- The grouting holes for the TSF construction project will be either 10m or 30-50m deep, with deeper holes only used if very fractured material is found at the base of shallower holes.
- Grouting will occur in 5m stages, with a water pressure test after each stage to check for fractures requiring grouting.
- Bentonite will not be required in the grout mix. Downstage grouting should be used where weathered rock is prevalent in upper strata.
- Consolidation grout holes should generally be drilled and grouted at least 10m in advance of curtain grout holes.
- The grouting holes for the TSF construction project will be either 10m or 30-50m deep, with deeper holes only used if very fractured material is found at the base of shallower holes.
- Grouting will occur in 5m stages, with a water pressure test after each stage to check for fractures requiring grouting.
- Bentonite will not be required in the grout mix. Downstage grouting should be used where weathered rock is prevalent in upper strata.
- Consolidation grout holes should generally be drilled and grouted at least 10m in advance of curtain grout holes.
- The grouting holes for the TSF construction project will be either 10m or 30-50m deep, with deeper holes only used if very fractured material is found at the base of shallower holes.
- Grouting will occur in 5m stages, with a water pressure test after each stage to check for fractures requiring grouting.
- Bentonite will not be required in the grout mix. Downstage grouting should be used where weathered rock is prevalent in upper strata.
- Consolidation grout holes should generally be drilled and grouted at least 10m in advance of curtain grout holes.
From: Morteza Taherian Date: 20 May 2014 Project Las Bambas TSF Construction Our Ref: 114001.05 ATCW SI 013 Subject: Grouting Holes
Dear Ricardo,
These are some clarification regarding the grouting holes, as below.
− The depth of the consolidation grout holes will be 10m – referenced to the top of prepared foundation level. − The depth of the curtain grout holes will be either 30m or 50m (referenced to the top of prepared foundation level), as illustrated on MWH dwgs OC-5525 and 5526. The only reason for deeper holes is if very fractured material is identified at the base of any hole. − The Principal reserves the right to order deeper holes if it is considered to be required. − There will be no change to hole diameter if deeper holes are specified. − Coring is not required. − Grout stages will be 5.0m. − All grout stages shall have a Water Pressure (i.e. packer) Test conducted, if the test returns a Lugeon value of less than 5.0, pressure grouting will not be required. − Bentonite will not be required in the grout mix. − The method of upstage grouting is generally acceptable, however, where weathered rock is prevalent in the upper strata, the method of downstage grouting should be locally employed. − Unless otherwise approved by the Principal’s Representative, Drilling and grouting of consolidation grout holes should in general be completed at least 10m in advance of the curtain grout holes.
Regards, Morteza