Professional Documents
Culture Documents
Contents
1 Scope ................................................................ 2
2 Conflicts and Deviations .................................... 2
3 Applicable Documents ....................................... 2
4 Definitions and Abbreviations ............................ 3
5 Roles and Responsibilities ................................ 4
6 Criteria for Cleaning........................................... 8
7 Preparations for Chemical Cleaning ................ 10
8 Cleaning Selection........................................... 13
9 Hot Alkaline Cleaning ...................................... 18
10 Removal of Copper.......................................... 25
11 Acid Cleaning .................................................. 26
12 Neutralization and Passivation ........................ 41
13 Fire-Side Cleaning ........................................... 44
14 Evaluating Cleaning Performance ................... 45
15 Precautions and Preparations after Cleaning .. 46
Revision Summary .................................................. 47
1 Scope
1.1 This procedure defines the minimum requirements for cleaning of new and
existing steam generation systems such as steam generation equipment and heat
recovery steam generators (HRSGs), to remove internal and external
construction debris, including oil, grease and mill scale, prior to operation.
Refer to SAEP-1662 for cleaning of plant equipment and piping for all other
service fluids.
1.2 This procedure defines the responsibilities of the various departments involved
in chemical cleaning of new and existing steam generation systems. It outlines
methods to determine the need for chemical cleaning, the criteria for selecting
specific cleaning procedures, and the steps involved in various cleaning
procedure alternatives.
1.3 The scope of the procedure extends to all fired or waste heat, water tube, and
steam generation equipment and systems operating from 400 – 900 psig (27.5 –
62 barg). For steam generation equipment rated above or below these limits or
other steam generation equipment types, an individual cleaning program shall be
produced in consultation with Consulting Services Department, Material
Engineering Division, Corrosion Engineering Group (CSD/MED/CEG).
Any conflicts between this document and other applicable Mandatory Saudi Aramco
Engineering Requirements (MSAERs) shall be addressed to the EK&RD Coordinator.
Any deviation from the requirements herein shall follow internal company procedure
SAEP-302.
3 Applicable Documents
The equipment cleaning covered by this procedure shall comply with all Saudi Aramco
Mandatory Engineering Requirements and industry codes and standards, with particular
emphasis on the documents listed below. Unless otherwise stated, the most recent
edition of each document shall be used
NACE International
NACE TM 0169 Laboratory Corrosion Testing of Metals
NACE TM 0193 Laboratory Corrosion Testing of Metals in Static
Chemical Cleaning Solutions at Temperatures
Below 93°C (200°F)
Alkaline Solution: Solutions of a soluble base that has a pH greater than 7 such as
soda ash.
Blend Filling: A method of filling a vessel with chemical cleaning solution in which
the chemical concentrate (in liquid form) is metered into the filling line at such a rate as
to maintain the desired concentration level in the liquid entering the vessel.
M-Alkalinity: Methyl orange alkalinity which exists above the pH range of 4.2 to 4.4.
Mill Scale: A layer of iron oxide consisting of magnetite (Fe3O4) on the surface of hot
rolled steel.
5.1.1 Ensure the implementation of this procedure and compliance with all
requirements.
5.1.2 Facilitate and resolve any issues related to the implementation of this
Saudi Aramco: Company General Use
Page 4 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
The execution authority shall be the construction agency for new constructions,
while the plant maintenance shall be the execution authority for existing
facilities responsible to:
5.2.5 Ensure the implementation of this procedure and compliance with all
requirements.
5.2.7 Coordinate disposal of all waste water and chemical solutions as per
SAEP-327, SAES-A-103, and SAHWC.
5.2.8 Provide all resources and materials required to implement the hydrostatic
test and lay-up procedure, refer to SAEP-1026. This includes, but is not
limited to, installing temporary piping and equipment and providing
necessary labor.
5.2.11 Provide all records to SAPMT for each cleaning operation and shall be
included in the Project Records turnover to SAPMT at the project end.
The approval authority for new construction and existing facilities shall the
Engineering Superintendent (or his delegate). The approval authority or
proponent shall be responsible to:
5.3.1 Work with plant Maintenance to develop scope of work for obtaining
contractor’s services.
5.3.2 Prepare necessary operation procedures and advise the foreman of the
plant during the chemical cleaning of the equipment.
5.3.4 Perform a Job Safety Analysis as per Saudi Aramco Safety Management
Guide #06-003-2013.
5.3.5 Review and approve the cleaning procedures from Saudi Aramco
approved service providers.
5.3.6 Monitor the quality of the chemical cleaning fluids during the cleaning
activities.
5.3.10 Coordinate sampling and testing during cleaning activities with Area and
Regional Laboratories, if needed.
5.3.11 Maintain Log Sheets of cleaning operation. Typical log sheets include
what is shown in Appendix B, contractor's log sheets and the on-line
corrosion monitoring charts indicating corrosion rates vs. time, and any
other required parameters.
5.4.1 The inspection authority for new constructions shall be the responsible
Projects Inspection Division (PID)/Inspection Department (ID).
5.4.2 For existing facilities, the proponent's Operations Inspection shall be the
inspection authority. The inspection authority shall be responsible to:
Inspect equipment before and after cleaning.
Get and keep the corrosion monitoring records from the contractor.
Maintain history of equipment chemical cleaning and incorporate
relevant reports and data into permanent plant records.
Monitor corrosion using weight loss coupons or equivalent.
5.5.2 CSD shall only review and approve new chemical cleaning methods not
specifically discussed in this standard prior to starting the chemical
cleaning activities.
5.5.3 CSD shall certify new cleaning contractors and recertify existing ones.
5.6.1 Test, evaluate and verify new chemical cleaning products, corrosion
inhibitors effectiveness, and perform chemical analysis, if required.
5.6.2 The tests shall be conducted at the recommended chemical dilution ratios
and control parameters in terms of concentration, temperature, pH, and
duration as follows:
1. Corrosion Test
Test the chemical per NACE TM 0193 and NACE TM 0169 for
common materials of construction
2. Performance tests only for the cleaning products and corrosion
inhibitors:
To show the effectiveness of their applications
To determine the biodegradability of the products
5.7.2 Verify degree of cleanliness before and after passivation on cut boiler
tube samples.
The full list of contractor responsibilities are stated in the chemical cleaning
contract. Below are major responsibilities:
5.9.3 Clean the steam generation systems to meet or exceed the acceptance
criteria for effective cleaning as outlined in Section 14.
5.9.5 Dispose of all waste water and chemical solutions as per SAEP-327,
SAES-A-103, and SAHWC.
5.9.6 Submit a final chemical cleaning report upon completion. The report
shall include, but is not limited to, implemented cleaning procedure(s),
cleaning log sheets, findings, cleaning parameters, and lessons learned.
6.1 The following are steps to determine the need to conduct chemical cleaning for
existing steam generation systems:
Saudi Aramco: Company General Use
Page 8 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
6.1.1 Based on cut out boiler tube samples, the following criteria shall be used
for existing boilers to determine when to schedule chemical cleaning
steam generation equipment rated from 400 – 900 psig (27.5 – 62 barg).
The tube section removal and scale density evaluation shall be as per
ASTM D3484-14.
6.1.2 The above recommendations do not consider the scale composition such
as its copper content, scale insulating properties, condition of the steam
generation equipment and hence are conservative. Operations
Engineering may recommend chemical cleaning sooner or later than the
time table given above, if information is available to support it.
6.1.3 Equipment rated 400 – 900 psig (27.5 – 62 barg) shall not exceed eight
(8) years of operation without conducting chemical cleaning.
6.2 For all new steam generating equipment, a thorough inspection shall be
conducted before-cleaning in order to determine the most appropriate cleaning
procedure even though the equipment was cleaned at the manufacturer’s facility.
6.2.1 For all new steam generating equipment, the solvent cleaning
procedure shall be based on the use of inhibited ammoniated citric acid.
The inhibited ammoniated citric acid cleaning procedure detailed in this
procedure is safe and cost-effective for the removal of mill scale.
6.2.3 After cleaning, the boiler tubes, the superheater tubes, the reheater tubes,
and the economizer tubes shall be inspected visually. Remote video
boroscope inspection before cleaning and after cleaning will ensure the
Saudi Aramco: Company General Use
Page 9 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
7.1.2 High Pressure Water Jetting uses targeted water jetting, and water
flushing to remove all loose scale and/or deposits. See SABP-A-051 for
more details.
7.1.3 Hot Alkaline Cleaning is used to remove oil, grease and for enhancing
the effectiveness of the acid cleaning stage.
7.2.1 Remove all steam separators including cyclones, baffle plates, etc., and
screens from the steam drum. Remove angle iron covering and drum
blowdowns. Identify and make available all permanent piping and other
necessary steam generation equipment for cleaning.
7.2.3 Install blinds, and adequately sized temporary drain valves, and vents to
permit rapid dumping of solvents. Use temporary plugs or slip blinds to
Saudi Aramco: Company General Use
Page 10 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
7.2.4 Store all chemicals needed for the procedure on-site prior to
commencing cleaning, including emergency neutralizing agents,
nitrogen, and wet layup chemicals.
7.2.7 Install fittings for liquid sampling, flow elements, temperature probes,
and pipe spools with on-line access fittings for corrosion monitoring
probes. Use two monitoring locations: in the solvent pump outlet line,
downstream of the flow reversal and mixing manifold; and in the solvent
outlet line leading to the recirculating pump inlet. Install corrosion
coupons in the steam and water drums.
7.2.9 Plan for the disposal of wastewater and spent chemical solutions per
SAEP-327, SAES-A-103, and SAHWC.
7.2.10 Perform checks on valve lineups as required for each major flush and
circulation path.
7.2.12 Remove level gauge and install a temporary gauge (if ammonium
bifluoride is to be added, use transparent Tygon tubing for level
measurement as glass will be etched by it) on the steam drum to cover
the maximum level on the steam drum upper manifold.
7.2.13 Remove existing safety relief valves from the steam drum. Fit a
temporary vent in the place of a displaced relief valve on the steam
drum. The vent size should be adequate to handle the evolved gas.
Saudi Aramco: Company General Use
Page 11 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
Install blinds on other relief valve fittings. Provide 150 psig (10.3 barg)
relief protection through temporary or sacrificial relief piping during
steam generation equipment cleaning. Ensure that the temporary vent
has a block valve adjacent to the steam drum, and the vent pipe work
extends to the sewer.
7.2.14 Ensure required amount of 80 psig (5.5 barg) nitrogen supply is available
in the cleaning area. Provide adequate nitrogen supply to drain the steam
generation equipment at least three times.
7.2.15 Calculate the total cross sectional area of the steam generation equipment
tubes.
Commentary Note:
7.2.16 Test steam generation equipment hydrostatically at 100 psig (6.9 barg) or
1.5 times the pump discharge pressure whichever is lower, after
installation of all temporary piping and connections, prior to chemical
cleaning.
7.2.17 Get a sufficient supply of grooved wooden plugs, blinds or other suitable
devices and use these to restrict preferential flow paths, to force
circulation uniformly through all the steam generation equipment tubes
during solvent cleaning, neutralization, and passivation.
7.2.19 Ensure spare pumps are available in case of circulating pump failure, and
sufficient pumping capacity to drain the cleaning solution within fifteen
to thirty minutes in case of an emergency. Ensure sufficient holding tank
capacity is available for draining and neutralizing cleaning solutions if
necessary.
7.2.20 Ensure, using standard samples, that on-site chemical analytical procedures
and laboratory analytical procedures yield comparable (±20%) results.
Saudi Aramco: Company General Use
Page 12 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
7.2.21 Ensure inhibitor to be used are compatible with the acid used. Test for
corrosion inhibitor effectiveness prior to injecting the acid into the steam
generation equipment. Refer to CSD/MED/Corrosion Engineering
Group for the approved list of corrosion inhibitors.
7.2.22 Measure the volume of the steam generation equipment by filling and
draining with condensate water by a flow meter installed in the drain,
and compare the volume readings to the steam generation equipment
data sheet. This volume shall be used to calculate the amount of
chemicals required for each stage. Moreover, this exact volume will be
used to calculate the amount of deposits that were removed from the
steam generation equipment tube internals.
8 Cleaning Selection
8.1.3 With these criteria satisfied, make the final selection, with due reference
to other constraints including cost, disposal problems, and cleaning time
available. Responsibility for the final specification of the cleaning stage
is defined in Section 5.
8.1.4 Chemical cleaning will normally involve one or more of the following
steps: hot alkaline degreasing (see Section 9), removal of copper (see
Section 10), acid cleaning (see Section 11), followed by neutralization
and passivation stage (see Section 12). Laboratory evaluation of tube
Saudi Aramco: Company General Use
Page 13 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
samples will determine the above sequence. High Pressure Water Jetting
could be utilized before or it may follow the cleaning operation to
remove loosened scale (see SABP-A-051). If high pressure water jetting
is used, it must be followed by flash rust removal and passivation per
Section 12.3. Remote fiber scope inspection recorded on a video tape,
before and after cleaning will provide visual evidence on cleaning
effectiveness.
8.2.1 General
This figure represents the weight percentage of the dry scale which can
be removed by heating the insoluble residue to 600°F (315°C) in a
laboratory furnace. The result is indicative of the organic content of the
scale in the forms of oil, grease, degraded polymers, and carbon. If the
figure is high (greater than 10.0%) further identification of the organic
content can be determined by refluxing the sample with a suitable
organic solvent which will indicate the relative proportions of (i) oil and
grease, and (ii) carbon. These proportions will assist in the selection of a
suitable hot alkaline cleaning stage.
This figure represents the weight percent of the dry scale which will
dissolve in boiling 7.5% inhibited hydrochloric acid. By comparing this
figure with others from different steam generation equipment, some
indication of the degree of difficulty which the scale removal will
present can be obtained.
This figure represents the insoluble complexes of other cations and, if the
quantity is significant (i.e., greater than 2.0%) further cleaning stages
with more concentrated hydrochloric acid may be required to render the
material soluble.
8.2.5 Silica
8.2.6 Metals
The metal ions present in the scale, are analyzed for iron (Fe), copper
(Cu), calcium (Ca), magnesium (Mg), zinc (Zn), manganese (Mn)
and sodium (Na). These results are useful to determine the need for
pre-treatment for copper removal, and the number of acid cleaning stages
that are likely to remove all the scale from the system.
8.2.7 Anions
8.3.1 If the solubility of organic deposits (i.e., oil, grease, carbon, or other
organic compounds) is >70% in the proposed acid cleaning solvent, then a
separate hot alkaline stage is not required; however, a surfactant shall be
added. Otherwise, a separate hot alkaline cleaning stage shall be used.
8.3.3 Caustic degreasing (NaOH) is the cleaning stage used for all new steam
generation equipment, and where mill scale is present, or organic
contamination is 5% to 25% (see Section 9.3).
the calcium sulfate amount is > 10.0% by weight (see Section 9.5).
Inhibited hydrochloric acid is the most widely used cleaning agent since
it produces good solubility with a wide variety of scales, is economic,
and easy to handle. It exhibits good corrosion characteristics when
correctly inhibited and the process is controlled within the accepted
limits. The process is flexible and can be modified to complex copper by
the addition of thiourea, enhance silica removal by the addition of
ammonium bifluoride, or to remove organics by the addition of
surfactants. It is not compatible with stainless steels.
Sulfuric acid is an effective solvent for iron oxides, iron sulfides and is
generally lower in cost than hydrochloric acid. It is also compatible with
austenitic stainless steels. However, it is considerably more dangerous to
handle. In its concentrated form, it is aggressive to organic material, and
contact with the skin or eyes is extremely dangerous. Its use is not
recommended where scales contain significant calcium, due to the
formation of insoluble calcium sulfate.
stage will give some protection to the metal surfaces. If internal surfaces have
been allowed to rust following acid cleaning, this rusting is removed by citric
acid, and ammonia and sodium nitrite, are added later to achieve a high degree
of passivation (see Section 12).
9.2.2 Testing
The solution can react violently with acids. Heating the solution will
expand its volume. Be prepared to open drain valves to maintain desired
levels.
9.2.4 Procedure
1. Verify volume of boiler to appropriate level by filling and draining.
Install a flow meter in the drain to measure the volume of the boiler.
2. Dissolve the chemicals externally and blend fill through the chemical
feed connection. Fill the boiler to a sufficiently high level to ensure
adequate cleaning solvent contact with the contaminated metal
surfaces. Do not raise the solvent levels to the superheater inlets,
unless the superheater is isolated with a blind.
3. Confirm the drum level in the level gauge and prepare for firing
after the boil out solution has been added. Operate the temporary
vent, and drain valves as required.
4. Water fill (wedge) superheaters and feed slowly with condensate
through a valve on its outlet header. Leave open superheater vent
valves and a small amount of steam should escape to assure that the
superheater is water cooled during boil out. The drum water level will
rise during this period and blowdown should be restricted to the
amount necessary to maintain the desired water level.
5. Fire the boiler to bring the pressure up to 60 psig (4.1 barg).
Hold the pressure between 30 - 60 psig (2.0 – 4.1 barg) for four
hours, observe the temperature of lower headers for an indication of
circulation.
6. After four hours, shut down. Allow the boiler pressure to decrease.
After the pressure has dropped noticeably, blowdown the boiler
using all bottom blowdown valves, operating them in sequence.
Blow down approximately 50 mm on the gauge glass. Restore the
alkaline boil out solution level to normal with condensate after the
blowdown.
For relatively light oil contamination without heavily carbonized oil the
process may be carried out at 195°F (90°C ± 5°C) without firing the
boiler. In such cases, maintain circulation at 1,200 liters/minute to
4,500 liters/minute, using chemical cleaning pumps.
9.3.2 Testing
9.3.4 Precautions
9.3.5 Procedure
9.4.2 Testing
9.4.4 Precautions
9.4.5 Procedure
1. Verify volume of boiler to appropriate level by filling and draining.
Install a flow meter in the drain line to measure the volume of the
boiler.
2. Dissolve the chemicals externally and blend through the chemical
feed connection. Blend fill the boiler to a sufficiently high level to
ensure adequate cleaning solvent contact with contaminated metal
surfaces.
3. Do not raise solvent level to the superheater inlets, unless the
superheater is isolated with a blind.
4. Confirm the drum level in the level gauge and prepare for firing after
the boil out solution has been added. Bypass the low-low (LL) level
switch and operate drain and vent valves to maintain proper level.
5. Water fill (wedge) superheaters and feed slowly with condensate
through a valve on its outlet header. Leave open superheater vent
valves and a small amount of steam should escape to assure that the
superheater is water cooled during boil out. The drum water level
will rise during this period and blowdown should be restricted to the
amount necessary to maintain the desired water level.
9.5.2 Testing
9.5.4 Procedure
1. Verify volume of boiler to appropriate level by filling and draining.
2. Dissolve the chemicals externally and blend through the chemical
feed connection. Blend fill the boiler to a sufficiently high level to
ensure adequate cleaning solvent contact with contaminated metal
surfaces.
3. Do not raise solvent level to the superheater inlets, unless the
superheater is isolated with a blind.
4. Confirm the drum level in the level gauge and prepare for firing
after the boil out solution has been added. Bypass the low-low (LL)
level switch, and operate temporary drain and vent valves to
maintain proper level.
5. Water fill (wedge) superheaters and feed slowly with condensate
through a valve on its outlet header. Leave open superheater vent
valves and a small amount of steam should escape to assure that the
superheater is water cooled during boil out. The drum water level
will rise during this period and blowdown should be restricted to the
amount necessary to maintain the desired water level.
6. Fire pilot burners to bring the water to desired temperature range.
Alternatively, raise temperature by external heating. Circulate, using
chemical cleaning pumps. Monitor the carbonate concentration.
7. Drain the boiler solution into a holding tank.
8. Back flush superheater with condensate for 5 minutes, unless the
superheater is isolated with a blind.
9. Following complete draining of alkaline solution, fill the boiler to
the level given in step 3 with condensate heated to 170°F (77°C) to
rinse. Drain the boiler and repeat the rinse.
10. Proceed with solvent cleaning.
10 Removal of Copper
If the copper concentration in the scale deposit is greater than 10.0%, a separate treatment
is necessary to dissolve copper as much as possible before solvent cleaning. Make an
estimate of copper to be removed from the scale analysis and use the following alkaline
treatment, to reduce the copper level below 10.0%. Other alkaline treatments with
ammonium carbonate, ammonium bromate, and sodium nitrite are also acceptable for the
removal of copper >10.0%, after review by CSD/MED/Corrosion Engineering Group and
R&DC. Repeated copper removal and solvent cleaning is required if copper is in layers
between other deposits. Any copper remaining in the boiler is removed during the solvent
cleaning and passivation procedures described in Section 11 and Section 12.3.
10.1.2 Testing
10.1.3 Procedure
1. Fill the boiler with hot condensate, to the top of the steam drum.
2. Drain back appropriate amount of water to waste to accommodate
aqua ammonia, premixed ammonium bicarbonate solution and air
injection. Verify drain back volume by turbine flow meter on the
waste line.
3. Inject aqua ammonia into the mud drum through the chemical feed
nozzle attached to the temporary mud drum nozzle connections.
Inject condensate to flush the chemical into the boiler.
4. Inject premixed solution containing ammonium bicarbonate into
the boiler through the chemical feed nozzle attached to the
temporary mud drum nozzle connections.
Saudi Aramco: Company General Use
Page 25 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
5. Ensure that the vents on top of the steam drum are cracked open
before air or oxygen injection begins to allow air or oxygen to exit
the boiler. Begin air or oxygen injection at a minimum flow rate
of 1.5 standard cubic meters/minute through both the side wall
headers, and into both ends of the mud drum. Alternatively, shut
in each end of the boiler to ensure even coverage/contact of air or
oxygen to both the front, and the back of the system every hour.
6. Begin analysis procedure for copper one hour after the
introduction of air or oxygen into the system. Test for copper
every hour thereafter, continue to alternate air or oxygen flow
between the front, and the back of the lower headers every hour.
Ensure that 1.5 standard cubic meters/minute air flow rate is
maintained. When the copper concentration levels out, as
indicated by analytical methods, drain the boiler to waste under
30 – 40 psig (2.1 – 2.8 barg) air pressure to allow for a quick drain
of the system, and to aid in the removal of any solids present in
the mud drum.
7. While maintaining a nitrogen cap in the boiler, flush the system
with the cold fill make up water until the outlet water stream is at
or near the pH of the make-up water.
8. Open the mud and steam drum man ways, hose down the drums
and all tubes and inspect.
11 Acid Cleaning
Following removal of organic material, and excess copper by hot alkaline treatment,
solvent cleaning is carried out to remove iron oxides, water borne scales, remaining
copper, and silica. The solvents are selected as noted in Section 8.3. Copper in the
scale below 10%, is easily removed by complexing it with thiourea during HCl acid
cleaning or by other solvents as described in this paragraph.
Although the solvent concentrations listed encompass most cleaning operations, there
may be instances where higher acid, inhibitor and ammonium bifluoride concentrations
may be beneficial. To assist in removal of moderate amount of copper (<10%), thiourea
can be used up to 1.0% concentration without excessive corrosion if a proper inhibitor
is used. Extended contact times may be required than those specified for removing
certain heavy and hard to remove deposits.
Commercial grade quality for all chemicals in this paragraph is adequate. The solvent
solution must not contain greater than 100 mg/L of iron in the concentrated form.
Where austenitic materials are present in the system to be cleaned the total chlorides of
all the chemicals in the mixture must not yield a final solution containing greater than
50 mg/L as chloride.
Perform a hydrostatic pressure test on the system, including all temporary piping, hoses,
fitting etc. at 1.5 times the pump discharge pressure before solvent addition.
11.1.2 Testing
Before adding the acid to the boiler verify its corrosion rate at 180°F
(82°C) by LPR for inhibitor effectiveness. During circulation monitor
the solution for acid, total iron and copper concentrations, corrosion
rate, temperature and inhibitor effectiveness. Take samples at
30 minute intervals, or more frequently. Perform analyses as rapidly as
possible and preferably on-site.
11.1.4 Precautions
11.1.5 Procedure
1. Replace all permanent valves which will come in contact with
acid, with “sacrificial” valves. These include all blowdown and
chemical feed valves. Others, such as boiler feed, can be
protected by blinds. If “sacrificial” valves are not available, keep
new valves on hand for replacing all valves contacted by acid
during the cleaning procedure.
2. Fill the boiler with condensate to the top of the steam drum
eliminating all air in the system. If the condensate is sufficiently
hot, circulate by chemical cleaning pumps to achieve uniform
metal temperatures throughout the boiler, and adjust to 140 –
158°F (60 – 70°C). If the condensate is not at a high enough
temperature, fire the boiler, or use an external heat exchanger, or
inject steam, to obtain temperature and adjust by circulation.
Approach metal temperatures from below because of the uneven
rate of cooling between the thin walled tubes and thick wall drums
and headers. All furnace openings and dampers must be closed to
retain the heat.
3. Bubble nitrogen at 1 m³/hr using a PVC pipe into the acid tanks
for at least 2 hours. This is to strip the oxygen, and mix
thoroughly the acid and inhibitor in the tank.
4. Using nitrogen drain back sufficient volume to accommodate acid
and inhibitor. Check inhibitor effectiveness in the acid on-site.
As quickly as possible, blend fill the boiler with inhibited acid
solution. Blend a slightly higher concentration during the
beginning of the fill than at the end because the initial acid
entering the boiler is consumed to some degree during the fill.
Ammonium bifluoride may be added in concentrations up to 1.0%
by weight to assist in the removal of silica. In the absence of
11. Fill the boiler with hot condensate mixed with 50 to 100 kg of soda
ash to a level slightly higher than the acid level (not out of sight in
the level gauge). Drain the boiler under nitrogen as before and refill
with condensate, for a second rinse. Drain the second rinse under a
positive nitrogen pressure. Soda ash may have to be added to the
solution drained directly into the sewer, to ensure that its pH is
above 7. When no repeat solvent cleaning is required (see step 12
below) add about 0.1% by weight of citric acid to the second rinse
to assure more thorough iron removal.
12. If the acid is drained because of any one of the three reasons cited
in step 5 above, i.e., iron level >10,000 mg/L or acid strength <3%
or corrosion rate >600 mpy for 15 minutes, open the mud drum
and remove sludge and solids, water flush to clear drains and
repeat steps 1 to 9 above.
Commentary Note:
Residence Time
Iron removal phase 4 to 8 hours
Copper removal and 4 to 8 hours
passivation phase
Total dissolved Iron 10,000 mg/L max.
Circulation Rate 1,200 liters/minute to 4,500 liters/minute
Max. Corrosion Rates <600 mpy
11.2.2 Testing
11.2.4 Precautions
11.2.5 Procedure
1. Replace all permanent valves which will come in contact with
acid, with “sacrificial” valves. These include all blowdown and
chemical feed valves. Others, such as boiler feed, can be
protected by blinds. If “sacrificial” valves are not available, keep
new valves on hand for replacing all valves contacted by acid
during the cleaning procedure.
11.3.2 Testing
1. Before adding the acid to the boiler verify its corrosion rate
at 300°F (149°C) by LPR for inhibitor for effectiveness.
Take samples every 30 minutes or more frequently.
Iron Removal Phase
2. Monitor pH, EDTA and iron concentration, corrosion rate, and
temperature.
Copper Removal and Passivation Phase
3. Monitor pH, EDTA and copper concentration and temperature.
11.3.3 Precautions
11.3.4 Procedure
1. Replace all permanent valves which will come in contact with
EDTA, with “sacrificial” valves. These include all blowdown and
chemical feed valves. Others, such as boiler feed, can be
protected by blinds. If “sacrificial” valves are not available, keep
new valves on hand for replacing all valves contacted by EDTA
during the cleaning procedure.
2. Iron removal phase: Fire boiler to 300°F (149°C), inject inhibitor
and circulate for 1 to 2 hours to uniformly coat the metal surface
with inhibitor. Inject concentrated solution of EDTA, to provide a
10.0% solution in the boiler. Stop firing when the temperature
stabilizes.
3. Allow the temperature to decay to 250°F (121°C). Monitor iron
and EDTA concentrations and pH. Maintain a pH of 9 to 9.5.
If the free EDTA concentration drops below 1.0% inject more
EDTA to restore the concentration to 3.0%.
4. Fire boiler again to reach 300°F (149°C) and repeat step 3 until iron
11.4.2 Testing
Before adding the acid to the boiler verify its corrosion rate at 180°F
(82°C) by LPR for inhibitor effectiveness. During circulation monitor
the solution for acid, total iron concentration, corrosion rate,
Saudi Aramco: Company General Use
Page 35 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
Sulfuric acid is a strong mineral acid, and must be handled with care,
particularly in the concentrated form. Considerable heat is evolved
during dilution, and all mixing must be carried out with extreme caution.
11.4.4 Precautions
11.4.5 Procedure
1. Replace all permanent valves which will come in contact with
acid, with “sacrificial” valves. These include all blowdown and
chemical feed valves. Others, such as boiler feed, can be
protected by blinds. If “sacrificial” valves are not available, keep
new valves on hand for replacing all valves contacted by acid
during the cleaning procedure.
2. Fill the boiler with condensate to the top of the steam drum
eliminating all air in the system. If the condensate is sufficiently
hot, circulate by chemical cleaning pumps to achieve a uniform
metal temperatures throughout the boiler, and adjust to 158°F
(70°C).
the level gauge). Drain the boiler under nitrogen as before and refill
with condensate, for a second rinse. Drain the second rinse under a
positive nitrogen pressure. Soda ash may have to be added to the
solution drained directly into the sewer, to ensure that its pH is
above 7. When no repeat solvent cleaning is required (see step 11
below) add about 0.1% by weight of citric acid to the second rinse
to assure more thorough iron removal.
11. If the acid is drained because of any one of the three reasons cited
in step 5 above, i.e., iron level >10,000 mg/L or acid strength <3%
or corrosion rate >600 mpy for 15 minutes, rinse the boiler with
condensate, open the mud drum and remove sludge and solids,
water flush to clear drains and repeat steps 1 to 9 above.
11.5.2 Testing
Before adding the acid to the boiler verify its corrosion rate at
149°F (65°C) by LPR for inhibitor for effectiveness. Take samples at
30 minute intervals, or more frequently. Perform analyses as rapidly as
possible and preferably on-site.
11.5.3 Precautions
11.5.4 Procedure
1. Replace all permanent valves which will come in contact with
acid, with “sacrificial” valves. These include all blowdown and
chemical feed valves. Others, such as boiler feed, can be
protected by blinds. If “sacrificial” valves are not available, keep
new valves on hand for replacing all valves contacted by acid
during the cleaning procedure.
2. Fill the boiler with condensate to the top of the steam drum
eliminating all air in the system. If the condensate is sufficiently
hot, circulate by chemical cleaning pumps to achieve uniform
metal temperatures throughout the boiler, and adjust to 140°F
(60°C). If the condensate is not at a high enough temperature, use
an external heat exchanger, or inject steam, to obtain temperature
and adjust by circulation. It is necessary to approach metal
temperatures from below because of the non-uniform rate of
cooling between the thin walled tubes and thick wall drums and
headers. All furnace openings and dampers must be closed to
retain the heat.
3. Using nitrogen drain back sufficient volume to accommodate acid
and inhibitor addition. Check inhibitor effectiveness in the acid
on-site. Blend inhibited acid solution into the boiler as quickly as
possible. It is good practice to blend a slightly higher
concentration during the beginning of the fill than at the end
because the initial acid entering the boiler is consumed to some
degree during the fill.
4. Back flush superheater with condensate for 5 minutes, unless the
superheater is isolated with a blind.
5. Circulate solution using chemical cleaning pumps. Reverse flow
direction every hour using flow reversal manifold. Continue
circulation to ensure that the various sections of the boiler are
circulated in turn, e.g., side walls, downcomers, etc., using valves
on lower header and drum connections. This is essential in order to
achieve good cleaning, reduce corrosion, and maintain uniform
Saudi Aramco: Company General Use
Page 39 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
and remove sludge and solids, water flush to clear drains and
repeat steps 1 to 9 above.
Immediately after solvent cleaning and rinsing of the boiler, the final step is
neutralization and passivation of the freshly cleaned surfaces using any one of the
procedures given under sections 12.1 to 12.3. Use commercial grade quality for all
chemicals in this paragraph except where austenitic materials are present in the system
to be cleaned, the total chlorides of all the chemicals in the mixture must not yield a
final solution containing greater than 50 mg/L as chloride.
Following the neutralization step, perform video boroscope inspection in boiler tubes to
determine whether another acid stage or high pressure water jetting is required.
Also perform video boroscope inspection following the high pressure water jetting to
determine its effectiveness in removing the scale and if more jetting is required before
moving to the passivation stage.
12.1 Carbonate
12.1.2 Testing
Sodium nitrite is a strong oxidizing agent and must be handled with care.
12.1.4 Precautions
12.1.5 Procedure
Blend fill the boiler to level slightly higher than the acid level with a
neutralizing and passivating solution.
Maintain the temperature at 190 – 200°F (88 – 93°C) for six hours and
circulate with chemical cleaning pumps. If necessary use an external
steam coil. At the end of the six hour period, drain the boiler under air
pressure. Open vents, mud and steam drums, and when the drum and
header temperatures fall sufficiently safe to allow entrance mechanically
remove all visible traces of water and loose material in the drums and
tubes using an industrial vacuum cleaner. Inspect internals for
completion of work.
12.2.2 Testing
Sodium nitrite is a strong oxidizing agent and must be handled with care.
12.2.4 Procedure
1. Blend fill the boiler to a level slightly higher than the solvent level
with the chemicals, and circulate by chemical cleaning pumps.
2. At the end of the six hour period, drain the boiler under air
pressure.
3. Open vents, mud and steam drums, and when the drum and header
Saudi Aramco: Company General Use
Page 42 of 50
Document Responsibility: Corrosion Control Standards Committee SAEP-1025
Issue Date: 1 January 2018
Next Planned Update: 16 October 2019 Chemical Cleaning of Steam Generation Systems
12.3.2 Testing
Monitor and maintain pH. Monitor dissolved iron, free citric acid
concentration, and corrosion rate during flash rust removal.
Sodium nitrite is a strong oxidizing agent and must be handled with care.
12.3.4 Procedure
Circulate until the iron level stabilizes while maintaining the free
citric acid concentration at 1% or above. Continue circulation and
cool to 122°F (50°C) by fan.
2. Add ammonia to get a pH of 9 to 9.5. Add 0.5% sodium nitrite.
Circulate for 6 to 8 hours. Drain under air pressure.
3. Refill boiler with hot condensate and drain under air pressure.
Open vents, mud and steam drums, and when the drum and header
temperatures fall sufficiently safe to allow entrance remove
mechanically all visible traces of water and loose material in the
drums and tubes using an industrial vacuum cleaner. Inspect
internals for completion of work.
13 Fire-Side Cleaning
13.1 Preparation
1. After neutralizing and cleaning immediate firing for drying out is mandatory.
2. Wear personnel protective equipment. See SABP-A-051 on the hazards of
steam generation equipment dust.
3. Sweep clean furnace side.
4. Keep open and clear all furnace and other fire-side drainage systems.
Remove all furnace refractory drain plugs and prove the drainage system is
clear.
5. Erect scaffolding in accordance with Saudi Aramco Construction Safety
Manual, Section 13 to enable those engaged in the cleaning to reach all
parts of the furnace and generating bank, including superheaters.
6. Seal all refractory and partially embedded tubes with bitumen if required to
protect the refractory.
7. Provide suitable pumping, distribution system, and storage for cooled
condensate water < 105°F (< 40°C) at the steam generation equipment.
13.2 Method
1. Mix the condensate water with 2 - 3% Soda Ash and 0.05 vol% wetting
agent. Keep the effluent water pH above 8.5 at all times during the
neutralizing and cleaning steps by checking the pH of samples from the
furnace drains.
2. Use the condensate water pressure, connect to a manifold, and inject the
mixed cleaning solution.
3. Keep all cleaning hose sizing ½ inch to ¾ inch, and suitably fitted with jets.
4. Keep a pressure of 116 psia (810 kPa) + 5% at the manifold, in the furnace.
5. During neutralizing and cleaning, do not use excessive water pressure to
prevent damage to the refractory.
6. Remove hard deposits manually rather than increasing pressure.
7. Man each cleaning hose with one operator.
8. Start neutralizing and cleaning at the highest point of each part to be cleaned.
9. Specially attend those areas where an accumulation of combustion deposits
are prone to gather, e.g., tube roots (top and bottom). Monitor and maintain
effluent in an alkaline condition.
10. Take care not to direct jet directly at refractory, or persons.
11. Do not allow water to build up a level in the furnace.
12. On completion of the neutralizing and cleaning, replace the furnace
refractory drain plugs, remove scaffolding and all equipment.
13. Close the furnace and fire the steam generation equipment on low flame to
dry out the furnace and burn off the protective coating from the refractory.
14. Shut off all drains when the steam generation equipment is on line.
14.1 Inspection
visually examine them, weigh them, and calculate the loss of metal thickness
(usually <25 microns) due to chemical cleaning (see SABP-A-036).
For boilers, the scale density shall be < 50 g/m2 of a cut out tube sample after
chemical cleaning.
15.2 Preparations for Putting the Steam Generation Equipment into Service
15.2.1 Procedure
Revision Summary
23 August 2011 Revised the Next Planned Update." Reaffirmed the content of the document, and reissued
with minor revision to ensure that only approved cleaning contractors should be contracted to
perform cleaning jobs.
18 June 2015 Editorial revision to change the primary contact and add list of appendices.
16 October 2016 Major revision to clarify and address gaps identified by the Standards Committee members.
Those gaps are outlined below:
a) Merge requirements from SAEP-1024 into SAEP-1025;
b) Include all related Saudi Aramco and International References;
c) Align Testing Requirements with International Standards NACE TM 0169, NACE TM 0193
and ASTM D3484;
d) Include New Section on Roles and Responsibilities;
e) Include New Section on Definitions and Abbreviations;
f) Clarify Criteria for Cleaning;
g) Clarify Criteria for Cleaning Performance; and
h) Relocate All Non-Mandatory Requirements to SABP-A-051 (new).
1 January 2018 Editorial revision to modify paragraphs 11.1.4, 11.2.4, 11.4.4, 11.5.3, 6.2.1, and Section 11
(2nd paragraph).
5 Control Parameters
Circulation rate, temperature limits, chemical concentrations, pH, M-alkalinity,
Fe, Cu, corrosion rate
Sketch of circulation path, showing locations of: pumps, control valves, chemical
injection, flow and temperature instruments, corrosion probes, vents, drains,
blinds, plugs
Waste disposal plan and approvals per SAEP-327, SAES-A-103, and SAHWC.
Chemical analysis procedures
Contractor safety manual
Contingency plans to handle piping leaks, pump failures, rescue from confined
spaces
Corrosion control methodology
Quality assurance and control procedures
Personnel assigned and their qualifications
Schedule of activities, start and end dates
6 Final Report
The contractor shall submit a final report to include the approved cleaning procedure,
all control parameters, log sheets, evaluating cleaning performance by Inspection, and
lessoned learned, etc.
7 Safety
Job safety analysis document
Material Safety Data Sheets (MSDS) for the cleaning chemicals