Professional Documents
Culture Documents
Important - click here for terms and conditions governing the use of this document.
Document History
Document Number Date Remarks
TM-000545-001A 12/2014 Original edition
TM-000545-001B 1/2015 Corrected part number in Table 8-1
Section 1
Introduction
1.1 Audience
This service manual is intended for technicians trained to service the Upper Control Card (UCC) as part of
the terminal alarm system.
This manual provides service information for the UCC. This manual also describes the following
information about the UCC:
• Functional requirements
• Communications capability
• Physical characteristics
• Electrical characteristics
• Embedded software
• On-board memory capacities
• USB interface
• Maintenance
• Troubleshooting
• Component pin out illustrations
Section 2
Upper Control Card Functional Requirements
The UCC provides input and output connections for the following:
The upper chassis is provided with two intrusion switches (primary and secondary) ports. The switch
circuits are normally closed (N.C.). These circuits will open when the fascia is opened (primary) or the
upper chassis rear access door is open (secondary). The signals are processed at the Upper Control
Card (UCC) and routed via the switch panel mount to the Lower Control Card (LCC) and the Alarm Out
interface cable.
Provide the ability to disable individual USB ports by command. May be accomplished by disabling
enumeration or disabling USB power, VBUS.
• Provide locking power connector that includes discrete lines connected to the ATM power switch
which will be connected directly to the ATM AC/DC module.
• Provide Upper Chassis Intrusion alarming capabilities by:
o Provide connection for safe door open/close monitoring used in maintenance operations
o Provide a door open/close port for primary entry, entry indicated by high logic
o Provide a door open/close port for secondary entry, entry indicated by high logic
• Provide four spare contacts for 5 VDC logic input as follows:
o IN1, J23 is allocated to equipment tray 1 closure switch
o IN2, J24, is allocated to equipment tray 2 closure switch in terminals with two equipment
trays in the upper chassis
o IN3, J25 is not allocated
o IN4, J26 is not allocated
• Provide (2) inputs for external sensor boards powered by the UCC.
• Provide two contacts in the power connector for the power switch signal from the UCC input
section.
• Provide a lock solenoid connection port.
• Provide signage output port used to activate signage light.
• Provide connector for remote status indicators, to include out of service, in service and supplies
low indicators.
• Provide four spare output contacts for 24 VDC output.
• Terminal shutdown with alarms still active, weekend mode. GREEN blink rate of one per second
while in weekend mode and six per second indication to release MOM switch.
• AC present in terminal indicated by GREEN LED controlled by AC/DC module.
• UCC board happy lights to indicate normal operation of UCC as follows:
o GREEN LED indicates U-controller is operating properly
o YELLOW LED indicates the terminal needs service
o RED LED indicate the U-controller is not operating correctly
• GREEN LED continuous for microcontroller operating.
• A BLUE LED on each USB port to indicate VBUS present.
• A GREEN LED on each USB port to indicate USB port enumeration.
UCC and cover will be used for the primary service entry into the ATM and provide the following:
• An ambient temperature sensor with an accuracy of +/- 2 degrees centigrade reported to Agilis
Module Interface (AMI) by an unsolicited message.
• A tilt sensor to monitor ATM mounting angle. A solicited message is generated and
communicated to the LCC via AMI when the UCC detects a 10 degree change in angle from the
last INIT value of the ATM.
2.2.3 Messaging
UCC shall generate the following USB event status messages and send as unsolicited messages to AMI
and forwarded by AMI to the listed device as follows:
The UCC will maintain and store all time stamped log files (two megabytes of nonvolatile memory
available) that are accessible as an AMI solicited message and includes the following:
• Sensor events.
• USB events.
• System events.
• Error status.
The UCC also provides access to AMI to module pairing table by access request message.
The UCC CCA is assembled as a module that includes the cover, switches and labels.
• Temperature 0° C to 60° C
o Max rate of change 10° C per hour
o
• Humidity 5 to 95% RH (non-condensing)
o Max rate of change 10% per hour
o High absolute humidity (32g/kg dry air; maximum wet bulb 35° C)
o Low absolute humidity (1g/kg dry air)
• Operate the terminal(s) from the 24 VDC supply voltage, with an acceptable input voltage range
of 21.6 volts to 26.4 volts
• Consume up to 10 watts of power.
• Customer supplied systems and sensors using UCC connections are to be self powered.
Section 3
Embedded Software
UCC uses the Freescale Kinetis K-61 chip set using Green Hills Multi firmware tools to provide the
following:
Section 4
UCC Maintenance
The UCC requires no adjustments or maintenance. Verify the following status LEDs:
Section 5
UCC Troubleshooting
Twenty-nine (29) light emitting diodes (LEDs) are mounted on the UCC and used to identify various
system status conditions. See Figure 5-1 and refer to Section 4.
UCC No +24V power available, D35, D36, and D37 LEDs Replace cable
24VDC OFF Replace power
power switch
failure • DC power cable fault
• Power switch fault Replace 400W
AC/DC power
• 400W AC/DC power supply fault supply
UCC 5VDC No 5VDC power available, D12 LED OFF Replace UCC
power
failure
UCC No 5VDC power available, any one of the following Replace UCC
3.3VDC LEDs are OFF D3,D4,D5,D6, D7,D8,
power D9,D20,D21,D22,D23,D24
failure
Communications USB hub USB cable faults Connect or
(7-port or 4- replace USB
port) signal cable
loss
UCC not functioning, any one of the following LEDs Attempt to reset
are OFF UCC code by
D10,D11,D13,D14,D15,D16,D17,D18,D19,D25,D26 pressing the
RESET button
on the UCC. If
this does not
correct the
problem, then
replace the UCC
USB bus fault Troubleshoot
USB hubs
HAPPY UCC fault Attempt to reset
Light status UCC code by
green LED pressing the
stops RESET button
flashing and on the UCC. If
yellow this does not
and/or red correct the
LED is problem, then
energized replace the UCC
Section 6
Diagnostics
Diagnostics for this module are handled through the terminal-resident Diebold Service Application (DSA)
software. There are no on-board diagnostics available for any of the alarm option components.
Section 7
Removing and Replacing the UCC
Refer to the appropriate terminal module removal and replacement manual for instructions.
Section 8
Parts
Field-replaceable parts are listed in this section.
CAUTION
The certifications received from various entities, for example: Canadian Standards Association
(CSA), Technischer Überwachungs Verein America (TUV) and Underwriters Laboratory (UL), are
based on the use of Diebold approved parts. Accordingly, Diebold strongly suggests that only
Diebold approved parts be used as replacement parts. Failure to do so may adversely impact the
reliability and safety of the equipment.
NOTE
• The Restriction of Hazardous Substances (RoHS) directive regulates the use of certain
materials in electrical and electronic equipment placed in the European Economic Area
(EEA) market starting July 1, 2006. Some parts listed in this document have both RoHS
compliant and RoHS noncompliant part numbers.
• RoHS compliant parts can be used in any equipment regardless of the equipment's
location or placed-in-market date.
• RoHS noncompliant parts can only be used in equipment located outside the EEA market
or in equipment placed in the EEA market before July 1, 2006.
Table 8-1 Upper Control Card (UCC) CCA
Item Diebold Part Number Description
Refer to Figure 8-1
[1]
1 49-246708-000E UCC, CCA
[1]
This part number is for the CCA only. To order the field replaceable assembly, use 49-254764-000A
Section 9
Wiring Diagrams for UCC CCA
See appropriate terminal cabling manuals for information on DC power, USB and logic cabling
connections.
GLOSSARY
ACU
AMI
CSA
CCA
DBDUSB
DSA
LCC
SRS
TUV
UCC
UL
Underwriters Laboratory