You are on page 1of 2

SPECIFICATION DATA

Multispectrum IR Flame Detector


Model X3301
Shown with Q9033A
Aluminum Mounting Arm

DESCRIPTION HIGHLIGHTS

Y E A R
The X3301 is a multispectrum infrared (MIR) flame X3301 TECHNOLOGY FEATURES

5
detector. It provides unsurpassed detection of fires ▲ Complies with FM 3260
from light to heavy hydrocarbon fuels combined ▲ EN54 certified
with the highest degree of false alarm rejection. ▲ Certified SIL 2 capable
The detector has Division and Zone explosion- ▲ ATEX Directive compliant
WARRANTY proof ratings and is suitable for use in indoor and ▲ Certified performance to multiple fuel types and fire sizes
outdoor applications. ▲ EQP models available
▲ Long detection range to carbonaceous fires
The X3301 contains three IR sensors with their associated signal ▲ HART models available
processing circuitry. The standard output configuration includes ▲ FDT/DTM capable
fire alarm, fault and auxiliary relays, with an isolated 0–20 mA output ▲ Multiple sensitivity levels
model with optional HART communication. ▲ Maximum false alarm rejection
▲ Calibrated automatic optical integrity
▲ Reliable flame detection with modulated IR background
The detector provides superior performance in applications that
▲ Microprocessor controlled heated optics
are at the extremes, and where background infrared radiation is a
▲ Third-party approved options for detector verification include
normal condition:
Magnetic Optical Integrity and Manual Optical Integrity tests
— Hangars ▲ Tri-color LED indicates detector status and field-of-view (FOV)
— Offshore production platforms ▲ RFI and EMC Directive compliant
— Offshore production ships ▲ Event logging with time and date stamp
— Refineries ▲ Integral wiring compartment for ease of installation
— Production facilities ▲ Operates under adverse weather conditions and in dirty
— Loading racks environments
— Compressor stations
— Turbine enclosures BENEFITS
— Airport water curtains ▲ Single detector for multiple hydrocarbon fuels
— Automotive Painting ▲ Low cost of coverage
— LNG/LPG ▲ Ability to detect smaller fires earlier
— Gas Separation Plants ▲ Detection range of up to 125 feet for methane
— Warehousing ▲ Better detection zoning capability
— Marine ▲ Best combination of flame detection and false alarm rejection
▲ Low maintenance costs
▲ Reliable fault diagnostics
▲ Suitable for heavy industrial applications
▲ Explosion/flame proof (Ex d) or increased safety installations
(Ex d e) in hazardous locations

2.2 08/20 90-1218


SPECIFICATIONS
Operating Voltage 24 Vdc nominal (18 Vdc minimum, 30 Vdc Field of View 90° horizontal by 75° vertical, at a minimum of 70%
maximum). Maximum ripple is 2 volts peak-to-peak of the on-axis detection distance.
Power Consumption 4 watts minimum (without heater), 17 watts at 30 Vdc Certification
with EOL resistor installed and heater on maximum
Relays Contacts rated 5 amperes at 30 Vdc ®

Fire Alarm: — Form C (NO and NC contacts) Class I, Div. 1, Groups B, C & D (T4A) DEMKO 01 ATEX 130204X
— normally de-energized Class II, Div 1, Groups E, F & G (T4A) Increased Safety Model
— latching/non-latching Class I, Div. 2 , Groups A, B, C & D (T3C) II 2 G
Fault: — Form A (NO contacts) Class II, Div 2. Groupd F & G (T3C) 0539 II 2 D
— normally energized Class III
Ex d e IIC T6...T5 Gb
— latching/non-latching Enclosure NEMA/Type 4X per NEMA 250
Ex tb IIIC T130°C
Auxiliary: — Form C (NO and NC contacts) For FM and CSA Zone approval information, T6 (Tamb – 50°C to +60°C)
— normally energized/de-energized refer to the X3301 instruction manual (95-8704) T5 (Tamb – 50°C to +75°C)
— latching/non-latching. IP66
Current Output 0–20 mA (± 0.3 mA), with a maximum loop Flameproof Model
(Optional) resistance of 500 ohms from 18–19.9 II 2 G
Vdc, 600 ohms from 20–30 Vdc 0539 II 2 D
IEC 61508
Temperature Range Operating: –40°F to +167°F (–40°C to +75°C) Certified SIL 2 Capable. Ex d IIC T6...T4 Gb
Storage: –67°F to +185°F (–55°C to +85°C) Applies to specific models – T6 (Tamb – 55°C to +60°C)
Refer to the SIL 2 Certified T5 (Tamb – 55°C to +75°C)
Hazardous location ratings from –55°C to +125°C X3301 Safety manual (95-8720) T4 (Tamb – 55°C to +125°C)
Humidity Range 0 to 95% relative humidity, can withstand 100% IP66/IP67
condensing humidity for short periods of time. RUSSIA & KAZAKHSTAN

Spectral Sensitivity Range 4 - 5 microns


VNIIFTRI
Wiring 16 AWG or 2.5 mm2 shielded cable is recommended. CERTIFICATE OF CONFORMITY TO
IECEx Certificate of Conformity
"TP TC 012/2011"
Enclosure Material Copper-free aluminum (painted) or stainless steel No TC RU C-US. BH02.B.00401 IECEx ULD 06.0017X
(316/CF8M Cast) Ex db eb IIC T6...T5 Gb
2ExdeIICT6/T5 IP66 Ex tb IIIC T130°C
Conduit Entry Size 3/4 inch NPT or M25 T6 (Tamb = –50°C to +60°C) T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C) T5 (Tamb = –50°C to +75°C)
Warranty 5 years Ex tb IIIC T130°C Db
IP66
– OR –
Response Characteristics – OR –
1ExdIICT6/T5/T4 IP66 Ex db IIC T6...T4 Gb
T6 (Tamb = –55°C to +60°C) T6 (Tamb = –55°C to +60°C)
Distance Ft Average Response T5 (Tamb = –55°C to +75°C)
Fuel Size
(m) Time (seconds)***
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C)
n-Heptane 1 x 1 foot 265 (80.7)* 22 Ex tb IIIC T130°C Db
T4 (Tamb = –55°C to +125°C)
n-Heptane 1 x 1 foot 250 (76.2) 17 IP66/IP67
n-Heptane 1 x 1 foot 100 (30.5) 3 RUSSIA
Very High Sensitivity

n-Heptane 6 in. x 6 in. 100 (24.4) 7


Isopropanol 6 in. x 6 in. 70 (21.3) 6
Diesel 1 x 1 foot 175 (53.3) 6**
Ethanol 1 x 1 foot 210 (64) 11
Methanol 6 in. x 6 in. 40 (12.2) 3 VNIIPO
Methanol 1 x 1 foot 150 (45.7) 7 CERTIFICATE OF CONFORMITY TO UL-BR 12.0093X
Methanol 1 x 1 foot 150 (45.7) 5** TECHNICAL REGULATIONS, Ex d e IIC T6-T5 Gb IP66/IP67
Methane 32 inch plume 125 (38.1) 5 GOST R 53325-2012 Ex tb IIIC T130°C
Propane 32 inch plume 125 (38.1) 5 C-US.ПБ01.B.02910 T6 (Tamb = –50°C to +60°C)
Jet A 1 x 1 foot 150 (45.7) 4** T5 (Tamb = –50°C to +75°C).
JP-5 2 x 2 feet 235 (71.6) 3** – OR –
JP-8 1 x 1 foot 150 (45.7) 5** VdS
Ex d IIC T6-T4 Gb IP66/IP67
Class A Ø12 in. x 7 in. 150 (45.7) 3**
Ex tb IIIC T130°C
n-Heptane 1 x 1 foot 100 (30.5) 7 T6 (Tamb = –55°C to +60°C)
Approvals to EN54-10. See instruction
n-Heptane 1 x 1 foot 50 (15.24) <2
T5 (Tamb = –55°C to +75°C)
Medium Sensitivity

Diesel 1 x 1 foot 70 (21.3) 4**


manual for details.
Ethanol 1 x 1 foot 85 (25.9) 7
T4 (Tamb = –55°C to +125°C).
Methanol 1 x 1 foot 70 (21.3) 6
Methane 32 inch plume 70 (21.3) 6 CANADA
Methane 32 inch plume 55 (16.8) 4 QPS
Propane 32 inch plume 75 (22.8) <5 US Coast Guard
JP-5 2 x 2 feet 150 (45.7) 3** Coast Guard Approval No. 161.002/49/0.
Class A Ø12 in. x 7 in. 50 (15.24) 4**
* Outdoor test condition. *** Add 2 seconds for EQP Model. ULC/ORD-C386:2015
** 10 second pre-burn from ignition. Ø Diameter ULC S529-09
NOTE: Refer to the X3301 instruction manual (95-8704) for additional sensitivity levels. QPS Cert # LR1371-1R1
DNV
Shipping Weight Aluminum: 7 lbs. (3.2 kg) Type Approval Certificate Number TAA00000V2
(Approximate) Stainless Steel: 13.8 lbs. (6.3 kg) DNV Certificate Number MED-B-9427

Specifications subject to change without notice.


All trademarks are the property of their respective owners. ­Corporate Office Phone: +1 952.941.5665
© 2020 Carrier. All Rights Reserved. 6901 West 110th Street Toll-free: +1 800.765.3473
Minneapolis, MN 55438 USA Fax: 952.829.8750
Det-Tronics manufacturing system is certified to ISO 9001—