68 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_68 BO Stop(0) Start(1)
StartStopStatus_68 BI Stop(0) Start(1)
LockCommand_68 BO Permit(0) Prohibit(1)
LockStatus_68 BI Permit(0) Prohibit(1)
FilterSign_68 BI Off(0) On(1)
FilterSignReset_68 BV - Reset(1)
AirConModeCommand_68 MO Cool(1)
AirConModeStatus_68 MI Cool(1)
SwingCommand_68 BO Stop(0) Run(1)
SwingStatus_68 BI Stop(0) Run(1)
FanSpeedCommand_68 MO Low(1)
FanSpeedStatus_68 MI Low(1)
SetRoomTemp_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_68 AI ℃
Alarm_68 BI Normal(0) Abnormal(1)
MalfunctionCode_68 AI Refer to the
SetTempStatus_68 AI ℃
Accumulated power(100 Watt)_68 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_68 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_68 AI ℃
TempRangeLowerLimitStatus_68 AI ℃
ModeLockCommand_68 BO Permit(0) Prohibit(1)
ModeLockStatus_68 BI Permit(0) Prohibit(1)
FanLockCommand_68 BO Permit(0) Prohibit(1)
FanLockStatus_68 BI Permit(0) Prohibit(1)
OccupancyCommand_68 BO Unoccupied(0) Occupied(1)
OccupancyStatus_68 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_68 BI Off(0) On(1)
AccumulatedGas(100 Watt)_68 AI Wattage values (Unit : 100Watt)
DustSensorAvail_68 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_68 BO Stop(0) Run(1)
AirCleaningOperStatus_68 BI Stop(0) Run(1)
FineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_68 AI %
ComfortCoolingAvail_68 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_68 BO Stop(0) Run(1)
ComfortCoolingOperStatus_68 BI Stop(0) Run(1)
ComfortCoolingStepCommand_68 AV 1~3 step
ComfortCoolingStepStatus_68 AI 1~3 step
HumanDetectionAvail_68 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_68 MO Off(1)
HumanDetectionOperStatus_68 MI Off(1)
HumanDetectionWindCommand_68 MO Off(1)
HumanDetectionWindStatus_68 MI Off(1)
HumanDetectionTimeCommand_68 MO 5min(1)
HumanDetectionTimeStatus_68 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4e ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4e BO Stop(0) Start(1)
StartStopStatus_4e BI Stop(0) Start(1)
LockCommand_4e BO Permit(0) Prohibit(1)
LockStatus_4e BI Permit(0) Prohibit(1)
FilterSign_4e BI Off(0) On(1)
FilterSignReset_4e BV - Reset(1)
AirConModeCommand_4e MO Cool(1)
AirConModeStatus_4e MI Cool(1)
SwingCommand_4e BO Stop(0) Run(1)
SwingStatus_4e BI Stop(0) Run(1)
FanSpeedCommand_4e MO Low(1)
FanSpeedStatus_4e MI Low(1)
SetRoomTemp_4e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4e AI ℃
Alarm_4e BI Normal(0) Abnormal(1)
MalfunctionCode_4e AI Refer to the
SetTempStatus_4e AI ℃
Accumulated power(100 Watt)_4e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4e AI ℃
TempRangeLowerLimitStatus_4e AI ℃
ModeLockCommand_4e BO Permit(0) Prohibit(1)
ModeLockStatus_4e BI Permit(0) Prohibit(1)
FanLockCommand_4e BO Permit(0) Prohibit(1)
FanLockStatus_4e BI Permit(0) Prohibit(1)
OccupancyCommand_4e BO Unoccupied(0) Occupied(1)
OccupancyStatus_4e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4e BI Off(0) On(1)
AccumulatedGas(100 Watt)_4e AI Wattage values (Unit : 100Watt)
DustSensorAvail_4e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4e BO Stop(0) Run(1)
AirCleaningOperStatus_4e BI Stop(0) Run(1)
FineDustStatus_4e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4e AI %
ComfortCoolingAvail_4e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4e BO Stop(0) Run(1)
ComfortCoolingOperStatus_4e BI Stop(0) Run(1)
ComfortCoolingStepCommand_4e AV 1~3 step
ComfortCoolingStepStatus_4e AI 1~3 step
HumanDetectionAvail_4e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4e MO Off(1)
HumanDetectionOperStatus_4e MI Off(1)
HumanDetectionWindCommand_4e MO Off(1)
HumanDetectionWindStatus_4e MI Off(1)
HumanDetectionTimeCommand_4e MO 5min(1)
HumanDetectionTimeStatus_4e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1 BO Stop(0) Start(1)
StartStopStatus_1 BI Stop(0) Start(1)
LockCommand_1 BO Permit(0) Prohibit(1)
LockStatus_1 BI Permit(0) Prohibit(1)
FilterSign_1 BI Off(0) On(1)
FilterSignReset_1 BV - Reset(1)
AirConModeCommand_1 MO Cool(1)
AirConModeStatus_1 MI Cool(1)
SwingCommand_1 BO Stop(0) Run(1)
SwingStatus_1 BI Stop(0) Run(1)
FanSpeedCommand_1 MO Low(1)
FanSpeedStatus_1 MI Low(1)
SetRoomTemp_1 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1 AI ℃
Alarm_1 BI Normal(0) Abnormal(1)
MalfunctionCode_1 AI Refer to the
SetTempStatus_1 AI ℃
Accumulated power(100 Watt)_1 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1 AI ℃
TempRangeLowerLimitStatus_1 AI ℃
ModeLockCommand_1 BO Permit(0) Prohibit(1)
ModeLockStatus_1 BI Permit(0) Prohibit(1)
FanLockCommand_1 BO Permit(0) Prohibit(1)
FanLockStatus_1 BI Permit(0) Prohibit(1)
OccupancyCommand_1 BO Unoccupied(0) Occupied(1)
OccupancyStatus_1 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1 BI Off(0) On(1)
AccumulatedGas(100 Watt)_1 AI Wattage values (Unit : 100Watt)
DustSensorAvail_1 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1 BO Stop(0) Run(1)
AirCleaningOperStatus_1 BI Stop(0) Run(1)
FineDustStatus_1 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1 AI %
ComfortCoolingAvail_1 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1 BO Stop(0) Run(1)
ComfortCoolingOperStatus_1 BI Stop(0) Run(1)
ComfortCoolingStepCommand_1 AV 1~3 step
ComfortCoolingStepStatus_1 AI 1~3 step
HumanDetectionAvail_1 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1 MO Off(1)
HumanDetectionOperStatus_1 MI Off(1)
HumanDetectionWindCommand_1 MO Off(1)
HumanDetectionWindStatus_1 MI Off(1)
HumanDetectionTimeCommand_1 MO 5min(1)
HumanDetectionTimeStatus_1 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2 BO Stop(0) Start(1)
StartStopStatus_2 BI Stop(0) Start(1)
LockCommand_2 BO Permit(0) Prohibit(1)
LockStatus_2 BI Permit(0) Prohibit(1)
FilterSign_2 BI Off(0) On(1)
FilterSignReset_2 BV - Reset(1)
AirConModeCommand_2 MO Cool(1)
AirConModeStatus_2 MI Cool(1)
SwingCommand_2 BO Stop(0) Run(1)
SwingStatus_2 BI Stop(0) Run(1)
FanSpeedCommand_2 MO Low(1)
FanSpeedStatus_2 MI Low(1)
SetRoomTemp_2 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2 AI ℃
Alarm_2 BI Normal(0) Abnormal(1)
MalfunctionCode_2 AI Refer to the
SetTempStatus_2 AI ℃
Accumulated power(100 Watt)_2 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2 AI ℃
TempRangeLowerLimitStatus_2 AI ℃
ModeLockCommand_2 BO Permit(0) Prohibit(1)
ModeLockStatus_2 BI Permit(0) Prohibit(1)
FanLockCommand_2 BO Permit(0) Prohibit(1)
FanLockStatus_2 BI Permit(0) Prohibit(1)
OccupancyCommand_2 BO Unoccupied(0) Occupied(1)
OccupancyStatus_2 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2 BI Off(0) On(1)
AccumulatedGas(100 Watt)_2 AI Wattage values (Unit : 100Watt)
DustSensorAvail_2 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2 BO Stop(0) Run(1)
AirCleaningOperStatus_2 BI Stop(0) Run(1)
FineDustStatus_2 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2 AI %
ComfortCoolingAvail_2 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2 BO Stop(0) Run(1)
ComfortCoolingOperStatus_2 BI Stop(0) Run(1)
ComfortCoolingStepCommand_2 AV 1~3 step
ComfortCoolingStepStatus_2 AI 1~3 step
HumanDetectionAvail_2 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2 MO Off(1)
HumanDetectionOperStatus_2 MI Off(1)
HumanDetectionWindCommand_2 MO Off(1)
HumanDetectionWindStatus_2 MI Off(1)
HumanDetectionTimeCommand_2 MO 5min(1)
HumanDetectionTimeStatus_2 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3 BO Stop(0) Start(1)
StartStopStatus_3 BI Stop(0) Start(1)
LockCommand_3 BO Permit(0) Prohibit(1)
LockStatus_3 BI Permit(0) Prohibit(1)
FilterSign_3 BI Off(0) On(1)
FilterSignReset_3 BV - Reset(1)
AirConModeCommand_3 MO Cool(1)
AirConModeStatus_3 MI Cool(1)
SwingCommand_3 BO Stop(0) Run(1)
SwingStatus_3 BI Stop(0) Run(1)
FanSpeedCommand_3 MO Low(1)
FanSpeedStatus_3 MI Low(1)
SetRoomTemp_3 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3 AI ℃
Alarm_3 BI Normal(0) Abnormal(1)
MalfunctionCode_3 AI Refer to the
SetTempStatus_3 AI ℃
Accumulated power(100 Watt)_3 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3 AI ℃
TempRangeLowerLimitStatus_3 AI ℃
ModeLockCommand_3 BO Permit(0) Prohibit(1)
ModeLockStatus_3 BI Permit(0) Prohibit(1)
FanLockCommand_3 BO Permit(0) Prohibit(1)
FanLockStatus_3 BI Permit(0) Prohibit(1)
OccupancyCommand_3 BO Unoccupied(0) Occupied(1)
OccupancyStatus_3 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3 BI Off(0) On(1)
AccumulatedGas(100 Watt)_3 AI Wattage values (Unit : 100Watt)
DustSensorAvail_3 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3 BO Stop(0) Run(1)
AirCleaningOperStatus_3 BI Stop(0) Run(1)
FineDustStatus_3 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3 AI %
ComfortCoolingAvail_3 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3 BO Stop(0) Run(1)
ComfortCoolingOperStatus_3 BI Stop(0) Run(1)
ComfortCoolingStepCommand_3 AV 1~3 step
ComfortCoolingStepStatus_3 AI 1~3 step
HumanDetectionAvail_3 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3 MO Off(1)
HumanDetectionOperStatus_3 MI Off(1)
HumanDetectionWindCommand_3 MO Off(1)
HumanDetectionWindStatus_3 MI Off(1)
HumanDetectionTimeCommand_3 MO 5min(1)
HumanDetectionTimeStatus_3 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4 BO Stop(0) Start(1)
StartStopStatus_4 BI Stop(0) Start(1)
LockCommand_4 BO Permit(0) Prohibit(1)
LockStatus_4 BI Permit(0) Prohibit(1)
FilterSign_4 BI Off(0) On(1)
FilterSignReset_4 BV - Reset(1)
AirConModeCommand_4 MO Cool(1)
AirConModeStatus_4 MI Cool(1)
SwingCommand_4 BO Stop(0) Run(1)
SwingStatus_4 BI Stop(0) Run(1)
FanSpeedCommand_4 MO Low(1)
FanSpeedStatus_4 MI Low(1)
SetRoomTemp_4 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4 AI ℃
Alarm_4 BI Normal(0) Abnormal(1)
MalfunctionCode_4 AI Refer to the
SetTempStatus_4 AI ℃
Accumulated power(100 Watt)_4 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4 AI ℃
TempRangeLowerLimitStatus_4 AI ℃
ModeLockCommand_4 BO Permit(0) Prohibit(1)
ModeLockStatus_4 BI Permit(0) Prohibit(1)
FanLockCommand_4 BO Permit(0) Prohibit(1)
FanLockStatus_4 BI Permit(0) Prohibit(1)
OccupancyCommand_4 BO Unoccupied(0) Occupied(1)
OccupancyStatus_4 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4 BI Off(0) On(1)
AccumulatedGas(100 Watt)_4 AI Wattage values (Unit : 100Watt)
DustSensorAvail_4 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4 BO Stop(0) Run(1)
AirCleaningOperStatus_4 BI Stop(0) Run(1)
FineDustStatus_4 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4 AI %
ComfortCoolingAvail_4 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4 BO Stop(0) Run(1)
ComfortCoolingOperStatus_4 BI Stop(0) Run(1)
ComfortCoolingStepCommand_4 AV 1~3 step
ComfortCoolingStepStatus_4 AI 1~3 step
HumanDetectionAvail_4 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4 MO Off(1)
HumanDetectionOperStatus_4 MI Off(1)
HumanDetectionWindCommand_4 MO Off(1)
HumanDetectionWindStatus_4 MI Off(1)
HumanDetectionTimeCommand_4 MO 5min(1)
HumanDetectionTimeStatus_4 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5 BO Stop(0) Start(1)
StartStopStatus_5 BI Stop(0) Start(1)
LockCommand_5 BO Permit(0) Prohibit(1)
LockStatus_5 BI Permit(0) Prohibit(1)
FilterSign_5 BI Off(0) On(1)
FilterSignReset_5 BV - Reset(1)
AirConModeCommand_5 MO Cool(1)
AirConModeStatus_5 MI Cool(1)
SwingCommand_5 BO Stop(0) Run(1)
SwingStatus_5 BI Stop(0) Run(1)
FanSpeedCommand_5 MO Low(1)
FanSpeedStatus_5 MI Low(1)
SetRoomTemp_5 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5 AI ℃
Alarm_5 BI Normal(0) Abnormal(1)
MalfunctionCode_5 AI Refer to the
SetTempStatus_5 AI ℃
Accumulated power(100 Watt)_5 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5 AI ℃
TempRangeLowerLimitStatus_5 AI ℃
ModeLockCommand_5 BO Permit(0) Prohibit(1)
ModeLockStatus_5 BI Permit(0) Prohibit(1)
FanLockCommand_5 BO Permit(0) Prohibit(1)
FanLockStatus_5 BI Permit(0) Prohibit(1)
OccupancyCommand_5 BO Unoccupied(0) Occupied(1)
OccupancyStatus_5 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5 BI Off(0) On(1)
AccumulatedGas(100 Watt)_5 AI Wattage values (Unit : 100Watt)
DustSensorAvail_5 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5 BO Stop(0) Run(1)
AirCleaningOperStatus_5 BI Stop(0) Run(1)
FineDustStatus_5 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5 AI %
ComfortCoolingAvail_5 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5 BO Stop(0) Run(1)
ComfortCoolingOperStatus_5 BI Stop(0) Run(1)
ComfortCoolingStepCommand_5 AV 1~3 step
ComfortCoolingStepStatus_5 AI 1~3 step
HumanDetectionAvail_5 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5 MO Off(1)
HumanDetectionOperStatus_5 MI Off(1)
HumanDetectionWindCommand_5 MO Off(1)
HumanDetectionWindStatus_5 MI Off(1)
HumanDetectionTimeCommand_5 MO 5min(1)
HumanDetectionTimeStatus_5 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
6 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_6 BO Stop(0) Start(1)
StartStopStatus_6 BI Stop(0) Start(1)
LockCommand_6 BO Permit(0) Prohibit(1)
LockStatus_6 BI Permit(0) Prohibit(1)
FilterSign_6 BI Off(0) On(1)
FilterSignReset_6 BV - Reset(1)
AirConModeCommand_6 MO Cool(1)
AirConModeStatus_6 MI Cool(1)
SwingCommand_6 BO Stop(0) Run(1)
SwingStatus_6 BI Stop(0) Run(1)
FanSpeedCommand_6 MO Low(1)
FanSpeedStatus_6 MI Low(1)
SetRoomTemp_6 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_6 AI ℃
Alarm_6 BI Normal(0) Abnormal(1)
MalfunctionCode_6 AI Refer to the
SetTempStatus_6 AI ℃
Accumulated power(100 Watt)_6 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_6 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_6 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_6 AI ℃
TempRangeLowerLimitStatus_6 AI ℃
ModeLockCommand_6 BO Permit(0) Prohibit(1)
ModeLockStatus_6 BI Permit(0) Prohibit(1)
FanLockCommand_6 BO Permit(0) Prohibit(1)
FanLockStatus_6 BI Permit(0) Prohibit(1)
OccupancyCommand_6 BO Unoccupied(0) Occupied(1)
OccupancyStatus_6 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_6 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_6 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_6 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_6 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_6 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_6 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_6 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_6 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_6 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_6 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_6 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_6 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_6 BI Off(0) On(1)
AccumulatedGas(100 Watt)_6 AI Wattage values (Unit : 100Watt)
DustSensorAvail_6 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_6 BO Stop(0) Run(1)
AirCleaningOperStatus_6 BI Stop(0) Run(1)
FineDustStatus_6 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_6 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_6 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_6 AI %
ComfortCoolingAvail_6 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_6 BO Stop(0) Run(1)
ComfortCoolingOperStatus_6 BI Stop(0) Run(1)
ComfortCoolingStepCommand_6 AV 1~3 step
ComfortCoolingStepStatus_6 AI 1~3 step
HumanDetectionAvail_6 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_6 MO Off(1)
HumanDetectionOperStatus_6 MI Off(1)
HumanDetectionWindCommand_6 MO Off(1)
HumanDetectionWindStatus_6 MI Off(1)
HumanDetectionTimeCommand_6 MO 5min(1)
HumanDetectionTimeStatus_6 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
7 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_7 BO Stop(0) Start(1)
StartStopStatus_7 BI Stop(0) Start(1)
LockCommand_7 BO Permit(0) Prohibit(1)
LockStatus_7 BI Permit(0) Prohibit(1)
FilterSign_7 BI Off(0) On(1)
FilterSignReset_7 BV - Reset(1)
AirConModeCommand_7 MO Cool(1)
AirConModeStatus_7 MI Cool(1)
SwingCommand_7 BO Stop(0) Run(1)
SwingStatus_7 BI Stop(0) Run(1)
FanSpeedCommand_7 MO Low(1)
FanSpeedStatus_7 MI Low(1)
SetRoomTemp_7 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_7 AI ℃
Alarm_7 BI Normal(0) Abnormal(1)
MalfunctionCode_7 AI Refer to the
SetTempStatus_7 AI ℃
Accumulated power(100 Watt)_7 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_7 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_7 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_7 AI ℃
TempRangeLowerLimitStatus_7 AI ℃
ModeLockCommand_7 BO Permit(0) Prohibit(1)
ModeLockStatus_7 BI Permit(0) Prohibit(1)
FanLockCommand_7 BO Permit(0) Prohibit(1)
FanLockStatus_7 BI Permit(0) Prohibit(1)
OccupancyCommand_7 BO Unoccupied(0) Occupied(1)
OccupancyStatus_7 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_7 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_7 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_7 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_7 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_7 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_7 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_7 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_7 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_7 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_7 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_7 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_7 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_7 BI Off(0) On(1)
AccumulatedGas(100 Watt)_7 AI Wattage values (Unit : 100Watt)
DustSensorAvail_7 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_7 BO Stop(0) Run(1)
AirCleaningOperStatus_7 BI Stop(0) Run(1)
FineDustStatus_7 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_7 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_7 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_7 AI %
ComfortCoolingAvail_7 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_7 BO Stop(0) Run(1)
ComfortCoolingOperStatus_7 BI Stop(0) Run(1)
ComfortCoolingStepCommand_7 AV 1~3 step
ComfortCoolingStepStatus_7 AI 1~3 step
HumanDetectionAvail_7 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_7 MO Off(1)
HumanDetectionOperStatus_7 MI Off(1)
HumanDetectionWindCommand_7 MO Off(1)
HumanDetectionWindStatus_7 MI Off(1)
HumanDetectionTimeCommand_7 MO 5min(1)
HumanDetectionTimeStatus_7 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
8 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_8 BO Stop(0) Start(1)
StartStopStatus_8 BI Stop(0) Start(1)
LockCommand_8 BO Permit(0) Prohibit(1)
LockStatus_8 BI Permit(0) Prohibit(1)
FilterSign_8 BI Off(0) On(1)
FilterSignReset_8 BV - Reset(1)
AirConModeCommand_8 MO Cool(1)
AirConModeStatus_8 MI Cool(1)
SwingCommand_8 BO Stop(0) Run(1)
SwingStatus_8 BI Stop(0) Run(1)
FanSpeedCommand_8 MO Low(1)
FanSpeedStatus_8 MI Low(1)
SetRoomTemp_8 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_8 AI ℃
Alarm_8 BI Normal(0) Abnormal(1)
MalfunctionCode_8 AI Refer to the
SetTempStatus_8 AI ℃
Accumulated power(100 Watt)_8 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_8 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_8 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_8 AI ℃
TempRangeLowerLimitStatus_8 AI ℃
ModeLockCommand_8 BO Permit(0) Prohibit(1)
ModeLockStatus_8 BI Permit(0) Prohibit(1)
FanLockCommand_8 BO Permit(0) Prohibit(1)
FanLockStatus_8 BI Permit(0) Prohibit(1)
OccupancyCommand_8 BO Unoccupied(0) Occupied(1)
OccupancyStatus_8 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_8 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_8 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_8 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_8 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_8 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_8 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_8 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_8 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_8 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_8 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_8 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_8 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_8 BI Off(0) On(1)
AccumulatedGas(100 Watt)_8 AI Wattage values (Unit : 100Watt)
DustSensorAvail_8 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_8 BO Stop(0) Run(1)
AirCleaningOperStatus_8 BI Stop(0) Run(1)
FineDustStatus_8 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_8 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_8 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_8 AI %
ComfortCoolingAvail_8 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_8 BO Stop(0) Run(1)
ComfortCoolingOperStatus_8 BI Stop(0) Run(1)
ComfortCoolingStepCommand_8 AV 1~3 step
ComfortCoolingStepStatus_8 AI 1~3 step
HumanDetectionAvail_8 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_8 MO Off(1)
HumanDetectionOperStatus_8 MI Off(1)
HumanDetectionWindCommand_8 MO Off(1)
HumanDetectionWindStatus_8 MI Off(1)
HumanDetectionTimeCommand_8 MO 5min(1)
HumanDetectionTimeStatus_8 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
9 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_9 BO Stop(0) Start(1)
StartStopStatus_9 BI Stop(0) Start(1)
LockCommand_9 BO Permit(0) Prohibit(1)
LockStatus_9 BI Permit(0) Prohibit(1)
FilterSign_9 BI Off(0) On(1)
FilterSignReset_9 BV - Reset(1)
AirConModeCommand_9 MO Cool(1)
AirConModeStatus_9 MI Cool(1)
SwingCommand_9 BO Stop(0) Run(1)
SwingStatus_9 BI Stop(0) Run(1)
FanSpeedCommand_9 MO Low(1)
FanSpeedStatus_9 MI Low(1)
SetRoomTemp_9 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_9 AI ℃
Alarm_9 BI Normal(0) Abnormal(1)
MalfunctionCode_9 AI Refer to the
SetTempStatus_9 AI ℃
Accumulated power(100 Watt)_9 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_9 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_9 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_9 AI ℃
TempRangeLowerLimitStatus_9 AI ℃
ModeLockCommand_9 BO Permit(0) Prohibit(1)
ModeLockStatus_9 BI Permit(0) Prohibit(1)
FanLockCommand_9 BO Permit(0) Prohibit(1)
FanLockStatus_9 BI Permit(0) Prohibit(1)
OccupancyCommand_9 BO Unoccupied(0) Occupied(1)
OccupancyStatus_9 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_9 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_9 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_9 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_9 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_9 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_9 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_9 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_9 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_9 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_9 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_9 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_9 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_9 BI Off(0) On(1)
AccumulatedGas(100 Watt)_9 AI Wattage values (Unit : 100Watt)
DustSensorAvail_9 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_9 BO Stop(0) Run(1)
AirCleaningOperStatus_9 BI Stop(0) Run(1)
FineDustStatus_9 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_9 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_9 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_9 AI %
ComfortCoolingAvail_9 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_9 BO Stop(0) Run(1)
ComfortCoolingOperStatus_9 BI Stop(0) Run(1)
ComfortCoolingStepCommand_9 AV 1~3 step
ComfortCoolingStepStatus_9 AI 1~3 step
HumanDetectionAvail_9 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_9 MO Off(1)
HumanDetectionOperStatus_9 MI Off(1)
HumanDetectionWindCommand_9 MO Off(1)
HumanDetectionWindStatus_9 MI Off(1)
HumanDetectionTimeCommand_9 MO 5min(1)
HumanDetectionTimeStatus_9 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
a ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_a BO Stop(0) Start(1)
StartStopStatus_a BI Stop(0) Start(1)
LockCommand_a BO Permit(0) Prohibit(1)
LockStatus_a BI Permit(0) Prohibit(1)
FilterSign_a BI Off(0) On(1)
FilterSignReset_a BV - Reset(1)
AirConModeCommand_a MO Cool(1)
AirConModeStatus_a MI Cool(1)
SwingCommand_a BO Stop(0) Run(1)
SwingStatus_a BI Stop(0) Run(1)
FanSpeedCommand_a MO Low(1)
FanSpeedStatus_a MI Low(1)
SetRoomTemp_a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_a AI ℃
Alarm_a BI Normal(0) Abnormal(1)
MalfunctionCode_a AI Refer to the
SetTempStatus_a AI ℃
Accumulated power(100 Watt)_a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_a AI ℃
TempRangeLowerLimitStatus_a AI ℃
ModeLockCommand_a BO Permit(0) Prohibit(1)
ModeLockStatus_a BI Permit(0) Prohibit(1)
FanLockCommand_a BO Permit(0) Prohibit(1)
FanLockStatus_a BI Permit(0) Prohibit(1)
OccupancyCommand_a BO Unoccupied(0) Occupied(1)
OccupancyStatus_a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_a BI Off(0) On(1)
AccumulatedGas(100 Watt)_a AI Wattage values (Unit : 100Watt)
DustSensorAvail_a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_a BO Stop(0) Run(1)
AirCleaningOperStatus_a BI Stop(0) Run(1)
FineDustStatus_a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_a AI %
ComfortCoolingAvail_a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_a BO Stop(0) Run(1)
ComfortCoolingOperStatus_a BI Stop(0) Run(1)
ComfortCoolingStepCommand_a AV 1~3 step
ComfortCoolingStepStatus_a AI 1~3 step
HumanDetectionAvail_a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_a MO Off(1)
HumanDetectionOperStatus_a MI Off(1)
HumanDetectionWindCommand_a MO Off(1)
HumanDetectionWindStatus_a MI Off(1)
HumanDetectionTimeCommand_a MO 5min(1)
HumanDetectionTimeStatus_a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
b ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_b BO Stop(0) Start(1)
StartStopStatus_b BI Stop(0) Start(1)
LockCommand_b BO Permit(0) Prohibit(1)
LockStatus_b BI Permit(0) Prohibit(1)
FilterSign_b BI Off(0) On(1)
FilterSignReset_b BV - Reset(1)
AirConModeCommand_b MO Cool(1)
AirConModeStatus_b MI Cool(1)
SwingCommand_b BO Stop(0) Run(1)
SwingStatus_b BI Stop(0) Run(1)
FanSpeedCommand_b MO Low(1)
FanSpeedStatus_b MI Low(1)
SetRoomTemp_b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_b AI ℃
Alarm_b BI Normal(0) Abnormal(1)
MalfunctionCode_b AI Refer to the
SetTempStatus_b AI ℃
Accumulated power(100 Watt)_b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_b AI ℃
TempRangeLowerLimitStatus_b AI ℃
ModeLockCommand_b BO Permit(0) Prohibit(1)
ModeLockStatus_b BI Permit(0) Prohibit(1)
FanLockCommand_b BO Permit(0) Prohibit(1)
FanLockStatus_b BI Permit(0) Prohibit(1)
OccupancyCommand_b BO Unoccupied(0) Occupied(1)
OccupancyStatus_b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_b BI Off(0) On(1)
AccumulatedGas(100 Watt)_b AI Wattage values (Unit : 100Watt)
DustSensorAvail_b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_b BO Stop(0) Run(1)
AirCleaningOperStatus_b BI Stop(0) Run(1)
FineDustStatus_b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_b AI %
ComfortCoolingAvail_b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_b BO Stop(0) Run(1)
ComfortCoolingOperStatus_b BI Stop(0) Run(1)
ComfortCoolingStepCommand_b AV 1~3 step
ComfortCoolingStepStatus_b AI 1~3 step
HumanDetectionAvail_b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_b MO Off(1)
HumanDetectionOperStatus_b MI Off(1)
HumanDetectionWindCommand_b MO Off(1)
HumanDetectionWindStatus_b MI Off(1)
HumanDetectionTimeCommand_b MO 5min(1)
HumanDetectionTimeStatus_b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
d ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_d BO Stop(0) Start(1)
StartStopStatus_d BI Stop(0) Start(1)
LockCommand_d BO Permit(0) Prohibit(1)
LockStatus_d BI Permit(0) Prohibit(1)
FilterSign_d BI Off(0) On(1)
FilterSignReset_d BV - Reset(1)
AirConModeCommand_d MO Cool(1)
AirConModeStatus_d MI Cool(1)
SwingCommand_d BO Stop(0) Run(1)
SwingStatus_d BI Stop(0) Run(1)
FanSpeedCommand_d MO Low(1)
FanSpeedStatus_d MI Low(1)
SetRoomTemp_d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_d AI ℃
Alarm_d BI Normal(0) Abnormal(1)
MalfunctionCode_d AI Refer to the
SetTempStatus_d AI ℃
Accumulated power(100 Watt)_d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_d AI ℃
TempRangeLowerLimitStatus_d AI ℃
ModeLockCommand_d BO Permit(0) Prohibit(1)
ModeLockStatus_d BI Permit(0) Prohibit(1)
FanLockCommand_d BO Permit(0) Prohibit(1)
FanLockStatus_d BI Permit(0) Prohibit(1)
OccupancyCommand_d BO Unoccupied(0) Occupied(1)
OccupancyStatus_d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_d BI Off(0) On(1)
AccumulatedGas(100 Watt)_d AI Wattage values (Unit : 100Watt)
DustSensorAvail_d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_d BO Stop(0) Run(1)
AirCleaningOperStatus_d BI Stop(0) Run(1)
FineDustStatus_d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_d AI %
ComfortCoolingAvail_d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_d BO Stop(0) Run(1)
ComfortCoolingOperStatus_d BI Stop(0) Run(1)
ComfortCoolingStepCommand_d AV 1~3 step
ComfortCoolingStepStatus_d AI 1~3 step
HumanDetectionAvail_d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_d MO Off(1)
HumanDetectionOperStatus_d MI Off(1)
HumanDetectionWindCommand_d MO Off(1)
HumanDetectionWindStatus_d MI Off(1)
HumanDetectionTimeCommand_d MO 5min(1)
HumanDetectionTimeStatus_d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
e ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_e BO Stop(0) Start(1)
StartStopStatus_e BI Stop(0) Start(1)
LockCommand_e BO Permit(0) Prohibit(1)
LockStatus_e BI Permit(0) Prohibit(1)
FilterSign_e BI Off(0) On(1)
FilterSignReset_e BV - Reset(1)
AirConModeCommand_e MO Cool(1)
AirConModeStatus_e MI Cool(1)
SwingCommand_e BO Stop(0) Run(1)
SwingStatus_e BI Stop(0) Run(1)
FanSpeedCommand_e MO Low(1)
FanSpeedStatus_e MI Low(1)
SetRoomTemp_e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_e AI ℃
Alarm_e BI Normal(0) Abnormal(1)
MalfunctionCode_e AI Refer to the
SetTempStatus_e AI ℃
Accumulated power(100 Watt)_e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_e AI ℃
TempRangeLowerLimitStatus_e AI ℃
ModeLockCommand_e BO Permit(0) Prohibit(1)
ModeLockStatus_e BI Permit(0) Prohibit(1)
FanLockCommand_e BO Permit(0) Prohibit(1)
FanLockStatus_e BI Permit(0) Prohibit(1)
OccupancyCommand_e BO Unoccupied(0) Occupied(1)
OccupancyStatus_e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_e BI Off(0) On(1)
AccumulatedGas(100 Watt)_e AI Wattage values (Unit : 100Watt)
DustSensorAvail_e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_e BO Stop(0) Run(1)
AirCleaningOperStatus_e BI Stop(0) Run(1)
FineDustStatus_e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_e AI %
ComfortCoolingAvail_e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_e BO Stop(0) Run(1)
ComfortCoolingOperStatus_e BI Stop(0) Run(1)
ComfortCoolingStepCommand_e AV 1~3 step
ComfortCoolingStepStatus_e AI 1~3 step
HumanDetectionAvail_e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_e MO Off(1)
HumanDetectionOperStatus_e MI Off(1)
HumanDetectionWindCommand_e MO Off(1)
HumanDetectionWindStatus_e MI Off(1)
HumanDetectionTimeCommand_e MO 5min(1)
HumanDetectionTimeStatus_e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
f ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_f BO Stop(0) Start(1)
StartStopStatus_f BI Stop(0) Start(1)
LockCommand_f BO Permit(0) Prohibit(1)
LockStatus_f BI Permit(0) Prohibit(1)
FilterSign_f BI Off(0) On(1)
FilterSignReset_f BV - Reset(1)
AirConModeCommand_f MO Cool(1)
AirConModeStatus_f MI Cool(1)
SwingCommand_f BO Stop(0) Run(1)
SwingStatus_f BI Stop(0) Run(1)
FanSpeedCommand_f MO Low(1)
FanSpeedStatus_f MI Low(1)
SetRoomTemp_f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_f AI ℃
Alarm_f BI Normal(0) Abnormal(1)
MalfunctionCode_f AI Refer to the
SetTempStatus_f AI ℃
Accumulated power(100 Watt)_f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_f AI ℃
TempRangeLowerLimitStatus_f AI ℃
ModeLockCommand_f BO Permit(0) Prohibit(1)
ModeLockStatus_f BI Permit(0) Prohibit(1)
FanLockCommand_f BO Permit(0) Prohibit(1)
FanLockStatus_f BI Permit(0) Prohibit(1)
OccupancyCommand_f BO Unoccupied(0) Occupied(1)
OccupancyStatus_f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_f BI Off(0) On(1)
AccumulatedGas(100 Watt)_f AI Wattage values (Unit : 100Watt)
DustSensorAvail_f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_f BO Stop(0) Run(1)
AirCleaningOperStatus_f BI Stop(0) Run(1)
FineDustStatus_f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_f AI %
ComfortCoolingAvail_f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_f BO Stop(0) Run(1)
ComfortCoolingOperStatus_f BI Stop(0) Run(1)
ComfortCoolingStepCommand_f AV 1~3 step
ComfortCoolingStepStatus_f AI 1~3 step
HumanDetectionAvail_f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_f MO Off(1)
HumanDetectionOperStatus_f MI Off(1)
HumanDetectionWindCommand_f MO Off(1)
HumanDetectionWindStatus_f MI Off(1)
HumanDetectionTimeCommand_f MO 5min(1)
HumanDetectionTimeStatus_f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
10 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_10 BO Stop(0) Start(1)
StartStopStatus_10 BI Stop(0) Start(1)
LockCommand_10 BO Permit(0) Prohibit(1)
LockStatus_10 BI Permit(0) Prohibit(1)
FilterSign_10 BI Off(0) On(1)
FilterSignReset_10 BV - Reset(1)
AirConModeCommand_10 MO Cool(1)
AirConModeStatus_10 MI Cool(1)
SwingCommand_10 BO Stop(0) Run(1)
SwingStatus_10 BI Stop(0) Run(1)
FanSpeedCommand_10 MO Low(1)
FanSpeedStatus_10 MI Low(1)
SetRoomTemp_10 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_10 AI ℃
Alarm_10 BI Normal(0) Abnormal(1)
MalfunctionCode_10 AI Refer to the
SetTempStatus_10 AI ℃
Accumulated power(100 Watt)_10 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_10 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_10 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_10 AI ℃
TempRangeLowerLimitStatus_10 AI ℃
ModeLockCommand_10 BO Permit(0) Prohibit(1)
ModeLockStatus_10 BI Permit(0) Prohibit(1)
FanLockCommand_10 BO Permit(0) Prohibit(1)
FanLockStatus_10 BI Permit(0) Prohibit(1)
OccupancyCommand_10 BO Unoccupied(0) Occupied(1)
OccupancyStatus_10 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_10 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_10 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_10 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_10 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_10 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_10 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_10 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_10 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_10 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_10 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_10 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_10 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_10 BI Off(0) On(1)
AccumulatedGas(100 Watt)_10 AI Wattage values (Unit : 100Watt)
DustSensorAvail_10 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_10 BO Stop(0) Run(1)
AirCleaningOperStatus_10 BI Stop(0) Run(1)
FineDustStatus_10 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_10 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_10 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_10 AI %
ComfortCoolingAvail_10 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_10 BO Stop(0) Run(1)
ComfortCoolingOperStatus_10 BI Stop(0) Run(1)
ComfortCoolingStepCommand_10 AV 1~3 step
ComfortCoolingStepStatus_10 AI 1~3 step
HumanDetectionAvail_10 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_10 MO Off(1)
HumanDetectionOperStatus_10 MI Off(1)
HumanDetectionWindCommand_10 MO Off(1)
HumanDetectionWindStatus_10 MI Off(1)
HumanDetectionTimeCommand_10 MO 5min(1)
HumanDetectionTimeStatus_10 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
11 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_11 BO Stop(0) Start(1)
StartStopStatus_11 BI Stop(0) Start(1)
LockCommand_11 BO Permit(0) Prohibit(1)
LockStatus_11 BI Permit(0) Prohibit(1)
FilterSign_11 BI Off(0) On(1)
FilterSignReset_11 BV - Reset(1)
AirConModeCommand_11 MO Cool(1)
AirConModeStatus_11 MI Cool(1)
SwingCommand_11 BO Stop(0) Run(1)
SwingStatus_11 BI Stop(0) Run(1)
FanSpeedCommand_11 MO Low(1)
FanSpeedStatus_11 MI Low(1)
SetRoomTemp_11 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_11 AI ℃
Alarm_11 BI Normal(0) Abnormal(1)
MalfunctionCode_11 AI Refer to the
SetTempStatus_11 AI ℃
Accumulated power(100 Watt)_11 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_11 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_11 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_11 AI ℃
TempRangeLowerLimitStatus_11 AI ℃
ModeLockCommand_11 BO Permit(0) Prohibit(1)
ModeLockStatus_11 BI Permit(0) Prohibit(1)
FanLockCommand_11 BO Permit(0) Prohibit(1)
FanLockStatus_11 BI Permit(0) Prohibit(1)
OccupancyCommand_11 BO Unoccupied(0) Occupied(1)
OccupancyStatus_11 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_11 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_11 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_11 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_11 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_11 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_11 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_11 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_11 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_11 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_11 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_11 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_11 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_11 BI Off(0) On(1)
AccumulatedGas(100 Watt)_11 AI Wattage values (Unit : 100Watt)
DustSensorAvail_11 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_11 BO Stop(0) Run(1)
AirCleaningOperStatus_11 BI Stop(0) Run(1)
FineDustStatus_11 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_11 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_11 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_11 AI %
ComfortCoolingAvail_11 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_11 BO Stop(0) Run(1)
ComfortCoolingOperStatus_11 BI Stop(0) Run(1)
ComfortCoolingStepCommand_11 AV 1~3 step
ComfortCoolingStepStatus_11 AI 1~3 step
HumanDetectionAvail_11 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_11 MO Off(1)
HumanDetectionOperStatus_11 MI Off(1)
HumanDetectionWindCommand_11 MO Off(1)
HumanDetectionWindStatus_11 MI Off(1)
HumanDetectionTimeCommand_11 MO 5min(1)
HumanDetectionTimeStatus_11 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
12 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_12 BO Stop(0) Start(1)
StartStopStatus_12 BI Stop(0) Start(1)
LockCommand_12 BO Permit(0) Prohibit(1)
LockStatus_12 BI Permit(0) Prohibit(1)
FilterSign_12 BI Off(0) On(1)
FilterSignReset_12 BV - Reset(1)
AirConModeCommand_12 MO Cool(1)
AirConModeStatus_12 MI Cool(1)
SwingCommand_12 BO Stop(0) Run(1)
SwingStatus_12 BI Stop(0) Run(1)
FanSpeedCommand_12 MO Low(1)
FanSpeedStatus_12 MI Low(1)
SetRoomTemp_12 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_12 AI ℃
Alarm_12 BI Normal(0) Abnormal(1)
MalfunctionCode_12 AI Refer to the
SetTempStatus_12 AI ℃
Accumulated power(100 Watt)_12 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_12 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_12 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_12 AI ℃
TempRangeLowerLimitStatus_12 AI ℃
ModeLockCommand_12 BO Permit(0) Prohibit(1)
ModeLockStatus_12 BI Permit(0) Prohibit(1)
FanLockCommand_12 BO Permit(0) Prohibit(1)
FanLockStatus_12 BI Permit(0) Prohibit(1)
OccupancyCommand_12 BO Unoccupied(0) Occupied(1)
OccupancyStatus_12 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_12 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_12 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_12 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_12 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_12 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_12 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_12 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_12 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_12 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_12 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_12 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_12 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_12 BI Off(0) On(1)
AccumulatedGas(100 Watt)_12 AI Wattage values (Unit : 100Watt)
DustSensorAvail_12 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_12 BO Stop(0) Run(1)
AirCleaningOperStatus_12 BI Stop(0) Run(1)
FineDustStatus_12 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_12 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_12 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_12 AI %
ComfortCoolingAvail_12 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_12 BO Stop(0) Run(1)
ComfortCoolingOperStatus_12 BI Stop(0) Run(1)
ComfortCoolingStepCommand_12 AV 1~3 step
ComfortCoolingStepStatus_12 AI 1~3 step
HumanDetectionAvail_12 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_12 MO Off(1)
HumanDetectionOperStatus_12 MI Off(1)
HumanDetectionWindCommand_12 MO Off(1)
HumanDetectionWindStatus_12 MI Off(1)
HumanDetectionTimeCommand_12 MO 5min(1)
HumanDetectionTimeStatus_12 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
13 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_13 BO Stop(0) Start(1)
StartStopStatus_13 BI Stop(0) Start(1)
LockCommand_13 BO Permit(0) Prohibit(1)
LockStatus_13 BI Permit(0) Prohibit(1)
FilterSign_13 BI Off(0) On(1)
FilterSignReset_13 BV - Reset(1)
AirConModeCommand_13 MO Cool(1)
AirConModeStatus_13 MI Cool(1)
SwingCommand_13 BO Stop(0) Run(1)
SwingStatus_13 BI Stop(0) Run(1)
FanSpeedCommand_13 MO Low(1)
FanSpeedStatus_13 MI Low(1)
SetRoomTemp_13 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_13 AI ℃
Alarm_13 BI Normal(0) Abnormal(1)
MalfunctionCode_13 AI Refer to the
SetTempStatus_13 AI ℃
Accumulated power(100 Watt)_13 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_13 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_13 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_13 AI ℃
TempRangeLowerLimitStatus_13 AI ℃
ModeLockCommand_13 BO Permit(0) Prohibit(1)
ModeLockStatus_13 BI Permit(0) Prohibit(1)
FanLockCommand_13 BO Permit(0) Prohibit(1)
FanLockStatus_13 BI Permit(0) Prohibit(1)
OccupancyCommand_13 BO Unoccupied(0) Occupied(1)
OccupancyStatus_13 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_13 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_13 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_13 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_13 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_13 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_13 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_13 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_13 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_13 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_13 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_13 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_13 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_13 BI Off(0) On(1)
AccumulatedGas(100 Watt)_13 AI Wattage values (Unit : 100Watt)
DustSensorAvail_13 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_13 BO Stop(0) Run(1)
AirCleaningOperStatus_13 BI Stop(0) Run(1)
FineDustStatus_13 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_13 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_13 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_13 AI %
ComfortCoolingAvail_13 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_13 BO Stop(0) Run(1)
ComfortCoolingOperStatus_13 BI Stop(0) Run(1)
ComfortCoolingStepCommand_13 AV 1~3 step
ComfortCoolingStepStatus_13 AI 1~3 step
HumanDetectionAvail_13 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_13 MO Off(1)
HumanDetectionOperStatus_13 MI Off(1)
HumanDetectionWindCommand_13 MO Off(1)
HumanDetectionWindStatus_13 MI Off(1)
HumanDetectionTimeCommand_13 MO 5min(1)
HumanDetectionTimeStatus_13 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
14 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_14 BO Stop(0) Start(1)
StartStopStatus_14 BI Stop(0) Start(1)
LockCommand_14 BO Permit(0) Prohibit(1)
LockStatus_14 BI Permit(0) Prohibit(1)
FilterSign_14 BI Off(0) On(1)
FilterSignReset_14 BV - Reset(1)
AirConModeCommand_14 MO Cool(1)
AirConModeStatus_14 MI Cool(1)
SwingCommand_14 BO Stop(0) Run(1)
SwingStatus_14 BI Stop(0) Run(1)
FanSpeedCommand_14 MO Low(1)
FanSpeedStatus_14 MI Low(1)
SetRoomTemp_14 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_14 AI ℃
Alarm_14 BI Normal(0) Abnormal(1)
MalfunctionCode_14 AI Refer to the
SetTempStatus_14 AI ℃
Accumulated power(100 Watt)_14 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_14 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_14 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_14 AI ℃
TempRangeLowerLimitStatus_14 AI ℃
ModeLockCommand_14 BO Permit(0) Prohibit(1)
ModeLockStatus_14 BI Permit(0) Prohibit(1)
FanLockCommand_14 BO Permit(0) Prohibit(1)
FanLockStatus_14 BI Permit(0) Prohibit(1)
OccupancyCommand_14 BO Unoccupied(0) Occupied(1)
OccupancyStatus_14 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_14 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_14 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_14 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_14 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_14 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_14 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_14 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_14 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_14 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_14 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_14 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_14 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_14 BI Off(0) On(1)
AccumulatedGas(100 Watt)_14 AI Wattage values (Unit : 100Watt)
DustSensorAvail_14 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_14 BO Stop(0) Run(1)
AirCleaningOperStatus_14 BI Stop(0) Run(1)
FineDustStatus_14 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_14 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_14 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_14 AI %
ComfortCoolingAvail_14 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_14 BO Stop(0) Run(1)
ComfortCoolingOperStatus_14 BI Stop(0) Run(1)
ComfortCoolingStepCommand_14 AV 1~3 step
ComfortCoolingStepStatus_14 AI 1~3 step
HumanDetectionAvail_14 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_14 MO Off(1)
HumanDetectionOperStatus_14 MI Off(1)
HumanDetectionWindCommand_14 MO Off(1)
HumanDetectionWindStatus_14 MI Off(1)
HumanDetectionTimeCommand_14 MO 5min(1)
HumanDetectionTimeStatus_14 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
15 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_15 BO Stop(0) Start(1)
StartStopStatus_15 BI Stop(0) Start(1)
LockCommand_15 BO Permit(0) Prohibit(1)
LockStatus_15 BI Permit(0) Prohibit(1)
FilterSign_15 BI Off(0) On(1)
FilterSignReset_15 BV - Reset(1)
AirConModeCommand_15 MO Cool(1)
AirConModeStatus_15 MI Cool(1)
SwingCommand_15 BO Stop(0) Run(1)
SwingStatus_15 BI Stop(0) Run(1)
FanSpeedCommand_15 MO Low(1)
FanSpeedStatus_15 MI Low(1)
SetRoomTemp_15 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_15 AI ℃
Alarm_15 BI Normal(0) Abnormal(1)
MalfunctionCode_15 AI Refer to the
SetTempStatus_15 AI ℃
Accumulated power(100 Watt)_15 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_15 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_15 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_15 AI ℃
TempRangeLowerLimitStatus_15 AI ℃
ModeLockCommand_15 BO Permit(0) Prohibit(1)
ModeLockStatus_15 BI Permit(0) Prohibit(1)
FanLockCommand_15 BO Permit(0) Prohibit(1)
FanLockStatus_15 BI Permit(0) Prohibit(1)
OccupancyCommand_15 BO Unoccupied(0) Occupied(1)
OccupancyStatus_15 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_15 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_15 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_15 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_15 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_15 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_15 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_15 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_15 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_15 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_15 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_15 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_15 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_15 BI Off(0) On(1)
AccumulatedGas(100 Watt)_15 AI Wattage values (Unit : 100Watt)
DustSensorAvail_15 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_15 BO Stop(0) Run(1)
AirCleaningOperStatus_15 BI Stop(0) Run(1)
FineDustStatus_15 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_15 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_15 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_15 AI %
ComfortCoolingAvail_15 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_15 BO Stop(0) Run(1)
ComfortCoolingOperStatus_15 BI Stop(0) Run(1)
ComfortCoolingStepCommand_15 AV 1~3 step
ComfortCoolingStepStatus_15 AI 1~3 step
HumanDetectionAvail_15 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_15 MO Off(1)
HumanDetectionOperStatus_15 MI Off(1)
HumanDetectionWindCommand_15 MO Off(1)
HumanDetectionWindStatus_15 MI Off(1)
HumanDetectionTimeCommand_15 MO 5min(1)
HumanDetectionTimeStatus_15 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
16 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_16 BO Stop(0) Start(1)
StartStopStatus_16 BI Stop(0) Start(1)
LockCommand_16 BO Permit(0) Prohibit(1)
LockStatus_16 BI Permit(0) Prohibit(1)
FilterSign_16 BI Off(0) On(1)
FilterSignReset_16 BV - Reset(1)
AirConModeCommand_16 MO Cool(1)
AirConModeStatus_16 MI Cool(1)
SwingCommand_16 BO Stop(0) Run(1)
SwingStatus_16 BI Stop(0) Run(1)
FanSpeedCommand_16 MO Low(1)
FanSpeedStatus_16 MI Low(1)
SetRoomTemp_16 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_16 AI ℃
Alarm_16 BI Normal(0) Abnormal(1)
MalfunctionCode_16 AI Refer to the
SetTempStatus_16 AI ℃
Accumulated power(100 Watt)_16 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_16 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_16 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_16 AI ℃
TempRangeLowerLimitStatus_16 AI ℃
ModeLockCommand_16 BO Permit(0) Prohibit(1)
ModeLockStatus_16 BI Permit(0) Prohibit(1)
FanLockCommand_16 BO Permit(0) Prohibit(1)
FanLockStatus_16 BI Permit(0) Prohibit(1)
OccupancyCommand_16 BO Unoccupied(0) Occupied(1)
OccupancyStatus_16 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_16 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_16 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_16 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_16 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_16 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_16 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_16 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_16 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_16 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_16 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_16 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_16 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_16 BI Off(0) On(1)
AccumulatedGas(100 Watt)_16 AI Wattage values (Unit : 100Watt)
DustSensorAvail_16 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_16 BO Stop(0) Run(1)
AirCleaningOperStatus_16 BI Stop(0) Run(1)
FineDustStatus_16 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_16 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_16 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_16 AI %
ComfortCoolingAvail_16 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_16 BO Stop(0) Run(1)
ComfortCoolingOperStatus_16 BI Stop(0) Run(1)
ComfortCoolingStepCommand_16 AV 1~3 step
ComfortCoolingStepStatus_16 AI 1~3 step
HumanDetectionAvail_16 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_16 MO Off(1)
HumanDetectionOperStatus_16 MI Off(1)
HumanDetectionWindCommand_16 MO Off(1)
HumanDetectionWindStatus_16 MI Off(1)
HumanDetectionTimeCommand_16 MO 5min(1)
HumanDetectionTimeStatus_16 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
17 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_17 BO Stop(0) Start(1)
StartStopStatus_17 BI Stop(0) Start(1)
LockCommand_17 BO Permit(0) Prohibit(1)
LockStatus_17 BI Permit(0) Prohibit(1)
FilterSign_17 BI Off(0) On(1)
FilterSignReset_17 BV - Reset(1)
AirConModeCommand_17 MO Cool(1)
AirConModeStatus_17 MI Cool(1)
SwingCommand_17 BO Stop(0) Run(1)
SwingStatus_17 BI Stop(0) Run(1)
FanSpeedCommand_17 MO Low(1)
FanSpeedStatus_17 MI Low(1)
SetRoomTemp_17 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_17 AI ℃
Alarm_17 BI Normal(0) Abnormal(1)
MalfunctionCode_17 AI Refer to the
SetTempStatus_17 AI ℃
Accumulated power(100 Watt)_17 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_17 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_17 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_17 AI ℃
TempRangeLowerLimitStatus_17 AI ℃
ModeLockCommand_17 BO Permit(0) Prohibit(1)
ModeLockStatus_17 BI Permit(0) Prohibit(1)
FanLockCommand_17 BO Permit(0) Prohibit(1)
FanLockStatus_17 BI Permit(0) Prohibit(1)
OccupancyCommand_17 BO Unoccupied(0) Occupied(1)
OccupancyStatus_17 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_17 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_17 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_17 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_17 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_17 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_17 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_17 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_17 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_17 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_17 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_17 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_17 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_17 BI Off(0) On(1)
AccumulatedGas(100 Watt)_17 AI Wattage values (Unit : 100Watt)
DustSensorAvail_17 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_17 BO Stop(0) Run(1)
AirCleaningOperStatus_17 BI Stop(0) Run(1)
FineDustStatus_17 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_17 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_17 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_17 AI %
ComfortCoolingAvail_17 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_17 BO Stop(0) Run(1)
ComfortCoolingOperStatus_17 BI Stop(0) Run(1)
ComfortCoolingStepCommand_17 AV 1~3 step
ComfortCoolingStepStatus_17 AI 1~3 step
HumanDetectionAvail_17 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_17 MO Off(1)
HumanDetectionOperStatus_17 MI Off(1)
HumanDetectionWindCommand_17 MO Off(1)
HumanDetectionWindStatus_17 MI Off(1)
HumanDetectionTimeCommand_17 MO 5min(1)
HumanDetectionTimeStatus_17 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
18 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_18 BO Stop(0) Start(1)
StartStopStatus_18 BI Stop(0) Start(1)
LockCommand_18 BO Permit(0) Prohibit(1)
LockStatus_18 BI Permit(0) Prohibit(1)
FilterSign_18 BI Off(0) On(1)
FilterSignReset_18 BV - Reset(1)
AirConModeCommand_18 MO Cool(1)
AirConModeStatus_18 MI Cool(1)
SwingCommand_18 BO Stop(0) Run(1)
SwingStatus_18 BI Stop(0) Run(1)
FanSpeedCommand_18 MO Low(1)
FanSpeedStatus_18 MI Low(1)
SetRoomTemp_18 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_18 AI ℃
Alarm_18 BI Normal(0) Abnormal(1)
MalfunctionCode_18 AI Refer to the
SetTempStatus_18 AI ℃
Accumulated power(100 Watt)_18 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_18 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_18 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_18 AI ℃
TempRangeLowerLimitStatus_18 AI ℃
ModeLockCommand_18 BO Permit(0) Prohibit(1)
ModeLockStatus_18 BI Permit(0) Prohibit(1)
FanLockCommand_18 BO Permit(0) Prohibit(1)
FanLockStatus_18 BI Permit(0) Prohibit(1)
OccupancyCommand_18 BO Unoccupied(0) Occupied(1)
OccupancyStatus_18 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_18 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_18 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_18 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_18 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_18 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_18 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_18 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_18 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_18 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_18 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_18 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_18 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_18 BI Off(0) On(1)
AccumulatedGas(100 Watt)_18 AI Wattage values (Unit : 100Watt)
DustSensorAvail_18 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_18 BO Stop(0) Run(1)
AirCleaningOperStatus_18 BI Stop(0) Run(1)
FineDustStatus_18 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_18 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_18 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_18 AI %
ComfortCoolingAvail_18 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_18 BO Stop(0) Run(1)
ComfortCoolingOperStatus_18 BI Stop(0) Run(1)
ComfortCoolingStepCommand_18 AV 1~3 step
ComfortCoolingStepStatus_18 AI 1~3 step
HumanDetectionAvail_18 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_18 MO Off(1)
HumanDetectionOperStatus_18 MI Off(1)
HumanDetectionWindCommand_18 MO Off(1)
HumanDetectionWindStatus_18 MI Off(1)
HumanDetectionTimeCommand_18 MO 5min(1)
HumanDetectionTimeStatus_18 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
19 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_19 BO Stop(0) Start(1)
StartStopStatus_19 BI Stop(0) Start(1)
LockCommand_19 BO Permit(0) Prohibit(1)
LockStatus_19 BI Permit(0) Prohibit(1)
FilterSign_19 BI Off(0) On(1)
FilterSignReset_19 BV - Reset(1)
AirConModeCommand_19 MO Cool(1)
AirConModeStatus_19 MI Cool(1)
SwingCommand_19 BO Stop(0) Run(1)
SwingStatus_19 BI Stop(0) Run(1)
FanSpeedCommand_19 MO Low(1)
FanSpeedStatus_19 MI Low(1)
SetRoomTemp_19 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_19 AI ℃
Alarm_19 BI Normal(0) Abnormal(1)
MalfunctionCode_19 AI Refer to the
SetTempStatus_19 AI ℃
Accumulated power(100 Watt)_19 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_19 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_19 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_19 AI ℃
TempRangeLowerLimitStatus_19 AI ℃
ModeLockCommand_19 BO Permit(0) Prohibit(1)
ModeLockStatus_19 BI Permit(0) Prohibit(1)
FanLockCommand_19 BO Permit(0) Prohibit(1)
FanLockStatus_19 BI Permit(0) Prohibit(1)
OccupancyCommand_19 BO Unoccupied(0) Occupied(1)
OccupancyStatus_19 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_19 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_19 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_19 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_19 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_19 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_19 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_19 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_19 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_19 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_19 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_19 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_19 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_19 BI Off(0) On(1)
AccumulatedGas(100 Watt)_19 AI Wattage values (Unit : 100Watt)
DustSensorAvail_19 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_19 BO Stop(0) Run(1)
AirCleaningOperStatus_19 BI Stop(0) Run(1)
FineDustStatus_19 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_19 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_19 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_19 AI %
ComfortCoolingAvail_19 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_19 BO Stop(0) Run(1)
ComfortCoolingOperStatus_19 BI Stop(0) Run(1)
ComfortCoolingStepCommand_19 AV 1~3 step
ComfortCoolingStepStatus_19 AI 1~3 step
HumanDetectionAvail_19 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_19 MO Off(1)
HumanDetectionOperStatus_19 MI Off(1)
HumanDetectionWindCommand_19 MO Off(1)
HumanDetectionWindStatus_19 MI Off(1)
HumanDetectionTimeCommand_19 MO 5min(1)
HumanDetectionTimeStatus_19 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1a ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1a BO Stop(0) Start(1)
StartStopStatus_1a BI Stop(0) Start(1)
LockCommand_1a BO Permit(0) Prohibit(1)
LockStatus_1a BI Permit(0) Prohibit(1)
FilterSign_1a BI Off(0) On(1)
FilterSignReset_1a BV - Reset(1)
AirConModeCommand_1a MO Cool(1)
AirConModeStatus_1a MI Cool(1)
SwingCommand_1a BO Stop(0) Run(1)
SwingStatus_1a BI Stop(0) Run(1)
FanSpeedCommand_1a MO Low(1)
FanSpeedStatus_1a MI Low(1)
SetRoomTemp_1a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1a AI ℃
Alarm_1a BI Normal(0) Abnormal(1)
MalfunctionCode_1a AI Refer to the
SetTempStatus_1a AI ℃
Accumulated power(100 Watt)_1a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1a AI ℃
TempRangeLowerLimitStatus_1a AI ℃
ModeLockCommand_1a BO Permit(0) Prohibit(1)
ModeLockStatus_1a BI Permit(0) Prohibit(1)
FanLockCommand_1a BO Permit(0) Prohibit(1)
FanLockStatus_1a BI Permit(0) Prohibit(1)
OccupancyCommand_1a BO Unoccupied(0) Occupied(1)
OccupancyStatus_1a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1a BI Off(0) On(1)
AccumulatedGas(100 Watt)_1a AI Wattage values (Unit : 100Watt)
DustSensorAvail_1a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1a BO Stop(0) Run(1)
AirCleaningOperStatus_1a BI Stop(0) Run(1)
FineDustStatus_1a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1a AI %
ComfortCoolingAvail_1a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1a BO Stop(0) Run(1)
ComfortCoolingOperStatus_1a BI Stop(0) Run(1)
ComfortCoolingStepCommand_1a AV 1~3 step
ComfortCoolingStepStatus_1a AI 1~3 step
HumanDetectionAvail_1a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1a MO Off(1)
HumanDetectionOperStatus_1a MI Off(1)
HumanDetectionWindCommand_1a MO Off(1)
HumanDetectionWindStatus_1a MI Off(1)
HumanDetectionTimeCommand_1a MO 5min(1)
HumanDetectionTimeStatus_1a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1d ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1d BO Stop(0) Start(1)
StartStopStatus_1d BI Stop(0) Start(1)
LockCommand_1d BO Permit(0) Prohibit(1)
LockStatus_1d BI Permit(0) Prohibit(1)
FilterSign_1d BI Off(0) On(1)
FilterSignReset_1d BV - Reset(1)
AirConModeCommand_1d MO Cool(1)
AirConModeStatus_1d MI Cool(1)
SwingCommand_1d BO Stop(0) Run(1)
SwingStatus_1d BI Stop(0) Run(1)
FanSpeedCommand_1d MO Low(1)
FanSpeedStatus_1d MI Low(1)
SetRoomTemp_1d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1d AI ℃
Alarm_1d BI Normal(0) Abnormal(1)
MalfunctionCode_1d AI Refer to the
SetTempStatus_1d AI ℃
Accumulated power(100 Watt)_1d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1d AI ℃
TempRangeLowerLimitStatus_1d AI ℃
ModeLockCommand_1d BO Permit(0) Prohibit(1)
ModeLockStatus_1d BI Permit(0) Prohibit(1)
FanLockCommand_1d BO Permit(0) Prohibit(1)
FanLockStatus_1d BI Permit(0) Prohibit(1)
OccupancyCommand_1d BO Unoccupied(0) Occupied(1)
OccupancyStatus_1d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1d BI Off(0) On(1)
AccumulatedGas(100 Watt)_1d AI Wattage values (Unit : 100Watt)
DustSensorAvail_1d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1d BO Stop(0) Run(1)
AirCleaningOperStatus_1d BI Stop(0) Run(1)
FineDustStatus_1d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1d AI %
ComfortCoolingAvail_1d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1d BO Stop(0) Run(1)
ComfortCoolingOperStatus_1d BI Stop(0) Run(1)
ComfortCoolingStepCommand_1d AV 1~3 step
ComfortCoolingStepStatus_1d AI 1~3 step
HumanDetectionAvail_1d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1d MO Off(1)
HumanDetectionOperStatus_1d MI Off(1)
HumanDetectionWindCommand_1d MO Off(1)
HumanDetectionWindStatus_1d MI Off(1)
HumanDetectionTimeCommand_1d MO 5min(1)
HumanDetectionTimeStatus_1d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1e ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1e BO Stop(0) Start(1)
StartStopStatus_1e BI Stop(0) Start(1)
LockCommand_1e BO Permit(0) Prohibit(1)
LockStatus_1e BI Permit(0) Prohibit(1)
FilterSign_1e BI Off(0) On(1)
FilterSignReset_1e BV - Reset(1)
AirConModeCommand_1e MO Cool(1)
AirConModeStatus_1e MI Cool(1)
SwingCommand_1e BO Stop(0) Run(1)
SwingStatus_1e BI Stop(0) Run(1)
FanSpeedCommand_1e MO Low(1)
FanSpeedStatus_1e MI Low(1)
SetRoomTemp_1e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1e AI ℃
Alarm_1e BI Normal(0) Abnormal(1)
MalfunctionCode_1e AI Refer to the
SetTempStatus_1e AI ℃
Accumulated power(100 Watt)_1e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1e AI ℃
TempRangeLowerLimitStatus_1e AI ℃
ModeLockCommand_1e BO Permit(0) Prohibit(1)
ModeLockStatus_1e BI Permit(0) Prohibit(1)
FanLockCommand_1e BO Permit(0) Prohibit(1)
FanLockStatus_1e BI Permit(0) Prohibit(1)
OccupancyCommand_1e BO Unoccupied(0) Occupied(1)
OccupancyStatus_1e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1e BI Off(0) On(1)
AccumulatedGas(100 Watt)_1e AI Wattage values (Unit : 100Watt)
DustSensorAvail_1e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1e BO Stop(0) Run(1)
AirCleaningOperStatus_1e BI Stop(0) Run(1)
FineDustStatus_1e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1e AI %
ComfortCoolingAvail_1e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1e BO Stop(0) Run(1)
ComfortCoolingOperStatus_1e BI Stop(0) Run(1)
ComfortCoolingStepCommand_1e AV 1~3 step
ComfortCoolingStepStatus_1e AI 1~3 step
HumanDetectionAvail_1e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1e MO Off(1)
HumanDetectionOperStatus_1e MI Off(1)
HumanDetectionWindCommand_1e MO Off(1)
HumanDetectionWindStatus_1e MI Off(1)
HumanDetectionTimeCommand_1e MO 5min(1)
HumanDetectionTimeStatus_1e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
1f ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_1f BO Stop(0) Start(1)
StartStopStatus_1f BI Stop(0) Start(1)
LockCommand_1f BO Permit(0) Prohibit(1)
LockStatus_1f BI Permit(0) Prohibit(1)
FilterSign_1f BI Off(0) On(1)
FilterSignReset_1f BV - Reset(1)
AirConModeCommand_1f MO Cool(1)
AirConModeStatus_1f MI Cool(1)
SwingCommand_1f BO Stop(0) Run(1)
SwingStatus_1f BI Stop(0) Run(1)
FanSpeedCommand_1f MO Low(1)
FanSpeedStatus_1f MI Low(1)
SetRoomTemp_1f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_1f AI ℃
Alarm_1f BI Normal(0) Abnormal(1)
MalfunctionCode_1f AI Refer to the
SetTempStatus_1f AI ℃
Accumulated power(100 Watt)_1f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_1f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_1f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_1f AI ℃
TempRangeLowerLimitStatus_1f AI ℃
ModeLockCommand_1f BO Permit(0) Prohibit(1)
ModeLockStatus_1f BI Permit(0) Prohibit(1)
FanLockCommand_1f BO Permit(0) Prohibit(1)
FanLockStatus_1f BI Permit(0) Prohibit(1)
OccupancyCommand_1f BO Unoccupied(0) Occupied(1)
OccupancyStatus_1f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_1f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_1f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_1f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_1f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_1f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_1f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_1f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_1f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_1f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_1f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_1f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_1f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_1f BI Off(0) On(1)
AccumulatedGas(100 Watt)_1f AI Wattage values (Unit : 100Watt)
DustSensorAvail_1f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_1f BO Stop(0) Run(1)
AirCleaningOperStatus_1f BI Stop(0) Run(1)
FineDustStatus_1f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_1f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_1f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_1f AI %
ComfortCoolingAvail_1f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_1f BO Stop(0) Run(1)
ComfortCoolingOperStatus_1f BI Stop(0) Run(1)
ComfortCoolingStepCommand_1f AV 1~3 step
ComfortCoolingStepStatus_1f AI 1~3 step
HumanDetectionAvail_1f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_1f MO Off(1)
HumanDetectionOperStatus_1f MI Off(1)
HumanDetectionWindCommand_1f MO Off(1)
HumanDetectionWindStatus_1f MI Off(1)
HumanDetectionTimeCommand_1f MO 5min(1)
HumanDetectionTimeStatus_1f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
20 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_20 BO Stop(0) Start(1)
StartStopStatus_20 BI Stop(0) Start(1)
LockCommand_20 BO Permit(0) Prohibit(1)
LockStatus_20 BI Permit(0) Prohibit(1)
FilterSign_20 BI Off(0) On(1)
FilterSignReset_20 BV - Reset(1)
AirConModeCommand_20 MO Cool(1)
AirConModeStatus_20 MI Cool(1)
SwingCommand_20 BO Stop(0) Run(1)
SwingStatus_20 BI Stop(0) Run(1)
FanSpeedCommand_20 MO Low(1)
FanSpeedStatus_20 MI Low(1)
SetRoomTemp_20 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_20 AI ℃
Alarm_20 BI Normal(0) Abnormal(1)
MalfunctionCode_20 AI Refer to the
SetTempStatus_20 AI ℃
Accumulated power(100 Watt)_20 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_20 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_20 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_20 AI ℃
TempRangeLowerLimitStatus_20 AI ℃
ModeLockCommand_20 BO Permit(0) Prohibit(1)
ModeLockStatus_20 BI Permit(0) Prohibit(1)
FanLockCommand_20 BO Permit(0) Prohibit(1)
FanLockStatus_20 BI Permit(0) Prohibit(1)
OccupancyCommand_20 BO Unoccupied(0) Occupied(1)
OccupancyStatus_20 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_20 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_20 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_20 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_20 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_20 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_20 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_20 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_20 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_20 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_20 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_20 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_20 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_20 BI Off(0) On(1)
AccumulatedGas(100 Watt)_20 AI Wattage values (Unit : 100Watt)
DustSensorAvail_20 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_20 BO Stop(0) Run(1)
AirCleaningOperStatus_20 BI Stop(0) Run(1)
FineDustStatus_20 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_20 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_20 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_20 AI %
ComfortCoolingAvail_20 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_20 BO Stop(0) Run(1)
ComfortCoolingOperStatus_20 BI Stop(0) Run(1)
ComfortCoolingStepCommand_20 AV 1~3 step
ComfortCoolingStepStatus_20 AI 1~3 step
HumanDetectionAvail_20 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_20 MO Off(1)
HumanDetectionOperStatus_20 MI Off(1)
HumanDetectionWindCommand_20 MO Off(1)
HumanDetectionWindStatus_20 MI Off(1)
HumanDetectionTimeCommand_20 MO 5min(1)
HumanDetectionTimeStatus_20 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
21 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_21 BO Stop(0) Start(1)
StartStopStatus_21 BI Stop(0) Start(1)
LockCommand_21 BO Permit(0) Prohibit(1)
LockStatus_21 BI Permit(0) Prohibit(1)
FilterSign_21 BI Off(0) On(1)
FilterSignReset_21 BV - Reset(1)
AirConModeCommand_21 MO Cool(1)
AirConModeStatus_21 MI Cool(1)
SwingCommand_21 BO Stop(0) Run(1)
SwingStatus_21 BI Stop(0) Run(1)
FanSpeedCommand_21 MO Low(1)
FanSpeedStatus_21 MI Low(1)
SetRoomTemp_21 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_21 AI ℃
Alarm_21 BI Normal(0) Abnormal(1)
MalfunctionCode_21 AI Refer to the
SetTempStatus_21 AI ℃
Accumulated power(100 Watt)_21 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_21 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_21 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_21 AI ℃
TempRangeLowerLimitStatus_21 AI ℃
ModeLockCommand_21 BO Permit(0) Prohibit(1)
ModeLockStatus_21 BI Permit(0) Prohibit(1)
FanLockCommand_21 BO Permit(0) Prohibit(1)
FanLockStatus_21 BI Permit(0) Prohibit(1)
OccupancyCommand_21 BO Unoccupied(0) Occupied(1)
OccupancyStatus_21 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_21 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_21 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_21 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_21 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_21 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_21 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_21 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_21 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_21 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_21 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_21 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_21 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_21 BI Off(0) On(1)
AccumulatedGas(100 Watt)_21 AI Wattage values (Unit : 100Watt)
DustSensorAvail_21 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_21 BO Stop(0) Run(1)
AirCleaningOperStatus_21 BI Stop(0) Run(1)
FineDustStatus_21 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_21 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_21 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_21 AI %
ComfortCoolingAvail_21 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_21 BO Stop(0) Run(1)
ComfortCoolingOperStatus_21 BI Stop(0) Run(1)
ComfortCoolingStepCommand_21 AV 1~3 step
ComfortCoolingStepStatus_21 AI 1~3 step
HumanDetectionAvail_21 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_21 MO Off(1)
HumanDetectionOperStatus_21 MI Off(1)
HumanDetectionWindCommand_21 MO Off(1)
HumanDetectionWindStatus_21 MI Off(1)
HumanDetectionTimeCommand_21 MO 5min(1)
HumanDetectionTimeStatus_21 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
22 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_22 BO Stop(0) Start(1)
StartStopStatus_22 BI Stop(0) Start(1)
LockCommand_22 BO Permit(0) Prohibit(1)
LockStatus_22 BI Permit(0) Prohibit(1)
FilterSign_22 BI Off(0) On(1)
FilterSignReset_22 BV - Reset(1)
AirConModeCommand_22 MO Cool(1)
AirConModeStatus_22 MI Cool(1)
SwingCommand_22 BO Stop(0) Run(1)
SwingStatus_22 BI Stop(0) Run(1)
FanSpeedCommand_22 MO Low(1)
FanSpeedStatus_22 MI Low(1)
SetRoomTemp_22 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_22 AI ℃
Alarm_22 BI Normal(0) Abnormal(1)
MalfunctionCode_22 AI Refer to the
SetTempStatus_22 AI ℃
Accumulated power(100 Watt)_22 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_22 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_22 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_22 AI ℃
TempRangeLowerLimitStatus_22 AI ℃
ModeLockCommand_22 BO Permit(0) Prohibit(1)
ModeLockStatus_22 BI Permit(0) Prohibit(1)
FanLockCommand_22 BO Permit(0) Prohibit(1)
FanLockStatus_22 BI Permit(0) Prohibit(1)
OccupancyCommand_22 BO Unoccupied(0) Occupied(1)
OccupancyStatus_22 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_22 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_22 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_22 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_22 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_22 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_22 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_22 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_22 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_22 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_22 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_22 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_22 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_22 BI Off(0) On(1)
AccumulatedGas(100 Watt)_22 AI Wattage values (Unit : 100Watt)
DustSensorAvail_22 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_22 BO Stop(0) Run(1)
AirCleaningOperStatus_22 BI Stop(0) Run(1)
FineDustStatus_22 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_22 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_22 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_22 AI %
ComfortCoolingAvail_22 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_22 BO Stop(0) Run(1)
ComfortCoolingOperStatus_22 BI Stop(0) Run(1)
ComfortCoolingStepCommand_22 AV 1~3 step
ComfortCoolingStepStatus_22 AI 1~3 step
HumanDetectionAvail_22 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_22 MO Off(1)
HumanDetectionOperStatus_22 MI Off(1)
HumanDetectionWindCommand_22 MO Off(1)
HumanDetectionWindStatus_22 MI Off(1)
HumanDetectionTimeCommand_22 MO 5min(1)
HumanDetectionTimeStatus_22 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
23 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_23 BO Stop(0) Start(1)
StartStopStatus_23 BI Stop(0) Start(1)
LockCommand_23 BO Permit(0) Prohibit(1)
LockStatus_23 BI Permit(0) Prohibit(1)
FilterSign_23 BI Off(0) On(1)
FilterSignReset_23 BV - Reset(1)
AirConModeCommand_23 MO Cool(1)
AirConModeStatus_23 MI Cool(1)
SwingCommand_23 BO Stop(0) Run(1)
SwingStatus_23 BI Stop(0) Run(1)
FanSpeedCommand_23 MO Low(1)
FanSpeedStatus_23 MI Low(1)
SetRoomTemp_23 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_23 AI ℃
Alarm_23 BI Normal(0) Abnormal(1)
MalfunctionCode_23 AI Refer to the
SetTempStatus_23 AI ℃
Accumulated power(100 Watt)_23 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_23 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_23 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_23 AI ℃
TempRangeLowerLimitStatus_23 AI ℃
ModeLockCommand_23 BO Permit(0) Prohibit(1)
ModeLockStatus_23 BI Permit(0) Prohibit(1)
FanLockCommand_23 BO Permit(0) Prohibit(1)
FanLockStatus_23 BI Permit(0) Prohibit(1)
OccupancyCommand_23 BO Unoccupied(0) Occupied(1)
OccupancyStatus_23 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_23 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_23 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_23 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_23 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_23 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_23 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_23 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_23 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_23 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_23 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_23 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_23 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_23 BI Off(0) On(1)
AccumulatedGas(100 Watt)_23 AI Wattage values (Unit : 100Watt)
DustSensorAvail_23 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_23 BO Stop(0) Run(1)
AirCleaningOperStatus_23 BI Stop(0) Run(1)
FineDustStatus_23 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_23 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_23 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_23 AI %
ComfortCoolingAvail_23 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_23 BO Stop(0) Run(1)
ComfortCoolingOperStatus_23 BI Stop(0) Run(1)
ComfortCoolingStepCommand_23 AV 1~3 step
ComfortCoolingStepStatus_23 AI 1~3 step
HumanDetectionAvail_23 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_23 MO Off(1)
HumanDetectionOperStatus_23 MI Off(1)
HumanDetectionWindCommand_23 MO Off(1)
HumanDetectionWindStatus_23 MI Off(1)
HumanDetectionTimeCommand_23 MO 5min(1)
HumanDetectionTimeStatus_23 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
24 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_24 BO Stop(0) Start(1)
StartStopStatus_24 BI Stop(0) Start(1)
LockCommand_24 BO Permit(0) Prohibit(1)
LockStatus_24 BI Permit(0) Prohibit(1)
FilterSign_24 BI Off(0) On(1)
FilterSignReset_24 BV - Reset(1)
AirConModeCommand_24 MO Cool(1)
AirConModeStatus_24 MI Cool(1)
SwingCommand_24 BO Stop(0) Run(1)
SwingStatus_24 BI Stop(0) Run(1)
FanSpeedCommand_24 MO Low(1)
FanSpeedStatus_24 MI Low(1)
SetRoomTemp_24 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_24 AI ℃
Alarm_24 BI Normal(0) Abnormal(1)
MalfunctionCode_24 AI Refer to the
SetTempStatus_24 AI ℃
Accumulated power(100 Watt)_24 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_24 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_24 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_24 AI ℃
TempRangeLowerLimitStatus_24 AI ℃
ModeLockCommand_24 BO Permit(0) Prohibit(1)
ModeLockStatus_24 BI Permit(0) Prohibit(1)
FanLockCommand_24 BO Permit(0) Prohibit(1)
FanLockStatus_24 BI Permit(0) Prohibit(1)
OccupancyCommand_24 BO Unoccupied(0) Occupied(1)
OccupancyStatus_24 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_24 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_24 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_24 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_24 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_24 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_24 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_24 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_24 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_24 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_24 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_24 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_24 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_24 BI Off(0) On(1)
AccumulatedGas(100 Watt)_24 AI Wattage values (Unit : 100Watt)
DustSensorAvail_24 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_24 BO Stop(0) Run(1)
AirCleaningOperStatus_24 BI Stop(0) Run(1)
FineDustStatus_24 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_24 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_24 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_24 AI %
ComfortCoolingAvail_24 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_24 BO Stop(0) Run(1)
ComfortCoolingOperStatus_24 BI Stop(0) Run(1)
ComfortCoolingStepCommand_24 AV 1~3 step
ComfortCoolingStepStatus_24 AI 1~3 step
HumanDetectionAvail_24 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_24 MO Off(1)
HumanDetectionOperStatus_24 MI Off(1)
HumanDetectionWindCommand_24 MO Off(1)
HumanDetectionWindStatus_24 MI Off(1)
HumanDetectionTimeCommand_24 MO 5min(1)
HumanDetectionTimeStatus_24 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
25 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_25 BO Stop(0) Start(1)
StartStopStatus_25 BI Stop(0) Start(1)
LockCommand_25 BO Permit(0) Prohibit(1)
LockStatus_25 BI Permit(0) Prohibit(1)
FilterSign_25 BI Off(0) On(1)
FilterSignReset_25 BV - Reset(1)
AirConModeCommand_25 MO Cool(1)
AirConModeStatus_25 MI Cool(1)
SwingCommand_25 BO Stop(0) Run(1)
SwingStatus_25 BI Stop(0) Run(1)
FanSpeedCommand_25 MO Low(1)
FanSpeedStatus_25 MI Low(1)
SetRoomTemp_25 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_25 AI ℃
Alarm_25 BI Normal(0) Abnormal(1)
MalfunctionCode_25 AI Refer to the
SetTempStatus_25 AI ℃
Accumulated power(100 Watt)_25 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_25 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_25 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_25 AI ℃
TempRangeLowerLimitStatus_25 AI ℃
ModeLockCommand_25 BO Permit(0) Prohibit(1)
ModeLockStatus_25 BI Permit(0) Prohibit(1)
FanLockCommand_25 BO Permit(0) Prohibit(1)
FanLockStatus_25 BI Permit(0) Prohibit(1)
OccupancyCommand_25 BO Unoccupied(0) Occupied(1)
OccupancyStatus_25 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_25 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_25 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_25 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_25 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_25 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_25 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_25 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_25 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_25 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_25 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_25 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_25 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_25 BI Off(0) On(1)
AccumulatedGas(100 Watt)_25 AI Wattage values (Unit : 100Watt)
DustSensorAvail_25 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_25 BO Stop(0) Run(1)
AirCleaningOperStatus_25 BI Stop(0) Run(1)
FineDustStatus_25 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_25 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_25 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_25 AI %
ComfortCoolingAvail_25 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_25 BO Stop(0) Run(1)
ComfortCoolingOperStatus_25 BI Stop(0) Run(1)
ComfortCoolingStepCommand_25 AV 1~3 step
ComfortCoolingStepStatus_25 AI 1~3 step
HumanDetectionAvail_25 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_25 MO Off(1)
HumanDetectionOperStatus_25 MI Off(1)
HumanDetectionWindCommand_25 MO Off(1)
HumanDetectionWindStatus_25 MI Off(1)
HumanDetectionTimeCommand_25 MO 5min(1)
HumanDetectionTimeStatus_25 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
26 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_26 BO Stop(0) Start(1)
StartStopStatus_26 BI Stop(0) Start(1)
LockCommand_26 BO Permit(0) Prohibit(1)
LockStatus_26 BI Permit(0) Prohibit(1)
FilterSign_26 BI Off(0) On(1)
FilterSignReset_26 BV - Reset(1)
AirConModeCommand_26 MO Cool(1)
AirConModeStatus_26 MI Cool(1)
SwingCommand_26 BO Stop(0) Run(1)
SwingStatus_26 BI Stop(0) Run(1)
FanSpeedCommand_26 MO Low(1)
FanSpeedStatus_26 MI Low(1)
SetRoomTemp_26 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_26 AI ℃
Alarm_26 BI Normal(0) Abnormal(1)
MalfunctionCode_26 AI Refer to the
SetTempStatus_26 AI ℃
Accumulated power(100 Watt)_26 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_26 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_26 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_26 AI ℃
TempRangeLowerLimitStatus_26 AI ℃
ModeLockCommand_26 BO Permit(0) Prohibit(1)
ModeLockStatus_26 BI Permit(0) Prohibit(1)
FanLockCommand_26 BO Permit(0) Prohibit(1)
FanLockStatus_26 BI Permit(0) Prohibit(1)
OccupancyCommand_26 BO Unoccupied(0) Occupied(1)
OccupancyStatus_26 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_26 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_26 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_26 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_26 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_26 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_26 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_26 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_26 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_26 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_26 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_26 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_26 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_26 BI Off(0) On(1)
AccumulatedGas(100 Watt)_26 AI Wattage values (Unit : 100Watt)
DustSensorAvail_26 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_26 BO Stop(0) Run(1)
AirCleaningOperStatus_26 BI Stop(0) Run(1)
FineDustStatus_26 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_26 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_26 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_26 AI %
ComfortCoolingAvail_26 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_26 BO Stop(0) Run(1)
ComfortCoolingOperStatus_26 BI Stop(0) Run(1)
ComfortCoolingStepCommand_26 AV 1~3 step
ComfortCoolingStepStatus_26 AI 1~3 step
HumanDetectionAvail_26 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_26 MO Off(1)
HumanDetectionOperStatus_26 MI Off(1)
HumanDetectionWindCommand_26 MO Off(1)
HumanDetectionWindStatus_26 MI Off(1)
HumanDetectionTimeCommand_26 MO 5min(1)
HumanDetectionTimeStatus_26 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
27 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_27 BO Stop(0) Start(1)
StartStopStatus_27 BI Stop(0) Start(1)
LockCommand_27 BO Permit(0) Prohibit(1)
LockStatus_27 BI Permit(0) Prohibit(1)
FilterSign_27 BI Off(0) On(1)
FilterSignReset_27 BV - Reset(1)
AirConModeCommand_27 MO Cool(1)
AirConModeStatus_27 MI Cool(1)
SwingCommand_27 BO Stop(0) Run(1)
SwingStatus_27 BI Stop(0) Run(1)
FanSpeedCommand_27 MO Low(1)
FanSpeedStatus_27 MI Low(1)
SetRoomTemp_27 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_27 AI ℃
Alarm_27 BI Normal(0) Abnormal(1)
MalfunctionCode_27 AI Refer to the
SetTempStatus_27 AI ℃
Accumulated power(100 Watt)_27 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_27 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_27 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_27 AI ℃
TempRangeLowerLimitStatus_27 AI ℃
ModeLockCommand_27 BO Permit(0) Prohibit(1)
ModeLockStatus_27 BI Permit(0) Prohibit(1)
FanLockCommand_27 BO Permit(0) Prohibit(1)
FanLockStatus_27 BI Permit(0) Prohibit(1)
OccupancyCommand_27 BO Unoccupied(0) Occupied(1)
OccupancyStatus_27 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_27 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_27 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_27 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_27 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_27 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_27 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_27 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_27 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_27 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_27 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_27 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_27 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_27 BI Off(0) On(1)
AccumulatedGas(100 Watt)_27 AI Wattage values (Unit : 100Watt)
DustSensorAvail_27 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_27 BO Stop(0) Run(1)
AirCleaningOperStatus_27 BI Stop(0) Run(1)
FineDustStatus_27 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_27 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_27 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_27 AI %
ComfortCoolingAvail_27 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_27 BO Stop(0) Run(1)
ComfortCoolingOperStatus_27 BI Stop(0) Run(1)
ComfortCoolingStepCommand_27 AV 1~3 step
ComfortCoolingStepStatus_27 AI 1~3 step
HumanDetectionAvail_27 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_27 MO Off(1)
HumanDetectionOperStatus_27 MI Off(1)
HumanDetectionWindCommand_27 MO Off(1)
HumanDetectionWindStatus_27 MI Off(1)
HumanDetectionTimeCommand_27 MO 5min(1)
HumanDetectionTimeStatus_27 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
28 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_28 BO Stop(0) Start(1)
StartStopStatus_28 BI Stop(0) Start(1)
LockCommand_28 BO Permit(0) Prohibit(1)
LockStatus_28 BI Permit(0) Prohibit(1)
FilterSign_28 BI Off(0) On(1)
FilterSignReset_28 BV - Reset(1)
AirConModeCommand_28 MO Cool(1)
AirConModeStatus_28 MI Cool(1)
SwingCommand_28 BO Stop(0) Run(1)
SwingStatus_28 BI Stop(0) Run(1)
FanSpeedCommand_28 MO Low(1)
FanSpeedStatus_28 MI Low(1)
SetRoomTemp_28 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_28 AI ℃
Alarm_28 BI Normal(0) Abnormal(1)
MalfunctionCode_28 AI Refer to the
SetTempStatus_28 AI ℃
Accumulated power(100 Watt)_28 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_28 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_28 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_28 AI ℃
TempRangeLowerLimitStatus_28 AI ℃
ModeLockCommand_28 BO Permit(0) Prohibit(1)
ModeLockStatus_28 BI Permit(0) Prohibit(1)
FanLockCommand_28 BO Permit(0) Prohibit(1)
FanLockStatus_28 BI Permit(0) Prohibit(1)
OccupancyCommand_28 BO Unoccupied(0) Occupied(1)
OccupancyStatus_28 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_28 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_28 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_28 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_28 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_28 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_28 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_28 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_28 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_28 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_28 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_28 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_28 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_28 BI Off(0) On(1)
AccumulatedGas(100 Watt)_28 AI Wattage values (Unit : 100Watt)
DustSensorAvail_28 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_28 BO Stop(0) Run(1)
AirCleaningOperStatus_28 BI Stop(0) Run(1)
FineDustStatus_28 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_28 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_28 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_28 AI %
ComfortCoolingAvail_28 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_28 BO Stop(0) Run(1)
ComfortCoolingOperStatus_28 BI Stop(0) Run(1)
ComfortCoolingStepCommand_28 AV 1~3 step
ComfortCoolingStepStatus_28 AI 1~3 step
HumanDetectionAvail_28 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_28 MO Off(1)
HumanDetectionOperStatus_28 MI Off(1)
HumanDetectionWindCommand_28 MO Off(1)
HumanDetectionWindStatus_28 MI Off(1)
HumanDetectionTimeCommand_28 MO 5min(1)
HumanDetectionTimeStatus_28 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
29 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_29 BO Stop(0) Start(1)
StartStopStatus_29 BI Stop(0) Start(1)
LockCommand_29 BO Permit(0) Prohibit(1)
LockStatus_29 BI Permit(0) Prohibit(1)
FilterSign_29 BI Off(0) On(1)
FilterSignReset_29 BV - Reset(1)
AirConModeCommand_29 MO Cool(1)
AirConModeStatus_29 MI Cool(1)
SwingCommand_29 BO Stop(0) Run(1)
SwingStatus_29 BI Stop(0) Run(1)
FanSpeedCommand_29 MO Low(1)
FanSpeedStatus_29 MI Low(1)
SetRoomTemp_29 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_29 AI ℃
Alarm_29 BI Normal(0) Abnormal(1)
MalfunctionCode_29 AI Refer to the
SetTempStatus_29 AI ℃
Accumulated power(100 Watt)_29 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_29 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_29 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_29 AI ℃
TempRangeLowerLimitStatus_29 AI ℃
ModeLockCommand_29 BO Permit(0) Prohibit(1)
ModeLockStatus_29 BI Permit(0) Prohibit(1)
FanLockCommand_29 BO Permit(0) Prohibit(1)
FanLockStatus_29 BI Permit(0) Prohibit(1)
OccupancyCommand_29 BO Unoccupied(0) Occupied(1)
OccupancyStatus_29 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_29 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_29 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_29 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_29 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_29 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_29 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_29 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_29 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_29 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_29 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_29 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_29 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_29 BI Off(0) On(1)
AccumulatedGas(100 Watt)_29 AI Wattage values (Unit : 100Watt)
DustSensorAvail_29 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_29 BO Stop(0) Run(1)
AirCleaningOperStatus_29 BI Stop(0) Run(1)
FineDustStatus_29 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_29 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_29 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_29 AI %
ComfortCoolingAvail_29 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_29 BO Stop(0) Run(1)
ComfortCoolingOperStatus_29 BI Stop(0) Run(1)
ComfortCoolingStepCommand_29 AV 1~3 step
ComfortCoolingStepStatus_29 AI 1~3 step
HumanDetectionAvail_29 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_29 MO Off(1)
HumanDetectionOperStatus_29 MI Off(1)
HumanDetectionWindCommand_29 MO Off(1)
HumanDetectionWindStatus_29 MI Off(1)
HumanDetectionTimeCommand_29 MO 5min(1)
HumanDetectionTimeStatus_29 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2a ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2a BO Stop(0) Start(1)
StartStopStatus_2a BI Stop(0) Start(1)
LockCommand_2a BO Permit(0) Prohibit(1)
LockStatus_2a BI Permit(0) Prohibit(1)
FilterSign_2a BI Off(0) On(1)
FilterSignReset_2a BV - Reset(1)
AirConModeCommand_2a MO Cool(1)
AirConModeStatus_2a MI Cool(1)
SwingCommand_2a BO Stop(0) Run(1)
SwingStatus_2a BI Stop(0) Run(1)
FanSpeedCommand_2a MO Low(1)
FanSpeedStatus_2a MI Low(1)
SetRoomTemp_2a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2a AI ℃
Alarm_2a BI Normal(0) Abnormal(1)
MalfunctionCode_2a AI Refer to the
SetTempStatus_2a AI ℃
Accumulated power(100 Watt)_2a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2a AI ℃
TempRangeLowerLimitStatus_2a AI ℃
ModeLockCommand_2a BO Permit(0) Prohibit(1)
ModeLockStatus_2a BI Permit(0) Prohibit(1)
FanLockCommand_2a BO Permit(0) Prohibit(1)
FanLockStatus_2a BI Permit(0) Prohibit(1)
OccupancyCommand_2a BO Unoccupied(0) Occupied(1)
OccupancyStatus_2a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2a BI Off(0) On(1)
AccumulatedGas(100 Watt)_2a AI Wattage values (Unit : 100Watt)
DustSensorAvail_2a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2a BO Stop(0) Run(1)
AirCleaningOperStatus_2a BI Stop(0) Run(1)
FineDustStatus_2a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2a AI %
ComfortCoolingAvail_2a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2a BO Stop(0) Run(1)
ComfortCoolingOperStatus_2a BI Stop(0) Run(1)
ComfortCoolingStepCommand_2a AV 1~3 step
ComfortCoolingStepStatus_2a AI 1~3 step
HumanDetectionAvail_2a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2a MO Off(1)
HumanDetectionOperStatus_2a MI Off(1)
HumanDetectionWindCommand_2a MO Off(1)
HumanDetectionWindStatus_2a MI Off(1)
HumanDetectionTimeCommand_2a MO 5min(1)
HumanDetectionTimeStatus_2a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2b ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2b BO Stop(0) Start(1)
StartStopStatus_2b BI Stop(0) Start(1)
LockCommand_2b BO Permit(0) Prohibit(1)
LockStatus_2b BI Permit(0) Prohibit(1)
FilterSign_2b BI Off(0) On(1)
FilterSignReset_2b BV - Reset(1)
AirConModeCommand_2b MO Cool(1)
AirConModeStatus_2b MI Cool(1)
SwingCommand_2b BO Stop(0) Run(1)
SwingStatus_2b BI Stop(0) Run(1)
FanSpeedCommand_2b MO Low(1)
FanSpeedStatus_2b MI Low(1)
SetRoomTemp_2b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2b AI ℃
Alarm_2b BI Normal(0) Abnormal(1)
MalfunctionCode_2b AI Refer to the
SetTempStatus_2b AI ℃
Accumulated power(100 Watt)_2b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2b AI ℃
TempRangeLowerLimitStatus_2b AI ℃
ModeLockCommand_2b BO Permit(0) Prohibit(1)
ModeLockStatus_2b BI Permit(0) Prohibit(1)
FanLockCommand_2b BO Permit(0) Prohibit(1)
FanLockStatus_2b BI Permit(0) Prohibit(1)
OccupancyCommand_2b BO Unoccupied(0) Occupied(1)
OccupancyStatus_2b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2b BI Off(0) On(1)
AccumulatedGas(100 Watt)_2b AI Wattage values (Unit : 100Watt)
DustSensorAvail_2b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2b BO Stop(0) Run(1)
AirCleaningOperStatus_2b BI Stop(0) Run(1)
FineDustStatus_2b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2b AI %
ComfortCoolingAvail_2b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2b BO Stop(0) Run(1)
ComfortCoolingOperStatus_2b BI Stop(0) Run(1)
ComfortCoolingStepCommand_2b AV 1~3 step
ComfortCoolingStepStatus_2b AI 1~3 step
HumanDetectionAvail_2b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2b MO Off(1)
HumanDetectionOperStatus_2b MI Off(1)
HumanDetectionWindCommand_2b MO Off(1)
HumanDetectionWindStatus_2b MI Off(1)
HumanDetectionTimeCommand_2b MO 5min(1)
HumanDetectionTimeStatus_2b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2c ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2c BO Stop(0) Start(1)
StartStopStatus_2c BI Stop(0) Start(1)
LockCommand_2c BO Permit(0) Prohibit(1)
LockStatus_2c BI Permit(0) Prohibit(1)
FilterSign_2c BI Off(0) On(1)
FilterSignReset_2c BV - Reset(1)
AirConModeCommand_2c MO Cool(1)
AirConModeStatus_2c MI Cool(1)
SwingCommand_2c BO Stop(0) Run(1)
SwingStatus_2c BI Stop(0) Run(1)
FanSpeedCommand_2c MO Low(1)
FanSpeedStatus_2c MI Low(1)
SetRoomTemp_2c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2c AI ℃
Alarm_2c BI Normal(0) Abnormal(1)
MalfunctionCode_2c AI Refer to the
SetTempStatus_2c AI ℃
Accumulated power(100 Watt)_2c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2c AI ℃
TempRangeLowerLimitStatus_2c AI ℃
ModeLockCommand_2c BO Permit(0) Prohibit(1)
ModeLockStatus_2c BI Permit(0) Prohibit(1)
FanLockCommand_2c BO Permit(0) Prohibit(1)
FanLockStatus_2c BI Permit(0) Prohibit(1)
OccupancyCommand_2c BO Unoccupied(0) Occupied(1)
OccupancyStatus_2c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2c BI Off(0) On(1)
AccumulatedGas(100 Watt)_2c AI Wattage values (Unit : 100Watt)
DustSensorAvail_2c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2c BO Stop(0) Run(1)
AirCleaningOperStatus_2c BI Stop(0) Run(1)
FineDustStatus_2c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2c AI %
ComfortCoolingAvail_2c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2c BO Stop(0) Run(1)
ComfortCoolingOperStatus_2c BI Stop(0) Run(1)
ComfortCoolingStepCommand_2c AV 1~3 step
ComfortCoolingStepStatus_2c AI 1~3 step
HumanDetectionAvail_2c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2c MO Off(1)
HumanDetectionOperStatus_2c MI Off(1)
HumanDetectionWindCommand_2c MO Off(1)
HumanDetectionWindStatus_2c MI Off(1)
HumanDetectionTimeCommand_2c MO 5min(1)
HumanDetectionTimeStatus_2c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2d ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2d BO Stop(0) Start(1)
StartStopStatus_2d BI Stop(0) Start(1)
LockCommand_2d BO Permit(0) Prohibit(1)
LockStatus_2d BI Permit(0) Prohibit(1)
FilterSign_2d BI Off(0) On(1)
FilterSignReset_2d BV - Reset(1)
AirConModeCommand_2d MO Cool(1)
AirConModeStatus_2d MI Cool(1)
SwingCommand_2d BO Stop(0) Run(1)
SwingStatus_2d BI Stop(0) Run(1)
FanSpeedCommand_2d MO Low(1)
FanSpeedStatus_2d MI Low(1)
SetRoomTemp_2d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2d AI ℃
Alarm_2d BI Normal(0) Abnormal(1)
MalfunctionCode_2d AI Refer to the
SetTempStatus_2d AI ℃
Accumulated power(100 Watt)_2d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2d AI ℃
TempRangeLowerLimitStatus_2d AI ℃
ModeLockCommand_2d BO Permit(0) Prohibit(1)
ModeLockStatus_2d BI Permit(0) Prohibit(1)
FanLockCommand_2d BO Permit(0) Prohibit(1)
FanLockStatus_2d BI Permit(0) Prohibit(1)
OccupancyCommand_2d BO Unoccupied(0) Occupied(1)
OccupancyStatus_2d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2d BI Off(0) On(1)
AccumulatedGas(100 Watt)_2d AI Wattage values (Unit : 100Watt)
DustSensorAvail_2d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2d BO Stop(0) Run(1)
AirCleaningOperStatus_2d BI Stop(0) Run(1)
FineDustStatus_2d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2d AI %
ComfortCoolingAvail_2d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2d BO Stop(0) Run(1)
ComfortCoolingOperStatus_2d BI Stop(0) Run(1)
ComfortCoolingStepCommand_2d AV 1~3 step
ComfortCoolingStepStatus_2d AI 1~3 step
HumanDetectionAvail_2d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2d MO Off(1)
HumanDetectionOperStatus_2d MI Off(1)
HumanDetectionWindCommand_2d MO Off(1)
HumanDetectionWindStatus_2d MI Off(1)
HumanDetectionTimeCommand_2d MO 5min(1)
HumanDetectionTimeStatus_2d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2e ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2e BO Stop(0) Start(1)
StartStopStatus_2e BI Stop(0) Start(1)
LockCommand_2e BO Permit(0) Prohibit(1)
LockStatus_2e BI Permit(0) Prohibit(1)
FilterSign_2e BI Off(0) On(1)
FilterSignReset_2e BV - Reset(1)
AirConModeCommand_2e MO Cool(1)
AirConModeStatus_2e MI Cool(1)
SwingCommand_2e BO Stop(0) Run(1)
SwingStatus_2e BI Stop(0) Run(1)
FanSpeedCommand_2e MO Low(1)
FanSpeedStatus_2e MI Low(1)
SetRoomTemp_2e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2e AI ℃
Alarm_2e BI Normal(0) Abnormal(1)
MalfunctionCode_2e AI Refer to the
SetTempStatus_2e AI ℃
Accumulated power(100 Watt)_2e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2e AI ℃
TempRangeLowerLimitStatus_2e AI ℃
ModeLockCommand_2e BO Permit(0) Prohibit(1)
ModeLockStatus_2e BI Permit(0) Prohibit(1)
FanLockCommand_2e BO Permit(0) Prohibit(1)
FanLockStatus_2e BI Permit(0) Prohibit(1)
OccupancyCommand_2e BO Unoccupied(0) Occupied(1)
OccupancyStatus_2e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2e BI Off(0) On(1)
AccumulatedGas(100 Watt)_2e AI Wattage values (Unit : 100Watt)
DustSensorAvail_2e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2e BO Stop(0) Run(1)
AirCleaningOperStatus_2e BI Stop(0) Run(1)
FineDustStatus_2e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2e AI %
ComfortCoolingAvail_2e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2e BO Stop(0) Run(1)
ComfortCoolingOperStatus_2e BI Stop(0) Run(1)
ComfortCoolingStepCommand_2e AV 1~3 step
ComfortCoolingStepStatus_2e AI 1~3 step
HumanDetectionAvail_2e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2e MO Off(1)
HumanDetectionOperStatus_2e MI Off(1)
HumanDetectionWindCommand_2e MO Off(1)
HumanDetectionWindStatus_2e MI Off(1)
HumanDetectionTimeCommand_2e MO 5min(1)
HumanDetectionTimeStatus_2e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
2f ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_2f BO Stop(0) Start(1)
StartStopStatus_2f BI Stop(0) Start(1)
LockCommand_2f BO Permit(0) Prohibit(1)
LockStatus_2f BI Permit(0) Prohibit(1)
FilterSign_2f BI Off(0) On(1)
FilterSignReset_2f BV - Reset(1)
AirConModeCommand_2f MO Cool(1)
AirConModeStatus_2f MI Cool(1)
SwingCommand_2f BO Stop(0) Run(1)
SwingStatus_2f BI Stop(0) Run(1)
FanSpeedCommand_2f MO Low(1)
FanSpeedStatus_2f MI Low(1)
SetRoomTemp_2f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_2f AI ℃
Alarm_2f BI Normal(0) Abnormal(1)
MalfunctionCode_2f AI Refer to the
SetTempStatus_2f AI ℃
Accumulated power(100 Watt)_2f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_2f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_2f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_2f AI ℃
TempRangeLowerLimitStatus_2f AI ℃
ModeLockCommand_2f BO Permit(0) Prohibit(1)
ModeLockStatus_2f BI Permit(0) Prohibit(1)
FanLockCommand_2f BO Permit(0) Prohibit(1)
FanLockStatus_2f BI Permit(0) Prohibit(1)
OccupancyCommand_2f BO Unoccupied(0) Occupied(1)
OccupancyStatus_2f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_2f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_2f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_2f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_2f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_2f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_2f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_2f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_2f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_2f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_2f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_2f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_2f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_2f BI Off(0) On(1)
AccumulatedGas(100 Watt)_2f AI Wattage values (Unit : 100Watt)
DustSensorAvail_2f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_2f BO Stop(0) Run(1)
AirCleaningOperStatus_2f BI Stop(0) Run(1)
FineDustStatus_2f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_2f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_2f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_2f AI %
ComfortCoolingAvail_2f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_2f BO Stop(0) Run(1)
ComfortCoolingOperStatus_2f BI Stop(0) Run(1)
ComfortCoolingStepCommand_2f AV 1~3 step
ComfortCoolingStepStatus_2f AI 1~3 step
HumanDetectionAvail_2f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_2f MO Off(1)
HumanDetectionOperStatus_2f MI Off(1)
HumanDetectionWindCommand_2f MO Off(1)
HumanDetectionWindStatus_2f MI Off(1)
HumanDetectionTimeCommand_2f MO 5min(1)
HumanDetectionTimeStatus_2f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
30 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_30 BO Stop(0) Start(1)
StartStopStatus_30 BI Stop(0) Start(1)
LockCommand_30 BO Permit(0) Prohibit(1)
LockStatus_30 BI Permit(0) Prohibit(1)
FilterSign_30 BI Off(0) On(1)
FilterSignReset_30 BV - Reset(1)
AirConModeCommand_30 MO Cool(1)
AirConModeStatus_30 MI Cool(1)
SwingCommand_30 BO Stop(0) Run(1)
SwingStatus_30 BI Stop(0) Run(1)
FanSpeedCommand_30 MO Low(1)
FanSpeedStatus_30 MI Low(1)
SetRoomTemp_30 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_30 AI ℃
Alarm_30 BI Normal(0) Abnormal(1)
MalfunctionCode_30 AI Refer to the
SetTempStatus_30 AI ℃
Accumulated power(100 Watt)_30 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_30 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_30 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_30 AI ℃
TempRangeLowerLimitStatus_30 AI ℃
ModeLockCommand_30 BO Permit(0) Prohibit(1)
ModeLockStatus_30 BI Permit(0) Prohibit(1)
FanLockCommand_30 BO Permit(0) Prohibit(1)
FanLockStatus_30 BI Permit(0) Prohibit(1)
OccupancyCommand_30 BO Unoccupied(0) Occupied(1)
OccupancyStatus_30 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_30 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_30 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_30 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_30 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_30 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_30 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_30 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_30 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_30 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_30 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_30 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_30 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_30 BI Off(0) On(1)
AccumulatedGas(100 Watt)_30 AI Wattage values (Unit : 100Watt)
DustSensorAvail_30 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_30 BO Stop(0) Run(1)
AirCleaningOperStatus_30 BI Stop(0) Run(1)
FineDustStatus_30 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_30 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_30 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_30 AI %
ComfortCoolingAvail_30 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_30 BO Stop(0) Run(1)
ComfortCoolingOperStatus_30 BI Stop(0) Run(1)
ComfortCoolingStepCommand_30 AV 1~3 step
ComfortCoolingStepStatus_30 AI 1~3 step
HumanDetectionAvail_30 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_30 MO Off(1)
HumanDetectionOperStatus_30 MI Off(1)
HumanDetectionWindCommand_30 MO Off(1)
HumanDetectionWindStatus_30 MI Off(1)
HumanDetectionTimeCommand_30 MO 5min(1)
HumanDetectionTimeStatus_30 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
31 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_31 BO Stop(0) Start(1)
StartStopStatus_31 BI Stop(0) Start(1)
LockCommand_31 BO Permit(0) Prohibit(1)
LockStatus_31 BI Permit(0) Prohibit(1)
FilterSign_31 BI Off(0) On(1)
FilterSignReset_31 BV - Reset(1)
AirConModeCommand_31 MO Cool(1)
AirConModeStatus_31 MI Cool(1)
SwingCommand_31 BO Stop(0) Run(1)
SwingStatus_31 BI Stop(0) Run(1)
FanSpeedCommand_31 MO Low(1)
FanSpeedStatus_31 MI Low(1)
SetRoomTemp_31 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_31 AI ℃
Alarm_31 BI Normal(0) Abnormal(1)
MalfunctionCode_31 AI Refer to the
SetTempStatus_31 AI ℃
Accumulated power(100 Watt)_31 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_31 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_31 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_31 AI ℃
TempRangeLowerLimitStatus_31 AI ℃
ModeLockCommand_31 BO Permit(0) Prohibit(1)
ModeLockStatus_31 BI Permit(0) Prohibit(1)
FanLockCommand_31 BO Permit(0) Prohibit(1)
FanLockStatus_31 BI Permit(0) Prohibit(1)
OccupancyCommand_31 BO Unoccupied(0) Occupied(1)
OccupancyStatus_31 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_31 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_31 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_31 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_31 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_31 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_31 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_31 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_31 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_31 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_31 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_31 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_31 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_31 BI Off(0) On(1)
AccumulatedGas(100 Watt)_31 AI Wattage values (Unit : 100Watt)
DustSensorAvail_31 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_31 BO Stop(0) Run(1)
AirCleaningOperStatus_31 BI Stop(0) Run(1)
FineDustStatus_31 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_31 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_31 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_31 AI %
ComfortCoolingAvail_31 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_31 BO Stop(0) Run(1)
ComfortCoolingOperStatus_31 BI Stop(0) Run(1)
ComfortCoolingStepCommand_31 AV 1~3 step
ComfortCoolingStepStatus_31 AI 1~3 step
HumanDetectionAvail_31 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_31 MO Off(1)
HumanDetectionOperStatus_31 MI Off(1)
HumanDetectionWindCommand_31 MO Off(1)
HumanDetectionWindStatus_31 MI Off(1)
HumanDetectionTimeCommand_31 MO 5min(1)
HumanDetectionTimeStatus_31 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
32 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_32 BO Stop(0) Start(1)
StartStopStatus_32 BI Stop(0) Start(1)
LockCommand_32 BO Permit(0) Prohibit(1)
LockStatus_32 BI Permit(0) Prohibit(1)
FilterSign_32 BI Off(0) On(1)
FilterSignReset_32 BV - Reset(1)
AirConModeCommand_32 MO Cool(1)
AirConModeStatus_32 MI Cool(1)
SwingCommand_32 BO Stop(0) Run(1)
SwingStatus_32 BI Stop(0) Run(1)
FanSpeedCommand_32 MO Low(1)
FanSpeedStatus_32 MI Low(1)
SetRoomTemp_32 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_32 AI ℃
Alarm_32 BI Normal(0) Abnormal(1)
MalfunctionCode_32 AI Refer to the
SetTempStatus_32 AI ℃
Accumulated power(100 Watt)_32 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_32 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_32 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_32 AI ℃
TempRangeLowerLimitStatus_32 AI ℃
ModeLockCommand_32 BO Permit(0) Prohibit(1)
ModeLockStatus_32 BI Permit(0) Prohibit(1)
FanLockCommand_32 BO Permit(0) Prohibit(1)
FanLockStatus_32 BI Permit(0) Prohibit(1)
OccupancyCommand_32 BO Unoccupied(0) Occupied(1)
OccupancyStatus_32 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_32 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_32 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_32 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_32 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_32 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_32 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_32 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_32 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_32 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_32 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_32 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_32 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_32 BI Off(0) On(1)
AccumulatedGas(100 Watt)_32 AI Wattage values (Unit : 100Watt)
DustSensorAvail_32 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_32 BO Stop(0) Run(1)
AirCleaningOperStatus_32 BI Stop(0) Run(1)
FineDustStatus_32 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_32 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_32 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_32 AI %
ComfortCoolingAvail_32 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_32 BO Stop(0) Run(1)
ComfortCoolingOperStatus_32 BI Stop(0) Run(1)
ComfortCoolingStepCommand_32 AV 1~3 step
ComfortCoolingStepStatus_32 AI 1~3 step
HumanDetectionAvail_32 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_32 MO Off(1)
HumanDetectionOperStatus_32 MI Off(1)
HumanDetectionWindCommand_32 MO Off(1)
HumanDetectionWindStatus_32 MI Off(1)
HumanDetectionTimeCommand_32 MO 5min(1)
HumanDetectionTimeStatus_32 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
33 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_33 BO Stop(0) Start(1)
StartStopStatus_33 BI Stop(0) Start(1)
LockCommand_33 BO Permit(0) Prohibit(1)
LockStatus_33 BI Permit(0) Prohibit(1)
FilterSign_33 BI Off(0) On(1)
FilterSignReset_33 BV - Reset(1)
AirConModeCommand_33 MO Cool(1)
AirConModeStatus_33 MI Cool(1)
SwingCommand_33 BO Stop(0) Run(1)
SwingStatus_33 BI Stop(0) Run(1)
FanSpeedCommand_33 MO Low(1)
FanSpeedStatus_33 MI Low(1)
SetRoomTemp_33 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_33 AI ℃
Alarm_33 BI Normal(0) Abnormal(1)
MalfunctionCode_33 AI Refer to the
SetTempStatus_33 AI ℃
Accumulated power(100 Watt)_33 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_33 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_33 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_33 AI ℃
TempRangeLowerLimitStatus_33 AI ℃
ModeLockCommand_33 BO Permit(0) Prohibit(1)
ModeLockStatus_33 BI Permit(0) Prohibit(1)
FanLockCommand_33 BO Permit(0) Prohibit(1)
FanLockStatus_33 BI Permit(0) Prohibit(1)
OccupancyCommand_33 BO Unoccupied(0) Occupied(1)
OccupancyStatus_33 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_33 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_33 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_33 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_33 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_33 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_33 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_33 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_33 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_33 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_33 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_33 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_33 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_33 BI Off(0) On(1)
AccumulatedGas(100 Watt)_33 AI Wattage values (Unit : 100Watt)
DustSensorAvail_33 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_33 BO Stop(0) Run(1)
AirCleaningOperStatus_33 BI Stop(0) Run(1)
FineDustStatus_33 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_33 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_33 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_33 AI %
ComfortCoolingAvail_33 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_33 BO Stop(0) Run(1)
ComfortCoolingOperStatus_33 BI Stop(0) Run(1)
ComfortCoolingStepCommand_33 AV 1~3 step
ComfortCoolingStepStatus_33 AI 1~3 step
HumanDetectionAvail_33 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_33 MO Off(1)
HumanDetectionOperStatus_33 MI Off(1)
HumanDetectionWindCommand_33 MO Off(1)
HumanDetectionWindStatus_33 MI Off(1)
HumanDetectionTimeCommand_33 MO 5min(1)
HumanDetectionTimeStatus_33 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
34 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_34 BO Stop(0) Start(1)
StartStopStatus_34 BI Stop(0) Start(1)
LockCommand_34 BO Permit(0) Prohibit(1)
LockStatus_34 BI Permit(0) Prohibit(1)
FilterSign_34 BI Off(0) On(1)
FilterSignReset_34 BV - Reset(1)
AirConModeCommand_34 MO Cool(1)
AirConModeStatus_34 MI Cool(1)
SwingCommand_34 BO Stop(0) Run(1)
SwingStatus_34 BI Stop(0) Run(1)
FanSpeedCommand_34 MO Low(1)
FanSpeedStatus_34 MI Low(1)
SetRoomTemp_34 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_34 AI ℃
Alarm_34 BI Normal(0) Abnormal(1)
MalfunctionCode_34 AI Refer to the
SetTempStatus_34 AI ℃
Accumulated power(100 Watt)_34 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_34 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_34 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_34 AI ℃
TempRangeLowerLimitStatus_34 AI ℃
ModeLockCommand_34 BO Permit(0) Prohibit(1)
ModeLockStatus_34 BI Permit(0) Prohibit(1)
FanLockCommand_34 BO Permit(0) Prohibit(1)
FanLockStatus_34 BI Permit(0) Prohibit(1)
OccupancyCommand_34 BO Unoccupied(0) Occupied(1)
OccupancyStatus_34 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_34 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_34 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_34 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_34 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_34 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_34 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_34 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_34 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_34 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_34 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_34 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_34 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_34 BI Off(0) On(1)
AccumulatedGas(100 Watt)_34 AI Wattage values (Unit : 100Watt)
DustSensorAvail_34 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_34 BO Stop(0) Run(1)
AirCleaningOperStatus_34 BI Stop(0) Run(1)
FineDustStatus_34 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_34 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_34 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_34 AI %
ComfortCoolingAvail_34 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_34 BO Stop(0) Run(1)
ComfortCoolingOperStatus_34 BI Stop(0) Run(1)
ComfortCoolingStepCommand_34 AV 1~3 step
ComfortCoolingStepStatus_34 AI 1~3 step
HumanDetectionAvail_34 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_34 MO Off(1)
HumanDetectionOperStatus_34 MI Off(1)
HumanDetectionWindCommand_34 MO Off(1)
HumanDetectionWindStatus_34 MI Off(1)
HumanDetectionTimeCommand_34 MO 5min(1)
HumanDetectionTimeStatus_34 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
35 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_35 BO Stop(0) Start(1)
StartStopStatus_35 BI Stop(0) Start(1)
LockCommand_35 BO Permit(0) Prohibit(1)
LockStatus_35 BI Permit(0) Prohibit(1)
FilterSign_35 BI Off(0) On(1)
FilterSignReset_35 BV - Reset(1)
AirConModeCommand_35 MO Cool(1)
AirConModeStatus_35 MI Cool(1)
SwingCommand_35 BO Stop(0) Run(1)
SwingStatus_35 BI Stop(0) Run(1)
FanSpeedCommand_35 MO Low(1)
FanSpeedStatus_35 MI Low(1)
SetRoomTemp_35 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_35 AI ℃
Alarm_35 BI Normal(0) Abnormal(1)
MalfunctionCode_35 AI Refer to the
SetTempStatus_35 AI ℃
Accumulated power(100 Watt)_35 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_35 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_35 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_35 AI ℃
TempRangeLowerLimitStatus_35 AI ℃
ModeLockCommand_35 BO Permit(0) Prohibit(1)
ModeLockStatus_35 BI Permit(0) Prohibit(1)
FanLockCommand_35 BO Permit(0) Prohibit(1)
FanLockStatus_35 BI Permit(0) Prohibit(1)
OccupancyCommand_35 BO Unoccupied(0) Occupied(1)
OccupancyStatus_35 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_35 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_35 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_35 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_35 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_35 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_35 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_35 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_35 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_35 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_35 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_35 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_35 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_35 BI Off(0) On(1)
AccumulatedGas(100 Watt)_35 AI Wattage values (Unit : 100Watt)
DustSensorAvail_35 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_35 BO Stop(0) Run(1)
AirCleaningOperStatus_35 BI Stop(0) Run(1)
FineDustStatus_35 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_35 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_35 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_35 AI %
ComfortCoolingAvail_35 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_35 BO Stop(0) Run(1)
ComfortCoolingOperStatus_35 BI Stop(0) Run(1)
ComfortCoolingStepCommand_35 AV 1~3 step
ComfortCoolingStepStatus_35 AI 1~3 step
HumanDetectionAvail_35 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_35 MO Off(1)
HumanDetectionOperStatus_35 MI Off(1)
HumanDetectionWindCommand_35 MO Off(1)
HumanDetectionWindStatus_35 MI Off(1)
HumanDetectionTimeCommand_35 MO 5min(1)
HumanDetectionTimeStatus_35 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
36 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_36 BO Stop(0) Start(1)
StartStopStatus_36 BI Stop(0) Start(1)
LockCommand_36 BO Permit(0) Prohibit(1)
LockStatus_36 BI Permit(0) Prohibit(1)
FilterSign_36 BI Off(0) On(1)
FilterSignReset_36 BV - Reset(1)
AirConModeCommand_36 MO Cool(1)
AirConModeStatus_36 MI Cool(1)
SwingCommand_36 BO Stop(0) Run(1)
SwingStatus_36 BI Stop(0) Run(1)
FanSpeedCommand_36 MO Low(1)
FanSpeedStatus_36 MI Low(1)
SetRoomTemp_36 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_36 AI ℃
Alarm_36 BI Normal(0) Abnormal(1)
MalfunctionCode_36 AI Refer to the
SetTempStatus_36 AI ℃
Accumulated power(100 Watt)_36 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_36 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_36 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_36 AI ℃
TempRangeLowerLimitStatus_36 AI ℃
ModeLockCommand_36 BO Permit(0) Prohibit(1)
ModeLockStatus_36 BI Permit(0) Prohibit(1)
FanLockCommand_36 BO Permit(0) Prohibit(1)
FanLockStatus_36 BI Permit(0) Prohibit(1)
OccupancyCommand_36 BO Unoccupied(0) Occupied(1)
OccupancyStatus_36 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_36 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_36 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_36 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_36 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_36 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_36 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_36 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_36 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_36 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_36 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_36 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_36 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_36 BI Off(0) On(1)
AccumulatedGas(100 Watt)_36 AI Wattage values (Unit : 100Watt)
DustSensorAvail_36 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_36 BO Stop(0) Run(1)
AirCleaningOperStatus_36 BI Stop(0) Run(1)
FineDustStatus_36 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_36 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_36 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_36 AI %
ComfortCoolingAvail_36 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_36 BO Stop(0) Run(1)
ComfortCoolingOperStatus_36 BI Stop(0) Run(1)
ComfortCoolingStepCommand_36 AV 1~3 step
ComfortCoolingStepStatus_36 AI 1~3 step
HumanDetectionAvail_36 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_36 MO Off(1)
HumanDetectionOperStatus_36 MI Off(1)
HumanDetectionWindCommand_36 MO Off(1)
HumanDetectionWindStatus_36 MI Off(1)
HumanDetectionTimeCommand_36 MO 5min(1)
HumanDetectionTimeStatus_36 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
37 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_37 BO Stop(0) Start(1)
StartStopStatus_37 BI Stop(0) Start(1)
LockCommand_37 BO Permit(0) Prohibit(1)
LockStatus_37 BI Permit(0) Prohibit(1)
FilterSign_37 BI Off(0) On(1)
FilterSignReset_37 BV - Reset(1)
AirConModeCommand_37 MO Cool(1)
AirConModeStatus_37 MI Cool(1)
SwingCommand_37 BO Stop(0) Run(1)
SwingStatus_37 BI Stop(0) Run(1)
FanSpeedCommand_37 MO Low(1)
FanSpeedStatus_37 MI Low(1)
SetRoomTemp_37 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_37 AI ℃
Alarm_37 BI Normal(0) Abnormal(1)
MalfunctionCode_37 AI Refer to the
SetTempStatus_37 AI ℃
Accumulated power(100 Watt)_37 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_37 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_37 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_37 AI ℃
TempRangeLowerLimitStatus_37 AI ℃
ModeLockCommand_37 BO Permit(0) Prohibit(1)
ModeLockStatus_37 BI Permit(0) Prohibit(1)
FanLockCommand_37 BO Permit(0) Prohibit(1)
FanLockStatus_37 BI Permit(0) Prohibit(1)
OccupancyCommand_37 BO Unoccupied(0) Occupied(1)
OccupancyStatus_37 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_37 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_37 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_37 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_37 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_37 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_37 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_37 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_37 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_37 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_37 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_37 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_37 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_37 BI Off(0) On(1)
AccumulatedGas(100 Watt)_37 AI Wattage values (Unit : 100Watt)
DustSensorAvail_37 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_37 BO Stop(0) Run(1)
AirCleaningOperStatus_37 BI Stop(0) Run(1)
FineDustStatus_37 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_37 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_37 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_37 AI %
ComfortCoolingAvail_37 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_37 BO Stop(0) Run(1)
ComfortCoolingOperStatus_37 BI Stop(0) Run(1)
ComfortCoolingStepCommand_37 AV 1~3 step
ComfortCoolingStepStatus_37 AI 1~3 step
HumanDetectionAvail_37 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_37 MO Off(1)
HumanDetectionOperStatus_37 MI Off(1)
HumanDetectionWindCommand_37 MO Off(1)
HumanDetectionWindStatus_37 MI Off(1)
HumanDetectionTimeCommand_37 MO 5min(1)
HumanDetectionTimeStatus_37 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
38 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_38 BO Stop(0) Start(1)
StartStopStatus_38 BI Stop(0) Start(1)
LockCommand_38 BO Permit(0) Prohibit(1)
LockStatus_38 BI Permit(0) Prohibit(1)
FilterSign_38 BI Off(0) On(1)
FilterSignReset_38 BV - Reset(1)
AirConModeCommand_38 MO Cool(1)
AirConModeStatus_38 MI Cool(1)
SwingCommand_38 BO Stop(0) Run(1)
SwingStatus_38 BI Stop(0) Run(1)
FanSpeedCommand_38 MO Low(1)
FanSpeedStatus_38 MI Low(1)
SetRoomTemp_38 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_38 AI ℃
Alarm_38 BI Normal(0) Abnormal(1)
MalfunctionCode_38 AI Refer to the
SetTempStatus_38 AI ℃
Accumulated power(100 Watt)_38 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_38 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_38 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_38 AI ℃
TempRangeLowerLimitStatus_38 AI ℃
ModeLockCommand_38 BO Permit(0) Prohibit(1)
ModeLockStatus_38 BI Permit(0) Prohibit(1)
FanLockCommand_38 BO Permit(0) Prohibit(1)
FanLockStatus_38 BI Permit(0) Prohibit(1)
OccupancyCommand_38 BO Unoccupied(0) Occupied(1)
OccupancyStatus_38 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_38 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_38 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_38 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_38 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_38 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_38 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_38 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_38 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_38 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_38 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_38 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_38 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_38 BI Off(0) On(1)
AccumulatedGas(100 Watt)_38 AI Wattage values (Unit : 100Watt)
DustSensorAvail_38 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_38 BO Stop(0) Run(1)
AirCleaningOperStatus_38 BI Stop(0) Run(1)
FineDustStatus_38 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_38 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_38 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_38 AI %
ComfortCoolingAvail_38 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_38 BO Stop(0) Run(1)
ComfortCoolingOperStatus_38 BI Stop(0) Run(1)
ComfortCoolingStepCommand_38 AV 1~3 step
ComfortCoolingStepStatus_38 AI 1~3 step
HumanDetectionAvail_38 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_38 MO Off(1)
HumanDetectionOperStatus_38 MI Off(1)
HumanDetectionWindCommand_38 MO Off(1)
HumanDetectionWindStatus_38 MI Off(1)
HumanDetectionTimeCommand_38 MO 5min(1)
HumanDetectionTimeStatus_38 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
39 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_39 BO Stop(0) Start(1)
StartStopStatus_39 BI Stop(0) Start(1)
LockCommand_39 BO Permit(0) Prohibit(1)
LockStatus_39 BI Permit(0) Prohibit(1)
FilterSign_39 BI Off(0) On(1)
FilterSignReset_39 BV - Reset(1)
AirConModeCommand_39 MO Cool(1)
AirConModeStatus_39 MI Cool(1)
SwingCommand_39 BO Stop(0) Run(1)
SwingStatus_39 BI Stop(0) Run(1)
FanSpeedCommand_39 MO Low(1)
FanSpeedStatus_39 MI Low(1)
SetRoomTemp_39 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_39 AI ℃
Alarm_39 BI Normal(0) Abnormal(1)
MalfunctionCode_39 AI Refer to the
SetTempStatus_39 AI ℃
Accumulated power(100 Watt)_39 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_39 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_39 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_39 AI ℃
TempRangeLowerLimitStatus_39 AI ℃
ModeLockCommand_39 BO Permit(0) Prohibit(1)
ModeLockStatus_39 BI Permit(0) Prohibit(1)
FanLockCommand_39 BO Permit(0) Prohibit(1)
FanLockStatus_39 BI Permit(0) Prohibit(1)
OccupancyCommand_39 BO Unoccupied(0) Occupied(1)
OccupancyStatus_39 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_39 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_39 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_39 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_39 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_39 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_39 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_39 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_39 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_39 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_39 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_39 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_39 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_39 BI Off(0) On(1)
AccumulatedGas(100 Watt)_39 AI Wattage values (Unit : 100Watt)
DustSensorAvail_39 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_39 BO Stop(0) Run(1)
AirCleaningOperStatus_39 BI Stop(0) Run(1)
FineDustStatus_39 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_39 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_39 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_39 AI %
ComfortCoolingAvail_39 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_39 BO Stop(0) Run(1)
ComfortCoolingOperStatus_39 BI Stop(0) Run(1)
ComfortCoolingStepCommand_39 AV 1~3 step
ComfortCoolingStepStatus_39 AI 1~3 step
HumanDetectionAvail_39 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_39 MO Off(1)
HumanDetectionOperStatus_39 MI Off(1)
HumanDetectionWindCommand_39 MO Off(1)
HumanDetectionWindStatus_39 MI Off(1)
HumanDetectionTimeCommand_39 MO 5min(1)
HumanDetectionTimeStatus_39 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3a ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3a BO Stop(0) Start(1)
StartStopStatus_3a BI Stop(0) Start(1)
LockCommand_3a BO Permit(0) Prohibit(1)
LockStatus_3a BI Permit(0) Prohibit(1)
FilterSign_3a BI Off(0) On(1)
FilterSignReset_3a BV - Reset(1)
AirConModeCommand_3a MO Cool(1)
AirConModeStatus_3a MI Cool(1)
SwingCommand_3a BO Stop(0) Run(1)
SwingStatus_3a BI Stop(0) Run(1)
FanSpeedCommand_3a MO Low(1)
FanSpeedStatus_3a MI Low(1)
SetRoomTemp_3a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3a AI ℃
Alarm_3a BI Normal(0) Abnormal(1)
MalfunctionCode_3a AI Refer to the
SetTempStatus_3a AI ℃
Accumulated power(100 Watt)_3a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3a AI ℃
TempRangeLowerLimitStatus_3a AI ℃
ModeLockCommand_3a BO Permit(0) Prohibit(1)
ModeLockStatus_3a BI Permit(0) Prohibit(1)
FanLockCommand_3a BO Permit(0) Prohibit(1)
FanLockStatus_3a BI Permit(0) Prohibit(1)
OccupancyCommand_3a BO Unoccupied(0) Occupied(1)
OccupancyStatus_3a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3a BI Off(0) On(1)
AccumulatedGas(100 Watt)_3a AI Wattage values (Unit : 100Watt)
DustSensorAvail_3a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3a BO Stop(0) Run(1)
AirCleaningOperStatus_3a BI Stop(0) Run(1)
FineDustStatus_3a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3a AI %
ComfortCoolingAvail_3a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3a BO Stop(0) Run(1)
ComfortCoolingOperStatus_3a BI Stop(0) Run(1)
ComfortCoolingStepCommand_3a AV 1~3 step
ComfortCoolingStepStatus_3a AI 1~3 step
HumanDetectionAvail_3a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3a MO Off(1)
HumanDetectionOperStatus_3a MI Off(1)
HumanDetectionWindCommand_3a MO Off(1)
HumanDetectionWindStatus_3a MI Off(1)
HumanDetectionTimeCommand_3a MO 5min(1)
HumanDetectionTimeStatus_3a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3b ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3b BO Stop(0) Start(1)
StartStopStatus_3b BI Stop(0) Start(1)
LockCommand_3b BO Permit(0) Prohibit(1)
LockStatus_3b BI Permit(0) Prohibit(1)
FilterSign_3b BI Off(0) On(1)
FilterSignReset_3b BV - Reset(1)
AirConModeCommand_3b MO Cool(1)
AirConModeStatus_3b MI Cool(1)
SwingCommand_3b BO Stop(0) Run(1)
SwingStatus_3b BI Stop(0) Run(1)
FanSpeedCommand_3b MO Low(1)
FanSpeedStatus_3b MI Low(1)
SetRoomTemp_3b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3b AI ℃
Alarm_3b BI Normal(0) Abnormal(1)
MalfunctionCode_3b AI Refer to the
SetTempStatus_3b AI ℃
Accumulated power(100 Watt)_3b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3b AI ℃
TempRangeLowerLimitStatus_3b AI ℃
ModeLockCommand_3b BO Permit(0) Prohibit(1)
ModeLockStatus_3b BI Permit(0) Prohibit(1)
FanLockCommand_3b BO Permit(0) Prohibit(1)
FanLockStatus_3b BI Permit(0) Prohibit(1)
OccupancyCommand_3b BO Unoccupied(0) Occupied(1)
OccupancyStatus_3b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3b BI Off(0) On(1)
AccumulatedGas(100 Watt)_3b AI Wattage values (Unit : 100Watt)
DustSensorAvail_3b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3b BO Stop(0) Run(1)
AirCleaningOperStatus_3b BI Stop(0) Run(1)
FineDustStatus_3b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3b AI %
ComfortCoolingAvail_3b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3b BO Stop(0) Run(1)
ComfortCoolingOperStatus_3b BI Stop(0) Run(1)
ComfortCoolingStepCommand_3b AV 1~3 step
ComfortCoolingStepStatus_3b AI 1~3 step
HumanDetectionAvail_3b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3b MO Off(1)
HumanDetectionOperStatus_3b MI Off(1)
HumanDetectionWindCommand_3b MO Off(1)
HumanDetectionWindStatus_3b MI Off(1)
HumanDetectionTimeCommand_3b MO 5min(1)
HumanDetectionTimeStatus_3b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3c ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3c BO Stop(0) Start(1)
StartStopStatus_3c BI Stop(0) Start(1)
LockCommand_3c BO Permit(0) Prohibit(1)
LockStatus_3c BI Permit(0) Prohibit(1)
FilterSign_3c BI Off(0) On(1)
FilterSignReset_3c BV - Reset(1)
AirConModeCommand_3c MO Cool(1)
AirConModeStatus_3c MI Cool(1)
SwingCommand_3c BO Stop(0) Run(1)
SwingStatus_3c BI Stop(0) Run(1)
FanSpeedCommand_3c MO Low(1)
FanSpeedStatus_3c MI Low(1)
SetRoomTemp_3c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3c AI ℃
Alarm_3c BI Normal(0) Abnormal(1)
MalfunctionCode_3c AI Refer to the
SetTempStatus_3c AI ℃
Accumulated power(100 Watt)_3c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3c AI ℃
TempRangeLowerLimitStatus_3c AI ℃
ModeLockCommand_3c BO Permit(0) Prohibit(1)
ModeLockStatus_3c BI Permit(0) Prohibit(1)
FanLockCommand_3c BO Permit(0) Prohibit(1)
FanLockStatus_3c BI Permit(0) Prohibit(1)
OccupancyCommand_3c BO Unoccupied(0) Occupied(1)
OccupancyStatus_3c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3c BI Off(0) On(1)
AccumulatedGas(100 Watt)_3c AI Wattage values (Unit : 100Watt)
DustSensorAvail_3c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3c BO Stop(0) Run(1)
AirCleaningOperStatus_3c BI Stop(0) Run(1)
FineDustStatus_3c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3c AI %
ComfortCoolingAvail_3c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3c BO Stop(0) Run(1)
ComfortCoolingOperStatus_3c BI Stop(0) Run(1)
ComfortCoolingStepCommand_3c AV 1~3 step
ComfortCoolingStepStatus_3c AI 1~3 step
HumanDetectionAvail_3c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3c MO Off(1)
HumanDetectionOperStatus_3c MI Off(1)
HumanDetectionWindCommand_3c MO Off(1)
HumanDetectionWindStatus_3c MI Off(1)
HumanDetectionTimeCommand_3c MO 5min(1)
HumanDetectionTimeStatus_3c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3d ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3d BO Stop(0) Start(1)
StartStopStatus_3d BI Stop(0) Start(1)
LockCommand_3d BO Permit(0) Prohibit(1)
LockStatus_3d BI Permit(0) Prohibit(1)
FilterSign_3d BI Off(0) On(1)
FilterSignReset_3d BV - Reset(1)
AirConModeCommand_3d MO Cool(1)
AirConModeStatus_3d MI Cool(1)
SwingCommand_3d BO Stop(0) Run(1)
SwingStatus_3d BI Stop(0) Run(1)
FanSpeedCommand_3d MO Low(1)
FanSpeedStatus_3d MI Low(1)
SetRoomTemp_3d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3d AI ℃
Alarm_3d BI Normal(0) Abnormal(1)
MalfunctionCode_3d AI Refer to the
SetTempStatus_3d AI ℃
Accumulated power(100 Watt)_3d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3d AI ℃
TempRangeLowerLimitStatus_3d AI ℃
ModeLockCommand_3d BO Permit(0) Prohibit(1)
ModeLockStatus_3d BI Permit(0) Prohibit(1)
FanLockCommand_3d BO Permit(0) Prohibit(1)
FanLockStatus_3d BI Permit(0) Prohibit(1)
OccupancyCommand_3d BO Unoccupied(0) Occupied(1)
OccupancyStatus_3d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3d BI Off(0) On(1)
AccumulatedGas(100 Watt)_3d AI Wattage values (Unit : 100Watt)
DustSensorAvail_3d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3d BO Stop(0) Run(1)
AirCleaningOperStatus_3d BI Stop(0) Run(1)
FineDustStatus_3d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3d AI %
ComfortCoolingAvail_3d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3d BO Stop(0) Run(1)
ComfortCoolingOperStatus_3d BI Stop(0) Run(1)
ComfortCoolingStepCommand_3d AV 1~3 step
ComfortCoolingStepStatus_3d AI 1~3 step
HumanDetectionAvail_3d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3d MO Off(1)
HumanDetectionOperStatus_3d MI Off(1)
HumanDetectionWindCommand_3d MO Off(1)
HumanDetectionWindStatus_3d MI Off(1)
HumanDetectionTimeCommand_3d MO 5min(1)
HumanDetectionTimeStatus_3d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3e ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3e BO Stop(0) Start(1)
StartStopStatus_3e BI Stop(0) Start(1)
LockCommand_3e BO Permit(0) Prohibit(1)
LockStatus_3e BI Permit(0) Prohibit(1)
FilterSign_3e BI Off(0) On(1)
FilterSignReset_3e BV - Reset(1)
AirConModeCommand_3e MO Cool(1)
AirConModeStatus_3e MI Cool(1)
SwingCommand_3e BO Stop(0) Run(1)
SwingStatus_3e BI Stop(0) Run(1)
FanSpeedCommand_3e MO Low(1)
FanSpeedStatus_3e MI Low(1)
SetRoomTemp_3e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3e AI ℃
Alarm_3e BI Normal(0) Abnormal(1)
MalfunctionCode_3e AI Refer to the
SetTempStatus_3e AI ℃
Accumulated power(100 Watt)_3e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3e AI ℃
TempRangeLowerLimitStatus_3e AI ℃
ModeLockCommand_3e BO Permit(0) Prohibit(1)
ModeLockStatus_3e BI Permit(0) Prohibit(1)
FanLockCommand_3e BO Permit(0) Prohibit(1)
FanLockStatus_3e BI Permit(0) Prohibit(1)
OccupancyCommand_3e BO Unoccupied(0) Occupied(1)
OccupancyStatus_3e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3e BI Off(0) On(1)
AccumulatedGas(100 Watt)_3e AI Wattage values (Unit : 100Watt)
DustSensorAvail_3e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3e BO Stop(0) Run(1)
AirCleaningOperStatus_3e BI Stop(0) Run(1)
FineDustStatus_3e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3e AI %
ComfortCoolingAvail_3e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3e BO Stop(0) Run(1)
ComfortCoolingOperStatus_3e BI Stop(0) Run(1)
ComfortCoolingStepCommand_3e AV 1~3 step
ComfortCoolingStepStatus_3e AI 1~3 step
HumanDetectionAvail_3e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3e MO Off(1)
HumanDetectionOperStatus_3e MI Off(1)
HumanDetectionWindCommand_3e MO Off(1)
HumanDetectionWindStatus_3e MI Off(1)
HumanDetectionTimeCommand_3e MO 5min(1)
HumanDetectionTimeStatus_3e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
3f ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_3f BO Stop(0) Start(1)
StartStopStatus_3f BI Stop(0) Start(1)
LockCommand_3f BO Permit(0) Prohibit(1)
LockStatus_3f BI Permit(0) Prohibit(1)
FilterSign_3f BI Off(0) On(1)
FilterSignReset_3f BV - Reset(1)
AirConModeCommand_3f MO Cool(1)
AirConModeStatus_3f MI Cool(1)
SwingCommand_3f BO Stop(0) Run(1)
SwingStatus_3f BI Stop(0) Run(1)
FanSpeedCommand_3f MO Low(1)
FanSpeedStatus_3f MI Low(1)
SetRoomTemp_3f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_3f AI ℃
Alarm_3f BI Normal(0) Abnormal(1)
MalfunctionCode_3f AI Refer to the
SetTempStatus_3f AI ℃
Accumulated power(100 Watt)_3f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_3f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_3f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_3f AI ℃
TempRangeLowerLimitStatus_3f AI ℃
ModeLockCommand_3f BO Permit(0) Prohibit(1)
ModeLockStatus_3f BI Permit(0) Prohibit(1)
FanLockCommand_3f BO Permit(0) Prohibit(1)
FanLockStatus_3f BI Permit(0) Prohibit(1)
OccupancyCommand_3f BO Unoccupied(0) Occupied(1)
OccupancyStatus_3f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_3f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_3f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_3f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_3f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_3f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_3f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_3f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_3f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_3f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_3f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_3f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_3f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_3f BI Off(0) On(1)
AccumulatedGas(100 Watt)_3f AI Wattage values (Unit : 100Watt)
DustSensorAvail_3f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_3f BO Stop(0) Run(1)
AirCleaningOperStatus_3f BI Stop(0) Run(1)
FineDustStatus_3f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_3f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_3f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_3f AI %
ComfortCoolingAvail_3f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_3f BO Stop(0) Run(1)
ComfortCoolingOperStatus_3f BI Stop(0) Run(1)
ComfortCoolingStepCommand_3f AV 1~3 step
ComfortCoolingStepStatus_3f AI 1~3 step
HumanDetectionAvail_3f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_3f MO Off(1)
HumanDetectionOperStatus_3f MI Off(1)
HumanDetectionWindCommand_3f MO Off(1)
HumanDetectionWindStatus_3f MI Off(1)
HumanDetectionTimeCommand_3f MO 5min(1)
HumanDetectionTimeStatus_3f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
40 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_40 BO Stop(0) Start(1)
StartStopStatus_40 BI Stop(0) Start(1)
LockCommand_40 BO Permit(0) Prohibit(1)
LockStatus_40 BI Permit(0) Prohibit(1)
FilterSign_40 BI Off(0) On(1)
FilterSignReset_40 BV - Reset(1)
AirConModeCommand_40 MO Cool(1)
AirConModeStatus_40 MI Cool(1)
SwingCommand_40 BO Stop(0) Run(1)
SwingStatus_40 BI Stop(0) Run(1)
FanSpeedCommand_40 MO Low(1)
FanSpeedStatus_40 MI Low(1)
SetRoomTemp_40 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_40 AI ℃
Alarm_40 BI Normal(0) Abnormal(1)
MalfunctionCode_40 AI Refer to the
SetTempStatus_40 AI ℃
Accumulated power(100 Watt)_40 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_40 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_40 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_40 AI ℃
TempRangeLowerLimitStatus_40 AI ℃
ModeLockCommand_40 BO Permit(0) Prohibit(1)
ModeLockStatus_40 BI Permit(0) Prohibit(1)
FanLockCommand_40 BO Permit(0) Prohibit(1)
FanLockStatus_40 BI Permit(0) Prohibit(1)
OccupancyCommand_40 BO Unoccupied(0) Occupied(1)
OccupancyStatus_40 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_40 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_40 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_40 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_40 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_40 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_40 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_40 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_40 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_40 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_40 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_40 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_40 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_40 BI Off(0) On(1)
AccumulatedGas(100 Watt)_40 AI Wattage values (Unit : 100Watt)
DustSensorAvail_40 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_40 BO Stop(0) Run(1)
AirCleaningOperStatus_40 BI Stop(0) Run(1)
FineDustStatus_40 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_40 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_40 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_40 AI %
ComfortCoolingAvail_40 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_40 BO Stop(0) Run(1)
ComfortCoolingOperStatus_40 BI Stop(0) Run(1)
ComfortCoolingStepCommand_40 AV 1~3 step
ComfortCoolingStepStatus_40 AI 1~3 step
HumanDetectionAvail_40 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_40 MO Off(1)
HumanDetectionOperStatus_40 MI Off(1)
HumanDetectionWindCommand_40 MO Off(1)
HumanDetectionWindStatus_40 MI Off(1)
HumanDetectionTimeCommand_40 MO 5min(1)
HumanDetectionTimeStatus_40 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
41 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_41 BO Stop(0) Start(1)
StartStopStatus_41 BI Stop(0) Start(1)
LockCommand_41 BO Permit(0) Prohibit(1)
LockStatus_41 BI Permit(0) Prohibit(1)
FilterSign_41 BI Off(0) On(1)
FilterSignReset_41 BV - Reset(1)
AirConModeCommand_41 MO Cool(1)
AirConModeStatus_41 MI Cool(1)
SwingCommand_41 BO Stop(0) Run(1)
SwingStatus_41 BI Stop(0) Run(1)
FanSpeedCommand_41 MO Low(1)
FanSpeedStatus_41 MI Low(1)
SetRoomTemp_41 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_41 AI ℃
Alarm_41 BI Normal(0) Abnormal(1)
MalfunctionCode_41 AI Refer to the
SetTempStatus_41 AI ℃
Accumulated power(100 Watt)_41 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_41 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_41 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_41 AI ℃
TempRangeLowerLimitStatus_41 AI ℃
ModeLockCommand_41 BO Permit(0) Prohibit(1)
ModeLockStatus_41 BI Permit(0) Prohibit(1)
FanLockCommand_41 BO Permit(0) Prohibit(1)
FanLockStatus_41 BI Permit(0) Prohibit(1)
OccupancyCommand_41 BO Unoccupied(0) Occupied(1)
OccupancyStatus_41 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_41 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_41 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_41 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_41 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_41 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_41 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_41 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_41 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_41 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_41 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_41 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_41 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_41 BI Off(0) On(1)
AccumulatedGas(100 Watt)_41 AI Wattage values (Unit : 100Watt)
DustSensorAvail_41 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_41 BO Stop(0) Run(1)
AirCleaningOperStatus_41 BI Stop(0) Run(1)
FineDustStatus_41 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_41 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_41 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_41 AI %
ComfortCoolingAvail_41 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_41 BO Stop(0) Run(1)
ComfortCoolingOperStatus_41 BI Stop(0) Run(1)
ComfortCoolingStepCommand_41 AV 1~3 step
ComfortCoolingStepStatus_41 AI 1~3 step
HumanDetectionAvail_41 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_41 MO Off(1)
HumanDetectionOperStatus_41 MI Off(1)
HumanDetectionWindCommand_41 MO Off(1)
HumanDetectionWindStatus_41 MI Off(1)
HumanDetectionTimeCommand_41 MO 5min(1)
HumanDetectionTimeStatus_41 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
42 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_42 BO Stop(0) Start(1)
StartStopStatus_42 BI Stop(0) Start(1)
LockCommand_42 BO Permit(0) Prohibit(1)
LockStatus_42 BI Permit(0) Prohibit(1)
FilterSign_42 BI Off(0) On(1)
FilterSignReset_42 BV - Reset(1)
AirConModeCommand_42 MO Cool(1)
AirConModeStatus_42 MI Cool(1)
SwingCommand_42 BO Stop(0) Run(1)
SwingStatus_42 BI Stop(0) Run(1)
FanSpeedCommand_42 MO Low(1)
FanSpeedStatus_42 MI Low(1)
SetRoomTemp_42 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_42 AI ℃
Alarm_42 BI Normal(0) Abnormal(1)
MalfunctionCode_42 AI Refer to the
SetTempStatus_42 AI ℃
Accumulated power(100 Watt)_42 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_42 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_42 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_42 AI ℃
TempRangeLowerLimitStatus_42 AI ℃
ModeLockCommand_42 BO Permit(0) Prohibit(1)
ModeLockStatus_42 BI Permit(0) Prohibit(1)
FanLockCommand_42 BO Permit(0) Prohibit(1)
FanLockStatus_42 BI Permit(0) Prohibit(1)
OccupancyCommand_42 BO Unoccupied(0) Occupied(1)
OccupancyStatus_42 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_42 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_42 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_42 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_42 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_42 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_42 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_42 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_42 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_42 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_42 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_42 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_42 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_42 BI Off(0) On(1)
AccumulatedGas(100 Watt)_42 AI Wattage values (Unit : 100Watt)
DustSensorAvail_42 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_42 BO Stop(0) Run(1)
AirCleaningOperStatus_42 BI Stop(0) Run(1)
FineDustStatus_42 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_42 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_42 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_42 AI %
ComfortCoolingAvail_42 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_42 BO Stop(0) Run(1)
ComfortCoolingOperStatus_42 BI Stop(0) Run(1)
ComfortCoolingStepCommand_42 AV 1~3 step
ComfortCoolingStepStatus_42 AI 1~3 step
HumanDetectionAvail_42 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_42 MO Off(1)
HumanDetectionOperStatus_42 MI Off(1)
HumanDetectionWindCommand_42 MO Off(1)
HumanDetectionWindStatus_42 MI Off(1)
HumanDetectionTimeCommand_42 MO 5min(1)
HumanDetectionTimeStatus_42 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
43 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_43 BO Stop(0) Start(1)
StartStopStatus_43 BI Stop(0) Start(1)
LockCommand_43 BO Permit(0) Prohibit(1)
LockStatus_43 BI Permit(0) Prohibit(1)
FilterSign_43 BI Off(0) On(1)
FilterSignReset_43 BV - Reset(1)
AirConModeCommand_43 MO Cool(1)
AirConModeStatus_43 MI Cool(1)
SwingCommand_43 BO Stop(0) Run(1)
SwingStatus_43 BI Stop(0) Run(1)
FanSpeedCommand_43 MO Low(1)
FanSpeedStatus_43 MI Low(1)
SetRoomTemp_43 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_43 AI ℃
Alarm_43 BI Normal(0) Abnormal(1)
MalfunctionCode_43 AI Refer to the
SetTempStatus_43 AI ℃
Accumulated power(100 Watt)_43 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_43 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_43 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_43 AI ℃
TempRangeLowerLimitStatus_43 AI ℃
ModeLockCommand_43 BO Permit(0) Prohibit(1)
ModeLockStatus_43 BI Permit(0) Prohibit(1)
FanLockCommand_43 BO Permit(0) Prohibit(1)
FanLockStatus_43 BI Permit(0) Prohibit(1)
OccupancyCommand_43 BO Unoccupied(0) Occupied(1)
OccupancyStatus_43 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_43 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_43 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_43 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_43 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_43 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_43 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_43 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_43 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_43 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_43 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_43 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_43 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_43 BI Off(0) On(1)
AccumulatedGas(100 Watt)_43 AI Wattage values (Unit : 100Watt)
DustSensorAvail_43 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_43 BO Stop(0) Run(1)
AirCleaningOperStatus_43 BI Stop(0) Run(1)
FineDustStatus_43 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_43 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_43 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_43 AI %
ComfortCoolingAvail_43 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_43 BO Stop(0) Run(1)
ComfortCoolingOperStatus_43 BI Stop(0) Run(1)
ComfortCoolingStepCommand_43 AV 1~3 step
ComfortCoolingStepStatus_43 AI 1~3 step
HumanDetectionAvail_43 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_43 MO Off(1)
HumanDetectionOperStatus_43 MI Off(1)
HumanDetectionWindCommand_43 MO Off(1)
HumanDetectionWindStatus_43 MI Off(1)
HumanDetectionTimeCommand_43 MO 5min(1)
HumanDetectionTimeStatus_43 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
44 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_44 BO Stop(0) Start(1)
StartStopStatus_44 BI Stop(0) Start(1)
LockCommand_44 BO Permit(0) Prohibit(1)
LockStatus_44 BI Permit(0) Prohibit(1)
FilterSign_44 BI Off(0) On(1)
FilterSignReset_44 BV - Reset(1)
AirConModeCommand_44 MO Cool(1)
AirConModeStatus_44 MI Cool(1)
SwingCommand_44 BO Stop(0) Run(1)
SwingStatus_44 BI Stop(0) Run(1)
FanSpeedCommand_44 MO Low(1)
FanSpeedStatus_44 MI Low(1)
SetRoomTemp_44 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_44 AI ℃
Alarm_44 BI Normal(0) Abnormal(1)
MalfunctionCode_44 AI Refer to the
SetTempStatus_44 AI ℃
Accumulated power(100 Watt)_44 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_44 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_44 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_44 AI ℃
TempRangeLowerLimitStatus_44 AI ℃
ModeLockCommand_44 BO Permit(0) Prohibit(1)
ModeLockStatus_44 BI Permit(0) Prohibit(1)
FanLockCommand_44 BO Permit(0) Prohibit(1)
FanLockStatus_44 BI Permit(0) Prohibit(1)
OccupancyCommand_44 BO Unoccupied(0) Occupied(1)
OccupancyStatus_44 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_44 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_44 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_44 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_44 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_44 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_44 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_44 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_44 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_44 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_44 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_44 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_44 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_44 BI Off(0) On(1)
AccumulatedGas(100 Watt)_44 AI Wattage values (Unit : 100Watt)
DustSensorAvail_44 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_44 BO Stop(0) Run(1)
AirCleaningOperStatus_44 BI Stop(0) Run(1)
FineDustStatus_44 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_44 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_44 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_44 AI %
ComfortCoolingAvail_44 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_44 BO Stop(0) Run(1)
ComfortCoolingOperStatus_44 BI Stop(0) Run(1)
ComfortCoolingStepCommand_44 AV 1~3 step
ComfortCoolingStepStatus_44 AI 1~3 step
HumanDetectionAvail_44 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_44 MO Off(1)
HumanDetectionOperStatus_44 MI Off(1)
HumanDetectionWindCommand_44 MO Off(1)
HumanDetectionWindStatus_44 MI Off(1)
HumanDetectionTimeCommand_44 MO 5min(1)
HumanDetectionTimeStatus_44 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
45 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_45 BO Stop(0) Start(1)
StartStopStatus_45 BI Stop(0) Start(1)
LockCommand_45 BO Permit(0) Prohibit(1)
LockStatus_45 BI Permit(0) Prohibit(1)
FilterSign_45 BI Off(0) On(1)
FilterSignReset_45 BV - Reset(1)
AirConModeCommand_45 MO Cool(1)
AirConModeStatus_45 MI Cool(1)
SwingCommand_45 BO Stop(0) Run(1)
SwingStatus_45 BI Stop(0) Run(1)
FanSpeedCommand_45 MO Low(1)
FanSpeedStatus_45 MI Low(1)
SetRoomTemp_45 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_45 AI ℃
Alarm_45 BI Normal(0) Abnormal(1)
MalfunctionCode_45 AI Refer to the
SetTempStatus_45 AI ℃
Accumulated power(100 Watt)_45 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_45 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_45 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_45 AI ℃
TempRangeLowerLimitStatus_45 AI ℃
ModeLockCommand_45 BO Permit(0) Prohibit(1)
ModeLockStatus_45 BI Permit(0) Prohibit(1)
FanLockCommand_45 BO Permit(0) Prohibit(1)
FanLockStatus_45 BI Permit(0) Prohibit(1)
OccupancyCommand_45 BO Unoccupied(0) Occupied(1)
OccupancyStatus_45 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_45 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_45 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_45 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_45 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_45 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_45 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_45 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_45 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_45 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_45 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_45 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_45 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_45 BI Off(0) On(1)
AccumulatedGas(100 Watt)_45 AI Wattage values (Unit : 100Watt)
DustSensorAvail_45 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_45 BO Stop(0) Run(1)
AirCleaningOperStatus_45 BI Stop(0) Run(1)
FineDustStatus_45 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_45 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_45 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_45 AI %
ComfortCoolingAvail_45 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_45 BO Stop(0) Run(1)
ComfortCoolingOperStatus_45 BI Stop(0) Run(1)
ComfortCoolingStepCommand_45 AV 1~3 step
ComfortCoolingStepStatus_45 AI 1~3 step
HumanDetectionAvail_45 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_45 MO Off(1)
HumanDetectionOperStatus_45 MI Off(1)
HumanDetectionWindCommand_45 MO Off(1)
HumanDetectionWindStatus_45 MI Off(1)
HumanDetectionTimeCommand_45 MO 5min(1)
HumanDetectionTimeStatus_45 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
46 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_46 BO Stop(0) Start(1)
StartStopStatus_46 BI Stop(0) Start(1)
LockCommand_46 BO Permit(0) Prohibit(1)
LockStatus_46 BI Permit(0) Prohibit(1)
FilterSign_46 BI Off(0) On(1)
FilterSignReset_46 BV - Reset(1)
AirConModeCommand_46 MO Cool(1)
AirConModeStatus_46 MI Cool(1)
SwingCommand_46 BO Stop(0) Run(1)
SwingStatus_46 BI Stop(0) Run(1)
FanSpeedCommand_46 MO Low(1)
FanSpeedStatus_46 MI Low(1)
SetRoomTemp_46 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_46 AI ℃
Alarm_46 BI Normal(0) Abnormal(1)
MalfunctionCode_46 AI Refer to the
SetTempStatus_46 AI ℃
Accumulated power(100 Watt)_46 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_46 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_46 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_46 AI ℃
TempRangeLowerLimitStatus_46 AI ℃
ModeLockCommand_46 BO Permit(0) Prohibit(1)
ModeLockStatus_46 BI Permit(0) Prohibit(1)
FanLockCommand_46 BO Permit(0) Prohibit(1)
FanLockStatus_46 BI Permit(0) Prohibit(1)
OccupancyCommand_46 BO Unoccupied(0) Occupied(1)
OccupancyStatus_46 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_46 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_46 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_46 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_46 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_46 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_46 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_46 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_46 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_46 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_46 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_46 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_46 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_46 BI Off(0) On(1)
AccumulatedGas(100 Watt)_46 AI Wattage values (Unit : 100Watt)
DustSensorAvail_46 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_46 BO Stop(0) Run(1)
AirCleaningOperStatus_46 BI Stop(0) Run(1)
FineDustStatus_46 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_46 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_46 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_46 AI %
ComfortCoolingAvail_46 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_46 BO Stop(0) Run(1)
ComfortCoolingOperStatus_46 BI Stop(0) Run(1)
ComfortCoolingStepCommand_46 AV 1~3 step
ComfortCoolingStepStatus_46 AI 1~3 step
HumanDetectionAvail_46 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_46 MO Off(1)
HumanDetectionOperStatus_46 MI Off(1)
HumanDetectionWindCommand_46 MO Off(1)
HumanDetectionWindStatus_46 MI Off(1)
HumanDetectionTimeCommand_46 MO 5min(1)
HumanDetectionTimeStatus_46 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
47 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_47 BO Stop(0) Start(1)
StartStopStatus_47 BI Stop(0) Start(1)
LockCommand_47 BO Permit(0) Prohibit(1)
LockStatus_47 BI Permit(0) Prohibit(1)
FilterSign_47 BI Off(0) On(1)
FilterSignReset_47 BV - Reset(1)
AirConModeCommand_47 MO Cool(1)
AirConModeStatus_47 MI Cool(1)
SwingCommand_47 BO Stop(0) Run(1)
SwingStatus_47 BI Stop(0) Run(1)
FanSpeedCommand_47 MO Low(1)
FanSpeedStatus_47 MI Low(1)
SetRoomTemp_47 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_47 AI ℃
Alarm_47 BI Normal(0) Abnormal(1)
MalfunctionCode_47 AI Refer to the
SetTempStatus_47 AI ℃
Accumulated power(100 Watt)_47 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_47 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_47 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_47 AI ℃
TempRangeLowerLimitStatus_47 AI ℃
ModeLockCommand_47 BO Permit(0) Prohibit(1)
ModeLockStatus_47 BI Permit(0) Prohibit(1)
FanLockCommand_47 BO Permit(0) Prohibit(1)
FanLockStatus_47 BI Permit(0) Prohibit(1)
OccupancyCommand_47 BO Unoccupied(0) Occupied(1)
OccupancyStatus_47 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_47 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_47 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_47 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_47 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_47 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_47 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_47 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_47 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_47 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_47 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_47 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_47 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_47 BI Off(0) On(1)
AccumulatedGas(100 Watt)_47 AI Wattage values (Unit : 100Watt)
DustSensorAvail_47 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_47 BO Stop(0) Run(1)
AirCleaningOperStatus_47 BI Stop(0) Run(1)
FineDustStatus_47 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_47 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_47 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_47 AI %
ComfortCoolingAvail_47 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_47 BO Stop(0) Run(1)
ComfortCoolingOperStatus_47 BI Stop(0) Run(1)
ComfortCoolingStepCommand_47 AV 1~3 step
ComfortCoolingStepStatus_47 AI 1~3 step
HumanDetectionAvail_47 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_47 MO Off(1)
HumanDetectionOperStatus_47 MI Off(1)
HumanDetectionWindCommand_47 MO Off(1)
HumanDetectionWindStatus_47 MI Off(1)
HumanDetectionTimeCommand_47 MO 5min(1)
HumanDetectionTimeStatus_47 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
48 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_48 BO Stop(0) Start(1)
StartStopStatus_48 BI Stop(0) Start(1)
LockCommand_48 BO Permit(0) Prohibit(1)
LockStatus_48 BI Permit(0) Prohibit(1)
FilterSign_48 BI Off(0) On(1)
FilterSignReset_48 BV - Reset(1)
AirConModeCommand_48 MO Cool(1)
AirConModeStatus_48 MI Cool(1)
SwingCommand_48 BO Stop(0) Run(1)
SwingStatus_48 BI Stop(0) Run(1)
FanSpeedCommand_48 MO Low(1)
FanSpeedStatus_48 MI Low(1)
SetRoomTemp_48 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_48 AI ℃
Alarm_48 BI Normal(0) Abnormal(1)
MalfunctionCode_48 AI Refer to the
SetTempStatus_48 AI ℃
Accumulated power(100 Watt)_48 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_48 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_48 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_48 AI ℃
TempRangeLowerLimitStatus_48 AI ℃
ModeLockCommand_48 BO Permit(0) Prohibit(1)
ModeLockStatus_48 BI Permit(0) Prohibit(1)
FanLockCommand_48 BO Permit(0) Prohibit(1)
FanLockStatus_48 BI Permit(0) Prohibit(1)
OccupancyCommand_48 BO Unoccupied(0) Occupied(1)
OccupancyStatus_48 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_48 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_48 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_48 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_48 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_48 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_48 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_48 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_48 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_48 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_48 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_48 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_48 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_48 BI Off(0) On(1)
AccumulatedGas(100 Watt)_48 AI Wattage values (Unit : 100Watt)
DustSensorAvail_48 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_48 BO Stop(0) Run(1)
AirCleaningOperStatus_48 BI Stop(0) Run(1)
FineDustStatus_48 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_48 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_48 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_48 AI %
ComfortCoolingAvail_48 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_48 BO Stop(0) Run(1)
ComfortCoolingOperStatus_48 BI Stop(0) Run(1)
ComfortCoolingStepCommand_48 AV 1~3 step
ComfortCoolingStepStatus_48 AI 1~3 step
HumanDetectionAvail_48 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_48 MO Off(1)
HumanDetectionOperStatus_48 MI Off(1)
HumanDetectionWindCommand_48 MO Off(1)
HumanDetectionWindStatus_48 MI Off(1)
HumanDetectionTimeCommand_48 MO 5min(1)
HumanDetectionTimeStatus_48 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
49 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_49 BO Stop(0) Start(1)
StartStopStatus_49 BI Stop(0) Start(1)
LockCommand_49 BO Permit(0) Prohibit(1)
LockStatus_49 BI Permit(0) Prohibit(1)
FilterSign_49 BI Off(0) On(1)
FilterSignReset_49 BV - Reset(1)
AirConModeCommand_49 MO Cool(1)
AirConModeStatus_49 MI Cool(1)
SwingCommand_49 BO Stop(0) Run(1)
SwingStatus_49 BI Stop(0) Run(1)
FanSpeedCommand_49 MO Low(1)
FanSpeedStatus_49 MI Low(1)
SetRoomTemp_49 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_49 AI ℃
Alarm_49 BI Normal(0) Abnormal(1)
MalfunctionCode_49 AI Refer to the
SetTempStatus_49 AI ℃
Accumulated power(100 Watt)_49 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_49 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_49 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_49 AI ℃
TempRangeLowerLimitStatus_49 AI ℃
ModeLockCommand_49 BO Permit(0) Prohibit(1)
ModeLockStatus_49 BI Permit(0) Prohibit(1)
FanLockCommand_49 BO Permit(0) Prohibit(1)
FanLockStatus_49 BI Permit(0) Prohibit(1)
OccupancyCommand_49 BO Unoccupied(0) Occupied(1)
OccupancyStatus_49 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_49 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_49 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_49 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_49 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_49 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_49 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_49 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_49 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_49 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_49 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_49 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_49 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_49 BI Off(0) On(1)
AccumulatedGas(100 Watt)_49 AI Wattage values (Unit : 100Watt)
DustSensorAvail_49 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_49 BO Stop(0) Run(1)
AirCleaningOperStatus_49 BI Stop(0) Run(1)
FineDustStatus_49 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_49 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_49 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_49 AI %
ComfortCoolingAvail_49 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_49 BO Stop(0) Run(1)
ComfortCoolingOperStatus_49 BI Stop(0) Run(1)
ComfortCoolingStepCommand_49 AV 1~3 step
ComfortCoolingStepStatus_49 AI 1~3 step
HumanDetectionAvail_49 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_49 MO Off(1)
HumanDetectionOperStatus_49 MI Off(1)
HumanDetectionWindCommand_49 MO Off(1)
HumanDetectionWindStatus_49 MI Off(1)
HumanDetectionTimeCommand_49 MO 5min(1)
HumanDetectionTimeStatus_49 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4a ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4a BO Stop(0) Start(1)
StartStopStatus_4a BI Stop(0) Start(1)
LockCommand_4a BO Permit(0) Prohibit(1)
LockStatus_4a BI Permit(0) Prohibit(1)
FilterSign_4a BI Off(0) On(1)
FilterSignReset_4a BV - Reset(1)
AirConModeCommand_4a MO Cool(1)
AirConModeStatus_4a MI Cool(1)
SwingCommand_4a BO Stop(0) Run(1)
SwingStatus_4a BI Stop(0) Run(1)
FanSpeedCommand_4a MO Low(1)
FanSpeedStatus_4a MI Low(1)
SetRoomTemp_4a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4a AI ℃
Alarm_4a BI Normal(0) Abnormal(1)
MalfunctionCode_4a AI Refer to the
SetTempStatus_4a AI ℃
Accumulated power(100 Watt)_4a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4a AI ℃
TempRangeLowerLimitStatus_4a AI ℃
ModeLockCommand_4a BO Permit(0) Prohibit(1)
ModeLockStatus_4a BI Permit(0) Prohibit(1)
FanLockCommand_4a BO Permit(0) Prohibit(1)
FanLockStatus_4a BI Permit(0) Prohibit(1)
OccupancyCommand_4a BO Unoccupied(0) Occupied(1)
OccupancyStatus_4a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4a BI Off(0) On(1)
AccumulatedGas(100 Watt)_4a AI Wattage values (Unit : 100Watt)
DustSensorAvail_4a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4a BO Stop(0) Run(1)
AirCleaningOperStatus_4a BI Stop(0) Run(1)
FineDustStatus_4a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4a AI %
ComfortCoolingAvail_4a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4a BO Stop(0) Run(1)
ComfortCoolingOperStatus_4a BI Stop(0) Run(1)
ComfortCoolingStepCommand_4a AV 1~3 step
ComfortCoolingStepStatus_4a AI 1~3 step
HumanDetectionAvail_4a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4a MO Off(1)
HumanDetectionOperStatus_4a MI Off(1)
HumanDetectionWindCommand_4a MO Off(1)
HumanDetectionWindStatus_4a MI Off(1)
HumanDetectionTimeCommand_4a MO 5min(1)
HumanDetectionTimeStatus_4a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4b ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4b BO Stop(0) Start(1)
StartStopStatus_4b BI Stop(0) Start(1)
LockCommand_4b BO Permit(0) Prohibit(1)
LockStatus_4b BI Permit(0) Prohibit(1)
FilterSign_4b BI Off(0) On(1)
FilterSignReset_4b BV - Reset(1)
AirConModeCommand_4b MO Cool(1)
AirConModeStatus_4b MI Cool(1)
SwingCommand_4b BO Stop(0) Run(1)
SwingStatus_4b BI Stop(0) Run(1)
FanSpeedCommand_4b MO Low(1)
FanSpeedStatus_4b MI Low(1)
SetRoomTemp_4b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4b AI ℃
Alarm_4b BI Normal(0) Abnormal(1)
MalfunctionCode_4b AI Refer to the
SetTempStatus_4b AI ℃
Accumulated power(100 Watt)_4b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4b AI ℃
TempRangeLowerLimitStatus_4b AI ℃
ModeLockCommand_4b BO Permit(0) Prohibit(1)
ModeLockStatus_4b BI Permit(0) Prohibit(1)
FanLockCommand_4b BO Permit(0) Prohibit(1)
FanLockStatus_4b BI Permit(0) Prohibit(1)
OccupancyCommand_4b BO Unoccupied(0) Occupied(1)
OccupancyStatus_4b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4b BI Off(0) On(1)
AccumulatedGas(100 Watt)_4b AI Wattage values (Unit : 100Watt)
DustSensorAvail_4b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4b BO Stop(0) Run(1)
AirCleaningOperStatus_4b BI Stop(0) Run(1)
FineDustStatus_4b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4b AI %
ComfortCoolingAvail_4b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4b BO Stop(0) Run(1)
ComfortCoolingOperStatus_4b BI Stop(0) Run(1)
ComfortCoolingStepCommand_4b AV 1~3 step
ComfortCoolingStepStatus_4b AI 1~3 step
HumanDetectionAvail_4b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4b MO Off(1)
HumanDetectionOperStatus_4b MI Off(1)
HumanDetectionWindCommand_4b MO Off(1)
HumanDetectionWindStatus_4b MI Off(1)
HumanDetectionTimeCommand_4b MO 5min(1)
HumanDetectionTimeStatus_4b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4c ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4c BO Stop(0) Start(1)
StartStopStatus_4c BI Stop(0) Start(1)
LockCommand_4c BO Permit(0) Prohibit(1)
LockStatus_4c BI Permit(0) Prohibit(1)
FilterSign_4c BI Off(0) On(1)
FilterSignReset_4c BV - Reset(1)
AirConModeCommand_4c MO Cool(1)
AirConModeStatus_4c MI Cool(1)
SwingCommand_4c BO Stop(0) Run(1)
SwingStatus_4c BI Stop(0) Run(1)
FanSpeedCommand_4c MO Low(1)
FanSpeedStatus_4c MI Low(1)
SetRoomTemp_4c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4c AI ℃
Alarm_4c BI Normal(0) Abnormal(1)
MalfunctionCode_4c AI Refer to the
SetTempStatus_4c AI ℃
Accumulated power(100 Watt)_4c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4c AI ℃
TempRangeLowerLimitStatus_4c AI ℃
ModeLockCommand_4c BO Permit(0) Prohibit(1)
ModeLockStatus_4c BI Permit(0) Prohibit(1)
FanLockCommand_4c BO Permit(0) Prohibit(1)
FanLockStatus_4c BI Permit(0) Prohibit(1)
OccupancyCommand_4c BO Unoccupied(0) Occupied(1)
OccupancyStatus_4c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4c BI Off(0) On(1)
AccumulatedGas(100 Watt)_4c AI Wattage values (Unit : 100Watt)
DustSensorAvail_4c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4c BO Stop(0) Run(1)
AirCleaningOperStatus_4c BI Stop(0) Run(1)
FineDustStatus_4c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4c AI %
ComfortCoolingAvail_4c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4c BO Stop(0) Run(1)
ComfortCoolingOperStatus_4c BI Stop(0) Run(1)
ComfortCoolingStepCommand_4c AV 1~3 step
ComfortCoolingStepStatus_4c AI 1~3 step
HumanDetectionAvail_4c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4c MO Off(1)
HumanDetectionOperStatus_4c MI Off(1)
HumanDetectionWindCommand_4c MO Off(1)
HumanDetectionWindStatus_4c MI Off(1)
HumanDetectionTimeCommand_4c MO 5min(1)
HumanDetectionTimeStatus_4c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
4d ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_4d BO Stop(0) Start(1)
StartStopStatus_4d BI Stop(0) Start(1)
LockCommand_4d BO Permit(0) Prohibit(1)
LockStatus_4d BI Permit(0) Prohibit(1)
FilterSign_4d BI Off(0) On(1)
FilterSignReset_4d BV - Reset(1)
AirConModeCommand_4d MO Cool(1)
AirConModeStatus_4d MI Cool(1)
SwingCommand_4d BO Stop(0) Run(1)
SwingStatus_4d BI Stop(0) Run(1)
FanSpeedCommand_4d MO Low(1)
FanSpeedStatus_4d MI Low(1)
SetRoomTemp_4d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_4d AI ℃
Alarm_4d BI Normal(0) Abnormal(1)
MalfunctionCode_4d AI Refer to the
SetTempStatus_4d AI ℃
Accumulated power(100 Watt)_4d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_4d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_4d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_4d AI ℃
TempRangeLowerLimitStatus_4d AI ℃
ModeLockCommand_4d BO Permit(0) Prohibit(1)
ModeLockStatus_4d BI Permit(0) Prohibit(1)
FanLockCommand_4d BO Permit(0) Prohibit(1)
FanLockStatus_4d BI Permit(0) Prohibit(1)
OccupancyCommand_4d BO Unoccupied(0) Occupied(1)
OccupancyStatus_4d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_4d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_4d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_4d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_4d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_4d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_4d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_4d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_4d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_4d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_4d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_4d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_4d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_4d BI Off(0) On(1)
AccumulatedGas(100 Watt)_4d AI Wattage values (Unit : 100Watt)
DustSensorAvail_4d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_4d BO Stop(0) Run(1)
AirCleaningOperStatus_4d BI Stop(0) Run(1)
FineDustStatus_4d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_4d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_4d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_4d AI %
ComfortCoolingAvail_4d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_4d BO Stop(0) Run(1)
ComfortCoolingOperStatus_4d BI Stop(0) Run(1)
ComfortCoolingStepCommand_4d AV 1~3 step
ComfortCoolingStepStatus_4d AI 1~3 step
HumanDetectionAvail_4d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_4d MO Off(1)
HumanDetectionOperStatus_4d MI Off(1)
HumanDetectionWindCommand_4d MO Off(1)
HumanDetectionWindStatus_4d MI Off(1)
HumanDetectionTimeCommand_4d MO 5min(1)
HumanDetectionTimeStatus_4d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
58 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_58 BO Stop(0) Start(1)
StartStopStatus_58 BI Stop(0) Start(1)
LockCommand_58 BO Permit(0) Prohibit(1)
LockStatus_58 BI Permit(0) Prohibit(1)
FilterSign_58 BI Off(0) On(1)
FilterSignReset_58 BV - Reset(1)
AirConModeCommand_58 MO Cool(1)
AirConModeStatus_58 MI Cool(1)
SwingCommand_58 BO Stop(0) Run(1)
SwingStatus_58 BI Stop(0) Run(1)
FanSpeedCommand_58 MO Low(1)
FanSpeedStatus_58 MI Low(1)
SetRoomTemp_58 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_58 AI ℃
Alarm_58 BI Normal(0) Abnormal(1)
MalfunctionCode_58 AI Refer to the
SetTempStatus_58 AI ℃
Accumulated power(100 Watt)_58 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_58 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_58 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_58 AI ℃
TempRangeLowerLimitStatus_58 AI ℃
ModeLockCommand_58 BO Permit(0) Prohibit(1)
ModeLockStatus_58 BI Permit(0) Prohibit(1)
FanLockCommand_58 BO Permit(0) Prohibit(1)
FanLockStatus_58 BI Permit(0) Prohibit(1)
OccupancyCommand_58 BO Unoccupied(0) Occupied(1)
OccupancyStatus_58 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_58 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_58 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_58 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_58 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_58 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_58 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_58 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_58 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_58 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_58 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_58 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_58 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_58 BI Off(0) On(1)
AccumulatedGas(100 Watt)_58 AI Wattage values (Unit : 100Watt)
DustSensorAvail_58 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_58 BO Stop(0) Run(1)
AirCleaningOperStatus_58 BI Stop(0) Run(1)
FineDustStatus_58 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_58 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_58 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_58 AI %
ComfortCoolingAvail_58 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_58 BO Stop(0) Run(1)
ComfortCoolingOperStatus_58 BI Stop(0) Run(1)
ComfortCoolingStepCommand_58 AV 1~3 step
ComfortCoolingStepStatus_58 AI 1~3 step
HumanDetectionAvail_58 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_58 MO Off(1)
HumanDetectionOperStatus_58 MI Off(1)
HumanDetectionWindCommand_58 MO Off(1)
HumanDetectionWindStatus_58 MI Off(1)
HumanDetectionTimeCommand_58 MO 5min(1)
HumanDetectionTimeStatus_58 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
59 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_59 BO Stop(0) Start(1)
StartStopStatus_59 BI Stop(0) Start(1)
LockCommand_59 BO Permit(0) Prohibit(1)
LockStatus_59 BI Permit(0) Prohibit(1)
FilterSign_59 BI Off(0) On(1)
FilterSignReset_59 BV - Reset(1)
AirConModeCommand_59 MO Cool(1)
AirConModeStatus_59 MI Cool(1)
SwingCommand_59 BO Stop(0) Run(1)
SwingStatus_59 BI Stop(0) Run(1)
FanSpeedCommand_59 MO Low(1)
FanSpeedStatus_59 MI Low(1)
SetRoomTemp_59 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_59 AI ℃
Alarm_59 BI Normal(0) Abnormal(1)
MalfunctionCode_59 AI Refer to the
SetTempStatus_59 AI ℃
Accumulated power(100 Watt)_59 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_59 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_59 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_59 AI ℃
TempRangeLowerLimitStatus_59 AI ℃
ModeLockCommand_59 BO Permit(0) Prohibit(1)
ModeLockStatus_59 BI Permit(0) Prohibit(1)
FanLockCommand_59 BO Permit(0) Prohibit(1)
FanLockStatus_59 BI Permit(0) Prohibit(1)
OccupancyCommand_59 BO Unoccupied(0) Occupied(1)
OccupancyStatus_59 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_59 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_59 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_59 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_59 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_59 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_59 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_59 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_59 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_59 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_59 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_59 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_59 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_59 BI Off(0) On(1)
AccumulatedGas(100 Watt)_59 AI Wattage values (Unit : 100Watt)
DustSensorAvail_59 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_59 BO Stop(0) Run(1)
AirCleaningOperStatus_59 BI Stop(0) Run(1)
FineDustStatus_59 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_59 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_59 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_59 AI %
ComfortCoolingAvail_59 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_59 BO Stop(0) Run(1)
ComfortCoolingOperStatus_59 BI Stop(0) Run(1)
ComfortCoolingStepCommand_59 AV 1~3 step
ComfortCoolingStepStatus_59 AI 1~3 step
HumanDetectionAvail_59 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_59 MO Off(1)
HumanDetectionOperStatus_59 MI Off(1)
HumanDetectionWindCommand_59 MO Off(1)
HumanDetectionWindStatus_59 MI Off(1)
HumanDetectionTimeCommand_59 MO 5min(1)
HumanDetectionTimeStatus_59 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5a ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5a BO Stop(0) Start(1)
StartStopStatus_5a BI Stop(0) Start(1)
LockCommand_5a BO Permit(0) Prohibit(1)
LockStatus_5a BI Permit(0) Prohibit(1)
FilterSign_5a BI Off(0) On(1)
FilterSignReset_5a BV - Reset(1)
AirConModeCommand_5a MO Cool(1)
AirConModeStatus_5a MI Cool(1)
SwingCommand_5a BO Stop(0) Run(1)
SwingStatus_5a BI Stop(0) Run(1)
FanSpeedCommand_5a MO Low(1)
FanSpeedStatus_5a MI Low(1)
SetRoomTemp_5a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5a AI ℃
Alarm_5a BI Normal(0) Abnormal(1)
MalfunctionCode_5a AI Refer to the
SetTempStatus_5a AI ℃
Accumulated power(100 Watt)_5a AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5a AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5a AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5a AI ℃
TempRangeLowerLimitStatus_5a AI ℃
ModeLockCommand_5a BO Permit(0) Prohibit(1)
ModeLockStatus_5a BI Permit(0) Prohibit(1)
FanLockCommand_5a BO Permit(0) Prohibit(1)
FanLockStatus_5a BI Permit(0) Prohibit(1)
OccupancyCommand_5a BO Unoccupied(0) Occupied(1)
OccupancyStatus_5a BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5a AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5a AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5a AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5a AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5a BI Off(0) On(1)
AccumulatedGas(100 Watt)_5a AI Wattage values (Unit : 100Watt)
DustSensorAvail_5a BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5a BO Stop(0) Run(1)
AirCleaningOperStatus_5a BI Stop(0) Run(1)
FineDustStatus_5a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5a AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5a AI %
ComfortCoolingAvail_5a BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5a BO Stop(0) Run(1)
ComfortCoolingOperStatus_5a BI Stop(0) Run(1)
ComfortCoolingStepCommand_5a AV 1~3 step
ComfortCoolingStepStatus_5a AI 1~3 step
HumanDetectionAvail_5a BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5a MO Off(1)
HumanDetectionOperStatus_5a MI Off(1)
HumanDetectionWindCommand_5a MO Off(1)
HumanDetectionWindStatus_5a MI Off(1)
HumanDetectionTimeCommand_5a MO 5min(1)
HumanDetectionTimeStatus_5a MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5b ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5b BO Stop(0) Start(1)
StartStopStatus_5b BI Stop(0) Start(1)
LockCommand_5b BO Permit(0) Prohibit(1)
LockStatus_5b BI Permit(0) Prohibit(1)
FilterSign_5b BI Off(0) On(1)
FilterSignReset_5b BV - Reset(1)
AirConModeCommand_5b MO Cool(1)
AirConModeStatus_5b MI Cool(1)
SwingCommand_5b BO Stop(0) Run(1)
SwingStatus_5b BI Stop(0) Run(1)
FanSpeedCommand_5b MO Low(1)
FanSpeedStatus_5b MI Low(1)
SetRoomTemp_5b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5b AI ℃
Alarm_5b BI Normal(0) Abnormal(1)
MalfunctionCode_5b AI Refer to the
SetTempStatus_5b AI ℃
Accumulated power(100 Watt)_5b AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5b AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5b AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5b AI ℃
TempRangeLowerLimitStatus_5b AI ℃
ModeLockCommand_5b BO Permit(0) Prohibit(1)
ModeLockStatus_5b BI Permit(0) Prohibit(1)
FanLockCommand_5b BO Permit(0) Prohibit(1)
FanLockStatus_5b BI Permit(0) Prohibit(1)
OccupancyCommand_5b BO Unoccupied(0) Occupied(1)
OccupancyStatus_5b BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5b AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5b AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5b AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5b AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5b BI Off(0) On(1)
AccumulatedGas(100 Watt)_5b AI Wattage values (Unit : 100Watt)
DustSensorAvail_5b BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5b BO Stop(0) Run(1)
AirCleaningOperStatus_5b BI Stop(0) Run(1)
FineDustStatus_5b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5b AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5b AI %
ComfortCoolingAvail_5b BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5b BO Stop(0) Run(1)
ComfortCoolingOperStatus_5b BI Stop(0) Run(1)
ComfortCoolingStepCommand_5b AV 1~3 step
ComfortCoolingStepStatus_5b AI 1~3 step
HumanDetectionAvail_5b BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5b MO Off(1)
HumanDetectionOperStatus_5b MI Off(1)
HumanDetectionWindCommand_5b MO Off(1)
HumanDetectionWindStatus_5b MI Off(1)
HumanDetectionTimeCommand_5b MO 5min(1)
HumanDetectionTimeStatus_5b MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5c ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5c BO Stop(0) Start(1)
StartStopStatus_5c BI Stop(0) Start(1)
LockCommand_5c BO Permit(0) Prohibit(1)
LockStatus_5c BI Permit(0) Prohibit(1)
FilterSign_5c BI Off(0) On(1)
FilterSignReset_5c BV - Reset(1)
AirConModeCommand_5c MO Cool(1)
AirConModeStatus_5c MI Cool(1)
SwingCommand_5c BO Stop(0) Run(1)
SwingStatus_5c BI Stop(0) Run(1)
FanSpeedCommand_5c MO Low(1)
FanSpeedStatus_5c MI Low(1)
SetRoomTemp_5c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5c AI ℃
Alarm_5c BI Normal(0) Abnormal(1)
MalfunctionCode_5c AI Refer to the
SetTempStatus_5c AI ℃
Accumulated power(100 Watt)_5c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5c AI ℃
TempRangeLowerLimitStatus_5c AI ℃
ModeLockCommand_5c BO Permit(0) Prohibit(1)
ModeLockStatus_5c BI Permit(0) Prohibit(1)
FanLockCommand_5c BO Permit(0) Prohibit(1)
FanLockStatus_5c BI Permit(0) Prohibit(1)
OccupancyCommand_5c BO Unoccupied(0) Occupied(1)
OccupancyStatus_5c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5c BI Off(0) On(1)
AccumulatedGas(100 Watt)_5c AI Wattage values (Unit : 100Watt)
DustSensorAvail_5c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5c BO Stop(0) Run(1)
AirCleaningOperStatus_5c BI Stop(0) Run(1)
FineDustStatus_5c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5c AI %
ComfortCoolingAvail_5c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5c BO Stop(0) Run(1)
ComfortCoolingOperStatus_5c BI Stop(0) Run(1)
ComfortCoolingStepCommand_5c AV 1~3 step
ComfortCoolingStepStatus_5c AI 1~3 step
HumanDetectionAvail_5c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5c MO Off(1)
HumanDetectionOperStatus_5c MI Off(1)
HumanDetectionWindCommand_5c MO Off(1)
HumanDetectionWindStatus_5c MI Off(1)
HumanDetectionTimeCommand_5c MO 5min(1)
HumanDetectionTimeStatus_5c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5d ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5d BO Stop(0) Start(1)
StartStopStatus_5d BI Stop(0) Start(1)
LockCommand_5d BO Permit(0) Prohibit(1)
LockStatus_5d BI Permit(0) Prohibit(1)
FilterSign_5d BI Off(0) On(1)
FilterSignReset_5d BV - Reset(1)
AirConModeCommand_5d MO Cool(1)
AirConModeStatus_5d MI Cool(1)
SwingCommand_5d BO Stop(0) Run(1)
SwingStatus_5d BI Stop(0) Run(1)
FanSpeedCommand_5d MO Low(1)
FanSpeedStatus_5d MI Low(1)
SetRoomTemp_5d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5d AI ℃
Alarm_5d BI Normal(0) Abnormal(1)
MalfunctionCode_5d AI Refer to the
SetTempStatus_5d AI ℃
Accumulated power(100 Watt)_5d AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5d AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5d AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5d AI ℃
TempRangeLowerLimitStatus_5d AI ℃
ModeLockCommand_5d BO Permit(0) Prohibit(1)
ModeLockStatus_5d BI Permit(0) Prohibit(1)
FanLockCommand_5d BO Permit(0) Prohibit(1)
FanLockStatus_5d BI Permit(0) Prohibit(1)
OccupancyCommand_5d BO Unoccupied(0) Occupied(1)
OccupancyStatus_5d BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5d AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5d AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5d AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5d AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5d BI Off(0) On(1)
AccumulatedGas(100 Watt)_5d AI Wattage values (Unit : 100Watt)
DustSensorAvail_5d BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5d BO Stop(0) Run(1)
AirCleaningOperStatus_5d BI Stop(0) Run(1)
FineDustStatus_5d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5d AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5d AI %
ComfortCoolingAvail_5d BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5d BO Stop(0) Run(1)
ComfortCoolingOperStatus_5d BI Stop(0) Run(1)
ComfortCoolingStepCommand_5d AV 1~3 step
ComfortCoolingStepStatus_5d AI 1~3 step
HumanDetectionAvail_5d BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5d MO Off(1)
HumanDetectionOperStatus_5d MI Off(1)
HumanDetectionWindCommand_5d MO Off(1)
HumanDetectionWindStatus_5d MI Off(1)
HumanDetectionTimeCommand_5d MO 5min(1)
HumanDetectionTimeStatus_5d MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5e ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5e BO Stop(0) Start(1)
StartStopStatus_5e BI Stop(0) Start(1)
LockCommand_5e BO Permit(0) Prohibit(1)
LockStatus_5e BI Permit(0) Prohibit(1)
FilterSign_5e BI Off(0) On(1)
FilterSignReset_5e BV - Reset(1)
AirConModeCommand_5e MO Cool(1)
AirConModeStatus_5e MI Cool(1)
SwingCommand_5e BO Stop(0) Run(1)
SwingStatus_5e BI Stop(0) Run(1)
FanSpeedCommand_5e MO Low(1)
FanSpeedStatus_5e MI Low(1)
SetRoomTemp_5e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5e AI ℃
Alarm_5e BI Normal(0) Abnormal(1)
MalfunctionCode_5e AI Refer to the
SetTempStatus_5e AI ℃
Accumulated power(100 Watt)_5e AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5e AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5e AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5e AI ℃
TempRangeLowerLimitStatus_5e AI ℃
ModeLockCommand_5e BO Permit(0) Prohibit(1)
ModeLockStatus_5e BI Permit(0) Prohibit(1)
FanLockCommand_5e BO Permit(0) Prohibit(1)
FanLockStatus_5e BI Permit(0) Prohibit(1)
OccupancyCommand_5e BO Unoccupied(0) Occupied(1)
OccupancyStatus_5e BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5e AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5e AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5e AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5e AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5e BI Off(0) On(1)
AccumulatedGas(100 Watt)_5e AI Wattage values (Unit : 100Watt)
DustSensorAvail_5e BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5e BO Stop(0) Run(1)
AirCleaningOperStatus_5e BI Stop(0) Run(1)
FineDustStatus_5e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5e AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5e AI %
ComfortCoolingAvail_5e BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5e BO Stop(0) Run(1)
ComfortCoolingOperStatus_5e BI Stop(0) Run(1)
ComfortCoolingStepCommand_5e AV 1~3 step
ComfortCoolingStepStatus_5e AI 1~3 step
HumanDetectionAvail_5e BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5e MO Off(1)
HumanDetectionOperStatus_5e MI Off(1)
HumanDetectionWindCommand_5e MO Off(1)
HumanDetectionWindStatus_5e MI Off(1)
HumanDetectionTimeCommand_5e MO 5min(1)
HumanDetectionTimeStatus_5e MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
5f ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_5f BO Stop(0) Start(1)
StartStopStatus_5f BI Stop(0) Start(1)
LockCommand_5f BO Permit(0) Prohibit(1)
LockStatus_5f BI Permit(0) Prohibit(1)
FilterSign_5f BI Off(0) On(1)
FilterSignReset_5f BV - Reset(1)
AirConModeCommand_5f MO Cool(1)
AirConModeStatus_5f MI Cool(1)
SwingCommand_5f BO Stop(0) Run(1)
SwingStatus_5f BI Stop(0) Run(1)
FanSpeedCommand_5f MO Low(1)
FanSpeedStatus_5f MI Low(1)
SetRoomTemp_5f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_5f AI ℃
Alarm_5f BI Normal(0) Abnormal(1)
MalfunctionCode_5f AI Refer to the
SetTempStatus_5f AI ℃
Accumulated power(100 Watt)_5f AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_5f AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_5f AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_5f AI ℃
TempRangeLowerLimitStatus_5f AI ℃
ModeLockCommand_5f BO Permit(0) Prohibit(1)
ModeLockStatus_5f BI Permit(0) Prohibit(1)
FanLockCommand_5f BO Permit(0) Prohibit(1)
FanLockStatus_5f BI Permit(0) Prohibit(1)
OccupancyCommand_5f BO Unoccupied(0) Occupied(1)
OccupancyStatus_5f BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_5f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_5f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_5f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_5f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_5f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_5f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_5f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_5f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_5f AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_5f AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_5f AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_5f AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_5f BI Off(0) On(1)
AccumulatedGas(100 Watt)_5f AI Wattage values (Unit : 100Watt)
DustSensorAvail_5f BI Disabled(0) Enabled(1)
AirCleaningOperCommand_5f BO Stop(0) Run(1)
AirCleaningOperStatus_5f BI Stop(0) Run(1)
FineDustStatus_5f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_5f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_5f AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_5f AI %
ComfortCoolingAvail_5f BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_5f BO Stop(0) Run(1)
ComfortCoolingOperStatus_5f BI Stop(0) Run(1)
ComfortCoolingStepCommand_5f AV 1~3 step
ComfortCoolingStepStatus_5f AI 1~3 step
HumanDetectionAvail_5f BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_5f MO Off(1)
HumanDetectionOperStatus_5f MI Off(1)
HumanDetectionWindCommand_5f MO Off(1)
HumanDetectionWindStatus_5f MI Off(1)
HumanDetectionTimeCommand_5f MO 5min(1)
HumanDetectionTimeStatus_5f MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
60 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_60 BO Stop(0) Start(1)
StartStopStatus_60 BI Stop(0) Start(1)
LockCommand_60 BO Permit(0) Prohibit(1)
LockStatus_60 BI Permit(0) Prohibit(1)
FilterSign_60 BI Off(0) On(1)
FilterSignReset_60 BV - Reset(1)
AirConModeCommand_60 MO Cool(1)
AirConModeStatus_60 MI Cool(1)
SwingCommand_60 BO Stop(0) Run(1)
SwingStatus_60 BI Stop(0) Run(1)
FanSpeedCommand_60 MO Low(1)
FanSpeedStatus_60 MI Low(1)
SetRoomTemp_60 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_60 AI ℃
Alarm_60 BI Normal(0) Abnormal(1)
MalfunctionCode_60 AI Refer to the
SetTempStatus_60 AI ℃
Accumulated power(100 Watt)_60 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_60 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_60 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_60 AI ℃
TempRangeLowerLimitStatus_60 AI ℃
ModeLockCommand_60 BO Permit(0) Prohibit(1)
ModeLockStatus_60 BI Permit(0) Prohibit(1)
FanLockCommand_60 BO Permit(0) Prohibit(1)
FanLockStatus_60 BI Permit(0) Prohibit(1)
OccupancyCommand_60 BO Unoccupied(0) Occupied(1)
OccupancyStatus_60 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_60 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_60 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_60 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_60 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_60 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_60 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_60 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_60 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_60 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_60 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_60 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_60 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_60 BI Off(0) On(1)
AccumulatedGas(100 Watt)_60 AI Wattage values (Unit : 100Watt)
DustSensorAvail_60 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_60 BO Stop(0) Run(1)
AirCleaningOperStatus_60 BI Stop(0) Run(1)
FineDustStatus_60 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_60 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_60 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_60 AI %
ComfortCoolingAvail_60 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_60 BO Stop(0) Run(1)
ComfortCoolingOperStatus_60 BI Stop(0) Run(1)
ComfortCoolingStepCommand_60 AV 1~3 step
ComfortCoolingStepStatus_60 AI 1~3 step
HumanDetectionAvail_60 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_60 MO Off(1)
HumanDetectionOperStatus_60 MI Off(1)
HumanDetectionWindCommand_60 MO Off(1)
HumanDetectionWindStatus_60 MI Off(1)
HumanDetectionTimeCommand_60 MO 5min(1)
HumanDetectionTimeStatus_60 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
61 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_61 BO Stop(0) Start(1)
StartStopStatus_61 BI Stop(0) Start(1)
LockCommand_61 BO Permit(0) Prohibit(1)
LockStatus_61 BI Permit(0) Prohibit(1)
FilterSign_61 BI Off(0) On(1)
FilterSignReset_61 BV - Reset(1)
AirConModeCommand_61 MO Cool(1)
AirConModeStatus_61 MI Cool(1)
SwingCommand_61 BO Stop(0) Run(1)
SwingStatus_61 BI Stop(0) Run(1)
FanSpeedCommand_61 MO Low(1)
FanSpeedStatus_61 MI Low(1)
SetRoomTemp_61 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_61 AI ℃
Alarm_61 BI Normal(0) Abnormal(1)
MalfunctionCode_61 AI Refer to the
SetTempStatus_61 AI ℃
Accumulated power(100 Watt)_61 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_61 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_61 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_61 AI ℃
TempRangeLowerLimitStatus_61 AI ℃
ModeLockCommand_61 BO Permit(0) Prohibit(1)
ModeLockStatus_61 BI Permit(0) Prohibit(1)
FanLockCommand_61 BO Permit(0) Prohibit(1)
FanLockStatus_61 BI Permit(0) Prohibit(1)
OccupancyCommand_61 BO Unoccupied(0) Occupied(1)
OccupancyStatus_61 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_61 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_61 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_61 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_61 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_61 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_61 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_61 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_61 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_61 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_61 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_61 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_61 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_61 BI Off(0) On(1)
AccumulatedGas(100 Watt)_61 AI Wattage values (Unit : 100Watt)
DustSensorAvail_61 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_61 BO Stop(0) Run(1)
AirCleaningOperStatus_61 BI Stop(0) Run(1)
FineDustStatus_61 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_61 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_61 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_61 AI %
ComfortCoolingAvail_61 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_61 BO Stop(0) Run(1)
ComfortCoolingOperStatus_61 BI Stop(0) Run(1)
ComfortCoolingStepCommand_61 AV 1~3 step
ComfortCoolingStepStatus_61 AI 1~3 step
HumanDetectionAvail_61 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_61 MO Off(1)
HumanDetectionOperStatus_61 MI Off(1)
HumanDetectionWindCommand_61 MO Off(1)
HumanDetectionWindStatus_61 MI Off(1)
HumanDetectionTimeCommand_61 MO 5min(1)
HumanDetectionTimeStatus_61 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
62 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_62 BO Stop(0) Start(1)
StartStopStatus_62 BI Stop(0) Start(1)
LockCommand_62 BO Permit(0) Prohibit(1)
LockStatus_62 BI Permit(0) Prohibit(1)
FilterSign_62 BI Off(0) On(1)
FilterSignReset_62 BV - Reset(1)
AirConModeCommand_62 MO Cool(1)
AirConModeStatus_62 MI Cool(1)
SwingCommand_62 BO Stop(0) Run(1)
SwingStatus_62 BI Stop(0) Run(1)
FanSpeedCommand_62 MO Low(1)
FanSpeedStatus_62 MI Low(1)
SetRoomTemp_62 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_62 AI ℃
Alarm_62 BI Normal(0) Abnormal(1)
MalfunctionCode_62 AI Refer to the
SetTempStatus_62 AI ℃
Accumulated power(100 Watt)_62 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_62 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_62 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_62 AI ℃
TempRangeLowerLimitStatus_62 AI ℃
ModeLockCommand_62 BO Permit(0) Prohibit(1)
ModeLockStatus_62 BI Permit(0) Prohibit(1)
FanLockCommand_62 BO Permit(0) Prohibit(1)
FanLockStatus_62 BI Permit(0) Prohibit(1)
OccupancyCommand_62 BO Unoccupied(0) Occupied(1)
OccupancyStatus_62 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_62 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_62 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_62 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_62 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_62 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_62 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_62 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_62 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_62 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_62 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_62 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_62 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_62 BI Off(0) On(1)
AccumulatedGas(100 Watt)_62 AI Wattage values (Unit : 100Watt)
DustSensorAvail_62 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_62 BO Stop(0) Run(1)
AirCleaningOperStatus_62 BI Stop(0) Run(1)
FineDustStatus_62 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_62 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_62 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_62 AI %
ComfortCoolingAvail_62 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_62 BO Stop(0) Run(1)
ComfortCoolingOperStatus_62 BI Stop(0) Run(1)
ComfortCoolingStepCommand_62 AV 1~3 step
ComfortCoolingStepStatus_62 AI 1~3 step
HumanDetectionAvail_62 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_62 MO Off(1)
HumanDetectionOperStatus_62 MI Off(1)
HumanDetectionWindCommand_62 MO Off(1)
HumanDetectionWindStatus_62 MI Off(1)
HumanDetectionTimeCommand_62 MO 5min(1)
HumanDetectionTimeStatus_62 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
63 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_63 BO Stop(0) Start(1)
StartStopStatus_63 BI Stop(0) Start(1)
LockCommand_63 BO Permit(0) Prohibit(1)
LockStatus_63 BI Permit(0) Prohibit(1)
FilterSign_63 BI Off(0) On(1)
FilterSignReset_63 BV - Reset(1)
AirConModeCommand_63 MO Cool(1)
AirConModeStatus_63 MI Cool(1)
SwingCommand_63 BO Stop(0) Run(1)
SwingStatus_63 BI Stop(0) Run(1)
FanSpeedCommand_63 MO Low(1)
FanSpeedStatus_63 MI Low(1)
SetRoomTemp_63 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_63 AI ℃
Alarm_63 BI Normal(0) Abnormal(1)
MalfunctionCode_63 AI Refer to the
SetTempStatus_63 AI ℃
Accumulated power(100 Watt)_63 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_63 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_63 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_63 AI ℃
TempRangeLowerLimitStatus_63 AI ℃
ModeLockCommand_63 BO Permit(0) Prohibit(1)
ModeLockStatus_63 BI Permit(0) Prohibit(1)
FanLockCommand_63 BO Permit(0) Prohibit(1)
FanLockStatus_63 BI Permit(0) Prohibit(1)
OccupancyCommand_63 BO Unoccupied(0) Occupied(1)
OccupancyStatus_63 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_63 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_63 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_63 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_63 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_63 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_63 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_63 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_63 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_63 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_63 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_63 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_63 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_63 BI Off(0) On(1)
AccumulatedGas(100 Watt)_63 AI Wattage values (Unit : 100Watt)
DustSensorAvail_63 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_63 BO Stop(0) Run(1)
AirCleaningOperStatus_63 BI Stop(0) Run(1)
FineDustStatus_63 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_63 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_63 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_63 AI %
ComfortCoolingAvail_63 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_63 BO Stop(0) Run(1)
ComfortCoolingOperStatus_63 BI Stop(0) Run(1)
ComfortCoolingStepCommand_63 AV 1~3 step
ComfortCoolingStepStatus_63 AI 1~3 step
HumanDetectionAvail_63 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_63 MO Off(1)
HumanDetectionOperStatus_63 MI Off(1)
HumanDetectionWindCommand_63 MO Off(1)
HumanDetectionWindStatus_63 MI Off(1)
HumanDetectionTimeCommand_63 MO 5min(1)
HumanDetectionTimeStatus_63 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
64 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_64 BO Stop(0) Start(1)
StartStopStatus_64 BI Stop(0) Start(1)
LockCommand_64 BO Permit(0) Prohibit(1)
LockStatus_64 BI Permit(0) Prohibit(1)
FilterSign_64 BI Off(0) On(1)
FilterSignReset_64 BV - Reset(1)
AirConModeCommand_64 MO Cool(1)
AirConModeStatus_64 MI Cool(1)
SwingCommand_64 BO Stop(0) Run(1)
SwingStatus_64 BI Stop(0) Run(1)
FanSpeedCommand_64 MO Low(1)
FanSpeedStatus_64 MI Low(1)
SetRoomTemp_64 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_64 AI ℃
Alarm_64 BI Normal(0) Abnormal(1)
MalfunctionCode_64 AI Refer to the
SetTempStatus_64 AI ℃
Accumulated power(100 Watt)_64 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_64 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_64 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_64 AI ℃
TempRangeLowerLimitStatus_64 AI ℃
ModeLockCommand_64 BO Permit(0) Prohibit(1)
ModeLockStatus_64 BI Permit(0) Prohibit(1)
FanLockCommand_64 BO Permit(0) Prohibit(1)
FanLockStatus_64 BI Permit(0) Prohibit(1)
OccupancyCommand_64 BO Unoccupied(0) Occupied(1)
OccupancyStatus_64 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_64 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_64 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_64 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_64 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_64 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_64 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_64 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_64 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_64 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_64 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_64 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_64 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_64 BI Off(0) On(1)
AccumulatedGas(100 Watt)_64 AI Wattage values (Unit : 100Watt)
DustSensorAvail_64 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_64 BO Stop(0) Run(1)
AirCleaningOperStatus_64 BI Stop(0) Run(1)
FineDustStatus_64 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_64 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_64 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_64 AI %
ComfortCoolingAvail_64 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_64 BO Stop(0) Run(1)
ComfortCoolingOperStatus_64 BI Stop(0) Run(1)
ComfortCoolingStepCommand_64 AV 1~3 step
ComfortCoolingStepStatus_64 AI 1~3 step
HumanDetectionAvail_64 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_64 MO Off(1)
HumanDetectionOperStatus_64 MI Off(1)
HumanDetectionWindCommand_64 MO Off(1)
HumanDetectionWindStatus_64 MI Off(1)
HumanDetectionTimeCommand_64 MO 5min(1)
HumanDetectionTimeStatus_64 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
65 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_65 BO Stop(0) Start(1)
StartStopStatus_65 BI Stop(0) Start(1)
LockCommand_65 BO Permit(0) Prohibit(1)
LockStatus_65 BI Permit(0) Prohibit(1)
FilterSign_65 BI Off(0) On(1)
FilterSignReset_65 BV - Reset(1)
AirConModeCommand_65 MO Cool(1)
AirConModeStatus_65 MI Cool(1)
SwingCommand_65 BO Stop(0) Run(1)
SwingStatus_65 BI Stop(0) Run(1)
FanSpeedCommand_65 MO Low(1)
FanSpeedStatus_65 MI Low(1)
SetRoomTemp_65 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_65 AI ℃
Alarm_65 BI Normal(0) Abnormal(1)
MalfunctionCode_65 AI Refer to the
SetTempStatus_65 AI ℃
Accumulated power(100 Watt)_65 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_65 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_65 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_65 AI ℃
TempRangeLowerLimitStatus_65 AI ℃
ModeLockCommand_65 BO Permit(0) Prohibit(1)
ModeLockStatus_65 BI Permit(0) Prohibit(1)
FanLockCommand_65 BO Permit(0) Prohibit(1)
FanLockStatus_65 BI Permit(0) Prohibit(1)
OccupancyCommand_65 BO Unoccupied(0) Occupied(1)
OccupancyStatus_65 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_65 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_65 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_65 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_65 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_65 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_65 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_65 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_65 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_65 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_65 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_65 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_65 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_65 BI Off(0) On(1)
AccumulatedGas(100 Watt)_65 AI Wattage values (Unit : 100Watt)
DustSensorAvail_65 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_65 BO Stop(0) Run(1)
AirCleaningOperStatus_65 BI Stop(0) Run(1)
FineDustStatus_65 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_65 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_65 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_65 AI %
ComfortCoolingAvail_65 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_65 BO Stop(0) Run(1)
ComfortCoolingOperStatus_65 BI Stop(0) Run(1)
ComfortCoolingStepCommand_65 AV 1~3 step
ComfortCoolingStepStatus_65 AI 1~3 step
HumanDetectionAvail_65 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_65 MO Off(1)
HumanDetectionOperStatus_65 MI Off(1)
HumanDetectionWindCommand_65 MO Off(1)
HumanDetectionWindStatus_65 MI Off(1)
HumanDetectionTimeCommand_65 MO 5min(1)
HumanDetectionTimeStatus_65 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
66 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_66 BO Stop(0) Start(1)
StartStopStatus_66 BI Stop(0) Start(1)
LockCommand_66 BO Permit(0) Prohibit(1)
LockStatus_66 BI Permit(0) Prohibit(1)
FilterSign_66 BI Off(0) On(1)
FilterSignReset_66 BV - Reset(1)
AirConModeCommand_66 MO Cool(1)
AirConModeStatus_66 MI Cool(1)
SwingCommand_66 BO Stop(0) Run(1)
SwingStatus_66 BI Stop(0) Run(1)
FanSpeedCommand_66 MO Low(1)
FanSpeedStatus_66 MI Low(1)
SetRoomTemp_66 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_66 AI ℃
Alarm_66 BI Normal(0) Abnormal(1)
MalfunctionCode_66 AI Refer to the
SetTempStatus_66 AI ℃
Accumulated power(100 Watt)_66 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_66 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_66 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_66 AI ℃
TempRangeLowerLimitStatus_66 AI ℃
ModeLockCommand_66 BO Permit(0) Prohibit(1)
ModeLockStatus_66 BI Permit(0) Prohibit(1)
FanLockCommand_66 BO Permit(0) Prohibit(1)
FanLockStatus_66 BI Permit(0) Prohibit(1)
OccupancyCommand_66 BO Unoccupied(0) Occupied(1)
OccupancyStatus_66 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_66 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_66 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_66 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_66 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_66 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_66 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_66 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_66 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_66 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_66 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_66 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_66 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_66 BI Off(0) On(1)
AccumulatedGas(100 Watt)_66 AI Wattage values (Unit : 100Watt)
DustSensorAvail_66 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_66 BO Stop(0) Run(1)
AirCleaningOperStatus_66 BI Stop(0) Run(1)
FineDustStatus_66 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_66 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_66 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_66 AI %
ComfortCoolingAvail_66 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_66 BO Stop(0) Run(1)
ComfortCoolingOperStatus_66 BI Stop(0) Run(1)
ComfortCoolingStepCommand_66 AV 1~3 step
ComfortCoolingStepStatus_66 AI 1~3 step
HumanDetectionAvail_66 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_66 MO Off(1)
HumanDetectionOperStatus_66 MI Off(1)
HumanDetectionWindCommand_66 MO Off(1)
HumanDetectionWindStatus_66 MI Off(1)
HumanDetectionTimeCommand_66 MO 5min(1)
HumanDetectionTimeStatus_66 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
67 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_67 BO Stop(0) Start(1)
StartStopStatus_67 BI Stop(0) Start(1)
LockCommand_67 BO Permit(0) Prohibit(1)
LockStatus_67 BI Permit(0) Prohibit(1)
FilterSign_67 BI Off(0) On(1)
FilterSignReset_67 BV - Reset(1)
AirConModeCommand_67 MO Cool(1)
AirConModeStatus_67 MI Cool(1)
SwingCommand_67 BO Stop(0) Run(1)
SwingStatus_67 BI Stop(0) Run(1)
FanSpeedCommand_67 MO Low(1)
FanSpeedStatus_67 MI Low(1)
SetRoomTemp_67 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_67 AI ℃
Alarm_67 BI Normal(0) Abnormal(1)
MalfunctionCode_67 AI Refer to the
SetTempStatus_67 AI ℃
Accumulated power(100 Watt)_67 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_67 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_67 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_67 AI ℃
TempRangeLowerLimitStatus_67 AI ℃
ModeLockCommand_67 BO Permit(0) Prohibit(1)
ModeLockStatus_67 BI Permit(0) Prohibit(1)
FanLockCommand_67 BO Permit(0) Prohibit(1)
FanLockStatus_67 BI Permit(0) Prohibit(1)
OccupancyCommand_67 BO Unoccupied(0) Occupied(1)
OccupancyStatus_67 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_67 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_67 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_67 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_67 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_67 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_67 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_67 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_67 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_67 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_67 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_67 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_67 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_67 BI Off(0) On(1)
AccumulatedGas(100 Watt)_67 AI Wattage values (Unit : 100Watt)
DustSensorAvail_67 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_67 BO Stop(0) Run(1)
AirCleaningOperStatus_67 BI Stop(0) Run(1)
FineDustStatus_67 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_67 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_67 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_67 AI %
ComfortCoolingAvail_67 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_67 BO Stop(0) Run(1)
ComfortCoolingOperStatus_67 BI Stop(0) Run(1)
ComfortCoolingStepCommand_67 AV 1~3 step
ComfortCoolingStepStatus_67 AI 1~3 step
HumanDetectionAvail_67 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_67 MO Off(1)
HumanDetectionOperStatus_67 MI Off(1)
HumanDetectionWindCommand_67 MO Off(1)
HumanDetectionWindStatus_67 MI Off(1)
HumanDetectionTimeCommand_67 MO 5min(1)
HumanDetectionTimeStatus_67 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
68 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_68 BO Stop(0) Start(1)
StartStopStatus_68 BI Stop(0) Start(1)
LockCommand_68 BO Permit(0) Prohibit(1)
LockStatus_68 BI Permit(0) Prohibit(1)
FilterSign_68 BI Off(0) On(1)
FilterSignReset_68 BV - Reset(1)
AirConModeCommand_68 MO Cool(1)
AirConModeStatus_68 MI Cool(1)
SwingCommand_68 BO Stop(0) Run(1)
SwingStatus_68 BI Stop(0) Run(1)
FanSpeedCommand_68 MO Low(1)
FanSpeedStatus_68 MI Low(1)
SetRoomTemp_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_68 AI ℃
Alarm_68 BI Normal(0) Abnormal(1)
MalfunctionCode_68 AI Refer to the
SetTempStatus_68 AI ℃
Accumulated power(100 Watt)_68 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_68 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_68 AI ℃
TempRangeLowerLimitStatus_68 AI ℃
ModeLockCommand_68 BO Permit(0) Prohibit(1)
ModeLockStatus_68 BI Permit(0) Prohibit(1)
FanLockCommand_68 BO Permit(0) Prohibit(1)
FanLockStatus_68 BI Permit(0) Prohibit(1)
OccupancyCommand_68 BO Unoccupied(0) Occupied(1)
OccupancyStatus_68 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_68 BI Off(0) On(1)
AccumulatedGas(100 Watt)_68 AI Wattage values (Unit : 100Watt)
DustSensorAvail_68 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_68 BO Stop(0) Run(1)
AirCleaningOperStatus_68 BI Stop(0) Run(1)
FineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_68 AI %
ComfortCoolingAvail_68 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_68 BO Stop(0) Run(1)
ComfortCoolingOperStatus_68 BI Stop(0) Run(1)
ComfortCoolingStepCommand_68 AV 1~3 step
ComfortCoolingStepStatus_68 AI 1~3 step
HumanDetectionAvail_68 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_68 MO Off(1)
HumanDetectionOperStatus_68 MI Off(1)
HumanDetectionWindCommand_68 MO Off(1)
HumanDetectionWindStatus_68 MI Off(1)
HumanDetectionTimeCommand_68 MO 5min(1)
HumanDetectionTimeStatus_68 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
68 ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_68 BO Stop(0) Start(1)
StartStopStatus_68 BI Stop(0) Start(1)
LockCommand_68 BO Permit(0) Prohibit(1)
LockStatus_68 BI Permit(0) Prohibit(1)
FilterSign_68 BI Off(0) On(1)
FilterSignReset_68 BV - Reset(1)
AirConModeCommand_68 MO Cool(1)
AirConModeStatus_68 MI Cool(1)
SwingCommand_68 BO Stop(0) Run(1)
SwingStatus_68 BI Stop(0) Run(1)
FanSpeedCommand_68 MO Low(1)
FanSpeedStatus_68 MI Low(1)
SetRoomTemp_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_68 AI ℃
Alarm_68 BI Normal(0) Abnormal(1)
MalfunctionCode_68 AI Refer to the
SetTempStatus_68 AI ℃
Accumulated power(100 Watt)_68 AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_68 AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_68 AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_68 AI ℃
TempRangeLowerLimitStatus_68 AI ℃
ModeLockCommand_68 BO Permit(0) Prohibit(1)
ModeLockStatus_68 BI Permit(0) Prohibit(1)
FanLockCommand_68 BO Permit(0) Prohibit(1)
FanLockStatus_68 BI Permit(0) Prohibit(1)
OccupancyCommand_68 BO Unoccupied(0) Occupied(1)
OccupancyStatus_68 BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_68 AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_68 AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_68 AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_68 AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_68 BI Off(0) On(1)
AccumulatedGas(100 Watt)_68 AI Wattage values (Unit : 100Watt)
DustSensorAvail_68 BI Disabled(0) Enabled(1)
AirCleaningOperCommand_68 BO Stop(0) Run(1)
AirCleaningOperStatus_68 BI Stop(0) Run(1)
FineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_68 AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_68 AI %
ComfortCoolingAvail_68 BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_68 BO Stop(0) Run(1)
ComfortCoolingOperStatus_68 BI Stop(0) Run(1)
ComfortCoolingStepCommand_68 AV 1~3 step
ComfortCoolingStepStatus_68 AI 1~3 step
HumanDetectionAvail_68 BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_68 MO Off(1)
HumanDetectionOperStatus_68 MI Off(1)
HumanDetectionWindCommand_68 MO Off(1)
HumanDetectionWindStatus_68 MI Off(1)
HumanDetectionTimeCommand_68 MO 5min(1)
HumanDetectionTimeStatus_68 MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
CC
c ※ Dev Type AC
address
instance
point Name
number
Unit
Object Name Object
Inactive Active
(XXX : Unit Address Number) Type
TEXT-0 TEXT-1
StartStopCommand_c BO Stop(0) Start(1)
StartStopStatus_c BI Stop(0) Start(1)
LockCommand_c BO Permit(0) Prohibit(1)
LockStatus_c BI Permit(0) Prohibit(1)
FilterSign_c BI Off(0) On(1)
FilterSignReset_c BV - Reset(1)
AirConModeCommand_c MO Cool(1)
AirConModeStatus_c MI Cool(1)
SwingCommand_c BO Stop(0) Run(1)
SwingStatus_c BI Stop(0) Run(1)
FanSpeedCommand_c MO Low(1)
FanSpeedStatus_c MI Low(1)
SetRoomTemp_c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
RoomTemp_c AI ℃
Alarm_c BI Normal(0) Abnormal(1)
MalfunctionCode_c AI Refer to the
SetTempStatus_c AI ℃
Accumulated power(100 Watt)_c AI Wattage values (Unit : 100Watt)
TempRangeUpperLimitCommand_c AV ℃ (18℃ ~ 30℃, 64℉ ~ 86℉)
TempRangeLowerLimitCommand_c AV ℃ (16℃ ~ 30℃, 60℉ ~ 86℉)
TempRangeUpperLimitStatus_c AI ℃
TempRangeLowerLimitStatus_c AI ℃
ModeLockCommand_c BO Permit(0) Prohibit(1)
ModeLockStatus_c BI Permit(0) Prohibit(1)
FanLockCommand_c BO Permit(0) Prohibit(1)
FanLockStatus_c BI Permit(0) Prohibit(1)
OccupancyCommand_c BO Unoccupied(0) Occupied(1)
OccupancyStatus_c BI Unoccupied(0) Occupied(1)
2SetCoolingTempCommand_c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingTempStatus_c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingTempCommand_c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingTempStatus_c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingUpperLimitCommand_c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingUpperLimitStatus_c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingUpperLimitCommand_c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingUpperLimitStatus_c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetCoolingLowerLimitCommand_c AV ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetCoolingLowerLimitStatus_c AI ℃ (10℃ ~ 37.5℃, 50℉ ~ 99℉)
2SetHeatingLowerLimitCommand_c AV ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
2SetHeatingLowerLimitStatus_c AI ℃ (4℃ ~ 32℃, 40℉ ~ 90℉)
ThermoStatus_c BI Off(0) On(1)
AccumulatedGas(100 Watt)_c AI Wattage values (Unit : 100Watt)
DustSensorAvail_c BI Disabled(0) Enabled(1)
AirCleaningOperCommand_c BO Stop(0) Run(1)
AirCleaningOperStatus_c BI Stop(0) Run(1)
FineDustStatus_c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
UltraFineDustStatus_c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
SuperUltraFineDustStatus_c AI ㎍/㎥ (219) : micrograms-per-cubic-meter
HumidityStatus_c AI %
ComfortCoolingAvail_c BI Disabled(0) Enabled(1)
ComfortCoolingOperCommand_c BO Stop(0) Run(1)
ComfortCoolingOperStatus_c BI Stop(0) Run(1)
ComfortCoolingStepCommand_c AV 1~3 step
ComfortCoolingStepStatus_c AI 1~3 step
HumanDetectionAvail_c BI Disabled(0) Enabled(1)
HumanDetectionOperCommand_c MO Off(1)
HumanDetectionOperStatus_c MI Off(1)
HumanDetectionWindCommand_c MO Off(1)
HumanDetectionWindStatus_c MI Off(1)
HumanDetectionTimeCommand_c MO 5min(1)
HumanDetectionTimeStatus_c MI 5min(1)
HotelCheckinCommand BO Check_out(0) Check_in(1)
HotelModeCommand MO Comfort(1)
TEXT-2 TEXT-3 TEXT-4 TEXT-5 TEXT-6
0Watt)
86℉)
86℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
~ 99℉)
~ 99℉)
0℉)
0℉)
0Watt)
Point 52-57 is available only when this point is Enabled.
-per-cubic-meter
-per-cubic-meter
-per-cubic-meter
Pre_comfort(2) Economy(3)
ACP BACnet v5.06.1
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4
ACS 5 v1.30.4 부재시간 설정(3bit) : 5(1), 10(2), 15(3), 30(0), 60(4), 90(5)
ACS 5 v1.30.4
ACS 5 v1.90.0
ACS 5 v1.90.0
BACnet ID 9040
MAC Addr.
IP address
SM
G/W