Professional Documents
Culture Documents
S M A RT E M P
S M A RT E M P
11.2013
Broad multiplex outlet BF-A
Preliminary remarks The high momentum air jets discharged by the nozzle
arrays remain largely discrete (fig 1) and are highly
The Broad Multiplex Outlet, type BF-A, is inductive, inducing both low momentum air jets discharged
a side-wall diffuser that provides high levels of by the fixed nozzles around the perimeter of the diffuser,
draught-free thermal comfort in such spaces and large quantities of room air, mixing these into the
as hotel rooms, apartments, restaurants and resultant air stream.
commercial offices. The patented design is both ae-
sthetically pleasing and technically advanced. Rapid temperature equalisation and intense discharge
velocity decay occur, bringing about low velocity air
Unlike standard side-blow air grilles, which motion with uniform temperature distribution throughout
produce broad, low momentum air bundles that mix the occupancy space.
poorly with room air, the Broad Multiplex Outlet
discharges a multitude of individual, high momentum The discharge direction of each nozzle array may be
air jets, each one of which is highly inductive. rotated via an Allen key inserted through the front face of
These produce largely UNIFORM temperature distribution the diffuser into the centre of each hexagonal nozzle plate
with low draught-risk throughout the occupancy (fig 3).
space. Thermal comfort levels are high even
when airflow rates are high. The Allen key shaft is aligned with the nozzle array axis
to act as a visual indicator of the nozzle array discharge
direction.
figure 1
Mode of operation
The draught-free air pattern from the diffuser has
adjustable throw, spread and discharge direction (up, down,
left and right) via the rotatable hexagonal nozzle plates (fig 2).
2
Broad multiplex outlet BF-A
Dimensions
Key
1 Mounting frame
2 Front face
3 Adjustable nozzles
4 Fixed nozzles
Design construction
The Broad Multiplex Outlet, type BF-A, consists
of an aluminium mounting frame 1 (which may optionally
be omitted, for frameless applications, or which is
optionally available in plastic to reduce the risk
of thermal bridging induced condensation in
the tropics) surrounding a perforated metal front plate 2,
behind which are located adjustable nozzles 3,
and fixed nozzles 4.
3
4
DN 950
V 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 320 340 360 380 400 L/s
1-row Pt 3 5 7 9 12 14 17 21 24 28 33 37 42 47 Pa
Airflow Tables
Key Throws
≤ 20 ≤ 30 ≤ 40 ≤ 50 Pa Green Yellow Orange Red
≤ 25 ≤ 30≤ 35 ≤ 40 NC* 3-6 m 4-7 m 5-8 m 6-9 m
* Based on 10 dB room absorption
Broad multiplex outlet BF-A
DN 1500
V 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 L/s
1-row Pt 4 6 7 8 9 11 13 14 16 18 21 23 25 28 30 33 36 39 42 45 48 52 Pa
Lp* < 5 < 5 7 10 13 15 17 19 21 23 25 26 28 30 31 32 34 35 36 37 38 39 NC
2-row Pt 4 5 6 6 7 8 9 10 12 13 14 15 17 18 20 21 23 25 26 30 34 38 43 47 Pa
Height Lp* <5 <5 6 8 10 12 14 16 17 19 20 22 23 24 26 27 28 29 30 32 34 36 38 39 NC
3-row Pt 4 5 6 6 7 8 8 9 10 11 12 13 14 15 16 18 21 23 26 29 32 35 38 41 45 Pa
Lp* <5 5 7 9 10 12 13 15 16 18 19 20 21 22 23 25 27 29 31 33 34 36 37 38 40 NC
4-row Pt 4 5 5 6 6 7 7 8 9 9 10 11 12 14 15 17 19 21 23 25 28 30 32 35 38 41 43 Pa
Lp* <5 5 6 8 9 11 12 13 14 16 17 18 20 22 24 25 27 29 30 32 33 34 35 37 38 39 40 NC
Broad multiplex outlet BF-A
5
Broad multiplex outlet BF-A
Number of rows
Nominal length
• Quiet operation – suitable for hotel rooms.
Colour
• Suitable for 3 to 9 m throws (airflow rate and discharge
direction dependent).
A galvanised perforated inlet plate is located upstream of Other colours available on request.
the nozzles.