Professional Documents
Culture Documents
1 Overview
AC power supply unit (PSU): Lithium battery: Lithium battery: DC distribution box:
DPU30A-N06A1 DBU20B-N12A2 DBU25B-N12A1/DBU40B-N12A2 DOU-DCD01
DC PSU:
DPU30D-N06A1
DPU40D-N06A1
Installation Installation
Max. Capacity/Layer Max. System Configuration
Scenario Method
2 PSUs +2 lithium batteries or 3 lithium 4 DC PSUs (DPU30D) /2 AC PSUs (DPU30A) + 5 lithium
batteries (Install the first battery exactly batteries (DBU20B)
Side
Small pole on the pole, the second battery on its left 4 DC PSUs (DPU40D) + 8 lithium batteries (DBU25B / DBU40B)
mounting
side, and the third battery or two PSUs
on its right side.)
Small pole, wall, If the system configuration exceeds the maximum
Flush
large pole, channel 1 PSU + 1 lithium battery or 2 PSUs capacity/layer, install the modules on different layers.
mounting
steel, angle steel
2 Installation Preparations
1
Installing the connecting kit to the lithium battery
NOTE
The installation and cable connection methods DBU20B-N12A2 DBU25B-N12A1、DBU40B-N12A2
for all lithium batteries are the same. The
DBU20B-N12A2 is used as an example.
The connecting kit and hanging kit for the
DBU20B-N12A2 is different from that of the
DBU25B-N12A1 and DBU40B-N12A2, as
shown below.
DBU25B-N12A1, DBU40B-N12A2
Remove the hanging kit from the rear of the lithium battery and Remove the hanging kit from the rear of the lithium battery and
install the kit on its right side. install the kit on its left side.
2
3.2 Side Mounting on a Small Pole (Mode 1): 1 PSU + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
Pole mounting kit Install the pole mounting Install the connecting
(Unit: mm) Cx1 kits. kit to the lithium battery.
Ax1 Bx1
Connecting kit x 1
Connecting
plate x 1
Install the lithium battery to Install the PSU to the Install the connecting plate.
the pole. lithium battery.
3.3 Side Mounting on a Small Pole (Mode 2): 1 PSU + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit Cx1 Install the pole mounting kits.
Ax1 Bx1
Dx1
Hanging
kit A x 2
Connecting
plate x 1
Install hanging Install the lithium Install the PSU to the pole. Install the connecting plate.
kit A to the PSU. battery to the pole.
3
3.4 Flush Mounting on a Small Pole (Mode 1): 1 PSU + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit Install the pole mounting
Install the connecting kit.
Bx1 Cx1 kits.
Ax2
Hanging
kit B x 1
Connecting
kit x 1
Connecting
plate x 2
Install hanging Install the lithium battery to Install PSUs to the pole. Install the connecting plates.
kit B to PSUs. the pole.
3.5 Side Mounting on a Small Pole (Mode 2): 2 PSUs + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit
Cx1 Install the pole mounting kit.
Ax1 Bx1
Dx2
Hanging
kit A x 2
Connecting
plate x 2
Install hanging Install the lithium battery to Install PSUs to the pole. Install the connecting plates.
kits A to PSUs. the pole.
4
3.6 Flush Mounting on a Small Pole: 1 PSU + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit Install the pole Remove the hanging kit from the rear
mounting kits. of the lithium battery and install the kit
Bx1 Cx1 on its left side.
Ax1
Connecting
kit x 1 Connecting
plate x 1
Install the connecting kit Install the lithium Install the PSU to Install the connecting plate.
to the lithium battery. battery to the pole. the lithium battery.
3.7 Flush Mounting on a Small Pole: 2 PSUs + 1 Lithium Battery (Pole Diameter: 60–114 mm)
Space Planning Required Accessories Installation Procedure
(Unit: mm) Pole mounting kit Install the pole mounting Assemble the PSUs and install
Bx2 Cx2 kits. the PSU hanging kit B.
Ax2
Connecting
plate x 1
Install the connecting Remove the hanging kit from the rear Install the PSUs to the Install the lithium battery to
plate. of the lithium battery and install the pole. the pole.
kit on its right side.
5
3.8 Flush Mounting on a Large Pole: 1 PSU + 1 Lithium Battery (Pole Diameter: 114–400 mm)
Space Planning Required Accessories Installation Procedure
Pole mounting kit Assemble the large pole Secure the large pole
(Unit: mm) Bx1 Cx0 installation kit. installation kit to the large pole.
Ax1
Front
Remove the hanging kit from the Install the Install the lithium battery to Install the PSU to
rear of the lithium battery and install connecting kit. the large pole. the lithium battery.
the kit on its left side.
2.9 Flush Mounting on a Large Pole: 2 PSUs + 1 Lithium Battery (Pole Diameter: 114–400 mm)
Space Planning Required Accessories Installation Procedure
Large pole Assemble the large pole Secure the large pole
installation installation kits. installation kits
kit x 2 sets to the large pole.
Connecting kit x 1
Hanging kit B x 1
Front
Ensure that the hoops
are attached closely to
(Unit: mm) the pole so that they
Connecting do not slide.
plate x 1
6
Assemble the PSUs Install the connecting plate. Remove the hanging kit from the rear
and install the PSU of the lithium battery and install the
hanging kit B. kit on its right side.
Install the PSUs to the large pole. Install the lithium battery to the large pole.
(Unit: mm)
Remove the hanging kit from the Install the lithium Install the PSU to
Install the connecting plate.
rear of the lithium battery and battery to the wall. the lithium battery.
install the kit on its left side.
7
3.11 Flush Mounting on a Wall (Mode 2): 1 PSU + 1 Lithium Battery
The wall must be able to bear a weight four times the weight of all PSUs and lithium batteries and the bolts' pulling force of 1.25 kN vertical to
the wall.
Space Planning Required Accessories Installation Procedure
(Unit: mm) Wall mounting Install expansion anchor bolts. Install the wall Install the
kit x 1 mounting kit. connecting kit.
Hole depth: 55–60 mm
Connecting
kit x 1
Connecting
plate x 1 (Unit: mm)
Remove the hanging kit from the Install the lithium Install the PSU to Install the connecting plate.
rear of the lithium battery and install battery to the wall. the lithium battery.
the kit on its left side.
Connecting
plate x 1 (Unit: mm)
Remove the hanging kit from the rear Assemble the PSUs Install the connecting plate.
of the lithium battery and install the kit and install the PSU
on its right side. hanging kit B.
8
Install the lithium battery to the wall. Install the PSUs to the wall.
Connecting Hanging
kit x 1 kit B x 1
(Unit: mm)
Remove the hanging kit from the Install the lithium Assemble the PSUs and Install the PSUs to the
rear of the lithium battery and battery to the wall. install the PSU hanging wall.
install the kit on its right side. kit B.
The DC distribution box can be installed in the same way as the PSU. For details, refer to the relevant sections.
9
5 Installing Cables
5.1 Installing a Ground Cable
NOTE It is recommended that the ground cable be prepared indoors.
The following figure uses one PSU, one lithium battery, and
one DC distribution box as an example. Core cross-sectional area: 10 mm²
NOTE
PSU load cables and AC input cables should be prepared onsite. DC load cables are used as an example here. Refer to this procedure
when preparing AC cables.
Multi-core cables should be used as AC and DC power cables; otherwise, water may seep into the waterproof connectors.
It is recommended that AC and DC power cables be prepared indoors.
Before assembling the waterproof connector, check whether the connection between the cable and terminal is firm and reliable.
Scale line
(Unit: mm)
Installing Ground Clips for DC Load Cables Cable binding hole (4 mm2) Cable binding hole (≥ 6 mm2)
Cable tie
Waterproof tape Insulation tape Cable tie Load cable Ground cable
10
5.3 Installing Power Cables and Communications Cables
The system does not simultaneously support AC input and DC input.
Ensure that caps and waterproof connectors are installed at all idle ports on the modules.
PSU PSU
Other lithium
batteries
Ground clip
Monitoring Monitoring
device Site ground bar device
AC input AC load
AC/DC input DC load
NOTE When all DC loads (Huawei RRU 5xxx or AAU 5xxx series), DC power modules (DPU40D-N06A1), and lithium batteries
(DBU25B-N12A1 or DBU40B-N12A2) can communicate with each other through power cables, no communications cable is
required between the DC power module, communications device, and lithium battery.
AC AC AC AC AC AC AC AC Monitoring device
input load load load input load load load
PSU 1 PSU 2
Lithium battery 1 Lithium battery 2 Lithium battery 3 Lithium battery 4 Lithium battery 5
11
Cascading Multiple DC PSUs and Lithium Batteries
If multiple PSUs are configured, they can be cascaded by connecting BAT and LOAD ports or by interconnecting LOAD ports. It is
recommended that DC loads be equally distributed on the PSUs.
If multiple lithium batteries are configured, they should be cascaded by interconnecting BAT ports.
When all DC loads, DC power modules, and lithium batteries can communicate with each other through power cables, no
communications cable is required between the DC power module and the communications device or lithium battery.
DC DC DC
load load load
DC distribution box
Monitoring
AC/DC DC DC AC/DC DC DC AC/DC DC DC AC/DC DC DC device
input load load input load load input load load input load load
7 Power-On Commissioning
AC PSU Power-On Commissioning
1. Measure the PSU input voltage. Ensure that the AC input voltage is in the range of 85–300 V AC.
2. Check the indicators on the PSUs and lithium batteries. Ensure that the green indicators are blinking slowly and that the yellow and red
indicators are off.
3. Measure the AC output voltage at each load port. Ensure that the output voltage is equal to the input voltage when there is mains input,
and that the output voltage is 220 V AC±3% (220 V system) or 110 V AC±3% (110 V system) when there is no mains input.
4. Measure the DC output voltage at each BAT port. Ensure that the voltage is in the range of –42 V DC to –58 V DC.
5. Observe the power system for about 15 minutes. If no alarm indicator is on, the system is running properly.
12
8 LIVE APP
8.1 Installing the LIVE APP
You have obtained the LIVE APP user name (initial value: liveapp) and password
(initial value: Changeme_123).
The mobile phone should be within 10 m away from the PSU.
The mobile phone APP may be occasionally disconnected due to difference in
phone model and Bluetooth signal strength. Please try again 5 minutes later.
Certain mobile phones may fail to connect in automatic Bluetooth pairing mode due
to Android system differences. Please select the manual pairing mode to connect.
Locate the pairing request in the notice column and enter the pairing PIN 0000 or
000000.
1. Tap the LIVE icon to access the LIVE APP login screen.
2. On the LIVE APP login screen, choose Bluetooth connection in the Select a
connection method drop-down list box to search for PSUs equipped with a Bluetooth
device nearby.
3. Enter the correct user name and password.
4. Tap Login, access Main Menu, and view the PSU running information.
9 Follow-up Operations
1. If the mains power needs to be disconnected for a long time after initial system power-on, remove the lithium battery communications
and power cables. After all lithium battery indicators turn off, reinstall the lithium battery communications and power cables.
2. Reinstall caps and waterproof connectors on all unused ports of the modules.
3. Ensure that the paint on the module exterior is intact. If paint has flaked off, repaint the area to avoid corrosion.
4. Clean the site and leave.
13