Linear Input: -9990~+30000 units defined by user. The parameters of AI-7021D5 can be set by an external E8 display AI-7021 DUAL TEMPERATURE ● Retransmission accuracy : 0.3%FS ± 1 digit (including input which can be used to configure AI-7021D5 at the initial set up, as TRANSMITTER / SIGNAL ISOLATOR and output error) well as remain connected to AI-7021D5 and serves as an external ● Output Specification: can be freely defined in the range of display. Operation Instruction 0~22mA with maximum output voltage ≥ 11V ● Temperature drift : ≤ 0.015%FS /℃ (including the temperature drift of input and output) ● Electromagnetic compatibility (EMC) : ±4KV/5KHz according ① to IEC61000-4-4 (EFT); 4KV according to IEC61000-4-5. ② ● Isolation withstanding voltage : voltage between power, signal input and output terminals ≥ 2300VDC; between inputs or 2 outputs ≥ 200VDC ③ ④ ● Power supply : ⑤ ⑥ 100~240VAC, -15%, +10% / 50Hz; or 24VDC/AC. ● Power consumption: ≤ 3W 1.SUMMARY ● Operating Ambient : Temperature -10~+60℃ ; AI-7021 acts as a dual channel transmitter or signal isolator. humidity ≤ 90%RH The functions of the parts of E8 external display panel is as below: ● It provides 2 channels of programmable inputs, supporting Note1: B thermocouple obtains the above measurement accuracy ① Upper display window, displays PV of channel 1 or parameter multiple voltage, RTD, thermocouple inputs with auto reference only at the range of 400~1800 ℃ . Its measurement from code, etc. when display keep flashing or the reading abnormal, junction compensation. If parallel connected to an exter- 60~400℃ . is less accurate. please check the input specification set correct or not. nal precise resistance, it accepts current signal input. Each ② Lower display window, displays PV of channel 2 or parameter channel has independent digital filter and can adjust its fil- 3.LAYOUT OF TERMINALS AND INDICATION LIGHTS value. When display keep flashing or the reading abnormal, tering degree. AND WIRING please check the input specification set correct or not. ● It generates two isolated current outputs, 4~20mA or 0~20mA. Layout of AI-7021D5 indication lights and terminals is illustrated ③ Setup key, for accessing parameter table and conforming The range of retransmission output can be freely defined. below: parameter modification. ● This model uses high performance hardware, which leads to Terminal 1 and 2 are for power supply of 100-240 ④ Data shift key. greatly decreased temperature drift and interference among 100-240VAC or 24VAC/DC. VAC~ ⑤ Data decrease key 1 2 3 4 the two channels. As a result, this multi-channel instrument Terminal 5 and 6 are the positive and negative 5 6 7 8 ⑥ Data increase key. achieves the same measurement accuracy and anti-interference pole of channel 1 current retransmission + OP1 - + OP2 - Note: The 1394 socket of the instrument only supports Yudian E8 ability as that of single channel instrument. output. UDIAN display. ● It generates digital adjusted current output without potentiometer, Terminal 7 and 8 are the positive and negative MODE
making the current output precise and stable. AI-7021
pole of channel 2 current retransmission OP1 Operation Instructions: ● The model is DIN rail mounted. Its width is only 22.5mm. output. The instrument can be easily configured by connecting to Terminal 14~16 are for channel 1 input. OP2 Setting parameters: our E8 external display. Terminal 10~12 are for channel 2 input. When the parameter lock “Loc” isn't locked, pressing ● Universal power supply of 100-240VAC or 24VDC. and holding for about 2 secondswill bring up the full parameter ● ISO9001 and CE certified and meets EMC standards. Its Indication light OP1~OP2: indicate the power and all I/O terminals pass 4KV/5KHz EFT test and IN2 - table. Pressing will bring up the parameters one by one. outputs of channel 1 and 2. The luminosity + can work reliably under interference. of the light indicates the magnitude of the 9 10 11 12 Press , or to modify the value of a parameter. 13 14 15 16 output. IN1 Pressing and holding will return to the preceding parameter. 2.TECHNICAL SPECIFICATION ● Input type: Pressing and holding and at the same time press key Indication light--- MODE: will get out of the parameter table. Thermocouple: K, S, R, E, J, T, B, N, WRe5-WRe26 When the light flickers even faster, at a rate of once every 0.3 RTD:Pt100, Cu50 second, it indicates severe errors such as input exceeding its When the parameter lock “Loc” is locked, pressing will Linear voltage: 0~20mV, 0~60mV, 0~100mV, 0~1V, 0.2~1V etc. acceptable range. bring up field parameter table which just shown INPx, SCLx and ● Instrument Input range When the light is off, it indicates that the instrument has no SCHx from display and can’t modify. K(-50~+1300℃ ), S(-50~+1700℃ ), R(-50~+1700℃ ), power or it is out of order. When the light is on (for at least The instrument will automatically leave the parameter table if no T(-200~+350℃ ), E(0~1000℃ ), J(0~1200℃ ), longer than 8 seconds), it indicates that the instrument has key is pressed in the past 25 seconds, and the change of the last B(0~1800℃ ), N(-50~+1300℃ ), WRe5-WRe26(0~2300℃ ), power on but is out of order. parameter will not be saved. 5.SETTING PARAMETERS Scb is used to shift input Define the low limit and x means channel number. It can be 1~2. to compensate the error Low limit high limit of current caused by transducer, of current retransmission of channel Setting OPL2 0~100 Parameter Name Remarks input signal, or auto cold retransmission 2. The engineering unit is range junction compensation of of Channel 2 0.1mA. Define the input specification thermocouple. For example, to retransmit of channel 1~ 2. PV_after_compensation= 0~1000℃ in input channel PV_before_compensation + High limit 2 to 4~20mA, then the -199~+999.0 INP Input spec. Scbx Input offset Scb of current parameter should be units or 0.1℃ OPH2 0~220 For thermocouple or three- retransmission set as below: SCL1=0, 0 K wire RTD inputs, the units of of Channel 2 SCH1=1000, OPn=1, Sc is 0.1℃ . For example, OPL=40, OPH=200. 1 S when Scb= -100, the actual offset= -10℃ , For adjusting the current of 2 R OP1 output. The greater then the measured OP1 current 3 T temperature will be 10℃ IVF1, the greater current correction lower than that when Scb=0. output. 0~3000 4 E IVF1 (Please record Note: This parameter was Default=(__) The value of FIL will the value when 5 J determine the ability of adjusted before delivery. It first use) is better not to change this filtering noise. 6 B value by yourself. FIL=0, no filtering; 7 N FIL=1, filtering with mean; For adjusting the current of OP2 current OP2 output. The greater 8 WRe3-WRe25 FIL=2~40, filtering with mean and integral. IVF1, the greater current correction output. 0~3000 Input 9 WRe5-WRe26 When a large value is set, IVF2 (Please record INPx 0 ~ 32 Note: This parameter was Default=(__) specification the measurement input is the value when Extended input stabilized but the response adjusted before delivery. It 10 first use) is better not to change this spec. FILx Digital filter speed is slow. Generally, it 0~40 can be set to 1 to 3. value by yourself. 11~19 Spare If great interference exists, Loc=808, allow to display then you can increase and modify all parameters. 20 Cu50 parameter FIL gradually to 21 Pt100 make momentary fluctuation Loc Parameter Lock Otherwise, all parameters 0 ~9999 of measured value less than can’t be modify and which 22~24 Spare 2 to 5. just shown INPx, SCLx and SCHx from display When the instrument is 25 0~75mV being metrological verified, 26~27 Spare FIL can be set to 0 or 1 to 6.SYMBOL DESCRIPTIONS shorten the response time. 28 0~20mV voltage Symbol Description OPn=1, Normal 29 0~100mV retransmission. OP1 outputs Retransmission IN1 while OP2 outputs IN2. Input specification setting is incorrect 30 0~60mV voltage OPn channel 0~6 Or assignment OPn=2, Enable splitter 31 0~1V mode. Single input from IN2 orAL Input wiring is disconnected/ thermocouple problem dual output. Or 32 0.2~1V Short circuited Define the low limit and Low limit high limit of current SCL and SCH define the of current corresponding scale range OPL retransmission at OUTP 0~110 EErr IC Software error SCLx Scale low limit of linear output. For retransmission position. The engineering of Channel 1 8888 IC Software error example, for channel 1, in unit is 0.1mA. order to retransmit 0~600℃ -999~ For example, to retransmit to output channel 1, SCL1 +3000 0~600℃ in input channel units High limit = 0, and = 600. of current 1 to 4~20mA, then the OPH 0~220 SCHx Scale high limit For channel 2, to transmit retransmission parameter should be set as 0~1000℃ , then SCL2=0, of Channel 1 below: SCL1=0, SCH1=600, SCH2=1000. OPn=1, OPL=40, OPH=200. http:www.yudian.com Yudian Copyright(C)1991-2013 S060-01