Image shown may not reflect actual configuration
ee
xo)
ay
renee
Bore — mm (in) 745 (6.7)
‘Stroke = mm (in) 762 (6.4)
Displacement — L (in?) 32.1 (1959)
Compression Ratio 15.0:1
Aspiration TA
Ful System EUI
Governor Type ADEM™ Aa
Continuous
ernie
Cs
1100280) | 1100.80) | 1000800) | arocvany | Cmdr Low Fuel Consumption
7260 (7000) | 1280 7000) | 100 (80) [eatin for Low Ful Consumption
Standard Features
Cat? Diesel Engine
+ Designed and optimized for low emissions or
low fuel consumption
+ Reliable and consistent performance proven in
thousands of applications worldwide
Generator Set Package
+ Accepts 100% block load in one step and meets
the NFPA 110 loading requirements
+ Conforms to ISO 8528-5 G3 load acceptance
requirements.
+ Reliability is verified through prototype
testing, which includes torsional vibration,
fuel consumption, oil consumption, transient
performance, and endurance testing
Alternators
+ Superior motor starting capability minimizes the
need for oversizing the generator
+ Designed to match the performance and output
characteristics of Cat diesel engines
Cooling System
+ Cooling systems available to operate in ambient
temperatures up to 50°C (12°F)
+ Tested to ensure proper generator set cooling
LeHEI211-04 |
EMCP 4 Control Panels
+ User-friendly interface and navigation
+ Scalable system to meet a wide range of
installation requirements
+ Expansion modules and site specific
programming for specific customer requirements.
Warranty
+ 24 months/1000-hour warranty for standby and
mission critical ratings
+ 12 months/unlimited hour warranty for prime
and continuous ratings
+ Extended service protection is available to
provide extended coverage options
Worldwide Product Support
+ Cat dealers have over 1,800 dealer branch
stores operating in 200 countries
+ Your local Cat dealer provides extensive
post-sale support, including maintenance and
repair agreements
Financing
+ Caterpillar offers an array of financial products
to help you succeed through financial service
excellence
+ Options include loans, finance lease,
operating lease, working capital, and revolving
line of credit
+ Contact your local Cat dealer for availability in
your region
Page 1 of 6
CATOptional Equipment
Engine
Air Cleaner
Single element
2 Dual element
Heavy duty
Muffler
1 Industrial grade (15 dB)
Starting
1 Standard batteries
1 Oversized batteries
1 Standard electric starter
1D Dual electric starter
1D Jacket water heater
Alternator
Output voltage
Q400v a 3300v
oatsv
Temperature Rise
(over 40°C ambient)
150°C
2. 125°C/130°C
O.405°¢
aoc
Winding type
Random wound
Form wound
Excitation
Self excited
internal excitation (IE)
Permanent magnet (PM)
Attachments
1 Anti-condensation heater
O Stator and bearing temperature
monitoring and protection
Power Termination
Type
Bus bar
O Circuit breaker
24008 800A,
212008 2 160A
220008 225004
230008 232008
QuL QlEC
A3-pole Q4-pole
‘OQ Manually operated
Electrically operated
Trip Unit
atsi — GLsiG
ALsIG-P
Factory Enclosure
A Weather protective
Sound attenuated
Attachments
Cold weather bundle
2G lighting package
LAC lighting package
A Motorized louvers
Fuel Tank
A Sub-base
1000 gal (3875 L)
1.2000 gal (7570 L)
1.3600 gal (13627 L)
Control System
Controller
QeMop 4.28
QeMop 4.3
QEMcp 4.4
Attachments
Local annunciator module
Remote annunciator module
Expansion 1/0 module
Remote monitoring software
Charging
U1 Battery charger — 108,
Vibration Isolators
Rubber
Spring
Seismic rated
Cat Connect
Connectivity
DEthemet
2 Cellular
a Satelite
Extended Service Options
Terms
22 year (prime)
23 year
25 year
2110 year
Coverage
a Silver
Gold
Platinum
Platinum Plus
Ancillary Equipment
Automatic transfer switch
(ATs)
Q Uninterruptible power supply
(UPS)
Paralleling switchgear
O Paralleling controls
Certifications
UIBC seismic certification
LEU Declaration of Conformity
Eurasian Conformity (EAC)
Note: Some options may not be available on al models. Certifications may not be available with al! mode! configurations
Consul factory for availabilty.
LeHe1211-04
Page 2 of 8C32 Diesel Generator Sets x -
Electric Power
Package Performance
41250 KVA Low Fuel Consumption
|
Pa
ee Nae
“maiNn levels ae corrected to §% O> Contact your local Cat dealer for futher information
LeHe1211-04 Page 3 ol 8C32 Diesel Generator Sets x -
Electric Power
Package Performance
1100 kVA Low Fuel Consumption
‘Gon set power rating with fan 280 kW 80 ekW 200 ek 725 ekW
‘Gen set power rating with fan @ 0.8 power factor | __1100KVA 1100 kVA 1000 KA, S10 KA
Fusing strategy Low Fuel Low Fuel Low Fuel Low Fuel
Performance number ‘Moest-02 | _emosa7-07 | _pMass2.05 | _DM99s3-071
oko)
100% load with fan — Ur (gal) 2254 (598) | 2264 (598) | 2067 (548) | 1895 (50.1)
75% toad with fan — Lie (ale) 703 (450) [703 so) | 1555 (41a) [1428 G77)
150% load with fan — Uhr (gan) vi74 (310) | 1974 (4.0) | 1088 (287) | 1004 (265)
25% load with fan — Line (gale) ea (183) | 694 (103) | 52 (17.2) | 608 (16.1)
Cito
Radiator air fow resticton (system) —KPa (n. water] 0.12 (048) | 0.12 (0.48) | 0.12 (048) | 0.12 (048)
ne |
Exhaust system backpressure (maximum allowable)
oe 67 ero) | 67 ero | 67 ero) | 67 ero)
Heat rejection to jacket water = KW (Btu) sia ister] ste (r8%67)] 300 (17054) | 261__(15996),
Heat rejection to exhaust (otal) — KW (Btu) 18 (aeste)| 818 ae5t8)| 757 __(4s047) | 698 9684)
Heat rejection to aercooler— KW (umn) set (ozeay[ ei (so2es)[ 140 (eet) | 125 (7788)
Heat ejection to atmosphere from engine —
ee 120 797) | 120 (6797) | 108 6150) | 102 (6819)
Heat rejection For alemator — KW (Btufmin
7 4 ares) | 1976) | 43 (aaa) | 38 (2163)
NOx mg/Nm? (g/hp-h)_ 2966.9 (5.84) | 2966.9 (5.84) | 2967.7 (5.84) | 2914.2 (5.76)
“img/Ni lvls are corocted to 5% 0. Contact your local Cat dealer for farther information
LeHEI211-04 Page 4 of 6C32 Diesel Generator Sets x -
Electric Power
Package Performance
41100 kVA Low Emissions
‘Gon set power rating with fan 280 kW 80 ekW 200 ek 725 ekW
‘Gen set power rating with fan @ 0.8 power factor 100 KA, 1100 kVA 1000 KYA, S10 KA
Fusing strategy Low Emissions | Low Emissions | Low Emissions | Low Emissions
Performance number ‘Mo04s-0¢ | ewoeae-oo | _pMoa46-o4 | _Dwgoa7-03
oko)
100% load with fan — Ur (gal) 243.2 (642) | 2432 (642) | 2242 (692) | 2030 (535)
75% toad with fan — Lie (ale) sea (48.6) | 1084 406) | s681 (444) [1549 (409)
150% load with fan — Uhr (gan) 7260 (933) | 1260 Ga.) | 1182 _@o4) | 1061 (28.0)
25% load with fan — Line (gale) vos (87) | 709 (187) | 59 (ira) | 615 (162)
Cito
Radiator air fow resticton (system) —KPa (n. water] 0.12 (048) | 0.12 (0.48) | 0.12 (048) | 0.12 (048)
ne ee
Exhaust system backpressure (maximum allowable)
oe 67 ero) | 67 ero | 67 ero) | 67 ero)
Heat rejection to jacket water = KW (Btu) si2_ 7723) 312 _(r7723)] 288 (16392)| 266 (18109)
Heat rejection to exhaust (otal) — KW (Btu) 951__(S4087)| 95% 4087)[_ 81 (S0080) | 80% (45572)
Heat rejection to aercooler— KW (umn) 253__(14386)| 259 (14086)| 225 _(T2680)| 179 (70754)
Heat ejection to atmosphere from engine — 7 , 7
toca 107 6077) | 107 (eo77) | 107 (6081) | 104 (5013)
Heat rejection For alemator — KW (Btufmin
7 4 ares) | 1976) | 43 (aaa) | 38 (2163)
“img/N levels are corected to 5% 0. Contact your focal Cat dealer for further information
LeHEI211-04 Page 5 of 6Weights and Dimensions
Mission Critical | Prime | Continuous ee een
pv) EVN a NM) mrp || co eS
1100 (880) | 1100 (880) | 1000 (800)| 910 (728) | 4165 (164.0)| 1684 (66.3) | 2162 (85.1) | 6668 (14,700)
1260 (1000){ 1250 (1000) [1100 (@80)| [4350 (171.3)| 1684 (66.3) [2162 (86.1) [6985 (15,400)
Note: For reference only. De not use for instalation design. Contact your loca Cat dealer fr precise weights and dimensions
Ratings Definitions
Standby Applicable Codes and Standards
‘Output available with varying load for the duration of
the interruption ofthe normal source power. Average
power output is 70% of the standay power rating. Typical
‘operation is 200 hours per year, with maximum expected
sage of 500 hours per year.
Mission Critical
‘Output available with varying load for the duration of
the interruption ofthe normal source power. Average
power output is 85% of the mission ertical power rating
Typical peak demand up to 100% of rated power for
Lp to 5% of the operating time. Typical operation is
200 hours per year, with maximum expected usage of
'500 hours per year.
Prime
(Output available with varying load for an unlimited time.
‘Average power output is 70% of the prime power rating
Typical peak demand is 100% of prime rated ekW
with 10% overload capability for emergency use for a
‘maximum of 1 hour in 12, Overload operation cannot
exceed 25 hours per year.
Continuous
(Output available with non-varying load for an unlimited
time, Average power output is 70-100% of the
Continuous power rating. Typical peak demand is 100%
of continuous rated kW for 100% of the operating hours.
32 PGDG, 632 PGB!
LEHE1211-0¢ (1719)
‘AS1359, CSA C22.2 No100-04, UL142, UL489, UL8S9,
UL2200, NFPA37, NFPA70, NEPASS, NFPA110, IBC,
1EC60034-1, 1803045, 1S08528, NEMA MG'.22,
NEMA MG1'33, 2014/35/EU, 2008/42/EC, 2014/30/EU,
Note: Codes may not be available in all model
configurations. Please consult your local Cat dealer for
availabilty.
Data Center Applications
Tier lllTier IV compliant per Uptime Institute
requirements, ANSV/TIA-942 compliant for Rated-4
through Rated-4 data centers.
Fuel Rates
Fuel rates are based on fuel oll of 35° API [16°C (60°F)]