You are on page 1of 25

INSTRUCTIONS AND

MAINTENANCE MANUAL FOR:


S C R E W COMPRESSORS
Models
VE 15÷22 B SE
VE 22÷37 C SE
VE 37÷45 H SE
Manufacturer: adicomp srl Model __________
Via del Progresso, 35
36050 Sovizzo (VI) Italy Serial number ___________
Tel. ++(39) 0444 573979
Fax ++(39) 0444 809186 Date of manufacture __________

Local adicomp agent:

Name_________________________________________

Address________________________________________

Telephone______________________________________

Fax___________________________________________
INSPECTION CERTIFICATE

adicomp srl, Via del Progresso, 35 36050 Sovizzo (VI) Italy declares that this screw compressor package,

has successfully passed internal test.

The following aspects were checked:

- All the components have been correctly assembled and tightened.

- Functioning of all the electric components complies with specified parameters.

- All electrical test on safety have been carried out and found within limit set.

- Parts subjected to pressure have been tested and found satisfactory.

- There are no leakage in the oil circuit and the air circuit.

- There are no flaws in the external appearance of the machine.

- Capacity, absorbed power and various operating temperature have been checked and found satisfactory.

adicomp srl
The Inspector

ATTENTION !
Failure to observe and apply the norms and recommendation listed in this manual
invalidates all type of guarantee on the compressor.

adicomp declines all responsibility with regard to damages caused to persons and/or things as a result of incorrect use
of the compressor and its accessories, lack of maintenance or neglect and, in general, the failure to observe the
warnings given in this manual, which are to be considered as complementary to the general safety standards in force.

2 Instructions and maintenance manual - VE screw compressor -


WARRANTY CONDITIONS

Each “VE” compressor is regularly shop tested and guaranteed for 3000 (three thousand) working hours in the 12
(twelve) months following the date of delivery. Warranty is 24 months for the air end.
This warranty applies only if the contractual and administrative norms have been observed and if the installation of the
machine and its use comply with the instructions of this manual.
Damaged or defective parts due to manufacturing faults will be repaired or replaced free of charge. The cost of labour
is excluded from this warranty (the relative amount will be charged).
The following is also excluded from this guarantee: all parts subject to wear (air filter, oil filter, etc...), transport costs
and the cost of the intervention of our technicians (on-site inspection, disassembly and re-assembly) for operational
faults not due to manufacturing defects
Only our "AUTHORISED SERVICE" technicians' decision will be regarded as final.
This guarantee excludes any responsibility for direct or indirect damage to people and/or objects, caused by improper
use or inadequate maintenance of the compressor and is limited only to manufacturing defects.
This guarantee is considered void in the event of tampering or changes - even small ones - and use of non-original
spare parts.

INDEX

Warranty conditions 3
Index 3
General information 4
Safety information 4
How to use this manual 4
Safety precautions 5
Unpacking 7
Lifting and handling the machine 7
Location 8
Installation 9
Warm air ducting 9
Electrical connections 9
Before first starting 10
First start up 10
Electric control panel 11
List of spare parts for routine maintenance 12
Principal diagram 16
Description of the machine 17
Flow diagram 19
Electric panel internal view 20
Electrical data 20
Technical data 21
Registration and commissioning report 23
Log book to check maintenance 24
Attached (electric diagram, electronic controller) 25

Instruction and maintenance manual – VE screw compressor 3


GENERAL INFORMATION

The screw compressor package “VE” should only be used as specified in this manual to be kept with care in a known
and easily accessible place, as it has to last for the whole operational life of the machine.
In the company where the compressor is to be installed, a person should be made responsible for the compressor. Any
check, adjustment and maintenance work is concern either of the person responsible or the authorised person.
Whenever the person responsible has to be temporarily or permanently substituted, his substitute should read carefully
this instruction and maintenance manual and any notes regarding technical interventions and maintenance made up to
that moment.
For any query or request always mention: MODEL and SERIAL N° of the machine.

SAFETY INFORMATION

WARNING! Before carrying out any operation this instruction and maintenance manual should be carefully read. The
non-compliance with information and instructions mentioned herein can cause damages to objects and injuries to
people.

 This machine has been designed, manufactured and protected for the following functions. Any other use is not
allowed.
 The compressor should be installed in premises where no explosion, fire or flooding risk exists.
 The compressor should be installed and maintained by specialised technicians only. Always comply with current
safety and accident prevention regulations.
 The manufacturer is not responsible for damages to people and/or objects that this machine may cause by misuse
of the compressor, non-compliance or partial compliance with safety standards mentioned in this manual, changes
even small ones, tampering and use of non-original spare parts.

HOW TO USE THIS MANUAL

For a quick and rational reading of this manual, symbols have been used for highlighting practical advice, simple
information or situations in which great care must be taken.
Said symbols can be next to a piece of text (and therefore refer only to that text), a figure (and refer to the subject
illustrated in the figure and the relative text) or at the top of the page (in which case they refer to all the subjects dealt
with on that page).

IMPORTANT! Pay maximum attention to the meaning of the symbols: their aim is not to have to repeat technical
concepts or safety warnings and as such should be considered as proper "reminders". Refer to the page below
whenever doubts arise as to their meaning.

CAUTION! Highlights an important description regarding technical interventions, dangerous


conditions, safety warnings, precautions and/or extremely important information.

MACHINE STOPPED! Every operation highlighted by this symbol must only be carried out with the
machine powered off.

POWER OFF! Before any intervention the machine should be necessarily powered off.

SPECIALISED PERSONNEL! Every intervention highlighted by this symbol is exclusively the job
of a specialised technician.

4 Instructions and maintenance manual - VE screw compressor -


SAFETY PRECAUTIONS TO BE FOLLOWED WHEN USING STATIONARY COMPRESSORS

READ CAREFULLY BEFORE STARTING UP THE UNIT.


Besides the normal safety regulations which must be observed when using stationary air compressors, the following
instructions and precautions are particularly important.
When using this unit the operator must comply with the local standards and regulations on safety at work.
The owner is responsible for ensuring that the compressor is kept in conditions that enable it to operate in absolute
safety. The compressor parts and accessories must be replaced if they do not guarantee safe operation.
Installation, operation, maintenance and repairs must be carried out only by authorised, trained and competent
personnel.
Critical operation data (pressure, temperatures, time intervals, etc.) must be indelibly marked and kept in legible
conditions.

If any provisions listed in this manual, especially regarding safety, do not comply with the local legislation, the
applicable one is the more restrictive of the two.
The precautions listed here are of a general nature and refer to many types of compressors and their respective
equipment, so some rules may not apply to the unit for which this manual is specifically intended.

INSTALLATION

Besides the general technical practice , which must comply with the regulation s enforced by the local authorities ,
particular attention is drawn to the following instructions:
1. Install the compressor in premises where the environmental air is as cold and clean as possible. If necessary fit an
intake duct. Never block the air inlet. Take care to allow as little humidity as possible to be taken in with the air.
2. The air taken in must be free from fumes or inflammable vapours, for example paint solvents, which could cause
fire or internal explosions.
3. Air-cooled compressors must be installed where there is a sufficient flow of cooling air, preventing the expelled
air from being recycled at input.
4. If a system includes several compressors, each one of these must be provided with manual cut-out valves. It is
absolutely forbidden to rely on the check valves to isolate each system under pressure.
5. Never remove or tamper with the safety devices, the protections or insulating materials applied on the compressor.
Each pressurised tank or auxiliary unit, installed outside the main unit and containing air at a higher pressure than
the environmental air, must be protected with one or more pressure discharge devices.
6. The electrical connections must comply with the local regulations. The units must be connected to earth and
protected against short circuits with fuses.

OPERATION

1. The flexible pipes for distributing compressed air must have adequate dimensions and must be suitable for the
working pressure. Never use flexible pipes that are worn, damaged or deteriorated. As regards couplings and
connections, use only the correct type and size. When feeding compressed air into a flexible pipe or an air line,
ensure that the free end of the pipe is securely fastened. A free end will give "whip lashes" and could cause
injury to people in the vicinity. Never play with compressed air. Never turn the jet of air against your own
body or anyone else's. Never use compressed air to remove dust from clothing. If using it to clean equipment,
take great care and wear protective goggles. Never inhale compressed air, if you are not sure that it has been
suitably purified for this purpose.
2. Never operate the compressor in places where there is a possibility of its taking in inflammable or toxic fumes.
3. Never run the unit at pressures lower or higher than the set limits indicated in the table of the Technical Data.
4. All parts of the casing must be closed when the unit is working.
5. All persons in a compressor room, where the noise level exceeds 90 dB(A), must protect their ears with
special ear muffs.

Instruction and maintenance manual – VE screw compressor 5


MAINTENANCE

Maintenance and repairs must be carried out only by sufficiently trained personnel, under the supervision of a
technician qualified to do the job.
1) Use only suitable tools for performing maintenance and repairs.
2) Use only original spare parts.
3) All maintenance jobs that are not routine supervision must be started only when the compressor is at a standstill.
Ensure that the unit cannot be started accidentally.
4) Before removing any component under pressure, efficiently isolate the unit from any source of pressure and
discharge pressure from the whole system.
5) Never use inflammable solvents or carbon tetrachloride to clean the parts. Take the necessary safety precautions
against the toxic vapours of fluids used for cleaning purposes.
6) Observe the strictest standards of cleanliness during maintenance and repair jobs. Protect the parts against dirt,
keeping them covered, and plug the openings with clean rags, paper or covers.
7) Never perform welding, or other operations that require heat, near the oil system. In particular the oil tanks must
be completely cleaned before these operations can be carried out on them, for example by washing them with
steam.
8) Never perform welding or make alterations of any kind on tanks under pressure. Ensure that no tools, loose parts
or cloths are left lying on the compressor, on the motor or on the moving parts.
9) Before leaving the unit to be started up after maintenance or overhauling, check that the pressures, the
temperatures and the settings are correct and that the control devices and safety stops work correctly.
10) Protect the motor, the electric parts and the regulation system components, etc. against infiltration of humidity, for
example when cleaning the unit with steam.
11) Maintain the noise level as specified. never remove sound-deadening material from the panels.
12) Never use caustic solvents or synthetic oils which may damage the materials used in the air system, for example
transparent polycarbonate containers.
13) When handling refrigerating substances, R22, R12, etc., the following safety precautions must be taken:
a. Do not inhale the refrigerant vapours. Ensure that the area where you are working is sufficiently ventilated.
b. Always wear special gloves. If any splashes of refrigerating substance get on your skin, wash immediately
with water. For no reason should you work on the machine without protective garments.
c. Always wear safety goggles.

6 Instructions and maintenance manual - VE screw compressor -


UNPACKING

The compressor should only be lifted either by pallet trucks or fork lift trucks (of suitable lifting capacity, see
"TECHNICAL DATA" on this manual).
• Check the integrity of the packaging.
• Unpack the machine (paying attention to any instruction on the packaging).
• Check the (outer) good condition of the machine.
• Open the access doors and check all inner parts (visual check).
• Dispose of the packaging in compliance with the current waste disposal regulations.

LIFTING AND HANDLING THE MACHINE

In Fig. 1 you’ll find suggested ways about how to lift and handle with fork lift or pallet truck the VE-B compressor s.

Fig. 1

Floor mounted

Instruction and maintenance manual – VE screw compressor 7


LOCATION

The room chosen for the installation of the "VE" compressor should meet the following requirements and comply with
the specifications of the current safety and accident prevention regulations:
A) Low percentage of fine dust.
B) Proper room ventilation and size which allow the temperature holding (3°C ÷ 40°C) - with the machine running.
Adequate air intake openings.
C) In the event of inadequate hot air discharge, fit the exhaust fans as high as possible (fig. 3).

Fig. 2 Fig. 3

ATTENTION: IN ALL CASES THE


TEMPERATURE IN THE ROOM
(OR BETTER INSIDE THE
CANOPY) MUST BE BETWEEN
3°C AND 40 °C
AN EXTRA COOLING FAN WITH
MINIMUM CAPACITY AS
INDICATED BELOW FIG.3 AND
FIG.4 MUST BE INSTALLED
WHEN WARM AIR FLOW IS
DUCTED

Fig. 4

Fig. 5 and 6 page


Model PROPOSAL 1 (fig.2) PROPOSAL 2 (fig.3) PROPOSAL 3 (fig.4)
10
Section of air inlet and Section of air inlet Section of air inlet passage A Minimum room
outlet passage passage Flow rate of fan D and section of dimensions
(A - B) A-C duct E ** A x B x C (m)
VE15B 0.40 m2 0.40 m - 4000 m3/h
2
0.40 m - 4000 m3/h - 600 x 400
2
3.0 x 2.2 x 3.0
VE18B 0.40 m2 0.40 m2 - 5000 m3/h 0.40 m2 - 5000 m3/h- 600 x 400 3.0 x 2.2 x 3.0
VE22B 0.50 m2 0.50 m2 - 6000 m3/h 0.50 m2 - 6000 m3/h- 600 x 400 3.0 x 2.2 x 3.0
VE22C 0.50 m2 0.50 m2 - 6000 m3/h 0.50 m2 - 6000 m3/h- 600 x 400 3.0 x 2.2 x 3.0
VE30C 0.75 m2 0.75 m2 - 10000 m3/h 0.75 m2 - 10000 m3/h- 750 x 750 4.0 x 3.5 x 3.0
VE30CS 0.75 m2 0.75 m2 - 10000 m3/h 0.75 m2 - 10000 m3/h- 750 x 750 4.0 x 3.5 x 3.0
VE37C 0.75 m2 0.75 m2 - 10000 m3/h 0.75 m2 - 10000 m3/h- 750 x 750 4.0 x 3.5 x 3.0
VE37H 0.75 m2 0.75 m2 - 10000 m3/h 0.75 m2 - 10000 m3/h- 750 x 750 4.0 x 3.5 x 3.0
VE45H 0.75 m2 0.75 m2 - 10000 m3/h 0.75 m2 - 10000 m3/h- 750 x 750 4.0 x 3.5 x 3.0

8 Instructions and maintenance manual - VE screw compressor -


INSTALLATION
• Position the machine in a stable and final manner. Make sure it is at least 50 cm away from the wall so that there is
free access of air to the fan (fig.6).

Do not fit check valve between the compressor and the tank.

Fig. 5

Fig. 6

If there is a possibility of the room falling below 0°C, fit heating resistance for the oil tank

WARM AIR DUCTING


• Hot air comes out from the side of the compressor at a temperature 15-35°C higher than the room temperature.
• If the room ventilation is not enough (door / window opening see technical features), a duct having the same cross-
section as the radiator area is absolutely necessary .This duct should be equipped with a valve conveying the hot air
outside in summertime and inside in wintertime, thus using the "VE" compressors heat energy as auxiliary heating unit.

These ducts should not be longer than 1/2 m without bend. Otherwise, an auxiliary fan should be
installed on the outlet side (fig.4).

Condensate is a polluting mixture and should not be disposed of in sewage system or dumped in the
environment. The condensate collector sump should either be equipped with a valve and a removable
container or connected to a suitable piece of equipment.

ELECTRICAL CONNECTIONS.
• The mains cable should have a cross-section suitable for the machine power and should include: three phase cable plus
earth for “VE” models.
• A fused switch (C) or an automatic switch with current differential device set at 30 mA is absolutely necessary to fit
before the compressor control panel (fig.5/6).
• The switch (C) should be easily reached by the operator (fig.5/6).

The cables should be of the approved type A and installed with the following grade of protection:
minimum IP44.
Note: see page 20 for the right cable cross-section.

Instruction and maintenance manual – VE screw compressor 9


BEFORE FIRST STARTING

Before starting compressor for the first time it is compulsory to make sure that:
• Incoming voltage is the same as indicated on the number plate.
• All external connection be made with cable of adequate size and type.
• Main automatic switch (on the wall) be of correct type and size.
• Oil level be correct (eventually top up with same type oil).
• Check and tighten all electrical connections.

An adequate size air receiver must be connected by using flexible pipes. Before the first starting up or after a long time
of non usage of the compressor pour 0.25 litre of oil into the suction of the air end after removing air filter ref. 1 (this
quantity of oil is better to take it from the oil receiver of compressor itself)

FIRST START UP

• The first start up of screw compressor package (commissioning) must be done compulsory by our authorised service
technician. *
• Although models "VE" have a safety device to protect them from wrong rotation it is advisable during first
starting up to make sure it is in the correct direction in order to avoid damages that can be very serious.
• Open the door to be able to see the rotation of air end it self.
•Push start button and after a few second push emergency button in order to stop immediately the compressor. During
this time it must be noted if the rotation of compressor is in accordance with the arrows on air end.
• In case the compressor rotates in the wrong direction (not in accordance with arrows). Remove voltage (locking the
main switch) and exchange two incoming phases.
• Put voltage back and re-start compressor checking through the open door that the rotation of air end is according to
arrows.
• Close the door properly.

AFTER ABOUT 50 HOURS OF OPERATION IT IS COMPULSORY TO CHECK AND EVENTUALLY


RE-TIGHT THE BELTS AND ALL ELECTRICAL CONNECTIONS

IN CASE OF SUBSTITUTION OF ELECTRIC MOTOR OR IN CASE COMPRESSOR IS CHANGED OF


LOCATION, IT IS IMPERATIVE TO CHECK THE ROTATION OF AIR END AS ABOVE DESCRIBED
BEFORE RESTARTING THE COMPRESSOR

Already during this phase it is compulsory to follow very carefully the SAFETY INFORMATION on the usage of the
compressor.

* = If the technician fill up the (R.C.R.) registration and commissioning report copy of which you can find at page 23
of this manual the possibility of a safer and more efficient operation of compressor unit are increased and eventual
warranty communications and decision will be more prompt.

10 Instructions and maintenance manual - VE screw compressor -


ELECTRIC PANEL

Compressor starts by pressing the start button. Once started, after a few seconds in star connection it changes over
into delta connection (load/off load solenoid valve energises) and start pumping. When max operating pressure set is
reached compressor goes off load (load/off load solenoid valve de-energises).
If compressor works off load for too long it stops. The compressor is ready to start as soon as pressure in the system
has reached the minimum re-set value of the pressure switch.
On the display below is indicated the operating pressure and on the display above the operating temperature (oil/air
mixture temperature at air end discharge flange).

Compressor stops by pressing the stop button after a settable off load time.
If emergency stop is pushed compressor will stop immediately and specific led will be lighted.
If there is a power failure, the compressor will stop immediately too, and when the power is restored compressor will
start automatically on a certainly delay time to prevent starty against load (ATTENTION! AUTOMATIC RESTART
UNIT).

The manual of the electronic controller is attached at the end of this manual.

Instruction and maintenance manual – VE screw compressor 11


Maintenance program for screw compressor series VE 15-18-22B
Every Every Every Every Every
MAINTENANCE ACTION Every
install 2000 4000 8000 16000 20000 Code Qty.
day
hours hours hours hours hours
CHECK (REMEDY IF NECCESARY)
Check suitable position 
Check sufficient access 
Check correct drive rotation 
Check oil flow on oil recover visor       
Check tension and condition of V
(1)     
belt
Check pressure drop separator
     
cartridge
Check ambient temperature      
Torque electrical connections      
Check adequate ventilation      
Check motor current      
Check for air leaks       
Check for oil leaks       
Check oil temperature       
Check clear of airborne
      
contaminants
Check correct oil level       
Check delivery pressure       
CLEANING
(2)
Clean gas / oil radiator external     
Clean external dirt from electric
(2)     
motor
REPLACE
(2) 4050.0016(15)
Change prefiltration panel      1
4050.0012(18-22)
(3) 4020.0001(15-18)
Change oil filter cartridge      1
4020.0007(22)
(3) 4030.0004(15-18)
Change air filter cartridge      1
4030.0001(22)
(3) 6500.0010(19lt)
Change oil ADI-L4     lt
6500.0011(208lt)
4010.0006(15-18)
Change separator cartridge     1
4010.0033(22)
Change suction valve kit     8820.0001 1
Change oil recover visor    3505.0001 1
2060.0036(15)
Change V belt 8bar   2060.0037(18) 3
2060.0038(22)
2060.0035(15)
Change V belt 10bar   2060.0036(18) 3
2060.0038(22)
2060.0026(15)
Change V belt 13bar   2060.0035(18) 3
2060.0038(22)
8810.0010(15)
Change minimum pressure valve kit    1
8810.0011(18-22)
Change thermostatic valve kit    8830.0001 1
(4)
Change oil seal kit  8850.0002 1
Change kit thrust bearings  8851.0005 1
Change kit journel bearings  8851.0004 1
Change kit gaskets  5430.0029 1
Change kit thrust collar  8852.0029 1
Change solenoids  8100.0001 1
8851.0072(15)
Replace motor bearings  8851.0033(18) 1
8851.0072(22)
Change manometer  5730.0002 1
(1) Check tension of the V-Belt every year
(2) In dirty and dusty places cleaning frequently
(3) Maximum replace every year
(4) Check the condition of the oil seal at 8000 and 12000 hours and replace if necessary

12 Instructions and maintenance manual - VE screw compressor -


Maintenance program for screw compressor series VE 18B (15 Bar)
MAINTENANCE ACTION
Every Every Every Every Every
Every
install 2000 4000 8000 16000 20000 Code Qty.
day
hours hours hours hours hours
CHECK (REMEDY IF NECCESARY)
Check suitable position 
Check sufficient access 
Check correct drive rotation 
Check oil flow on oil recover visor       
Check tension and condition of V
(1)     
belt
Check pressure drop separator
     
cartridge
Check ambient temperature      
Torque electrical connections      
Check adequate ventilation      
Check motor current      
Check for air leaks       
Check for oil leaks       
Check oil temperature       
Check clear of airborne
      
contaminants
Check correct oil level       
Check delivery pressure       
CLEANING
(2)
Clean gas / oil radiator external     
Clean external dirt from electric
(2)     
motor
REPLACE
(2)
Change prefiltration panel      4050.0012 1
(3)
Change oil filter cartridge      4020.0015 1
(3)
Change air filter cartridge      4030.0001 1
(3) 6500.0010(19lt)
Change oil ADI-L4     lt
6500.0011(208lt)
Change separator cartridge     4010.0052 1
Change suction valve kit     8820.0001 1
Change oil recover visor    3505.0001 1
Change V belt 15 bar   2060.0036 3
Change minimum pressure valve
   8810.0011 1
kit
Change thermostatic valve kit    8830.0007 1
(4)
Change oil seal kit  8850.0002 1
Change kit thrust bearings  8851.0005 1
Change kit journel bearings  8851.0004 1
Change kit gaskets  5430.0029 1
Change kit thrust collar  8852.0029 1
Change solenoids  8100.0001 1
Replace motor bearings  8851.0033 1
Change manometer  5730.0002 1
(1) Check tension of the V-Belt every year
(2) In dirty and dusty places cleaning frequently
(3) Maximum replace every year
(4) Check the condition of the oil seal at 8000 and 12000 hours and replace if necessary

Instruction and maintenance manual – VE screw compressor 13


Maintenance program for screw compressor series VE 22-30-37C - 30CS
Every Every Every Every Every
MAINTENANCE ACTION Every
install 2000 4000 8000 16000 20000 Code Qty.
day
hours hours hours hours hours
CHECK (REMEDY IF NECCESARY)
Check suitable position 
Check sufficient access 
Check correct drive rotation 
Check oil flow on oil recover visor       
Check tension and condition of V
(1)     
belt
Check pressure drop separator
     
cartridge
Check ambient temperature      
Torque electrical connections      
Check adequate ventilation      
Check motor current      
Check for air leaks       
Check for oil leaks       
Check oil temperature       
Check clear of airborne
      
contaminants
Check correct oil level       
Check delivery pressure       
CLEANING
(2)
Clean gas / oil radiator external     
Clean external dirt from electric
(2)     
motor
REPLACE
(2) 4050.0012(22-30C)
Change prefiltration panel      1
4050.0013(30CS-37)
(3)
Change oil filter cartridge      4020.0007 1
(3)
Change air filter cartridge      4030.0004 1
(3) 6500.0010(19lt)
Change oil ADI-L4     lt
6500.0011(208lt)
4010.0033(22-30C) 1
Change separator cartridge    
4010.0033(30CS-37) 2
Change suction valve kit     8820.0003 1
Change oil recover visor    3505.0006 1
2060.0040(22-30C)
Change V belt 8bar   4
2060.0039(30CS-37)
2060.0040(22-30C)
Change V belt 10bar   4
2060.0039(30CS-37)
2060.0039(22-37)
Change V belt 13bar   2060.0036(30C) 4
2060.0041(30CS)
8810.0011(22-30-
Change minimum pressure valve kit    30CS) 1
8810.0005(37)
Change thermostatic valve kit    8830.0001 1
(4)
Change oil seal kit  8850.0002 1
Change kit thrust bearings  8851.0003 1
Change kit journel bearings  8851.0004 1
Change kit gaskets  5430.0029 1
Change kit thrust collar  8852.0002 1
Change solenoids  8100.0001 1
8851.0072(22)
Replace motor bearings  8851.0073(30) 1
8851.0046(37)
Change manometer  5730.0002 1
(1) Check tension of the V-Belt every year
(2) In dirty and dusty places cleaning frequently
(3) Maximum replace every year
(4) Check the condition of the oil seal at 8000 and 12000 hours and replace if necessary

14 Instructions and maintenance manual - VE screw compressor -


Maintenance program for screw compressor series VE 37-45H

Every Every Every Every Every


MAINTENANCE ACTION Every
install 2000 4000 8000 16000 20000 Code Qty.
day
hours hours hours hours hours
CHECK (REMEDY IF NECCESARY)
Check suitable position 
Check sufficient access 
Check correct drive rotation 
Check oil flow on oil recover visor       
Check tension and condition of V
(1)     
belt
Check pressure drop separator
     
cartridge
Check ambient temperature      
Torque electrical connections      
Check adequate ventilation      
Check motor current      
Check for air leaks       
Check for oil leaks       
Check oil temperature       
Check clear of airborne
      
contaminants
Check correct oil level       
Check delivery pressure       
CLEANING
(2)
Clean gas / oil radiator external     
Clean external dirt from electric
(2)     
motor
REPLACE
(2)
Change prefiltration panel      4050.0013 1
(3)
Change oil filter cartridge      4020.0007 1
(3)
Change air filter cartridge      4030.0029 1
(3) 6500.0010(19lt)
Change oil ADI-L4     lt
6500.0011(208lt)
Change separator cartridge     4010.0033 2
Change suction valve kit     8820.0004 1
Change oil recover visor    3505.0006 1
2060.0041(37)
Change V belt 8bar   4
2060.0040(45)
Change V belt 10bar   2060.0040 4
2060.0039(37)
Change V belt 13bar   4
2060.0040(45)
Change minimum pressure valve kit    8810.0005 1
Change thermostatic valve kit    8830.0001 1
(4)
Change oil seal kit  8850.0004 1
Change kit thrust bearings  8851.0006 1
Change kit journel bearings  8851.0007 1
Change kit gaskets  5430.0031 1
Change kit thrust collar  8852.0003 1
Change solenoids  8100.0001 1
8851.0046(37)
Replace motor bearings  1
8851.0048(45)
Change manometer  5730.0002 1
(1) Check tension of the V-Belt every year
(2) In dirty and dusty places cleaning frequently
(3) Maximum replace every year
(4) Check the condition of the oil seal at 8000 and 12000 hours and replace if necessary

Instruction and maintenance manual – VE screw compressor 15


PRINCIPAL DIAGRAM

Load/off load pressure (cutting in, cutting out) it is visible on the electronic lower panel display and must be found
within the limits indicated at page 21.
Operating temperature it is visible on the electronic upper panel display and must not be found within ambient
temperature plus 55°C.
To check the pressure drop on air/oil separator it is necessary to read contemporaneously the cut off pressure in the
pressure gauge 26 and the one in the pressure display. The difference must be less than 0.6 bar.
Idling pressure must be checked on gauge ref.26 and must be 2-2,5 bar for all “VE” models.

COMPRESSOR OPERATING DIAGRAM

• The motor start in "star" connection. During such phase the compressor starts slowly, the solenoid valve ref.5 is
open, the suction control valve ref.2 is closed.
• Compressor starts in these condition for a few seconds .
• After some time motor change into "delta" connection, the solenoid valve ref.5 is energised, and opening the suction
valve the compressor can start pumping.
During this phase the compressor pumps air into air/oil receiver ref. 11.
• Compressed air cannot go out through the minimum pressure valve ref.16 until the pressure has not reached 3÷4 bar.
• The air pressure inside the air/oil receiver ref. 11 makes the oil to go through various pipes to the oil thermostatic
valve, oil cooler to air end.
• If operating temperature is below 71°C the oil coming from the oil receiver goes through oil thermostatic valve, oil
filter, the air end.
• If operating temperature is above 71°C the oil coming from the oil receiver is deviated by the thermostatic valve into
the oil cooler and then going through oil filter to the air end.
• The oil that reaches the air end is mixed with air during the compression making thus an air/oil mixture that
lubricates seal and cools all moving parts during compression.
• Air/oil mixture is then pushed into the air/oil receiver where it happens a first mechanical pre-separation of air from
oil and subsequently a final fine separation into the air/oil separator cartridge.
• From minimum pressure valve ref.16 goes out then only air which goes through the after-cooler ref.22 and
subsequently goes to the air receiver directly .
• The oil collected after the air/oil separator cartridge return into the air end by the scavenge line ref.34.
The water condensate will accumulated inside the air receiver and must be drained manually every day ref.36 or
automatically if a proper drainer is fitted.

16 Instructions and maintenance manual - VE screw compressor -


DESCRIPTION OF THE MACHINE
16
2 1 13
20

17

14

11

4
9
8

10
6

21 - inside
12

22

15

Instruction and maintenance manual – VE screw compressor 17


3

18

19

1. Suction air filter 12. Safety valve


2. Suction control valve 13. Air/oil separator cartridge
3. Load/off load solenoid valve for 14. Minimum pressure valve
suction valve control 15. Pressure gauge (air/oil receiver)
4. Air end 16. Oil filter cartridge
5. V belt 17. Oil cooler
6. Electric motor 18. Air after-cooler
7. Ventilating fan motor 19. Electric panel
8. Air/oil receiver 20. Cooling air flow filtration panel
9. Oil level visor 21. Air filter cartridge
10. Oil drain plug (oil receiver) 22. Scavenge oil sight glass
11. Oil filling plug

18 Instructions and maintenance manual - VE screw compressor -


FLOW DIAGRAM

Instruction and maintenance manual – VE screw compressor 19


ELECTRIC PANEL – INTERNAL VIEW

LEGENDA:
TCI (transformer)
RSF = Relay phases sequences
FU1 = Fuses (primary)
FU2 = Auxiliary fuses (secondary)
FR1 = Main motor thermal overload
FR2 = Fan motor thermal overload
KML = Line Contactor
KMD = Delta Contactor
KMX = Star Contactor
ISG = Isolator switch
A.T.S. = Auxiliary terminal strip
Electronic panel (power)

ATTENTION!
COMPRESSOR WITH AUTOMATIC
RESTART!

The electric diagram is attached at the end of this manual.

ELECTRICAL DATA (V400)

MODEL
MODELLO VE15B VE18B VE22B VE22C VE30C
Minimum section inlet cable 2
1 mm 4 x 10 4 x10 4 x 16 4 x 16 4x16
Sezione minima cavi in entrata
Delayed fuse for motor starting (aM)
2 A 3 x 63 3 x 63 3 x 80 3 x 80 3x80
Fusibili ad azione ritardata (aM)
Main motor thermal overload setting
3 A 23 27 34 34 34
Taratura termico motore principale
Electric fan thermal overload setting
4 A 0.5 1.35 1.35 1.35 1.35
Taratura termico elettroventilatore
Auxiliary fuses FU1 (10x38)
5 A 2x1 2x1 2x1 2x1 2x1
Fusibili ausiliari FU1 (10x38)
Auxiliary fuses FU2 (5x20)
6 A 1x4 1x4 1x4 1x4 1x4
Fusibili ausiliari FU2 (5x20)
Auxiliary voltage
7 V 24 24 24 24 24
Voltaggio ausiliari

MODEL
MODELLO VE30CS VE37C VE37H VE45H
Minimum section inlet cable
1 mm2 4x16 4 x 16 4x25 4x25
Sezione minima cavi in entrata
Delayed fuse for motor starting (aM)
2 A 3x80 3 x 100 3x100 3x125
Fusibili ad azione ritardata (aM)
Main motor thermal overload setting
3 A 34 41 41 50
Taratura termico motore principale
Electric fan thermal overload setting
4 A 1.35 1.35 1.35 1.35
Taratura termico elettroventilatore
Auxiliary fuses FU1 (10x38)
5 A 2x1 2x1 2x1 2x1
Fusibili ausiliari FU1 (10x38)
Auxiliary fuses FU2 (10x38)
6 A 1x4 1x4 1x4 1x4
Fusibili ausiliari FU2 (10x38)
Auxiliary voltage
7 V 24 24 24 24
Voltaggio ausiliari

TECHNICAL DATA
20 Instructions and maintenance manual - VE screw compressor -
MODEL VE VE VE VE VE VE VE VE VE
MODELLO 1508B 1510B 1513B 1808B 1810B 1813B 2208B 2210B 2213B
Normal operating pressure
1 bar 6.5-7.5 8.5-9.5 11.5-12.5 6.5-7.5 8.5-9.5 11.5-12.5 6.5-7.5 8.5-9.5 11.5-12.5
Pressione normale/taratura
Max working pressure
2 bar 8 10 13 8 10 13 8 10 13
Pressione max di esercizio
Minimum working pressure
3 bar 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Pressione minima di esercizio
Air end model
4 Mod. SCA 9 SCA 9 SCA 9 SCA 9 SCA 9 SCA 9 SCA 9 SCA 9 SCA 9
Tipo di compressore
Free air delivery ISO1217
5 m3/min 2.40 2.10 1.80 2.90 2.50 2.05 3.25 2.95 2.50
Aria resa effettiva ISO 1217
Air/oil receiver capacity
6 l 6 6 6 14 14 14 14 14 14
Capacità serbatoio aria/olio
Oil quantity
7 l 4 4 4 6 6 6 6 6 6
Quantita olio
Electric motor type Type
8 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55
Tipo di motore elettrico Tipo
Motor power/Service factor
9 KW/s.f 15/1.0 15/1.0 15/1.0 18/1.0 18/1.0 18/1.0 22/1.0 22/1.0 22/1.0
Potenza motore / Fattore di servizio
Full load current
10 A 31 31 31 37.8 37.8 37.8 41.7 41.7 41.7
Corrente a pieno carico
Electric fan power
11 kW 0.200 0.200 0.200 0.200 0.200 0.200 0.200 0.200 0.200
Potenza motore elettroventilatore
Recoverable heat
12 Kcal/h 10300 10300 10300 12700 12700 12700 15100 15100 15100
Calore recuperabile
Safety valve setting
13 bar 14 14 14 14 14 14 14 14 14
Taratura valvola di sicurezza
Noise level at 1 m
14 dB (A) 70 70 70 72 72 72 72 72 72
Livello rumore a 1 m
Dimensions 1020x550 1020x550 1020x550 1135x650 1135x650 1135x650 1135x650 1135x650 1135x650
15 mm
Dimensioni x1045 x1045 x1045 x1310 x1310 x1310 x1310 x1310 x1310
Weight
16 Kg 210 210 210 260 260 260 290 290 290
Peso
Electrical cable gland
17 Pg 29 29 29 29 29 29 29 29 29
Passacavo entrata cavi
Compressed air outlet
18 “ Gas 1 1 1 1 1 1 1 1 1
Diametro uscita aria compressa

MODEL VE VE VE VE VE VE VE VE VE
MODELLO 2208C 2210C 2213C 3008C 3010C 3013C 3008CS 3010CS 3013CS
Normal operating pressure 11.5- 11.5-
1 Bar 6.5-7.5 8.5-9.5 6.5-7.5 8.5-9.5 6.5-7.5 8.5-9.5 11.5-12.5
Pressione normale/taratura 12.5 12.5
Max working pressure
2 Bar 8 10 13 8 10 13 8 10 13
Pressione max di esercizio
Minimum working pressure
3 Bar 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Pressione minima di esercizio
Air end model
4 Mod. SCA 10 SCA10 SCA 10 SCA 10 SCA10 SCA 10 SCA 10 SCA10 SCA 10
Tipo di compressore
Free air delivery ISO1217
5 m3/min 3.9 3.4 3.0 5.20 4.55 3.85 5.2 4.55 3.85
Aria resa effettiva ISO 1217
Air/oil receiver capacity
6 l 14 14 14 14 14 14 30 30 30
Capacità serbatoio aria/olio
Oil quantity
7 l 6 6 6 6 6 6 16 16 16
Quantita olio
Electric motor type Type B5 – B5 – B5 –
8 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55
Tipo di motore elettrico Tipo IP55 IP55 IP55
Motor power/Service factor
9 KW/s.f 22/1.0 22/1.0 22/1.0 30/1.0 30/1.0 30/1.0 30/1.0 30/1.0 30/1.0
Potenza motore/Fattore servizio
Full load current
10 A 41.7 41.7 41.7 54 54 54 54 54 54
Corrente a pieno carico
Electric fan power
11 kW 0.200 0.200 0.200 0.200 0.200 0.200 0.78 0.78 0.78
Potenza motore elettroventilatore
Recoverable heat
12 Kcal/h 15100 15100 15100 20000 20000 20000 20000 20000 20000
Calore recuperabile
Safety valve setting
13 bar 14 14 14 14 14 14 14 14 14
Taratura valvola di sicurezza
Noise level at 1 m
14 dB (A) 72 72 72 72 72 72 72 72 72
Livello rumore a 1 m
Dimensions 1135x650 1135x650 1135x65 1135x650 1135x650 1135x65 1135x650 1135x65 1135x650
15 mm
Dimensioni x1310 x1310 0x1310 x1310 x1310 0x1310 x1310 0x1310 x1310
Weight
16 Kg 320 320 320 340 340 340 470 470 470
Peso
Electrical cable gland
17 Pg 29 29 29 36 36 36 36 36 36
Passacavo entrata cavi
Compressed air outlet
18 “ Gas 1 1 1 1 1 1 1 1 1
Diametro uscita aria compressa

Instruction and maintenance manual – VE screw compressor 21


MODEL VE VE VE VE VE VE VE VE VE
MODELLO 3708C 3710C 3713C 3708H 3710H 3713H 4508H 4510H 4513H
Normal operating pressure 11.5-
1 Bar 6.5-7.5 8.5-9.5 11.5-12.5 6.5-7.5 8.5-9.5 6.5-7.5 8.5-9.5 11.5-12.5
Pressione normale/taratura 12.5
Max working pressure
2 Bar 8 10 13 8 10 13 8 10 13
Pressione max di esercizio
Minimum working pressure
3 Bar 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Pressione minima di esercizio
Air end model
4 Mod. SCA10 SCA 10 SCA 10 SCA 13 SCA13 SCA 13 SCA 13 SCA13 SCA 13
Tipo di compressore
Free air delivery ISO1217 3
5 m /min 6.20 5.45 4.80 6.35 5.60 4.8 7.5 6.8 5.8
Aria resa effettiva ISO 1217
Air/oil receiver capacity
6 l 30 30 30 30 30 30 30 30 30
Capacità serbatoio aria/olio
Oil quantity
7 l 16 16 16 16 16 16 16 16 16
Quantita olio
Electric motor type Type B5 – B5 – B5 –
8 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55 B5 – IP55
Tipo di motore elettrico Tipo IP55 IP55 IP55
Motor power/Service factor
9 Potenza motore / Fattore di KW/s.f 37/1.0 37/1.0 37/1.0 37/1.0 37/1.0 37/1.0 45/1.0 45/1.0 45/1.0
servizio
Full load current
10 A 65 65 65 65 65 65 80 80 80
Corrente a pieno carico
Electric fan power
11 kW 0.78 0.78 0.78 0.78 0.78 0.78 0.78 0.78 0.78
Potenza motore elettroventilatore
Recoverable heat
12 Kcal/h 25000 25000 25000 25000 25000 25000 30000 30000 30000
Calore recuperabile
Safety valve setting
13 bar 14 14 14 14 14 14 14 14 14
Taratura valvola di sicurezza
Noise level at 1 m
14 dB (A) 74 74 74 72 72 72 74 74 74
Livello rumore a 1 m
Dimensions 1440x780 1440x78 1440x780 1440x780 1440x780 1440x78 1440x780 1440x78 1440x780
15 mm
Dimensioni x1560 0x1560 x1560 x1560 x1560 0x1560 x1560 0x1560 x1560
Weight
16 Kg 500 500 500 550 550 550 630 630 630
Peso
Electrical cable gland
17 Pg 36 36 36 42 42 42 42 42 42
Passacavo entrata cavi
Compressed air outlet
18 “ Gas 1 1 1 1¼ 1¼ 1¼ 1¼ 1¼ 1¼
Diametro uscita aria compressa

MODEL VE
MODELLO 1815B
Normal operating pressure
1 Bar 13.5-14.5
Pressione normale/taratura
Max working pressure
2 Bar 15
Pressione max di esercizio
Minimum working pressure
3 Bar 5
Pressione minima di esercizio
Air end model
4 Mod. SCA 9
Tipo di compressore
Free air delivery ISO1217
5 m3/min 1.86
Aria resa effettiva ISO 1217
Air/oil receiver capacity
6 l 14
Capacità serbatoio aria/olio
Oil quantity
7 l 10
Quantita olio
Electric motor type Type
8 B5 – IP55
Tipo di motore elettrico Tipo
Motor power/Service factor
9 Potenza motore / Fattore di KW/s.f 18/1.0
servizio
Full load current
10 A 37.8
Corrente a pieno carico
Electric fan power
11 kW 0.200
Potenza motore elettroventilatore
Recoverable heat
12 Kcal/h 12700
Calore recuperabile
Safety valve setting
13 bar 14
Taratura valvola di sicurezza
Noise level at 1 m
14 dB (A) 72
Livello rumore a 1 m
Dimensions 1135x650
15 mm
Dimensioni x1310
Weight
16 Kg 260
Peso
Electrical cable gland
17 Pg 29
Passacavo entrata cavi
Compressed air outlet
18 “ Gas 1
Diametro uscita aria compressa

22 Instructions and maintenance manual - VE screw compressor -


R.C.R - REGISTRATION and COMMISSIONING REPORT

Distributor
Customer name
Compressor model ..................................................................... Date of installation…………………………….
Serial number ............................................................................. Date of adicomp invoice………………………
Year of manufacture .................................................................. and invoice number ……………………………

INSTALLATION
1. Location of compressor (compressor room, shop floor, outside, etc....) ..............................................................….…..
2. Atmosphere (dirty, dusty, damp, enclosed, ventilated, etc ) ……………………………………………………………
3. Ambient temperature (min and max)……………………………………………………………………………….(°C)
4. System of layout (compressor, receiver, dryer, filter, etc) ……………………………………………………………...

COMMISSIONING
5. Check oil level .................................................................................................................................…………………….
6. Check tightness of all electric components .................................................................................................…………….
7. Connect electrical supply:
a) Check voltage at input (Volt)
b) Check control voltage (auxiliary) (Volt)
8. Confirm correct direction of rotation:
a) Check on load current (Amp)
b) Check off load current (Amp)
c) Check overloads protection device (value) main motor
d) Check overloads protection device (value) fan motor.....................................................................………
9. Run compressor up to temperature and then check compressor for:
a) Air leaks ..................................................................….........................................................……………
b) b) Oil leaks ...............................................................……............................................................……...
c) Oil in scavenge transparent pipe..................................................................................................……….
10. Fill system to working pressure, then check:
a) System pressure set in / set out (Bar)
b) Air/oil receiver pressure on load/off load (Bar)
c) Load/off load cycles (Min)
d) Oil temperature with ambient temperature at °C (°C)

HANDING OVER
a) compressor start up/shut down procedure explained Yes/No
b) Customer servicing responsability explained Yes/No
c) Service contract required Yes/No
d) Handover
1. Cabinet key .................................................................................................................……….……...
2. Instruction book .............................................................................................................…………….
3. Parts book .....................................................................................................................……….……..
4. Copy registration and commissioning report (R.C.R.) .........................................................…….......

I am satisfied with the condition, installation and operation of my adicomp compressor


Customer signature …………………………………….. Engineer signature
Print name ……………………………………………… Print name
Position in company ................................................…....

One copy for customer - one copy for distributor - one copy for adicomp
Date of fault………………………. at operating hours ………………………
Faulty part ............................................................................................................................................……..……………..
............................................................................................................................................................………………….….
Reason ..................................................................................................................................................…………….……..
............................................................................................................................................................……………….…….
……………………………………………………………………………………………………………………………..
……………………………………………………………………………………………………………………………..
……………………………………………………………………………………………………………………………..
……………………………………………………………………………………………………………………………..

Instruction and maintenance manual – VE screw compressor 23


LOG BOOK TO CHEK MAINTENANCE

Working Prefiltration Air filter Oil filter Air/oil separator Oil Belt Date Signature
hours panel cartridge cartridge cartridge

Replacement

Replacement

Replacement

Replacement

Tensioning
differential
Pressure

Change

Change
Top up
Check

Check
Clean

Clean

24 Instructions and maintenance manual - VE screw compressor -


ATTACHED

-Electronic controller manual


-Electric diagram

Instruction and maintenance manual – VE screw compressor 25

You might also like