Aerzener AERtronic
Modbus communication
This document describes the easy startup of an AS 300 AERtronic control unit with RS-485 Modbus/RTU interface and an
FL COMSERVER UNI 232/422/485 Modbus gateway. The FL COMSERVER UNI converts serial data from Modbus/RTU
to Modbus/TCP and makes it available in any Ethernet network.
This document is only valid in association with the associated user manuals.
Make sure that you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog (FL COMSERVER UNI) and www.aerzener.com
(AS 300 AERtronic).
FL COMSERVER UNI + Aerzener AERtronic
The document describes the step-by-step startup of the AS 300 AERtronic control unit and the FL COMSERVER UNI
(item no. 2313452). The “Modbus Poll” software is running on a Windows PC serving as the Modbus master. Modbus Poll
reads the registers of the AS 300 via the FL COMSERVER UNI.
RS-485 +
RS-485 -
RS-485
+ - GND
AIR-Tronic
AS 300
FL COMSERVER UNI
1. Start the browser and enter the default IP address. In the site map, select the option “General
Configuration“. Select the option “Serial“. Enter the values as shown in the figure below.
Press “Confirm“.
2. Change to the menu ”General Configuration, Application“ and select the Modbus/TCP operation
mode.
Select
“MODBUS/TCP“.
Press “Confirm“.
3. In the site map, select the option “Save and Reboot“. Enter the values as shown in the figure below.
Enter the default password “private”. Press “Confirm”.
40024
3. Select Slave ID 1 (serial Modbus/RTU address of the AS 300) and the desired measured value.
4. To have access to the address 40025 (End pressure, Signed [mbar]), enter the address 40024.
In the documentation of the AS 300, you will find reference tables showing the measured values and the corresponding
Modbus addresses.
6. Select Modbus TCP/IP and enter the IP address of the FL COMSERVER UNI. The default
Modbus port is preset to 502.
7. Click ”OK“ to establish the connection between the FL COMSERVER UNI and the AS 300. The main
window shows the measured values of the AS 300.
5 Troubleshooting / FAQ
Error:
Yon cannot establish the connection to the FL COMSERVER UNI.
(”Modbus Connection Failed. Connect Timeout“ in Modbus Poll)
Reason:
- FL COMSERVER UNI is not connected to the Ethernet network.
- FL COMSERVER UNI is not set to Modbus mode.
Correction:
Open the web-based management and check the settings.
Note: At the FL COMSERVER UNI, you can see the current TCP connection via web-based management.
-> Under ”Device Information, General“ (bottom)
Error:
”Gateway target device failed to respond“ im Modbus Poll (Tx and error counters are counting up)
Reason:
- Serial parameters of the RS-485 interface are not correct.
- RS-485 interface is not selected.
- RS-485 wiring is wrong.
- Slave-ID in Modbus Poll is not correct.
Correction:
- Check the serial settings and the wiring of the FL COMSERVER UNI and the AS 300.
- Check the slave ID in Modbus Poll.
Note: At the FL COMSERVER UNI, the RS-485 terminal D(B) is used for the positive data wire.
Memory aid: ”B“ means „bositive“
Error:
”Illegal Data Value“ in Modbus Poll (Tx and error counters are counting up)
Reason:
Wrong main measured value address in Modbus Poll
Correction:
Set the right address via ”Read/Write Definition“ (see table).