Classification: Public Uncontrolled if printed Rev: 1.0
primary power and as well as the number and type of secondary power
sources.
4.10.1.4 The feeders leaving the LVAC board should be split into essential and non-
essential circuits. This will ensure that power is maintained during fault
conditions as far as possible to the essential equipment reliant on LVAC
supplies.
4.10.1.6 The LVAC systems should be labelled clearly, consistently and in line with the
Owner’s preference.
4.10.2 Batteries
4.10.2.2 Batteries may be used as a secondary power supply to the LVAC board. If
this is the case they will need to be charged continually from the LVAC board.
The battery bank should be sized to meet the needs of the essential LVAC
outgoing feeders for a specified period of time. It is at the Owner’s discretion
the size and the operational characteristics of the batteries.
4.10.2.3 Batteries can also be installed to meet the needs of the communication
systems, normally 110V and 48V DC supplies. There is an option to optimise
the necessary battery system if a single DC supply voltage can be agreed.
4.10.2.4 Any room were batteries are stored in banks should also contain a ventilation
system to maintain the temperature within the manufactures recommended
range and prevent any dangerous gas being stored within its atmosphere.
4.10.2.5 The batteries should be labelled clearly, consistently and in line with the
Owner’s preference.
4.11.1 Permanent welfare provisions should be assessed against the projected maintenance
requirements and at the Owner’s discretion.
4.11.2 Where welfare elements such as a mess room are not included, alternative arrangements
should be provided when personnel are present for longer periods of time.
4.11.3 When required, hardstanding area suitable for portable welfare cabins should be included.
Ideally adjacent to the roadway facilitating delivery/pickup.
4.12.1 A generator module may or may not be required; it is at the Owner’s discretion.
4.12.2 If a generator is required, it should be sized correctly to meet the required LVAC power
needs.