Foreword
Weichai Heavy Machinery Co., Ltd. is China’s appointed manufacturer of
various types of stationary gen-set and marine gen-set.
Contents
CHAPTER I CODE REPRESENTING METHOD ................................................. - 5 -
CHAPTER II WORKING CONDITIONS ............................................................... - 5 -
I. RELIABLE WORKING CONDITIONS .............................................................. - 5 -
II. WORKING CONDITIONS FOR GEN-SET TO OUTPUT RATED POWER ... - 2 -
CHAPTER III TECHNICAL SPECIFICATIONS AND MAIN PARAMETERS ... - 2 -
I. MAIN TECHNICAL SPECIFICATIONS ............................................................. - 2 -
II. MAIN ELECTRICAL PERFORMANCE INDICATORS................................... - 2 -
III. GEN-SET PROTECTION PARAMETERS ....................................................... - 3 -
IV.OVERALL DIMENSIONS OF GEN-SET ...................................................... - 4 -
V. GEN-SET OUTLINE DRAWING ....................................................................... - 4 -
CHAPTER IV OVERVIEW OF MAIN STRUCTURES ......................................... - 6 -
I. DIESEL ENGINE .............................................................................................. - 6 -
II. AC ALTERNATOR .............................................................................................. - 7 -
III. INSTRUMENT BOX ......................................................................................... - 8 -
IV. SOLID BASE FRAME ....................................................................................... - 8 -
CHAPTER V STORAGE AND INSTALLATION .................................................. - 8 -
I. STORAGE ............................................................................................................. - 8 -
II. UNPACKING ACCEPTANCE ............................................................................ - 8 -
III. LIFTING & HANDLING ........................................................................... - 9 -
IV. INSTALLATION ................................................................................................ - 9 -
1. Installation of gen-set external pipes .................................................................... - 9 -
2. Installation of vent-pipe ...................................................................................... - 10 -
3. Installation of fuel pipes...................................................................................... - 11 -
4. Installation of cooling pipes ................................................................................ - 12 -
5.Installation of starting system ........................................................................... - 13 -
6. Other requirements.............................................................................................. - 13 -
CHAPTER VI GEN-SET ELECTRICAL SYSTEM ............................................. - 14 -
I. INSTRUMENT BOX .......................................................................................... - 14 -
1. Local ordinary instrument box ............................................................................ - 14 -
2. Local self-starting instrument box ...................................................................... - 18 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
CCF × ×
-2-
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
No.
Steady-state voltage regulation
1 ±2.5% (for emergency gen-set ±3.5%)
factor
Transient voltage regulation
2 -15% transient voltage regulation factor +20%
factor
3 Voltage stabilization time 1.5s
4 Voltage fluctuation ratio ±1%
5 No-load voltage setting range ≥±5% rated voltage
Steady-state speed regulation Electronic speed regulation 3%/(mechanical speed
6
factor regulation 5%)
Transient speed regulation
7 ±10%
factor
8 Stabilization time 5S
9 Speed fluctuation ratio ±0.5%
110% rated load operating for 1 hour is allowed by gen-set continuously running for each
10
12 hours
Two gen-sets can maintain long-term stable parallel operation. It can maintain stable
operation and steadily transfer active power and reactive power when the load varies
11 within 20%-100% of total rated power against rated power factors; the active power
sharing unbalance is not greater than 15% of alternator’s rated power and reactive power
sharing unbalance is greater than 10% of alternator’s rated reactive power.
Serial
Alarm description Alarm value Remarks
No.
110% rated
1 Speed is high Alarming
speed
2 Oil pressure is low 0.12±0.02Mpa Alarming
3 Water temperature is high 95+3C Alarming
4 Oil temperature is high 102+3C Alarming
5 Speed is too high 115% rated speed Alarming and shutdown
6 Oil pressure is too low 0.08±0.02Mpa Alarming and shutdown
7 Storage battery voltage is low <19V Alarming
-3-
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Note: “*”in “W*” represents the alternator to be used for the diesel gen-set. “*”
can be replaced by E, I, U, Q, Y, among which, E represents LD alternator, I
represents Marathon alternator, U represents Stanford alternator, Q represents Kangfu
alternator (formerly known as Sanbo alternator) and Y represents Wuxi Siemens
alternator.
-4-
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
①Belt
Intercooler cooling
water outlet
I. Diesel engine
Diesel engine is the power source of gen-set and this unit adopts Weichai
WP10CD series alternator (please refer to Operation and Maintenance Manual for
WP10CD Series Gas Alternator for detailed structure principles). Main technical
specifications of the diesel engine are shown in Table 4-1:
Serial Model
WP10CD200E200 WP10CD238E200 WP10CD264E200
No. Items
In-line, four-stroke, water cooling, direct injection,
1 Model
pressurization, intercooling
2 Number of cylinders 6
Cylinder diameter/stroke
3 126/130
mm/mm
Rotation of crankshaft
4 (towards the end of Anticlockwise
flywheel)
5 Declared speed r/min 1500
6 Declared power kW 182 216 240
Piston total displacement
7 9.726
L
8 Compression ratio 17:1
9 Start-up mode Electrical starting/pneumatic starting
Electric motor starting
10 5.4
power kW
Starting battery capacity
11 150*2
Ah
12 Starting cable mm2 70(mm2)
Fuel consumption under
13 200±5%
rated conditions g/kW.h
14 Fuel type Domestic 0# or -10# light diesel oil (GB252)
15 Fuel system Mechanical/electrical pump
16 Engine oil grade CF or above
Maximum oil volume of
17 23
oil pan L
-6-
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
II. AC alternator
Alternator is a kind of equipment which is able to convert mechanical energy
into electric energy. Please refer to alternator manual for detailed structure principles.
Main technical specifications are shown in Table 4-2:
Serial
Item Value Remarks
No.
1 Rated voltage V 400
2 Rated frequency 50
Rated power factor
3 0.8 (legging)
cosφ
4 Rated current A I=1.804P
5 Insulation grade F/H
6 Protection level IP23
7 Exciting mode Brushless self-excitation
8 Outgoing line Three-phase Y-connection
9 Bearing type Rolling bearing
-7-
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Note: alternators operating at other voltage levels and with 1800r/min speed
(corresponding rated frequency 60 Hz) may be selected as required by the customer.
Check the spare parts according to the “list of accompanying spare parts” and
make records;
In case that gen-set has any damages in appearance and accompanying spare
parts, attachment, documents and tools are inconsistent with the list. The
consigner and carrier shall be informed within 24 hours by fax or telephone
after acceptance for claims.
Steel wire rope shall be attached onto the lifting position of gen-set packing case
base.
When bare machine is lifted, steel wire rope shall be attached onto the lifting
position of the common chassisof the generating unit. Contact between steel wire rope
and other gen-set components shall be prohibited, if not, separate them with a board.
Cover lifting shall be stopped if contact parts are small or non-bearing parts, and try
again after changing the length of rope or adding support to change force bearing
point. Please contact us for any questions.
IV. Installation
1. Installation of gen‐set external pipes
Sharp turn shall be avoided on the pipe line, and bend & tee shall be avoided
in most cases.
-9-
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
After the completion of gen-set installation, oil supply and water supply can
only be allowed after pipes are totally cleaned. Test run shall be carried out
for checking whether various pipes meet relevant requirements, pipeline
pressure drop is too large, pump drive capability is enough and cooling water
flow meets operating requirements. Otherwise, pipes in larger size shall be
used.
2. Installation of vent‐pipe
b. External vent-pipe shall be made from steel tube without too many turns and
shall be fixed tightly on ship body with no vibrations. Its weight shall not be applied
on diesel expansion pipe. Exhaust back pressure of diesel engine shall be not greater
than 6kPa after the completion of exhaust system installation. Otherwise, diesel
engine performance will be affected. As diesel vent-pipe surface temperature is high
during operation, vent-pipe shall be kept away from flammable objects to avoid
worker scald. Thermal insulation apparatus shall be mounted on the surface of
external exhaust pipes.
The size of the bellow expansion joint provided by the manufacturer is not
- 10 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
exactly the same as the diameter of vent-pipe. Sometimes, a 500-800mm long diffuser
pipe with increasing diameter is needed, which is also used as a connector to reduce
airflow resistance. Diffuser pipe can be made from 3-5mm sheet steel.
Exhaust silencer can consume and absorb the energy of pressure wave to reduce
pressure wave amplitude of exhaust gas discharged from exhaust silencer. Most diesel
exhaust silencer reduces acoustics energy by reflecting the pressure wave. Generally,
increase of silencer dimension will improve noise reduction effect. If there is
limitation on silencer dimension, increase of silencer decay degree will result in
increase of exhaust resistance. Therefore, proper silencer shall be selected according
to the resistance of exhaust system.
Exhaust silencer is not covered in standard supply scope. The user can purchase
in the market or order from us.
a. Volume of fuel tank for everyday use can keep gen-set continuously running
for at least 8h.
b. Oil tank shall be made aluminum sheet, phosphatization steel plate, and
reinforced plastic plate instead of galvanized steel plate.
c. Contact between oil return pipe and high temperature components (such as
vent-pipe, turbocharger, exhaust gas return pipe) of diesel engine shall be avoided
during installation. Throttling area is not allowed in oil return pipe. Return pipe shall
not contact with sharp edges, be bended with sharp corners or distorted. Improper
installation of return pipe will lead to fuel leakage on alternator. Fuel return pipe shall
be connected to fuel tank with returned oil flowing along with the tank wall to reduce
eddying flow. The return oil of WP10CD series diesel engine is internal return oil
passed through cylinder head (Figure 5-1). Oil injector mounting hole in cylinder
head can ensure that return oil can be fully sealed.
- 11 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Seal ring
d. Diesel engine inlet and outlet fuel pipe shall be equipped with stop valve for
the convenience of maintenance.
(1) Diameter of inlet and outlet pipes shall meet relevant requirements of
gen-set. Large diameter pipes shall be used when too many lengthy pipelines are
required. Excessive resistance of pipeline system will lead to insufficient flow of
cooling water; therefore, the diesel engine is lack of sufficient cooling water which
causes abnormal operation of the diesel engine. Elbows and tees shall be minimized.
(2) Pump suction pipe shall be as short as possible to guarantee that pump water
inlet pressure is greater than atmospheric pressure (i.e. positive pressure). Negative
pressure will cause pump gas etching and insufficient cooling water flow which cause
abnormal operation of pump.
(3) Pipeline system must be equipped with exhaust apparatus to discharge air in
pipeline.
(4) Purchase a new pump when the lift of the pump supplied with the unit can
not satisfy pipeline lift requirement.
(5) Preservative must be added to cooling water in closed cooling system. Filter
screen shall be mounted on water suction pipe mouth in open type cooling system to
- 12 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Small circulation
Diesel engine
Intercooler
Fresh water
pump
Diesel engine intake
Sectional area of cables (multi-core copper flexible cable) between starting engine
and the battery shall be not less than 70mm² and the length shall not exceed 1.5m. Our
standard marine diesel gen-sets are all equipped with starting battery cable.
6. Other requirements
- 13 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
bending angle shall be not less than 90° without too many bends. Inner diameter of
external vent-pipe shall not be less that the inner diameter stipulated in Diesel Engine
Operation and Maintenance Manual. Vent-pipe shall not be too long and satisfy fire
protection requirements. Vent-pipe and the diesel engine shall be in flexible
connection instead of rigid coupling. Water drain valve shall be installed at the lowest
position of vent-pipe in order to guarantee the smooth discharge of condensate water
in vent-pipe. For other requirements, follow the Diesel Engine Operation and
Maintenance Manual.
d. The cabin shall be equipped with intake channel and exhaust channel. There
shall be no obstacles obviously hindering the airflow.
f. Fuel tank separate from gen-set shall be 0.5m above the ground.
g. Sectional area of gen-set major loop connecting cable shall meet relevant
current requirements.
I. Instrument box
Please refer to Operation Manual for Diesel Engine Monitoring and Control
Instrument delivered with gen-set for main operation and maintenance instructions for
instrument box. Brief introduction to several common instrument boxes is hereunder
provided. We can also produce special instrument boxes according to customer’s
special requirements.
- 14 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Serial
Name Function description
No.
1 Power switch Turn on this switch to power on the instrument box.
Local/remote
2 Selection of diesel control position.
control
Instrument box will send out signals to start the diesel engine by
3 Starting
pressing this button.
When the switch is in “rated” position, diesel engine runs in high speed;
4 Idling/rated
When the switch is in “idling” position, diesel engine runs in low speed.
Instrument box will send out shutdown signal to shutdown the diesel
5 Shutdown
engine forcefully by pressing this button.
- 15 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Serial
Alarm description Alarm value Remarks
No.
110% rated
1 Speed is high Audible and visual alarm
speed
0.12±
2 Oil pressure is low Audible and visual alarm
0.02Mpa
Water temperature is
3 95+3C Audible and visual alarm
high
Oil temperature is
4 102+3C Audible and visual alarm
high
115% rated
5 Speed is too high Audible and visual alarm and shutdown
speed
6 Oil pressure is too 0.080.02Mpa Audible and visual alarm and shutdown
- 16 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
low
7 Battery voltage is low <19V Audible and visual alarm
Fuel leakage alarm Audible and visual alarm; fuel leakage alarm
8
(optional) apparatus is required
Relay board
Alarm Alarm Alarm when Alarm Battery Fuel Stop when Stop Stop when Stop Successful Rated
when oil
when speed when oil water undervolta leakage speed is when oil water
indication starting speed
pressure is temperature temperatur high temperatur
is high low is high e is high ge pressure
is low e is high
Wiring diagram
Control position signal output
Remote starting
Diesel operation signal output
Remote emergency
Comprehensive alarm output
Remote shutdown
Fuel leakage alarm input
Outage magnetic valve
pneumatic starting
Double output during
Power supply-
Power supply+
Onboard alternator
Excitation voltage
Starting motor
- 17 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Figure 6-3 shows standard local self-starting instrument box operation panel
Serial
Name Function description
No.
1 Power switch Turn on this switch to power on the instrument box.
Local operation can be performed when the switch is in
“manual” position.
Manual/
Gen-set is in standby status when the switch is in “automatic”
2 automatic
position to automatically supply power for startup or stop
switching
power supply for shutdown according to instructions from
switch panel.
Self-starting instrument box will send out signals to start the
3 Starting
diesel engine by pressing this button.
When the switch is in “rated” position, diesel engine runs in
high speed;
4 Idling/rated
When the switch is on “idling” position, diesel engine runs in
low speed.
5 Shutdown Press this button to stop the diesel engine forcefully.
Operator can manually shut down the diesel engine in
emergency cases by pressing this button. Actuator can be
Emergency controlled manually to cut down the fuel pipe by this button
6
shutdown so as to shut down the diesel engine and open the main switch
of gen-set forcefully.
Speed up/speed
7 Diesel engine speed fine adjustment
down
Voltage fine
8 Alternator voltage fine adjustment
adjustment
When gen-set is in standby status, open this switch and the
heater works after being charged. When diesel engine is
9 Heating switch
started or in operation, the heater will be automatically
switched off and stop work.
Press this button when there is no rotation, self-starting
10 Self-inspection instrument box will simulate external changing conditions to
carry out self-inspection items one by one. Audible and visual
- 19 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
5 Speed is high 115% rated Audible and visual alarm and shutdown
speed
6 Oil pressure is low 0.08 ± Audible and visual alarm and shutdown
0.02Mpa
7 Battery voltage is <19V Audible and visual alarm
low
8 Starting fails three Audible and visual alarm
times
9 Fuel leakage alarm Audible and visual alarm, and fuel leakage
(optional) alarm apparatus is required
- 21 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
diesel engine speed, oil pressure, water temperature, oil temperature, water pressure
and other parameters and monitors all detected parameters according to user’s settings
and sends out audible alarm, visual alarm, remote alarm and other signals. If there is a
stop setting, it will send out shutdown signal when the parameter exceeds shutdown
value. Meanwhile, remote displayer or diesel engine remote control display
instrument can also be provided to realize remote monitoring and control of diesel
engine operating parameters. There are several indicators on instrument box which
can display the operating status and functional status of gen-set in real time. Diesel
engine instrument box also has diesel engine running time accumulation function. It
can also provide extended alarms, diesel engine operating parameter and computer
data communication functions according to user’s special requirements.
- 23 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Serial
Name Function description
No.
1 Power switch Turn on this switch to power on instrument box.
Local/ remote
2 Selection of diesel engine control position.
control
Instrument box will send out signals to start the diesel engine by
3 Starting
pressing this button.
When the switch is in “rated” position, diesel engine runs in high
speed;
4 Idling/rated
When the switch is in “idling” position, diesel engine runs in low
speed.
Instrument box will send out shutdown signal to shutdown the diesel
5 Shutdown
engine forcefully by pressing this button.
When diesel shutdown and emergency shutdown functions are used,
this button has self-locking function. Press this button to close fuel
Emergency
6 magnetic valve and close the diesel engine forcefully. Press this button
shutdown
again after the diesel is completely stopped to open fuel magnetic
valve for next starting.
Speed fine
7 Diesel speed fine adjustment
adjustment
Press this button when there is no rotation, various channels of
instrument box will simulate external changing conditions to carry out
self-inspection items one by one. Instrument box will send out audible
8 Self-inspection
and visual alarm signal when alarm setting value is reached and
instrument box will send out automatic stopping signal when stopping
setting value is reached.
Press this button when there is alarm signal, and the audible alarm will
9 Silencer
be turned off and alarm light keeps shining and stop blinking.
Press this button, and speed display window displays the diesel
10 Timekeeping
accumulative running time. Speed will be displayed after 5 sec.
11 reset Press this button to reset the instrument box.
Table 6-6 new style local ordinary instrument alarm protection function
Serial
Alarm descriptions Alarm value Remarks
No.
110% rated
1 Speed is high Audible and visual alarming
speed
0.12 ±
2 Oil pressure is low Audible and visual alarming
0.02Mpa
Water temperature is
3 95+3℃ Audible and visual alarming
high
Oil temperature is
4 102+3℃ Audible and visual alarming
high
115% rated
5 Speed is too high Audible and visual alarming and shutdown
speed
Oil pressure is too 0.08 ±
6 Audible and visual alarming and shutdown
low 0.02Mpa
Storage battery
7 <19V Audible and visual alarming
voltage is low
8 Water pressure is low 0.01MPa Audible and visual alarming
Fuel leakage alarm Audible and visual alarm, and fuel leakage
9
(optional) alarm apparatus is required
Main power source
10 Audible and visual alarming
fails
Auxiliary power
11 Audible and visual alarming
source fails
- 25 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
- 26 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Marine diesel alternator new style local self-starting instrument box (hereinafter
referred to as instrument box) is a full-automatic alternator working condition
electronic monitoring and control system, which is controlled by a control system
consisting of GEC16W monitoring display module and GEC8000-K1 safety
protection module. GEC16W monitoring display module has a large LCD which has
CAN communication interface and displays alternator speed, oil pressure, water
temperature, oil temperature and other parameters. Meanwhile, it can also detect
battery voltage, alternator accumulative operating time and other parameters; monitor
and display all detected parameters in real time. When there is alarm signal detected
in control box, it will send out audible and visual alarm signals; when fault shutdown
signal is detected (for example over-speed shutdown), control box will output
shutdown control signal automatically to stop the alternator. Control box system can
be used to perform automatic starting and automatic shutdown operations. Meanwhile,
remote displayer or diesel engine remote control display instrument can be used to
perform remote monitoring and control of diesel engine remote display instrument.
Figure 6-7 shows the new style local self-starting instrument box operation panel
- 27 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Table 6-7 shows the operation functions of new style local self-starting
instrument
Serial
Name Function description
No.
1 Power switch Open this switch to power on the instrument.
Serial
Alarm description Alarm value Remarks
No.
110% rated
1 Speed is high Audible and visual alarming
speed
0.12±
2 Oil pressure is low Audible and visual alarming
0.02Mpa
Water temperature is
3 95+3℃ Audible and visual alarming
high
4 Oil temperature is high 102+3℃ Audible and visual alarming
115% rated
5 Speed is too high Audible and visual alarm and shutdown
speed
0.08±
6 Oil pressure is too low Audible and visual alarming and shutdown
0.02Mpa
Storage battery voltage is
7 <19V Audible and visual alarming
low
Starting fails for three
8 Audible and visual alarming
times
Fuel leakage alarm Audible and visual alarming, and fuel
9
(optional) leakage alarm apparatus is required
Water level/oil level is Audible and visual alarm, and level switch
10
low (optional) is required
- 30 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Figure 6-8 a)new style local self-starting instrument box wiring diagram
Figure 6-8 b) new style local self-starting instrument box wiring diagram
5. Onboard instrument
Serial
Name Function description
No.
1 Power switch Turn on this switch to power on the onboard instrument.
When “local/remote” control change-over switch is in “remote”
position, the monitoring and control instrument shall be in remote
Local/ remote control state; therefore, remote control instrument can be used to start
2
control the diesel engine remotely. When “local/remote” change-over switch
is in “local” position, monitoring and control instrument shall be in
local status; therefore, the diesel engine can be controlled locally.
Onboard instrument will send out signals to start the diesel engine by
3 Starting
pressing this button.
Onboard instrument will send out shutdown signal to shut down the
4 Shutdown
diesel engine forcefully by pressing this button.
Press this button when there is no rotation, various channels of
onboard instrument will simulate external changing conditions to carry
5 Self-inspection
out self-inspection items one by one. Onboard instrument will send out
audible and visual alarm signal when alarm setting value is reached
- 32 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
and instrument will send out automatic stopping signal when stopping
setting value is reached.
Press this button when there is alarm signal, and the audible alarm will
6 Silencer
be turned off and alarm light keeps shining and stop blinking.
Press this button, speed display window displays the diesel
7 Timekeeping
accumulative running time. Speed will be displayed after 5 sec.
8 Reset Press this button to reset onboard instrument.
Serial
Alarm description Alarm value Remarks
No.
1 Speed is high 110% Rated speed Alarming
2 Oil pressure is low 0.12±0.02Mpa Alarming
3 Water temperature is high 95+3℃ Alarming
4 Oil temperature is high 102+3℃ Alarming
5 Speed is too high 115% rated speed Alarming and shutdown
6 Oil pressure is too low 0.08±0.02Mpa Alarming and shutdown
Storage battery voltage is Alarming
7 <19V
low
Audible and visual alarming, and
8 Fuel leakage alarm (optional) fuel leakage alarm apparatus is
required
- 33 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Power
supply-
Power
supply+
Battery
charging+
Excitation+
Starting+
Shutdown+
Shutdown-
Alarm+
Comprehensive
alarm
Fuel leakage
(input)
Fuel leakage
(input)
- 34 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Notes:
KMA1, KMA2, KMA3 adopts Schneider
CJX2-Z/25A auxiliary equipment
Contact 2-open, 1-close A-300B3 type servo
mechanism
Buttons SA1, SA2, SA3 adopts LA18.
Indicator AD11
(4) Precautions
1)Hand wheel shall rotate in clockwise direction from left to right during
electric or manual operation.
2)Hand wheel shall be pulled back during manual operation and make spindle
nose turn right by 60.
3)Hand wheel shall be pulled back during electric operation and make spindle
- 35 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Please refer to Operation Manual for Servo Mechanism for more information about
the operation of servo mechanism.
II. Alternator
1. WP10CD Series marine diesel gen-set adopts five kinds of alternators:
Marathon alternator, Stanford alternator, Siemens alternator, Kangfu alternator
(formerly known as Sanbo alternator) and Landian alternator. WP10CD Series
marine diesel gen-set is mainly configured with above-mentioned five alternators.
Please refer to relevant alternator operation manual supplied with the unit for
relevant alternator descriptions and wiring principles.
Some dust, oil mist can be removed by installing air filter on alternator air inlet
to prevent moist air during shutdown.
220V electric heater shall be mounted on the end of alternator stator winding.
Electric heater shall heat alternator winding to remove moist air and prevent water
condensation on the winding.
Alternator’s external circuit or improper operation will lead to the sharp rise of
winding temperature which will exceed the alternator’s temperature rise limit. In
order to prevent motor winding damage, temperature sensor shall be embedded on
motor winding. Temperature sensors are divided into two kinds: one is PTC
thermistor, the other is PT100, which together with detection, alarm and trip circuit,
can provide protection for the alternator.
- 36 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
I. Preparation
1.Clean the dust and other dirt on gen-set surface.
2.Check whether various fasteners and connectors are loose and various
revolving components are flexible.
3.Check whether all electrical connection parts are in good contact and correct
wiring.
4.Add corresponding fuel into fuel tank to remove the air left in fuel system
according to fuel specifications stipulated in Diesel Engine Operation and
Maintenance Manual.
(1) Gen-set power distribution system air isolation switch shall be in normal
tripping position;
II. Commissioning
1.Gen-set starting
2.Engine heating
The diesel engine shall operate for 5-10min in idling status after the starting of
gen-set meanwhile observing diesel oil pressure, oil temperature, cooling water
temperature and diesel operating conditions, in case of abnormalities, shut down the
unit for inspection.
Regulate voltage setting resistor to make it reach rated value; then turn the voltage
change-over switch mounted on onboard detection device to check whether
three-phase voltage is in balance, no current value is shown, and alternator indicator
light turns on.
4.Test run
1)During normal operation of the unit, connect the load and observe
whether various parts are in reliable operation and indicating device is in
normal operation;
2)About 25% rated load shall be connected during test run, and check
whether various parameter indicators and whether any abnormal noise
arising from alternators or diesel engine;
3)Load shall be added gradually under normal operation and the load for
first test run shall be not greater than 80% rated load.
4)Observe the water temperature, oil temperature, oil pressure and other
diesel engine parameters and voltage, current and other electrical
parameters.
- 38 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Notes: sharp increase and decrease of load shall be prohibited during initial
operation.
5.Shutdown
Reduce the load gradually, turn off main switch and open load disconnector. The
diesel engine will operate at the speed reduced to idling value for 2~5 min; then the
alternator will be stopped and various switches shall be turned off to separate these
units. Then the commissioning is finished.
Parallel operation of gen-set can increase power supply reliability and stability,
in addition, number of parallel gen-sets shall be determined according to load level in
places subject to large load fluctuation for economic operation.
(1) Voltage of gen-set to be connected shall be the same as that of operating unit;
II. Methods
Common parallel connection methods include light extinction method, light
rotation method and synchronizing device method. Currently, the most commonly
used method is synchronizing device method. And synchronizing device method can
be divided into quasi-synchronizing parallel method and automatic self synchronizing
parallel method. Hereinafter provide the introduction of quasi-synchronizing parallel
method.
(1) Check whether phase sequences of two parallel gen-sets are consistent with
each other before parallel operation and use phase sequence indicating device to
check alternator stator winding leading-out terminal marks.
(2) Start the gen-set and adjust the speed and voltage of two gen-sets into rated
value, meanwhile, their phase sequences shall be consistent (the adjustment of
gen-set steady-state speed regulation factor and steady-state voltage regulation
factor shall be completed before delivery). One gen-set shall be switched on
firstly (it can operate without load or be used to supply power);
- 40 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Chapter IX Precautions
2.Gen-set output current shall not exceed the rated current stipulated on
alternator nameplate. Please refer to power correction method stipulated in diesel
engine Operation Manual to correct gen-set output power when gen-set working
condition does not conform to working conditions stipulated in this manual.
3.During initial operation, maximum power of the unit shall not exceed 90% of
rated power which help extend service life. When gen-set is started in emergency
status, initial load shall not exceed 50% of rated power.
6.During operation of gen-set, pay attention to cooling water level in box cooler
and replenish if necessary.
7.Repair it in a timely manner in case that there is oil leakage, water leakage and
air leakage in various pipes.
- 41 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
12.As gen-set can be exposed in moisture air, salt mist, oil mist and mould
environment, the user shall start it up regularly to guarantee that gen-set is in
good working condition to prevent gen-set from being corroded or damaged.
13.Pay attention to keep gen-set clean and make it in good working conditions.
14.Gen-set is heavy equipment. For the sake of human body and equipment safety,
it shall be operated with care. Operation against rules and drunk operation are
prohibited.
15.In case that there are any failures and factory assistance is required, the user
should provide the detailed information for quick solution.
Alternator speed is Electron speed regulator does Refer to electronic speed regulator
unstable. not work in optimum status Operation Manual.
- 42 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
3.See Operation Manual for Diesel Engine Monitoring and Control Instrument
for gen-set instrument box fault troubleshooting methods.
4.See Operation Manual for Electronic Speed Regulator for electronic speed
regulator fault and troubleshooting methods.
2.Open flame is forbidden in cabin with fuel oil and lubricating oil to avoid fire.
4.Whole gen-set must be earthed reliably and meet applicable neutral earthing
requirements.
5.The equipment, barriers and dangerous goods not to be used for the unit shall
not be placed on the unit and the ground shall be dry and clean without oil
contamination.
6.As there are noises generated during gen-set operation, it is recommended that
worker in noise environment shall wear proper safety devices, such as ear
protector.
2.Generally, gen-set shall be inspected once a week. Operate for a short time with
load (best of all) to confirm that gen-set is in good status; meanwhile make
- 43 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
(1)Check the conditions of air filter, fuel filter elements, clean them in time and
replace them if necessary.
(3)Check whether there is lubricating oil, fuel and cooling water leakage.
(4)Check whether oil in pump body is within specified limit and replenish it in
time.
(7)Check whether electric connection and mechanical joint is loose and fasten it if
necessary.
(1)Diesel maintenance
First inspection (P) after diesel engine runs for 30-50 hours
Level I maintenance (WD1) after diesel engine runs for each 250 hours
Level II maintenance (WD2) after diesel engine runs for each 500 hours
Level III (WD3) after diesel engine runs for each 1000 hours
Level IV (WD4) after diesel engine runs for each 4000 hours
- 44 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
not exceed 500 hours, diesel engine maintenance frequency shall be 0.5 times
above-mentioned maintenance frequency; in case that diesel working time annually
exceeds 1500 hours, the maintenance frequency shall be 1.5 times above-mentioned
frequency.
Note: Lubricating oil of CE grade or lower is not allowed for WP10CD Series diesel
engine. Replace oil filter element during oil replacement.
Note: “1” in Table 12-2 represents inspection after operation for each 12 h or
once a week; “2” represents inspection after operation for each 100h or once a month;
“3” represents inspection after operation for each 200h or once a year.
- 45 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
- 46 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
Annex II: List of Spare Parts Delivered with Gen-set (Ex-factory Standard
Configuration)
- 47 -
Operation & Maintenance Manual for WP10CD Series Marine Diesel Gen-set
- 48 -