You are on page 1of 12

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO.

1, JANUARY 2010 35

A Novel Fault-Locator System; Algorithm,


Principle and Practical Implementation
Mohammad A. Mirzai and Ali A. Afzalian, Senior Member, IEEE

Abstract—This paper presents a novel fault-locator system for plemented in practice, for estimating the location of distribution
radial distribution feeders based on the feeder architecture and faults, consist of using voltages and currents measured at one
voltage and current measurements at a subtransmission substa- or some points of a feeder. Fault-location methods can be di-
tion (63/20 kV). The proposed algorithm determines the fault lo-
cation precisely by considering the variable characteristic of the vided into three categories: 1) methods that are based on trav-
load, unbalanced condition, and unsymmetrical nature of distri- eling waves [2], [3], [21]; 2) methods that use higher frequency
bution feeders. Load variations affect the accuracy of fault-locator components (harmonics) [4] of currents and voltages; and 3)
systems significantly. Real-time load estimation is implemented to methods that use the fundamental frequency voltages and cur-
reduce the differences between the calculated fault location and rents [5] measured at the terminals of a line. The last method,
the actual fault location. In addition, self-supervisory characteris-
tics are added to the system to increase the accuracy of the collected
also classified as the impedance-based method, consists of cal-
data. Actual test results demonstrate the effectiveness of the system culating line impedances as seen from the line terminals and es-
in practical applications. timating distances of the faults. Impedance-based methods are
Index Terms—Calculus of variations, distribution feeder, fault
more popular among utilities, because of their ease of imple-
diagnosis, fault locator. mentation. The methods in this category can be further clas-
sified into two subcategories: methods that use measurements
from one terminal of the transmission line and methods that use
I. INTRODUCTION measurements taken from both terminals.
The apparent impedance that is calculated by using a funda-

D ISTRIBUTION feeders are the final nuts of the energy


chain, in which energy has been produced, transmitted,
and delivered to the customer. This part of electrical power sys-
mental component is the most widely used method [3]. In the
later case, the results of research led to a fault locator unit in dis-
tance protection relays. Fault locating in the distribution system
tems is just as important as power generation and transmis-
is not an easy task because of its high complexity and difficulty
sion. Commercial experts believe that the distribution feeder
caused by the nonhomogeneity of lines, fault resistance, load
is even more important than the other two parts, because the
uncertainty, and phase unbalance. However, the basic approach
final goal of electrical power generation is selling this energy
to calculate the fault location using voltage and current measure-
to the customer. The reliability of electrical energy is very im-
ment is still the same as in the transmission system case (i.e.,
portant for the customer. The fulfillment of this necessity is not
calculation of the impedance by using the fundamental compo-
always an easy task because distribution feeders are susceptible
nent [5], harmonics [4], or unsymmetrical component [6]).
to faults caused by storms, lightning, snow, freezing, rain, insu-
Recalculation of the voltage and current at each node is also
lation breakdown, and short circuits caused by birds and other
needed for the compensation of the distribution system char-
external objects. When a fault occurs on a distribution line, it
acteristics [5], [7], and [8]. The fact that a distribution feeder
is very important for the utilities to identify the fault location
has many branches or laterals adds the difficulty in the problem
as quickly as possible to improve the service reliability. The
of locating the fault, since estimating the fault location based
restoration can be expedited if the location of the fault is either
on the voltage and current signals yields more than one loca-
known or can be estimated with reasonable accuracy. Therefore,
tion. Heuristic and expert system approaches [9] for locating the
an automatic fault-locator system is an unavoidable part of a dis-
fault in distribution systems are also proposed, which use more
tribution system.
measurements. Measurements are assumed to be available at the
There has been much research on the fault-location problem
sending end of the faulty line segment, that is not true in reality,
in transmission systems [1]. Methods, proposed in papers or im-
as the measurements are only available at the substation and at
limited nodes [10], [11] of the distribution networks through the
use of remote terminal units. The emerging techniques of artifi-
Manuscript received October 16, 2008; revised September 10, 2009. First
published December 04, 2009; current version published December 23, 2009.
cial intelligence (AI) can be a solution to this problem
Paper no. TPWRD-00768-2008. A fuzzy-logic approach was suggested [12], [18] to determine
M. A. Mirzaei is with the Department of Electronic, Control and Instrumen- the most possible fault location.
tation, Niroo Research Institute, Tehran 14686-17151, Iran (e-mail: mirzai142.
nri@gmail.com).
The main contributions of the paper are summarized as fol-
A. A. Afzalian is with Department of Electrical Engineering, Shahid lows.
Abbaspour University of Technology, Tehran 16589-53571, Iran (e-mail: 1) A new method is used in the proposed algorithm to calcu-
afzalian@pwut.ac.ir).
Color versions of one or more of the figures in this paper are available online
late the fault location based on the differences between the
at http://ieeexplore.ieee.org. values of prefaults and during-faults voltages and currents.
Digital Object Identifier 10.1109/TPWRD.2009.2034809

0885-8977/$26.00 © 2009 IEEE


36 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010

Fig. 1. Hypothetical distribution feeder.

2) This novel fault locator algorithm is derived from the cal- Fig. 2. Prefault equivalent circuit.
culus of variations and is implemented in load-flow anal-
ysis for the first time.
3) Since constant impedance model is used for load modeling,
the variation of the load in the actual condition needs to
be calculated and exerted in the during-fault calculations.
Load variations will be determined based on the prefault
data and the configuration of the distribution feeder. Fi-
nally, the real-time impedances are applied in the fault-lo-
cator algorithm.
4) The output of “Trip Start” contact is employed as an aux-
iliary means to check the accuracy of fault discrimination.
The rest of this paper is organized as follows.
Theoretical and mathematical principles are presented in Sec-
tion II where the proposed method is thoroughly explained. In
Sections II and III, the proposed fault diagnosis, fault classifica-
tion, and fault-locator algorithms are explained and clarified by
using simple examples and illustrations. The required hardware
configuration for collecting data from the distribution feeder is
described in Section IV. The software analysis including Elec-
Fig. 3. One section of a hypothetical distribution feeder.
tromagnetic Transient Program (EMTP) simulation results and
sensitivity analysis is depicted and compared in Section V. The
result of field tests is presented in Section VI. Both simulation In addition, the impedances used in the during-fault equiv-
and practical results were interpreted as well as compared with alent circuit of each section of the distribution feeder are cal-
the results of other studies in Section VII. culated based on the prefault condition. Therefore, the prefault
load variation must be exerted in the postfault equivalent circuit.
The equivalent circuit for section is illustrated for the pre-
II. FAULT-LOCATION PRINCIPLES fault condition in Fig. 2. Thevenin equivalent impedances of the
rest of the feeder toward the end of the feeder are measured from
Consider the feeder shown in Fig. 1 as an example of a radial point of the section .
distribution feeder. In this feeder, sections and buses are speci- In Fig. 3, the ideal three-phase voltage sources represent the
fied with unique numbers starting from 1 to for the sections input voltage at point . The voltage values are extracted from
and from 1 to for the buses. the prefault load flow information. The equivalent Y model of
the load is shown for each section in Fig. 2 where is the
load variation.
A. Prefault Load Estimation The objective of the load estimation is to determine the
amount of changes in impedances ( , , and )
Loads vary unpredictably in distribution feeders. These vari- based on the prefault values of voltages and currents in this
ations affect the performance of fault locator systems signifi- section.
cantly. A fault-locator system is a real-time device and needs KVL equations at the source side can be written in the matrix
to measure the load variation somehow. In this study, the con- form
stant impedance model is used. The amount of load impedance
varies in each phase during the normal operation of the distribu-
tion feeder before the fault takes place. The variations should be
incorporated in the during-fault equivalent circuit because it is
assumed that the load remains unchanged during the short fault (1)
interval.
MIRZAI AND AFZALIAN: NOVEL FAULT LOCATOR SYSTEM 37

Fig. 4. Underground cable single line ( model).

K.V.L equations at the load side are written as


Fig. 5. Limitation of using (4).

Fig. 3 shows the “during fault” equivalent circuit of section J.


the during-fault equivalent circuit is the same as the “pre-fault”
circuit shown in Fig. 2 except, R has been added at the point F.
Using the circuit in Fig. 3, D and R values can be determined
Let s rewrite equations in the matrix form as follows.
We know from the calculus of variations [16] that the varia-
tion of a functional can be approximated as

(2)
Vector can be easily worked out by
solving (1) and (2) simultaneously. Finally, during-fault equiv- (4)
alent Impedance is achieved and will be used in the
during-fault calculation
KVL equations for loop 1 in Fig. 3 can be written as
Loop 1
(3)

The current and voltage signals are measured at the substation


(5)
but only the prefault values are used in the feedforward load
flow to determine the values of the currents and voltages at the Let us define a fault function F as
other points. The calculated values are used for the real-time
load estimation in the other sections.
A simple prefault equivalent circuit is used for the modeling,
each section of the distribution feeder is as shown in Fig. 2.
The measured voltages at bus 1 are used as the sources-side (6)
voltages for section 1 in the equivalent circuit. For the other
sections, the sources-side voltages are the end-point voltages of The deviation of the functional can be approximated as
the previous section. The end-point voltages are calculated by
using (1). The vector and are calculated based on (2),
(3) and are sorted in a database for “during fault” calculations.
This procedure is repeated for other sections of the feeder up to
the last section. (7)

B. Fault-Location Algorithm It is assumed that there is no change in and during the


fault (i.e., and ).
Assume that a single-phase fault occurs at kilometers from Therefore
the beginning of the section along the distribution feeder of
Fig. 1. The final goal is to determinate which is the accurate
location of the fault by using the currents and voltages values
measured at the beginning of the distribution feeder (63/20 kV
subtransmission substation). The fault resistance (R) is also
achieved as a subsidiary result. (8)
38 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010

Fig. 6. Waveform patterns associated with different faults (a) A conductor was broken and immediately eliminated by CB. (b) Fuse. (c) CB. (d) Coordinated fuse
and Autorecloser operation waveform.

or By solving (13), D and R are achieved

(9)
(17)
Let us define
(10)
or
(11)
Then, we can write
(18)
(12)
(13) (19)
(14)

The fault location (D) can be easily calculated based on (9). Equations (18) and (19) are used in the fault-locator algo-
Thereafter, R is achieved easily. rithm. As shown in (18) and (19), D and R are strongly de-
To do this, (9) is rewritten in the complex form pendent on and . Considering the fact that the “prefault”
voltage is approximately constant, the “prefault” current varia-
(15) tion determines the “prefault” load variation in the distribution
feeder.
Therefore In order to use (4), the variation must be small as shown
in Fig. 4 [13].
As a result, the terms and
(16)
are neglected in (1).
MIRZAI AND AFZALIAN: NOVEL FAULT LOCATOR SYSTEM 39

In the cases where the during-fault current variation is signif- TABLE I


icant in proportion to the prefault current, (18) and (19) are not RELATION BETWEEN PREFAULT AND DURING-FAULT QUANTITY
accurate.
In these cases, (22) and (23) are used to determine and ,
respectively, but the variation of the during-fault and prefault
values meets the condition of

(20)

(21)

On the other hand, for the faults to take place in the beginning V : faulted line voltage;
sections of the feeder, (22) and (23) are used but for the other I : prefault current;
sections, (18) and (19) are strongly recommended [7] V : zero-sequence voltage;
I : faulted line current;
V : unfaulted line voltage;
(22) I : zero-sequence current;
V : nominal phase voltage.
(23)
[14], which is classified under “pattern recognition.” In order to
The flowchart of the algorithm for finding the fault location is apply the method for the fault diagnosis purpose, four main pat-
shown in Fig. 5. Due to the radial structure of distribution sys- terns are defined and called basic pattern. A fault current wave-
tems, the fault-location algorithm can obtain multiple choices form in the distribution feeder is then compared with each basic
for the fault locations when measurements are only available at pattern. The patterns are defined over three or four intervals (i.e.,
the substation. Thus, it is necessary to identify the actual fault prefault, during-fault, and postfaults time intervals. These wave-
location from the calculated multiple choices by using an addi- form patterns are shown in Fig. 6. Distribution feeders are al-
tional fault diagnosis algorithm. ways liable to be affected by dangerous situations of various
types of faults. There are varieties of protective devices, such
C. Underground Cable as cutout fuses, autoreclosers, and protective relays. Protective
relays (OC/EF) are installed in the substation in order to protect
The algorithm and the system are designated to find the fault the main branch of the feeder while cutout fuses and autore-
location in underground and overhead distribution feeders. The closers are mainly erected in the lateral branches. In the pro-
underground fault-location estimation formula is slightly dif- tection expert point of view, faults are classified into three main
ferent than the overhead line because the parallel capacitors in groups: 1) low impedance fault along the main branch; 2) broken
the section model (Fig. 4) cannot be neglected and the amount conductor faults; and 3) the operation of the protective devices
of this capacitor is significant. in the lateral branches [18].
In the case of underground cables, (10) will be substituted by The overcurrent relay operates immediately when low
impedance faults occur along the main branch. Consequently,
(24) C.B. operates to prevent further damage. The waveform of this
class of fault is illustrated in Fig. 6(c). The class of fault (low
where impedance) can be identified by using Table I [15].
Sometimes, a severe accident causes a breakdown in con-
(25) ductors of overhead lines. If broken conductors fell on other
live conductors, the fault can be easily detected because of
and the current increase in the affected phases. However, the main
branch current differs slightly when the conductors fall on
(26) the ground. This type of fault cannot be detected easily if the
earthing transformer connected the secondary side of power
transformer (63/20) to the ground. Indeed, the fault detection in
this type of fault strongly depended on the network grounding
III. FAULT DIAGNOSIS ALGORITHM
method.
The voltage and current signals are being recorded in the sub- The waveform changes when the overhead line conductors
station when a fault occurs along the main or lateral branches of are broken and falling on the ground, the second interval is di-
a distribution feeder. These recorded signals contain important vided into two parts (i.e., “open-line” and “during-fault.” On the
information which can be used for diagnosing the fault. other hand, in addition to the three fundamental parts of the fault
The first piece of evidence which can be applied to the fault current waveform, “line-open” interval is added to the sequen-
diagnosis process, involves the sequence of events extracted tial events of the waveform. The current pattern of this kind of
from the waveforms. The method is called “waveform pattern” fault is illustrated in Fig. 6(a)
40 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010

Fig. 8. Fault diagnosis in the scheme that the autorecloser and fuse were coor-
dinated.

the protective coordination knowledge is applied to the diag-


nostic process, consider a fault on a lateral as shown in Fig. 8.
In these cases, the exact place of the fault is determined by using
the same way as explained in example1.
Example1. Suppose a fault occurs at point 1 in the network as
shown in Fig. 8. If a fuse-saving scheme is employed, the fault is
first treated as a temporary fault, and the recloser on the feeder
operates tries to clear the fault. If the fault is permanent, the
fuse at the head of the tap melts to clear it permanently before
the recloser operates at the third or the fourth time. This practice
limits the number of customers affected by a permanent outage.
The waveform of this practice is shown in Fig. 6(d).
Note that the operation of the distribution protective devices
can be observed from the voltage and current waveforms
recorded at the substation. Fig. 6(d) shows a faulty-phase
current waveform.
The second piece of data is the load-change pattern observed
at the substation during the operation of the protective devices.
After the operation of each protective device along the distribu-
tion feeder, the load level on the faulted phase observed at the
substation drops from the normal condition to the postfault con-
dition, as illustrated in Fig. 6(a), (b), and (d).
When a fault occurs at point 1, the fault-locator algorithm
suggests three points as fault-location candidates. The asym-
metry of lateral branches must be considered in order to find
the correct answer. In addition, the probability of having two
branches with the same current is very low. Therefore, it is as-
sumed that no branches have similar current. Thus, the reduction
in the source current due to outage of a specific lateral branch is
definite and unique [15].
There are three for the fault at point 1:
In branch I

(27)

In branch II

(28)
Fig. 7. Fault-locator algorithm. In branch III

(29)
The fault-locator algorithm suggests multiple choices for the
fault location in lateral branches (Fig. 7). As an example of how Only is the right answer (Fig. 8).
MIRZAI AND AFZALIAN: NOVEL FAULT LOCATOR SYSTEM 41

Fig. 9. Hardware schematic of data acquisition, fault diagnosis, and locator


system.

Fig. 11. Flowchart of the fault-locator software.

rather than disturbance. Furthermore, the trip contact in the


fault locator subsystem initiates a special function dealing with
the main branch fault in order to find possible multiple or single
fault location along the main branch of the distribution feeder.
The sample-and-hold subsystem includes eight channels of an
analog-to-digital converter (ADC) based on the PCI bus with a
10-kb/s sample rate. The fault diagnosis and locator subsystem
are implemented on an industrial PC with a high-speed Pentium
processor (3 GHz). This unit is compatible with a 110-VDC
power supply of the substation.
The system must work in high-voltage environments; there-
Fig. 10. Start and trip signals sequence and priority. fore the electromagnetic compatibility (EMC) requirement is
considered in the design and implementation processes.
The fault-locator system is implemented in user-friendly
Note that the load-flow calculations must be carried out on software. The software consists of three parts; sample-and-hold
the collected data before this step, twice (prefault and during). driver, fault locator and diagnosis, the distribution architec-
ture, and protection coordination database (Fig. 11). The
IV. HARDWARE CONFIGURATION fault-locator system uses the fundamental power frequency
Fig. 9 shows the block diagram of the experimental component. Fast Fourier transform (FFT) is applied to convert
system, including data acquisition, fault locator, and diag- these samples (48 samples per cycle) to the equivalent vector
nosis subsystems. of the measurements. The actual fault-locator system also uses
The current and the voltage transformers sample-and-hold in- the prefault load-flow information as another input to find the
terface, fault locator, and fault diagnosis subsystem are essential fault location.
parts of an actual distribution fault-locator system. In this paper, The distribution feeder is analyzed by EMTP [19]. EMTP is
two outputs contacts of the OC/EF relay; “Protection Trip” and also used for preparing the artificial fault signal in the various
“Trip Start” signals are used to help the data-acquisition system conditions to test the fault-locator algorithm. The fault current
work precisely. When every transient or steady-state phenom- is sent as a matrix to the fault-locator functions by the software
enon occurs in the distribution feeder; OC/EF relay becomes interface module.
ready to send a “trip” signal to the circuit breaker if it diagnoses ATPDraw is a graphical preprocessor and is used to create
a fault. Current variations are observed by the protection relay and edit circuit files. Fig. 12 was modeled in ATPDraw and all
continuously. If the change in the current amplitude becomes of the fault signal generation, load flow, and sensitivity studies
more than the start threshold, then the protection relay activates had been conducted in this software before starting the practical
“Trip Start” output. When the amplitude of current increases to phase of the project, and parameters, such as, fault location, fault
the level of trip threshold, moreover, it remains to fulfill the time impedance, load impedance changed frequently. The effect of
setting of the OC/EF relay, then the “protection trip” output is changes in each parameter on the calculation result were studied
activated. This simple procedure is shown in Fig. 10. by using ATPDraw (Fig. 16–21). Transformers, overhead lines,
The “Protection Trip” and “Trip Start” output help switches, and load models are available in the ATPDraw library.
sample-and-hold the subsystem to collect actual fault data The parameters of these models can be tuned easily. Moreover,
42 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010

as load, the place of fault, and the resistance of fault are changed
intentionally and the error of this variation is measured. Both of
these results are very important.
Simulation signals are prepared for the test in the EMTP soft-
ware [20]. A set of generated voltages and currents signals is
shown in Fig. 14 and 15, respectively. The fault resistance in
this case is .

A. Algorithm Accuracy Test


The accuracy test results for faults in different places of the
feeder are given in Table II. In this test, a phase-ground fault is
placed from the beginning to the end of the feeder and then the
difference between actual fault place and the calculated
fault place is measured.
In this study, a phase-ground fault is studied. Similar results
are achieved with the other types of faults (Table II).
Fig. 12. Fault simulator and algorithm tester.
B. Sensitivity Analysis Test
ATPDraw can be used for steady-state and transient analyses The sensitivity of the fault location to the variation in load,
precisely. section length, and fault resistance are studied (Fig. 16–21).
The load-flow files are used as a part of the distribution data- The load is changed from 50% to 175% of its nominal value.
base and updated periodically every six months based on the These changes do not happen in reality. The variations in the
newest changes in the feeder architecture and devices. The re- amplitude of the feeder currents are approximately 15% of
sulting database is applied to the fault-locator system. the nominal current in a short period of time. Mostly, the dis-
ATPDraw file is created for preparing the load-flow file and tribution feeder is over designed based on a 10-year extension.
set for steady-state simulation. The output of this process is used In these cases, the maximum current of the feeder increases
as the prefault load-flow file. In addition, some information re- steadily up to 175% of the nominal current during future years.
ferring to protection devices, such as fuses and autoreclosers
VI. FIELD TEST RESULTS
information, is incorporated in this file. Other parts of the block
diagram (Fig. 11.) are common modules. In order to evaluate the performance of the proposed system,
The operation of the algorithm was tested in the laboratory field tests have been conducted on several distribution feeders
environment before it was used in the field. A setup is prepared by using actual data signals. The DAQ circuit is used to gather
to check the functionality of the system (Fig. 12.) The block di- transient data at the substation. Outage reports on this feeder are
agram is very similar to the real system block diagram (Fig. 11) provided by the area distribution operations center and subtrans-
except the fault signals. The laboratory fault signals are pre- mission dispatching center in order to determine the location of
pared in EMTP software while in the fault locator system, the the faults.
analog-to-digital interface cards collect data (Fig. 11). The calculated fault distance is compared with the dis-
The electrical single-line diagram of the feeder map is shown tance from the actual fault location to the substation . The
in Fig. 13 test results are summarized in Table III. The error of the fault
First, the information of the feeder (i.e., overhead line con- distance computation is between 1.65% and 3.31%. This corre-
figuration, transformer nameplate data, conductor, and load in- sponds to a distance ranging from 75 to 366 m. For distribution
formation) is collected by a global positioning system (GPS) feeders with a length of several kilometers, this accuracy makes
receiver. Second, this information is converted to the AutoCAD it possible for personnel to quickly find the location of the fault.
file and completed by other electrical information. The ATP- Actual voltage and current waveforms are shown in Figs. 22 and
Draw file is prepared by using the appropriate model for each 23.
element of the distribution feeder and in accord with the infor- The fault locator was employed actually in the field test, and
mation in the AutoCAD file. The GENTRAFO model, LCC line the algorithm was tested via a set of online recorded data in
model, and RLCY3 models are used to model the distribution the substation (All data collection hardware and fault location
and 63/20 power transformer, overhead line and load, respec- algorithm were tested online). Indeed, fault calculation never
tively. Finally, operation functions, such as vector estimation, implemented on the off-line system based on actual collected
fault detector, and fault locator are prepared in MATLAB and signals in the laboratory, the system works online and without
converted to the C++ by using the and changer. interruption, exactly similar to a protection relay.

V. SIMULATION RESULTS VII. DISCUSSION


The simulation study consists of two parts: algorithm accu- In [7] the error fluctuates from 1.13% to 3.42, however the
racy test and sensitivity test. In the algorithm accuracy test, the fault type varies in some cases. The error (%) versus fault loca-
fault-locator algorithm is evaluated and its accuracy has been tion (km) of this study is compared with the one reported in [7]
achieved. In the sensitivity test results, some parameters, such (Fig. 24). as shown in Fig. 24, the error in the fault location in
MIRZAI AND AFZALIAN: NOVEL FAULT LOCATOR SYSTEM 43

Fig. 13. Electrical single-line map.

the proposed system is less than or equal to the one in [7] in five That is because; two different algorithms were applied for the
cases. There is only one case where our result is worse than [7]. different part of the distribution in this study.
44 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010

Fig. 14. Generated fault voltage waveform in EMTP for the fault in phase C Fig. 16. Error in D versus load variation in three different fault resistances
R = 2
. ( )
R along the 18th section.

Fig. 17. Error in D versus load variation in three R along the 12th section.
Fig. 15. Generated fault current waveform in the EMTP for a fault in phase C
R = 2
.

TABLE II
ALGORITHM ACCURACY TEST RESULT

Fig. 18. Error in D versus load variation in three R along the 25th section.

different cases, such as unbalanced phases, unpredictable load


variation, various structure, and configuration of distribution
feeders and a variety of fault types.
The error curves (Fig. 16–21) do not have regular patterns.
VIII. CONCLUSION
They decrease in the first part and increase in the second part in
many cases. Regular error patterns change absolutely increase This paper proposed an effective fault-location algorithm as
or decrease from the beginning to the end. Therefore, they can be well as a novel fault diagnosis scheme. The proposed fault-lo-
reduced or compensated easily. This study not only presented a cation algorithm identifies a fault locations candidate by using
new method for estimating the fault location precisely, but also an iterative estimation of the load current and the fault current at
suggests that a future research work looks for algorithms and each line section. The diagnosis subsystem determines the ac-
methods which compensate and reduce the calculation error in tual location by comparing the current waveform pattern with
MIRZAI AND AFZALIAN: NOVEL FAULT LOCATOR SYSTEM 45

TABLE III
SUMMARY OF THE TEST RESULT

Fig. 19. Error in D


versus fault-location distance from the beginning of the
feeder in threeR in the ABG fault type.

Fig. 22. Measured current waveform (phase A is the faulted phase).

Fig. 20. Error in D


versus fault-location distance from the beginning of the
feeder in threeR in the ACG fault type.

Fig. 23. Measured voltage waveform (phase A is the faulted phase).

accuracy of the system outcome. Various simulation results and


field tests have shown a practically satisfactory accuracy and
Fig. 21. Error in D versus the fault-location distance from the beginning of the robustness of the proposed algorithm to the load variation.
the feeder in three R in the AB fault type. The actual test reports and simulation results validated the ac-
curacy and applicability of this new algorithm in practice. An
efficient mathematical method, based on calculus of variations,
the expected pattern belonging‘ to the operation of the protec- was also presented. The method can also be employed in the
tive devices. In the non-DA system, the proposed technique can load estimation and dynamic network analysis of distribution
be implemented on a digital fault locator system installed at a feeders. This method solves some of the problems in conven-
substation. This digital system can also be applied for the dis- tional fault locating algorithms such as the dependency of the
tribution-management system (DMS) as a subsystem. Although accuracy on the length of the feeder, sensitivity of location to the
the fault locator can be installed as a stand-alone device, addi- fault resistance, and load variation. This method is very useful
tional digital input from the digital protection relay increases the for high-impedance fault-locator systems.
46 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010

[13] D. Thukaram, U. J. Shenoy, and H. Ashageetha, “Neural net-


work approach for fault location in unbalanced distribution net-
works with limited measurements,” presented at the Power India
Conf., New Delhi, India, 2006. [Online]. Available: http://ieeex-
plore.ieee.org/xp/freeabs_all.jsp?arnumber=1632510
[14] J. Wan and K. Nan Miu, “Meter placement for load estimation in radial
power distribution systems,” in Proc. IEEE Int. Symp. Circuits Systems,
2004.
[15] P. H. Divsheli, H. Ghadiri, A. H. Hesaminia, and B. Amini, “A novel
approach for meter placement for load estimation in radial distribution
networks,” in Proc. 3rd Int. Conf. Electric Utility Deregulation and
Restructuring and Power Technologies, Nanjuing, China, Apr. 2008,
pp. 1576–1579.
[16] P. Jarventausta, P. Verho, and J. Partanen, “Using fuzzy sets to model
the uncertainty in the fault location process of distribution networks,”
IEEE Trans. Power Del., vol. 9, no. 2, pp. 954–960, Apr. 1994.
[17] D. S. Naidu, Optimal. Control Systems. Boca Raton, FL: CRC, 2003.
[18] S.-J. Lee and M.-S. Choi, “An intelligent and efficient fault location and
Fig. 24. Actual test results in this paper and the same study. diagnosis scheme for radial distribution systems,” IEEE Trans. Power
Del., vol. 19, no. 2, pp. 524–532, Apr. 2004.
[19] M. Kezunovic and C. W. Formen, “An expert system for transmission
REFERENCES substation event analysis,” IEEE Trans. Power Del., vol. 8, no. 4, pp.
1942–1949, Oct. 1993.
[1] M. Saha, R. Das, P. Verho, and D. Novosel, “Review of fault location [20] P. Kirawanich and R. M. O’Connell, “ETP-EMTP study of potential
techniques for distribution networks,” presented at the PS&CIF, Bei- adjustable speed drive rejection due to voltage sag,” in Proc. 11th Int.
jing, China, Sep. 2002. Conf. Harmonics and Quality of Power, 2004, pp. 123–128.
[2] G. B. Ancell and N. C. Pahalawaththa, “Maximum likelihood estima- [21] M.-S. Choi, S.-J. Lee, D.-S. Lee, and B.-G. Jin, “A new fault location
tion of fault location on transmission lines using traveling waves,” IEEE algorithm using direct current analysis for distribution system,” IEEE
Trans. Power Del., vol. 9, no. 2, pp. 680–689, Apr. 1994. Trans. Power Del., vol. 19, no. 1, pp. 35–41, Jan. 2004.
[3] Z. Xiangjun, K. K. Li, L. Zhengyi, and Y. Xianggen, “Fault location
using traveling wave for power network,” presented at the IAS Annu.
Meet., Seattle, WA, 2004.
[4] V. N. Gohokar and V. V. Gohokar, “Fault location in automated dis- Mohammad A. Mirzai received the B.Sc. degree in
tribution network,” in Proc. IEEE Power Eng. Transm. Distrib. Conf., electrical engineering from the Power and Water Uni-
2005, pp. 3898–3901. versity of Technology, Tehran, Iran, in 2002.
[5] H. Hizam and P. A. Crossley, “Single ended fault location technique He joined Sapta Co., Tehran, in 2004. Since 2006,
on a radial distribution network using fault generated current signal,” he has been a Project Manager and Research Engi-
Proc. Int. J. Eng. Technol., vol. 3, pp. 148–158, Sep 2006. neer in the Department of Electronics, Control and
[6] M. E. Hami, L. L. Lai, D. J. Daruvala, and A. T. Johns, “A new trav- Instrumentation of Niroo Research Institute, Tehran,
eling- wave based scheme for fault detection on overhead power distri- Iran. His current research interests include the appli-
bution feeders,” IEEE Trans. Power Del., vol. 7, no. 4, pp. 1825–1833, cation of fiber-optic technology and data communi-
Oct. 1992. cation in substation and powerplant automation, nu-
[7] A. A. Girgis, C. M. Fallon, and D. L. Lubkeman, “A fault location merical protection and control, intelligent electronic
technique for rural distribution feeders,” IEEE Trans. Ind. Appl., vol. devices, bay control units, fault locators, and event recorders in the distribution
29, no. 6, pp. 1170–1175, Nov./Dec. 1993. network.
[8] D. Novosel, D. Hart, and Y. Hu, “System for locating faults and esti-
mating fault resistance in distribution networks with tapped lads,” U.S.
Patent 5 839 093, 1998.
[9] Y. J. Ahn, M. S. Choi, S. H. Kang, and S. J. Lee, “An accurate fault Ali A. Afzalian (M’93–SM’06) received the B.Eng.
location algorithm for double-circuit transmission systems,” in Proc. and M.Sc. degrees in electrical engineering from
IEEE Power Eng. Soc. Summer Meeting, 2000, vol. 3, pp. 1344–1349. the University of Tehran, Tehran, Iran, in 1988 and
[10] R. Das, M. S. Sachdev, and T. S. Sidhu, “A fault locator for radial sub- 1991, respectively, and the Ph.D. degree in control
transmission and distribution lines,” in Proc. IEEE Power Eng. Soc. system engineering from the University of Sheffield,
Summer Meeting, 2000, vol. 1, pp. 443–448. Sheffield, U.K., in 1998.
[11] J. Zhu, D. L. Lubkeman, and A. A. Girgis, “Automated fault loca- He is a Faculty Member (Lecturer in 1991, As-
tion and diagnosis on electric power distribution feeders,” IEEE Trans. sistant Professor in 1998, and Associate Professor in
Power Del., vol. 12, no. 2, pp. 801–809, Apr. 1997. 2008) in the Department of Electrical Engineering of
[12] T. Takagi, Y. Yamakoshi, J. Baba, K. Uemura, and T. Sakaguchi, Shahid Abbaspour University of Technology, Tehran.
“Anew algorithm of an accurate fault location for EHV/UHV trans- His research interests include supervisory control of
mission lines: Part I—Fourier transform method,” IEEE Trans. Power discrete-event systems, fuzzy logic, neural networks, neurofuzzy systems, ge-
App. Syst., vol. PAS-100, no. 3, pp. 1316–1323, Mar. 1981. netic algorithms, as well as electrical power systems control and dynamics.

You might also like