User’s Guide
Over Current & Earth Fault Relay: PAC-E100
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
Table of Contents
1. Overview ........................................................................ 5
1.1. Features ......................................................................... 5
1.2. Functional Single line Diagram ................................... 6
2/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
3/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
4/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
1. Overview
1.1. Features
Numerical-type Over Current (OCR), Ground Over Current (OCGR), Thermal
Overload, Under Current, and Negative Phase Sequence Over Current Protections
Various TC Curves including 4 IEC Curves, 7 ANSI Curves, 2 KEPCO’s Induction-
type Compatible Curves
Digital Indication of Setting and Metering on LCD (2 Lines × 16 Characters)
Self-Diagnosis and Internal Status Monitoring
Operation Blocking of Individual Relay Element by External Contact Inputs during the
Relay Maintenance
Configurable System Frequency (50 / 60Hz)
Easy setting of 4 Contact Outputs and 4 Programmable LED to use Logic
Contact Output: Available Trip and Signaling Contact
Direct Trip/Close Control of 1 CB from Front Panel Locally and SCADA remotely
Useful PC Application (Setting Tool)
: System Configuration, Protection & Logic Setting, Monitoring & Measurement
Self-Test Function of Contact Output by Manual Trip Emulation
Access Security by Password for Setting Change and CB Control.
Communication Interface
- RS-232C (Front and Rear), RS485C (SCADA Communication)
- Protocol: MODBUS, DNP3.0, IEC60870-5-103
Measurement: 3-phase Currents, Sequence Currents, Thermal, Frequency
EMI/EMC Performance Reinforced.
5/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
46 37 49
52
PAC-E100
6/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
2. Technical Data
2.1.6. Case
Construction Draw-out type
IP Protection Level IP51
Material Steel with Hard-Combustion Plastic Cover
7/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
ANSI/IEEE
-Inverse (ANSI_I)
TC Curve -Short Inverse (ANSI_SI)
-Long Inverse (ANSI_LI)
-Moderately Inverse (ANSI_MI)
-Very Inverse (ANSI_VI)
-Extremely Inverse (ANSI_EI)
-Definite Inverse (ANSI_DI)
ANSI/IEEE
TC Curve -Inverse (ANSI_I)
-Short inverse (ANSI_SI)
-Long inverse (ANSI_LI)
-Moderately inverse (ANSI_MI)
-Very inverse (ANSI_VI)
-Extremely inverse (ANSI_EI)
-Definite inverse (ANSI_DI)
8/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
9/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
10/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
11/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
12/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
3. Functional Description
⎛ ⎞
⎜ ⎟
⎜ ⎟
⎟ × TM (sec )
K
T =⎜ L
+ C
⎜⎛ G ⎞ ⎟
⎜ ⎜⎜ ⎟⎟ − 1 ⎟
⎝ ⎝ GS ⎠ ⎠
Curve K L C
IEC normal inverse (IEC_NI) 0.14 0.02 0.00
IEC very inverse (IEC_VI) 13.50 1.00 0.00
IEC extremely inverse (IEC_EI) 80.00 2.00 0.00
IEC long inverse (IEC_LI) 120.00 1.00 0.00
ANSI inverse (ANSI_I) 8.9341 2.0938 0.17966
ANSI short inverse (ANSI_SI) 0.2663 1.2969 0.03393
ANSI long inverse (ANSI_LI) 5.6143 1 2.18592
ANSI moderately inverse (ANSI_MI) 0.0103 0.02 0.0228
ANSI very inverse (ANSI_VI) 3.922 2 0.0982
ANSI extremely inverse (ANSI_EI) 5.64 2 0.02434
ANSI definite inverse (ANSI_DI) 0.4797 1.5625 0.21359
KEPCO normal inverse (KNI) 0.11 0.02 0.42
KEPCO very inverse (KVI) 39.85 1.95 1.08
T : Trip time in second
K,C,L : Constants
G : Current input
GS : Pickup current setting
TM : Time multiplier
Trip time for G/Gs ≥20 are identical to those for G/Gs = 20.
13/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
FUNCTION
= ENABLE 50_PKP_A
50_PKP_OR
IA > 50_PKP_B
PICKUP
50_PKP_C
IB >
PICKUP
BLOCK 50_OP_C
= YES
..
.
CONT IN #1
=1
CONNECTION
= PROT_BLK
.
.
.
CONT IN #4
=1
CONNECTION
= PROT_BLK
14/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
FUNCTION
= ENABLE 51_PKP_A
51_PKP_OR
IA > 51_PKP_B
PICKUP
51_PKP_C
IB >
PICKUP
CURVE
51_OP_C
BLOCK
= YES
..
.
CONT IN #1
=1
CONNECTION
= PROT_BLK
.
.
.
CONT IN #4
=1
CONNECTION
= PROT_BLK
15/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
FUNCTION
= ENABLE 50N_PKP
IN >
PICKUP
BLOCK
= YES
..
. DELAY 50N_OP
CONT IN #1
=1
CONNECTION
= PROT_BLK
.
.
.
CONT IN #4
=1
CONNECTION
= PROT_BLK
IN:INFeeder
: 피더 지락전류
Ground Current
FUNCTIONSetting
FUNCTION: : 순시Function
지락 과전류계전요소의 Function
of Instantaneous Ground Over설정
Current
PICKUP:
PICKUPSetting
: 순시Pickup of Instantaneous Ground
지락 과전류계전요소의 Over 설정값
PICKUP Current
DELAY:
DELAYSetting
: 순시Delay
지락 of Instantaneous Ground
과전류계전요소의 Over 설정값
DELAY Current
BLOCK: Setting Block Instantaneous
BLOCK : 순시 지락 과전류계전요소의 BLOCK 설정 Ground Over Current
CONNECTION-PROT_BLK: Connection of Contact input is shown PROT_BLK
CONNECTION = PROT_BLK : 접점입력 CONNECTION이
CONT IN #1~#4-1: Contact input is LOGIC “1”
PROT_BLK임을 나타냄
CONT INEach
50N_PKP: #1~#4 =1pickup
phase : 접점입력의 상태가 LOGIC
for Instantaneous Ground"1"임
Over Current
50N_OP: Each phase Operation for Instantaneous Ground Over Current
50N_PKP : 순시 지락 과전류 계전요소의 Pickup
50N_OP : 순시 지락 과전류 계전요소의 Operation
16/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
FUNCTION
= ENABLE 51N_PKP
IN >
PICKUP
CURVE
Multiplier 51N_OP
BLOCK
= YES
..
.
CONT IN #1
=1
CONNECTION
= PROT_BLK
.
.
.
CONT IN #4
=1
CONNECTION
= PROT_BLK
INFeeder
IN: : 피더Ground
지락전류 Current
FUNCTIONSetting
FUNCTION: : 한시 Function
지락 과전류계전요소의 Function
of Time-delayed Ground Over설정
Current
PICKUPSetting
PICKUP: : 한시Pickup
지락 과전류계전요소의
of Time-delayed Ground PICKUP
Over 설정값
Current
CURVE:
CURVESetting
: 한시Curve
지락 of Time-delayed
과전류 계전요소의 Ground Over Current
CURVE 설정
MULTIPLIER:
MULTIPLIER Setting
: 한시 Multiplier
지락 과전류계전요소의 of Time-delayed Ground Over Current
MULTIPLIER 설정값
BLOCK: Setting Block Time-delayed Ground Over Current
BLOCK : 한시 지락 과전류계전요소의 BLOCK 설정
CONNECTION-PROT_BLK: Connection of Contact input is shown PROT_BLK
CONNECTION
CONT IN #1~#4-1:= PROT_BLK
Contact input: is
접점입력 CONNECTION이
LOGIC “1”
PROT_BLK임을 나타냄
CONT INEach
51N_PKP: #1~#4 =1pickup
phase : 접점입력의 상태가 LOGIC
for Time-delayed "1"임
Over Current
51N_OP: Each phase Operation for Time-delayed Over Current
51N_PKP : 한시 지락 과전류 계전요소의 Pickup
51N_OP : 한시 지락 과전류 계전요소의 Operation
17/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
[Trip TC Curve]
t Trip time
τ Temperature rise time constant
I Load current
IP Pre-load current
k Setting factor
IN Nominal current
18/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
FUNCTION
= ENABLE Time Thermal >
Constant ALARM
49_ALARM
Imax >
K-factor * In
BLOCK
= YES
.. Thermal
. >= 100 % 49_OP
CONT IN #1
=1
CONNECTION
= PROT_BLK
.
.
.
CONT IN #4
=1
CONNECTION
= PROT_BLK
19/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
FUNCTION
= ENABLE 37_PKP_A
37_PKP_OR
IA < 37_PKP_B
PICKUP
37_PKP_C
IB <
PICKUP
CONNECTION
= PROT_BLK
.
.
.
CONT IN #4
=1
CONNECTION
= PROT_BLK
IA / IB / IC : A/B/C
IA/IB/IC: A/B/C상phase
피더전류 Feeder Current
FUNCTION : 저전류계전요소의 Function 설정
FUNCTION:
PICKUP Setting Function
: 저전류계전요소의 PICKUPof Under Current
설정값
PICKUP:
DELAY Setting PickupDELAY
: 저전류계전요소의 of Under
설정값 Current
BLOCK
DELAY: : 저전류계전요소의
Setting Delay ofBLOCK
Under설정
Current
CONNECTION
BLOCK: Setting= PROT_BLK
Block :Under
접점입력 CONNECTION이
Current
PROT_BLK임을 나타냄
CONNECTION-PROT_BLK: Connection
CONT IN #1~#4 =1 : 접점입력의 상태가 LOGIC "1"임
of Contact input is shown PROT_BLK
CONT IN #1~#4-1: Contact input is LOGIC “1”
37_PKP_A/B/C : 저전류 계전요소의 상별 Pickup
37_PKP_OR : 저전류Each
37_PKP_A/B/C: 계전요소의phase 최소 한상이
pickup Pickup Current
for Under
37_OP_A/B/C
37_PKP_OR: : 저전류 계전요소의
The least 1 phase상별
for Operation
Under Current
37_OP_OR : 저전류 계전요소의 최소 한상이 Operation
37_OP_A/B/C: Each phase Operation for Under Current
37 OP OR: The least 1 phase for Under Current is Operation
20/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
FUNCTION
= ENABLE 46_PKP
I2 >
PICKUP
BLOCK
= YES
..
. DELAY 46_OP
CONT IN #1
=1
CONNECTION
= PROT_BLK
.
.
.
CONT IN #4
=1
CONNECTION
= PROT_BLK
I2 : 역상전류
I2: Negative Current
FUNCTION Setting
FUNCTION: : 역상 Function
과전류계전요소의 Function
of Negative Phase 설정 Over Current
Sequence
PICKUPSetting
PICKUP: : 역상 Pickup
과전류계전요소의 PICKUP
of Negative Phase 설정값
Sequence Over Current
DELAYSetting
DELAY: : 역상 Delay
과전류계전요소의 DELAY
of Negative Phase 설정값
Sequence Over Current
BLOCK : 역상
MULTIPLIER: 과전류계전요소의
Setting BLOCK 설정
Multiplier of Time-delayed Ground Over Current
CONNECTION
BLOCK: = PROT_BLK
Setting Block Negative:Phase
접점입력 CONNECTION이
Sequence Over Current
PROT_BLK임을 나타냄 Connection of Contact input is shown PROT_BLK
CONNECTION-PROT_BLK:
CONTININ#1~#4-1:
CONT #1~#4 Contact
=1 : 접점입력의 상태가
input is LOGIC “1”LOGIC "1"임
46_PKP:
46_PKPEach
: 역상phase
과전류pickup계전요소의
for NegativePickup
Phase Sequence Over Current
46_OP: Each phase Operation for
46_OP : 역상 과전류 계전요소의 Operation Negative Phase Sequence Over Current
21/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
CB OPEN / CLOSE
This function performs trip (open)/close control actions of CB. CB Open or Close button on
the front panel is activated only on the Local mode (“L” LED on). On the Remote mode, only
control command from SCADA through communication is accepted.
Before control command via front panel, SELECT button and Password enter are required
first. SELECT button is the concept to prevent the mal-operation on the front panel and this
concept is the same with SBO (Select Before Operate) concept in communication protocol, i.e.
DNP3.0, where SCADA (master system) selects first the equipment to control remotely before
setting out actual control command to keep other masters from selecting the same equipment so
that control right is granted to that SCADA only. This dedicated concept is adopted equally to
Local control and this is also used for mal-operation prevention of direct open/close command.
After the correct password enter and SELECT button again, then a phrase that CB is selected is
displayed on LCD and SELECT LED is blinking. After while, CB OPEN/CLOSE buttons are
activated for 15 seconds.
22/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
Input#1
Input#2
Input#3
Input#4 Reset Type
Input#5
Input#6 = Self Contact Out
Input#7
Input#8 #1 ~ #4
Input#1
Input#2
Input#3
Input#4 0.00 ~ 60.00
Input#5
Input#6
Input#7
Input#8
LED#1~#4
Input#1
Input#2
Reset Type
Input#3
Input#4 = Manual
Input#5
Input#6
Input#7
Input#8
Input#1
S Q
Input#2
Input#3
Input#4
Input#5 R
Input#6
Input#7
Input#8
Logic Annunciator
23/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
24/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
3.2.5. Communication
1 RS232 Port (19200 BPS, ModBus Protocol)
Front
For maintenance and Setting software (Engineering Tool)
1 RS232 Port (19200 BPS, ModBus Protocol)
For maintenance and Setting software (Engineering Tool)
Rear 1 RS485 Port (300 ~ 38400 BPS, DNP3.0/Modbus/
IEC870-5-103 Protocol)
For SCADA communication
25/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
System Configuration & Set Value Upload to PC and Batch Download to PAC-E100
Set Value & Recorded Data Saving
The manipulation of setting software is explained in more detail on chapter 6 and the
following figure shows protection page of setting program.
26/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
4. Operational Description
조임 나사
Screw
Display
Display LCD LCD
Indicators
Indicators LED LED -2 각종 계측치
Line LCD 및 설정 정보를
for indicating
--Run
전원LED 인가 상태 LED 표시하기
metering and위한 2Line
setting valueLCD
--System
자기진단 Error상태
LED표시 LED
--Protection
보호계전Element 요소 Pickup
Pickup LED
LED
--Protection
보호계전Element 요소 Trip
TripLED
LED Programmable LED
4 Configurable LED
- 사용자의 설정에 맞게 표시하
방향 Key
Up/Down/Left/Right 기 위한 LED
Key
- 설정값 변경 및 메뉴간 이동
Reset Key
Reset Key
- 계전기 보호요소 동작 복귀,
CB차단기 제어부
Control LED LED 자기진단기능 수동 복귀
--Local/Remote
제어권(Local)표시 LED LED
--Control
제어권(Remote)표시
Select LED LED Menu Key
Menu Key
--CB
차단기Open제어LED 선택 LED
--CB
차단기CloseOpen
LED LED -Confirm
설정된and 정정치 확인
Change 및value
of set 변경
- 차단기 Close LED
Enter Key
Enter Key
CB차단기
Control Key Key
제어부 --Confirm
정정치 set 설정 확인,
value and 비밀번호
Password
--Local/Remote
차단기 제어권 Key변경 Key 확인 Key
--Control
차단기Select
제어 Key
선택 Key
--CB
차단기Open Open
Key Key
--CB
차단기CloseClose
Key Key RS232 Connector
RS232 Port for
-Local
PC와의Maintenance
연계를 위한 RS232
조임 나사
Screw 통신 포트
27/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
4.1.2. LEDs
4.1.3. Keypad
UP
Menu Move, Value Change
DOWN
ARROW
RIGHT Menu Move, Menu Item Selection
LEFT
Menu Move, Escape to Upper Menu / Cancel Item
RESET Manual Reset of System Error and Trip LED
MENU Enter into Menu Tree Display
ENT Setting Value Enter and Confirm
L/R Local / Remote Control Mode Change
CONTROL SELECT CB Control Selection
(Password) OPEN CB Trip Control
CLOSE CB Close Control
28/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
29/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
SETTING menu is composed of SYSTEM and PROTECTION sub menus. This menu is
used for settings modification. SYSTEM menu is composed of POWER SYSTEM, CB
CONTROL, COM, DNP3.0, CONTACT INPUT, CONTACT OUTPUT, LED, and
PASSWORD. POWER SYSTEM is used for setting of frequency, frequency tracking, phase CT
ratio and ground CT. CB CONTROL is used for time setting TRIP and CLOSE PULSE. COM
is used for communication setting. DNP3.0 is used for setting of DNP when communication
method is DNP3.0. CONTACT INPUT / OUTPUT and LED are used for setting contact
input/output and Programmable LED respectively. PASSWORD is used when change password.
PROTECTION menu is composed of protection elements, IOC1 (50_1), IOC2 (50_2),
TOC (51), IOCG1 (50N_1), IOCG2 (50N_2), TOCG (51N), THERMAL (49), UC (37), and
NSOC (46), and is used setting each of protection elements.
COMMAND menu is composed of CONT OUT TEST and PANEL TEST sub menus. This
menu is used to test output contacts and LCD/LEDs of front-face display panel.
30/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
MAIN
DISPLAY STATUS CONTACT INPUT CONT IN#1 ~ 4
Display
CONTACT OUTPUT CONT OUT#1 ~ 4
SELF DIAGNOSIS MEMORY
SETTING
AD CONVERTER
CALIBRATION
PROTECTION IOC1(50_1), IOC2(50_2),
TOC(51), IOCG1(50N_1),
IOCG2(50N_2), TOCG(51N),
THERMAL(49), UC(37),
NSOC(46)
PASSWORD
PROTECTION IOC1(50_1) FUNCTION, PICKUP,
DELAY, BLOCK
31/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
PAC - E 1 0 0
S Y S T EM OK
PAC - E 1 0 0
S Y S T EM ERROR
PAC - E 1 0 0 ▶D I S P L A Y
MENU
S Y S T EM OK
▶S E T T I N G
MENU
▶ C O MM A N D
MENU
32/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶D I S P L A Y ▶D I S P L A Y
ENT
▶S T A T U S
▶D I S P L A Y
▶M E A S U R E
▶D I S P L A Y
▶S Y S T EM I NFO .
4.4.1.1. DISPLAY/STATUS
DISPLAY menu is composed of CONTACT INPUT, CONTACT OUTPUT, SELF
DIAGNOSIS, and PROTECTION sub menu.
Each of sub menus shows contact input, contact output, self-diagnosis and operating status
of protection elements.
▶D I S P L A Y ▶S T A T U S
▶S T A T U S ▶C O N T A C T I NPUT
▶S T A T U S
▶C O N T A C T OUT P UT
▶S T A T U S
▶S E L F D I AGNO S I S
▶S T A T U S
▶P R O T E C T I O N
33/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶S T A T U S CONT I N# 1 1 / 4
▶C O N T A C T I NPUT : OFF
CONT I N# 2 2 / 4
: OFF
CONT I N# 3 3 / 4
: OFF
CONT I N# 4 4 / 4
: OFF
▶S T A T U S CONT OUT # 1 1 / 4
▶C O N T A C T OUT PUT : DE ENERG I Z ED
CONT OUT # 2 2 / 4
: DE ENERG I Z ED
CONT OUT # 3 3 / 4
: DE ENERG I Z ED
CONT OUT # 4 4 / 4
: DE ENERG I Z ED
▶S T A T U S ME MO R Y 1 / 4
▶S E L F D I AGNO S I S : OK
S ETT I NG 2 / 4
: OK
34/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
AD CONVERT ER 3 / 4
: OK
CAL I BRAT I ON 4 / 4
: OK
4.4.1.5. DISPLAY/STATUS/PROTECTION
This menu displays picked-up started and operated status of 9 protection elements. Phase
elements show started and operated phases A, B, and C, and ground elements show “PK” and
“OP” symbols, when the fault current is picked up and the relaying element is signaled to
operate.
▶S T A T U S I OC 1 ( 5 0 _ 1 ) 1 / 9
▶P R O T E C T I O N PKP : ABC , OP : ABC
I OC 2 ( 5 0 _ 2 ) 2 / 9
PKP : ABC , OP : ABC
TOC ( 5 1 ) 3 / 9
PKP : ABC , OP : ABC
I OCG 1 ( 5 0 N _ 1 ) 4 / 9
PKP : PKP , OP : OP
I OCG 2 ( 5 0 N _ 2 ) 5 / 9
PKP : PKP , OP : OP
TOCG ( 5 1 N ) 6 / 9
PKP : PKP , OP : OP
T H E RMA L ( 4 9 ) 7 / 9
PKP : PKP , OP : OP
UC ( 3 7 ) 8 / 9
PKP : ABC , OP : ABC
N SOC ( 4 6 ) 9 / 9
PKP : PKP , OP : OP
35/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
4.4.1.6. DISPLAY/MEASURE
This menu displays measurement and metering data of electric values. PAC-E100 has 4
current input. (Frequency is show according to input value of A-phase current.)
▶D I S P L A Y CURR ( I A ) 1 / 1 2
▶M E A S U R E : 0 . 0 0 A , < 0 . 0
CURR ( I B ) 2 / 1 2
: 0 . 0 0 A , < 0 . 0
CURR ( I C ) 3 / 1 2
: 0 . 0 0 A , < 0 . 0
CURR ( I N ) 4 / 1 2
: 0 . 0 0 A , < 0 . 0
S EQ ( I 0 ) 5 / 1 2
: 0 . 0 0 A , < 0 . 0
S EQ ( I 1 ) 6 / 1 2
: 0 . 0 0 A , < 0 . 0
S EQ ( I 2 ) 7 / 1 2
: 0 . 0 0 A , < 0 . 0
THD ( I A ) 8 / 1 2
: 0 . 0 %
THD ( I B ) 9 / 1 2
: 0 . 0 %
THD ( I C ) 1 0 / 1 2
: 0 . 0 %
T H E RMA L 1 1 / 1 2
: 0 . 0 %
FREQUENCY 1 2 / 1 2
: 0 . 0 0Hz
36/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶D I S P L A Y PAC - E 1 0 0
▶S Y S T EM I NFO . V e r : V1 . 0 0
37/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶S E T T I N G ▶S E T T I N G
ENT
▶S Y S T EM
▶S E T T I N G
▶P R O T E C T I O N
4.4.2.1. SETTING/SYSTEM
SYSTEM menu is composed of POWER SYSTEM, CB CONTROL, COM, DNP3.0,
CONTACT INPUT, CONTACT OUTPUT, LED, and PASSWORD. POWER SYSTEM is used
for setting of frequency, frequency tracking, phase CT ratio and ground CT. CB CONTROL is
used for time setting TRIP and CLOSE PULSE. COM is used for communication setting.
DNP3.0 is used for setting of DNP when communication method is DNP3.0. CONTACT
INPUT / OUTPUT and LED are used for setting contact input/output and Programmable LED
respectively. PASSWORD is used when change password.
▶S E T T I N G ▶S Y S T EM
▶S Y S T EM ▶P OWE R S Y S T EM
▶S Y S T EM
▶C B CONTROL
▶S Y S T EM
▶C O M
▶S Y S T EM
▶D N P 3 . 0
▶S Y S T EM
▶C O N T A C T I NPUT
▶S Y S T EM
▶C O N T A C T OUT P UT
38/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶S Y S T EM
▶L E D
▶S Y S T EM
▶ P A S S WO R D
▶S E T T I N G FREQUENCY 1 / 4
▶P OWE R S Y S T EM : 6 0 H z
FREQ TRACK 2 / 4
: D I SABLE
PHS CT RAT I O 3 / 4
: 5 : 5
GND CT RAT I O 4 / 4
: 5 : 5
Setting Basic
Item Range Description
unit value
FREQUENCY 50Hz / 60Hz 60Hz Frequency setting
FREQ TRACK ENABLE/DISABLE DISABLE Frequency tracking setting
PHS CT RATIO 1 ~ 6000: 5 1 5 Phase CT ratio setting
GND CT RATIO 1 ~ 6000: 5 1 5 Ground CT ratio setting
39/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶S E T T I N G TR I P PUL S E 1 / 2
▶C B CONTROL : 5 . 0 s
CLOS E PULSE 2 / 2
: 5 . 0 s
Setting Basic
Item Range Description
unit value
TRIP PULSE 0.1 ~ 5.0s 0.1s 5.0s Time setting of CB Trip
CLOSE PULSE 0.1 ~ 5.0s 0.1s 5.0s Time setting of CB Close
4.4.2.4. SETTING/SYSTEM/COM
COM menu is composed of FUNCTION, SLAVE ADDR, BPS, and PROTOCOL and each
menu set up communication function, slave address, BPS and protocol.
▶S E T T I N G F UNCT I ON 1 / 4
▶C O M : D I SABLE
S LAVE ADDR 2 / 4
: 1
BP S 3 / 4
: 3 0 0
PROTOCOL 4 / 4
: MO D B U S
Setting Basic
Item Range Description
unit value
FUNCTION ENABLE/DISABLE DISABLE Setting of use or not
SLAVE ADDR 1 ~ 65534 1 1 Slave address setting
Setting of
BPS 300 ~ 38400 9600
communication speed
PROTOCOL MODBUS/DNP3.0/IEC870 MODBUS Protocol setting
40/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
4.4.2.5. SETTING/SYSTEM/DNP3.0
DNP3.0 menu is composed of TX DELAY, LINK CONFIRM, LINK RETRY, LINK
TIMEOUT, SBO TIMEOUT, WR TIME INT and COLD RESTART, and each menu set up Tx
delay, Link confirm, Link retry, Link timeout, SBO timeout, Write time interval and Cold restart.
▶S E T T I N G TX DELAY 1 / 7
▶D N P 3 . 0 : 0 m s e c
L I NK C O N F I RM 2 / 7
: NEVER
L I NK RETRY 3 / 7
: 1
L I NK T I ME OU T 4 / 7
: 1 m s e c
S BO T I ME O U T 5 / 7
: 1 m s e c
WR T I ME I NT 6 / 7
: 0 m i n
COL D RE S TART 7 / 7
: D I SABLE
Setting
Item Range Basic value Description
unit
TX DELAY 0 ~ 65000msec 1msec 0msec Tx delay setting
NEVER/ALWAYS
LINK CONFIRM NEVER Link confirm setting
/SOMETIMES
LINK RETRY 0~5 1msec 0 Link retry setting
LINK TIMEOUT 1 ~ 65000msec 1msec 1msec Link timeout setting
SBO TIMEOUT 1 ~ 65000msec 1msec 1msec SBO timeout setting
WR TIME INT 0 ~ 65000min 1min 0min Write time interval setting
COLD RESTART ENABLE/DISABLE DISABLE Cold restart setting
41/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶S E T T I N G CONT I N# 1 1 / 4
▶C O N T A C T I NPUT : NOT _ CONNECT ED
CONT I N# 2 2 / 4
: NOT _ CONNECT ED
CONT I N# 3 3 / 4
: NOT _ CONNECT ED
CONT I N# 4 4 / 4
: NOT _ CONNECT ED
Setting
Item Range Basic value Description
unit
NOT_CONNECTED/
CB_OPENED/
CB_CLOSED/ Setting of contact
CONT IN #1~#4 NOT_CONNECTED
ANNUN_RESET/ input
PROT_BLOCK/
GENERAL_INPUT
Contact Input
Description
elements
NOT_CONNECTED No effect
CB_OPENED Open CB, when input is logic “1”.
CB_CLOSED Close CB, when input is logic “1”
ANNUN_RESET Operate Annunciator Reset, if there is status change of Input Logic.
Do action that protection element make BLOCK, when input is logic
PROT_BLOCK
“1” and BLOCK of protection element is “Yes”.
GENERAL_INPUT Used general Contact Input
42/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶S E T T I N G ▶C O N T A C T OUT P UT
▶C O N T A C T OUT PUT ▶C O N T OUT # 1
▶C O N T A C T OUT P UT
▶C O N T OUT # 2
▶C O N T A C T OUT P UT
▶C O N T OUT # 3
▶C O N T A C T OUT P UT
▶C O N T OUT # 4
I NPUT # 1 2 / 1 1
: L _OF F
I NPUT # 2 3 / 1 1
: L _OF F
I NPUT # 3 4 / 1 1
: L _OF F
I NPUT # 4 5 / 1 1
: L _OF F
I NPUT # 5 6 / 1 1
: L _OF F
I NPUT # 6 7 / 1 1
: L _OF F
43/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
I NPUT # 7 8 / 1 1
: L _OF F
I NPUT # 8 9 / 1 1
: L _OF F
RE S ET TYPE 1 0 / 1 1
: S ELF
RE S ET DELAY 1 1 / 1 1
: 6 0 . 0 0 s
Setting Basic
Item Range Description
unit value
OR8/HALF-OR8/
LOGIC OR8 Operator setting
AND8/HALF-AND8
Refer to
INPUT #1~#8 Input setting of Operator
Table 3.2.3.3.
Form of Contact Output
RESET TYPE SELF/MANUAL
setting
Off delay setting (Activated
RESET DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec when RESET TYPE is
“SELF”)
44/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
4.4.2.8. SETTING/SYSTEM/LED
PAC-E100 provides 4 Programmable LED for the convenience of user. The setting method
is same with CONTACT OUTPUT.
▶S E T T I N G ▶L E D
▶L E D ▶L E D # 1
▶L E D
▶L E D # 2
▶L E D
▶L E D # 3
▶L E D
▶L E D # 4
- LED (LED#1 ~ 4)
▶L E D LOG I C 1 / 1 1
▶L E D # 1 : OR 8
I NPUT # 1 2 / 1 1
: L _OF F
I NPUT # 2 3 / 1 1
: L _OF F
I NPUT # 3 4 / 1 1
: L _OF F
I NPUT # 4 5 / 1 1
: L _OF F
I NPUT # 5 6 / 1 1
: L _OF F
I NPUT # 6 7 / 1 1
: L _OF F
I NPUT # 7 8 / 1 1
: L _OF F
I NPUT # 8 9 / 1 1
: L _OF F
45/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
RE S ET TYPE 1 0 / 1 1
: S ELF
RE S ET DELAY 1 1 / 1 1
: 6 0 . 0 0 s
Setting Basic
Item Range Description
unit value
OR8/HALF-OR8/
LOGIC OR8 Operator setting
AND8/HALF-AND8
INPUT #1~#8 Table 3.2.3.3. 참조 Input setting of Operator
Form of Contact Output
RESET TYPE SELF/MANUAL
setting
Off delay setting (Activated
RESET DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec when RESET TYPE is
“SELF”)
4.4.2.9. SETTING/SYSTEM/PASSWORD
There are 2 types of passwords for PAC-E100: Settings modification password and Control
action password. Both passwords are same and 4-digit decimal 0~9 numbers and have the initial
values of “0000” on delivery of PAC-E100.
▶S Y S T EM N EW P A S S WO R D
▶ P A S S WO R D : * * * *
46/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
4.4.2.10. SETTING/PROTECTION
PROTECTION menu is composed of protection elements, IOC1 (50_1), IOC2 (50_2),
TOC (51), IOCG1 (50N_1), IOCG2 (50N_2), TOCG (51N), THERMAL (49), UC (37), and
NSOC (46), and is used setting each of protection elements.
▶S E T T I N G ▶P R O T E C T I O N
▶P R O T E C T I O N ▶I OC 1 ( 5 0 _ 1 )
▶P R O T E C T I O N
▶I OC 2 ( 5 0 _ 2 )
▶P R O T E C T I O N
▶T O C ( 5 1 )
▶P R O T E C T I O N
▶I OCG 1 ( 5 0 N _ 1 )
▶P R O T E C T I O N
▶I OCG 2 ( 5 0 N _ 2 )
▶P R O T E C T I O N
▶T O C G ( 5 1 N )
▶P R O T E C T I O N
▶T H E R M A L ( 4 9 )
▶P R O T E C T I O N
▶U C ( 3 7 )
▶P R O T E C T I O N
▶N S O C ( 4 6 )
47/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶P R O T E C T I O N F UNCT I ON 1 / 4
▶I OC 1 ( 5 0 _ 1 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 6 0 . 0 0 s
BLOCK 4 / 4
: NO
Setting
Item Range Basic value Description
unit
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec Operation delay time setting
Ban protection function
It is set PROT_BLOCK of
Contact Input, and banned
BLOCK YES/NO NO
protection function when
Contact input status is Logic
“1”.
48/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶P R O T E C T I O N F UNCT I ON 1 / 4
▶I OC 2 ( 5 0 _ 2 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 6 0 . 0 0 s
BLOCK 4 / 4
: NO
Setting
Item Range Basic value Description
unit
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec Operation delay time setting
Ban protection function
It is set PROT_BLOCK of
Contact Input, and banned
BLOCK YES/NO NO
protection function when
Contact input status is Logic
“1”.
49/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶P R O T E C T I O N F UNCT I ON 1 / 6
▶T O C ( 5 1 ) : D I SABLE
CURVE 2 / 6
: I EC_ N I
P I CKU P 3 / 6
: 2 0 . 0 0 A
MU L T I P L I E R 4 / 6
: 1 0 . 0 0
RE S ET TYPE 5 / 6
: I NST
BLOCK 6 / 6
: NO
Setting
Item Range Basic value Description
unit
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
IEC_NI/IEC_VI/
IEC_EI/IEC_LI/
ANSI_I/ANSI_SI/
CURVE IEC_NI TC Curve setting
ANSI_LI/ANSI_MI/
ANSI_VI/ANSI_EI/
ANSI_DI/KNI/KVI
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
MULTIPLIER 0.01 ~ 10.00 0.01 10.00 Multiplier setting
RESET TYPE INST/TIMED INST Reset type setting
Ban protection function
It is set PROT_BLOCK of
Contact Input, and banned
BLOCK YES/NO NO
protection function when
Contact input status is Logic
“1”.
50/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶P R O T E C T I O N F UNCT I ON 1 / 4
▶I O CG 1 ( 5 0 N _ 1 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 6 0 . 0 0 s
BLOCK 4 / 4
: NO
Setting
Item Range Basic value Description
unit
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec Operation Delay Time setting
Ban protection function
It is set PROT_BLOCK of
Contact Input, and banned
BLOCK YES/NO NO
protection function when
Contact input status is Logic
“1”.
51/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶P R O T E C T I O N F UNCT I ON 1 / 4
▶I O CG 2 ( 5 0 N _ 2 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 6 0 . 0 0 s
BLOCK 4 / 4
: NO
Setting
Item Range Basic value Description
unit
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec Operation Delay Time setting
Ban protection function
It is set PROT_BLOCK of
Contact Input, and banned
BLOCK YES/NO NO
protection function when
Contact input status is Logic
“1”.
52/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶P R O T E C T I O N F UNCT I ON 1 / 6
▶T O C G ( 5 1 N ) : D I SABLE
CURVE 2 / 6
: I EC_ N I
P I CKU P 3 / 6
: 2 0 . 0 0 A
MU L T I P L I E R 4 / 6
: 1 0 . 0 0
RE S ET TYPE 5 / 6
: I NST
BLOCK 6 / 6
: NO
Setting
Item Range Basic value Description
unit
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
IEC_NI/IEC_VI/
IEC_EI/IEC_LI/
ANSI_I/ANSI_SI/
CURVE IEC_NI TC Curve setting
ANSI_LI/ANSI_MI/
ANSI_VI/ANSI_EI/
ANSI_DI/KNI/KVI
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
MULTIPLIER 0.01 ~ 10.00 0.01 10.00 Multiplier setting
RESET TYPE INST/TIMED INST Reset type setting
Ban protection function
It is set PROT_BLOCK of
Contact Input, and banned
BLOCK YES/NO NO
protection function when
Contact input status is Logic
“1”.
53/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶P R O T E C T I O N F UNCT I ON 1 / 5
▶T H E R M A L ( 4 9 ) : D I SABLE
K - F ACTOR 2 / 5
: 4 . 0 0
T I ME CON S T 3 / 5
: 9 9 9 . 9 m i n
A L A RM 4 / 5
: 1 0 0 %
BLOCK 5 / 5
: NO
Setting
Item Range Basic value Description
unit
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
K-FACTOR 0.10 ~ 4.00 0.01 4.00 Trip Pickup setting
TIME
CONST
1 ~ 999.9min 0.1min 999.9min Multiplier setting
ALARM 50 ~ 100% 1% 100% Alarm Pickup setting
Ban protection function
It is set PROT_BLOCK of
Contact Input, and banned
BLOCK YES/NO NO
protection function when
Contact input status is Logic
“1”.
54/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶P R O T E C T I O N F UNCT I ON 1 / 4
▶U C ( 3 7 ) : D I SABLE
P I CKU P 2 / 4
: 1 . 0 0 A
DELAY 3 / 4
: 1 8 0 . 0 0 s
BLOCK 4 / 4
: NO
Setting
Item Range Basic value Description
unit
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.02 ~ 1.00*In 0.01*In 1.00*In Pickup setting
DELAY 0.00 ~ 180.00sec 0.01sec 180.00sec Operation Delay Time setting
Ban protection function
It is set PROT_BLOCK of
Contact Input, and banned
BLOCK YES/NO NO
protection function when
Contact input status is Logic
“1”.
55/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶P R O T E C T I O N F UNCT I ON 1 / 4
▶N S O C ( 4 6 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 1 8 0 . 0 0 s
BLOCK 4 / 4
: NO
Setting
Item Range Basic value Description
unit
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 180.00sec 0.01sec 180.00sec Operation Delay Time setting
Ban protection function
It is set PROT_BLOCK of
Contact Input, and banned
BLOCK YES/NO NO
protection function when
Contact input status is Logic
“1”.
56/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▶C O M M A N D ▶C O MM A N D
ENT
▶C O N T OUT TEST
▶C O MM A N D
▶P A N E L TEST
▶C O M M A N D CONT OUT # 1 1 / 4
▶C O N T OUT TEST : DE ENERG I Z ED
CONT OUT # 2 2 / 4
: DE ENERG I Z ED
CONT OUT # 3 3 / 4
: DE ENERG I Z ED
CONT OUT # 4 4 / 4
: DE ENERG I Z ED
1) Right arrow key from CONT OUT TEST menu in Menu Tree
2) Select test item of 16 contact outputs using Up/Down key and Right key
3) Enter settings modification password if required
4) Execute Energized or DeEnergized test using Up/Down key
”Run/Test” LED blinking green or Error message
5) Left key to escape and Repeat steps 2~4 for other items
57/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
58/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
59/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
PAC-E100
No Description No Description
16 IA+ 1 IA-
17 IB+ 2 IB-
18 IC+ 3 IC-
19 IN+ 4 IN-
20 5
21 TS1_COM 6 TS1_NO
22 TS2_COM 7 TS2_NO
23 TS3_COM 8 TS3_NO
24 TS4_COM 9 TS3_NC
25 TS4_NC 10 TS4_NO
26 DI1_COM 11 DI1_P
27 DI2_COM 12 DI2_P
28 PWR+ 13 DI3_P
29 PWR- 14 DI4_P
30 FG 15 DI3_4_COM
60/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
AC or DC
30 28 29
Internally Fused
PAC-E100
61/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
5.3.2. CT Connections
Refer to the Table 5.2. Terminal Block Diagram Table in the above
A B C
PAC-E100
16 IA+
01 IA-
17 IB+
02 IB-
18 IC+
03 IC-
A B C
PAC-E100
16 IA+
01 IA-
17 IB+
02 IB-
18 IC+
03 IC-
62/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
A B C N
PAC-E100
16 IA+
01 IA-
17 IB+
02 IB-
18 IC+
03 IC-
19 IN+
04 IN-
A B C N
PAC-E100
16 IA+
01 IA-
17 IB+
02 IB-
18 IC+
03 IC-
19 IN+
04 IN-
63/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
+ PAC-E100
6 TS1_NO
21 TS1_COM
T
C
(Wet)
11 DI1_P
–
26 DI1_N
DC 125V
64/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
PAC-E00 Notebook
PC
1: NA
2: TXD
3: RXD 1 Pin No. 2 & 3 1
4: NA
5: Signal
Ground 5 5
6: NA
7: NA
8: NA 9 Pin RS232
9: NA RS232 D-sub Connector
D-sub Connector
Female
PAC-E100
SCADA Twisted
ZT (*) Pair 1
2:RS485_DATA+
+ 3:RS485_DATA-
SHIELD
5:RS485_COM
–
Chassis 5
Grounded
only Rear RS485
D-sub Connector
(*) ZT : 120 Ω
(Terminal Resistor)
65/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
B B
C C
16 1 17 2 18 3 19 4
IA + IA - IB + IB - IC + IC - IN + IN -
Current Inputs
11 DI1_P TS1_NO 6
C DIGITAL I/O
o
26 DI1_COM n TS1_COM 21
C
t
o
12 DI2_P a TS2_NO 7
n
c
t
t
27 DI2_COM a TS2_COM 22
c
I
13 DI3_P t TS3_NO 8
n
p
14 DI4_P u TS3_COM 23
O
t
u
s
15 DI3_4_COM t TS3_NC 9
p
u TS4_NO 10
DC t
s
AC TS4_COM 24
28 POWER+ POWER or
DC TS4_NC 25
29 POWER- POWER
66/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
▪Program Menu
Device Selecting
Open Saved Project File Loading
Save Edited Data Saving to File
Report Edited Data Saving to Text File and Printing
COM Communication Port Selection on PC. (Addr: 1 fixed)
67/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
68/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
69/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
70/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
71/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
72/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
6.1.8. Monitor
Monitor display shows status monitoring of PAC-E100. Elements or status monitoring is
composed of Measurement, Self Diagnosis, Protection Component, LED Output, Breaker and
Contact Input/ Output, and there is “Annun Reset” button on front panel’s left.
Refer to LCD setting menu on chapter 4 Operational Description for more detailed
explanation.
73/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
74/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
75/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
76/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
77/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
78/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
79/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
80/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
81/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
82/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
83/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
84/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
85/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
86/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
87/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
< Figure A.15 TC Curve for Thermal Overload Protection: In case of 80%>
88/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual
P A C - E 1 0 0 - I P C
1 - Normal Current : 1A
2 - Normal Current : 5A
89/90
Over Current & Earth Fault Relay (PAC-E100) User’s Manual