FanLockCommand_42 BO Permit(0) Prohibit(1)
FanLockStatus_42 BI Permit(0) Prohibit(1)
OccupancyCommand_42 BO Unoccupied(0) Occupied(1)
OccupancyStatus_42 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_42 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_42 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_42 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_42 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_42 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_42 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_42 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_42 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_42 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_42 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_42 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_42 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_42 BI Off(0) On(1)
AccumulatedGas(100 Watt)_42 AI Wattage values (Unit : 100Watt)
DustSensorAvail_42 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_42 BO Stop(0) Run(1)
AirCleaningOperStatus_42 BI Stop(0) Run(1)
FineDustStatus_42 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_42 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_42 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_42 AI %
ComfortCoolingAvail_42 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_42 BO Stop(0) Run(1)
ComfortCoolingOperStatus_42 BI Stop(0) Run(1)
ComfortCoolingStepCommand_42 AV 1~3 step
ComfortCoolingStepStatus_42 AI 1~3 step
HumanDetectionAvail_42 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_42 MO Off(1)
HumanDetectionOperStatus_42 MI Off(1)
HumanDetectionWindCommand_42 MO Off(1)
HumanDetectionWindStatus_42 MI Off(1)
HumanDetectionTimeCommand_42 MO 5min(1)
HumanDetectionTimeStatus_42 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
43 ※ Dev Type AC
address

instance
point Name
number

17153 1 On/Off (Setting)


17154 2 On/Off (Status)
17155 3 Lock (Setting)
17156 4 Lock (Status)
17157 5 Filter Sign
17158 6 Filter Sign reset
17159 7 Operation Mode (Setting)
17160 8 Operation Mode (Status)
17161 9 Swing (Setting)
17162 10 Swing (Status)
17163 11 Fan Speed (Setting)
17164 12 Fan Speed (Status)
17165 13 Set Room Temperature
17166 14 Room Temperature
17167 15 Alarm
17168 16 Error Code
17171 19 Set Temperature (Status)
17172 20 Accumulated Power Distribution (Status)
17179 27 Set Upper Temperature (Setting)
17180 28 Set Lower Temperature (Setting)
17181 29 Set Upper Tempaerature (Status)
17182 30 Set Lower Temperature (Status)
17183 31 Mode Lock (Setting)
17184 32 Mode Lock (Status)
17185 33 Fan Lock (Setting)
17186 34 Fan Lock (Status)
17187 35 Occupancy (Setting)
17188 36 Occupancy (Status)
17189 37 2Set Cooling Set Temperature (Setting)
17190 38 2Set Cooling Set Temperature (Status)
17191 39 2Set Heating Set Temperature (Setting)
17192 40 2Set Heating Set Temperature (Status)
17193 41 2Set Cooling Upper Temperature (Setting)
17194 42 2Set Cooling Upper Temperature (Status)
17195 43 2Set Heating Upper Temperature (Setting)
17196 44 2Set Heating Upper Temperature (Status)
17197 45 2Set Cooling Lower Temperature (Setting)
17198 46 2Set Cooling Lower Temperature (Status)
17199 47 2Set Heating Lower Temperature (Setting)
17200 48 2Set Heating Lower Temperature (Status)
17201 49 Thermo Status (Status)
17202 50 Accumulated Gas Distribution (Status)
17203 51 Dust Sensor Available (Status)
17204 52 Air Cleaning Opereration (Setting)
17205 53 Air Cleaning Opereration (Status)
17206 54 Fine Dust (Status)
17207 55 Ultra Fine Dust (Status)
17208 56 Super Ultra Fine Dust (Status)
17209 57 Humidity (Status)
17210 58 Comfort Cooling Available (Status)
17211 59 Comfort Cooling Opereration (Setting)
17212 60 Comfort Cooling Opereration (Status)
17213 61 Comfort Cooling Step (Setting)
17214 62 Comfort Cooling Step (Status)
17215 63 Human Detection Available (Status)
17216 64 Human Detection Opereration (Setting)
17217 65 Human Detection Opereration (Status)
17218 66 Human Detection Wind (Setting)
17219 67 Human Detection Wind (Status)
17220 68 Human Detection Time (Setting)
17221 69 Human Detection Time (Status)
17222 70 Hotel Checkin (Setting)
17223 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_43 BO Stop(0) Start(1)
StartStopStatus_43 BI Stop(0) Start(1)
LockCommand_43 BO Permit(0) Prohibit(1)
LockStatus_43 BI Permit(0) Prohibit(1)
FilterSign_43 BI Off(0) On(1)
FilterSignReset_43 BV - Reset(1)
AirConModeCommand_43 MO Cool(1)
AirConModeStatus_43 MI Cool(1)
SwingCommand_43 BO Stop(0) Run(1)
SwingStatus_43 BI Stop(0) Run(1)
FanSpeedCommand_43 MO Low(1)
FanSpeedStatus_43 MI Low(1)
SetRoomTemp_43 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_43 AI ℃
Alarm_43 BI Normal(0) Abnormal(1)
MalfunctionCode_43 AI Refer to the
SetTempStatus_43 AI ℃
Accumulated power(100 Watt)_43 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_43 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_43 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_43 AI ℃
TempRangeLowerLimitStatus_43 AI ℃
ModeLockCommand_43 BO Permit(0) Prohibit(1)
ModeLockStatus_43 BI Permit(0) Prohibit(1)
FanLockCommand_43 BO Permit(0) Prohibit(1)
FanLockStatus_43 BI Permit(0) Prohibit(1)
OccupancyCommand_43 BO Unoccupied(0) Occupied(1)
OccupancyStatus_43 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_43 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_43 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_43 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_43 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_43 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_43 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_43 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_43 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_43 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_43 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_43 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_43 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_43 BI Off(0) On(1)
AccumulatedGas(100 Watt)_43 AI Wattage values (Unit : 100Watt)
DustSensorAvail_43 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_43 BO Stop(0) Run(1)
AirCleaningOperStatus_43 BI Stop(0) Run(1)
FineDustStatus_43 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_43 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_43 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_43 AI %
ComfortCoolingAvail_43 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_43 BO Stop(0) Run(1)
ComfortCoolingOperStatus_43 BI Stop(0) Run(1)
ComfortCoolingStepCommand_43 AV 1~3 step
ComfortCoolingStepStatus_43 AI 1~3 step
HumanDetectionAvail_43 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_43 MO Off(1)
HumanDetectionOperStatus_43 MI Off(1)
HumanDetectionWindCommand_43 MO Off(1)
HumanDetectionWindStatus_43 MI Off(1)
HumanDetectionTimeCommand_43 MO 5min(1)
HumanDetectionTimeStatus_43 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
44 ※ Dev Type AC
address

instance
point Name
number

17409 1 On/Off (Setting)


17410 2 On/Off (Status)
17411 3 Lock (Setting)
17412 4 Lock (Status)
17413 5 Filter Sign
17414 6 Filter Sign reset
17415 7 Operation Mode (Setting)
17416 8 Operation Mode (Status)
17417 9 Swing (Setting)
17418 10 Swing (Status)
17419 11 Fan Speed (Setting)
17420 12 Fan Speed (Status)
17421 13 Set Room Temperature
17422 14 Room Temperature
17423 15 Alarm
17424 16 Error Code
17427 19 Set Temperature (Status)
17428 20 Accumulated Power Distribution (Status)
17435 27 Set Upper Temperature (Setting)
17436 28 Set Lower Temperature (Setting)
17437 29 Set Upper Tempaerature (Status)
17438 30 Set Lower Temperature (Status)
17439 31 Mode Lock (Setting)
17440 32 Mode Lock (Status)
17441 33 Fan Lock (Setting)
17442 34 Fan Lock (Status)
17443 35 Occupancy (Setting)
17444 36 Occupancy (Status)
17445 37 2Set Cooling Set Temperature (Setting)
17446 38 2Set Cooling Set Temperature (Status)
17447 39 2Set Heating Set Temperature (Setting)
17448 40 2Set Heating Set Temperature (Status)
17449 41 2Set Cooling Upper Temperature (Setting)
17450 42 2Set Cooling Upper Temperature (Status)
17451 43 2Set Heating Upper Temperature (Setting)
17452 44 2Set Heating Upper Temperature (Status)
17453 45 2Set Cooling Lower Temperature (Setting)
17454 46 2Set Cooling Lower Temperature (Status)
17455 47 2Set Heating Lower Temperature (Setting)
17456 48 2Set Heating Lower Temperature (Status)
17457 49 Thermo Status (Status)
17458 50 Accumulated Gas Distribution (Status)
17459 51 Dust Sensor Available (Status)
17460 52 Air Cleaning Opereration (Setting)
17461 53 Air Cleaning Opereration (Status)
17462 54 Fine Dust (Status)
17463 55 Ultra Fine Dust (Status)
17464 56 Super Ultra Fine Dust (Status)
17465 57 Humidity (Status)
17466 58 Comfort Cooling Available (Status)
17467 59 Comfort Cooling Opereration (Setting)
17468 60 Comfort Cooling Opereration (Status)
17469 61 Comfort Cooling Step (Setting)
17470 62 Comfort Cooling Step (Status)
17471 63 Human Detection Available (Status)
17472 64 Human Detection Opereration (Setting)
17473 65 Human Detection Opereration (Status)
17474 66 Human Detection Wind (Setting)
17475 67 Human Detection Wind (Status)
17476 68 Human Detection Time (Setting)
17477 69 Human Detection Time (Status)
17478 70 Hotel Checkin (Setting)
17479 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_44 BO Stop(0) Start(1)
StartStopStatus_44 BI Stop(0) Start(1)
LockCommand_44 BO Permit(0) Prohibit(1)
LockStatus_44 BI Permit(0) Prohibit(1)
FilterSign_44 BI Off(0) On(1)
FilterSignReset_44 BV - Reset(1)
AirConModeCommand_44 MO Cool(1)
AirConModeStatus_44 MI Cool(1)
SwingCommand_44 BO Stop(0) Run(1)
SwingStatus_44 BI Stop(0) Run(1)
FanSpeedCommand_44 MO Low(1)
FanSpeedStatus_44 MI Low(1)
SetRoomTemp_44 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_44 AI ℃
Alarm_44 BI Normal(0) Abnormal(1)
MalfunctionCode_44 AI Refer to the
SetTempStatus_44 AI ℃
Accumulated power(100 Watt)_44 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_44 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_44 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_44 AI ℃
TempRangeLowerLimitStatus_44 AI ℃
ModeLockCommand_44 BO Permit(0) Prohibit(1)
ModeLockStatus_44 BI Permit(0) Prohibit(1)
FanLockCommand_44 BO Permit(0) Prohibit(1)
FanLockStatus_44 BI Permit(0) Prohibit(1)
OccupancyCommand_44 BO Unoccupied(0) Occupied(1)
OccupancyStatus_44 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_44 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_44 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_44 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_44 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_44 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_44 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_44 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_44 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_44 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_44 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_44 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_44 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_44 BI Off(0) On(1)
AccumulatedGas(100 Watt)_44 AI Wattage values (Unit : 100Watt)
DustSensorAvail_44 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_44 BO Stop(0) Run(1)
AirCleaningOperStatus_44 BI Stop(0) Run(1)
FineDustStatus_44 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_44 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_44 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_44 AI %
ComfortCoolingAvail_44 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_44 BO Stop(0) Run(1)
ComfortCoolingOperStatus_44 BI Stop(0) Run(1)
ComfortCoolingStepCommand_44 AV 1~3 step
ComfortCoolingStepStatus_44 AI 1~3 step
HumanDetectionAvail_44 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_44 MO Off(1)
HumanDetectionOperStatus_44 MI Off(1)
HumanDetectionWindCommand_44 MO Off(1)
HumanDetectionWindStatus_44 MI Off(1)
HumanDetectionTimeCommand_44 MO 5min(1)
HumanDetectionTimeStatus_44 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
45 ※ Dev Type AC
address

instance
point Name
number

17665 1 On/Off (Setting)


17666 2 On/Off (Status)
17667 3 Lock (Setting)
17668 4 Lock (Status)
17669 5 Filter Sign
17670 6 Filter Sign reset
17671 7 Operation Mode (Setting)
17672 8 Operation Mode (Status)
17673 9 Swing (Setting)
17674 10 Swing (Status)
17675 11 Fan Speed (Setting)
17676 12 Fan Speed (Status)
17677 13 Set Room Temperature
17678 14 Room Temperature
17679 15 Alarm
17680 16 Error Code
17683 19 Set Temperature (Status)
17684 20 Accumulated Power Distribution (Status)
17691 27 Set Upper Temperature (Setting)
17692 28 Set Lower Temperature (Setting)
17693 29 Set Upper Tempaerature (Status)
17694 30 Set Lower Temperature (Status)
17695 31 Mode Lock (Setting)
17696 32 Mode Lock (Status)
17697 33 Fan Lock (Setting)
17698 34 Fan Lock (Status)
17699 35 Occupancy (Setting)
17700 36 Occupancy (Status)
17701 37 2Set Cooling Set Temperature (Setting)
17702 38 2Set Cooling Set Temperature (Status)
17703 39 2Set Heating Set Temperature (Setting)
17704 40 2Set Heating Set Temperature (Status)
17705 41 2Set Cooling Upper Temperature (Setting)
17706 42 2Set Cooling Upper Temperature (Status)
17707 43 2Set Heating Upper Temperature (Setting)
17708 44 2Set Heating Upper Temperature (Status)
17709 45 2Set Cooling Lower Temperature (Setting)
17710 46 2Set Cooling Lower Temperature (Status)
17711 47 2Set Heating Lower Temperature (Setting)
17712 48 2Set Heating Lower Temperature (Status)
17713 49 Thermo Status (Status)
17714 50 Accumulated Gas Distribution (Status)
17715 51 Dust Sensor Available (Status)
17716 52 Air Cleaning Opereration (Setting)
17717 53 Air Cleaning Opereration (Status)
17718 54 Fine Dust (Status)
17719 55 Ultra Fine Dust (Status)
17720 56 Super Ultra Fine Dust (Status)
17721 57 Humidity (Status)
17722 58 Comfort Cooling Available (Status)
17723 59 Comfort Cooling Opereration (Setting)
17724 60 Comfort Cooling Opereration (Status)
17725 61 Comfort Cooling Step (Setting)
17726 62 Comfort Cooling Step (Status)
17727 63 Human Detection Available (Status)
17728 64 Human Detection Opereration (Setting)
17729 65 Human Detection Opereration (Status)
17730 66 Human Detection Wind (Setting)
17731 67 Human Detection Wind (Status)
17732 68 Human Detection Time (Setting)
17733 69 Human Detection Time (Status)
17734 70 Hotel Checkin (Setting)
17735 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_45 BO Stop(0) Start(1)
StartStopStatus_45 BI Stop(0) Start(1)
LockCommand_45 BO Permit(0) Prohibit(1)
LockStatus_45 BI Permit(0) Prohibit(1)
FilterSign_45 BI Off(0) On(1)
FilterSignReset_45 BV - Reset(1)
AirConModeCommand_45 MO Cool(1)
AirConModeStatus_45 MI Cool(1)
SwingCommand_45 BO Stop(0) Run(1)
SwingStatus_45 BI Stop(0) Run(1)
FanSpeedCommand_45 MO Low(1)
FanSpeedStatus_45 MI Low(1)
SetRoomTemp_45 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_45 AI ℃
Alarm_45 BI Normal(0) Abnormal(1)
MalfunctionCode_45 AI Refer to the
SetTempStatus_45 AI ℃
Accumulated power(100 Watt)_45 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_45 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_45 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_45 AI ℃
TempRangeLowerLimitStatus_45 AI ℃
ModeLockCommand_45 BO Permit(0) Prohibit(1)
ModeLockStatus_45 BI Permit(0) Prohibit(1)
FanLockCommand_45 BO Permit(0) Prohibit(1)
FanLockStatus_45 BI Permit(0) Prohibit(1)
OccupancyCommand_45 BO Unoccupied(0) Occupied(1)
OccupancyStatus_45 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_45 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_45 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_45 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_45 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_45 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_45 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_45 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_45 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_45 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_45 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_45 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_45 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_45 BI Off(0) On(1)
AccumulatedGas(100 Watt)_45 AI Wattage values (Unit : 100Watt)
DustSensorAvail_45 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_45 BO Stop(0) Run(1)
AirCleaningOperStatus_45 BI Stop(0) Run(1)
FineDustStatus_45 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_45 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_45 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_45 AI %
ComfortCoolingAvail_45 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_45 BO Stop(0) Run(1)
ComfortCoolingOperStatus_45 BI Stop(0) Run(1)
ComfortCoolingStepCommand_45 AV 1~3 step
ComfortCoolingStepStatus_45 AI 1~3 step
HumanDetectionAvail_45 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_45 MO Off(1)
HumanDetectionOperStatus_45 MI Off(1)
HumanDetectionWindCommand_45 MO Off(1)
HumanDetectionWindStatus_45 MI Off(1)
HumanDetectionTimeCommand_45 MO 5min(1)
HumanDetectionTimeStatus_45 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
46 ※ Dev Type AC
address

instance
point Name
number

17921 1 On/Off (Setting)


17922 2 On/Off (Status)
17923 3 Lock (Setting)
17924 4 Lock (Status)
17925 5 Filter Sign
17926 6 Filter Sign reset
17927 7 Operation Mode (Setting)
17928 8 Operation Mode (Status)
17929 9 Swing (Setting)
17930 10 Swing (Status)
17931 11 Fan Speed (Setting)
17932 12 Fan Speed (Status)
17933 13 Set Room Temperature
17934 14 Room Temperature
17935 15 Alarm
17936 16 Error Code
17939 19 Set Temperature (Status)
17940 20 Accumulated Power Distribution (Status)
17947 27 Set Upper Temperature (Setting)
17948 28 Set Lower Temperature (Setting)
17949 29 Set Upper Tempaerature (Status)
17950 30 Set Lower Temperature (Status)
17951 31 Mode Lock (Setting)
17952 32 Mode Lock (Status)
17953 33 Fan Lock (Setting)
17954 34 Fan Lock (Status)
17955 35 Occupancy (Setting)
17956 36 Occupancy (Status)
17957 37 2Set Cooling Set Temperature (Setting)
17958 38 2Set Cooling Set Temperature (Status)
17959 39 2Set Heating Set Temperature (Setting)
17960 40 2Set Heating Set Temperature (Status)
17961 41 2Set Cooling Upper Temperature (Setting)
17962 42 2Set Cooling Upper Temperature (Status)
17963 43 2Set Heating Upper Temperature (Setting)
17964 44 2Set Heating Upper Temperature (Status)
17965 45 2Set Cooling Lower Temperature (Setting)
17966 46 2Set Cooling Lower Temperature (Status)
17967 47 2Set Heating Lower Temperature (Setting)
17968 48 2Set Heating Lower Temperature (Status)
17969 49 Thermo Status (Status)
17970 50 Accumulated Gas Distribution (Status)
17971 51 Dust Sensor Available (Status)
17972 52 Air Cleaning Opereration (Setting)
17973 53 Air Cleaning Opereration (Status)
17974 54 Fine Dust (Status)
17975 55 Ultra Fine Dust (Status)
17976 56 Super Ultra Fine Dust (Status)
17977 57 Humidity (Status)
17978 58 Comfort Cooling Available (Status)
17979 59 Comfort Cooling Opereration (Setting)
17980 60 Comfort Cooling Opereration (Status)
17981 61 Comfort Cooling Step (Setting)
17982 62 Comfort Cooling Step (Status)
17983 63 Human Detection Available (Status)
17984 64 Human Detection Opereration (Setting)
17985 65 Human Detection Opereration (Status)
17986 66 Human Detection Wind (Setting)
17987 67 Human Detection Wind (Status)
17988 68 Human Detection Time (Setting)
17989 69 Human Detection Time (Status)
17990 70 Hotel Checkin (Setting)
17991 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_46 BO Stop(0) Start(1)
StartStopStatus_46 BI Stop(0) Start(1)
LockCommand_46 BO Permit(0) Prohibit(1)
LockStatus_46 BI Permit(0) Prohibit(1)
FilterSign_46 BI Off(0) On(1)
FilterSignReset_46 BV - Reset(1)
AirConModeCommand_46 MO Cool(1)
AirConModeStatus_46 MI Cool(1)
SwingCommand_46 BO Stop(0) Run(1)
SwingStatus_46 BI Stop(0) Run(1)
FanSpeedCommand_46 MO Low(1)
FanSpeedStatus_46 MI Low(1)
SetRoomTemp_46 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_46 AI ℃
Alarm_46 BI Normal(0) Abnormal(1)
MalfunctionCode_46 AI Refer to the
SetTempStatus_46 AI ℃
Accumulated power(100 Watt)_46 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_46 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_46 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_46 AI ℃
TempRangeLowerLimitStatus_46 AI ℃
ModeLockCommand_46 BO Permit(0) Prohibit(1)
ModeLockStatus_46 BI Permit(0) Prohibit(1)
FanLockCommand_46 BO Permit(0) Prohibit(1)
FanLockStatus_46 BI Permit(0) Prohibit(1)
OccupancyCommand_46 BO Unoccupied(0) Occupied(1)
OccupancyStatus_46 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_46 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_46 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_46 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_46 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_46 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_46 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_46 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_46 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_46 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_46 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_46 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_46 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_46 BI Off(0) On(1)
AccumulatedGas(100 Watt)_46 AI Wattage values (Unit : 100Watt)
DustSensorAvail_46 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_46 BO Stop(0) Run(1)
AirCleaningOperStatus_46 BI Stop(0) Run(1)
FineDustStatus_46 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_46 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_46 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_46 AI %
ComfortCoolingAvail_46 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_46 BO Stop(0) Run(1)
ComfortCoolingOperStatus_46 BI Stop(0) Run(1)
ComfortCoolingStepCommand_46 AV 1~3 step
ComfortCoolingStepStatus_46 AI 1~3 step
HumanDetectionAvail_46 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_46 MO Off(1)
HumanDetectionOperStatus_46 MI Off(1)
HumanDetectionWindCommand_46 MO Off(1)
HumanDetectionWindStatus_46 MI Off(1)
HumanDetectionTimeCommand_46 MO 5min(1)
HumanDetectionTimeStatus_46 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
47 ※ Dev Type AC
address

instance
point Name
number

18177 1 On/Off (Setting)


18178 2 On/Off (Status)
18179 3 Lock (Setting)
18180 4 Lock (Status)
18181 5 Filter Sign
18182 6 Filter Sign reset
18183 7 Operation Mode (Setting)
18184 8 Operation Mode (Status)
18185 9 Swing (Setting)
18186 10 Swing (Status)
18187 11 Fan Speed (Setting)
18188 12 Fan Speed (Status)
18189 13 Set Room Temperature
18190 14 Room Temperature
18191 15 Alarm
18192 16 Error Code
18195 19 Set Temperature (Status)
18196 20 Accumulated Power Distribution (Status)
18203 27 Set Upper Temperature (Setting)
18204 28 Set Lower Temperature (Setting)
18205 29 Set Upper Tempaerature (Status)
18206 30 Set Lower Temperature (Status)
18207 31 Mode Lock (Setting)
18208 32 Mode Lock (Status)
18209 33 Fan Lock (Setting)
18210 34 Fan Lock (Status)
18211 35 Occupancy (Setting)
18212 36 Occupancy (Status)
18213 37 2Set Cooling Set Temperature (Setting)
18214 38 2Set Cooling Set Temperature (Status)
18215 39 2Set Heating Set Temperature (Setting)
18216 40 2Set Heating Set Temperature (Status)
18217 41 2Set Cooling Upper Temperature (Setting)
18218 42 2Set Cooling Upper Temperature (Status)
18219 43 2Set Heating Upper Temperature (Setting)
18220 44 2Set Heating Upper Temperature (Status)
18221 45 2Set Cooling Lower Temperature (Setting)
18222 46 2Set Cooling Lower Temperature (Status)
18223 47 2Set Heating Lower Temperature (Setting)
18224 48 2Set Heating Lower Temperature (Status)
18225 49 Thermo Status (Status)
18226 50 Accumulated Gas Distribution (Status)
18227 51 Dust Sensor Available (Status)
18228 52 Air Cleaning Opereration (Setting)
18229 53 Air Cleaning Opereration (Status)
18230 54 Fine Dust (Status)
18231 55 Ultra Fine Dust (Status)
18232 56 Super Ultra Fine Dust (Status)
18233 57 Humidity (Status)
18234 58 Comfort Cooling Available (Status)
18235 59 Comfort Cooling Opereration (Setting)
18236 60 Comfort Cooling Opereration (Status)
18237 61 Comfort Cooling Step (Setting)
18238 62 Comfort Cooling Step (Status)
18239 63 Human Detection Available (Status)
18240 64 Human Detection Opereration (Setting)
18241 65 Human Detection Opereration (Status)
18242 66 Human Detection Wind (Setting)
18243 67 Human Detection Wind (Status)
18244 68 Human Detection Time (Setting)
18245 69 Human Detection Time (Status)
18246 70 Hotel Checkin (Setting)
18247 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_47 BO Stop(0) Start(1)
StartStopStatus_47 BI Stop(0) Start(1)
LockCommand_47 BO Permit(0) Prohibit(1)
LockStatus_47 BI Permit(0) Prohibit(1)
FilterSign_47 BI Off(0) On(1)
FilterSignReset_47 BV - Reset(1)
AirConModeCommand_47 MO Cool(1)
AirConModeStatus_47 MI Cool(1)
SwingCommand_47 BO Stop(0) Run(1)
SwingStatus_47 BI Stop(0) Run(1)
FanSpeedCommand_47 MO Low(1)
FanSpeedStatus_47 MI Low(1)
SetRoomTemp_47 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_47 AI ℃
Alarm_47 BI Normal(0) Abnormal(1)
MalfunctionCode_47 AI Refer to the
SetTempStatus_47 AI ℃
Accumulated power(100 Watt)_47 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_47 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_47 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_47 AI ℃
TempRangeLowerLimitStatus_47 AI ℃
ModeLockCommand_47 BO Permit(0) Prohibit(1)
ModeLockStatus_47 BI Permit(0) Prohibit(1)
FanLockCommand_47 BO Permit(0) Prohibit(1)
FanLockStatus_47 BI Permit(0) Prohibit(1)
OccupancyCommand_47 BO Unoccupied(0) Occupied(1)
OccupancyStatus_47 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_47 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_47 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_47 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_47 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_47 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_47 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_47 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_47 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_47 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_47 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_47 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_47 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_47 BI Off(0) On(1)
AccumulatedGas(100 Watt)_47 AI Wattage values (Unit : 100Watt)
DustSensorAvail_47 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_47 BO Stop(0) Run(1)
AirCleaningOperStatus_47 BI Stop(0) Run(1)
FineDustStatus_47 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_47 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_47 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_47 AI %
ComfortCoolingAvail_47 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_47 BO Stop(0) Run(1)
ComfortCoolingOperStatus_47 BI Stop(0) Run(1)
ComfortCoolingStepCommand_47 AV 1~3 step
ComfortCoolingStepStatus_47 AI 1~3 step
HumanDetectionAvail_47 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_47 MO Off(1)
HumanDetectionOperStatus_47 MI Off(1)
HumanDetectionWindCommand_47 MO Off(1)
HumanDetectionWindStatus_47 MI Off(1)
HumanDetectionTimeCommand_47 MO 5min(1)
HumanDetectionTimeStatus_47 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
48 ※ Dev Type AC
address

instance
point Name
number

18433 1 On/Off (Setting)


18434 2 On/Off (Status)
18435 3 Lock (Setting)
18436 4 Lock (Status)
18437 5 Filter Sign
18438 6 Filter Sign reset
18439 7 Operation Mode (Setting)
18440 8 Operation Mode (Status)
18441 9 Swing (Setting)
18442 10 Swing (Status)
18443 11 Fan Speed (Setting)
18444 12 Fan Speed (Status)
18445 13 Set Room Temperature
18446 14 Room Temperature
18447 15 Alarm
18448 16 Error Code
18451 19 Set Temperature (Status)
18452 20 Accumulated Power Distribution (Status)
18459 27 Set Upper Temperature (Setting)
18460 28 Set Lower Temperature (Setting)
18461 29 Set Upper Tempaerature (Status)
18462 30 Set Lower Temperature (Status)
18463 31 Mode Lock (Setting)
18464 32 Mode Lock (Status)
18465 33 Fan Lock (Setting)
18466 34 Fan Lock (Status)
18467 35 Occupancy (Setting)
18468 36 Occupancy (Status)
18469 37 2Set Cooling Set Temperature (Setting)
18470 38 2Set Cooling Set Temperature (Status)
18471 39 2Set Heating Set Temperature (Setting)
18472 40 2Set Heating Set Temperature (Status)
18473 41 2Set Cooling Upper Temperature (Setting)
18474 42 2Set Cooling Upper Temperature (Status)
18475 43 2Set Heating Upper Temperature (Setting)
18476 44 2Set Heating Upper Temperature (Status)
18477 45 2Set Cooling Lower Temperature (Setting)
18478 46 2Set Cooling Lower Temperature (Status)
18479 47 2Set Heating Lower Temperature (Setting)
18480 48 2Set Heating Lower Temperature (Status)
18481 49 Thermo Status (Status)
18482 50 Accumulated Gas Distribution (Status)
18483 51 Dust Sensor Available (Status)
18484 52 Air Cleaning Opereration (Setting)
18485 53 Air Cleaning Opereration (Status)
18486 54 Fine Dust (Status)
18487 55 Ultra Fine Dust (Status)
18488 56 Super Ultra Fine Dust (Status)
18489 57 Humidity (Status)
18490 58 Comfort Cooling Available (Status)
18491 59 Comfort Cooling Opereration (Setting)
18492 60 Comfort Cooling Opereration (Status)
18493 61 Comfort Cooling Step (Setting)
18494 62 Comfort Cooling Step (Status)
18495 63 Human Detection Available (Status)
18496 64 Human Detection Opereration (Setting)
18497 65 Human Detection Opereration (Status)
18498 66 Human Detection Wind (Setting)
18499 67 Human Detection Wind (Status)
18500 68 Human Detection Time (Setting)
18501 69 Human Detection Time (Status)
18502 70 Hotel Checkin (Setting)
18503 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_48 BO Stop(0) Start(1)
StartStopStatus_48 BI Stop(0) Start(1)
LockCommand_48 BO Permit(0) Prohibit(1)
LockStatus_48 BI Permit(0) Prohibit(1)
FilterSign_48 BI Off(0) On(1)
FilterSignReset_48 BV - Reset(1)
AirConModeCommand_48 MO Cool(1)
AirConModeStatus_48 MI Cool(1)
SwingCommand_48 BO Stop(0) Run(1)
SwingStatus_48 BI Stop(0) Run(1)
FanSpeedCommand_48 MO Low(1)
FanSpeedStatus_48 MI Low(1)
SetRoomTemp_48 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_48 AI ℃
Alarm_48 BI Normal(0) Abnormal(1)
MalfunctionCode_48 AI Refer to the
SetTempStatus_48 AI ℃
Accumulated power(100 Watt)_48 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_48 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_48 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_48 AI ℃
TempRangeLowerLimitStatus_48 AI ℃
ModeLockCommand_48 BO Permit(0) Prohibit(1)
ModeLockStatus_48 BI Permit(0) Prohibit(1)
FanLockCommand_48 BO Permit(0) Prohibit(1)
FanLockStatus_48 BI Permit(0) Prohibit(1)
OccupancyCommand_48 BO Unoccupied(0) Occupied(1)
OccupancyStatus_48 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_48 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_48 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_48 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_48 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_48 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_48 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_48 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_48 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_48 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_48 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_48 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_48 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_48 BI Off(0) On(1)
AccumulatedGas(100 Watt)_48 AI Wattage values (Unit : 100Watt)
DustSensorAvail_48 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_48 BO Stop(0) Run(1)
AirCleaningOperStatus_48 BI Stop(0) Run(1)
FineDustStatus_48 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_48 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_48 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_48 AI %
ComfortCoolingAvail_48 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_48 BO Stop(0) Run(1)
ComfortCoolingOperStatus_48 BI Stop(0) Run(1)
ComfortCoolingStepCommand_48 AV 1~3 step
ComfortCoolingStepStatus_48 AI 1~3 step
HumanDetectionAvail_48 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_48 MO Off(1)
HumanDetectionOperStatus_48 MI Off(1)
HumanDetectionWindCommand_48 MO Off(1)
HumanDetectionWindStatus_48 MI Off(1)
HumanDetectionTimeCommand_48 MO 5min(1)
HumanDetectionTimeStatus_48 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
49 ※ Dev Type AC
address

instance
point Name
number

18689 1 On/Off (Setting)


18690 2 On/Off (Status)
18691 3 Lock (Setting)
18692 4 Lock (Status)
18693 5 Filter Sign
18694 6 Filter Sign reset
18695 7 Operation Mode (Setting)
18696 8 Operation Mode (Status)
18697 9 Swing (Setting)
18698 10 Swing (Status)
18699 11 Fan Speed (Setting)
18700 12 Fan Speed (Status)
18701 13 Set Room Temperature
18702 14 Room Temperature
18703 15 Alarm
18704 16 Error Code
18707 19 Set Temperature (Status)
18708 20 Accumulated Power Distribution (Status)
18715 27 Set Upper Temperature (Setting)
18716 28 Set Lower Temperature (Setting)
18717 29 Set Upper Tempaerature (Status)
18718 30 Set Lower Temperature (Status)
18719 31 Mode Lock (Setting)
18720 32 Mode Lock (Status)
18721 33 Fan Lock (Setting)
18722 34 Fan Lock (Status)
18723 35 Occupancy (Setting)
18724 36 Occupancy (Status)
18725 37 2Set Cooling Set Temperature (Setting)
18726 38 2Set Cooling Set Temperature (Status)
18727 39 2Set Heating Set Temperature (Setting)
18728 40 2Set Heating Set Temperature (Status)
18729 41 2Set Cooling Upper Temperature (Setting)
18730 42 2Set Cooling Upper Temperature (Status)
18731 43 2Set Heating Upper Temperature (Setting)
18732 44 2Set Heating Upper Temperature (Status)
18733 45 2Set Cooling Lower Temperature (Setting)
18734 46 2Set Cooling Lower Temperature (Status)
18735 47 2Set Heating Lower Temperature (Setting)
18736 48 2Set Heating Lower Temperature (Status)
18737 49 Thermo Status (Status)
18738 50 Accumulated Gas Distribution (Status)
18739 51 Dust Sensor Available (Status)
18740 52 Air Cleaning Opereration (Setting)
18741 53 Air Cleaning Opereration (Status)
18742 54 Fine Dust (Status)
18743 55 Ultra Fine Dust (Status)
18744 56 Super Ultra Fine Dust (Status)
18745 57 Humidity (Status)
18746 58 Comfort Cooling Available (Status)
18747 59 Comfort Cooling Opereration (Setting)
18748 60 Comfort Cooling Opereration (Status)
18749 61 Comfort Cooling Step (Setting)
18750 62 Comfort Cooling Step (Status)
18751 63 Human Detection Available (Status)
18752 64 Human Detection Opereration (Setting)
18753 65 Human Detection Opereration (Status)
18754 66 Human Detection Wind (Setting)
18755 67 Human Detection Wind (Status)
18756 68 Human Detection Time (Setting)
18757 69 Human Detection Time (Status)
18758 70 Hotel Checkin (Setting)
18759 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_49 BO Stop(0) Start(1)
StartStopStatus_49 BI Stop(0) Start(1)
LockCommand_49 BO Permit(0) Prohibit(1)
LockStatus_49 BI Permit(0) Prohibit(1)
FilterSign_49 BI Off(0) On(1)
FilterSignReset_49 BV - Reset(1)
AirConModeCommand_49 MO Cool(1)
AirConModeStatus_49 MI Cool(1)
SwingCommand_49 BO Stop(0) Run(1)
SwingStatus_49 BI Stop(0) Run(1)
FanSpeedCommand_49 MO Low(1)
FanSpeedStatus_49 MI Low(1)
SetRoomTemp_49 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_49 AI ℃
Alarm_49 BI Normal(0) Abnormal(1)
MalfunctionCode_49 AI Refer to the
SetTempStatus_49 AI ℃
Accumulated power(100 Watt)_49 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_49 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_49 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_49 AI ℃
TempRangeLowerLimitStatus_49 AI ℃
ModeLockCommand_49 BO Permit(0) Prohibit(1)
ModeLockStatus_49 BI Permit(0) Prohibit(1)
FanLockCommand_49 BO Permit(0) Prohibit(1)
FanLockStatus_49 BI Permit(0) Prohibit(1)
OccupancyCommand_49 BO Unoccupied(0) Occupied(1)
OccupancyStatus_49 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_49 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_49 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_49 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_49 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_49 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_49 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_49 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_49 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_49 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_49 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_49 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_49 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_49 BI Off(0) On(1)
AccumulatedGas(100 Watt)_49 AI Wattage values (Unit : 100Watt)
DustSensorAvail_49 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_49 BO Stop(0) Run(1)
AirCleaningOperStatus_49 BI Stop(0) Run(1)
FineDustStatus_49 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_49 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_49 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_49 AI %
ComfortCoolingAvail_49 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_49 BO Stop(0) Run(1)
ComfortCoolingOperStatus_49 BI Stop(0) Run(1)
ComfortCoolingStepCommand_49 AV 1~3 step
ComfortCoolingStepStatus_49 AI 1~3 step
HumanDetectionAvail_49 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_49 MO Off(1)
HumanDetectionOperStatus_49 MI Off(1)
HumanDetectionWindCommand_49 MO Off(1)
HumanDetectionWindStatus_49 MI Off(1)
HumanDetectionTimeCommand_49 MO 5min(1)
HumanDetectionTimeStatus_49 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4a ※ Dev Type AC
address

instance
point Name
number

18945 1 On/Off (Setting)


18946 2 On/Off (Status)
18947 3 Lock (Setting)
18948 4 Lock (Status)
18949 5 Filter Sign
18950 6 Filter Sign reset
18951 7 Operation Mode (Setting)
18952 8 Operation Mode (Status)
18953 9 Swing (Setting)
18954 10 Swing (Status)
18955 11 Fan Speed (Setting)
18956 12 Fan Speed (Status)
18957 13 Set Room Temperature
18958 14 Room Temperature
18959 15 Alarm
18960 16 Error Code
18963 19 Set Temperature (Status)
18964 20 Accumulated Power Distribution (Status)
18971 27 Set Upper Temperature (Setting)
18972 28 Set Lower Temperature (Setting)
18973 29 Set Upper Tempaerature (Status)
18974 30 Set Lower Temperature (Status)
18975 31 Mode Lock (Setting)
18976 32 Mode Lock (Status)
18977 33 Fan Lock (Setting)
18978 34 Fan Lock (Status)
18979 35 Occupancy (Setting)
18980 36 Occupancy (Status)
18981 37 2Set Cooling Set Temperature (Setting)
18982 38 2Set Cooling Set Temperature (Status)
18983 39 2Set Heating Set Temperature (Setting)
18984 40 2Set Heating Set Temperature (Status)
18985 41 2Set Cooling Upper Temperature (Setting)
18986 42 2Set Cooling Upper Temperature (Status)
18987 43 2Set Heating Upper Temperature (Setting)
18988 44 2Set Heating Upper Temperature (Status)
18989 45 2Set Cooling Lower Temperature (Setting)
18990 46 2Set Cooling Lower Temperature (Status)
18991 47 2Set Heating Lower Temperature (Setting)
18992 48 2Set Heating Lower Temperature (Status)
18993 49 Thermo Status (Status)
18994 50 Accumulated Gas Distribution (Status)
18995 51 Dust Sensor Available (Status)
18996 52 Air Cleaning Opereration (Setting)
18997 53 Air Cleaning Opereration (Status)
18998 54 Fine Dust (Status)
18999 55 Ultra Fine Dust (Status)
19000 56 Super Ultra Fine Dust (Status)
19001 57 Humidity (Status)
19002 58 Comfort Cooling Available (Status)
19003 59 Comfort Cooling Opereration (Setting)
19004 60 Comfort Cooling Opereration (Status)
19005 61 Comfort Cooling Step (Setting)
19006 62 Comfort Cooling Step (Status)
19007 63 Human Detection Available (Status)
19008 64 Human Detection Opereration (Setting)
19009 65 Human Detection Opereration (Status)
19010 66 Human Detection Wind (Setting)
19011 67 Human Detection Wind (Status)
19012 68 Human Detection Time (Setting)
19013 69 Human Detection Time (Status)
19014 70 Hotel Checkin (Setting)
19015 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4a BO Stop(0) Start(1)
StartStopStatus_4a BI Stop(0) Start(1)
LockCommand_4a BO Permit(0) Prohibit(1)
LockStatus_4a BI Permit(0) Prohibit(1)
FilterSign_4a BI Off(0) On(1)
FilterSignReset_4a BV - Reset(1)
AirConModeCommand_4a MO Cool(1)
AirConModeStatus_4a MI Cool(1)
SwingCommand_4a BO Stop(0) Run(1)
SwingStatus_4a BI Stop(0) Run(1)
FanSpeedCommand_4a MO Low(1)
FanSpeedStatus_4a MI Low(1)
SetRoomTemp_4a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4a AI ℃
Alarm_4a BI Normal(0) Abnormal(1)
MalfunctionCode_4a AI Refer to the
SetTempStatus_4a AI ℃
Accumulated power(100 Watt)_4a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4a AI ℃
TempRangeLowerLimitStatus_4a AI ℃
ModeLockCommand_4a BO Permit(0) Prohibit(1)
ModeLockStatus_4a BI Permit(0) Prohibit(1)
FanLockCommand_4a BO Permit(0) Prohibit(1)
FanLockStatus_4a BI Permit(0) Prohibit(1)
OccupancyCommand_4a BO Unoccupied(0) Occupied(1)
OccupancyStatus_4a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4a BI Off(0) On(1)
AccumulatedGas(100 Watt)_4a AI Wattage values (Unit : 100Watt)
DustSensorAvail_4a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4a BO Stop(0) Run(1)
AirCleaningOperStatus_4a BI Stop(0) Run(1)
FineDustStatus_4a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4a AI %
ComfortCoolingAvail_4a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4a BO Stop(0) Run(1)
ComfortCoolingOperStatus_4a BI Stop(0) Run(1)
ComfortCoolingStepCommand_4a AV 1~3 step
ComfortCoolingStepStatus_4a AI 1~3 step
HumanDetectionAvail_4a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4a MO Off(1)
HumanDetectionOperStatus_4a MI Off(1)
HumanDetectionWindCommand_4a MO Off(1)
HumanDetectionWindStatus_4a MI Off(1)
HumanDetectionTimeCommand_4a MO 5min(1)
HumanDetectionTimeStatus_4a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4b ※ Dev Type AC
address

instance
point Name
number

19201 1 On/Off (Setting)


19202 2 On/Off (Status)
19203 3 Lock (Setting)
19204 4 Lock (Status)
19205 5 Filter Sign
19206 6 Filter Sign reset
19207 7 Operation Mode (Setting)
19208 8 Operation Mode (Status)
19209 9 Swing (Setting)
19210 10 Swing (Status)
19211 11 Fan Speed (Setting)
19212 12 Fan Speed (Status)
19213 13 Set Room Temperature
19214 14 Room Temperature
19215 15 Alarm
19216 16 Error Code
19219 19 Set Temperature (Status)
19220 20 Accumulated Power Distribution (Status)
19227 27 Set Upper Temperature (Setting)
19228 28 Set Lower Temperature (Setting)
19229 29 Set Upper Tempaerature (Status)
19230 30 Set Lower Temperature (Status)
19231 31 Mode Lock (Setting)
19232 32 Mode Lock (Status)
19233 33 Fan Lock (Setting)
19234 34 Fan Lock (Status)
19235 35 Occupancy (Setting)
19236 36 Occupancy (Status)
19237 37 2Set Cooling Set Temperature (Setting)
19238 38 2Set Cooling Set Temperature (Status)
19239 39 2Set Heating Set Temperature (Setting)
19240 40 2Set Heating Set Temperature (Status)
19241 41 2Set Cooling Upper Temperature (Setting)
19242 42 2Set Cooling Upper Temperature (Status)
19243 43 2Set Heating Upper Temperature (Setting)
19244 44 2Set Heating Upper Temperature (Status)
19245 45 2Set Cooling Lower Temperature (Setting)
19246 46 2Set Cooling Lower Temperature (Status)
19247 47 2Set Heating Lower Temperature (Setting)
19248 48 2Set Heating Lower Temperature (Status)
19249 49 Thermo Status (Status)
19250 50 Accumulated Gas Distribution (Status)
19251 51 Dust Sensor Available (Status)
19252 52 Air Cleaning Opereration (Setting)
19253 53 Air Cleaning Opereration (Status)
19254 54 Fine Dust (Status)
19255 55 Ultra Fine Dust (Status)
19256 56 Super Ultra Fine Dust (Status)
19257 57 Humidity (Status)
19258 58 Comfort Cooling Available (Status)
19259 59 Comfort Cooling Opereration (Setting)
19260 60 Comfort Cooling Opereration (Status)
19261 61 Comfort Cooling Step (Setting)
19262 62 Comfort Cooling Step (Status)
19263 63 Human Detection Available (Status)
19264 64 Human Detection Opereration (Setting)
19265 65 Human Detection Opereration (Status)
19266 66 Human Detection Wind (Setting)
19267 67 Human Detection Wind (Status)
19268 68 Human Detection Time (Setting)
19269 69 Human Detection Time (Status)
19270 70 Hotel Checkin (Setting)
19271 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4b BO Stop(0) Start(1)
StartStopStatus_4b BI Stop(0) Start(1)
LockCommand_4b BO Permit(0) Prohibit(1)
LockStatus_4b BI Permit(0) Prohibit(1)
FilterSign_4b BI Off(0) On(1)
FilterSignReset_4b BV - Reset(1)
AirConModeCommand_4b MO Cool(1)
AirConModeStatus_4b MI Cool(1)
SwingCommand_4b BO Stop(0) Run(1)
SwingStatus_4b BI Stop(0) Run(1)
FanSpeedCommand_4b MO Low(1)
FanSpeedStatus_4b MI Low(1)
SetRoomTemp_4b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4b AI ℃
Alarm_4b BI Normal(0) Abnormal(1)
MalfunctionCode_4b AI Refer to the
SetTempStatus_4b AI ℃
Accumulated power(100 Watt)_4b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4b AI ℃
TempRangeLowerLimitStatus_4b AI ℃
ModeLockCommand_4b BO Permit(0) Prohibit(1)
ModeLockStatus_4b BI Permit(0) Prohibit(1)
FanLockCommand_4b BO Permit(0) Prohibit(1)
FanLockStatus_4b BI Permit(0) Prohibit(1)
OccupancyCommand_4b BO Unoccupied(0) Occupied(1)
OccupancyStatus_4b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4b BI Off(0) On(1)
AccumulatedGas(100 Watt)_4b AI Wattage values (Unit : 100Watt)
DustSensorAvail_4b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4b BO Stop(0) Run(1)
AirCleaningOperStatus_4b BI Stop(0) Run(1)
FineDustStatus_4b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4b AI %
ComfortCoolingAvail_4b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4b BO Stop(0) Run(1)
ComfortCoolingOperStatus_4b BI Stop(0) Run(1)
ComfortCoolingStepCommand_4b AV 1~3 step
ComfortCoolingStepStatus_4b AI 1~3 step
HumanDetectionAvail_4b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4b MO Off(1)
HumanDetectionOperStatus_4b MI Off(1)
HumanDetectionWindCommand_4b MO Off(1)
HumanDetectionWindStatus_4b MI Off(1)
HumanDetectionTimeCommand_4b MO 5min(1)
HumanDetectionTimeStatus_4b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4c ※ Dev Type AC
address

instance
point Name
number

19457 1 On/Off (Setting)


19458 2 On/Off (Status)
19459 3 Lock (Setting)
19460 4 Lock (Status)
19461 5 Filter Sign
19462 6 Filter Sign reset
19463 7 Operation Mode (Setting)
19464 8 Operation Mode (Status)
19465 9 Swing (Setting)
19466 10 Swing (Status)
19467 11 Fan Speed (Setting)
19468 12 Fan Speed (Status)
19469 13 Set Room Temperature
19470 14 Room Temperature
19471 15 Alarm
19472 16 Error Code
19475 19 Set Temperature (Status)
19476 20 Accumulated Power Distribution (Status)
19483 27 Set Upper Temperature (Setting)
19484 28 Set Lower Temperature (Setting)
19485 29 Set Upper Tempaerature (Status)
19486 30 Set Lower Temperature (Status)
19487 31 Mode Lock (Setting)
19488 32 Mode Lock (Status)
19489 33 Fan Lock (Setting)
19490 34 Fan Lock (Status)
19491 35 Occupancy (Setting)
19492 36 Occupancy (Status)
19493 37 2Set Cooling Set Temperature (Setting)
19494 38 2Set Cooling Set Temperature (Status)
19495 39 2Set Heating Set Temperature (Setting)
19496 40 2Set Heating Set Temperature (Status)
19497 41 2Set Cooling Upper Temperature (Setting)
19498 42 2Set Cooling Upper Temperature (Status)
19499 43 2Set Heating Upper Temperature (Setting)
19500 44 2Set Heating Upper Temperature (Status)
19501 45 2Set Cooling Lower Temperature (Setting)
19502 46 2Set Cooling Lower Temperature (Status)
19503 47 2Set Heating Lower Temperature (Setting)
19504 48 2Set Heating Lower Temperature (Status)
19505 49 Thermo Status (Status)
19506 50 Accumulated Gas Distribution (Status)
19507 51 Dust Sensor Available (Status)
19508 52 Air Cleaning Opereration (Setting)
19509 53 Air Cleaning Opereration (Status)
19510 54 Fine Dust (Status)
19511 55 Ultra Fine Dust (Status)
19512 56 Super Ultra Fine Dust (Status)
19513 57 Humidity (Status)
19514 58 Comfort Cooling Available (Status)
19515 59 Comfort Cooling Opereration (Setting)
19516 60 Comfort Cooling Opereration (Status)
19517 61 Comfort Cooling Step (Setting)
19518 62 Comfort Cooling Step (Status)
19519 63 Human Detection Available (Status)
19520 64 Human Detection Opereration (Setting)
19521 65 Human Detection Opereration (Status)
19522 66 Human Detection Wind (Setting)
19523 67 Human Detection Wind (Status)
19524 68 Human Detection Time (Setting)
19525 69 Human Detection Time (Status)
19526 70 Hotel Checkin (Setting)
19527 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4c BO Stop(0) Start(1)
StartStopStatus_4c BI Stop(0) Start(1)
LockCommand_4c BO Permit(0) Prohibit(1)
LockStatus_4c BI Permit(0) Prohibit(1)
FilterSign_4c BI Off(0) On(1)
FilterSignReset_4c BV - Reset(1)
AirConModeCommand_4c MO Cool(1)
AirConModeStatus_4c MI Cool(1)
SwingCommand_4c BO Stop(0) Run(1)
SwingStatus_4c BI Stop(0) Run(1)
FanSpeedCommand_4c MO Low(1)
FanSpeedStatus_4c MI Low(1)
SetRoomTemp_4c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4c AI ℃
Alarm_4c BI Normal(0) Abnormal(1)
MalfunctionCode_4c AI Refer to the
SetTempStatus_4c AI ℃
Accumulated power(100 Watt)_4c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4c AI ℃
TempRangeLowerLimitStatus_4c AI ℃
ModeLockCommand_4c BO Permit(0) Prohibit(1)
ModeLockStatus_4c BI Permit(0) Prohibit(1)
FanLockCommand_4c BO Permit(0) Prohibit(1)
FanLockStatus_4c BI Permit(0) Prohibit(1)
OccupancyCommand_4c BO Unoccupied(0) Occupied(1)
OccupancyStatus_4c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4c BI Off(0) On(1)
AccumulatedGas(100 Watt)_4c AI Wattage values (Unit : 100Watt)
DustSensorAvail_4c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4c BO Stop(0) Run(1)
AirCleaningOperStatus_4c BI Stop(0) Run(1)
FineDustStatus_4c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4c AI %
ComfortCoolingAvail_4c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4c BO Stop(0) Run(1)
ComfortCoolingOperStatus_4c BI Stop(0) Run(1)
ComfortCoolingStepCommand_4c AV 1~3 step
ComfortCoolingStepStatus_4c AI 1~3 step
HumanDetectionAvail_4c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4c MO Off(1)
HumanDetectionOperStatus_4c MI Off(1)
HumanDetectionWindCommand_4c MO Off(1)
HumanDetectionWindStatus_4c MI Off(1)
HumanDetectionTimeCommand_4c MO 5min(1)
HumanDetectionTimeStatus_4c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4d ※ Dev Type AC
address

instance
point Name
number

19713 1 On/Off (Setting)


19714 2 On/Off (Status)
19715 3 Lock (Setting)
19716 4 Lock (Status)
19717 5 Filter Sign
19718 6 Filter Sign reset
19719 7 Operation Mode (Setting)
19720 8 Operation Mode (Status)
19721 9 Swing (Setting)
19722 10 Swing (Status)
19723 11 Fan Speed (Setting)
19724 12 Fan Speed (Status)
19725 13 Set Room Temperature
19726 14 Room Temperature
19727 15 Alarm
19728 16 Error Code
19731 19 Set Temperature (Status)
19732 20 Accumulated Power Distribution (Status)
19739 27 Set Upper Temperature (Setting)
19740 28 Set Lower Temperature (Setting)
19741 29 Set Upper Tempaerature (Status)
19742 30 Set Lower Temperature (Status)
19743 31 Mode Lock (Setting)
19744 32 Mode Lock (Status)
19745 33 Fan Lock (Setting)
19746 34 Fan Lock (Status)
19747 35 Occupancy (Setting)
19748 36 Occupancy (Status)
19749 37 2Set Cooling Set Temperature (Setting)
19750 38 2Set Cooling Set Temperature (Status)
19751 39 2Set Heating Set Temperature (Setting)
19752 40 2Set Heating Set Temperature (Status)
19753 41 2Set Cooling Upper Temperature (Setting)
19754 42 2Set Cooling Upper Temperature (Status)
19755 43 2Set Heating Upper Temperature (Setting)
19756 44 2Set Heating Upper Temperature (Status)
19757 45 2Set Cooling Lower Temperature (Setting)
19758 46 2Set Cooling Lower Temperature (Status)
19759 47 2Set Heating Lower Temperature (Setting)
19760 48 2Set Heating Lower Temperature (Status)
19761 49 Thermo Status (Status)
19762 50 Accumulated Gas Distribution (Status)
19763 51 Dust Sensor Available (Status)
19764 52 Air Cleaning Opereration (Setting)
19765 53 Air Cleaning Opereration (Status)
19766 54 Fine Dust (Status)
19767 55 Ultra Fine Dust (Status)
19768 56 Super Ultra Fine Dust (Status)
19769 57 Humidity (Status)
19770 58 Comfort Cooling Available (Status)
19771 59 Comfort Cooling Opereration (Setting)
19772 60 Comfort Cooling Opereration (Status)
19773 61 Comfort Cooling Step (Setting)
19774 62 Comfort Cooling Step (Status)
19775 63 Human Detection Available (Status)
19776 64 Human Detection Opereration (Setting)
19777 65 Human Detection Opereration (Status)
19778 66 Human Detection Wind (Setting)
19779 67 Human Detection Wind (Status)
19780 68 Human Detection Time (Setting)
19781 69 Human Detection Time (Status)
19782 70 Hotel Checkin (Setting)
19783 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4d BO Stop(0) Start(1)
StartStopStatus_4d BI Stop(0) Start(1)
LockCommand_4d BO Permit(0) Prohibit(1)
LockStatus_4d BI Permit(0) Prohibit(1)
FilterSign_4d BI Off(0) On(1)
FilterSignReset_4d BV - Reset(1)
AirConModeCommand_4d MO Cool(1)
AirConModeStatus_4d MI Cool(1)
SwingCommand_4d BO Stop(0) Run(1)
SwingStatus_4d BI Stop(0) Run(1)
FanSpeedCommand_4d MO Low(1)
FanSpeedStatus_4d MI Low(1)
SetRoomTemp_4d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4d AI ℃
Alarm_4d BI Normal(0) Abnormal(1)
MalfunctionCode_4d AI Refer to the
SetTempStatus_4d AI ℃
Accumulated power(100 Watt)_4d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4d AI ℃
TempRangeLowerLimitStatus_4d AI ℃
ModeLockCommand_4d BO Permit(0) Prohibit(1)
ModeLockStatus_4d BI Permit(0) Prohibit(1)
FanLockCommand_4d BO Permit(0) Prohibit(1)
FanLockStatus_4d BI Permit(0) Prohibit(1)
OccupancyCommand_4d BO Unoccupied(0) Occupied(1)
OccupancyStatus_4d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4d BI Off(0) On(1)
AccumulatedGas(100 Watt)_4d AI Wattage values (Unit : 100Watt)
DustSensorAvail_4d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4d BO Stop(0) Run(1)
AirCleaningOperStatus_4d BI Stop(0) Run(1)
FineDustStatus_4d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4d AI %
ComfortCoolingAvail_4d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4d BO Stop(0) Run(1)
ComfortCoolingOperStatus_4d BI Stop(0) Run(1)
ComfortCoolingStepCommand_4d AV 1~3 step
ComfortCoolingStepStatus_4d AI 1~3 step
HumanDetectionAvail_4d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4d MO Off(1)
HumanDetectionOperStatus_4d MI Off(1)
HumanDetectionWindCommand_4d MO Off(1)
HumanDetectionWindStatus_4d MI Off(1)
HumanDetectionTimeCommand_4d MO 5min(1)
HumanDetectionTimeStatus_4d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
58 ※ Dev Type AC
address

instance
point Name
number

22529 1 On/Off (Setting)


22530 2 On/Off (Status)
22531 3 Lock (Setting)
22532 4 Lock (Status)
22533 5 Filter Sign
22534 6 Filter Sign reset
22535 7 Operation Mode (Setting)
22536 8 Operation Mode (Status)
22537 9 Swing (Setting)
22538 10 Swing (Status)
22539 11 Fan Speed (Setting)
22540 12 Fan Speed (Status)
22541 13 Set Room Temperature
22542 14 Room Temperature
22543 15 Alarm
22544 16 Error Code
22547 19 Set Temperature (Status)
22548 20 Accumulated Power Distribution (Status)
22555 27 Set Upper Temperature (Setting)
22556 28 Set Lower Temperature (Setting)
22557 29 Set Upper Tempaerature (Status)
22558 30 Set Lower Temperature (Status)
22559 31 Mode Lock (Setting)
22560 32 Mode Lock (Status)
22561 33 Fan Lock (Setting)
22562 34 Fan Lock (Status)
22563 35 Occupancy (Setting)
22564 36 Occupancy (Status)
22565 37 2Set Cooling Set Temperature (Setting)
22566 38 2Set Cooling Set Temperature (Status)
22567 39 2Set Heating Set Temperature (Setting)
22568 40 2Set Heating Set Temperature (Status)
22569 41 2Set Cooling Upper Temperature (Setting)
22570 42 2Set Cooling Upper Temperature (Status)
22571 43 2Set Heating Upper Temperature (Setting)
22572 44 2Set Heating Upper Temperature (Status)
22573 45 2Set Cooling Lower Temperature (Setting)
22574 46 2Set Cooling Lower Temperature (Status)
22575 47 2Set Heating Lower Temperature (Setting)
22576 48 2Set Heating Lower Temperature (Status)
22577 49 Thermo Status (Status)
22578 50 Accumulated Gas Distribution (Status)
22579 51 Dust Sensor Available (Status)
22580 52 Air Cleaning Opereration (Setting)
22581 53 Air Cleaning Opereration (Status)
22582 54 Fine Dust (Status)
22583 55 Ultra Fine Dust (Status)
22584 56 Super Ultra Fine Dust (Status)
22585 57 Humidity (Status)
22586 58 Comfort Cooling Available (Status)
22587 59 Comfort Cooling Opereration (Setting)
22588 60 Comfort Cooling Opereration (Status)
22589 61 Comfort Cooling Step (Setting)
22590 62 Comfort Cooling Step (Status)
22591 63 Human Detection Available (Status)
22592 64 Human Detection Opereration (Setting)
22593 65 Human Detection Opereration (Status)
22594 66 Human Detection Wind (Setting)
22595 67 Human Detection Wind (Status)
22596 68 Human Detection Time (Setting)
22597 69 Human Detection Time (Status)
22598 70 Hotel Checkin (Setting)
22599 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_58 BO Stop(0) Start(1)
StartStopStatus_58 BI Stop(0) Start(1)
LockCommand_58 BO Permit(0) Prohibit(1)
LockStatus_58 BI Permit(0) Prohibit(1)
FilterSign_58 BI Off(0) On(1)
FilterSignReset_58 BV - Reset(1)
AirConModeCommand_58 MO Cool(1)
AirConModeStatus_58 MI Cool(1)
SwingCommand_58 BO Stop(0) Run(1)
SwingStatus_58 BI Stop(0) Run(1)
FanSpeedCommand_58 MO Low(1)
FanSpeedStatus_58 MI Low(1)
SetRoomTemp_58 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_58 AI ℃
Alarm_58 BI Normal(0) Abnormal(1)
MalfunctionCode_58 AI Refer to the
SetTempStatus_58 AI ℃
Accumulated power(100 Watt)_58 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_58 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_58 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_58 AI ℃
TempRangeLowerLimitStatus_58 AI ℃
ModeLockCommand_58 BO Permit(0) Prohibit(1)
ModeLockStatus_58 BI Permit(0) Prohibit(1)
FanLockCommand_58 BO Permit(0) Prohibit(1)
FanLockStatus_58 BI Permit(0) Prohibit(1)
OccupancyCommand_58 BO Unoccupied(0) Occupied(1)
OccupancyStatus_58 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_58 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_58 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_58 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_58 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_58 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_58 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_58 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_58 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_58 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_58 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_58 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_58 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_58 BI Off(0) On(1)
AccumulatedGas(100 Watt)_58 AI Wattage values (Unit : 100Watt)
DustSensorAvail_58 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_58 BO Stop(0) Run(1)
AirCleaningOperStatus_58 BI Stop(0) Run(1)
FineDustStatus_58 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_58 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_58 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_58 AI %
ComfortCoolingAvail_58 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_58 BO Stop(0) Run(1)
ComfortCoolingOperStatus_58 BI Stop(0) Run(1)
ComfortCoolingStepCommand_58 AV 1~3 step
ComfortCoolingStepStatus_58 AI 1~3 step
HumanDetectionAvail_58 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_58 MO Off(1)
HumanDetectionOperStatus_58 MI Off(1)
HumanDetectionWindCommand_58 MO Off(1)
HumanDetectionWindStatus_58 MI Off(1)
HumanDetectionTimeCommand_58 MO 5min(1)
HumanDetectionTimeStatus_58 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
59 ※ Dev Type AC
address

instance
point Name
number

22785 1 On/Off (Setting)


22786 2 On/Off (Status)
22787 3 Lock (Setting)
22788 4 Lock (Status)
22789 5 Filter Sign
22790 6 Filter Sign reset
22791 7 Operation Mode (Setting)
22792 8 Operation Mode (Status)
22793 9 Swing (Setting)
22794 10 Swing (Status)
22795 11 Fan Speed (Setting)
22796 12 Fan Speed (Status)
22797 13 Set Room Temperature
22798 14 Room Temperature
22799 15 Alarm
22800 16 Error Code
22803 19 Set Temperature (Status)
22804 20 Accumulated Power Distribution (Status)
22811 27 Set Upper Temperature (Setting)
22812 28 Set Lower Temperature (Setting)
22813 29 Set Upper Tempaerature (Status)
22814 30 Set Lower Temperature (Status)
22815 31 Mode Lock (Setting)
22816 32 Mode Lock (Status)
22817 33 Fan Lock (Setting)
22818 34 Fan Lock (Status)
22819 35 Occupancy (Setting)
22820 36 Occupancy (Status)
22821 37 2Set Cooling Set Temperature (Setting)
22822 38 2Set Cooling Set Temperature (Status)
22823 39 2Set Heating Set Temperature (Setting)
22824 40 2Set Heating Set Temperature (Status)
22825 41 2Set Cooling Upper Temperature (Setting)
22826 42 2Set Cooling Upper Temperature (Status)
22827 43 2Set Heating Upper Temperature (Setting)
22828 44 2Set Heating Upper Temperature (Status)
22829 45 2Set Cooling Lower Temperature (Setting)
22830 46 2Set Cooling Lower Temperature (Status)
22831 47 2Set Heating Lower Temperature (Setting)
22832 48 2Set Heating Lower Temperature (Status)
22833 49 Thermo Status (Status)
22834 50 Accumulated Gas Distribution (Status)
22835 51 Dust Sensor Available (Status)
22836 52 Air Cleaning Opereration (Setting)
22837 53 Air Cleaning Opereration (Status)
22838 54 Fine Dust (Status)
22839 55 Ultra Fine Dust (Status)
22840 56 Super Ultra Fine Dust (Status)
22841 57 Humidity (Status)
22842 58 Comfort Cooling Available (Status)
22843 59 Comfort Cooling Opereration (Setting)
22844 60 Comfort Cooling Opereration (Status)
22845 61 Comfort Cooling Step (Setting)
22846 62 Comfort Cooling Step (Status)
22847 63 Human Detection Available (Status)
22848 64 Human Detection Opereration (Setting)
22849 65 Human Detection Opereration (Status)
22850 66 Human Detection Wind (Setting)
22851 67 Human Detection Wind (Status)
22852 68 Human Detection Time (Setting)
22853 69 Human Detection Time (Status)
22854 70 Hotel Checkin (Setting)
22855 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_59 BO Stop(0) Start(1)
StartStopStatus_59 BI Stop(0) Start(1)
LockCommand_59 BO Permit(0) Prohibit(1)
LockStatus_59 BI Permit(0) Prohibit(1)
FilterSign_59 BI Off(0) On(1)
FilterSignReset_59 BV - Reset(1)
AirConModeCommand_59 MO Cool(1)
AirConModeStatus_59 MI Cool(1)
SwingCommand_59 BO Stop(0) Run(1)
SwingStatus_59 BI Stop(0) Run(1)
FanSpeedCommand_59 MO Low(1)
FanSpeedStatus_59 MI Low(1)
SetRoomTemp_59 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_59 AI ℃
Alarm_59 BI Normal(0) Abnormal(1)
MalfunctionCode_59 AI Refer to the
SetTempStatus_59 AI ℃
Accumulated power(100 Watt)_59 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_59 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_59 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_59 AI ℃
TempRangeLowerLimitStatus_59 AI ℃
ModeLockCommand_59 BO Permit(0) Prohibit(1)
ModeLockStatus_59 BI Permit(0) Prohibit(1)
FanLockCommand_59 BO Permit(0) Prohibit(1)
FanLockStatus_59 BI Permit(0) Prohibit(1)
OccupancyCommand_59 BO Unoccupied(0) Occupied(1)
OccupancyStatus_59 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_59 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_59 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_59 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_59 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_59 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_59 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_59 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_59 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_59 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_59 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_59 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_59 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_59 BI Off(0) On(1)
AccumulatedGas(100 Watt)_59 AI Wattage values (Unit : 100Watt)
DustSensorAvail_59 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_59 BO Stop(0) Run(1)
AirCleaningOperStatus_59 BI Stop(0) Run(1)
FineDustStatus_59 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_59 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_59 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_59 AI %
ComfortCoolingAvail_59 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_59 BO Stop(0) Run(1)
ComfortCoolingOperStatus_59 BI Stop(0) Run(1)
ComfortCoolingStepCommand_59 AV 1~3 step
ComfortCoolingStepStatus_59 AI 1~3 step
HumanDetectionAvail_59 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_59 MO Off(1)
HumanDetectionOperStatus_59 MI Off(1)
HumanDetectionWindCommand_59 MO Off(1)
HumanDetectionWindStatus_59 MI Off(1)
HumanDetectionTimeCommand_59 MO 5min(1)
HumanDetectionTimeStatus_59 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5a ※ Dev Type AC
address

instance
point Name
number

23041 1 On/Off (Setting)


23042 2 On/Off (Status)
23043 3 Lock (Setting)
23044 4 Lock (Status)
23045 5 Filter Sign
23046 6 Filter Sign reset
23047 7 Operation Mode (Setting)
23048 8 Operation Mode (Status)
23049 9 Swing (Setting)
23050 10 Swing (Status)
23051 11 Fan Speed (Setting)
23052 12 Fan Speed (Status)
23053 13 Set Room Temperature
23054 14 Room Temperature
23055 15 Alarm
23056 16 Error Code
23059 19 Set Temperature (Status)
23060 20 Accumulated Power Distribution (Status)
23067 27 Set Upper Temperature (Setting)
23068 28 Set Lower Temperature (Setting)
23069 29 Set Upper Tempaerature (Status)
23070 30 Set Lower Temperature (Status)
23071 31 Mode Lock (Setting)
23072 32 Mode Lock (Status)
23073 33 Fan Lock (Setting)
23074 34 Fan Lock (Status)
23075 35 Occupancy (Setting)
23076 36 Occupancy (Status)
23077 37 2Set Cooling Set Temperature (Setting)
23078 38 2Set Cooling Set Temperature (Status)
23079 39 2Set Heating Set Temperature (Setting)
23080 40 2Set Heating Set Temperature (Status)
23081 41 2Set Cooling Upper Temperature (Setting)
23082 42 2Set Cooling Upper Temperature (Status)
23083 43 2Set Heating Upper Temperature (Setting)
23084 44 2Set Heating Upper Temperature (Status)
23085 45 2Set Cooling Lower Temperature (Setting)
23086 46 2Set Cooling Lower Temperature (Status)
23087 47 2Set Heating Lower Temperature (Setting)
23088 48 2Set Heating Lower Temperature (Status)
23089 49 Thermo Status (Status)
23090 50 Accumulated Gas Distribution (Status)
23091 51 Dust Sensor Available (Status)
23092 52 Air Cleaning Opereration (Setting)
23093 53 Air Cleaning Opereration (Status)
23094 54 Fine Dust (Status)
23095 55 Ultra Fine Dust (Status)
23096 56 Super Ultra Fine Dust (Status)
23097 57 Humidity (Status)
23098 58 Comfort Cooling Available (Status)
23099 59 Comfort Cooling Opereration (Setting)
23100 60 Comfort Cooling Opereration (Status)
23101 61 Comfort Cooling Step (Setting)
23102 62 Comfort Cooling Step (Status)
23103 63 Human Detection Available (Status)
23104 64 Human Detection Opereration (Setting)
23105 65 Human Detection Opereration (Status)
23106 66 Human Detection Wind (Setting)
23107 67 Human Detection Wind (Status)
23108 68 Human Detection Time (Setting)
23109 69 Human Detection Time (Status)
23110 70 Hotel Checkin (Setting)
23111 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5a BO Stop(0) Start(1)
StartStopStatus_5a BI Stop(0) Start(1)
LockCommand_5a BO Permit(0) Prohibit(1)
LockStatus_5a BI Permit(0) Prohibit(1)
FilterSign_5a BI Off(0) On(1)
FilterSignReset_5a BV - Reset(1)
AirConModeCommand_5a MO Cool(1)
AirConModeStatus_5a MI Cool(1)
SwingCommand_5a BO Stop(0) Run(1)
SwingStatus_5a BI Stop(0) Run(1)
FanSpeedCommand_5a MO Low(1)
FanSpeedStatus_5a MI Low(1)
SetRoomTemp_5a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5a AI ℃
Alarm_5a BI Normal(0) Abnormal(1)
MalfunctionCode_5a AI Refer to the
SetTempStatus_5a AI ℃
Accumulated power(100 Watt)_5a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5a AI ℃
TempRangeLowerLimitStatus_5a AI ℃
ModeLockCommand_5a BO Permit(0) Prohibit(1)
ModeLockStatus_5a BI Permit(0) Prohibit(1)
FanLockCommand_5a BO Permit(0) Prohibit(1)
FanLockStatus_5a BI Permit(0) Prohibit(1)
OccupancyCommand_5a BO Unoccupied(0) Occupied(1)
OccupancyStatus_5a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5a BI Off(0) On(1)
AccumulatedGas(100 Watt)_5a AI Wattage values (Unit : 100Watt)
DustSensorAvail_5a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5a BO Stop(0) Run(1)
AirCleaningOperStatus_5a BI Stop(0) Run(1)
FineDustStatus_5a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5a AI %
ComfortCoolingAvail_5a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5a BO Stop(0) Run(1)
ComfortCoolingOperStatus_5a BI Stop(0) Run(1)
ComfortCoolingStepCommand_5a AV 1~3 step
ComfortCoolingStepStatus_5a AI 1~3 step
HumanDetectionAvail_5a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5a MO Off(1)
HumanDetectionOperStatus_5a MI Off(1)
HumanDetectionWindCommand_5a MO Off(1)
HumanDetectionWindStatus_5a MI Off(1)
HumanDetectionTimeCommand_5a MO 5min(1)
HumanDetectionTimeStatus_5a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5b ※ Dev Type AC
address

instance
point Name
number

23297 1 On/Off (Setting)


23298 2 On/Off (Status)
23299 3 Lock (Setting)
23300 4 Lock (Status)
23301 5 Filter Sign
23302 6 Filter Sign reset
23303 7 Operation Mode (Setting)
23304 8 Operation Mode (Status)
23305 9 Swing (Setting)
23306 10 Swing (Status)
23307 11 Fan Speed (Setting)
23308 12 Fan Speed (Status)
23309 13 Set Room Temperature
23310 14 Room Temperature
23311 15 Alarm
23312 16 Error Code
23315 19 Set Temperature (Status)
23316 20 Accumulated Power Distribution (Status)
23323 27 Set Upper Temperature (Setting)
23324 28 Set Lower Temperature (Setting)
23325 29 Set Upper Tempaerature (Status)
23326 30 Set Lower Temperature (Status)
23327 31 Mode Lock (Setting)
23328 32 Mode Lock (Status)
23329 33 Fan Lock (Setting)
23330 34 Fan Lock (Status)
23331 35 Occupancy (Setting)
23332 36 Occupancy (Status)
23333 37 2Set Cooling Set Temperature (Setting)
23334 38 2Set Cooling Set Temperature (Status)
23335 39 2Set Heating Set Temperature (Setting)
23336 40 2Set Heating Set Temperature (Status)
23337 41 2Set Cooling Upper Temperature (Setting)
23338 42 2Set Cooling Upper Temperature (Status)
23339 43 2Set Heating Upper Temperature (Setting)
23340 44 2Set Heating Upper Temperature (Status)
23341 45 2Set Cooling Lower Temperature (Setting)
23342 46 2Set Cooling Lower Temperature (Status)
23343 47 2Set Heating Lower Temperature (Setting)
23344 48 2Set Heating Lower Temperature (Status)
23345 49 Thermo Status (Status)
23346 50 Accumulated Gas Distribution (Status)
23347 51 Dust Sensor Available (Status)
23348 52 Air Cleaning Opereration (Setting)
23349 53 Air Cleaning Opereration (Status)
23350 54 Fine Dust (Status)
23351 55 Ultra Fine Dust (Status)
23352 56 Super Ultra Fine Dust (Status)
23353 57 Humidity (Status)
23354 58 Comfort Cooling Available (Status)
23355 59 Comfort Cooling Opereration (Setting)
23356 60 Comfort Cooling Opereration (Status)
23357 61 Comfort Cooling Step (Setting)
23358 62 Comfort Cooling Step (Status)
23359 63 Human Detection Available (Status)
23360 64 Human Detection Opereration (Setting)
23361 65 Human Detection Opereration (Status)
23362 66 Human Detection Wind (Setting)
23363 67 Human Detection Wind (Status)
23364 68 Human Detection Time (Setting)
23365 69 Human Detection Time (Status)
23366 70 Hotel Checkin (Setting)
23367 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5b BO Stop(0) Start(1)
StartStopStatus_5b BI Stop(0) Start(1)
LockCommand_5b BO Permit(0) Prohibit(1)
LockStatus_5b BI Permit(0) Prohibit(1)
FilterSign_5b BI Off(0) On(1)
FilterSignReset_5b BV - Reset(1)
AirConModeCommand_5b MO Cool(1)
AirConModeStatus_5b MI Cool(1)
SwingCommand_5b BO Stop(0) Run(1)
SwingStatus_5b BI Stop(0) Run(1)
FanSpeedCommand_5b MO Low(1)
FanSpeedStatus_5b MI Low(1)
SetRoomTemp_5b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5b AI ℃
Alarm_5b BI Normal(0) Abnormal(1)
MalfunctionCode_5b AI Refer to the
SetTempStatus_5b AI ℃
Accumulated power(100 Watt)_5b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5b AI ℃
TempRangeLowerLimitStatus_5b AI ℃
ModeLockCommand_5b BO Permit(0) Prohibit(1)
ModeLockStatus_5b BI Permit(0) Prohibit(1)
FanLockCommand_5b BO Permit(0) Prohibit(1)
FanLockStatus_5b BI Permit(0) Prohibit(1)
OccupancyCommand_5b BO Unoccupied(0) Occupied(1)
OccupancyStatus_5b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5b BI Off(0) On(1)
AccumulatedGas(100 Watt)_5b AI Wattage values (Unit : 100Watt)
DustSensorAvail_5b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5b BO Stop(0) Run(1)
AirCleaningOperStatus_5b BI Stop(0) Run(1)
FineDustStatus_5b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5b AI %
ComfortCoolingAvail_5b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5b BO Stop(0) Run(1)
ComfortCoolingOperStatus_5b BI Stop(0) Run(1)
ComfortCoolingStepCommand_5b AV 1~3 step
ComfortCoolingStepStatus_5b AI 1~3 step
HumanDetectionAvail_5b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5b MO Off(1)
HumanDetectionOperStatus_5b MI Off(1)
HumanDetectionWindCommand_5b MO Off(1)
HumanDetectionWindStatus_5b MI Off(1)
HumanDetectionTimeCommand_5b MO 5min(1)
HumanDetectionTimeStatus_5b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5c ※ Dev Type AC
address

instance
point Name
number

23553 1 On/Off (Setting)


23554 2 On/Off (Status)
23555 3 Lock (Setting)
23556 4 Lock (Status)
23557 5 Filter Sign
23558 6 Filter Sign reset
23559 7 Operation Mode (Setting)
23560 8 Operation Mode (Status)
23561 9 Swing (Setting)
23562 10 Swing (Status)
23563 11 Fan Speed (Setting)
23564 12 Fan Speed (Status)
23565 13 Set Room Temperature
23566 14 Room Temperature
23567 15 Alarm
23568 16 Error Code
23571 19 Set Temperature (Status)
23572 20 Accumulated Power Distribution (Status)
23579 27 Set Upper Temperature (Setting)
23580 28 Set Lower Temperature (Setting)
23581 29 Set Upper Tempaerature (Status)
23582 30 Set Lower Temperature (Status)
23583 31 Mode Lock (Setting)
23584 32 Mode Lock (Status)
23585 33 Fan Lock (Setting)
23586 34 Fan Lock (Status)
23587 35 Occupancy (Setting)
23588 36 Occupancy (Status)
23589 37 2Set Cooling Set Temperature (Setting)
23590 38 2Set Cooling Set Temperature (Status)
23591 39 2Set Heating Set Temperature (Setting)
23592 40 2Set Heating Set Temperature (Status)
23593 41 2Set Cooling Upper Temperature (Setting)
23594 42 2Set Cooling Upper Temperature (Status)
23595 43 2Set Heating Upper Temperature (Setting)
23596 44 2Set Heating Upper Temperature (Status)
23597 45 2Set Cooling Lower Temperature (Setting)
23598 46 2Set Cooling Lower Temperature (Status)
23599 47 2Set Heating Lower Temperature (Setting)
23600 48 2Set Heating Lower Temperature (Status)
23601 49 Thermo Status (Status)
23602 50 Accumulated Gas Distribution (Status)
23603 51 Dust Sensor Available (Status)
23604 52 Air Cleaning Opereration (Setting)
23605 53 Air Cleaning Opereration (Status)
23606 54 Fine Dust (Status)
23607 55 Ultra Fine Dust (Status)
23608 56 Super Ultra Fine Dust (Status)
23609 57 Humidity (Status)
23610 58 Comfort Cooling Available (Status)
23611 59 Comfort Cooling Opereration (Setting)
23612 60 Comfort Cooling Opereration (Status)
23613 61 Comfort Cooling Step (Setting)
23614 62 Comfort Cooling Step (Status)
23615 63 Human Detection Available (Status)
23616 64 Human Detection Opereration (Setting)
23617 65 Human Detection Opereration (Status)
23618 66 Human Detection Wind (Setting)
23619 67 Human Detection Wind (Status)
23620 68 Human Detection Time (Setting)
23621 69 Human Detection Time (Status)
23622 70 Hotel Checkin (Setting)
23623 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5c BO Stop(0) Start(1)
StartStopStatus_5c BI Stop(0) Start(1)
LockCommand_5c BO Permit(0) Prohibit(1)
LockStatus_5c BI Permit(0) Prohibit(1)
FilterSign_5c BI Off(0) On(1)
FilterSignReset_5c BV - Reset(1)
AirConModeCommand_5c MO Cool(1)
AirConModeStatus_5c MI Cool(1)
SwingCommand_5c BO Stop(0) Run(1)
SwingStatus_5c BI Stop(0) Run(1)
FanSpeedCommand_5c MO Low(1)
FanSpeedStatus_5c MI Low(1)
SetRoomTemp_5c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5c AI ℃
Alarm_5c BI Normal(0) Abnormal(1)
MalfunctionCode_5c AI Refer to the
SetTempStatus_5c AI ℃
Accumulated power(100 Watt)_5c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5c AI ℃
TempRangeLowerLimitStatus_5c AI ℃
ModeLockCommand_5c BO Permit(0) Prohibit(1)
ModeLockStatus_5c BI Permit(0) Prohibit(1)
FanLockCommand_5c BO Permit(0) Prohibit(1)
FanLockStatus_5c BI Permit(0) Prohibit(1)
OccupancyCommand_5c BO Unoccupied(0) Occupied(1)
OccupancyStatus_5c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5c BI Off(0) On(1)
AccumulatedGas(100 Watt)_5c AI Wattage values (Unit : 100Watt)
DustSensorAvail_5c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5c BO Stop(0) Run(1)
AirCleaningOperStatus_5c BI Stop(0) Run(1)
FineDustStatus_5c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5c AI %
ComfortCoolingAvail_5c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5c BO Stop(0) Run(1)
ComfortCoolingOperStatus_5c BI Stop(0) Run(1)
ComfortCoolingStepCommand_5c AV 1~3 step
ComfortCoolingStepStatus_5c AI 1~3 step
HumanDetectionAvail_5c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5c MO Off(1)
HumanDetectionOperStatus_5c MI Off(1)
HumanDetectionWindCommand_5c MO Off(1)
HumanDetectionWindStatus_5c MI Off(1)
HumanDetectionTimeCommand_5c MO 5min(1)
HumanDetectionTimeStatus_5c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5d ※ Dev Type AC
address

instance
point Name
number

23809 1 On/Off (Setting)


23810 2 On/Off (Status)
23811 3 Lock (Setting)
23812 4 Lock (Status)
23813 5 Filter Sign
23814 6 Filter Sign reset
23815 7 Operation Mode (Setting)
23816 8 Operation Mode (Status)
23817 9 Swing (Setting)
23818 10 Swing (Status)
23819 11 Fan Speed (Setting)
23820 12 Fan Speed (Status)
23821 13 Set Room Temperature
23822 14 Room Temperature
23823 15 Alarm
23824 16 Error Code
23827 19 Set Temperature (Status)
23828 20 Accumulated Power Distribution (Status)
23835 27 Set Upper Temperature (Setting)
23836 28 Set Lower Temperature (Setting)
23837 29 Set Upper Tempaerature (Status)
23838 30 Set Lower Temperature (Status)
23839 31 Mode Lock (Setting)
23840 32 Mode Lock (Status)
23841 33 Fan Lock (Setting)
23842 34 Fan Lock (Status)
23843 35 Occupancy (Setting)
23844 36 Occupancy (Status)
23845 37 2Set Cooling Set Temperature (Setting)
23846 38 2Set Cooling Set Temperature (Status)
23847 39 2Set Heating Set Temperature (Setting)
23848 40 2Set Heating Set Temperature (Status)
23849 41 2Set Cooling Upper Temperature (Setting)
23850 42 2Set Cooling Upper Temperature (Status)
23851 43 2Set Heating Upper Temperature (Setting)
23852 44 2Set Heating Upper Temperature (Status)
23853 45 2Set Cooling Lower Temperature (Setting)
23854 46 2Set Cooling Lower Temperature (Status)
23855 47 2Set Heating Lower Temperature (Setting)
23856 48 2Set Heating Lower Temperature (Status)
23857 49 Thermo Status (Status)
23858 50 Accumulated Gas Distribution (Status)
23859 51 Dust Sensor Available (Status)
23860 52 Air Cleaning Opereration (Setting)
23861 53 Air Cleaning Opereration (Status)
23862 54 Fine Dust (Status)
23863 55 Ultra Fine Dust (Status)
23864 56 Super Ultra Fine Dust (Status)
23865 57 Humidity (Status)
23866 58 Comfort Cooling Available (Status)
23867 59 Comfort Cooling Opereration (Setting)
23868 60 Comfort Cooling Opereration (Status)
23869 61 Comfort Cooling Step (Setting)
23870 62 Comfort Cooling Step (Status)
23871 63 Human Detection Available (Status)
23872 64 Human Detection Opereration (Setting)
23873 65 Human Detection Opereration (Status)
23874 66 Human Detection Wind (Setting)
23875 67 Human Detection Wind (Status)
23876 68 Human Detection Time (Setting)
23877 69 Human Detection Time (Status)
23878 70 Hotel Checkin (Setting)
23879 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5d BO Stop(0) Start(1)
StartStopStatus_5d BI Stop(0) Start(1)
LockCommand_5d BO Permit(0) Prohibit(1)
LockStatus_5d BI Permit(0) Prohibit(1)
FilterSign_5d BI Off(0) On(1)
FilterSignReset_5d BV - Reset(1)
AirConModeCommand_5d MO Cool(1)
AirConModeStatus_5d MI Cool(1)
SwingCommand_5d BO Stop(0) Run(1)
SwingStatus_5d BI Stop(0) Run(1)
FanSpeedCommand_5d MO Low(1)
FanSpeedStatus_5d MI Low(1)
SetRoomTemp_5d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5d AI ℃
Alarm_5d BI Normal(0) Abnormal(1)
MalfunctionCode_5d AI Refer to the
SetTempStatus_5d AI ℃
Accumulated power(100 Watt)_5d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5d AI ℃
TempRangeLowerLimitStatus_5d AI ℃
ModeLockCommand_5d BO Permit(0) Prohibit(1)
ModeLockStatus_5d BI Permit(0) Prohibit(1)
FanLockCommand_5d BO Permit(0) Prohibit(1)
FanLockStatus_5d BI Permit(0) Prohibit(1)
OccupancyCommand_5d BO Unoccupied(0) Occupied(1)
OccupancyStatus_5d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5d BI Off(0) On(1)
AccumulatedGas(100 Watt)_5d AI Wattage values (Unit : 100Watt)
DustSensorAvail_5d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5d BO Stop(0) Run(1)
AirCleaningOperStatus_5d BI Stop(0) Run(1)
FineDustStatus_5d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5d AI %
ComfortCoolingAvail_5d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5d BO Stop(0) Run(1)
ComfortCoolingOperStatus_5d BI Stop(0) Run(1)
ComfortCoolingStepCommand_5d AV 1~3 step
ComfortCoolingStepStatus_5d AI 1~3 step
HumanDetectionAvail_5d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5d MO Off(1)
HumanDetectionOperStatus_5d MI Off(1)
HumanDetectionWindCommand_5d MO Off(1)
HumanDetectionWindStatus_5d MI Off(1)
HumanDetectionTimeCommand_5d MO 5min(1)
HumanDetectionTimeStatus_5d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5e ※ Dev Type AC
address

instance
point Name
number

24065 1 On/Off (Setting)


24066 2 On/Off (Status)
24067 3 Lock (Setting)
24068 4 Lock (Status)
24069 5 Filter Sign
24070 6 Filter Sign reset
24071 7 Operation Mode (Setting)
24072 8 Operation Mode (Status)
24073 9 Swing (Setting)
24074 10 Swing (Status)
24075 11 Fan Speed (Setting)
24076 12 Fan Speed (Status)
24077 13 Set Room Temperature
24078 14 Room Temperature
24079 15 Alarm
24080 16 Error Code
24083 19 Set Temperature (Status)
24084 20 Accumulated Power Distribution (Status)
24091 27 Set Upper Temperature (Setting)
24092 28 Set Lower Temperature (Setting)
24093 29 Set Upper Tempaerature (Status)
24094 30 Set Lower Temperature (Status)
24095 31 Mode Lock (Setting)
24096 32 Mode Lock (Status)
24097 33 Fan Lock (Setting)
24098 34 Fan Lock (Status)
24099 35 Occupancy (Setting)
24100 36 Occupancy (Status)
24101 37 2Set Cooling Set Temperature (Setting)
24102 38 2Set Cooling Set Temperature (Status)
24103 39 2Set Heating Set Temperature (Setting)
24104 40 2Set Heating Set Temperature (Status)
24105 41 2Set Cooling Upper Temperature (Setting)
24106 42 2Set Cooling Upper Temperature (Status)
24107 43 2Set Heating Upper Temperature (Setting)
24108 44 2Set Heating Upper Temperature (Status)
24109 45 2Set Cooling Lower Temperature (Setting)
24110 46 2Set Cooling Lower Temperature (Status)
24111 47 2Set Heating Lower Temperature (Setting)
24112 48 2Set Heating Lower Temperature (Status)
24113 49 Thermo Status (Status)
24114 50 Accumulated Gas Distribution (Status)
24115 51 Dust Sensor Available (Status)
24116 52 Air Cleaning Opereration (Setting)
24117 53 Air Cleaning Opereration (Status)
24118 54 Fine Dust (Status)
24119 55 Ultra Fine Dust (Status)
24120 56 Super Ultra Fine Dust (Status)
24121 57 Humidity (Status)
24122 58 Comfort Cooling Available (Status)
24123 59 Comfort Cooling Opereration (Setting)
24124 60 Comfort Cooling Opereration (Status)
24125 61 Comfort Cooling Step (Setting)
24126 62 Comfort Cooling Step (Status)
24127 63 Human Detection Available (Status)
24128 64 Human Detection Opereration (Setting)
24129 65 Human Detection Opereration (Status)
24130 66 Human Detection Wind (Setting)
24131 67 Human Detection Wind (Status)
24132 68 Human Detection Time (Setting)
24133 69 Human Detection Time (Status)
24134 70 Hotel Checkin (Setting)
24135 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5e BO Stop(0) Start(1)
StartStopStatus_5e BI Stop(0) Start(1)
LockCommand_5e BO Permit(0) Prohibit(1)
LockStatus_5e BI Permit(0) Prohibit(1)
FilterSign_5e BI Off(0) On(1)
FilterSignReset_5e BV - Reset(1)
AirConModeCommand_5e MO Cool(1)
AirConModeStatus_5e MI Cool(1)
SwingCommand_5e BO Stop(0) Run(1)
SwingStatus_5e BI Stop(0) Run(1)
FanSpeedCommand_5e MO Low(1)
FanSpeedStatus_5e MI Low(1)
SetRoomTemp_5e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5e AI ℃
Alarm_5e BI Normal(0) Abnormal(1)
MalfunctionCode_5e AI Refer to the
SetTempStatus_5e AI ℃
Accumulated power(100 Watt)_5e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5e AI ℃
TempRangeLowerLimitStatus_5e AI ℃
ModeLockCommand_5e BO Permit(0) Prohibit(1)
ModeLockStatus_5e BI Permit(0) Prohibit(1)
FanLockCommand_5e BO Permit(0) Prohibit(1)
FanLockStatus_5e BI Permit(0) Prohibit(1)
OccupancyCommand_5e BO Unoccupied(0) Occupied(1)
OccupancyStatus_5e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5e BI Off(0) On(1)
AccumulatedGas(100 Watt)_5e AI Wattage values (Unit : 100Watt)
DustSensorAvail_5e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5e BO Stop(0) Run(1)
AirCleaningOperStatus_5e BI Stop(0) Run(1)
FineDustStatus_5e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5e AI %
ComfortCoolingAvail_5e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5e BO Stop(0) Run(1)
ComfortCoolingOperStatus_5e BI Stop(0) Run(1)
ComfortCoolingStepCommand_5e AV 1~3 step
ComfortCoolingStepStatus_5e AI 1~3 step
HumanDetectionAvail_5e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5e MO Off(1)
HumanDetectionOperStatus_5e MI Off(1)
HumanDetectionWindCommand_5e MO Off(1)
HumanDetectionWindStatus_5e MI Off(1)
HumanDetectionTimeCommand_5e MO 5min(1)
HumanDetectionTimeStatus_5e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5f ※ Dev Type AC
address

instance
point Name
number

24321 1 On/Off (Setting)


24322 2 On/Off (Status)
24323 3 Lock (Setting)
24324 4 Lock (Status)
24325 5 Filter Sign
24326 6 Filter Sign reset
24327 7 Operation Mode (Setting)
24328 8 Operation Mode (Status)
24329 9 Swing (Setting)
24330 10 Swing (Status)
24331 11 Fan Speed (Setting)
24332 12 Fan Speed (Status)
24333 13 Set Room Temperature
24334 14 Room Temperature
24335 15 Alarm
24336 16 Error Code
24339 19 Set Temperature (Status)
24340 20 Accumulated Power Distribution (Status)
24347 27 Set Upper Temperature (Setting)
24348 28 Set Lower Temperature (Setting)
24349 29 Set Upper Tempaerature (Status)
24350 30 Set Lower Temperature (Status)
24351 31 Mode Lock (Setting)
24352 32 Mode Lock (Status)
24353 33 Fan Lock (Setting)
24354 34 Fan Lock (Status)
24355 35 Occupancy (Setting)
24356 36 Occupancy (Status)
24357 37 2Set Cooling Set Temperature (Setting)
24358 38 2Set Cooling Set Temperature (Status)
24359 39 2Set Heating Set Temperature (Setting)
24360 40 2Set Heating Set Temperature (Status)
24361 41 2Set Cooling Upper Temperature (Setting)
24362 42 2Set Cooling Upper Temperature (Status)
24363 43 2Set Heating Upper Temperature (Setting)
24364 44 2Set Heating Upper Temperature (Status)
24365 45 2Set Cooling Lower Temperature (Setting)
24366 46 2Set Cooling Lower Temperature (Status)
24367 47 2Set Heating Lower Temperature (Setting)
24368 48 2Set Heating Lower Temperature (Status)
24369 49 Thermo Status (Status)
24370 50 Accumulated Gas Distribution (Status)
24371 51 Dust Sensor Available (Status)
24372 52 Air Cleaning Opereration (Setting)
24373 53 Air Cleaning Opereration (Status)
24374 54 Fine Dust (Status)
24375 55 Ultra Fine Dust (Status)
24376 56 Super Ultra Fine Dust (Status)
24377 57 Humidity (Status)
24378 58 Comfort Cooling Available (Status)
24379 59 Comfort Cooling Opereration (Setting)
24380 60 Comfort Cooling Opereration (Status)
24381 61 Comfort Cooling Step (Setting)
24382 62 Comfort Cooling Step (Status)
24383 63 Human Detection Available (Status)
24384 64 Human Detection Opereration (Setting)
24385 65 Human Detection Opereration (Status)
24386 66 Human Detection Wind (Setting)
24387 67 Human Detection Wind (Status)
24388 68 Human Detection Time (Setting)
24389 69 Human Detection Time (Status)
24390 70 Hotel Checkin (Setting)
24391 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5f BO Stop(0) Start(1)
StartStopStatus_5f BI Stop(0) Start(1)
LockCommand_5f BO Permit(0) Prohibit(1)
LockStatus_5f BI Permit(0) Prohibit(1)
FilterSign_5f BI Off(0) On(1)
FilterSignReset_5f BV - Reset(1)
AirConModeCommand_5f MO Cool(1)
AirConModeStatus_5f MI Cool(1)
SwingCommand_5f BO Stop(0) Run(1)
SwingStatus_5f BI Stop(0) Run(1)
FanSpeedCommand_5f MO Low(1)
FanSpeedStatus_5f MI Low(1)
SetRoomTemp_5f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5f AI ℃
Alarm_5f BI Normal(0) Abnormal(1)
MalfunctionCode_5f AI Refer to the
SetTempStatus_5f AI ℃
Accumulated power(100 Watt)_5f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5f AI ℃
TempRangeLowerLimitStatus_5f AI ℃
ModeLockCommand_5f BO Permit(0) Prohibit(1)
ModeLockStatus_5f BI Permit(0) Prohibit(1)
FanLockCommand_5f BO Permit(0) Prohibit(1)
FanLockStatus_5f BI Permit(0) Prohibit(1)
OccupancyCommand_5f BO Unoccupied(0) Occupied(1)
OccupancyStatus_5f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5f BI Off(0) On(1)
AccumulatedGas(100 Watt)_5f AI Wattage values (Unit : 100Watt)
DustSensorAvail_5f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5f BO Stop(0) Run(1)
AirCleaningOperStatus_5f BI Stop(0) Run(1)
FineDustStatus_5f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5f AI %
ComfortCoolingAvail_5f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5f BO Stop(0) Run(1)
ComfortCoolingOperStatus_5f BI Stop(0) Run(1)
ComfortCoolingStepCommand_5f AV 1~3 step
ComfortCoolingStepStatus_5f AI 1~3 step
HumanDetectionAvail_5f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5f MO Off(1)
HumanDetectionOperStatus_5f MI Off(1)
HumanDetectionWindCommand_5f MO Off(1)
HumanDetectionWindStatus_5f MI Off(1)
HumanDetectionTimeCommand_5f MO 5min(1)
HumanDetectionTimeStatus_5f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
60 ※ Dev Type AC
address

instance
point Name
number

24577 1 On/Off (Setting)


24578 2 On/Off (Status)
24579 3 Lock (Setting)
24580 4 Lock (Status)
24581 5 Filter Sign
24582 6 Filter Sign reset
24583 7 Operation Mode (Setting)
24584 8 Operation Mode (Status)
24585 9 Swing (Setting)
24586 10 Swing (Status)
24587 11 Fan Speed (Setting)
24588 12 Fan Speed (Status)
24589 13 Set Room Temperature
24590 14 Room Temperature
24591 15 Alarm
24592 16 Error Code
24595 19 Set Temperature (Status)
24596 20 Accumulated Power Distribution (Status)
24603 27 Set Upper Temperature (Setting)
24604 28 Set Lower Temperature (Setting)
24605 29 Set Upper Tempaerature (Status)
24606 30 Set Lower Temperature (Status)
24607 31 Mode Lock (Setting)
24608 32 Mode Lock (Status)
24609 33 Fan Lock (Setting)
24610 34 Fan Lock (Status)
24611 35 Occupancy (Setting)
24612 36 Occupancy (Status)
24613 37 2Set Cooling Set Temperature (Setting)
24614 38 2Set Cooling Set Temperature (Status)
24615 39 2Set Heating Set Temperature (Setting)
24616 40 2Set Heating Set Temperature (Status)
24617 41 2Set Cooling Upper Temperature (Setting)
24618 42 2Set Cooling Upper Temperature (Status)
24619 43 2Set Heating Upper Temperature (Setting)
24620 44 2Set Heating Upper Temperature (Status)
24621 45 2Set Cooling Lower Temperature (Setting)
24622 46 2Set Cooling Lower Temperature (Status)
24623 47 2Set Heating Lower Temperature (Setting)
24624 48 2Set Heating Lower Temperature (Status)
24625 49 Thermo Status (Status)
24626 50 Accumulated Gas Distribution (Status)
24627 51 Dust Sensor Available (Status)
24628 52 Air Cleaning Opereration (Setting)
24629 53 Air Cleaning Opereration (Status)
24630 54 Fine Dust (Status)
24631 55 Ultra Fine Dust (Status)
24632 56 Super Ultra Fine Dust (Status)
24633 57 Humidity (Status)
24634 58 Comfort Cooling Available (Status)
24635 59 Comfort Cooling Opereration (Setting)
24636 60 Comfort Cooling Opereration (Status)
24637 61 Comfort Cooling Step (Setting)
24638 62 Comfort Cooling Step (Status)
24639 63 Human Detection Available (Status)
24640 64 Human Detection Opereration (Setting)
24641 65 Human Detection Opereration (Status)
24642 66 Human Detection Wind (Setting)
24643 67 Human Detection Wind (Status)
24644 68 Human Detection Time (Setting)
24645 69 Human Detection Time (Status)
24646 70 Hotel Checkin (Setting)
24647 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_60 BO Stop(0) Start(1)
StartStopStatus_60 BI Stop(0) Start(1)
LockCommand_60 BO Permit(0) Prohibit(1)
LockStatus_60 BI Permit(0) Prohibit(1)
FilterSign_60 BI Off(0) On(1)
FilterSignReset_60 BV - Reset(1)
AirConModeCommand_60 MO Cool(1)
AirConModeStatus_60 MI Cool(1)
SwingCommand_60 BO Stop(0) Run(1)
SwingStatus_60 BI Stop(0) Run(1)
FanSpeedCommand_60 MO Low(1)
FanSpeedStatus_60 MI Low(1)
SetRoomTemp_60 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_60 AI ℃
Alarm_60 BI Normal(0) Abnormal(1)
MalfunctionCode_60 AI Refer to the
SetTempStatus_60 AI ℃
Accumulated power(100 Watt)_60 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_60 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_60 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_60 AI ℃
TempRangeLowerLimitStatus_60 AI ℃
ModeLockCommand_60 BO Permit(0) Prohibit(1)
ModeLockStatus_60 BI Permit(0) Prohibit(1)
FanLockCommand_60 BO Permit(0) Prohibit(1)
FanLockStatus_60 BI Permit(0) Prohibit(1)
OccupancyCommand_60 BO Unoccupied(0) Occupied(1)
OccupancyStatus_60 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_60 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_60 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_60 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_60 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_60 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_60 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_60 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_60 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_60 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_60 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_60 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_60 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_60 BI Off(0) On(1)
AccumulatedGas(100 Watt)_60 AI Wattage values (Unit : 100Watt)
DustSensorAvail_60 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_60 BO Stop(0) Run(1)
AirCleaningOperStatus_60 BI Stop(0) Run(1)
FineDustStatus_60 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_60 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_60 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_60 AI %
ComfortCoolingAvail_60 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_60 BO Stop(0) Run(1)
ComfortCoolingOperStatus_60 BI Stop(0) Run(1)
ComfortCoolingStepCommand_60 AV 1~3 step
ComfortCoolingStepStatus_60 AI 1~3 step
HumanDetectionAvail_60 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_60 MO Off(1)
HumanDetectionOperStatus_60 MI Off(1)
HumanDetectionWindCommand_60 MO Off(1)
HumanDetectionWindStatus_60 MI Off(1)
HumanDetectionTimeCommand_60 MO 5min(1)
HumanDetectionTimeStatus_60 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
61 ※ Dev Type AC
address

instance
point Name
number

24833 1 On/Off (Setting)


24834 2 On/Off (Status)
24835 3 Lock (Setting)
24836 4 Lock (Status)
24837 5 Filter Sign
24838 6 Filter Sign reset
24839 7 Operation Mode (Setting)
24840 8 Operation Mode (Status)
24841 9 Swing (Setting)
24842 10 Swing (Status)
24843 11 Fan Speed (Setting)
24844 12 Fan Speed (Status)
24845 13 Set Room Temperature
24846 14 Room Temperature
24847 15 Alarm
24848 16 Error Code
24851 19 Set Temperature (Status)
24852 20 Accumulated Power Distribution (Status)
24859 27 Set Upper Temperature (Setting)
24860 28 Set Lower Temperature (Setting)
24861 29 Set Upper Tempaerature (Status)
24862 30 Set Lower Temperature (Status)
24863 31 Mode Lock (Setting)
24864 32 Mode Lock (Status)
24865 33 Fan Lock (Setting)
24866 34 Fan Lock (Status)
24867 35 Occupancy (Setting)
24868 36 Occupancy (Status)
24869 37 2Set Cooling Set Temperature (Setting)
24870 38 2Set Cooling Set Temperature (Status)
24871 39 2Set Heating Set Temperature (Setting)
24872 40 2Set Heating Set Temperature (Status)
24873 41 2Set Cooling Upper Temperature (Setting)
24874 42 2Set Cooling Upper Temperature (Status)
24875 43 2Set Heating Upper Temperature (Setting)
24876 44 2Set Heating Upper Temperature (Status)
24877 45 2Set Cooling Lower Temperature (Setting)
24878 46 2Set Cooling Lower Temperature (Status)
24879 47 2Set Heating Lower Temperature (Setting)
24880 48 2Set Heating Lower Temperature (Status)
24881 49 Thermo Status (Status)
24882 50 Accumulated Gas Distribution (Status)
24883 51 Dust Sensor Available (Status)
24884 52 Air Cleaning Opereration (Setting)
24885 53 Air Cleaning Opereration (Status)
24886 54 Fine Dust (Status)
24887 55 Ultra Fine Dust (Status)
24888 56 Super Ultra Fine Dust (Status)
24889 57 Humidity (Status)
24890 58 Comfort Cooling Available (Status)
24891 59 Comfort Cooling Opereration (Setting)
24892 60 Comfort Cooling Opereration (Status)
24893 61 Comfort Cooling Step (Setting)
24894 62 Comfort Cooling Step (Status)
24895 63 Human Detection Available (Status)
24896 64 Human Detection Opereration (Setting)
24897 65 Human Detection Opereration (Status)
24898 66 Human Detection Wind (Setting)
24899 67 Human Detection Wind (Status)
24900 68 Human Detection Time (Setting)
24901 69 Human Detection Time (Status)
24902 70 Hotel Checkin (Setting)
24903 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_61 BO Stop(0) Start(1)
StartStopStatus_61 BI Stop(0) Start(1)
LockCommand_61 BO Permit(0) Prohibit(1)
LockStatus_61 BI Permit(0) Prohibit(1)
FilterSign_61 BI Off(0) On(1)
FilterSignReset_61 BV - Reset(1)
AirConModeCommand_61 MO Cool(1)
AirConModeStatus_61 MI Cool(1)
SwingCommand_61 BO Stop(0) Run(1)
SwingStatus_61 BI Stop(0) Run(1)
FanSpeedCommand_61 MO Low(1)
FanSpeedStatus_61 MI Low(1)
SetRoomTemp_61 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_61 AI ℃
Alarm_61 BI Normal(0) Abnormal(1)
MalfunctionCode_61 AI Refer to the
SetTempStatus_61 AI ℃
Accumulated power(100 Watt)_61 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_61 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_61 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_61 AI ℃
TempRangeLowerLimitStatus_61 AI ℃
ModeLockCommand_61 BO Permit(0) Prohibit(1)
ModeLockStatus_61 BI Permit(0) Prohibit(1)
FanLockCommand_61 BO Permit(0) Prohibit(1)
FanLockStatus_61 BI Permit(0) Prohibit(1)
OccupancyCommand_61 BO Unoccupied(0) Occupied(1)
OccupancyStatus_61 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_61 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_61 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_61 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_61 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_61 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_61 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_61 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_61 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_61 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_61 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_61 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_61 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_61 BI Off(0) On(1)
AccumulatedGas(100 Watt)_61 AI Wattage values (Unit : 100Watt)
DustSensorAvail_61 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_61 BO Stop(0) Run(1)
AirCleaningOperStatus_61 BI Stop(0) Run(1)
FineDustStatus_61 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_61 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_61 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_61 AI %
ComfortCoolingAvail_61 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_61 BO Stop(0) Run(1)
ComfortCoolingOperStatus_61 BI Stop(0) Run(1)
ComfortCoolingStepCommand_61 AV 1~3 step
ComfortCoolingStepStatus_61 AI 1~3 step
HumanDetectionAvail_61 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_61 MO Off(1)
HumanDetectionOperStatus_61 MI Off(1)
HumanDetectionWindCommand_61 MO Off(1)
HumanDetectionWindStatus_61 MI Off(1)
HumanDetectionTimeCommand_61 MO 5min(1)
HumanDetectionTimeStatus_61 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
62 ※ Dev Type AC
address

instance
point Name
number

25089 1 On/Off (Setting)


25090 2 On/Off (Status)
25091 3 Lock (Setting)
25092 4 Lock (Status)
25093 5 Filter Sign
25094 6 Filter Sign reset
25095 7 Operation Mode (Setting)
25096 8 Operation Mode (Status)
25097 9 Swing (Setting)
25098 10 Swing (Status)
25099 11 Fan Speed (Setting)
25100 12 Fan Speed (Status)
25101 13 Set Room Temperature
25102 14 Room Temperature
25103 15 Alarm
25104 16 Error Code
25107 19 Set Temperature (Status)
25108 20 Accumulated Power Distribution (Status)
25115 27 Set Upper Temperature (Setting)
25116 28 Set Lower Temperature (Setting)
25117 29 Set Upper Tempaerature (Status)
25118 30 Set Lower Temperature (Status)
25119 31 Mode Lock (Setting)
25120 32 Mode Lock (Status)
25121 33 Fan Lock (Setting)
25122 34 Fan Lock (Status)
25123 35 Occupancy (Setting)
25124 36 Occupancy (Status)
25125 37 2Set Cooling Set Temperature (Setting)
25126 38 2Set Cooling Set Temperature (Status)
25127 39 2Set Heating Set Temperature (Setting)
25128 40 2Set Heating Set Temperature (Status)
25129 41 2Set Cooling Upper Temperature (Setting)
25130 42 2Set Cooling Upper Temperature (Status)
25131 43 2Set Heating Upper Temperature (Setting)
25132 44 2Set Heating Upper Temperature (Status)
25133 45 2Set Cooling Lower Temperature (Setting)
25134 46 2Set Cooling Lower Temperature (Status)
25135 47 2Set Heating Lower Temperature (Setting)
25136 48 2Set Heating Lower Temperature (Status)
25137 49 Thermo Status (Status)
25138 50 Accumulated Gas Distribution (Status)
25139 51 Dust Sensor Available (Status)
25140 52 Air Cleaning Opereration (Setting)
25141 53 Air Cleaning Opereration (Status)
25142 54 Fine Dust (Status)
25143 55 Ultra Fine Dust (Status)
25144 56 Super Ultra Fine Dust (Status)
25145 57 Humidity (Status)
25146 58 Comfort Cooling Available (Status)
25147 59 Comfort Cooling Opereration (Setting)
25148 60 Comfort Cooling Opereration (Status)
25149 61 Comfort Cooling Step (Setting)
25150 62 Comfort Cooling Step (Status)
25151 63 Human Detection Available (Status)
25152 64 Human Detection Opereration (Setting)
25153 65 Human Detection Opereration (Status)
25154 66 Human Detection Wind (Setting)
25155 67 Human Detection Wind (Status)
25156 68 Human Detection Time (Setting)
25157 69 Human Detection Time (Status)
25158 70 Hotel Checkin (Setting)
25159 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_62 BO Stop(0) Start(1)
StartStopStatus_62 BI Stop(0) Start(1)
LockCommand_62 BO Permit(0) Prohibit(1)
LockStatus_62 BI Permit(0) Prohibit(1)
FilterSign_62 BI Off(0) On(1)
FilterSignReset_62 BV - Reset(1)
AirConModeCommand_62 MO Cool(1)
AirConModeStatus_62 MI Cool(1)
SwingCommand_62 BO Stop(0) Run(1)
SwingStatus_62 BI Stop(0) Run(1)
FanSpeedCommand_62 MO Low(1)
FanSpeedStatus_62 MI Low(1)
SetRoomTemp_62 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_62 AI ℃
Alarm_62 BI Normal(0) Abnormal(1)
MalfunctionCode_62 AI Refer to the
SetTempStatus_62 AI ℃
Accumulated power(100 Watt)_62 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_62 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_62 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_62 AI ℃
TempRangeLowerLimitStatus_62 AI ℃
ModeLockCommand_62 BO Permit(0) Prohibit(1)
ModeLockStatus_62 BI Permit(0) Prohibit(1)
FanLockCommand_62 BO Permit(0) Prohibit(1)
FanLockStatus_62 BI Permit(0) Prohibit(1)
OccupancyCommand_62 BO Unoccupied(0) Occupied(1)
OccupancyStatus_62 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_62 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_62 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_62 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_62 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_62 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_62 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_62 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_62 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_62 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_62 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_62 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_62 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_62 BI Off(0) On(1)
AccumulatedGas(100 Watt)_62 AI Wattage values (Unit : 100Watt)
DustSensorAvail_62 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_62 BO Stop(0) Run(1)
AirCleaningOperStatus_62 BI Stop(0) Run(1)
FineDustStatus_62 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_62 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_62 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_62 AI %
ComfortCoolingAvail_62 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_62 BO Stop(0) Run(1)
ComfortCoolingOperStatus_62 BI Stop(0) Run(1)
ComfortCoolingStepCommand_62 AV 1~3 step
ComfortCoolingStepStatus_62 AI 1~3 step
HumanDetectionAvail_62 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_62 MO Off(1)
HumanDetectionOperStatus_62 MI Off(1)
HumanDetectionWindCommand_62 MO Off(1)
HumanDetectionWindStatus_62 MI Off(1)
HumanDetectionTimeCommand_62 MO 5min(1)
HumanDetectionTimeStatus_62 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
63 ※ Dev Type AC
address

instance
point Name
number

25345 1 On/Off (Setting)


25346 2 On/Off (Status)
25347 3 Lock (Setting)
25348 4 Lock (Status)
25349 5 Filter Sign
25350 6 Filter Sign reset
25351 7 Operation Mode (Setting)
25352 8 Operation Mode (Status)
25353 9 Swing (Setting)
25354 10 Swing (Status)
25355 11 Fan Speed (Setting)
25356 12 Fan Speed (Status)
25357 13 Set Room Temperature
25358 14 Room Temperature
25359 15 Alarm
25360 16 Error Code
25363 19 Set Temperature (Status)
25364 20 Accumulated Power Distribution (Status)
25371 27 Set Upper Temperature (Setting)
25372 28 Set Lower Temperature (Setting)
25373 29 Set Upper Tempaerature (Status)
25374 30 Set Lower Temperature (Status)
25375 31 Mode Lock (Setting)
25376 32 Mode Lock (Status)
25377 33 Fan Lock (Setting)
25378 34 Fan Lock (Status)
25379 35 Occupancy (Setting)
25380 36 Occupancy (Status)
25381 37 2Set Cooling Set Temperature (Setting)
25382 38 2Set Cooling Set Temperature (Status)
25383 39 2Set Heating Set Temperature (Setting)
25384 40 2Set Heating Set Temperature (Status)
25385 41 2Set Cooling Upper Temperature (Setting)
25386 42 2Set Cooling Upper Temperature (Status)
25387 43 2Set Heating Upper Temperature (Setting)
25388 44 2Set Heating Upper Temperature (Status)
25389 45 2Set Cooling Lower Temperature (Setting)
25390 46 2Set Cooling Lower Temperature (Status)
25391 47 2Set Heating Lower Temperature (Setting)
25392 48 2Set Heating Lower Temperature (Status)
25393 49 Thermo Status (Status)
25394 50 Accumulated Gas Distribution (Status)
25395 51 Dust Sensor Available (Status)
25396 52 Air Cleaning Opereration (Setting)
25397 53 Air Cleaning Opereration (Status)
25398 54 Fine Dust (Status)
25399 55 Ultra Fine Dust (Status)
25400 56 Super Ultra Fine Dust (Status)
25401 57 Humidity (Status)
25402 58 Comfort Cooling Available (Status)
25403 59 Comfort Cooling Opereration (Setting)
25404 60 Comfort Cooling Opereration (Status)
25405 61 Comfort Cooling Step (Setting)
25406 62 Comfort Cooling Step (Status)
25407 63 Human Detection Available (Status)
25408 64 Human Detection Opereration (Setting)
25409 65 Human Detection Opereration (Status)
25410 66 Human Detection Wind (Setting)
25411 67 Human Detection Wind (Status)
25412 68 Human Detection Time (Setting)
25413 69 Human Detection Time (Status)
25414 70 Hotel Checkin (Setting)
25415 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_63 BO Stop(0) Start(1)
StartStopStatus_63 BI Stop(0) Start(1)
LockCommand_63 BO Permit(0) Prohibit(1)
LockStatus_63 BI Permit(0) Prohibit(1)
FilterSign_63 BI Off(0) On(1)
FilterSignReset_63 BV - Reset(1)
AirConModeCommand_63 MO Cool(1)
AirConModeStatus_63 MI Cool(1)
SwingCommand_63 BO Stop(0) Run(1)
SwingStatus_63 BI Stop(0) Run(1)
FanSpeedCommand_63 MO Low(1)
FanSpeedStatus_63 MI Low(1)
SetRoomTemp_63 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_63 AI ℃
Alarm_63 BI Normal(0) Abnormal(1)
MalfunctionCode_63 AI Refer to the
SetTempStatus_63 AI ℃
Accumulated power(100 Watt)_63 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_63 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_63 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_63 AI ℃
TempRangeLowerLimitStatus_63 AI ℃
ModeLockCommand_63 BO Permit(0) Prohibit(1)
ModeLockStatus_63 BI Permit(0) Prohibit(1)
FanLockCommand_63 BO Permit(0) Prohibit(1)
FanLockStatus_63 BI Permit(0) Prohibit(1)
OccupancyCommand_63 BO Unoccupied(0) Occupied(1)
OccupancyStatus_63 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_63 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_63 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_63 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_63 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_63 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_63 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_63 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_63 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_63 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_63 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_63 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_63 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_63 BI Off(0) On(1)
AccumulatedGas(100 Watt)_63 AI Wattage values (Unit : 100Watt)
DustSensorAvail_63 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_63 BO Stop(0) Run(1)
AirCleaningOperStatus_63 BI Stop(0) Run(1)
FineDustStatus_63 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_63 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_63 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_63 AI %
ComfortCoolingAvail_63 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_63 BO Stop(0) Run(1)
ComfortCoolingOperStatus_63 BI Stop(0) Run(1)
ComfortCoolingStepCommand_63 AV 1~3 step
ComfortCoolingStepStatus_63 AI 1~3 step
HumanDetectionAvail_63 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_63 MO Off(1)
HumanDetectionOperStatus_63 MI Off(1)
HumanDetectionWindCommand_63 MO Off(1)
HumanDetectionWindStatus_63 MI Off(1)
HumanDetectionTimeCommand_63 MO 5min(1)
HumanDetectionTimeStatus_63 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
64 ※ Dev Type AC
address

instance
point Name
number

25601 1 On/Off (Setting)


25602 2 On/Off (Status)
25603 3 Lock (Setting)
25604 4 Lock (Status)
25605 5 Filter Sign
25606 6 Filter Sign reset
25607 7 Operation Mode (Setting)
25608 8 Operation Mode (Status)
25609 9 Swing (Setting)
25610 10 Swing (Status)
25611 11 Fan Speed (Setting)
25612 12 Fan Speed (Status)
25613 13 Set Room Temperature
25614 14 Room Temperature
25615 15 Alarm
25616 16 Error Code
25619 19 Set Temperature (Status)
25620 20 Accumulated Power Distribution (Status)
25627 27 Set Upper Temperature (Setting)
25628 28 Set Lower Temperature (Setting)
25629 29 Set Upper Tempaerature (Status)
25630 30 Set Lower Temperature (Status)
25631 31 Mode Lock (Setting)
25632 32 Mode Lock (Status)
25633 33 Fan Lock (Setting)
25634 34 Fan Lock (Status)
25635 35 Occupancy (Setting)
25636 36 Occupancy (Status)
25637 37 2Set Cooling Set Temperature (Setting)
25638 38 2Set Cooling Set Temperature (Status)
25639 39 2Set Heating Set Temperature (Setting)
25640 40 2Set Heating Set Temperature (Status)
25641 41 2Set Cooling Upper Temperature (Setting)
25642 42 2Set Cooling Upper Temperature (Status)
25643 43 2Set Heating Upper Temperature (Setting)
25644 44 2Set Heating Upper Temperature (Status)
25645 45 2Set Cooling Lower Temperature (Setting)
25646 46 2Set Cooling Lower Temperature (Status)
25647 47 2Set Heating Lower Temperature (Setting)
25648 48 2Set Heating Lower Temperature (Status)
25649 49 Thermo Status (Status)
25650 50 Accumulated Gas Distribution (Status)
25651 51 Dust Sensor Available (Status)
25652 52 Air Cleaning Opereration (Setting)
25653 53 Air Cleaning Opereration (Status)
25654 54 Fine Dust (Status)
25655 55 Ultra Fine Dust (Status)
25656 56 Super Ultra Fine Dust (Status)
25657 57 Humidity (Status)
25658 58 Comfort Cooling Available (Status)
25659 59 Comfort Cooling Opereration (Setting)
25660 60 Comfort Cooling Opereration (Status)
25661 61 Comfort Cooling Step (Setting)
25662 62 Comfort Cooling Step (Status)
25663 63 Human Detection Available (Status)
25664 64 Human Detection Opereration (Setting)
25665 65 Human Detection Opereration (Status)
25666 66 Human Detection Wind (Setting)
25667 67 Human Detection Wind (Status)
25668 68 Human Detection Time (Setting)
25669 69 Human Detection Time (Status)
25670 70 Hotel Checkin (Setting)
25671 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_64 BO Stop(0) Start(1)
StartStopStatus_64 BI Stop(0) Start(1)
LockCommand_64 BO Permit(0) Prohibit(1)
LockStatus_64 BI Permit(0) Prohibit(1)
FilterSign_64 BI Off(0) On(1)
FilterSignReset_64 BV - Reset(1)
AirConModeCommand_64 MO Cool(1)
AirConModeStatus_64 MI Cool(1)
SwingCommand_64 BO Stop(0) Run(1)
SwingStatus_64 BI Stop(0) Run(1)
FanSpeedCommand_64 MO Low(1)
FanSpeedStatus_64 MI Low(1)
SetRoomTemp_64 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_64 AI ℃
Alarm_64 BI Normal(0) Abnormal(1)
MalfunctionCode_64 AI Refer to the
SetTempStatus_64 AI ℃
Accumulated power(100 Watt)_64 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_64 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_64 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_64 AI ℃
TempRangeLowerLimitStatus_64 AI ℃
ModeLockCommand_64 BO Permit(0) Prohibit(1)
ModeLockStatus_64 BI Permit(0) Prohibit(1)
FanLockCommand_64 BO Permit(0) Prohibit(1)
FanLockStatus_64 BI Permit(0) Prohibit(1)
OccupancyCommand_64 BO Unoccupied(0) Occupied(1)
OccupancyStatus_64 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_64 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_64 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_64 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_64 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_64 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_64 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_64 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_64 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_64 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_64 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_64 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_64 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_64 BI Off(0) On(1)
AccumulatedGas(100 Watt)_64 AI Wattage values (Unit : 100Watt)
DustSensorAvail_64 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_64 BO Stop(0) Run(1)
AirCleaningOperStatus_64 BI Stop(0) Run(1)
FineDustStatus_64 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_64 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_64 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_64 AI %
ComfortCoolingAvail_64 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_64 BO Stop(0) Run(1)
ComfortCoolingOperStatus_64 BI Stop(0) Run(1)
ComfortCoolingStepCommand_64 AV 1~3 step
ComfortCoolingStepStatus_64 AI 1~3 step
HumanDetectionAvail_64 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_64 MO Off(1)
HumanDetectionOperStatus_64 MI Off(1)
HumanDetectionWindCommand_64 MO Off(1)
HumanDetectionWindStatus_64 MI Off(1)
HumanDetectionTimeCommand_64 MO 5min(1)
HumanDetectionTimeStatus_64 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
65 ※ Dev Type AC
address

instance
point Name
number

25857 1 On/Off (Setting)


25858 2 On/Off (Status)
25859 3 Lock (Setting)
25860 4 Lock (Status)
25861 5 Filter Sign
25862 6 Filter Sign reset
25863 7 Operation Mode (Setting)
25864 8 Operation Mode (Status)
25865 9 Swing (Setting)
25866 10 Swing (Status)
25867 11 Fan Speed (Setting)
25868 12 Fan Speed (Status)
25869 13 Set Room Temperature
25870 14 Room Temperature
25871 15 Alarm
25872 16 Error Code
25875 19 Set Temperature (Status)
25876 20 Accumulated Power Distribution (Status)
25883 27 Set Upper Temperature (Setting)
25884 28 Set Lower Temperature (Setting)
25885 29 Set Upper Tempaerature (Status)
25886 30 Set Lower Temperature (Status)
25887 31 Mode Lock (Setting)
25888 32 Mode Lock (Status)
25889 33 Fan Lock (Setting)
25890 34 Fan Lock (Status)
25891 35 Occupancy (Setting)
25892 36 Occupancy (Status)
25893 37 2Set Cooling Set Temperature (Setting)
25894 38 2Set Cooling Set Temperature (Status)
25895 39 2Set Heating Set Temperature (Setting)
25896 40 2Set Heating Set Temperature (Status)
25897 41 2Set Cooling Upper Temperature (Setting)
25898 42 2Set Cooling Upper Temperature (Status)
25899 43 2Set Heating Upper Temperature (Setting)
25900 44 2Set Heating Upper Temperature (Status)
25901 45 2Set Cooling Lower Temperature (Setting)
25902 46 2Set Cooling Lower Temperature (Status)
25903 47 2Set Heating Lower Temperature (Setting)
25904 48 2Set Heating Lower Temperature (Status)
25905 49 Thermo Status (Status)
25906 50 Accumulated Gas Distribution (Status)
25907 51 Dust Sensor Available (Status)
25908 52 Air Cleaning Opereration (Setting)
25909 53 Air Cleaning Opereration (Status)
25910 54 Fine Dust (Status)
25911 55 Ultra Fine Dust (Status)
25912 56 Super Ultra Fine Dust (Status)
25913 57 Humidity (Status)
25914 58 Comfort Cooling Available (Status)
25915 59 Comfort Cooling Opereration (Setting)
25916 60 Comfort Cooling Opereration (Status)
25917 61 Comfort Cooling Step (Setting)
25918 62 Comfort Cooling Step (Status)
25919 63 Human Detection Available (Status)
25920 64 Human Detection Opereration (Setting)
25921 65 Human Detection Opereration (Status)
25922 66 Human Detection Wind (Setting)
25923 67 Human Detection Wind (Status)
25924 68 Human Detection Time (Setting)
25925 69 Human Detection Time (Status)
25926 70 Hotel Checkin (Setting)
25927 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_65 BO Stop(0) Start(1)
StartStopStatus_65 BI Stop(0) Start(1)
LockCommand_65 BO Permit(0) Prohibit(1)
LockStatus_65 BI Permit(0) Prohibit(1)
FilterSign_65 BI Off(0) On(1)
FilterSignReset_65 BV - Reset(1)
AirConModeCommand_65 MO Cool(1)
AirConModeStatus_65 MI Cool(1)
SwingCommand_65 BO Stop(0) Run(1)
SwingStatus_65 BI Stop(0) Run(1)
FanSpeedCommand_65 MO Low(1)
FanSpeedStatus_65 MI Low(1)
SetRoomTemp_65 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_65 AI ℃
Alarm_65 BI Normal(0) Abnormal(1)
MalfunctionCode_65 AI Refer to the
SetTempStatus_65 AI ℃
Accumulated power(100 Watt)_65 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_65 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_65 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_65 AI ℃
TempRangeLowerLimitStatus_65 AI ℃
ModeLockCommand_65 BO Permit(0) Prohibit(1)
ModeLockStatus_65 BI Permit(0) Prohibit(1)
FanLockCommand_65 BO Permit(0) Prohibit(1)
FanLockStatus_65 BI Permit(0) Prohibit(1)
OccupancyCommand_65 BO Unoccupied(0) Occupied(1)
OccupancyStatus_65 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_65 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_65 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_65 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_65 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_65 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_65 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_65 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_65 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_65 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_65 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_65 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_65 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_65 BI Off(0) On(1)
AccumulatedGas(100 Watt)_65 AI Wattage values (Unit : 100Watt)
DustSensorAvail_65 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_65 BO Stop(0) Run(1)
AirCleaningOperStatus_65 BI Stop(0) Run(1)
FineDustStatus_65 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_65 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_65 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_65 AI %
ComfortCoolingAvail_65 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_65 BO Stop(0) Run(1)
ComfortCoolingOperStatus_65 BI Stop(0) Run(1)
ComfortCoolingStepCommand_65 AV 1~3 step
ComfortCoolingStepStatus_65 AI 1~3 step
HumanDetectionAvail_65 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_65 MO Off(1)
HumanDetectionOperStatus_65 MI Off(1)
HumanDetectionWindCommand_65 MO Off(1)
HumanDetectionWindStatus_65 MI Off(1)
HumanDetectionTimeCommand_65 MO 5min(1)
HumanDetectionTimeStatus_65 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
66 ※ Dev Type AC
address

instance
point Name
number

26113 1 On/Off (Setting)


26114 2 On/Off (Status)
26115 3 Lock (Setting)
26116 4 Lock (Status)
26117 5 Filter Sign
26118 6 Filter Sign reset
26119 7 Operation Mode (Setting)
26120 8 Operation Mode (Status)
26121 9 Swing (Setting)
26122 10 Swing (Status)
26123 11 Fan Speed (Setting)
26124 12 Fan Speed (Status)
26125 13 Set Room Temperature
26126 14 Room Temperature
26127 15 Alarm
26128 16 Error Code
26131 19 Set Temperature (Status)
26132 20 Accumulated Power Distribution (Status)
26139 27 Set Upper Temperature (Setting)
26140 28 Set Lower Temperature (Setting)
26141 29 Set Upper Tempaerature (Status)
26142 30 Set Lower Temperature (Status)
26143 31 Mode Lock (Setting)
26144 32 Mode Lock (Status)
26145 33 Fan Lock (Setting)
26146 34 Fan Lock (Status)
26147 35 Occupancy (Setting)
26148 36 Occupancy (Status)
26149 37 2Set Cooling Set Temperature (Setting)
26150 38 2Set Cooling Set Temperature (Status)
26151 39 2Set Heating Set Temperature (Setting)
26152 40 2Set Heating Set Temperature (Status)
26153 41 2Set Cooling Upper Temperature (Setting)
26154 42 2Set Cooling Upper Temperature (Status)
26155 43 2Set Heating Upper Temperature (Setting)
26156 44 2Set Heating Upper Temperature (Status)
26157 45 2Set Cooling Lower Temperature (Setting)
26158 46 2Set Cooling Lower Temperature (Status)
26159 47 2Set Heating Lower Temperature (Setting)
26160 48 2Set Heating Lower Temperature (Status)
26161 49 Thermo Status (Status)
26162 50 Accumulated Gas Distribution (Status)
26163 51 Dust Sensor Available (Status)
26164 52 Air Cleaning Opereration (Setting)
26165 53 Air Cleaning Opereration (Status)
26166 54 Fine Dust (Status)
26167 55 Ultra Fine Dust (Status)
26168 56 Super Ultra Fine Dust (Status)
26169 57 Humidity (Status)
26170 58 Comfort Cooling Available (Status)
26171 59 Comfort Cooling Opereration (Setting)
26172 60 Comfort Cooling Opereration (Status)
26173 61 Comfort Cooling Step (Setting)
26174 62 Comfort Cooling Step (Status)
26175 63 Human Detection Available (Status)
26176 64 Human Detection Opereration (Setting)
26177 65 Human Detection Opereration (Status)
26178 66 Human Detection Wind (Setting)
26179 67 Human Detection Wind (Status)
26180 68 Human Detection Time (Setting)
26181 69 Human Detection Time (Status)
26182 70 Hotel Checkin (Setting)
26183 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_66 BO Stop(0) Start(1)
StartStopStatus_66 BI Stop(0) Start(1)
LockCommand_66 BO Permit(0) Prohibit(1)
LockStatus_66 BI Permit(0) Prohibit(1)
FilterSign_66 BI Off(0) On(1)
FilterSignReset_66 BV - Reset(1)
AirConModeCommand_66 MO Cool(1)
AirConModeStatus_66 MI Cool(1)
SwingCommand_66 BO Stop(0) Run(1)
SwingStatus_66 BI Stop(0) Run(1)
FanSpeedCommand_66 MO Low(1)
FanSpeedStatus_66 MI Low(1)
SetRoomTemp_66 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_66 AI ℃
Alarm_66 BI Normal(0) Abnormal(1)
MalfunctionCode_66 AI Refer to the
SetTempStatus_66 AI ℃
Accumulated power(100 Watt)_66 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_66 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_66 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_66 AI ℃
TempRangeLowerLimitStatus_66 AI ℃
ModeLockCommand_66 BO Permit(0) Prohibit(1)
ModeLockStatus_66 BI Permit(0) Prohibit(1)
FanLockCommand_66 BO Permit(0) Prohibit(1)
FanLockStatus_66 BI Permit(0) Prohibit(1)
OccupancyCommand_66 BO Unoccupied(0) Occupied(1)
OccupancyStatus_66 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_66 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_66 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_66 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_66 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_66 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_66 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_66 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_66 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_66 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_66 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_66 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_66 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_66 BI Off(0) On(1)
AccumulatedGas(100 Watt)_66 AI Wattage values (Unit : 100Watt)
DustSensorAvail_66 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_66 BO Stop(0) Run(1)
AirCleaningOperStatus_66 BI Stop(0) Run(1)
FineDustStatus_66 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_66 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_66 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_66 AI %
ComfortCoolingAvail_66 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_66 BO Stop(0) Run(1)
ComfortCoolingOperStatus_66 BI Stop(0) Run(1)
ComfortCoolingStepCommand_66 AV 1~3 step
ComfortCoolingStepStatus_66 AI 1~3 step
HumanDetectionAvail_66 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_66 MO Off(1)
HumanDetectionOperStatus_66 MI Off(1)
HumanDetectionWindCommand_66 MO Off(1)
HumanDetectionWindStatus_66 MI Off(1)
HumanDetectionTimeCommand_66 MO 5min(1)
HumanDetectionTimeStatus_66 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
67 ※ Dev Type AC
address

instance
point Name
number

26369 1 On/Off (Setting)


26370 2 On/Off (Status)
26371 3 Lock (Setting)
26372 4 Lock (Status)
26373 5 Filter Sign
26374 6 Filter Sign reset
26375 7 Operation Mode (Setting)
26376 8 Operation Mode (Status)
26377 9 Swing (Setting)
26378 10 Swing (Status)
26379 11 Fan Speed (Setting)
26380 12 Fan Speed (Status)
26381 13 Set Room Temperature
26382 14 Room Temperature
26383 15 Alarm
26384 16 Error Code
26387 19 Set Temperature (Status)
26388 20 Accumulated Power Distribution (Status)
26395 27 Set Upper Temperature (Setting)
26396 28 Set Lower Temperature (Setting)
26397 29 Set Upper Tempaerature (Status)
26398 30 Set Lower Temperature (Status)
26399 31 Mode Lock (Setting)
26400 32 Mode Lock (Status)
26401 33 Fan Lock (Setting)
26402 34 Fan Lock (Status)
26403 35 Occupancy (Setting)
26404 36 Occupancy (Status)
26405 37 2Set Cooling Set Temperature (Setting)
26406 38 2Set Cooling Set Temperature (Status)
26407 39 2Set Heating Set Temperature (Setting)
26408 40 2Set Heating Set Temperature (Status)
26409 41 2Set Cooling Upper Temperature (Setting)
26410 42 2Set Cooling Upper Temperature (Status)
26411 43 2Set Heating Upper Temperature (Setting)
26412 44 2Set Heating Upper Temperature (Status)
26413 45 2Set Cooling Lower Temperature (Setting)
26414 46 2Set Cooling Lower Temperature (Status)
26415 47 2Set Heating Lower Temperature (Setting)
26416 48 2Set Heating Lower Temperature (Status)
26417 49 Thermo Status (Status)
26418 50 Accumulated Gas Distribution (Status)
26419 51 Dust Sensor Available (Status)
26420 52 Air Cleaning Opereration (Setting)
26421 53 Air Cleaning Opereration (Status)
26422 54 Fine Dust (Status)
26423 55 Ultra Fine Dust (Status)
26424 56 Super Ultra Fine Dust (Status)
26425 57 Humidity (Status)
26426 58 Comfort Cooling Available (Status)
26427 59 Comfort Cooling Opereration (Setting)
26428 60 Comfort Cooling Opereration (Status)
26429 61 Comfort Cooling Step (Setting)
26430 62 Comfort Cooling Step (Status)
26431 63 Human Detection Available (Status)
26432 64 Human Detection Opereration (Setting)
26433 65 Human Detection Opereration (Status)
26434 66 Human Detection Wind (Setting)
26435 67 Human Detection Wind (Status)
26436 68 Human Detection Time (Setting)
26437 69 Human Detection Time (Status)
26438 70 Hotel Checkin (Setting)
26439 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_67 BO Stop(0) Start(1)
StartStopStatus_67 BI Stop(0) Start(1)
LockCommand_67 BO Permit(0) Prohibit(1)
LockStatus_67 BI Permit(0) Prohibit(1)
FilterSign_67 BI Off(0) On(1)
FilterSignReset_67 BV - Reset(1)
AirConModeCommand_67 MO Cool(1)
AirConModeStatus_67 MI Cool(1)
SwingCommand_67 BO Stop(0) Run(1)
SwingStatus_67 BI Stop(0) Run(1)
FanSpeedCommand_67 MO Low(1)
FanSpeedStatus_67 MI Low(1)
SetRoomTemp_67 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_67 AI ℃
Alarm_67 BI Normal(0) Abnormal(1)
MalfunctionCode_67 AI Refer to the
SetTempStatus_67 AI ℃
Accumulated power(100 Watt)_67 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_67 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_67 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_67 AI ℃
TempRangeLowerLimitStatus_67 AI ℃
ModeLockCommand_67 BO Permit(0) Prohibit(1)
ModeLockStatus_67 BI Permit(0) Prohibit(1)
FanLockCommand_67 BO Permit(0) Prohibit(1)
FanLockStatus_67 BI Permit(0) Prohibit(1)
OccupancyCommand_67 BO Unoccupied(0) Occupied(1)
OccupancyStatus_67 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_67 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_67 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_67 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_67 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_67 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_67 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_67 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_67 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_67 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_67 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_67 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_67 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_67 BI Off(0) On(1)
AccumulatedGas(100 Watt)_67 AI Wattage values (Unit : 100Watt)
DustSensorAvail_67 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_67 BO Stop(0) Run(1)
AirCleaningOperStatus_67 BI Stop(0) Run(1)
FineDustStatus_67 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_67 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_67 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_67 AI %
ComfortCoolingAvail_67 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_67 BO Stop(0) Run(1)
ComfortCoolingOperStatus_67 BI Stop(0) Run(1)
ComfortCoolingStepCommand_67 AV 1~3 step
ComfortCoolingStepStatus_67 AI 1~3 step
HumanDetectionAvail_67 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_67 MO Off(1)
HumanDetectionOperStatus_67 MI Off(1)
HumanDetectionWindCommand_67 MO Off(1)
HumanDetectionWindStatus_67 MI Off(1)
HumanDetectionTimeCommand_67 MO 5min(1)
HumanDetectionTimeStatus_67 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
68 ※ Dev Type AC
address

instance
point Name
number

26625 1 On/Off (Setting)


26626 2 On/Off (Status)
26627 3 Lock (Setting)
26628 4 Lock (Status)
26629 5 Filter Sign
26630 6 Filter Sign reset
26631 7 Operation Mode (Setting)
26632 8 Operation Mode (Status)
26633 9 Swing (Setting)
26634 10 Swing (Status)
26635 11 Fan Speed (Setting)
26636 12 Fan Speed (Status)
26637 13 Set Room Temperature
26638 14 Room Temperature
26639 15 Alarm
26640 16 Error Code
26643 19 Set Temperature (Status)
26644 20 Accumulated Power Distribution (Status)
26651 27 Set Upper Temperature (Setting)
26652 28 Set Lower Temperature (Setting)
26653 29 Set Upper Tempaerature (Status)
26654 30 Set Lower Temperature (Status)
26655 31 Mode Lock (Setting)
26656 32 Mode Lock (Status)
26657 33 Fan Lock (Setting)
26658 34 Fan Lock (Status)
26659 35 Occupancy (Setting)
26660 36 Occupancy (Status)
26661 37 2Set Cooling Set Temperature (Setting)
26662 38 2Set Cooling Set Temperature (Status)
26663 39 2Set Heating Set Temperature (Setting)
26664 40 2Set Heating Set Temperature (Status)
26665 41 2Set Cooling Upper Temperature (Setting)
26666 42 2Set Cooling Upper Temperature (Status)
26667 43 2Set Heating Upper Temperature (Setting)
26668 44 2Set Heating Upper Temperature (Status)
26669 45 2Set Cooling Lower Temperature (Setting)
26670 46 2Set Cooling Lower Temperature (Status)
26671 47 2Set Heating Lower Temperature (Setting)
26672 48 2Set Heating Lower Temperature (Status)
26673 49 Thermo Status (Status)
26674 50 Accumulated Gas Distribution (Status)
26675 51 Dust Sensor Available (Status)
26676 52 Air Cleaning Opereration (Setting)
26677 53 Air Cleaning Opereration (Status)
26678 54 Fine Dust (Status)
26679 55 Ultra Fine Dust (Status)
26680 56 Super Ultra Fine Dust (Status)
26681 57 Humidity (Status)
26682 58 Comfort Cooling Available (Status)
26683 59 Comfort Cooling Opereration (Setting)
26684 60 Comfort Cooling Opereration (Status)
26685 61 Comfort Cooling Step (Setting)
26686 62 Comfort Cooling Step (Status)
26687 63 Human Detection Available (Status)
26688 64 Human Detection Opereration (Setting)
26689 65 Human Detection Opereration (Status)
26690 66 Human Detection Wind (Setting)
26691 67 Human Detection Wind (Status)
26692 68 Human Detection Time (Setting)
26693 69 Human Detection Time (Status)
26694 70 Hotel Checkin (Setting)
26695 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_68 BO Stop(0) Start(1)
StartStopStatus_68 BI Stop(0) Start(1)
LockCommand_68 BO Permit(0) Prohibit(1)
LockStatus_68 BI Permit(0) Prohibit(1)
FilterSign_68 BI Off(0) On(1)
FilterSignReset_68 BV - Reset(1)
AirConModeCommand_68 MO Cool(1)
AirConModeStatus_68 MI Cool(1)
SwingCommand_68 BO Stop(0) Run(1)
SwingStatus_68 BI Stop(0) Run(1)
FanSpeedCommand_68 MO Low(1)
FanSpeedStatus_68 MI Low(1)
SetRoomTemp_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_68 AI ℃
Alarm_68 BI Normal(0) Abnormal(1)
MalfunctionCode_68 AI Refer to the
SetTempStatus_68 AI ℃
Accumulated power(100 Watt)_68 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_68 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_68 AI ℃
TempRangeLowerLimitStatus_68 AI ℃
ModeLockCommand_68 BO Permit(0) Prohibit(1)
ModeLockStatus_68 BI Permit(0) Prohibit(1)
FanLockCommand_68 BO Permit(0) Prohibit(1)
FanLockStatus_68 BI Permit(0) Prohibit(1)
OccupancyCommand_68 BO Unoccupied(0) Occupied(1)
OccupancyStatus_68 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_68 BI Off(0) On(1)
AccumulatedGas(100 Watt)_68 AI Wattage values (Unit : 100Watt)
DustSensorAvail_68 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_68 BO Stop(0) Run(1)
AirCleaningOperStatus_68 BI Stop(0) Run(1)
FineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_68 AI %
ComfortCoolingAvail_68 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_68 BO Stop(0) Run(1)
ComfortCoolingOperStatus_68 BI Stop(0) Run(1)
ComfortCoolingStepCommand_68 AV 1~3 step
ComfortCoolingStepStatus_68 AI 1~3 step
HumanDetectionAvail_68 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_68 MO Off(1)
HumanDetectionOperStatus_68 MI Off(1)
HumanDetectionWindCommand_68 MO Off(1)
HumanDetectionWindStatus_68 MI Off(1)
HumanDetectionTimeCommand_68 MO 5min(1)
HumanDetectionTimeStatus_68 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
68 ※ Dev Type AC
address

instance
point Name
number

26625 1 On/Off (Setting)


26626 2 On/Off (Status)
26627 3 Lock (Setting)
26628 4 Lock (Status)
26629 5 Filter Sign
26630 6 Filter Sign reset
26631 7 Operation Mode (Setting)
26632 8 Operation Mode (Status)
26633 9 Swing (Setting)
26634 10 Swing (Status)
26635 11 Fan Speed (Setting)
26636 12 Fan Speed (Status)
26637 13 Set Room Temperature
26638 14 Room Temperature
26639 15 Alarm
26640 16 Error Code
26643 19 Set Temperature (Status)
26644 20 Accumulated Power Distribution (Status)
26651 27 Set Upper Temperature (Setting)
26652 28 Set Lower Temperature (Setting)
26653 29 Set Upper Tempaerature (Status)
26654 30 Set Lower Temperature (Status)
26655 31 Mode Lock (Setting)
26656 32 Mode Lock (Status)
26657 33 Fan Lock (Setting)
26658 34 Fan Lock (Status)
26659 35 Occupancy (Setting)
26660 36 Occupancy (Status)
26661 37 2Set Cooling Set Temperature (Setting)
26662 38 2Set Cooling Set Temperature (Status)
26663 39 2Set Heating Set Temperature (Setting)
26664 40 2Set Heating Set Temperature (Status)
26665 41 2Set Cooling Upper Temperature (Setting)
26666 42 2Set Cooling Upper Temperature (Status)
26667 43 2Set Heating Upper Temperature (Setting)
26668 44 2Set Heating Upper Temperature (Status)
26669 45 2Set Cooling Lower Temperature (Setting)
26670 46 2Set Cooling Lower Temperature (Status)
26671 47 2Set Heating Lower Temperature (Setting)
26672 48 2Set Heating Lower Temperature (Status)
26673 49 Thermo Status (Status)
26674 50 Accumulated Gas Distribution (Status)
26675 51 Dust Sensor Available (Status)
26676 52 Air Cleaning Opereration (Setting)
26677 53 Air Cleaning Opereration (Status)
26678 54 Fine Dust (Status)
26679 55 Ultra Fine Dust (Status)
26680 56 Super Ultra Fine Dust (Status)
26681 57 Humidity (Status)
26682 58 Comfort Cooling Available (Status)
26683 59 Comfort Cooling Opereration (Setting)
26684 60 Comfort Cooling Opereration (Status)
26685 61 Comfort Cooling Step (Setting)
26686 62 Comfort Cooling Step (Status)
26687 63 Human Detection Available (Status)
26688 64 Human Detection Opereration (Setting)
26689 65 Human Detection Opereration (Status)
26690 66 Human Detection Wind (Setting)
26691 67 Human Detection Wind (Status)
26692 68 Human Detection Time (Setting)
26693 69 Human Detection Time (Status)
26694 70 Hotel Checkin (Setting)
26695 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_68 BO Stop(0) Start(1)
StartStopStatus_68 BI Stop(0) Start(1)
LockCommand_68 BO Permit(0) Prohibit(1)
LockStatus_68 BI Permit(0) Prohibit(1)
FilterSign_68 BI Off(0) On(1)
FilterSignReset_68 BV - Reset(1)
AirConModeCommand_68 MO Cool(1)
AirConModeStatus_68 MI Cool(1)
SwingCommand_68 BO Stop(0) Run(1)
SwingStatus_68 BI Stop(0) Run(1)
FanSpeedCommand_68 MO Low(1)
FanSpeedStatus_68 MI Low(1)
SetRoomTemp_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_68 AI ℃
Alarm_68 BI Normal(0) Abnormal(1)
MalfunctionCode_68 AI Refer to the
SetTempStatus_68 AI ℃
Accumulated power(100 Watt)_68 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_68 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_68 AI ℃
TempRangeLowerLimitStatus_68 AI ℃
ModeLockCommand_68 BO Permit(0) Prohibit(1)
ModeLockStatus_68 BI Permit(0) Prohibit(1)
FanLockCommand_68 BO Permit(0) Prohibit(1)
FanLockStatus_68 BI Permit(0) Prohibit(1)
OccupancyCommand_68 BO Unoccupied(0) Occupied(1)
OccupancyStatus_68 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_68 BI Off(0) On(1)
AccumulatedGas(100 Watt)_68 AI Wattage values (Unit : 100Watt)
DustSensorAvail_68 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_68 BO Stop(0) Run(1)
AirCleaningOperStatus_68 BI Stop(0) Run(1)
FineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_68 AI %
ComfortCoolingAvail_68 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_68 BO Stop(0) Run(1)
ComfortCoolingOperStatus_68 BI Stop(0) Run(1)
ComfortCoolingStepCommand_68 AV 1~3 step
ComfortCoolingStepStatus_68 AI 1~3 step
HumanDetectionAvail_68 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_68 MO Off(1)
HumanDetectionOperStatus_68 MI Off(1)
HumanDetectionWindCommand_68 MO Off(1)
HumanDetectionWindStatus_68 MI Off(1)
HumanDetectionTimeCommand_68 MO 5min(1)
HumanDetectionTimeStatus_68 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
c ※ Dev Type AC
address

instance
point Name
number

3073 1 On/Off (Setting)


3074 2 On/Off (Status)
3075 3 Lock (Setting)
3076 4 Lock (Status)
3077 5 Filter Sign
3078 6 Filter Sign reset
3079 7 Operation Mode (Setting)
3080 8 Operation Mode (Status)
3081 9 Swing (Setting)
3082 10 Swing (Status)
3083 11 Fan Speed (Setting)
3084 12 Fan Speed (Status)
3085 13 Set Room Temperature
3086 14 Room Temperature
3087 15 Alarm
3088 16 Error Code
3091 19 Set Temperature (Status)
3092 20 Accumulated Power Distribution (Status)
3099 27 Set Upper Temperature (Setting)
3100 28 Set Lower Temperature (Setting)
3101 29 Set Upper Tempaerature (Status)
3102 30 Set Lower Temperature (Status)
3103 31 Mode Lock (Setting)
3104 32 Mode Lock (Status)
3105 33 Fan Lock (Setting)
3106 34 Fan Lock (Status)
3107 35 Occupancy (Setting)
3108 36 Occupancy (Status)
3109 37 2Set Cooling Set Temperature (Setting)
3110 38 2Set Cooling Set Temperature (Status)
3111 39 2Set Heating Set Temperature (Setting)
3112 40 2Set Heating Set Temperature (Status)
3113 41 2Set Cooling Upper Temperature (Setting)
3114 42 2Set Cooling Upper Temperature (Status)
3115 43 2Set Heating Upper Temperature (Setting)
3116 44 2Set Heating Upper Temperature (Status)
3117 45 2Set Cooling Lower Temperature (Setting)
3118 46 2Set Cooling Lower Temperature (Status)
3119 47 2Set Heating Lower Temperature (Setting)
3120 48 2Set Heating Lower Temperature (Status)
3121 49 Thermo Status (Status)
3122 50 Accumulated Gas Distribution (Status)
3123 51 Dust Sensor Available (Status)
3124 52 Air Cleaning Opereration (Setting)
3125 53 Air Cleaning Opereration (Status)
3126 54 Fine Dust (Status)
3127 55 Ultra Fine Dust (Status)
3128 56 Super Ultra Fine Dust (Status)
3129 57 Humidity (Status)
3130 58 Comfort Cooling Available (Status)
3131 59 Comfort Cooling Opereration (Setting)
3132 60 Comfort Cooling Opereration (Status)
3133 61 Comfort Cooling Step (Setting)
3134 62 Comfort Cooling Step (Status)
3135 63 Human Detection Available (Status)
3136 64 Human Detection Opereration (Setting)
3137 65 Human Detection Opereration (Status)
3138 66 Human Detection Wind (Setting)
3139 67 Human Detection Wind (Status)
3140 68 Human Detection Time (Setting)
3141 69 Human Detection Time (Status)
3142 70 Hotel Checkin (Setting)
3143 71 Hotel Mode (Setting)
0

Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_c BO Stop(0) Start(1)
StartStopStatus_c BI Stop(0) Start(1)
LockCommand_c BO Permit(0) Prohibit(1)
LockStatus_c BI Permit(0) Prohibit(1)
FilterSign_c BI Off(0) On(1)
FilterSignReset_c BV - Reset(1)
AirConModeCommand_c MO Cool(1)
AirConModeStatus_c MI Cool(1)
SwingCommand_c BO Stop(0) Run(1)
SwingStatus_c BI Stop(0) Run(1)
FanSpeedCommand_c MO Low(1)
FanSpeedStatus_c MI Low(1)
SetRoomTemp_c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_c AI ℃
Alarm_c BI Normal(0) Abnormal(1)
MalfunctionCode_c AI Refer to the
SetTempStatus_c AI ℃
Accumulated power(100 Watt)_c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_c AI ℃
TempRangeLowerLimitStatus_c AI ℃
ModeLockCommand_c BO Permit(0) Prohibit(1)
ModeLockStatus_c BI Permit(0) Prohibit(1)
FanLockCommand_c BO Permit(0) Prohibit(1)
FanLockStatus_c BI Permit(0) Prohibit(1)
OccupancyCommand_c BO Unoccupied(0) Occupied(1)
OccupancyStatus_c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_c BI Off(0) On(1)
AccumulatedGas(100 Watt)_c AI Wattage values (Unit : 100Watt)
DustSensorAvail_c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_c BO Stop(0) Run(1)
AirCleaningOperStatus_c BI Stop(0) Run(1)
FineDustStatus_c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_c AI %
ComfortCoolingAvail_c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_c BO Stop(0) Run(1)
ComfortCoolingOperStatus_c BI Stop(0) Run(1)
ComfortCoolingStepCommand_c AV 1~3 step
ComfortCoolingStepStatus_c AI 1~3 step
HumanDetectionAvail_c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_c MO Off(1)
HumanDetectionOperStatus_c MI Off(1)
HumanDetectionWindCommand_c MO Off(1)
HumanDetectionWindStatus_c MI Off(1)
HumanDetectionTimeCommand_c MO 5min(1)
HumanDetectionTimeStatus_c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6

Dry(2) Fan(3) Auto(4) Heat(5)


Dry(2) Fan(3) Auto(4) Heat(5)

Middle(2) High(3) Auto(4)


Middle(2) High(3) Auto(4)
86℉)

Refer to the LG Errror code list

0Watt)
86℉)
86℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

~ 99℉)
~ 99℉)
0℉)
0℉)

0Watt)
Point 52-57 is available only when this point is Enabled.

-per-cubic-meter
-per-cubic-meter
-per-cubic-meter

Point 55-58 is available only when this point is Enabled.

향후 스텝이 더 늘어날 수 있다 해서.. 아날로그로 선언

Point 64-69 is available only when this point is Enabled.


OnOffSaving(2) TempSaving(3)
OnOffSaving(2) TempSaving(3)
Direct(2) Indirect(3)
Direct(2) Indirect(3)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)
10min(2) 15min(3) 30min(4) <- default 60min(5) 90min(6)

Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)