CoSy Radio

Installation and User Manual UK

1. Electronic roomthermostat Contact

Application
The electronic thermostat regulates the air temperature in dry closed rooms.
Wirsbo
SPACE HOUSE, SATELLITE BUSINESS VILLAGE
Function CRAWLEY, WEST SUSSEX RH10 2NE
The internal sensor registers the actual temperature. Turning the dial sets the required temperature. Phone 01293 548512 • Fax 01293 548552
If the actual temperature is below the required temperature, an electronic switch connects and signals wirsboenquiries@uponor.co.uk • www.wirsbo.co.uk
to the UFH system that heat is required. A green light diode (seen from the side of the thermostat)
shows that heat is required.

2. Operating

30
Min. 35

30 35
25 40

Max 25 40
20 45
20 45

2 3 4 5 6 11 12 2 3 4 5 6 11 12
Min./ max.
limits

Select temperature Setting minimum/ maximum tem- Setting the night set-back Setting max temperature
• The temperature is set by rature • Position “SUN” => normal => • Setting max. temperature is
turning the dial • Remove the dial no temperature set-back typically used to prevent
• Longer strokes indicate higher • Press and turn the right pin to Manual set-back overheating of wooden floors.
temperature adjust the minimum tempera • Position “MOON” => night set- • Connect the external sensor to
• Shorter strokes indicate lower ture setting. back => 4°C set-back at 20°C terminal 11 and 12
temperature • Press and turn the left pin Important • The switch must be in position
• Long thin stroke in the middle of to adjust the maximum tempe Works only if terminal 4 and 5 “max”
the dial indicates approx. 21°C rature setting. are connected inside the thermostat. • The temperature is set by a pot
• Starting point 21°C (shown as With manual night setback it is not meter - see the above figure.
0 on the scale). necessary to connect terminal 5.
Important • Replace the dial. The amount Setting min. temperature
If thermostat with night setback and the thermostat can be Timer controlled set-back • Setting of min. temperature is
extern sensor is used, but the exter- adjusted is now limited. • Position “MOON” => time typically used to ensure tile
nal sensor is not installed, the switch • Factory pre-set values: controlled night setback floors in kitchen and bathrooms
minimum/ maximum must be positio- Minimum temperature 6°C. Important always are warm.
ned “normal” Maximum temperature 30°C. Works only if timer module is instal- • Connect the external sensor to
led in the connection box, and termi- connector 11 and 12
Additional accessories: Example: If 14°C is required to be nal 5 in thermostat is connected to • The switch must be in position
1) External sensor (only available the minimum temperature setting, the wiring box. “min”
for thermostat with night the right “leg” is turned to position -7 • The temperature is set by a pot
setback), art. no. 080463 = (21°C - 7°C). If 26°C is required meter - see the above figure
2) Timermodule for night setback/ as the maximum temperature set-
holiday setback (only available ting, the left “leg” is turned to position
for thermostat with night set 5 = (21°C + 5°C).
back), art no. 080462
3. Mounting

Fig. 1 Fig. 2 Fig. 3

30 35

25 40

20 45

2 3 4 5 6 11 12

Push 60 mm
• Disassemble the dial from the ther- • Then demount the thermostat front • The thermostat can be fixed to the wall.
mostat by pressing in the button with a • Max. screw size ø3,0 mm.
screwdriver
• Lift off the front.
4. Connection box

Fig. 1
Wiring diagram 24V

4 3 3 2 4 5 5 4 2 3 3 4

4 3 3 2 4 5 5 4 2 3 3 4

4 3 3 2 4 5 5 4 2 3 3 4
2 3 4 5 6 11 12
! 24 V
L (2)
N (4)

Optional

RT24 out → Box in


Terminal 2 → Phase 24V → Terminal 2 L
230V
Terminal 3 → Switched phase → Terminal 3 N
Terminal 4 → Neutral 24V → Terminal 4
Terminal 5 → Timer clock → Terminal 5
Terminal 6 → Optional Fig. 2

4 3 3 2 4 5 5 4 2 3 3 4

4 3 3 2 4 5 5 4 2 3 3 4

4 3 3 2 4 5 5 4 2 3 3 4
Terminal 11 → Connection for external sensor Connecting the ther-
Terminal 12 → Connection for external sensor mostats
a) Connection of
CoSy Basic
5. Types of Thermostats thermostat
b) Connection of a
thermostat with
30 35 timer control on
25 40
channel 1
20 45
c) Connection of a
a. b. c. thermostat with
timer control of
2 3 4 2 3 4 5 6 11 12 channel 2

Fig. 3
CoSy Basic (Art. no. 080466) Connecting one
4 3 3 2 4 5 5 4 2 3 3 4

4 3 3 2 4 5 5 4 2 3 3 4

4 3 3 2 4 5 5 4 2 3 3 4
• Without night setback CoSy Switch (Art. no. 080465)
thermostat to
• With night setback by timer
two actuators.
module or switch. External
sensor with min./max. limiter.
30 35

25 40
• External sensor, art. no. 080463
20 45

2 3 4 5 6 11 12

CoSy Public (Art. no. 080464)


• With night setback by timer module or
switch. External sensor with min./max.
limiter.
• No temperature regulation on front of
thermostat

6. Technical Data
Thermostat Min/max voltage: ................................. +/- 10% => 207 - 253 VAC
Temperature range: ............................ 6 to 30°C Connector type: .................................. Two pole ED500-P02 (Dinkle)
Colour: ................................................ RAL 9010 Note:
Voltage: ............................................... 19-30V AC, 50-60 Hz No cord and plug is delivered with the baseunit
Max. current (I-max): ........................... 2,5A
Led function: ....................................... ON, when call for heat Connection for actuators
Hysteresis: .......................................... 1°C @ 20°C Number of outputs/connections: ......... 12 (pair wise parallel)
Night setback: ..................................... 4°C drop @ 20°C (20° to 16° C) Voltage: ............................................... 24V
Core: ................................................... Min = 0,75 mm2 (AVG 18); Connector type: .................................. Screw terminals
............................................................. Max = 2,0 mm2 (AVG 14) Actuator type: ..................................... 24V, normally Closed
Thermostats connections (24V): ......... 12
Connection for Pump
Connection for Mains Output type: ........................................ Dry contact relay (optional)
Voltage: ............................................... 230VAC Max current: ........................................ 5 Amp AC