Project : Mong Duong 2 CFPP O&M Manual Section-2 (1/7)

Plant : ECS Appendix-6 Kind of alarm, possible causes and remedial actions

Set
No. Kind of alarm Unit Possible causes Remedial actions
point

1) Supply source pressure dropped. 1) Check supply pressure level.


1 Instrument air supply pressure Low kg/cm2 2) Instrumrnt air supply valve closed. 2) Open supply valve more.
3) Leakage caused at piping/tubing joint(s). 3) Stop leakage at line joints.
1) Brine water injection FCV out of order. 1) Check FCV control loop to normalize.
3 Brine water supply flow Low Low 0.35 m3/h 2) Brine injection pump foot valve stuck. 2) Clean foot valve to move smoothly.
3) Brine injection pump outlet non returrn valve stuck. 3) Clean non return valve to swing properly.

1) P0PUS53CF001(FT) or P0PUS53CF501(FE) failed.


4 Brine water supply flow transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

1) Supply source conductivity dropped. 1) Check supply conductivity level.


6 Seawater supply conductivity Low Low µS/cm 2) Brine concentration reduced. (not saturated) 2) Put more salt into brine water pit.
3) Brine injection flow less. 3) Check brine water FCV control loop.
1) P0PUS53CQ001(AT) or P0PUS53CQ501(AE)
7 Seawater supply conductivity transmitter Fail - - failed. * Notify to I&C maintenance personnel.
2) Wire connection loosened.

1) Supply source pressure dropped. 1) Check supply pressure level.


8 Seawater supply pressure Low 0.3 kg/cm2
2) Seawater supply valve closed. 2) Open supply valve more.

1) P0PUS00CP001(PT) failed.
9 Seawater supply pressure transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

* See Section-3, 1. Stainless steel pump and 10. LV


10 Seawater booster pump A Fault - - 1) Drive motor over load (over current). motor trouble shooting.
1) Adjust outlet flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
11 Seawater booster pump A Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.
* See Section-3, 1. Stainless steel pump and 10. LV
12 Seawater booster pump B Fault - - 1) Drive motor over load (over current). motor trouble shooting.
1) Adjust outlet flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
13 Seawater booster pump B Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.
1) Instrument air not supplied to actuator.
* Notify to PLC maintenance personnel.
14 Potable water supply XV Sequence trouble - - 2) Signal command, but no feedback.
3) Check actuator movement.
3) Actuator troubled.

15 Brine water pit level High High - - 1) Potable water supply XV failed (not fully closed). 1) Repair or replace XV.

1) Potable water supply XV failed (not fully opened). 1) Repair or replace XV.
18 Brine water pit level Low Low - -
2) Potable water supply valve closed. 2) Open supply valve more.

* See Section-3, 6. Magnetic coupling pump and 10.


19 Brine injection pump A Fault - - 1) Drive motor over load (over current). LV motor trouble shooting.
1) Adjust outlet flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
20 Brine injection pump A Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.
* See Section-3, 6. Magnetic coupling pump and 10.
21 Brine injection pump B Fault - - 1) Drive motor over load (over current). LV motor trouble shooting.
1) Adjust outlet flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
22 Brine injection pump B Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.

Daiki Ataka Engineering Co., Ltd.


Project : Mong Duong 2 CFPP O&M Manual Section-2 (2/7)
Plant : ECS Appendix-6 Kind of alarm, possible causes and remedial actions

Set
No. Kind of alarm Unit Possible causes Remedial actions
point

23 Auto wash strainer A inlet XV Sequence trouble - - 1) Instrument air not supplied to actuator.
* Notify to PLC maintenance personnel.
2) Signal command, but no feedback.
3) Check actuator movement.
24 Auto wash strainer A blow XV Sequence trouble - - 3) Actuator troubled.

Auto wash strainer A differential pressure High


25 0.7 kg/cm2 1) Strainer element clogged with debris. 1) Clean strainer element.
High
2) Back washing not effective. 2) Check inner movements.
3) Strainer blow XV failed (not opened). 3) Check XV actuator.
26 Auto wash strainer A differential pressure High 0.5 kg/cm2

Auto wash strainer A differential pressure 1) P0PUS04CP001(PDT) failed.


27 - - * Notify to I&C maintenance personnel.
transmitter Fail 2) Wire connection loosened.

28 Auto wash strainer A Fault - - 1) Drive motor over load (over current). * See Section-3, 2. Seawater strainer trouble shooting.

1) Drive motor not started within time setup.


* Notify to PLC maintenance personnel.
29 Auto wash strainer A Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.

30 Auto wash strainer B inlet XV Sequence trouble - - 1) Instrument air not supplied to actuator.
* Notify to PLC maintenance personnel.
2) Signal command, but no feedback.
3) Check actuator movement.
31 Auto wash strainer B blow XV Sequence trouble - - 3) Actuator troubled.

Auto wash strainer B differential pressure High


32 0.7 kg/cm2 1) Strainer element clogged with debris. 1) Clean strainer element.
High
2) Back washing not effective. 2) Check inner movements.
3) Strainer blow XV failed (not opened). 3) Check XV actuator.
33 Auto wash strainer B differential pressure High 0.5 kg/cm2

Auto wash strainer B differential pressure 1) P0PUS04CP001(PDT) failed.


34 - - * Notify to I&C maintenance personnel.
transmitter Fail 2) Wire connection loosened.

35 Auto wash strainer B Fault - - 1) Drive motor over load (over current). * See Section-3, 2. Seawater strainer trouble shooting.

1) Drive motor not started within time setup.


* Notify to PLC maintenance personnel.
36 Auto wash strainer B Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.

37 Hypochlorite generator A inlet flow Low 17 m3/h 1) Electrolytic cells clogged with scale deposition. 1) Clean electrolytic cells with acid solution.
2) Seawater feed FCV out of order. 2) Check FCV actuator and positioner.
3) Seawater inlet valve closed. 3) Open seawater inlet valve.
38 Hypochlorite generator A inlet flow Low Low 13.5 m3/h 4) Hypochlorite outlet valve closed. 4) Open hypochlorite outlet valve.

1) P0PUS11CF001(FT) or P0PUS11CF501(FE) failed.


39 Hypochlorite generator A inlet flow transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

Daiki Ataka Engineering Co., Ltd.


Project : Mong Duong 2 CFPP O&M Manual Section-2 (3/7)
Plant : ECS Appendix-6 Kind of alarm, possible causes and remedial actions

Set
No. Kind of alarm Unit Possible causes Remedial actions
point

* Notify to electrical maintenance personnel.


1) DC output control unit failed (out of order).
40 Transformer/Rectifier A DC over current - - 1) Replace DC output control board.
2) Electrolytic cell electrode short-circuit.
2) Replace electrode assembly.

1) Cooling air flow unevenly, not effective. 1) Improve air flow around thyristors with baffle.
41 Transformer/Rectifier A thyristor temp. High - -
2) Cooling fan stopped. 2) Check fan motor circuit.

1) Drive motor over load (over current). 1) Check fan rotation smoothness, remove obstacls.
42 Transformer/Rectifier A cooling fan Tripped - -
2) Circuit-breaker opened. 2) Close circuit-breaker.

1) Ventilation air flow not effective. 1) Improve air flow with baffle.
43 Transformer/Rectifier A transformer temp. High - -
2) Ambient temperature rised too high. 2) Check ambient temperature to re-start.

1) Thyristor over current. 1) Replace faulty fuse.


44 Transformer/Rectifier A fuse Blowout - -
2) Protection fuse failed. 2) Reset fault indicator (microswitch).

1) Line voltage dropped. 1) Check circuit supply voltage level.


45 Transformer/Rectifier A synchronized power Fail - -
2) Circuit-breaker opened. 2) Close circuit-breaker.

1) 400 V line under-voltage. 1) Check auxiliary supply circuit voltage level.


46 Transformer/Rectifier A auxiliary power Fail - -
2) Circuit-breaker Q11.1 opened. 2) Close circuit-breaker.

47 Transformer/Rectifier A Common fault - - 1) Protection relay(s) activated. * Notify to electrical maintenance personnel.

1) Cooling air flow reduced. 1) Check fan rotation smoothness, remove obstacls.
48 Transformer/Rectifier A cubicle temp. High - -
2) Ambient temperature rised too high. 2) Check ambient temperature to re-start.

49 Transformer/Rectifier A Sequence trouble - - 1) On/Off command, but no feedback. * Notify to I&C maintenance personnel.

1) Analog signal lost.


50 Transformer/Rectifier A voltage transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

1) Analog signal lost.


51 Transformer/Rectifier A current transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

52 Hypochlorite generator A cell 1 voltage High High 57.5 V 1) Electrolytic cell clogged with scale deposition. 1) Clean electrolytic cell with acid solution.
2) Seawater conductivity reduced. 2) Increase brine injection flow.
53 Hypochlorite generator A cell 1 voltage High 50 V 3) Electrode coating deteriorated. 3) Replace electrode assembly.

Hypochlorite generator A cell 1 voltage convertor 1) Analog signal lost.


54 - - * Notify to I&C maintenance personnel.
Fail 2) Wire connection loosened.

55 Hypochlorite generator A cell 2 voltage High High 57.5 V 1) Electrolytic cell clogged with scale deposition. 1) Clean electrolytic cell with acid solution.
2) Seawater conductivity reduced. 2) Increase brine injection flow.
56 Hypochlorite generator A cell 2 voltage High 50 V 3) Electrode coating deteriorated. 3) Replace electrode assembly.

Hypochlorite generator A cell 2 voltage convertor 1) Analog signal lost.


57 - - * Notify to I&C maintenance personnel.
Fail 2) Wire connection loosened.

58 Hypochlorite generator A cell 3 voltage High High 57.5 V 1) Electrolytic cell clogged with scale deposition. 1) Clean electrolytic cell with acid solution.
2) Seawater conductivity reduced. 2) Increase brine injection flow.
3) Electrode coating deteriorated. 3) Replace electrode assembly.
59 Hypochlorite generator A cell 3 voltage High 50 V 4) Hydrogen gas not released from separator. 4) Clean degassing valve of hydrogen separator.

Hypochlorite generator A cell 3 voltage convertor 1) Analog signal lost.


60 - - * Notify to I&C maintenance personnel.
Fail 2) Wire connection loosened.

61 Hypochlorite generator A cell 4 voltage High High 57.5 V 1) Electrolytic cell clogged with scale deposition. 1) Clean electrolytic cell with acid solution.
2) Seawater conductivity reduced. 2) Increase brine injection flow.
3) Electrode coating deteriorated. 3) Replace electrode assembly.
62 Hypochlorite generator A cell 4 voltage High 50 V 4) Hydrogen gas not released from separator. 4) Clean degassing valve of hydrogen separator.

Hypochlorite generator A cell 4 voltage convertor 1) Analog signal lost.


63 - - * Notify to I&C maintenance personnel.
Fail 2) Wire connection loosened.

Daiki Ataka Engineering Co., Ltd.


Project : Mong Duong 2 CFPP O&M Manual Section-2 (4/7)
Plant : ECS Appendix-6 Kind of alarm, possible causes and remedial actions

Set
No. Kind of alarm Unit Possible causes Remedial actions
point

64 Hypochlorite generator B inlet flow Low 17 m3/h 1) Electrolytic cells clogged with scale deposition. 1) Clean electrolytic cells with acid solution.
2) Seawater feed FCV out of order. 2) Check FCV actuator and positioner.
3) Seawater inlet valve closed. 3) Open seawater inlet valve.
65 Hypochlorite generator B inlet flow Low Low 13.5 m3/h 4) Hypochlorite outlet valve closed. 4) Open hypochlorite outlet valve.

66 Hypochlorite generator B inlet flow transmitter Fail - - 1) P0PUS11CF001(FT) or P0PUS11CF501(FE) failed. * Notify to I&C maintenance personnel.

* Notify to electrical maintenance personnel.


1) DC output control unit failed (out of order).
67 Transformer/Rectifier B DC over current - - 1) Replace DC output control board.
2) Electrolytic cell electrode short-circuit.
2) Replace electrode assembly.

1) Cooling air flow unevenly, not effective. 1) Improve air flow around thyristors with baffle.
68 Transformer/Rectifier B thyristor temp. High - -
2) Cooling fan stopped. 2) Check fan motor circuit.

1) Drive motor over load (over current). 1) Check fan rotation smoothness, remove obstacls.
69 Transformer/Rectifier B cooling fan Tripped - -
2) Circuit-breaker opened. 2) Close circuit-breaker.

1) Ventilation air flow not effective. 1) Improve air flow with baffle.
70 Transformer/Rectifier B transformer temp. High - -
2) Ambient temperature rised too high. 2) Check ambient temperature to re-start.

1) Thyristor over current. 1) Replace faulty fuse.


71 Transformer/Rectifier B fuse Blowout - -
2) Protection fuse failed. 2) Reset fault indicator (microswitch).

1) Line voltage dropped. 1) Check circuit supply voltage level.


72 Transformer/Rectifier B synchronized power Fail - -
2) Circuit-breaker opened. 2) Close circuit-breaker.

1) 400 V line under-voltage. 1) Check auxiliary supply circuit voltage level.


73 Transformer/Rectifier B auxiliary power Fail - -
2) Circuit-breaker Q11.1 opened. 2) Close circuit-breaker.

74 Transformer/Rectifier B Common fault - - 1) Protection relay(s) activated. * Notify to electrical maintenance personnel.

1) Thyristor overload. 1) Check fan rotation smoothness, remove obstacls.


75 Transformer/Rectifier B cubicle temp. High - -
2) Ambient temperature rised too high. 2) Check ambient temperature to re-start.

76 Transformer/Rectifier B Sequence trouble - - 1) On/Off command, but no feedback. * Notify to I&C maintenance personnel.

1) Analog signal lost.


77 Transformer/Rectifier B voltage transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

1) Analog signal lost.


78 Transformer/Rectifier B current transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

79 Hypochlorite generator B cell 1 voltage High High 57.5 V 1) Electrolytic cell clogged with scale deposition. 1) Clean electrolytic cell with acid solution.
2) Seawater conductivity reduced. 2) Increase brine injection flow.
80 Hypochlorite generator B cell 1 voltage High 50 V 3) Electrode coating deteriorated. 3) Replace electrode assembly.

Hypochlorite generator B cell 1 voltage convertor 1) Analog signal lost.


81 - - * Notify to I&C maintenance personnel.
Fail 2) Wire connection loosened.

82 Hypochlorite generator B cell 2 voltage High High 57.5 V 1) Electrolytic cell clogged with scale deposition. 1) Clean electrolytic cell with acid solution.
2) Seawater conductivity reduced. 2) Increase brine injection flow.
83 Hypochlorite generator B cell 2 voltage High 50 V 3) Electrode coating deteriorated. 3) Replace electrode assembly.

Hypochlorite generator B cell 2 voltage convertor 1) Analog signal lost.


84 - - * Notify to I&C maintenance personnel.
Fail 2) Wire connection loosened.

85 Hypochlorite generator B cell 3 voltage High High 57.5 V 1) Electrolytic cell clogged with scale deposition. 1) Clean electrolytic cell with acid solution.
2) Seawater conductivity reduced. 2) Increase brine injection flow.
3) Electrode coating deteriorated. 3) Replace electrode assembly.
86 Hypochlorite generator B cell 3 voltage High 50 V 4) Hydrogen gas not released from separator. 4) Clean degassing valve of hydrogen separator.

Hypochlorite generator B cell 3 voltage convertor 1) Analog signal lost.


87 - - * Notify to I&C maintenance personnel.
Fail 2) Wire connection loosened.

88 Hypochlorite generator B cell 4 voltage High High 57.5 V 1) Electrolytic cell clogged with scale deposition. 1) Clean electrolytic cell with acid solution.
2) Seawater conductivity reduced. 2) Increase brine injection flow.
3) Electrode coating deteriorated. 3) Replace electrode assembly.
89 Hypochlorite generator B cell 4 voltage High 50 V 4) Hydrogen gas not released from separator. 4) Clean degassing valve of hydrogen separator.

Hypochlorite generator B cell 4 voltage convertor 1) Analog signal lost.


90 - - * Notify to I&C maintenance personnel.
Fail 2) Wire connection loosened.

Daiki Ataka Engineering Co., Ltd.


Project : Mong Duong 2 CFPP O&M Manual Section-2 (5/7)
Plant : ECS Appendix-6 Kind of alarm, possible causes and remedial actions

Set
No. Kind of alarm Unit Possible causes Remedial actions
point

91 H2 gas concentration High High 25 % LEL


1) Stop leakage at hypochlorite line flange connection.
1) Hydrogen leakage caused in mechanical room.
2) Close hypochlorite sampling valve.
92 H2 gas concentration High 10 % LEL

1) P0PUS10CA001(AT) or P0PUS10CA501(AE)
93 H2 gas detector transmitter Fail - - failed. * Notify to I&C maintenance personnel.
2) Wire connection loosened.

Hypochlorite solution storage tank A level High 1) Continuous dosing valve closed. 1) Open continuous dosing valve.
94 9,160 mm
High High 2) Continuous dosing FCV out of order (not opened). 2) Check continuous FCV actuator and positioner.
3) Shock dosing valve closed. 3) Open shock dosing valve.
Hypochlorite solution storage tank A level High
95 8,960 mm 4) Shock dosing FCV out of order (not opened). 4) Check shock FCV actuator and positioner.
High

98 Hypochlorite solution storage tank A level Low Low 500 mm 1) Hypochlorite inlet valve closed. 1) Open hypochlorite inlet valve.
2) Continuous dosing FCV out of order (not closed). 2) Check continuous FCV actuator and positioner.
Hypochlorite solution storage tank A level Low Low 3) Shock dosing FCV out of order (not closed). 3) Check shock FCV actuator and positioner.
99 300 mm
Low

Hypochlorite solution storage tank A level 1) P0PUS21CL001(LT) failed.


100 - - * Notify to I&C maintenance personnel.
transmitter Fail 2) Wire connection loosened.

Hypochlorite solution storage tank B level High 1) Continuous dosing valve closed. 1) Open continuous dosing valve.
101 9,160 mm
High High 2) Continuous dosing FCV out of order (not opened). 2) Check continuous FCV actuator and positioner.
3) Shock dosing valve closed. 3) Open shock dosing valve.
Hypochlorite solution storage tank B level High
102 8,960 mm 4) Shock dosing FCV out of order (not opened). 4) Check shock FCV actuator and positioner.
High

105 Hypochlorite solution storage tank B level Low Low 500 mm 1) Hypochlorite inlet valve closed. 1) Open hypochlorite inlet valve.
2) Continuous dosing FCV out of order (not closed). 2) Check continuous FCV actuator and positioner.
Hypochlorite solution storage tank B level Low Low 3) Shock dosing FCV out of order (not closed). 3) Check shock FCV actuator and positioner.
106 300 mm
Low

Hypochlorite solution storage tank B level 1) P0PUS22CL001(LT) failed.


107 - - * Notify to I&C maintenance personnel.
transmitter Fail 2) Wire connection loosened.

Hypochlorite solution storage tank dike sump pit 1) Leakage caused at hypochlorite tank. 1) Stop ECS operation.
108 - -
level High 2) Overflow from hypochlorite tank. 2) Neutralize to discharge into neutrarized water pit.

* See Section-3, 4. Air blower and 10. LV motor


109 Air blower A Fault - - 1) Drive motor over load (over current). trouble shooting.
1) Adjust air flow at rated or less.

1) Suction filter clogged with debris. 1) Clean suction filter.


110 Air blower A flow Fault - -
2) Outlet non return damper stuck. 2) Clean non return damper to swing properly.

1) Drive motor not started within time setup.


* Notify to PLC maintenance personnel.
111 Air blower A Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.
* See Section-3, 4. Air blower and 10. LV motor
112 Air blower B Fault - - 1) Drive motor over load (over current). trouble shooting.
1) Adjust air flow at rated or less.

1) Suction filter clogged with debris. 1) Clean suction filter.


113 Air blower B flow Fault - -
2) Outlet non return damper stuck. 2) Clean non return damper to swing properly.

1) Drive motor not started within time setup.


* Notify to PLC maintenance personnel.
114 Air blower B Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.
1) Open air blower outlet valve.
115 Dilution air flow Low 5,610 Nm3/h 1) Air blower outlet valve closed.
2) Clean blower outlet non return valve to swing
2) Air blower outlet non return valve stuck.
properly.
116 Dilution air flow Low Low 4,950 Nm3/h 3) Hypochlorite tank inlet damper closed. 3) Open hypochlorite tank inlet damper.

1) P0PUS25CF001(FT) or P0PUS25CF501(FE) failed.


117 Dilution air flow transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

Daiki Ataka Engineering Co., Ltd.


Project : Mong Duong 2 CFPP O&M Manual Section-2 (6/7)
Plant : ECS Appendix-6 Kind of alarm, possible causes and remedial actions

Set
No. Kind of alarm Unit Possible causes Remedial actions
point

* See Section-3, 5. FRP pump and 10. LV motor


118 Continuous dosing pump A Fault - - 1) Drive motor over load (over current). trouble shooting.
1) Adjust dosing flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
119 Continuous dosing pump A Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.
* See Section-3, 5. FRP pump and 10. LV motor
120 Continuous dosing pump B Fault - - 1) Drive motor over load (over current). trouble shooting.
1) Adjust dosing flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
121 Continuous dosing pump B Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.

122 Continuous dosing flow Low 15.5 m3/h


1) Continuous dosing valve closed. 1) Open continuous dosing valve.
2) Continuous dosing FCV out of order (not opened). 2) Check dosing FCV actuator and positioner.
123 Continuous dosing flow Low Low 6.2 m3/h

1) P0PUS33CF001(FT) or P0PUS33CF501(FE) failed.


124 Continuous dosing flow transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

* See Section-3, 5. FRP pump and 10. LV motor


125 Shock dosing pump A Fault - - 1) Drive motor over load (over current). trouble shooting.
1) Adjust dosing flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
126 Shock dosing pump A Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.
* See Section-3, 5. FRP pump and 10. LV motor
127 Shock dosing pump B Fault - - 1) Drive motor over load (over current). trouble shooting.
1) Adjust dosing flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
128 Shock dosing pump B Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.

129 Shock dosing flow Low 155 m3/h


1) Shock dosing valve closed. 1) Open shock dosing valve.
2) Shock dosing FCV out of order (not opened). 2) Check dosing FCV actuator and positioner.
130 Shock dosing flow Low Low 62 m3/h

1) P0PUS43CF001(FT) or P0PUS43CF501(FE) failed.


131 Shock dosing flow transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

1) Potable water feed valve not closed. 1) Close potable water feed valve.
132 Acid solution tank level High High 2,900 mm
2) Seawater passing from hypochlorite generator. 2) Check valves in acid cleaning pipe line.

1) Drain valve not closed. 1) Close drain valve.


134 Acid solution tank level Low 200 mm
2) Leakage caused at acid pipe flange connection. 2) Check leakage at acid pipe line and stop it.

1) P0PUS80CL001(LT) failed.
135 Acid solution tank level transmitter Fail - - * Notify to I&C maintenance personnel.
2) Wire connection loosened.

* See Section-3, 5. FRP pump and 10. LV motor


136 Acid cleaning pump A Fault - - 1) Drive motor over load (over current). trouble shooting.
1) Adjust acid flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
137 Acid cleaning pump A Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.
* See Section-3, 5. FRP pump and 10. LV motor
138 Acid cleaning pump B Fault - - 1) Drive motor over load (over current). trouble shooting.
1) Adjust acid flow at rated or less.
1) Drive motor not started within time setup.
* Notify to PLC maintenance personnel.
139 Acid cleaning pump B Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.

Daiki Ataka Engineering Co., Ltd.


Project : Mong Duong 2 CFPP O&M Manual Section-2 (7/7)
Plant : ECS Appendix-6 Kind of alarm, possible causes and remedial actions

Set
No. Kind of alarm Unit Possible causes Remedial actions
point

* See Section-3, 7. Submerge pump trouble shooting.


140 Neutralized water transfer pump A Fault - - 1) Drive motor over load (over current).
1) Adjust discharge flow at rated or less.

1) Drive motor not started within time setup.


Neutralized water transfer pump A Sequence * Notify to PLC maintenance personnel.
141 - - 2) Command signal to MCC failed.
trouble 3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.

* See Section-3, 7. Submerge pump trouble shooting.


142 Neutralized water transfer pump B Fault - - 1) Drive motor over load (over current).
1) Adjust discharge flow at rated or less.

1) Drive motor not started within time setup.


* Notify to PLC maintenance personnel.
143 Neutralized water transfer pump B Sequence trouble - - 2) Command signal to MCC failed.
3) See Section-3, 9. MCC trouble shooting.
3) MCC starter unit troubled.

1) Transfer pump outlet valve closed. 1) Open transfer pump outlet valve.
144 Neutralized water pit level High High - -
2) Transfer pump outlet non return valve stuck. 2) Clean non return valve to swing properly.

147 Neutralized water pit level Low Low - - 1) Embedded pipe clogged with debris. 1) Clean embedded pipes.

148 Neutralized water pit pH High pH 1) Caustic soda mixed in oversupply. 1) Add hydrochloric acid to reduce pH.

149 Neutralized water pit pH Low pH 1) Caustic soda mixed in undersupply. 1) Add caustic soda to increase pH.

1) P0PUS90CA001(AT) or P0PUS90CA501 (AE)


150 Neutralized water pit pH transmitter Fail - - failed. * Notify to I&C maintenance personnel.
2) Wire connection loosened.
1) Supply source pressure dropped. 1) Check supply pressure level.
155 Potable water supply pressure Low - - 2) Potable water supply valve closed. 2) Open supply valve more.
3) Leakage caused at piping joint(s). 3) Stop leakage at line joints.

157 Emergency stop - - 1) Emergency stop button on PLC panel operated. 1) Reset push button to restart.

1) Circuit-breaker opened.
158 Control power failure (Major) power Fail (Major) - - * Notify to electrical maintenance personnel.
2) Wire connection loosened.

1) Circuit-breaker opened.
159 Control power failure (Minor) power Fail (Minor) - - * Notify to electrical maintenance personnel.
2) Wire connection loosened.

1) Circuit-breaker opened.
160 DC24V Power supply A power Fail - - * Notify to electrical maintenance personnel.
2) Wire connection loosened.

1) Circuit-breaker opened.
161 DC24V Power supply B power Fail - - * Notify to electrical maintenance personnel.
2) Wire connection loosened.

1) Circuit-breaker opened.
162 Auxiliary power failure power Fail - - * Notify to electrical maintenance personnel.
2) Wire connection loosened.

163 PLC A Trouble - - 1) PLC A failed. (self diagnosis) * Notify to PLC maintenance personnel.

164 PLC B Trouble - - 1) PLC B failed. (self diagnosis) * Notify to PLC maintenance personnel.

165 Electrolytic chlorination system Major FLT - - 1) Trip fault occurred. * Notify to process engineering personnel.

166 Electrolytic chlorination system Minor FLT - - 1) Non trip failure occurred. * Notify to process engineering personnel.

167 PLC Fault - - 1) PLC failed. (self diagnosis) * Notify to PLC maintenance personnel.

168 Safety shower and eye washer - - 1) Safety shower and eye washer in service. * Indication only, no action required.