You are on page 1of 134

Series 1000 and 2000

Transmitters

Installation and Operation Manual

April 2001
Series 1000 and 2000
Transmitters

Installation and Operation Manual

January 2001

For technical assistance, telephone the Micro Motion Customer


Service Department:
•In the United States, telephone 1-800-522-6277, 24 hours
•Outside the United States, telephone 303-530-8400, 24 hours
•In Europe, telephone +31 (0) 308 549 549
•In Asia, telephone (65) 770-8155
•In Japan, telephone (81) 3 5769-6803

Copyright © 2001 Micro Motion, Inc. All rights reserved.

Micro Motion is a registered trademark of Micro Motion, Inc.


ProLink II is a trademark of Micro Motion, Inc.
SMART FAMILY is a registered trademark of Rosemount, Inc.
HART is a registered trademark of the HART Communication Foundation.
Modbus is a registered trademark of Modicon, Inc.
Contents

1 Installing the Transmitter . . . . . . . . . . . . . . . . . 1


1.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Determining an appropriate location . . . . . . . . . . . . . . 1
Environmental requirements . . . . . . . . . . . . . . . . . . . . 1
Wire distances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Hazardous area classifications . . . . . . . . . . . . . . . . . . . 2
1.4 Mounting the transmitter remotely from the sensor . . 2
Installing the remote mount transmitter . . . . . . . . . . . 4
Mounting the transmitter/core processor assembly
remotely from the sensor . . . . . . . . . . . . . . . . . . . . 7
1.5 Rotating an integrally mounted transmitter . . . . . . . . 8
1.6 Connecting the transmitter wires . . . . . . . . . . . . . . . . . 9
1.7 Grounding the transmitter . . . . . . . . . . . . . . . . . . . . . 12
1.8 Rotating the display. . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2 Starting the Flowmeter . . . . . . . . . . . . . . . . . . .15


2.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2 Applying power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3 Performing a loop test . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.4 Trimming the milliamp output . . . . . . . . . . . . . . . . . . 19
2.5 Zeroing the flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.6 Changing the RS-485 communication settings . . . . . 22
Changing RS-485 options . . . . . . . . . . . . . . . . . . . . . . 22

3 Using the Transmitter . . . . . . . . . . . . . . . . . . . .25


3.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2 Viewing process variables . . . . . . . . . . . . . . . . . . . . . . 25
3.3 Responding to alarms . . . . . . . . . . . . . . . . . . . . . . . . . 26
Viewing alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Acknowledging alarms. . . . . . . . . . . . . . . . . . . . . . . . . 27
3.4 Using the totalizers and inventories. . . . . . . . . . . . . . 28
Viewing the mass totalizer . . . . . . . . . . . . . . . . . . . . . 28
Viewing the volume totalizer . . . . . . . . . . . . . . . . . . . 29
Viewing the mass inventory . . . . . . . . . . . . . . . . . . . . 30
Viewing the volume inventory . . . . . . . . . . . . . . . . . . 30
Starting the totalizers and inventories. . . . . . . . . . . . 31
Stopping the totalizers and inventories . . . . . . . . . . . 31
Resetting the mass totalizer . . . . . . . . . . . . . . . . . . . . 32
Resetting the volume totalizer . . . . . . . . . . . . . . . . . . 32
Resetting both totalizers . . . . . . . . . . . . . . . . . . . . . . . 33

Series 1000 and 2000 Transmitters i


Contents continued

4 Changing the Transmitter Settings . . . . . . . . . . 35


4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.2 Configuration map . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.3 Changing the measurement units . . . . . . . . . . . . . . . . 37
Mass-flow units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Volume-flow units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Density units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Temperature units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.4 Creating special measurement units. . . . . . . . . . . . . . 42
Special mass-flow unit . . . . . . . . . . . . . . . . . . . . . . . . . 43
Special volume-flow unit . . . . . . . . . . . . . . . . . . . . . . . 44
4.5 Changing event settings. . . . . . . . . . . . . . . . . . . . . . . . 45
4.6 Changing the damping values . . . . . . . . . . . . . . . . . . . 46
Flow damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Density damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Temperature damping . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.7 Adjusting meter factors . . . . . . . . . . . . . . . . . . . . . . . . 48
4.8 Changing slug-flow limits and duration . . . . . . . . . . . 48
Low slug-flow limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
High slug-flow limit . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Slug-flow duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.9 Changing low-flow cutoff . . . . . . . . . . . . . . . . . . . . . . . 51
Mass low-flow cutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Volume low-flow cutoff . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.10 Changing the flow direction parameter . . . . . . . . . . . 52
4.11 Changing the software tag. . . . . . . . . . . . . . . . . . . . . . 53
4.12 Changing the display functionality . . . . . . . . . . . . . . . 54
Enabling and disabling display parameters . . . . . . . . 54
Changing the scroll rate. . . . . . . . . . . . . . . . . . . . . . . . 55
Changing the off-line password . . . . . . . . . . . . . . . . . . 55
Changing the display variables . . . . . . . . . . . . . . . . . . 56
4.13 Assigning process variables to analog outputs . . . . . . 57
With a Series 1000 transmitter . . . . . . . . . . . . . . . . . . 57
With a Series 2000 transmitter . . . . . . . . . . . . . . . . . . 58
4.14 Changing the milliamp output . . . . . . . . . . . . . . . . . . 59
Changing the upper range value . . . . . . . . . . . . . . . . . 59
Changing the lower range value . . . . . . . . . . . . . . . . . 61
Changing damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Changing the fault output indicator . . . . . . . . . . . . . . 62
4.15 Changing the frequency output . . . . . . . . . . . . . . . . . . 63
Changing the output scale . . . . . . . . . . . . . . . . . . . . . . 63
Changing the fault output indicator . . . . . . . . . . . . . . 66
Changing the pulse width . . . . . . . . . . . . . . . . . . . . . . 67
4.16 Changing the fault timeout parameter . . . . . . . . . . . . 68
4.17 RS-485 communication settings . . . . . . . . . . . . . . . . . 68
4.18 HART® burst mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Enabling and disabling burst mode. . . . . . . . . . . . . . . 70
Changing the burst mode setting . . . . . . . . . . . . . . . . 71
4.19 Changing the polling address . . . . . . . . . . . . . . . . . . . 72
4.20 Enteringmilliampandfrequencyrangevalueswiththedisplay
73

ii Series 1000 and 2000 Transmitters


Contents continued

5 Characterizing and Calibrating. . . . . . . . . . . . . .75


5.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
5.2 Characterizing the flowmeter . . . . . . . . . . . . . . . . . . . 75
When to characterize . . . . . . . . . . . . . . . . . . . . . . . . . . 75
How to characterize . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
5.3 Calibrating the flowmeter . . . . . . . . . . . . . . . . . . . . . . 78
When to calibrate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
How to calibrate for density . . . . . . . . . . . . . . . . . . . . 78
Density calibration with a HART® Communicator . . 79
Density calibration with ProLink II™ software . . . . . 83
How to calibrate for temperature . . . . . . . . . . . . . . . . 87
Temperature calibration with ProLink II™ software . 87

6 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . .89
6.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
6.2 Transmitter does not operate . . . . . . . . . . . . . . . . . . . 89
6.3 Transmitter does not communicate . . . . . . . . . . . . . . 89
6.4 Zero or calibration failure . . . . . . . . . . . . . . . . . . . . . . 89
6.5 HART® output problems . . . . . . . . . . . . . . . . . . . . . . . 89
6.6 Analog output problems. . . . . . . . . . . . . . . . . . . . . . . . 90
Fault conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
6.7 Status alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
6.8 Diagnosing wiring problems . . . . . . . . . . . . . . . . . . . . 94
Checking the power-supply wiring . . . . . . . . . . . . . . . 94
Checking the core processor-to-transmitter wiring . . 94
Checking the communication loop . . . . . . . . . . . . . . . 94
6.9 Checking the receiving device . . . . . . . . . . . . . . . . . . . 95
6.10 Setting the HART® polling address to zero . . . . . . . . 95
6.11 Checking the upper and lower range values . . . . . . . 95
6.12 Checking the frequency output scale and method . . . 95
6.13 Checking the characterization . . . . . . . . . . . . . . . . . . 95
6.14 Checking the calibration . . . . . . . . . . . . . . . . . . . . . . . 96
6.15 Checking the test points . . . . . . . . . . . . . . . . . . . . . . . 96
Obtaining the test points . . . . . . . . . . . . . . . . . . . . . . . 96
Evaluating the test points . . . . . . . . . . . . . . . . . . . . . . 97
Excessive drive gain. . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Erratic drive gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Bad pickoff voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.16 Contacting customer service . . . . . . . . . . . . . . . . . . . . 98

Appendix A: Specifications . . . . . . . . . . . . . . . . . .99


A.1 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . 99
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . 99
Input/output signals . . . . . . . . . . . . . . . . . . . . . . . . . 100
Digital communications . . . . . . . . . . . . . . . . . . . . . . . 100
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Environmental requirements . . . . . . . . . . . . . . . . . . 101
Electromagnetic interference effects. . . . . . . . . . . . . 101

Series 1000 and 2000 Transmitters iii


Contents continued

A.2 Hazardous area classifications . . . . . . . . . . . . . . . . . 101


UL and CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
CENELEC compliance . . . . . . . . . . . . . . . . . . . . . . . . 101
A.3 Performance specifications . . . . . . . . . . . . . . . . . . . . 101
A.4 Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . 102
Field-mount housing . . . . . . . . . . . . . . . . . . . . . . . . . 102
Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Interface/display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

Appendix B: Using the HART® Communicator . . . . .107


B.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
B.2 Connecting the HART® Communicator . . . . . . . . . . . 107
Connecting to communication terminals . . . . . . . . . 107
Connecting to a multidrop network. . . . . . . . . . . . . . 108
B.3 Conventions used in this manual . . . . . . . . . . . . . . . 108
B.4 HART® Communicator safety messages and notes . 108
B.5 HART® Communicator menu tree . . . . . . . . . . . . . . . 108

Appendix C: Using ProLink II™ Software . . . . . . . . .111


C.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
C.2 Connecting to a personal computer . . . . . . . . . . . . . . 111
Connecting to communication terminals . . . . . . . . . 112
Connecting to a RS-485 or Bell 202 standard network .
113
Connecting to the service port . . . . . . . . . . . . . . . . . . 114

Appendix D: Using the Display . . . . . . . . . . . . . . .115


D.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
D.2 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
D.3 Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

Appendix E: Return Policy . . . . . . . . . . . . . . . . . .117


E.1 General guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
E.2 New and unused equipment . . . . . . . . . . . . . . . . . . . 117
E.3 Used equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119

iv Series 1000 and 2000 Transmitters


Installing
1 Installing the Transmitter

1.1 Overview This section describes how to install the Micro Motion® Series 1000
and 2000 transmitters. These procedures will enable you to:
• Determine an appropriate location to install the transmitter

Starting
• Mount the transmitter remotely from or integral to the sensor
• Rotate an integrally mounted transmitter
• Connect the transmitter wires
• Rotate the display

1.2 Safety Safety messages are provided throughout this manual to protect
personnel and equipment. Read each safety message carefully before
proceeding to the next step.

Using
I IMPORTANT
Procedures and instructions in this manual may
require special precautions. Actions that raise
potential safety issues are preceded by a safety
message. Read each safety message before
performing the task that follows the message.

Changing Settings
1.3 Determining an To determine an appropriate location for the transmitter, you must
appropriate location consider the transmitter’s environmental requirements, wire
distances, accessibility for maintenance, visibility of the display (if it
is equipped with a display), and hazardous area classification.

Environmental Install the transmitter in an environment where ambient


requirements temperature is between –35 and 140°F (–37 and 60°C).

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 1


Installing the Transmitter continued

Wire distances Power source


Connect to a voltage source of 18–100 VDC or 85–250 VAC.
• The transmitter automatically recognizes the source voltage.
• Install up to 1000 feet (300 meters) of 18 AWG (0.8 mm2) or larger
wire. At distances approaching 1000 feet, a minimum DC input of
22 V is required.

Core processor to remote-mount transmitter


• Install up to 300 feet (100 meters) of 22 AWG (0.35 mm2) or up to
1000 feet (300 meters) of 18 AWG (0.8mm2) 4-wire twisted-pair
instrument cable.
• Install shielded wiring with drain wires connected at both ends or
unshielded wiring in continuous metallic conduit that provides
360° termination shielding for the enclosed wiring.

Hazardous area If you plan to mount the transmitter in a hazardous area, verify that
classifications the transmitter has the appropriate hazardous area approval. Each
transmitter has a hazardous area approval tag attached to the
outside of the transmitter housing.
For more information about hazardous area classifications, see the
instruction manual shipped with the transmitter.

1.4 Mounting the transmitter Mounting the transmitter apart from the sensor involves attaching
remotely from the sensor it to an instrument pole or wall with the mounting bracket. The
bracket will accommodate either of two possible mounting
configurations:
• Mount the transmitter apart from the sensor and core processor
assembly.
• Mount the transmitter with core processor assembly apart from
the sensor.
Instrument pole and wall-mount options for either of the two
possible mounting configurations are shown in Figure 1-1. You can
mount the transmitter in any orientation as long as the conduit
openings do not point upward.

2 Series 1000 and 2000 Transmitters


Installing
Installing the Transmitter continued

Figure 1-1. Instrument pole or wall mount


TRANSMITTER ALONE

Starting
Mounting bracket Mounting bracket
(instrument pole mount) (wall mount)

TRANSMITTER WITH CORE


PROCESSOR ATTACHED

Using
Mounting bracket

Changing Settings
CAUTION
Condensation or excessive moisture entering the
transmitter could damage the transmitter and result in
measurement error or flowmeter failure.

• Ensure the integrity of gaskets and O-rings.


• Do not mount the transmitter with the conduit openings
pointing upward.
• Install drip legs if a conduit is used.
• Seal the conduit openings.
• Fully tighten the transmitter cover.

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 3


Installing the Transmitter continued

Installing the remote The following procedure assumes that the core processor is attached
mount transmitter to the sensor. To mount the transmitter apart from the sensor and
core processor assembly:
1. Refer to the components in Figure 1-1 and Figure 1-2, page 5.
2. Remove the junction end-cap from the junction housing (see
Figure 1-2, page 5).
3. If desired, re-orient the transmitter on the bracket:
a. Using a 4mm hex key, loosen each of the four cap screws in the
junction housing three or four turns (see Figure 1-2, page 5).
b. Rotate the bracket so the transmitter is oriented as desired.
c. Tighten the cap screws, torquing to 30-38 in-lbf (3-4N-m).
4. Securely mount the bracket and transmitter to a panel or an
instrument pole.
5. Use one of these methods to shield the wiring from the core
processor to the transmitter:
a. Connect the drain wires to the ground screws in the junction
housing and core processor, or
b. If wiring is in metallic conduit, make sure the conduit provides
360° termination shielding for the enclosed wiring.
6. Connect wiring from the core processor on the sensor to the
transmitter.
a. Prepare wiring for connection by cutting back sheathing and
stripping wire ends. If you are using shielded wiring, unwind
drain wires back to sheathing and twist the ends together for
grounding.
b. Pull the mating connector out of the junction housing.
c. Pass the cable end through the conduit opening in the junction
housing.
d. Connect the four wires to the numbered slots on the mating
connector, matching corresponding numbered terminals on the
core processor.
e. Plug the mating connector into the socket in the junction
housing.
f. If you are using cable shields for grounding, connect the shield
wire ends to the ground screw (see Figure 1-3, page 5).
7. Reattach the junction end-cap, tightening until O-ring seats.

4 Series 1000 and 2000 Transmitters


Installing
Installing the Transmitter continued

Figure 1-2. Remote mount transmitter components


Ground lug Main enclosure

Bracket

Starting
Junction end-cap Junction housing

Mating connector Mating connector


socket

Figure 1-3. Remote-mount transmitter, junction end-cap removed

Ground screw

Using
Conduit opening for
sensor interface

Changing Settings
Cap screws

Figure 1-4. Sensor and core processor, exploded view


Core processor cover

Sensor

Characterizing and
Calibrating
Core processor Troubleshooting

Series 1000 and 2000 Transmitters 5


Installing the Transmitter continued

Figure 1-5. Connecting the mating connector to the core processor

Main enclosure

Ground screw

Mating connector socket

Core
processor

Mating
Use the grounds screws to connector
connect ground wiring at
both ends.

Color-coded
wires

Connect the four color-coded wires to


the numbered slots on the mating
connector. Connect the opposite end
of each color-coded wire to the
same-numbered terminal on the core
processor.

6 Series 1000 and 2000 Transmitters


Installing
Installing the Transmitter continued

Mounting the The following procedure assumes that the core processor is attached
transmitter/core processor to the transmitter. To mount the transmitter and core processor
assembly remotely from assembly remotely from the sensor:
the sensor 1. Attach the mounting bracket to an instrument pole or wall.
2. Remove the lower conduit ring and the end-cap from the bottom
of the transmitter and core processor assembly (see Figure 1-6).
3. Place the transmitter and core processor assembly onto the

Starting
mounting bracket.
4. Replace the lower conduit ring, clamping the mounting bracket
between the core processor and the conduit ring as shown in
Figure 1-1, page 3.
5. Connect the transmitter end of a Micro Motion 9-wire flowmeter
cable to the underside of the core processor. Refer to the manual
shipped with the cable for flowmeter cable preparation and
wiring instructions.
6. Replace the end cap on the conduit ring.

Figure 1-6. Transmitter/core processor assembly exploded view

Using
Changing Settings
Mounting bracket

Lower conduit ring

End cap

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 7


Installing the Transmitter continued

1.5 Rotating an integrally You can rotate an integrally mounted transmitter on the sensor up
mounted transmitter to 360° in 90° increments to one of four possible positions. See
Figure 1-7.

WARNING
Twisting the core processor will damage the sensor.

Do not twist the core processor.

Figure 1-7. Rotating the transmitter


Transmitter

Transition

Core
processor

Sensor

CAUTION
To avoid damaging the wires that connect the
transmitter to the core processor, do not move the
transmitter more than a few inches from the core
processor.

To rotate the transmitter on the core processor:


1. Push down and turn the transmitter counterclockwise
(approximately 1/8 turn) to disengage the transmitter at the
transition.
2. Rotate the transmitter to the desired position.
3. Align the camlock pins (not shown) with the grooves on the
transition.
4. Push down and turn the transmitter clockwise to lock it into place
on the sensor.

8 Series 1000 and 2000 Transmitters


Installing
Installing the Transmitter continued

1.6 Connecting the transmitter There are multiple ways to connect the transmitter wires depending
wires upon how you will use the HART®or Modbus® protocol or analog
functionality. Pages 10 and 11 provide several possible
configurations, including:
• Analog wiring (Figure 1-8, page 10)
• HART/analog single-loop wiring (Figure 1-9, page 10)
• RS-485 point-to-point wiring (Figure 1-10, page 11)

Starting
• HART multidrop wiring with SMART FAMILY® transmitters and
a configuration tool (Figure 1-11, page 11)

WARNING
Hazardous voltage can cause severe injury or death.

Shut off the power before wiring the transmitter.

Using
WARNING
A transmitter that has been improperly wired or
installed in a hazardous area could cause an
explosion.

• Make sure the transmitter is wired to meet or exceed


local code requirements.
• Install the transmitter in an environment that complies

Changing Settings
with the classification tag on the transmitter. See
Hazardous area classifications, page 101.

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 9


Installing the Transmitter continued

Figure 1-8. Analog wiring


Milliamp (mA) receiving device reports mass flow, volume flow,
temperature, or density. See Assigning process variables to
analog outputs, page 57.
+

+
– Power supply
85–265 VAC,
50/60 Hz,
18–100 VDC

Frequency receiving device


reports mass flow or volume flow. See Assigning
process variables to analog outputs, page 57.

Figure 1-9. HART/analog single-loop wiring

mA receiving device HART-


compatible host
or controller

+

Power supply
85–265 VAC,
50/60 Hz,
18–100 VDC

10 Series 1000 and 2000 Transmitters


Installing
Installing the Transmitter continued

Figure 1-10. RS-485 point-to-point wiring

Note: The RS-485 communication


wires must be shielded.
Primary
controller

Multiplexer

Starting
Power supply
85–265 VAC,
50/60 Hz,
RS-485A 18–100 VDC
RS-485B

Other devices

Using
Figure 1-11. HART multidrop wiring with SMART FAMILY transmitters and a configuration tool

Changing Settings
HART-compatible
transmitters SMART FAMILY™
HART® Communicator or transmitters
interface for ProLink II™ or
AMS software

+ +

24 VDC loop power


supply required for

Characterizing and
250 Ω loop
resistance HART 4–20 mA

Calibrating
passive transmitters

Note: For optimum HART communication,


– loop is single point,
make sure the output
grounded to an instrument-grade ground.
Troubleshooting

Series 1000 and 2000 Transmitters 11


Installing the Transmitter continued

1.7 Grounding the transmitter Ground the transmitter and the sensor independently.
The transmitter can be grounded via the piping, if joints in the
pipeline are ground-bonded, or by means of a ground screw on the
outside of the core processor housing.

WARNING
Improper grounding could cause measurement error.

To reduce the risk of measurement error:


• Ground the flowmeter to earth, or follow ground network
requirements for the facility.
• For installation in an area that requires intrinsic safety,
refer to Micro Motion UL, CSA, or CENELEC installation
instructions.
• For hazardous area installations in Europe, refer to
standard EN 60079-14 if national standards do not apply.

The transmitter is grounded by means of a ground screw on the


outside of the transmitter housing. If national standards are not in
effect, adhere to these transmitter grounding guidelines:
• Use copper wire, 14 AWG (2.5mm2) or larger
• Keep all ground leads as short as possible
• Ground leads must have less than 1 Ω impedance
• Connect ground leads directly to earth, or follow plant standards

1.8 Rotating the display You can rotate the display on the transmitter up to 360° in 90°
increments.

WARNING
Removing the display cover in explosive atmospheres
while the power is on can cause an explosion.

Do not remove the display cover in explosive atmospheres


before shutting off the power and waiting the required delay
time as indicated on the transmitter housing.

WARNING
Using a dry cloth to clean the display cover can cause
static discharge, which could result in an explosion in
an explosive atmosphere.

Always use a damp cloth to clean the display cover in an


explosive atmosphere.

12 Series 1000 and 2000 Transmitters


Installing
Installing the Transmitter continued

To rotate the display, complete the following procedure:


1. Remove the end-cap clamp by removing the cap screw. See
Figure 1-12.
2. Turn the display cover counterclockwise to remove it from the
main enclosure.
3. Carefully loosen (and remove if necessary) the semicaptive
display screws while holding the display module in place.

Starting
4. Carefully pull the display module out of the main enclosure until
the sub-bezel pin terminals are disengaged from the display
module.
5. Rotate the display module to the desired position.
6. Insert the sub-bezel pin terminals into the display module pin
holes to secure the display in its new position.
7. If you have removed the display screws, then reinsert and tighten
them.
8. Place the display cover onto the main enclosure. Turn the display
cover clockwise until it is snug.

Using
9. Replace the end-cap clamp by reinserting and tightening the cap
screw.

Figure 1-12. Display components

Main enclosure Pin terminals

Changing Settings
Sub-bezel

Display module

Display cover

Characterizing and
Calibrating
Display screws

End-cap clamp

Cap screw
Troubleshooting

Series 1000 and 2000 Transmitters 13


14 Series 1000 and 2000 Transmitters
Installing
2 Starting the Flowmeter

2.1 Overview This section describes the procedures you should perform the first
time you start the flowmeter. You do not need to use these
procedures every time you cycle power to the flowmeter.

Starting
The procedures in this chapter will enable you to:
• Apply power to the flowmeter
• Perform a loop test on the transmitter
• Trim the mA output, if necessary
• Zero the flowmeter
Figure 2-1 provides an overview of the flowmeter startup
procedures.

Figure 2-1. Startup procedures

Using
Start

Perform these steps


if you are using
analog outputs.

Perform a
Apply power. loop test.

Changing Settings
Trim mA
Zero the
output (if
flowmeter.
necessary).

Finish

Characterizing and
Calibrating
Note: All HART Communicator key sequences provided in this
section assume that you are starting from the “Online” menu.
See Using the HART Communicator, page 107.
Note: All ProLink II procedures provided in this section
assume that your computer is already connected to the
transmitter and you have established communication. See
Using ProLink II Software, page 111.
Troubleshooting

Series 1000 and 2000 Transmitters 15


Starting the Flowmeter continued

2.2 Applying power Before you apply power to the flowmeter, close and tighten all
housing covers.

WARNING
Operating the flowmeter without covers in place
creates electrical hazards that can cause death,
injury, or property damage.

Make sure safety barrier partition and covers for the


field-wiring, circuit board compartments, electronics module,
and housing are all in place before applying power to the
transmitter.

Turn on the electrical power at the power supply. The flowmeter will
automatically perform diagnostic routines. When the flowmeter has
completed its power-up sequence, the display status indicator will
turn green and begin to flash (if the transmitter is equipped with a
display).

2.3 Performing a loop test A loop test is a means to:


• Verify that analog outputs (mA and frequency) are being sent by
the transmitter and received accurately by the receiving devices
• Determine whether or not you need to trim the mA output
You can perform a loop test with a HART Communicator, the
display, or ProLink II software.

With a HART Communicator


To perform a loop test with a HART Communicator:
1. Press 2.
2. Select Loop test.
3. Select Fix Analog Out 1.
4. Select 4 mA.
5. Read the mA output at the receiving device or another point on
the loop. The reading should be near 4 mA.
Note: The 4 mA reading does not need to be exact at this point.
You will correct differences when you trim the mA output. See
Trimming the milliamp output, page 19.
6. If you don’t get a reading, then the loop test has failed. Abort the
loop test and see Table 6-1, page 90.
7. Select End.
8. Select Fix frequency out.

16 Series 1000 and 2000 Transmitters


Installing
Starting the Flowmeter continued

9. Select 10 KHz.
10. Read the frequency output at the receiving device or another
point on the loop. The reading should be 10 kilohertz (KHz).
11. If you don’t get a reading, then the loop test has failed. Abort the
loop test and see Table 6-1, page 90.
12. Select “End.”

Starting
With the display
To perform a loop test with the display:
1. Simultaneously press and hold Scroll and Select for 4 seconds.
When SEE ALARM or OFF-LINE MAINT appears on the display,
then release the buttons.
2. If OFF-LINE MAINT does not appear on the screen, then press
Scroll until OFF-LINE MAINT appears.
3. Press Select.
4. If CODE? appears on the display, then enter the off-line password
(see Changing the off-line password, page 58):

Using
a. Press Scroll to select the first number (0–9) of the off-line
password.
b. When you see the correct number, press Select. The selection
moves over by one decimal place so you can enter the next
digit.
c. Repeat steps a and b until you complete the four-digit
password.

Changing Settings
5. Press Scroll until OFF-LINE SIM appears on the display. See
Figure 2-2, page 17.

Figure 2-2. Loop test with the display

Characterizing and
Calibrating

Scroll button Select button

6. Press Select.
Troubleshooting

7. Press Scroll until one of three possible test points appears: 4 mA,
12 mA, or 20 mA.

Series 1000 and 2000 Transmitters 17


Starting the Flowmeter continued

8. Press Select. The transmitter begins to simulate its mA output.


Dots will traverse the top line of the display while the loop test is
in progress.
9. Read the mA output at the receiving device. The reading should
be near the test point value you selected in Step 7.
Note: The mA reading does not need to be exact at this point.
You will correct differences when you trim the mA output. See
Trimming the milliamp output, page 19.
10. If you don’t get a reading, then the loop test has failed. Abort the
loop test and see Table 6-1, page 90.
11. Press Select to stop the simulation.
12. Press Scroll until one of two possible test points appears: 1 KHz
or 10 KHz.
13. Press Select. The transmitter begins to simulate its KHz output.
Dots will traverse the top line of the display while the loop test is
in progress.
14. Read the frequency output at the receiving device. The reading
should be the test point value you selected in Step 12.
15. If you don’t get a reading, then the loop test has failed. Abort the
loop test and see Table 6-1, page 90.
16. Press Select to stop the simulation.
17. Press Scroll until OFF-LINE EXIT appears on the display.
18. Press Select to exit off-line mode.

With ProLink II software


To perform a loop test with ProLink II software:
1. Click ProLink.
2. Select Test.
3. Select Fix Freq Out.
4. Type the number of pulses per second that you want the
transmitter to report. The number of pulses can be any number
within the frequency range of the transmitter.
5. Click Do Cal.
6. Read the frequency output at the receiving device. The reading
should be the value you typed in Step 4.
7. If you don’t get a reading, then the loop test has failed. Abort the
loop test and see Table 6-1, page 90.
8. Click Stop.
9. Click ProLink.
10. Select Test.
11. Select Fix Milliamp 1.
12. Type the number of mA pulses that you want the transmitter to
report. The number of pulses can be any number within the mA
range of the transmitter.

18 Series 1000 and 2000 Transmitters


Installing
Starting the Flowmeter continued

13. Click Do Cal.


14. Read the mA output at the receiving device. The reading should
be near the value you typed in Step 12.
Note: The mA reading does not need to be exact. You will
correct differences when you trim the mA output. See
Trimming the milliamp output, below.
15. If you don’t get a reading, then the loop test has failed. Abort the

Starting
loop test and see Table 6-1, page 90.
16. Click Stop. The loop test is complete

2.4 Trimming the milliamp Trimming the mA output creates a common measurement range
output between the transmitter and the device that receives the mA output.
For instance, a transmitter might send a 4 mA signal that the
receiving device reports incorrectly as 3.8 mA. If the transmitter
output is trimmed correctly, it will send a signal appropriately
compensated to ensure that the receiving device actually indicates a
4 mA signal.

Using
You must trim the output at both the 4 mA and 20 mA points to
ensure appropriate compensation across the entire range of outputs.
You can trim the output with the HART Communicator or
ProLink II software.

With a HART Communicator


To trim the mA output with a HART Communicator:

Changing Settings
1. Press 2.
2. Select Trim Analog Out 1.
3. Read the mA output at the receiving device.
4. Return to the HART Communicator.
5. Type the value that you read at the receiving device. The value
can contain up to two decimal places.
6. Press F4 ENTER.
7. Read the mA output again at the receiving device.
8. If the receiving device and the HART Communicator readings are

Characterizing and
NOT equal, then press 2 NO. Repeat Step 3 through Step 7 until

Calibrating
the outputs are equal.
9. If the receiving device and the HART Communicator readings are
equal, then press 1 YES. The HART Communicator will proceed
to the 20 mA trim.
10. Repeat the procedure beginning with Step 3.
After you have completed the 20 mA trim, the procedure is complete.
Troubleshooting

Series 1000 and 2000 Transmitters 19


Starting the Flowmeter continued

With ProLink II software


To trim the mA output with ProLink II software:
1. Select Milliamp Trim from the Calibrate menu.
2. Click OK to begin the 4 mA trim.
3. Read the mA output at the receiving device.
4. Type the value that you read at the receiving device in the Enter
Meas box.
5. Click Do Cal.
6. Read the mA output again at the receiving device.
7. If the receiving device and the ProLink II software readings are
NOT equal, then click No and go to Step 4.
8. If the receiving device and the Prolink II software readings are
equal, then click Yes.
9. Click OK to begin the 20 mA trim.
10. Repeat the procedure beginning with Step 3.
Once you have completed the 20 mA trim, the procedure is complete.

2.5 Zeroing the flowmeter Zeroing the flowmeter establishes the flowmeter’s point of reference
when there is no flow.
When you zero the flowmeter, you may need to adjust the zero time
parameter. Zero time is the amount of time the transmitter takes to
determine its zero-flow reference point. The default zero time is
20 seconds.
• A long zero time may produce a more accurate zero reference but is
more likely to result in a zero failure.
• A short zero time is less likely to result in a zero failure but may
produce a less accurate zero reference.
You can zero the flowmeter with a HART Communicator, the
display, or ProLink II software.

With a HART Communicator


To zero the flowmeter with a HART Communicator:
1. Apply power to the flowmeter. Allow the flowmeter to warm up for
approximately 30 minutes.
2. Run the process fluid through the sensor until the sensor
temperature approximates the normal process operating
temperature.
3. Close the shutoff valve downstream from the sensor.
4. Ensure that the sensor is completely filled with fluid.
5. Ensure that the process flow has completely stopped.
6. Press 2, 3, 1.
7. Look at the number of seconds to the right of Zero time.

20 Series 1000 and 2000 Transmitters


Installing
Starting the Flowmeter continued

8. If you want to change the zero time, then:


a. Select Zero time.
b. Type a new zero time.
c. Press F4 OK.
9. Select Perform auto zero.
10. If Auto Zero Failed appears on the HART Communicator, then
the zero procedure failed. See Zero or calibration failure, page 89.

Starting
11. If Auto Zero Passed appears on the HART Communicator, then
the zero procedure succeeded.
12. Press F4 OK.

With the display


If the off-line menu has been disabled, you will not be able to zero
the transmitter with the display. For information about enabling
and disabling the off-line menu, see Enabling and disabling display
parameters, page 54.
To zero the flowmeter with the display:

Using
Note: You cannot change the zero time with the display. If you
need to change the zero time, you must use ProLink II
software.
1. Apply power to the flowmeter. Allow the flowmeter to warm up for
approximately 30 minutes.
2. Run the process fluid through the sensor until the sensor
temperature approximates the normal process operating

Changing Settings
temperature.
3. Close the shutoff valve downstream from the sensor.
4. Ensure that the sensor is completely filled with fluid.
5. Ensure that the process flow has completely stopped.
6. Simultaneously press and hold Scroll and Select for 4 seconds.
When SEE ALARM or OFF-LINE MAINT appears on the display,
then release the buttons.
7. If OFF-LINE MAINT does not appear on the screen, then press
Scroll until OFF-LINE MAINT appears.

Characterizing and
8. Press Select.

Calibrating
9. If CODE? appears on the display, then enter the off-line password
(see Changing the off-line password, page 58):
a. Press Scroll to select the first number (0–9) of the off-line
password.
b. When you see the correct number, press Select. The selection
moves over by one decimal place so you can enter the next
digit.
c. Repeat steps a and b until you complete the four-digit
password.
Troubleshooting

10. Press Scroll until OFF-LINE ZERO appears on the display.

Series 1000 and 2000 Transmitters 21


Starting the Flowmeter continued

11. Press Select. Dots will traverse the top line of the display while
the zero is in progress.
12. If ZERO FAIL appears on the display, then the zero procedure
failed. See Zero or calibration failure, page 89.
13. If ZERO OK appears on the display, then the zero procedure
succeeded.
14. Press Select until OFF-LINE EXIT appears on the display.
15. Press Select to exit off-line mode.

With ProLink II software


To zero the flowmeter with ProLink II software:
1. Apply power to the flowmeter. Allow the flowmeter to warm up for
approximately 30 minutes.
2. Run the process fluid through the sensor until the sensor
temperature reaches the normal process operating temperature.
3. Close the shutoff valve downstream from the sensor.
4. Ensure that the sensor is completely filled with fluid.
5. Ensure that the process flow has completely stopped.
6. Select Zero Calibration from the Calibrate menu.
7. Type a new zero time in the Zero Time box or accept the default
value.
8. Click Zero. The flowmeter will begin zeroing.
9. If the Zero Failure box appears, then the zero procedure failed.
See Zero or calibration failure, page 89.
10. Click Done.

2.6 Changing the RS-485 You can use the display to change the transmitter’s RS-485
communication settings communication settings. You can modify the following settings:
• Protocol
• Baud
• Parity
• Stop bits
• Address (protocol address)

Changing RS-485 options If the off-line menu has been disabled, you will not be able to change
the RS-485 options with the display. For information about enabling
and disabling the off-line menu, see Enabling and disabling display
parameters, page 54.
To change the RS-485 options:
1. Simultaneously press and hold Scroll and Select for 4 seconds.
When SEE ALARM appears on the screen, then release the
buttons.
2. Press Scroll until OFFLINE CONFIG appears.

22 Series 1000 and 2000 Transmitters


Installing
Starting the Flowmeter continued

3. Press Select.
4. If CODE? appears on the display, then enter the off-line password
(see Changing the off-line password, page 58):
a. Press Scroll to select the first number (0–9) of the off-line
password.
b. When you see the correct number, press Select. The selection
moves over by one decimal place so you can enter the next

Starting
digit.
c. Repeat steps a and b until you complete the four-digit
password.
5. Press Scroll until CONFIG RS-485 appears on the display.
6. Press Select.
7. Press Scroll to loop through and select one of the following
main-menu options:
- PROTOCOL/RS485
- BAUD/RS485
- PARITY/RS485

Using
- STOP/RS485
- ADDRESS/RS485
- EXIT
8. When the option you want is on the screen, press Select.
9. If you selected protocol, follow the steps below to select an RS-485
data protocol:
a. Press Scroll to loop through and select one of the following

Changing Settings
options:
- NONE
- HART
- M_RTU
- M_ASC
b. When the option you want is on the screen, press Select.
c. To save and exit, skip to step 14.
10. If you selected baud, follow the steps below to select an RS-485
baud:
a. Press Scroll to loop through and select one of the following

Characterizing and
options:

Calibrating
- 1200
- 2400
- 4800
- 9600
- 19200
- 38400
b. When the option you want is on the screen, press Select.
c. To save and exit, skip to step 14.
Troubleshooting

Series 1000 and 2000 Transmitters 23


Starting the Flowmeter continued

11. If you selected parity, follow the steps below to select an RS-485
parity:
a. Press Scroll to loop through and select one of the following
options:
- ODD
- EVEN
- NONE
b. When the option you want is on the screen, press Select.
c. To save and exit, skip to step 14.
12. If you selected stop, follow the steps below to select RS-485 stop
bits:
a. Press Scroll to loop through and select one of the following
options:
- 1
- 2
b. When the option you want is on the screen, press Select.
c. To save and exit, skip to step 14.
13. If you selected address, follow the steps below to read/write the
polling address for the protocol configured:
Note: If the protocol is set at NONE, the address item will not
appear. The address item allows users to enter the polling
address.
a. Press Scroll to select the first number (0–9).
b. When you see the correct number, press Select. The selection
moves over by one decimal place so you can enter the next digit
in the protocol address.
c. Repeat steps a and b until you enter the entire address.
d. When you are finished, press both Select and Scroll to save the
number.
e. To save and exit, skip to step 14.
Note: To leave the current setting selected for any of the
options in steps 9–13, press and hold both the Scroll and the
Select buttons for about 4 seconds and you will be returned to
the previous screen (step 7).
14. Press Scroll until EXIT appears.
15. Press Select.

24 Series 1000 and 2000 Transmitters


Installing
3 Using the Transmitter

3.1 Overview This section describes how to use the transmitter in everyday
operation. The procedures in this section will enable you to:

Starting
• View process variables
• Respond to alarms
• Use the totalizers and inventories
Note: All HART Communicator key sequences in this section
assume that you are starting from the “Online” menu. See
Using the HART Communicator, page 107.
Note: All ProLink II procedures provided in this section
assume that your computer is already connected to the
transmitter and you have established communication. See
Using ProLink II Software, page 111.

Using
3.2 Viewing process variables Process variables include measurements such as mass-flow rate,
volume-flow rate, mass total, volume total, temperature, and
density.
You can view process variables with a HART Communicator, the
display, or ProLink II software.

With a HART Communicator

Changing Settings
To view process variables with a HART Communicator:
1. Press 1, 1.
2. Scroll through the list of process variables by pressing the Down
Arrow key.
3. Press the number corresponding to the process variable you wish
to view.

With the display


The display reports the abbreviated name of the process variable

Characterizing and
(e.g., DENS for density), the current value of that process variable,

Calibrating
and the associated units of measure (e.g., g/cc).
To view a process variable with the display, press Scroll until the
name of the desired process variable either:
• Appears on the process variable line
• Begins to alternate with the units of measure
Troubleshooting

Series 1000 and 2000 Transmitters 25


Using the Transmitter continued

With ProLink II software


To view process variables with ProLink II software:
1. Click Prolink.
2. Select Process Variables.

3.3 Responding to alarms The transmitter broadcasts alarms whenever a process variable
exceeds its defined limits or the transmitter detects a fault
condition. For instructions regarding all the possible alarms, see
Status alarms, page 91.

Viewing alarms You can view alarms with a HART Communicator, the display, or
ProLink II software.

With a HART Communicator


To view alarms with a HART Communicator:
1. Press 1.
2. Select “View Status.”
3. Press F4 “OK” to scroll through the list of current alarms.

With the display


The display reports alarms with a status indicator. See Figure 3-1.
The status indicator can be in one of six possible states, as listed in
Table 3-1.

Figure 3-1. Display alarm menu

Status
indicator

26 Series 1000 and 2000 Transmitters


Installing
Using the Transmitter continued

Table 3-1. Priorities reported by the status indicator


Status indicator state Alarm priority
Green No alarm—normal operating mode
Flashing green Unacknowledged corrected
condition

Starting
Yellow Acknowledged low severity alarm
Flashing yellow Unacknowledged low severity alarm
Red Acknowledged high severity alarm
Flashing red Unacknowledged high severity alarm

Alarms reported by the display are arranged according to priority in


an alarm queue. To view specific alarms in the queue:
1. Simultaneously press and hold Scroll and Select for 4 seconds.
When the words “SEE ALARM” appear on the screen, then
release the buttons. See Figure 3-1, page 26.

Using
2. Press Select.
3. If the alternating words “ACK ALL” appear, then press Scroll.
4. If the words “NO ALARM” appear, then go to Step 6.
5. Press Scroll to view each alarm in the queue. See Status alarms,
page 91, for an explanation of the alarm codes reported by the
display.
6. Press Scroll until the word “EXIT” appears.

Changing Settings
7. Press Select.

With ProLink II software


To view alarms with ProLink II software:
1. Click ProLink.
2. Select Status.
3. View the status indicators. Red status indicators indicate current
status alarms.

Characterizing and
Acknowledging alarms You can acknowledge alarms with the display.

Calibrating
Note: If the alarm menu has been disabled, then the display
will not indicate an alarm condition.
To acknowledge alarms:
1. Simultaneously press and hold Scroll and Select for 4 seconds.
When the words “SEE ALARM” appear on the screen, then
release the buttons. See Figure 3-1, page 26.
2. Press Select.
3. If the words “NO ALARM” appear, then go to Step 8.
Troubleshooting

Series 1000 and 2000 Transmitters 27


Using the Transmitter continued

4. If you want to acknowledge all alarms, then:


a. Press Scroll until the word “ACK” appears by itself. The word
“ACK” begins to alternate with the word “ALL?”
b. Press Select.
Note: If the “acknowledge all alarms” feature has been
disabled, then you must acknowledge each alarm
individually. See Step 5.
5. If you want to acknowledge a single alarm, then:
a. Press Scroll until the alarm you want to acknowledge appears.
b. Press Select. The word “ALARM” begins to alternate with the
word “ACK.”
c. Press Select to acknowledge the alarm.
6. If you want to acknowledge another alarm, then go to Step 3.
7. If you do NOT want to acknowledge any more alarms, then go to
Step 8.
8. Press Scroll until the word “EXIT” appears.
9. Press Select.

3.4 Using the totalizers and The totalizers keep track of the total amount of mass or volume
inventories measured by the transmitter over a period of time. The totalizers
can be viewed, started, stopped, and reset.
The Inventories track the same values as the totalizers but are
normally never reset.

Viewing the mass totalizer You can view the current value of the mass totalizer with a HART
Communicator, the display, or ProLink II software.

With a HART Communicator


To view the current value of the mass totalizer with a HART
Communicator:
1. Press 1, 1.
2. Select “Mass totl.”

With the display


To view the current value of the mass totalizer with the display:
1. Press Scroll until the process variable “TOTAL” appears and the
units of measure are mass units (e.g., kg, lb). See Figure 3-2,
page 29.
2. Read the current value from the top line of the display.

28 Series 1000 and 2000 Transmitters


Installing
Using the Transmitter continued

Figure 3-2. Display totalizer

Current value

Process
variable line

Starting
Units of
measure

Scroll button

Using
With ProLink II software
To view the current value of the mass totalizer with ProLink II
software:
1. Click ProLink.
2. Select Process Variables.

Viewing the volume You can view the current value of the volume totalizer with a HART

Changing Settings
totalizer Communicator, the display, or ProLink II software.

With a HART Communicator


To view the current value of the volume totalizer with a HART
Communicator:
1. Press 1, 1.
2. Select “Vol totl.”

With the display

Characterizing and
To view the current value of the volume totalizer with the display:

Calibrating
1. Press Scroll until the process variable “TOTAL” appears and the
units of measure are volume units (e.g., gal, cuft).
2. Read the current value from the top line of the display.

With ProLink II software


To view the current value of the volume totalizer with ProLink II
software:
1. Click ProLink.
2. Select Process Variables.
Troubleshooting

Series 1000 and 2000 Transmitters 29


Using the Transmitter continued

Viewing the mass You can view the current value of the mass inventory with a HART
inventory Communicator, the display, or ProLink II software.

With a HART Communicator


To view the current value of the mass inventory with a HART
Communicator:
1. Press 1, 1.
2. Select “Mass inventory.”

With the display


To view the current value of the mass inventory with the display:
1. Press Scroll until the process variable “TOTAL” appears and the
word “MASSI” alternates with the units of measure.
2. Read the current value from the top line of the display.

With ProLink II software


To view the current value of the mass inventory with ProLink II
software:
1. Click ProLink.
2. Select Process Variables.

Viewing the volume You can view the current value of the volume inventory with a
inventory HART Communicator, the display, or ProLink II software.

With a HART Communicator


To view the current value of the volume inventory with a HART
Communicator:
1. Press 1, 1.
2. Select “Vol inventory.”

With the display


To view the current value of the volume inventory with the display:
1. Press Scroll until the process variable “TOTAL” appears and the
word “LVOLI” alternates with the units of measure.
2. Read the current value from the top line of the display.

With ProLink II software


To view the current value of the volume inventory with ProLink II
software:
1. Click ProLink.
2. Select Process Variables.

30 Series 1000 and 2000 Transmitters


Installing
Using the Transmitter continued

Starting the totalizers and The totalizers and inventories are always started together.
inventories You can start the totalizers and inventories with a HART
Communicator, the display, or ProLink II software.

With a HART Communicator


To start all totalizers and inventories with a HART Communicator:
1. Press 1, 4.

Starting
2. Select “Start totalizer.”

With the display


To start all totalizers and inventories with the display:
1. Press Scroll until the process variable “TOTAL” appears.
2. Press Select.
3. Press Scroll. The word “START” appears beneath the current
totalizer value.
4. Press Select. The word “YES?” begins to alternate with the word

Using
“START.”
5. Press Select to start all totalizers and inventories.

With ProLink II software


To start all totalizers and inventories with ProLink II software:
1. Click ProLink.
2. Select Totalizer Control.

Changing Settings
3. Click Start.

Stopping the totalizers and The totalizers and inventories are always stopped together.
inventories You can stop the totalizers and inventories with a HART
Communicator, the display, or ProLink II software.

With a HART Communicator


To stop all totalizers and inventories with a HART Communicator:
1. Press 1, 4.

Characterizing and
2. Select “Stop totalizer.”
Calibrating
With the display
To stop all totalizers and inventories with the display:
1. Press Scroll until the process variable “TOTAL” appears.
2. Press Select.
3. Press Scroll until the word “STOP” appears beneath the current
totalizer value.
4. Press Select. The word “YES?” begins to alternate with the word
Troubleshooting

“STOP.”
5. Press Select to stop the totalizers and inventories.

Series 1000 and 2000 Transmitters 31


Using the Transmitter continued

With ProLink II software


To stop all totalizers and inventories with ProLink II software:
1. Click ProLink.
2. Select Totalizer Control.
3. Click Stop.

Resetting the mass Resetting the mass totalizer sets the mass total to zero.
totalizer You can reset the mass totalizer independent of the volume totalizer
with a HART Communicator or the display.

With a HART Communicator


To reset the mass totalizer with a HART Communicator:
1. Press 1, 4.
2. Select “Reset mass total.”

With the display


If the ability to reset totalizers has been disabled, you will not be
able to reset the mass totalizer with the display. For information
about enabling and disabling the display parameters, see Changing
the display functionality, page 54.
To reset the mass totalizer with the display:
1. Press Scroll until the process variable “TOTAL” appears and the
units of measure are mass units (e.g., kg, lb).
2. Press Select. The word “RESET” appears beneath the current
totalizer value.
3. Press Select. The word “YES?” begins to alternate with the word
“RESET.”
4. Press Select to reset the mass totalizer.

Resetting the volume Resetting the volume totalizer sets the volume total to zero.
totalizer You can reset the volume totalizer independent of the mass totalizer
with a HART Communicator or the display.

With a HART Communicator


To reset the volume totalizer with a HART Communicator:
1. Press 1, 4.
2. Select “Reset volume total.”

32 Series 1000 and 2000 Transmitters


Installing
Using the Transmitter continued

With the display


If the ability to reset totalizers has been disabled, you will not be
able to reset the volume totalizer with the display. For information
about enabling and disabling the display parameters, see Changing
the display functionality, page 54.
To reset the volume totalizer with the display:
1. Press Scroll until the process variable “TOTAL” appears and the

Starting
units of measure are volume units (e.g., gal, ft3).
2. Press Select. The word “RESET” appears beneath the current
totalizer value.
3. Press Select. The word “YES?” begins to alternate with the word
“RESET.”
4. Press Select to reset the volume totalizer.

Resetting both totalizers Resetting both totalizers simultaneously sets the mass and volume
totals to zero.

Using
You can reset both totalizers with a HART Communicator or
ProLink II software.

With a HART Communicator


To reset the mass and volume totalizers with a HART
Communicator:
1. Press 1, 4.

Changing Settings
2. Select “Reset all totals.”

With ProLink II software


To reset the mass and volume totalizers with ProLink II software:
1. Click ProLink.
2. Select Totalizer Control.
3. Click Reset.

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 33


34 Series 1000 and 2000 Transmitters
Installing
4 Changing the Transmitter
Settings

Starting
Aside from performing the startup procedures in Section 2, you
should only change the transmitter’s settings if the application
needs have changed or the transmitter is being put into a service
Stop
other than the one for which it was ordered.

4.1 Overview This section describes procedures for changing the operating
settings of the transmitter. The procedures in this section will
enable you to:

Using
• Change the measurement units
• Create special measurement units
• Change event settings
• Change the damping and slug-flow values
• Change the low-flow cutoff
• Change the flow direction parameter
• Change the software tag

Changing Settings
• Change the display functionality
• Assign process variables to analog outputs
• Change the mA output
• Change the frequency output
• Change the fault timeout parameter
• Change communications settings
Note: All HART Communicator key sequences in this section
assume that you are starting from the “Online” menu. See
Conventions used in this manual, page 108.

Characterizing and
Note: All ProLink II procedures provided in this section
assume that your computer is already connected to the Calibrating
transmitter and you have established communication. See
Using ProLink II Software, page 111.

4.2 Configuration map Use the map in Figure 4-1, page 36, to guide you through a complete
or partial configuration of the transmitter.
Troubleshooting

Series 1000 and 2000 Transmitters 35


Changing the Transmitter Settings continued

Figure 4-1. Configuration map

Measurement Pages 37–41


units
Mass-flow Volume-flow Density Temperature
units units units units
Special
measurement Pages 42–44
units Mass-flow Volume-flow
units units

Events Page 45

Damping Pages 46–47


Flow Density Temperature
damping damping damping

Slug flow Pages 48–50


Low High Slug-flow
slug-flow slug-flow duration
limit limit
Low-flow cutoff Pages 51–51
Mass low-flow Volume low-flow
cutoff cutoff

Flow direction Page 52

Software tag Page 53

Display Pages 54–56


functionality
Enable and Scroll rate Off-line Display
disable password variables

Analog output Pages 57–58


variables
Series 1000 Series 2000
Transmitter Transmitter

mA Pages 59–62
output
Upper range Lower range Damping Fault output
value value

Frequency Pages 63–67


output
Output scale Fault output Pulse width

Fault timeout Page 68

Communication Pages 68–73


RS-485 settings HART burst mode Polling address mA & Freq.
range values

36 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

4.3 Changing the You can change the unit of measure used for each process variable
measurement units with a HART Communicator or ProLink II software.

Mass-flow units You can change the mass-flow measurement unit with a HART
Communicator or ProLink II software.

With a HART Communicator

Starting
To change the mass-flow measurement unit with a HART
Communicator:
1. Press 4, 2, 1.
2. Select “Mass flo unit.”
3. Select a unit from the list. See Table 4-1 for a complete list of
mass-flow measurement units.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

Using
Table 4-1. Mass-flow measurement units
Mass-flow unit Unit description
g/s Grams per second
g/min Grams per minute
g/h Grams per hour
kg/s Kilograms per second
kg/min Kilograms per minute

Changing Settings
kg/h Kilograms per hour
kg/d Kilograms per day
MetTon/min Metric tons per minute
MetTon/h Metric tons per hour
MetTon/d Metric tons per day
lb/s Pounds per second
lb/min Pounds per minute
lb/h Pounds per hour

Characterizing and
lb/d Pounds per day

Calibrating
STon/min Short tons (2000 pounds) per minute
STon/h Short tons (2000 pounds) per hour
STon/d Short tons (2000 pounds) per day
LTon/h Long tons (2240 pounds) per hour
LTon/d Long tons (2240 pounds) per day
Spcl Special unit (See Creating special measurement
units, page 42)
Troubleshooting

Series 1000 and 2000 Transmitters 37


Changing the Transmitter Settings continued

With ProLink II software


To change the mass-flow measurement unit with ProLink II
software:
1. Click the Flow tab.
2. Click the arrow in the Mass Flow Units box, and select a
measurement unit from the list.
3. Click Apply.

Volume-flow units You can change the volume-flow measurement unit with a HART
Communicator or ProLink II software.

With a HART Communicator


To change the volume-flow measurement unit with a HART
Communicator:
1. Press 4, 2, 1.
2. Select “Vol flo unit.”
3. Select a measurement unit from the list. See Table 4-2, page 39,
for a complete list of volume-flow measurement units.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the volume-flow measurement unit with ProLink II
software:
1. Click the Flow tab.
2. Click the arrow in the Vol Flow Units box, and select a
measurement unit from the list.
3. Click Apply.

38 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

Table 4-2. Volume-flow measurement units


Volume-flow unit Unit description
Cuft/s Cubic feet per second
Cuft/min Cubic feet per minute
Cuft/h Cubic feet per hour
Cuft/d Cubic feet per day

Starting
Cum/s Cubic meters per second
Cum/min Cubic meters per minute
Cum/h Cubic meters per hour
Cum/d Cubic meters per day
gal/s U.S. gallons per second
gal/min U.S. gallons per minute
gal/h U.S. gallons per hour
gal/d U.S. gallons per day
MMgal/d Million U.S. gallons per day

Using
L/s Liters per second
L/min Liters per minute
L/hr Liters per hour
ML/d Million liters per day
Impgal/s Imperial gallons per second
Impgal/min Imperial gallons per minute
Impgal/h Imperial gallons per hour

Changing Settings
Impgal/d Imperial gallons per day
bbl/s Barrels per second
bbl/min Barrels per minute
bbl/h Barrels per hour
bbl/d Barrels per day
Spcl Special unit (See Creating special measurement
units, page 42)

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 39


Changing the Transmitter Settings continued

Density units You can change the density measurement units with a HART
Communicator or ProLink II software.

With a HART Communicator


To change the density measurement unit with a HART
Communicator:
1. Press 4, 2, 2.
2. Select “Dens unit.”
3. Select a unit from the list. See Table 4-3 for a complete list of
density measurement units.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

Table 4-3. Density measurement units


Density unit Unit description
SGU Specific gravity unit
g/Cucm Grams per cubic centimeter
kg/Cum Kilograms per cubic meter
lb/gal Pounds per gallon
lb/Cuft Pounds per cubic foot
g/mL Grams per milliliter
kg/L Kilograms per liter
g/L Grams per liter
lb/Cuin Pounds per cubic inch
STon/Cuyd Short ton per cubic yard

With ProLink II software


To change the density measurement unit with ProLink II software:
1. Click the Density tab.
2. Click the arrow in the Dens Units box, and select a measurement
unit from the list.
3. Click Apply.

40 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

Temperature units You can change the temperature measurement unit with a HART
Communicator or ProLink II software.

With a HART Communicator


To change the temperature measurement unit with a HART
Communicator:
1. Press 4, 2, 3.

Starting
2. Select “Temp unit.”
3. Select a unit from the list. See Table 4-4 for a complete list of
temperature measurement units.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

Table 4-4. Temperature measurement units


Temperature unit Unit description
degC Degrees Celsius

Using
degF Degrees Fahrenheit
degR Degrees Rankine
Kelvin Kelvin

With ProLink II software


To change the temperature measurement unit with ProLink II
software:

Changing Settings
1. Click the Temperature tab.
2. Click the arrow in the Temp Units box, and select a measurement
unit from the list.
3. Click Apply.

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 41


Changing the Transmitter Settings continued

4.4 Creating special If you need to use a non-standard unit of measure, you can create
measurement units one special measurement unit for mass flow and one special
measurement unit for volume flow. Special measurement units
consist of:
• Base unit—A combination of:
- Base mass or base volume unit—A measurement unit that the
transmitter already recognizes (e.g., kg, m 3)
- Base time unit—A unit of time that the transmitter already
recognizes (e.g., seconds, days)
• Conversion factor—The number by which the base unit will be
divided to convert to the special unit
• Special unit—A non-standard volume-flow or mass-flow unit of
measure that you want to be reported by the transmitter
The terms above are related by the following formula:

Base unit
------------------------------- = Conversion factor
Special unit

To create a special unit, you must:


1. Identify the simplest base volume or mass and base time units for
your special mass-flow or volume-flow unit. For example, to
create the special volume-flow unit pints per minute, the simplest
base units are gallons per minute:
a. Base volume unit: gallon
b. Base time unit: minute
2. Calculate the conversion factor using the formula below:
Note: 1 gallon per minute = 8 pints per minute

1 (gallon per minute)


------------------------------------------------------- = 0.125 (conversion factor)
8 (pints per minute)

3. Name the new special mass-flow or volume-flow measurement


unit and its corresponding totalizer measurement unit:
a. Special volume-flow measurement unit name: Pint/min
b. Volume totalizer measurement unit name: Pints
Note: Special measurement unit names can be up to 8
characters long (i.e., 8 numbers or letters), but only the first 5
characters appear on the display.

42 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

Special mass-flow unit You can create a special mass-flow measurement unit with a HART
Communicator or ProLink II software.

With a HART Communicator


To create a special mass-flow measurement unit with a HART
Communicator:
1. Press 4, 2, 1.

Starting
2. Select “Spcl mass units.”
3. Specify the base mass unit:
a. Select “Base mass unit.”
b. Select a mass unit from the list.
c. Press F4 “ENTER.”
4. Specify the base mass time:
a. Select “Base mass time.”
b. Select a time unit from the list.
c. Press F4 “ENTER.”

Using
5. Specify the mass-flow conversion factor:
a. Select “Mass flo conv fact.”
b. Type a conversion factor. The value can contain up to 5 digits.
c. Press F4 “ENTER.”
6. Assign a name to the new special mass-flow measurement unit:
a. Select “Mass flo text.”
b. Type the name of the special mass-flow measurement unit.
c. Press F4 “ENTER.”

Changing Settings
7. Assign a name to the mass totalizer measurement unit:
a. Select “Mass totl text.”
b. Type the name of the mass totalizer measurement unit.
c. Press F4 “ENTER.”
8. Press F2 “SEND.”

With ProLink II software


To create a special mass-flow measurement unit with ProLink II
software:

Characterizing and
1. Click the Special Units tab.
2. Click the arrow in the Base Mass Unit box, and select a base Calibrating
mass unit from the list.
3. Click the arrow in the Base Mass Time box, and select a base
time unit from the list.
4. Type the conversion factor in the Mass Flow Conv Fact box.
5. Type the name of the special mass-flow measurement unit in the
Mass Flow Text box.
6. Type the name of the mass totalizer measurement unit in the
Troubleshooting

Mass Total Text box.


7. Click Apply.

Series 1000 and 2000 Transmitters 43


Changing the Transmitter Settings continued

Special volume-flow unit You can create a special volume-flow measurement unit with a
HART Communicator or ProLink II software.

With a HART Communicator


To create a special volume-flow measurement unit with a HART
Communicator:
1. Press 4, 2, 1.
2. Select “Spcl vol units.”
3. Specify the base volume unit:
a. Select “Base vol unit.”
b. Select a volume unit from the list.
c. Press F4 “ENTER.”
4. Specify the base time unit:
a. Select “Base vol time.”
b. Select a time unit from the list.
c. Press F4 “ENTER.”
5. Specify the volume-flow conversion factor:
a. Select “Vol flo conv fact.”
b. Type a conversion factor. The value can contain up to 5 digits.
c. Press F4 “ENTER.”
6. Assign a name to the new special volume-flow measurement unit:
a. Select “Vol flo text.”
b. Type the name of the special volume-flow measurement unit.
c. Press F4 “ENTER.”
7. Assign a name to the volume totalizer measurement unit:
a. Select “Vol totl text.”
b. Type the name of the volume totalizer measurement unit.
c. Press F4 “ENTER.”
8. Press F2 “SEND.”

With ProLink II software


To create a special volume-flow measurement unit with ProLink II
software:
1. Click the Special Units tab.
2. Click the arrow in the Base Vol Units box, and select a volume
unit from the list.
3. Click the arrow in the Base Vol Time box, and select a time unit
from the list.
4. Type the conversion factor in the Vol Flow Conv Fact box.
5. Type the name of the special volume-flow measurement unit in
the Vol Flow Text box.
6. Type the name of the volume totalizer measurement unit in the
Vol Total Text box.
7. Click Apply.

44 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

4.5 Changing event settings Events are specified process variable levels that trigger alarms. You
can set up to two events, either on the same process variable or on
two different process variables. Each event is associated with either
a high or a low alarm.
Before you set the events, determine the process variable, alarm
type, and setpoint that will be associated with each event. Table 4-5
lists the process variables, alarm types, and setpoints you must
specify for each event.

Starting
Table 4-5. Event settings
Event number Process variable Alarm type Setpoint
Event 1 Any process variable • High alarm—Event 1 is The user-defined value at which
for Event 1 triggered if the process variable the Event 1 alarm is triggered
exceeds the setpoint.
• Low alarm—Event 1 is
triggered if the process variable
drops below the setpoint.
Event 2 Any process variable • High alarm—Event 2 is The user-defined value at which
for Event 2 triggered if the process variable the Event 2 alarm is triggered

Using
exceeds the setpoint.
• Low alarm—Event 2 is
triggered if the process variable
drops below the setpoint.

You can change the event settings with a HART Communicator or


ProLink II software.

With a HART Communicator

Changing Settings
To change the event settings with a HART Communicator:
1. Select the process variable:
a. Press 4, 5.
b. Select “Event 1” or “Event 2.”
c. Press 1 “var.”
d. Select a process variable from the list.
e. Press F4 “ENTER.”
f. Press F2 “SEND.”
2. Select the alarm type:

Characterizing and
a. Press 2 “type.”
Calibrating
b. Select “High alarm” or “Low alarm.”
c. Press F4 “OK.”
d. Press F2 “SEND.”
3. Define the setpoint:
a. Press 3 “setpoint.”
b. Type the setpoint. The setpoint can contain up to 8 digits.
c. Press F4 “ENTER.”
d. Press F2 “SEND.”
Troubleshooting

Series 1000 and 2000 Transmitters 45


Changing the Transmitter Settings continued

With ProLink II software


To change the event settings with ProLink II software:
1. Click the Events tab.
2. Click the arrow in each Var box, and select a process variable.
3. Click the arrow in each Type box, and select an alarm type.
4. Type the setpoint level for each event in the Setpoint boxes.
5. Click Apply.

4.6 Changing the damping A damping value is a period of time, in seconds, that helps the
values transmitter smooth out small, rapid measurement fluctuations.
• A high damping value makes the output appear to be smoother
because the output must change slowly.
• A low damping value makes the output appear to be more erratic
because the output changes more quickly.
You can change the damping values for flow, density, and
temperature.

Flow damping Flow damping affects mass flow and volume flow. You can change
the flow damping value with a HART Communicator or ProLink II
software.

With a HART Communicator


To change the flow damping value with a HART Communicator:
1. Press 4, 2, 1.
2. Select “Flo damp.”
3. Type a new damping value.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the flow damping value with ProLink II software:
1. Click the Flow tab.
2. Type a new damping value in the Flow Damp box.
3. Click Apply.

46 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

Density damping You can change the density damping value with a HART
Communicator or ProLink II software.

With a HART Communicator


To change the density damping value with a HART Communicator:
1. Press 4, 2, 2.
2. Select “Dens damp.”

Starting
3. Type a new damping value.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the density damping value with ProLink II software:
1. Click the Density tab.
2. Type a new damping value in the Dens Damping box.
3. Click Apply.

Using
Temperature damping You can change the temperature damping value with a HART
Communicator or ProLink II software.

With a HART Communicator


To change the temperature damping value with a HART
Communicator:

Changing Settings
1. Press 4, 2, 3.
2. Select “Temp damp.”
3. Type a new damping value.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the temperature damping value with ProLink II software:

Characterizing and
1. Click the Temperature tab.

Calibrating
2. Type a new damping value in the Temp Damp box.
3. Click Apply. Troubleshooting

Series 1000 and 2000 Transmitters 47


Changing the Transmitter Settings continued

4.7 Adjusting meter factors Meter factors allow you to modify the transmitter’s output so that it
matches an external measurement standard. For example, if you
need to fill a customer’s 500-gallon tank based on the customer’s
definition of a gallon, you can use the meter factors to make the
transmitter match the customer’s gallon definition.
You can adjust meter factors for mass flow, volume flow, and
density.
• If you adjust the mass-flow or density meter factor, the volume
meter factor defaults to 1.0000.
• If you adjust the volume-flow meter factor, the mass and density
meter factors each default to 1.0000.
• Only values from 0.8 to 1.2 may be entered.
To determine a meter factor’s value, divide the value of the external
standard by the actual output of the transmitter, as in the following
formula:

External standard
Meter factor = -----------------------------------------------------------------
Actual transmitter output

For example, if the external standard states that the transmitter


should have a flow output of 5 gallons for a given volume of fluid,
then divide the transmitter’s actual output (in gallons) by 5. The
result is the volume flow meter factor.
You can adjust meter factors with a HART Communicator.
To adjust the mass flow, volume flow, or density meter factor:
1. Press 4, 1, 5.
2. Select the meter factor you want to change.
3. Press F4 “ENTER.”
4. Type a new meter factor value.
5. Press F2 “SEND.”

4.8 Changing slug-flow limits Slugs—gas in a liquid process or liquid in a gas


and duration process—occasionally appear in some applications. The presence of
slugs can affect the process density reading dramatically. Slug-flow
limits and duration can help the transmitter suppress dramatic
changes in reading.

48 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

Low slug-flow limit The low slug-flow limit is the lowest point of the typical density
range of the process you are measuring. The transmitter uses the
low slug-flow limit to distinguish between normal process flow and
slug flow.
You can change the low slug-flow limit with a HART Communicator
or ProLink II software.

Starting
With a HART Communicator
To change the low slug-flow limit with a HART Communicator:
1. Press 4, 2, 2.
2. Select “Slug low limit.”
3. Type a new low slug-flow limit.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software

Using
To change the low slug-flow limit with ProLink II software:
1. Click the Density tab.
2. Type a new low slug-flow limit in the Slug Low Limit box. The
value must be between –0.1 and 5.0 g/cc.
3. Click Apply.

High slug-flow limit The high slug-flow limit is the highest point of the typical density

Changing Settings
range of the process you are measuring. The transmitter uses the
high slug-flow limit to distinguish between normal process flow and
slug flow.
You can change the high slug-flow limit with a HART
Communicator or ProLink II software.

With a HART Communicator


To change the high slug-flow limit with a HART Communicator:
1. Press 4, 2, 2.

Characterizing and
2. Select “Slug high limit.”

Calibrating
3. Type a new high slug-flow limit.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the high slug-flow limit with ProLink II software:
1. Click the Density tab.
2. Type a new high slug-flow limit in the Slug High Limit box. The
value must be between –0.1 and 5.0 g/cc.
Troubleshooting

3. Click Apply.

Series 1000 and 2000 Transmitters 49


Changing the Transmitter Settings continued

Slug-flow duration The slug-flow duration is the number of seconds the transmitter
waits for a slug-flow condition (outside the slug-flow limits) to return
to normal (inside the slug-flow limits). If the transmitter detects
slug flow, it will post a slug-flow alarm and hold its last “pre-slug”
flow rate until the end of the slug-flow duration. If slugs are still
present after the slug-flow duration has expired, the transmitter
will report a flow rate of zero.
You can change the slug-flow duration with a HART Communicator
or ProLink II software.

With a HART Communicator


To change the slug-flow duration with a HART Communicator:
1. Press 4, 2, 2.
2. Select “Slug duration.”
3. Type a new slug-flow duration.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the slug-flow duration with ProLink II software:
1. Click the Density tab.
2. Type a new slug-flow duration in the Slug Duration box.
3. Click Apply.

50 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

4.9 Changing low-flow cutoff Low-flow cutoff is a user-defined flow measurement below which the
transmitter reports zero flow. Low-flow cutoff can be changed for
either mass flow or volume flow.

Mass low-flow cutoff You can change the mass low-flow cutoff with a HART
Communicator or ProLink II software.

Starting
With a HART Communicator
To change the mass low-flow cutoff with a HART Communicator:
1. Press 4, 2, 1.
2. Select “Mass flo cutoff.”
3. Type the new mass low-flow cutoff.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software

Using
To change the mass low-flow cutoff with ProLink II software:
1. Click the Flow tab.
2. Type the new mass low-flow cutoff in the Mass Flow Cutoff box.
3. Click Apply.

Volume low-flow cutoff You can change the volume low-flow cutoff with a HART

Changing Settings
Communicator or ProLink II software.

With a HART Communicator


To change the volume low-flow cutoff with a HART Communicator:
1. Press 4, 2, 1.
2. Select “Vol flo cutoff.”
3. Type the new volume low-flow cutoff.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

Characterizing and
Calibrating
With ProLink II software
To change the volume low-flow cutoff with ProLink II software:
1. Click the Flow tab.
2. Type the new volume low-flow cutoff in the Vol Flow Cutoff box.
3. Click Apply.
Troubleshooting

Series 1000 and 2000 Transmitters 51


Changing the Transmitter Settings continued

4.10 Changing the flow The flow direction parameter defines whether the transmitter
direction parameter reports a positive or negative flow rate and how the flow is added to
or subtracted from the totalizers.
Table 4-6 shows the possible values for the flow direction parameter
and the transmitter’s behavior when the flow is positive or negative.
• Positive flow moves in the direction of the arrow on the sensor.
• Negative flow moves in the direction opposite of the arrow on the
sensor.

Table 4-6. Transmitter behavior for each flow direction value


Process fluid flow is positive Process fluid flow is negative
Milliamp Flow values Milliamp Flow values
Flow and on display or and on display or
direction frequency Flow via digital frequency Flow via digital
value outputs totals comm. outputs totals comm.
Forward only Increase Increase Read positive Zero No change Read negative
Reverse only Zero No change Read positive Increase Increase Read negative
Bidirectional Increase Increase Read positive Increase Decrease Read negative
1
Absolute value Increase Increase Read positive Increase Increase Read positive1
1. Refer to the digital communications status bits for an indication of whether flow is positive or negative.

You can change the flow direction parameter with a HART


Communicator or ProLink II software.

With a HART Communicator


To change the flow direction parameter with a HART
Communicator:
1. Press 4, 2, 1.
2. Select “Flo direction.”
3. Select a flow direction value. See Table 4-6.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the flow direction parameter with ProLink II software:
1. Click the Flow tab.
2. Click the arrow in the Flow Direction box, and select a flow
direction value from the list. See Table 4-6.
3. Click Apply.

52 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

4.11 Changing the software tag The transmitter is capable of holding a software tag in its memory.
The software tag is a short name or identifier for the transmitter.
You can change the software tag with a HART Communicator or
ProLink II software.

With a HART Communicator


To change the software tag with a HART Communicator:

Starting
1. Press 3.
2. Select “Tag.”
3. Type the new software tag name. The name can contain up to 8
characters (i.e., 8 numbers or letters).
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the software tag with ProLink II software:

Using
1. Click the Device tab.
2. Type the desired software tag in the Descriptor box.
3. Click Apply.

Changing Settings
Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 53


Changing the Transmitter Settings continued

4.12 Changing the display You can restrict the display functionality or change the variables
functionality that are shown on the display.

Enabling and disabling Each display parameter is listed in Table 4-7.


display parameters

Table 4-7. Display parameters


Parameter Enabled Disabled
Totalizer reset Operators are able to reset the mass and Operators are prevented from resetting the
volume totalizers. mass and volume totalizers.
Auto scroll The display automatically scrolls through Operators must press the Scroll button to
each process variable. view process variables.
Off-line menu Operators have access to the off-line menu Operators are prevented from gaining access
(zero and simulation). to the off-line menu.
Off-line password Operators must use a password to gain Operators have access to the off-line menu
access to the off-line menu. See Changing without a password.
the off-line password, page 55.
Alarm menu Operators have access to the alarm menu Operators are prevented from gaining access
(viewing and acknowledging alarms). to the alarm menu.
Acknowledge all Operators are able to acknowledge all current Operators must acknowledge alarms
alarms alarms at once. individually.

You can enable and disable the display parameters with a HART
Communicator or ProLink II software.

With a HART Communicator


To enable or disable the display parameters with a HART
Communicator:
1. Press 4, 6.
2. Select “Enable/Disable.”
3. Select one of the display parameters listed.
4. Select “Enable” or “Disable.”
5. Press F4 “ENTER.”
6. Press F2 “SEND.”

With ProLink II software


To enable or disable the display parameters with ProLink II
software:
1. Click the Transmitter Options tab.
2. If you want to enable a display function, then select the checkbox
next to the parameter name. Parameters with check marks next
to them indicate enabled functions.
3. If you want to disable a display function, then clear the checkbox
next to the parameter name. Parameters without checkmarks
next to them indicate disabled functions.
4. Click Apply.

54 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

Changing the scroll rate The scroll rate is the speed at which the defined display variables
cycle on the display screen. A shorter scroll rate makes the variables
cycle more quickly.
You can change the scroll rate with a HART Communicator or
ProLink II software.

With a HART Communicator

Starting
You must enable auto scroll before the scroll rate will appear on the
HART Communicator (see Enabling and disabling display
parameters, page 54).
To change the display scroll rate with a HART Communicator:
1. Enable “Auto scroll” (see Enabling and disabling display
parameters, page 54).
2. Select “Scroll Rate.”
3. Type the desired scroll rate (from 1 to 10 seconds).
4. Press F4 “ENTER.”

Using
5. Press F2 “SEND.”

With ProLink II software


To change the scroll rate with ProLink II software:
1. Click the Display Config tab.
2. Type the desired scroll rate (from 1 to 10 seconds) in the Scroll
Rate box.
3. Click Apply.

Changing Settings
Changing the off-line The off-line password prevents unauthorized users from gaining
password access to the off-line menu.
You can change the off-line password with a HART Communicator
or ProLink II software.

With a HART Communicator


You must enable the off-line password before you can set the off-line
password (see Enabling and disabling display parameters, page 54).

Characterizing and
To change the off-line password with a HART Communicator:
1. Enable the off-line password (see Enabling and disabling display Calibrating
parameters, page 54).
2. Select “Offline Password.”
3. Type a new password. The password can contain up to four
numbers.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”
Troubleshooting

Series 1000 and 2000 Transmitters 55


Changing the Transmitter Settings continued

With ProLink II software


To change the off-line password with ProLink II software:
1. Click the Display Config tab.
2. Type the desired off-line password in the Display Offline
Password box. The password can contain up to four numbers.
3. Click Apply.

Changing the display The display can scroll through up to 15 process variables in any
variables order. You can select the process variables you wish to see and the
order in which they should appear. The first process variable is
permanently set to the variable assigned to the mA output.
Table 4-8 shows an example of a display variable configuration.
Notice that you can repeat variables.

Table 4-8. Example of a display variable configuration


Display variable Process variable
Display variable 11 Mass flow
Display variable 2 Volume flow
Display variable 3 Density
Display variable 4 Mass flow
Display variable 5 Volume flow
Display variable 6 Mass totalizer
Display variable 7 Mass flow
Display variable 8 Temperature
Display variable 9 Volume flow
Display variable 10 Volume totalizer
Display variable 11 Density
Display variable 12 Temperature
Display variable 13 None
Display variable 14 None
Display variable 15 None
1. Display variable 1 always represents the same process variable that is assigned
to the mA output, and cannot be changed.

You can change the display variables with a HART Communicator


or ProLink II software.

With a HART Communicator


To change the display variables with a HART Communicator:
1. Press 4.
2. Select “Display Setup.”
3. Select the display variable number you want to change.

56 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

4. Select a process variable from the list.


Note: You can also select “None” from the list, which disables
a variable from being shown in the position.
5. Press F4 “ENTER.”
6. Repeat Step 2 through Step 5 to change the remaining display
variables. You can select as many as 14 process variables.

Starting
7. Press F2 “SEND.”

With ProLink II software


To change the display variables with ProLink II software:
1. Click the Display Config tab.
2. Click the arrow in each variable’s box, and select a process
variable from the list.
3. Click Apply.

Using
4.13 Assigning process Depending upon whether you are using a Series 1000 transmitter or
variables to analog a Series 2000 transmitter, you can assign one or two process
outputs variables to the analog outputs.

With a Series 1000 With a Series 1000 transmitter, you can assign one process variable
transmitter as the primary variable (PV), which is reported by the analog
outputs. The way the assigned variable is reported depends upon
which variable it is. Table 4-9 shows the results of assigning each

Changing Settings
process variable as the PV.

Table 4-9. Series 1000 transmitter primary variable assignment


Milliamp output Frequency output
Primary variable (terminals 1 and 2) (terminals 3 and 4)
Mass flow or Reports the mass flow Reports the same
volume flow or volume flow variable as the milliamp
output
Temperature or Reports the Reports no variable
density temperature or density (terminals are disabled)

Characterizing and
Calibrating
You can assign a process variable as the PV with a HART
Communicator or ProLink II software.

With a HART Communicator


To assign a process variable as the PV with a HART Communicator:
1. Press 4, 3, 1.
2. Select “PV is.”
3. Select a process variable.
4. Press F4 “ENTER.”
Troubleshooting

5. Press F2 “SEND.”

Series 1000 and 2000 Transmitters 57


Changing the Transmitter Settings continued

With ProLink II software


To assign a process variable as the PV with ProLink II software:
1. Click the Analog Output tab.
2. Click the arrow in the PV is box, and select the desired process
variable.
3. Click Apply.

With a Series 2000 With a Series 2000 transmitter, you can assign two process
transmitter variables, which are reported by the analog outputs:
• Primary variable (PV)—reported as the mA output
• Tertiary variable (TV)—reported as the frequency output
Table 4-10 lists the process variables that can or cannot be assigned
as the PV or TV.

Table 4-10. Series 2000 transmitter primary and tertiary variable


assignment
Primary variable Tertiary variable
Process variable (milliamp output) (frequency output)
Mass flow yes yes
Volume flow yes yes
Temperature yes no
Density yes no

You can assign process variables as the Series 2000 transmitter PV


and TV with a HART Communicator or ProLink II software.

58 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

With a HART Communicator


To assign process variables as the Series 2000 transmitter PV and
TV with a HART Communicator:
1. Press 4, 3, 1.
2. Select “PV is.”
3. Select a process variable.

Starting
4. Press F4 “ENTER.”
5. Press the Left Arrow.
6. Press 2.
7. Select “TV is.”
8. Select a process variable. You can select only mass flow or volume
flow.
9. Press F4 “ENTER.”
10. Press F2 “SEND.”

With ProLink II software

Using
To assign process variables as the Series 2000 transmitter PV and
TV with ProLink II software:
1. Click the Analog Output tab.
2. Click the arrow in the PV is box, and select a process variable.
3. Click Apply.
4. Click the Frequency Output tab.

Changing Settings
5. Click the arrow in the TV is box, and select a process variable.
You can select only mass flow or volume flow.
6. Click Apply.

4.14 Changing the milliamp To change the mA output for analog measurement, define or change
output the following values:
• Upper range value (URV)
• Lower range value (LRV)
• Damping

Characterizing and
• Fault output indicator
Calibrating

Changing the upper range The transmitter uses a range of 4 to 20 mA. The upper range value
value (URV) is the measurement that you want to associate with the 20
mA output.
You can change the URV with a HART Communicator, the display,
or ProLink II software.
Troubleshooting

Series 1000 and 2000 Transmitters 59


Changing the Transmitter Settings continued

With a HART Communicator


To change the URV with a HART Communicator:
1. Press 4, 3, 1, 2.
2. Select “PV URV.”
3. Type a new URV.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With the display


To change the URV with the display:
1. Simultaneously press and hold Scroll and Select for 4 seconds.
When the words “SEE ALARM” or “OFF-LINE MAINT” appear
on the display, then release the buttons.
2. If the words “OFF-LINE MAINT” do not appear on the display,
then press Scroll until the words “OFF-LINE MAINT” appear.
3. Press Select.
4. If the word “CODE?” appears on the display, then enter the
off-line password (see Changing the off-line password, page 55):
a. Press Scroll until the digit above “CODE?” equals the first digit
of the off-line password.
b. Press Select.
c. Repeat steps a and b for the second, third, and fourth digits of
the off-line password.
5. Press Scroll until the words “OFF-LINE CONFIG” appear on the
display.
6. Press Select.
7. Press Scroll until the words “CONFIG 20 MA” appear on the
display.
8. Press Select.
9. Enter a new URV. See Entering milliamp and frequency range
values with the display, page 73.
10. Press Scroll, if necessary, until the words “CONFIG EXIT”
appear on the display.
11. Press Select to exit the off-line configuration menu.
12. Press Scroll until the words “OFF-LINE EXIT” appear on the
display.
13. Press Select to exit the off-line menu.

With ProLink II software


To change the URV with ProLink II software:
1. Click the Analog Output tab.
2. Type a new URV in the URV box.
3. Click Apply.

60 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

Changing the lower range The transmitter uses a range of 4 to 20 mA. The lower range value
value (LRV) is the measurement that you want to associate with the 4 mA
output.
You can change the LRV with a HART Communicator, the display,
or ProLink II software.

With a HART Communicator

Starting
To change the LRV with a HART Communicator:
1. Press 4, 3, 1, 2.
2. Select “PV LRV.”
3. Type a new LRV.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With the display


To change the LRV with the display:

Using
1. Simultaneously press and hold Scroll and Select for 4 seconds.
When the words “SEE ALARM” or “OFF-LINE MAINT” appear
on the display, then release the buttons.
2. If the words “OFF-LINE MAINT” do not appear on the display,
then press Scroll until the words “OFF-LINE MAINT” appear.
3. Press Select.
4. If the word “CODE?” appears on the display, then enter the
off-line password (see Changing the off-line password, page 55):

Changing Settings
a. Press Scroll until the digit above “CODE?” equals the first digit
of the off-line password.
b. Press Select.
c. Repeat steps a and b for the second, third, and fourth digits of
the off-line password.
5. Press Scroll until the words “OFF-LINE CONFIG” appear on the
display.
6. Press Select.
7. Press Scroll until the words “CONFIG 4 MA” appear on the

Characterizing and
display.

Calibrating
8. Press Select.
9. Enter a new LRV. See Entering milliamp and frequency range
values with the display, page 73.
10. Press Scroll, if necessary, until the words “CONFIG EXIT”
appear on the display.
11. Press Select to exit the off-line configuration menu.
12. Press Scroll until the words “OFF-LINE EXIT” appear on the
display.
13. Press Select to exit the off-line menu.
Troubleshooting

Series 1000 and 2000 Transmitters 61


Changing the Transmitter Settings continued

With ProLink II software


To change the LRV with ProLink II software:
1. Click the Analog Output tab.
2. Type a new LRV in the LRV box.
3. Click Apply.

Changing damping You can specify a damping value strictly for the mA output. (See
Changing the damping values, page 46, for general information
about damping.) If you specify damping for the mA output, it affects
only the mA output, not the HART digital output.
You can change the damping value for the mA output with a HART
Communicator or ProLink II software.

With a HART Communicator


To change the damping value for the mA output with a HART
Communicator:
1. Press 4, 3, 1.
2. Select “PV AO added damp.”
3. Type the desired number of seconds for damping.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the damping value for the mA output with ProLink II
software:
1. Click the Analog Output tab.
2. Type a new damping value in the AO Added Damp box.
3. Click Apply.

Changing the fault output If the transmitter encounters an internal fault condition, it will send
indicator a preprogrammed measurement value to the receiving device. You
can change the value by changing the output indicator. See
Table 4-11.
Note: By default, the transmitter immediately reports a fault
when a fault is encountered. You can delay reporting faults
by changing the fault timeout. See Changing the fault
timeout parameter, page 68.

Table 4-11. Milliamp fault output indicators and values


Fault indicator Fault output value
Upscale 21–24 mA (22 mA by default)
Downscale 1–3 mA (2 mA by default)
Internal zero The value associated with 0 (zero) flow

62 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

You can change the fault output indicator with a HART


Communicator or ProLink II software.

With a HART Communicator


To change the fault output indicator with a HART Communicator:
1. Press 4, 3, 1.
2. Select “AO Fault Setup.”

Starting
3. Select “AO Fault Indicator.”
4. Select a fault indicator. See Table 4-11, page 62.
5. Press F4 “ENTER.”
6. Press F2 “SEND.”

With ProLink II software


To change the fault output indicator with ProLink II software:
1. Click the Analog Output tab.
2. Click the arrow in the Fault Code box, and select the desired fault

Using
output indicator.
3. Click Apply.

4.15 Changing the frequency To change the frequency output, select or change the following
output variables:
• Output scale

Changing Settings
• Fault output indicator
• Pulse width

Changing the output scale The frequency output scale denotes the relationship between each
pulse the transmitter reports and the number of flow units each
pulse represents. You can select one of three output scale methods
as listed in Table 4-12.

Table 4-12. Frequency output scale methods and results

Characterizing and
Method Parameters you must define Scale result

Calibrating
Frequency = flow • TV frequency factor—The number of The relationship between the frequency and
pulses you want to equal the TV rate factor the units is defined by the TV frequency
• TV rate factor—The number of units you factor and the TV rate factor.
want to equal the TV frequency factor
Pulses per unit • TV pulses/unit—The number of pulses you One measurement unit equals the number of
want to equal one unit pulses defined as “TV pulses/unit.”
Units per pulse • TV units/pulse—The number of units you One pulse equals the number of units of
want to equal one pulse measure defined as “TV units/pulse.”

You can change the frequency output scale with a HART


Troubleshooting

Communicator, the display, or ProLink II software.

Series 1000 and 2000 Transmitters 63


Changing the Transmitter Settings continued

With a HART Communicator


To change the frequency output scale with a HART Communicator:
1. Press 4, 3, 2.
2. Select “FO Scale Method.”
3. Select one of the scale methods listed in Table 4-12.
4. Press F2 “SEND.”
5. If you selected “Freq=flow” in Step 3, then:
a. Press 3 “FO Scaling.”
b. Press 1 “TV Freq factr.”
c. Type the number of pulses you want to equal a specific number
of units.
d. Press F4 “ENTER.”
e. Press 2 “TV Rate factr.”
f. Type the number of units you want to equal the number of
pulses you assigned to the TV frequency factor in Step c.
g. Press F4 “ENTER.”
h. Press F2 “SEND.”
6. If you selected “Pulses Per Unit” in Step 3, then:
a. Press 3 “FO Scaling.”
b. Press 1 “TV Pulses/Unit.”
c. Type the number of pulses you want to equal one measurement
unit.
d. Press F4 “ENTER.”
e. Press F2 “SEND.”
7. If you selected “Units Per Pulse” in Step 3, then:
a. Press 3 “FO Scaling.”
b. Press 2 “TV Units/Pulse.”
c. Type the number of units you want to equal one frequency
pulse.
d. Press F4 “ENTER.”
e. Press F2 “SEND.”

64 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

With the display


If the off-line menu has been disabled, you will not be able to change
the output scale with the display. For information about enabling
and disabling the off-line menu, see Enabling and disabling display
parameters, page 54.
To change the frequency output scale with the display:
1. Simultaneously press and hold Scroll and Select for 4 seconds.

Starting
When the words “SEE ALARM” or “OFF-LINE MAINT” appear
on the display, then release the buttons.
2. If the words “OFF-LINE MAINT” do not appear on the display,
then press Scroll until the words “OFF-LINE MAINT” appear.
3. Press Select.
4. If the word “CODE?” appears on the display, then enter the
off-line password (see Changing the off-line password, page 55):
a. Press Scroll until the digit above “CODE?” equals the first digit
of the off-line password.
b. Press Select.

Using
c. Repeat steps a and b for the second, third, and fourth digits of
the off-line password.
5. Press Scroll until the words “OFF-LINE CONFIG” appear on the
display.
6. Press Select.
7. Press Scroll until the words “CONFIG FREQ” appear on the
display.

Changing Settings
8. Press Select.
9. Enter the number of pulses you want to equal a specific number
of units. See Entering milliamp and frequency range values with
the display, page 73.
10. Press Scroll until the words “CONFIG RATE” appear on the
display.
11. Enter the number of units you want to equal the number of
pulses you entered in Step 9. See Entering milliamp and
frequency range values with the display, page 73.
12. Press Scroll, if necessary, until the words “CONFIG EXIT”

Characterizing and
appear on the display.

Calibrating
13. Press Select to exit the off-line configuration menu.
14. Press Scroll until the words “OFF-LINE EXIT” appear on the
display.
15. Press Select to exit the off-line menu.
Troubleshooting

Series 1000 and 2000 Transmitters 65


Changing the Transmitter Settings continued

With ProLink II software


To change the frequency output scale with ProLink II software:
1. Click the Frequency tab.
2. Click the arrow next to Scaling Method, and select one of the
scale methods listed in Table 4-12, page 63.
3. If you selected “Freq = Flow” in Step 2, then:
a. Type the number of pulses you want to equal a specific number
of units in the Pulses Per Unit box.
b. Type the number of units you want to equal the number of
pulses per unit you typed in Step a in the Units Per Pulse box.
c. Click Apply.
4. If you selected “Pulses Per Unit” in Step 2, then:
a. Type the number of pulses you want to equal one measurement
unit in the Pulses Per Unit box.
b. Click Apply.
5. If you selected “Units Per Pulse” in Step 2, then:
a. Type the number of units you want to equal one pulse in the
Units Per Pulse box.
b. Click Apply.

Changing the fault output If the transmitter encounters an internal fault condition, it will send
indicator a preprogrammed measurement value to the receiving device. You
can change the value by changing the fault output indicator. See
Table 4-13.
Note: By default, the transmitter immediately reports a fault
when a fault is encountered. You can delay reporting faults
by changing the fault timeout. See Changing the fault
timeout parameter, page 68.

Table 4-13. Frequency fault output indicators and values


Fault indicator Fault output value
Upscale The user-specified upscale value in Hz
Downscale 0 Hz
Internal zero 0 Hz

You can change the fault output indicator with a HART


Communicator or ProLink II software.

66 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

With a HART Communicator


To change the fault output indicator with a HART Communicator:
1. Press 4, 3, 2.
2. Select “FO Fault Setup.”
3. Select “FO Fault Indicator.”
4. Select a fault output setting.

Starting
5. Press F4 “ENTER.”
6. Press F2 “SEND.”

With ProLink II software


To change the fault output indicator with ProLink II software:
1. Click the Frequency tab.
2. Click the arrow in the Fault Code box, and select the desired fault
indicator.
3. Click Apply.

Using
Changing the pulse width The frequency output pulse width denotes the maximum duration of
each pulse the transmitter sends to the frequency receiving device.
If you have a receiving device that cannot recognize long pulse
durations (widths), you might need to change the maximum pulse
width.
You can change the maximum pulse width with a HART
Communicator or ProLink II software.

Changing Settings
With a HART Communicator
To change the maximum pulse width with a HART Communicator:
1. Press 4, 3, 2.
2. Select “FO Scaling.”
3. Select “Max Pulse Width.”
4. Type a new maximum pulse width (duration), in milliseconds.
5. Press F4 “ENTER.”

Characterizing and
6. Press F2 “SEND.”

With ProLink II software Calibrating


To change the maximum pulse width with ProLink II software:
1. Click the Frequency tab.
2. Type a new maximum pulse width (duration), in milliseconds, in
the Freq Pulse Width box.
3. Click Apply.
Troubleshooting

Series 1000 and 2000 Transmitters 67


Changing the Transmitter Settings continued

4.16 Changing the fault timeout By default, the transmitter immediately reports a fault when a fault
parameter is encountered. You can configure the transmitter to delay reporting
a fault by changing the fault timeout parameter to a nonzero value.
During the fault timeout period, the transmitter continues to report
its last valid measurement.
You can change the fault timeout parameter with a HART
Communicator or ProLink II software.

With the HART Communicator


To change the fault timeout parameter with a HART
Communicator:
1. Press 4, 3.
2. Select “Fault Timeout.”
3. Type a new fault timeout value. The value can be no greater than
60 seconds.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the fault timeout parameter with ProLink II software:
1. Click the Analog Output tab.
2. Type a new value in the LMV Timeout box.
3. Click Apply.

4.17 RS-485 communication Transmitter terminals 5 and 6 communicate digitally via RS-485
settings communication standard. You can change the communication
protocol, parity, number of stop bits, and baud rate of the terminals
to the values shown in Table 4-14.

Table 4-14. RS-485 communication settings for terminals 5 and 6


Protocol Parity Stop bits Baud rate
Modbus or HART Odd, even, or none 1 or 2 1200 to 38,400

You can change the RS-485 communication settings with a HART


Communicator or ProLink II software
Note: Changing the RS-485 communication settings affects
only terminals 5 and 6; it does not affect the mA/Bell 202
terminals (1 and 2) or the service port (terminals 7 and 8).

68 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

With a HART Communicator


To change the RS-485 Communication settings with a HART
Communicator:
1. Press 4, 3, 4.
2. Select “RS485 Setup.”
3. If you want to change the communication protocol, then:

Starting
a. Select “RS485 Protocol.”
b. Select one of the protocol options.
c. Press F4 “ENTER.”
4. If you want to change the baud rate, then:
a. Select “RS485 Baudrate.”
b. Select one of the baud rate options.
c. Press F4 “ENTER.”
5. If you want to change the parity, then:
a. Select “RS485 Parity.”
b. Select one of the parity options. If you chose “HART” in Step 3,

Using
then parity must be set to odd.
c. Press F4 “ENTER.”
6. If you want to change the number of stop bits, then:
a. Select “RS485 Stop Bits.”
b. Type a new number of stop bits. If you chose “HART” in Step 3,
then stop bits must be 1.
c. Press F4 “ENTER.”

Changing Settings
7. Press F2 “SEND.”

With ProLink II software


To change the RS-485 communication settings with ProLink II
software:
1. Click the Comm tab.
2. Click one of the two options under Protocol.
3. Click one of the two options under Parity.
4. Click one of the six options under Baud rate.

Characterizing and
Note: If you are communicating with the transmitter via

Calibrating
terminals 5 and 6, ProLink II software will lose
communication with the transmitter as soon as you complete
Step 5. Thereafter, you can change the ProLink II
communication settings and reestablish communication.
5. Click Apply.
Troubleshooting

Series 1000 and 2000 Transmitters 69


Changing the Transmitter Settings continued

4.18 HART® burst mode The following HART communication settings can be changed:
• Enable and disable burst mode
• Change burst-mode options
• Change the polling address

Enabling and disabling Burst mode is a specialized mode of communication during which
burst mode the primary mA output is fixed at 4 mA and the transmitter
regularly broadcasts HART digital information. Burst mode is
ordinarily disabled, and should be enabled only if another device on
the network requires HART burst-mode communication.
You can enable or disable HART burst mode with a HART
Communicator or ProLink II software.

With a HART Communicator


To enable or disable HART burst mode with a HART
Communicator:
1. Press 4, 3, 3.
2. Select “Burst Mode.”
3. If you want to enable burst mode, then select “On.”
4. If you want to disable burst mode, then select “Off.”
5. Press F4 “ENTER.”
6. Press F2 “SEND.”

With ProLink II software


To enable or disable HART burst mode with ProLink II software:
1. Click the Comm tab.
2. Click the Burst Mode checkbox. When the checkbox is selected,
burst mode is enabled.
3. Click Apply.

70 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

Changing the burst mode When the transmitter is in burst mode, it produces one of the
setting following outputs:
• PV—The transmitter repeats the primary variable (in
measurement units) in each burst (e.g., 14.0 g/s, 13.5 g/s, 12.0 g/s).
• % range/current—the transmitter sends the PV’s percent of range
and the PV’s actual mA level in each burst. (e.g., 25%, 11.0 mA).
• Process variables/current—the transmitter sends PV, SV, TV, and

Starting
quaternary variable (QV) in measurement units and the PV’s
actual milliamp reading in each burst (e.g., 50 lb/min, 23°C,
50 lb/min, 0.0023 g/cc, 11.8 mA).
You can change the burst-mode setting with a HART Communicator
or ProLink II software.

With a HART Communicator


To change the burst-mode setting with a HART Communicator:
1. Press 4, 3, 3.
2. Select “Burst option.”

Using
3. Select one of the three burst-mode settings.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the burst-mode setting with ProLink II software:
Note: Enable burst mode before you change the burst mode

Changing Settings
output. See Enabling and disabling burst mode, page 70.
1. Click the Comm tab.
2. Click the arrow next to Burst Option and select an item from the
drop-down list.
3. Click Apply.

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 71


Changing the Transmitter Settings continued

4.19 Changing the polling Polling addresses are integers assigned to transmitters to
address distinguish them from other devices on multidrop networks. Each
transmitter on a multidrop network must have a polling address
that is different from the polling addresses of other devices on the
network.
Transmitters that communicate using HART protocol can have
polling addresses of 0–15. Zero is a special-purpose polling address
that enables the primary mA output to vary according to the PV.
When a transmitter’s HART polling address is set to any value other
than zero, the primary mA output is fixed at 4 mA.
Transmitters that communicate using Modbus protocol can have
polling addresses of 1–15, 32–47, 64–79, or 96–110.
You can change the transmitter’s polling address with a HART
Communicator or ProLink II software.

With a HART Communicator


To change the transmitter’s polling address with a HART
Communicator:
1. Press 4, 3, 3.
2. Select “Poll addr.”
3. Type a new polling address.
4. Press F4 “ENTER.”
5. Press F2 “SEND.”

With ProLink II software


To change the transmitter’s polling address with ProLink II
software:
1. Click the Device tab.
2. Type a new polling address in the Address box.
Note: ProLink II software will lose communication with the
transmitter as soon as you complete Step 3. Thereafter, you
can change the ProLink II communication settings and
reestablish communication.
3. Click Apply.

72 Series 1000 and 2000 Transmitters


Installing
Changing the Transmitter Settings continued

4.20 Entering milliamp and The display uses a standard format and procedure for entering
frequency range values range values for either mA or frequency outputs.
with the display Enter range and scale values in scientific notation according to the
following format:

SX.XXXESY

Starting
Sign Exponent
For positive numbers, Enter the power
leave this space blank. Digits of 10 by which
For negative numbers, Enter a four-digit the digits will be
enter a dash (–). number; three digits Sign multiplied.
must fall to the right of E
the decimal point. Enter the
letter “E”.

Using
Example of range value format
The correct format for the number –810,000 is shown below:

–8.100E 5

To enter mA or frequency range values with the display:


Note: This procedure assumes that you are already at the
correct point in the display menu to begin entering the range

Changing Settings
values.
1. Press Scroll, if necessary, until the first space is either a dash (–)
for a negative number or a blank space for a positive number.
2. Press Select.
3. Press Scroll until the first digit is the correct number.
4. Press Select.
5. Press Scroll until the second digit is the correct number.
6. Press Select.

Characterizing and
7. Press Scroll until the third digit is the correct number.
8. Press Select.
9. Press Scroll until the fourth digit is the correct number. Calibrating
10. Press Select.
11. Press Scroll, if necessary, until the sign for the exponent is either
a dash (–) for a negative exponent or a blank space for a positive
exponent.
12. Press Select.
13. Press Scroll until the exponent is the correct power of ten.
14. Press Scroll and Select simultaneously for four seconds to exit.
Troubleshooting

Series 1000 and 2000 Transmitters 73


74 Series 1000 and 2000 Transmitters
Installing
5 Characterizing and Calibrating

If the sensor and transmitter were ordered together as a Coriolis


flowmeter, then the transmitter has already been characterized

Starting
for the sensor. Only perform the procedures described in this
Stop
section when the conditions under When to characterize and When
to calibrate are met.

5.1 Overview This section describes transmitter characterization and calibration


procedures. Using the procedures in this section, you will be able to:
• Characterize the flowmeter
• Calibrate the flowmeter

Using
Note: All HART Communicator key sequences in this section
assume that you are starting from the “Online” menu. See
Conventions used in this manual, page 108.
Note: All ProLink II procedures provided in this section
assume that your computer is already connected to the
transmitter and you have established communication. See
Using ProLink II Software, page 111.

Changing Settings
5.2 Characterizing the Characterizing the flowmeter adjusts the transmitter to compensate
flowmeter for the unique traits of the sensor it is paired with.

When to characterize If the transmitter and the sensor were ordered together as a Coriolis
flowmeter, then the flowmeter has already been characterized. You
need to characterize the flowmeter only if the transmitter and the
sensor are being paired together for the first time.

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 75


Characterizing and Calibrating continued

How to characterize Every sensor’s characterization data are printed on its factory tag.
See Figure 5-1.

Figure 5-1. Sample sensor factory tag

To characterize the flowmeter, you must enter data from the


sensor’s factory tag into the transmitter memory. You can
characterize the flowmeter with a HART Communicator or ProLink
II software.

With a HART Communicator


To characterize the flowmeter with a HART Communicator, first
select the appropriate sensor. Complete the following procedure to
select the sensor:
1. Press 4, 1.
2. Select “Sensor Selection.”
3. Select “T-Series.”
4. Press F4 “ENTER.”
Next, set each of the HART parameters to the values printed on the
sensor’s factory tag. See Figure 5-1. The HART Communicator
locations for each sensor tag name are listed in Table 5-1, page 77.

76 Series 1000 and 2000 Transmitters


Installing
Characterizing and Calibrating continued

Table 5-1. Characterization guide


Sensor factory tag name HART Communicator location
1
FCF and FT 4, 1, 2, FCF
FTG 4, 1, 2, FTG
FFQ 4, 1, 2, FFQ
D1 4, 1, 3, D1

Starting
K1 4, 1, 3, K1
D2 4, 1, 3, D2
K2 4, 1, 3, K2
DTG 4, 1, 3, DTG
DFQ1 4, 1, 3, DFQ1
DFQ2 4, 1, 3, DFQ2
DT 4, 1, 3, DT
FD 4, 1, 3, FD
1. FCF and FT consist of 10 characters that are labeled “FCF” and “FT” on

Using
the sensor tag. To characterize the flowmeter for FCF and FT, type the
six characters that appear after “FCF” and the four characters that
appear after “FT” on the sensor’s factory tag.

FCF and FT

Changing Settings
With ProLink II software
To characterize the flowmeter with ProLink II software:
1. Click the Density tab.
2. Type the K1 data from the sensor’s factory tag in the K1 box.
3. Type the K2 data from the sensor’s factory tag in the K2 box.
4. Type the FD data from the sensor’s factory tag in the K3 box.
5. Type the D1 data from the sensor’s factory tag in the D1 box.
6. Type the D2 data from the sensor’s factory tag in the D2 box.

Characterizing and
7. Type the DT data from the sensor’s factory tag in the Temp Coeff
Calibrating
box.
8. Click Apply.
9. Click the Flow tab.
10. Type the FCF and FT data from the sensor’s factory tag in the
Flow Cal box.
Note: FCF and FT data consist of 10 characters that are
labeled “FCF” and “FT” on the sensor’s factory tag. To
properly characterize the transmitter, enter all six characters
Troubleshooting

that appear after “FCF” followed by all four characters that


appear after “FT”.

Series 1000 and 2000 Transmitters 77


Characterizing and Calibrating continued

11. Click Apply.


12. Click the T Series Config tab.
13. Type the FTG data from the sensor’s factory tag in the FTG box.
14. Type the FFQ data from the sensor’s factory tag in the FFQ box.
15. Type the DTG data from the sensor’s factory tag in the DTG box.
16. Type the DFQ1 data from the sensor’s factory tag in the DFQ1
box.
17. Type the DFQ2 data from the sensor’s factory tag in the DFQ2
box.
18. Click Apply.

5.3 Calibrating the flowmeter The flowmeter measures process variables based on fixed points of
reference. Calibration adjusts those points of reference.

When to calibrate The transmitter is factory calibrated and does not normally need to
be calibrated in the field. Calibrate the transmitter only if you must
do so to meet regulatory requirements.

How to calibrate for Density calibration consists of three mandatory calibration points
density and two optional calibration points:
• Point one (low density)
• Point two (high density)
• Flowing density
• Optional D3 calibration
• Optional D4 calibration
You must perform all of the density calibration procedures in
sequence, without interruption, including the optional D3 and D4
calibrations if you choose to include them.

When to perform optional D3 or D4 calibration


The optional D3 and D4 calibration might improve the accuracy of
the density measurement. If the density measurement is critical at
high flow rates, or if the process fluid varies greatly in flow rate or
density, consider performing the D3 and D4 calibration.

78 Series 1000 and 2000 Transmitters


Installing
Characterizing and Calibrating continued

Density calibration with a Perform the following steps to calibrate the flowmeter for density
HART® Communicator with a HART Communicator.

Step 1: Point one (low-density calibration)


To perform a low-density calibration:
1. Close the shutoff valve downstream from the sensor.
2. Fill the sensor completely with a low-density fluid (e.g., air).

Starting
3. Press 2, 3.
4. Select “Density cal.”
5. Select “Dens Pt1.”
6. Select “Perform Cal.”
7. Type the density of the low-density fluid.
8. Press F4 “ENTER.”
9. Press F4 “OK” to begin the calibration.
10. Press F4 “OK” when the calibration is complete.

Using
11. Press F3 “HOME” and proceed to the high-density calibration
procedure.

Step 2: Point two (high-density calibration)


To perform a high-density calibration:
1. Close the shutoff valve downstream from the sensor.
2. Fill the sensor completely with a high-density fluid (e.g., water).

Changing Settings
3. Press 2, 3.
4. Select “Density cal.”
5. Select “Dens Pt2.”
6. Select “Perform Cal.”
7. Type the density of the high-density fluid.
8. Press F4 “ENTER.”
9. Press F4 “OK” to begin the calibration.
10. Press F4 “OK” when the calibration is complete.
11. Press F3 “HOME” and proceed to the flowing-density calibration

Characterizing and
procedure.

Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 79


Characterizing and Calibrating continued

Step 3: Flowing-density calibration


To perform a flowing-density calibration:
1. Press 2, 3.
2. Select “Density cal.”
3. Select “Flowing Dens (FD).”
4. Adjust process conditions so that the process flow rate is greater
than or equal to the appropriate flow rate that is listed in
Table 5-2, page 81. If the maximum flow rate for the process is
lower than the appropriate flow rate listed in Table 5-2, then the
flowing-density calibration should not be performed.
5. Select “Perform Cal.”
6. Type the density of the fluid.
7. Press F4 “ENTER.”
8. Press F4 “OK” to begin the calibration.
9. Press F4 “OK” when the calibration is complete.
10. Press F3 “HOME.”

80 Series 1000 and 2000 Transmitters


Installing
Characterizing and Calibrating continued

Table 5-2. Flowing density calibration minimum flow rates


Minimum flow rate Minimum flow rate
Sensor model in lb/min in kg/h
ELITE® sensor CMF010 2.5 69
CMF025 27 720
CMF050 86 2350

Starting
CMF100 280 7575
CMF200 1270 34,540
CMF300 4390 119,600
CMF400 15,000 409,000
T-Series sensor T075 500 13,630
T100 1100 29,990
T150 3500 95,430
F-Series sensor F200 2315 63,045
All other F-Series sensors Flowing density calibration not necessary

Using
Model D sensor D6 0.8 25
D12 4.5 125
D25 18 485
D40 stainless steel 33 900
®
D40 Hastelloy C-22 52 1395
D65 115 3060
D100 405 11,010

Changing Settings
D150 1140 31,050
D300 2705 73,660
D600 9005 245,520
Model DH sensor All DH sensors Flowing density calibration not necessary
Model DL sensor DL65 115 3075
DL100 325 8,780
DL200 1210 32,950
Model DT sensor DT65 150 4040
DT100 315 8460

Characterizing and
DT150 580 15,780

Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 81


Characterizing and Calibrating continued

Step 4: Optional D3 calibration


You may perform a D3 calibration, a D4 calibration, or both
calibrations.
• The minimum density of the D3 or D4 fluid is 0.6 g/cc.
• The difference between the density of the D3 calibration fluid and
the fluid that was used to perform the high-density calibration
must be at least 0.1 g/cc.
• The difference between the density of the D4 calibration fluid and
the fluid that was used to perform the high-density calibration
must be at least 0.1 g/cc.
• If D3 and D4 density calibrations are performed, the difference
between the densities of the D3 and D4 calibration fluids must be
at least 0.1 g/cc.
To perform the optional D3 calibration:
1. Close the shutoff valve downstream from the sensor.
2. Fill the sensor completely with a fluid with a known density.
3. Press 2, 3.
4. Select “Density cal.”
5. Select “Dens Pt3 T-series.”
6. Select “Perform Cal.”
7. Type the density of the fluid.
8. Press F4 “ENTER.”
9. Press F4 “OK” to begin the calibration.
10. Press F4 “OK” when the calibration is complete.
11. Press F3 “HOME.”

82 Series 1000 and 2000 Transmitters


Installing
Characterizing and Calibrating continued

Step 5: Optional D4 calibration


You may perform a D3 calibration, a D4 calibration, or both
calibrations.
• The minimum density of the D3 or D4 fluid is 0.6 g/cc.
• The difference between the density of the D3 calibration fluid and
the fluid that was used to perform the high-density calibration
must be at least 0.1 g/cc.

Starting
• The difference between the density of the D4 calibration fluid and
the fluid that was used to perform the high-density calibration
must be at least 0.1 g/cc.
• If D3 and D4 density calibrations are performed, the difference
between the densities of the D3 and D4 calibration fluids must be
at least 0.1 g/cc.
To perform the optional D4 calibration:
1. Close the shutoff valve downstream from the sensor.
2. Fill the sensor completely with a fluid with a known density.

Using
3. Press 2, 3.
4. Select “Density cal.”
5. Select “Dens Pt4 T-series.”
6. Select “Perform Cal.”
7. Type the density of the fluid.
8. Press F4 “ENTER.”
9. Press F4 “OK” to begin the calibration.

Changing Settings
10. Press F4 “OK” when the calibration is complete.
11. Press F3 “HOME.”

Density calibration with Perform the following procedures to calibrate the flowmeter for
ProLink II™ software density with ProLink II software.

Step 1: Point one (low-density calibration)


To perform a low-density calibration:

Characterizing and
1. Select Density Cal - Point 1 from the Calibrate menu.

Calibrating
2. Close the shutoff valve downstream from the sensor.
3. Fill the sensor completely with a low-density fluid (e.g., air).
4. Type the density of the low-density fluid in the Enter box.
5. Click Do Cal.
6. If a dialog box appears containing a reason for failure, then the
calibration procedure has failed. See Checking the calibration,
page 96.
7. Read the results of the calibration in the K1 box.
8. Click Done and proceed to the high-density calibration procedure.
Troubleshooting

Series 1000 and 2000 Transmitters 83


Characterizing and Calibrating continued

Step 2: Point two (high-density calibration)


To perform a high-density calibration:
1. Select Density Cal - Point 2 from the Calibrate menu.
2. Close the shutoff valve downstream from the sensor.
3. Fill the sensor completely with a high-density fluid (e.g., water).
4. Type the density of the fluid in the Enter box.
5. Click Do Cal.
6. If a dialog box appears containing a reason for failure, then the
calibration procedure has failed. See Checking the calibration,
page 96.
7. Read the results of the calibration in the K2 box.
8. Click Done and proceed to the flowing-density calibration
procedure.

Step 3: Flowing-density calibration


To perform a flowing-density calibration:
1. Select Density Cal - Flowing Density from the Calibrate menu.
2. Adjust process conditions so that the process flow is greater than
or equal to the appropriate flow rate that is listed in Table 5-2,
page 81. If the maximum flow rate for the process is lower than
the appropriate flow rate listed in Table 5-2, then the
flowing-density calibration should not be performed.
3. Type the density of the fluid in the Enter box.
4. Click Do Cal.
5. If a dialog box appears containing a reason for failure, then the
calibration procedure has failed. See Checking the calibration,
page 96.
6. Read the results of the calibration in the FD box.
7. Click Done.

84 Series 1000 and 2000 Transmitters


Installing
Characterizing and Calibrating continued

Step 4: Optional D3 calibration


You may perform a D3 calibration, a D4 calibration, or both
calibrations.
• The minimum density of the D3 or D4 fluid is 0.6 g/cc.
• The difference between the density of the D3 calibration fluid and
the fluid that was used to perform the high-density calibration
must be at least 0.1 g/cc.

Starting
• The difference between the density of the D4 calibration fluid and
the fluid that was used to perform the high-density calibration
must be at least 0.1 g/cc.
• If D3 and D4 density calibrations are performed, the difference
between the densities of the D3 and D4 calibration fluids must be
at least 0.1 g/cc.
To perform an optional D3 calibration with ProLink II software:
1. On the ProLink menu, point to Calibration then select
Density Cal - Point 3.
2. Close the shutoff valve downstream from the sensor.

Using
3. Fill the sensor completely with a fluid of known density
4. Type the density of the fluid in the Enter box.
5. Click Do Cal.
6. If a dialog box appears containing a reason for failure, then the
calibration procedure has failed. See Zero or calibration failure,
page 89.
7. Read the results of the calibration in the K3 box.

Changing Settings
8. Click Done.

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 85


Characterizing and Calibrating continued

Step 5: Optional D4 calibration


You may perform a D3 calibration, a D4 calibration, or both
calibrations.
• The minimum density of the D3 or D4 fluid is 0.6 g/cc.
• The difference between the density of the D3 calibration fluid and
the fluid that was used to perform the high-density calibration
must be at least 0.1 g/cc.
• The difference between the density of the D4 calibration fluid and
the fluid that was used to perform the high-density calibration
must be at least 0.1 g/cc.
• If D3 and D4 density calibrations are performed, the difference
between the densities of the D3 and D4 calibration fluids must be
at least 0.1 g/cc.
To perform an optional D4 calibration with ProLink II software:
1. On the ProLink menu, point to Calibration then select
Density Cal - Point 4.
2. Close the shutoff valve downstream from the sensor.
3. Fill the sensor completely with a fluid of known density.
4. Type the density of the fluid in the Enter box.
5. Click Do Cal.
6. If a dialog box appears containing a reason for failure, then the
calibration procedure has failed. See Zero or calibration failure,
page 89.
7. Read the results of the calibration in the K4 box.
8. Click Done.

86 Series 1000 and 2000 Transmitters


Installing
Characterizing and Calibrating continued

How to calibrate for Temperature calibration is a two-point procedure. The entire


temperature procedure must be completed without interruption.
You can calibrate for temperature with ProLink II software.

Temperature calibration To calibrate for temperature with ProLink II software:


with ProLink II™ software 1. On the ProLink menu, point to Calibration then select

Starting
Temp Offset Cal.
2. Fill the sensor with a low-temperature fluid, and allow the sensor
to achieve thermal equilibrium.
3. Type the temperature of the low-temperature fluid in the Enter
box.
4. Click Do Cal.
5. If a dialog box appears containing a reason for failure, then the
calibration procedure has failed. See Zero or calibration failure,
page 89.
6. Read the results of the calibration in the Measured Temp box.

Using
7. Click Done.
8. On the ProLink menu, point to Calibration then select Temp
Slope Cal.
9. Fill the sensor with a high-temperature fluid, and allow the
sensor to achieve thermal equilibrium.
10. Type the temperature of the high-temperature fluid in the Enter
box.

Changing Settings
11. Click Do Cal.
12. If a dialog box appears containing a reason for failure, then the
calibration procedure has failed. See Zero or calibration failure,
page 89.
13. Read the results of the calibration in the Measured Temp box.
14. Click Done.

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 87


88 Series 1000 and 2000 Transmitters
Installing
6 Troubleshooting

6.1 Overview This section describes guidelines and procedures for troubleshooting
the flowmeter. The information in this section will enable you to:

Starting
• Categorize the problem
• Determine whether you are able to correct the problem
• Take corrective measures (if possible)
• Contact the appropriate support agency
Note: All HART Communicator key sequences in this section
assume that you are starting from the “Online” menu. See
Conventions used in this manual, page 108.
Note: All ProLink II procedures provided in this section
assume that your computer is already connected to the
transmitter and you have established communication. See

Using
Using ProLink II Software, page 111.

6.2 Transmitter does not If the transmitter does not operate at all (i.e., the transmitter is not
operate receiving power and cannot communicate over the HART network or
the display), then perform all of the procedures under Diagnosing
wiring problems, page 94.
If the procedures do not indicate a problem with the electrical

Changing Settings
connections, contact the Micro Motion Customer Service
Department. See Contacting customer service, page 98.

6.3 Transmitter does not If the transmitter does not appear to be communicating on the
communicate HART network, then the network wiring may be faulty. Perform the
procedures under Checking the communication loop, page 94.

6.4 Zero or calibration failure If a zero or calibration procedure fails, the transmitter will send a
status alarm indicating the cause of failure. See Status alarms,

Characterizing and
page 91, for specific remedies for status alarms indicating
calibration failure.
Calibrating

6.5 HART® output problems HART output problems include inconsistent or unexpected behavior
that does not trigger status alarms. For example, the HART
Communicator might show incorrect units of measure or respond
sluggishly. If you experience HART output problems, verify that the
transmitter configuration is correct.
If you discover that the configuration is incorrect, change the
necessary transmitter settings. See Changing the Transmitter
Troubleshooting

Settings, page 35, for the procedures to change the appropriate


transmitter settings.

Series 1000 and 2000 Transmitters 89


Troubleshooting continued

If you confirm that all the settings are correct, but the unexpected
outputs prevail, then the transmitter or sensor could require service.
See Contacting customer service, page 98.

6.6 Analog output problems If you are experiencing problems with the analog outputs (frequency
or mA), use Table 6-1 to identify an appropriate remedy.

Table 6-1. Analog output problems and remedies


Symptom Possible cause Possible remedy
No mA output and Power supply problem Check power supply and power-supply wiring.
no frequency output or loop See page 94.
test failed
Fault condition present if fault outputs Check the fault output settings to verify
are set to downscale or internal zero whether or not the transmitter is in a fault
condition. See page 62 to check the mA fault
output or page 66 to check the frequency fault
output.
If a fault condition is present, then see page 91.
No mA output Fault condition if fault output is set to Check the fault output settings to verify
internal zero whether or not the transmitter is in a fault
condition. See page 62.
If a fault condition is present, then see page 91.
Bad mA receiving device Check the mA receiving device or try another
mA receiving device. See page 95.
No frequency output Actual flow is below low-flow cutoff Verify or change the low-flow cutoff. See
page 51.
Fault condition if fault output is set to Check the fault output settings to verify
downscale or internal zero whether or not the transmitter is in a fault
condition. See page 66.
If a fault condition is present, then see page 91.
Bad frequency receiving device Check the frequency receiving device or try
another frequency receiving device. See
page 95.
Constant 4 mA output Transmitter is set to multidrop (digital Set HART polling address to zero. See
only) communication page 95.
mA output consistently out Fault condition if fault output is set to Check the fault output settings to verify
of range upscale or downscale whether or not the transmitter is in a fault
condition. See page 62.
If a fault condition is present, then see page 91.
LRV and URV not set correctly Check the LRV and URV. See page 95.
Consistently incorrect mA Output not trimmed correctly Trim the output. See page 19.
measurement
LRV and URV not set correctly Check the LRV and URV. See page 95.
Consistently incorrect Output not scaled correctly Check frequency output scale and method.
frequency measurement See page 95.

90 Series 1000 and 2000 Transmitters


Installing
Troubleshooting continued

Fault conditions If the analog outputs indicate a fault condition (by reporting a fault
output), determine the exact nature of the fault by checking the
status alarms with a HART Communicator, the display, or ProLink
II software. Once you have identified the status alarm(s) associated
with the fault condition, refer to Status alarms.

6.7 Status alarms Status alarms are reported by a HART Communicator, the display,

Starting
and ProLink II software. Remedies for the alarm states appear in
Table 6-2, page 91.

Table 6-2. Status alarms and remedies


Display HART
code Communicator ProLink II software Possible remedy
A1 EEPROM EEPROM Checksum The flowmeter needs service. Contact Micro
Checksum—Core Motion. See page 98.
Processor
A2 RAM Error—Core RAM Error Cycle power to the flowmeter.

Using
Processor
The flowmeter might need service. Contact Micro
Motion. See page 98.
A3 Sensor failure Sensor Failure Check the test points. See page 96.
A4 Temperature out of Temperature Check the test points. See page 96.
range Overrange
A5 Input over range Input Overrange Check the test points. See page 96.
A6 Field device not Not Configured Check the characterization. Specifically, verify the
characterized FCF and K1 values. See page 95.

Changing Settings
If the problem persists, contact Micro Motion. See
page 98.
A7 Real time interrupt RTI Failure The transmitter needs service. Contact Micro
failure Motion. See page 98.
A8 Density outside limits Density Overrange Check the test points. See page 96.
A9 Field device warming Transmitter Initializing Allow the flowmeter to warm up. The error should
up disappear once the flowmeter is ready for normal
operation.
A10 Calibration failed Calibration Failure Cycle power to the flowmeter, then retry calibrating
the transmitter. See page 96.

Characterizing and
A11 Excess calibration Zero too Low Cycle power to the flowmeter, then retry calibrating
correction, zero too low the transmitter. See page 96.

Calibrating
A12 Excess calibration Zero too High Cycle power to the flowmeter, then retry calibrating
correction, zero too the transmitter. See page 96.
high
A13 Process too noisy to Zero too Noisy Remove or reduce sources of electromechanical
perform auto zero noise, then attempt the calibration or zero
procedure again.
Sources of noise include:
• Mechanical pumps
• Electrical interference
• Vibration effects from nearby machinery
Troubleshooting

A14 Electronics failure Transmitter Fail The flowmeter needs service. Contact Micro
Motion. See page 98.

Series 1000 and 2000 Transmitters 91


Troubleshooting continued

Table 6-2. Status alarms and remedies (continued)


Display HART
code Communicator ProLink II software Possible remedy
A15 Data loss possible Data Loss Possible Cycle power to the flowmeter.
View the entire current configuration to determine
what data was lost. Configure any settings with
missing or incorrect data.
The transmitter might need service. Contact Micro
Motion. See page 98.
A16 Line RTD Overrange Temperature Check the test points. See page 96.
Overrange
A17 Case RTD Overrange Temperature Check the test points. See page 96.
Overrange
A18 EEPROM Checksum— EEPROM Checksum The flowmeter needs service. Contact Micro
1000/2000 Motion. See page 98.
A19 RAM Error— RAM Error Cycle power to the flowmeter.
1000/2000
The transmitter might need service. Contact Micro
Motion. See page 98.
A20 Calibration Factor Not Configured Check the characterization. Specifically, verify the
Unentered (Flocal) FCF value. See page 76.
A21 Unrecognized/Unenter Not Configured Check the characterization. Specifically, verify the
ed Sensor Type (K1) K1 value. See page 76.
A22 EEPROM Config EEPROM Checksum The flowmeter needs service. Contact Micro
Corrupt–Core Motion. See page 98.
Processor
A23 EEPROM Totals EEPROM Checksum The flowmeter needs service. Contact Micro
Corrupt–Core Motion. See page 98.
Processor
A24 EEPROM Program EEPROM Checksum The flowmeter needs service. Contact Micro
Corrupt–Core Motion. See page 98.
Processor
A25 Core Processor Boot Transmitter Fail The flowmeter needs service. Contact Micro
Sector Fault Motion. See page 98.
A26 Sensor/Xmtr Sensor Failure Check the wiring between the transmitter and the
Communication Error core processor. The wires may be swapped. See
page 6.
A100 Analog output 1 Analog 1 Saturated Change the mA output scale. See page 59.
saturated
A101 Analog output 1 fixed Analog 1 Fixed Check the HART polling address. See page 95.
Be advised that a loop test is in progress.
A102 Drive over range Drive Overrange Excessive drive gain. See page 97.
A103 Data loss possible Data Loss Possible Cycle power to the flowmeter.
View the entire current configuration to determine
what data were lost. Configure any settings with
missing or incorrect data.
The transmitter might need service. Contact Micro
Motion. See page 98.
A104 Calibration in progress Calibration in Progress Allow the flowmeter to complete calibration.

92 Series 1000 and 2000 Transmitters


Installing
Troubleshooting continued

Table 6-2. Status alarms and remedies (continued)


Display HART
code Communicator ProLink II software Possible remedy
A105 Slug flow Slug Flow Allow the slug flow to clear from the process.
Adjust slug-flow limits and duration to prevent
future error. See page 48.
A106 Burst mode enabled Burst Mode No action required.

Starting
A107 Power reset occurred Power Reset No action required.
A108 Event 1 triggered Event 1 On Be advised of alarm condition.
If you believe the event has been triggered
erroneously, verify the Event 1 settings. See
page 45.
A109 Event 2 triggered Event 2 On Be advised of alarm condition.
If you believe the event has been triggered
erroneously, verify the Event 2 settings. See
page 45.
A110 Frequency over range Frequency Saturated Change the frequency output. See page 63.

Using
A111 Freq output fixed Frequency Fixed Be advised that a loop test is in progress.
A112 Series 1000/2000 NA Contact Micro Motion to get a Series 1000/2000
software upgrade transmitter software upgrade. See page 98. Note
recommended that the device is still functional.
NA Density FD cal in NA Be advised that density calibration is in progress.
progress
NA Density 1st point cal in NA Be advised that density calibration is in progress.
progress

Changing Settings
NA Density 2nd point cal in NA Be advised that density calibration is in progress.
progress
NA Density 3rd point cal in NA Be advised that density calibration is in progress.
progress
NA Density 4th point cal in NA Be advised that density calibration is in progress.
progress
NA Mech. zero cal in NA Be advised that zero calibration is in progress.
progress
NA Flow is in reverse NA Be advised that the process is flowing in reverse
direction direction.

Characterizing and
Calibrating
Troubleshooting

Series 1000 and 2000 Transmitters 93


Troubleshooting continued

6.8 Diagnosing wiring Use the procedures under the following headings to check the
problems transmitter installation for wiring problems.

Checking the power-supply To check the power-supply wiring:


wiring

WARNING
Removing the wiring compartment covers in
explosive atmospheres while the power is on can
cause an explosion.

Do not remove the field wiring compartment cover in


explosive atmospheres before shutting off the power and
waiting the required delay time as indicated on the
transmitter housing.

1. Open the field-wiring compartment cover.


2. Inspect the voltage label on the inside of the field-wiring
compartment. Verify that the voltage supplied to the transmitter
matches the voltage specified on the label.
3. Use a voltmeter to test the voltage at the power-supply terminals.
4. Verify that the power-supply wires are making good contact with
the power-supply terminals.

Checking the core To check the core processor-to-transmitter wiring, verify that:
processor-to-transmitter • The transmitter is connected to the core processor according to the
wiring wiring information beginning on page 1.
• The wires are making good contact with the terminals.

Checking the To check the communication loop, verify that the loop wires are
communication loop connected as shown in the wiring diagrams on pages 9–11.
If your HART network is more complex than the wiring diagrams on
pages 9–11, either:
• Contact the Micro Motion Customer Service Department. See
page 98.
• Contact the HART Communication Foundation or refer to the
HART Application Guide, available from the HART
Communication Foundation on the Internet at:
http://www.hartcomm.org

94 Series 1000 and 2000 Transmitters


Installing
Troubleshooting continued

6.9 Checking the receiving If you receive an inaccurate frequency or mA reading, you might be
device using a faulty receiving device. Use a different receiving device to
confirm that the mA or frequency reading you are receiving is
accurate. Another receiving device will help you determine if the
problem exists in the receiving device or in the transmitter.

6.10 Setting the HART® polling If the HART polling address is set to a nonzero number, or if the

Starting
address to zero transmitter is in burst mode, the mA output is fixed at 4 mA. If the
polling address is changed to zero and the transmitter is not in burst
mode, the mA output will report the primary variable on a 4–20 mA
scale. See Changing the polling address, page 72 and Enabling and
disabling burst mode, page 70.

6.11 Checking the upper and A saturated mA output or incorrect mA measurement could indicate
lower range values a faulty URV or LRV. Verify that the URV and LRV are correct and
change them if necessary. See Changing the upper range value and
Changing the lower range value, page 61.

Using
6.12 Checking the frequency A saturated frequency output or an incorrect frequency
output scale and method measurement could indicate a faulty frequency output scale and/or
method. Verify that the frequency output scale and method are
correct and change them if necessary. See Changing the output
scale, page 63.

Changing Settings
6.13 Checking the A flowmeter that is incorrectly characterized for its sensor might
characterization produce inaccurate output values. If the flowmeter appears to be
operating correctly but sends inaccurate output values, then an
incorrect characterization could be the cause.
To verify the characterization with a HART Communicator:
1. Press 5.
2. Select “Charize sensor.”
3. Press F3 “NEXT” to scroll through the list of characterization
data.

Characterizing and
4. Compare the characterization data to the characterization data

Calibrating
on the sensor’s factory tag.
5. Press F4 “EXIT.”
If you discover that any of the characterization data are wrong, then
perform a complete characterization. See How to characterize,
page 76.
Troubleshooting

Series 1000 and 2000 Transmitters 95


Troubleshooting continued

6.14 Checking the calibration Improper calibration can cause the transmitter to send unexpected
output values. If the transmitter appears to be operating correctly
but sends inaccurate output values, then an improper calibration
may be the cause.
Micro Motion calibrates every transmitter at the factory. Therefore,
you should only suspect improper calibration if the transmitter has
been calibrated after it was shipped from the factory.
The calibration procedures in this manual are designed for
calibration to a regulatory standard. See Calibrating the flowmeter,
page 78. To calibrate for true accuracy, always use a measurement
source that is more accurate than the flowmeter. Contact the Micro
Motion Customer Service Department for assistance. See Contacting
customer service, page 98.

6.15 Checking the test points Some status alarms that indicate a sensor failure or overrange
condition can be caused by problems other than a failed sensor. You
can diagnose sensor failure or overrange status alarms by checking
the flowmeter test points. The test points include left and right
pickoff voltages, drive gain, and tube frequency.

Obtaining the test points You can obtain the test points with a HART Communicator or
ProLink II software.

With a HART Communicator


To obtain the test points with a HART Communicator:
1. Press 2, 6.
2. Select “Drive.”
3. Write down the drive gain.
4. Press F4.
5. Select “LPO.”
6. Write down the left pickoff voltage.
7. Press F4.
8. Select “RPO.”
9. Write down the right pickoff voltage.
10. Press F4.
11. Select “Tube Frequency.”
12. Write down the tube frequency.

With ProLink II software


To obtain the test points with ProLink II software:
1. Select Diagnostic Information from the Prolink menu.
2. Write down the value you find in the Tube Frequency box, the
Left Pickoff box, the Right Pickoff box, and the Drive Gain box.

96 Series 1000 and 2000 Transmitters


Installing
Troubleshooting continued

Evaluating the test points Use the following guidelines to evaluate the test points:
• If the drive gain is unstable, refer to Excessive drive gain.
• If the value for the left or right pickoff does not equal the
appropriate value from Table 6-3, based on the sensor flow tube
frequency, refer to Bad pickoff voltage.
• If the values for the left and right pickoffs equal the appropriate
values from Table 6-3, based on the sensor flow tube frequency,

Starting
contact the Micro Motion Customer Service Department for
assistance. See Contacting customer service, page 98.

Table 6-3. Sensor pickoff values


Sensor model Pickoff value
®
ELITE Model CMF sensors 3.4 mV per Hz based on sensor flow tube frequency
Model D, DL, and DT sensors 3.4 mV per Hz based on sensor flow tube frequency
®
Micro Motion F-Series sensors 3.4 mV per Hz based on sensor flow tube frequency
Model R025, R050, or R100 sensor 3.4 mV per Hz based on sensor flow tube frequency

Using
Model R200 sensor 2.0 mV per Hz based on sensor flow tube frequency
Micro Motion T-Series sensors 0.5 mV per Hz based on sensor flow tube frequency

Excessive drive gain Excessive drive can be caused by several problems. See Table 6-4.

Table 6-4. Excessive drive gain causes and solutions


Cause Solution

Changing Settings
Excessive slug flow Eliminate slugs.
Change the sensor orientation.
Plugged flow tube Purge the flow tubes.
Cavitation or flashing Increase inlet or back pressure at the
sensor.
If a pump is located upstream from
the sensor, increase the distance
between the pump and sensor.
Drive board or module failure, Contact Micro Motion. See page 98.
cracked flow tube, or sensor

Characterizing and
imbalance

Calibrating
Erratic drive gain Erratic drive gain can be caused by several problems. See Table 6-5.

Table 6-5. Erratic drive gain causes and solutions


Cause Solution
Wrong K1 characterization constant Re-enter the K1 characterization
for sensor constant. See page 76.
Polarity of pick-off reversed or Contact Micro Motion. See page 98.
polarity of drive reversed
Troubleshooting

Series 1000 and 2000 Transmitters 97


Troubleshooting continued

Bad pickoff voltage Bad pickoff voltage can be caused by several problems. See
Table 6-6.

Table 6-6. Bad pickoff voltage causes and solutions


Cause Solution
Faulty wiring runs between the Refer to the sensor manual.
sensor and core processor.
The process flow rate is beyond Verify that the process flow rate is not out
the limits of the sensor. of range of the sensor.
There is moisture in the sensor Eliminate the moisture in the sensor
electronics. electronics.
The sensor is damaged. Contact Micro Motion. See page 98.

6.16 Contacting customer For technical assistance, contact the Micro Motion Customer Service
service Department at:
• 1-800-522-6277 in the United States, 24 hours
• 303-530-8400 outside the United States, 24 hours
• +31 (0) 318 549 443 in Europe
• (65) 770-8155 in Asia

98 Series 1000 and 2000 Transmitters


Appendix A Specifications

A.1 Functional specifications The transmitter’s functional specifications include:


• Electrical connections
• Input/output signals
• Digital communications
• Power supply
• Environmental requirements
• Electromagnetic interference (EMI) effects

Electrical connections Input and output connections


The transmitter has the following input and output connections:
• Three pairs of wiring terminals for transmitter outputs
• Screw terminals accept one or two solid conductors, 14 to 12 AWG
(2.5 to 4 mm2); or one or two stranded conductors, 22 to 14 AWG
(0.34 to 2.5 mm2)

Power connection
The transmitter has the following power connection:
• One pair of wiring terminals accepts either AC or DC power
• One internal ground lug for power-supply ground wiring
• Screw terminals accept one or two solid conductors, 14 to 12 AWG
(2.5 to 4 mm2); or one or two stranded conductors, 22 to 14 AWG
(0.34 to 2.5 mm2)

Service port connection


The transmitter has two clips for temporary connection to the
service port.

Series 1000 and 2000 Transmitters 99


Specifications continued

Input/output signals The transmitter communicates using the following input and output
methods:
• One 4-wire sensor signal input connection with ground,
intrinsically safe
• One active 4-20 mA output
- Not intrinsically safe
- Isolated to ±50 VDC from all other outputs and earth ground
- Maximum load limit, 600 ohms
- Can report mass flow, volume flow, density, or temperature
- Output is linear with process from 3.8 to 20.5 mA, per NAMUR
NE43 (June 1994)
• One active frequency/pulse output
- Not intrinsically safe
- Can report mass flow or volume flow, which can be used to
indicate flow rate or total
- For Series 1000, output is dependent on mA output; for Series
2000, output is independent
- Scalable to 10,000 Hz
- Maximum output of 30 VDC max., 24 VDC typical
- Internal 2.2 kohm pull-up
- Output is linear with flow rate to 12,500 Hz

Digital communications The transmitter has the following digital communications ports:
• One service port can be used for temporary connection only
• Uses RS-485 Modbus signal, baud rate of 38.4 kilobaud, one stop
bit, no parity
• HART Bell 202 signal is superimposed on the primary milliamp
output, and is available for host system interface
- Frequency 1.2 and 2.2 kHz
- Amplitude 0.8 V peak-to-peak
- 1200 baud
- Requires 250 to 600 ohms load resistance
• One RS-485 output can be used for direct connection to a HART or
Modbus host system, which accepts baud rates between 1200 baud
and 38.4 kilobaud

Power supply The power supply switches automatically to accept AC or DC power:


• 18–100 VDC or 85–250 VAC 50/60 Hz:
- 9 W maximum power
- 1.25 A slow-blow fuse
- Complies with low-voltage directive 73/23/EEC per IEC 1010-1
with Amendment 2
- Installation (Overvoltage) Category II, Pollution Degree 2

100 Series 1000 and 2000 Transmitters


Specifications continued

Environmental Environmental requirements include ambient temperature limits:


requirements • Ambient temperature limits between –35 and 140°F (–37- 60°C)
- Some darkening of the display may occur above 131 °F (55 °C)
- Display responsiveness decreases below –4 °F (20 °C)

Electromagnetic The transmitter meets the following EMI effects standards:


interference effects • Series 1000 and 2000 transmitters conform to NAMUR NE21
(June 1997)
• Series 1000 and 2000 transmitters meet EMC directive
89/336/EEC per EN 50081-2 (August 1993) and EN 50082-2
(March 1995), and EN 61326 Industrial

A.2 Hazardous area The transmitter may have a tag listing hazardous area
classifications classifications, which indicate compliance with the standards listed
below.

UL and CSA UL and CSA marked transmitters comply to the following


standards:
• Transmitter: Class I, Div. 1, Groups C and D. Class II, Div. 1,
Groups E, F, and G explosion proof (when installed with approved
conduit seals). Otherwise, Class I, Div. 2, Groups A, B, C, and D.
• Outputs: Provides nonincendive sensor outputs for use in Class I,
Div. 2, Groups A, B, C, and D; or intrinsically safe sensor outputs
for use in Class I, Div. 1, Groups C and D or Class II, Div. 1, Groups
E, F, and G.

CENELEC compliance Transmitters with the CENELEC-compliant tag are suitable for
installation in hazardous areas as follows:
• Flameproof when installed with approved cable glands:
- with display EEx d [ib] IIB+H2 T6
- without display EEx d [ib] IIB T6
• Increased safety when installed with approved cable glands:
- with display EEx de [ib] IIB+H2 T6
- without display EEx de [ib] IIB T6

A.3 Performance The performance specifications below apply when used with Micro
specifications Motion T-Series sensors on liquids and slurries only.

Flow
• Accuracy ±0.15% ± [(zero stability/flow rate) x 100]% of rate
• Repeatability ±0.05% ± [½(zero stability/flow rate) x 100]% of rate

Series 1000 and 2000 Transmitters 101


Specifications continued

Note: Flow accuracy includes the combined effects of


repeatability, linearity, and hysteresis. All specifications are
based on reference conditions of water at 68 to 77°F (20 to
25°C), and 15 to 30 psig (1 to 2 bar) unless otherwise noted.
For values of zero stability, refer to product specifications for
each sensor.

Density
• Accuracy ±0.002 g/cc (±2.0 kg/m3)
• Repeatability ±0.0005 g/cc (±0.5 kg/m3)

Temperature
• Accuracy ±1°C ± 0.5% of reading in °C
• Repeatability ±0.2°C

A.4 Physical specifications The physical specifications of the transmitter include:


• Field-mount housing
• Mounting
• Interface/display
• Weight

Field-mount housing The characteristics of the field-mount transmitter housing are as


follows:
• NEMA 4X (IP67) epoxy-painted cast aluminum housing
• Terminal compartment contains output terminals, power
terminals and service-port terminals. The output terminals are
physically separated from the power- and service-port terminals.
- The electronics compartment contains all electronics and the
standard display.
- The sensor compartment contains the wiring terminals for
connection to the core processor on the sensor.
• Screw-terminal on housing for chassis ground
• Cable gland entrances are either ½-14 NPT or M20 x 1.5 female
conduit ports

Mounting Model 1700 and 2700 field-mount transmitters are available


integrally mounted to Micro Motion T-Series sensors, or in a
remote-mount configuration.
• Remote-mount transmitters include a mounting bracket, and
require standard 4-wire signal cable, up to 1000 feet (300 meters)
in length, between the sensor and the transmitter. Hardware for
installing the transmitter on the mounting bracket is included.
• The transmitter can be rotated on the sensor or the mounting
bracket, 360 degrees, in 90-degree increments.

102 Series 1000 and 2000 Transmitters


Specifications continued

Interface/display The characteristics of the display are as follows:


• Segmented 2-line display with LCD screen with optical controls
and flowmeter-status LED is standard and is suitable for
hazardous area installation.
• To facilitate various mounting orientations, the display can rotate
360° on the transmitter in 90° increments.
- LCD line 1 lists the process variable, line 2 lists engineering
unit of measure through a non-glare tempered glass lens.
- Display controls feature optical switches that are operated
through the glass with a red LED visual-feedback to confirm
when a “button” is pressed.

Display functions
The display supports the following functions:
• Operational: view process variables; start, stop, and reset
totalizers
• Off-line: view diagnostic messages, zero flowmeter, initiate output
simulation and diagnostic self-check

Status light
Three-color LED status light on display panel indicates flowmeter
condition at a glance. A green, yellow, or red status light, either
continuously on or blinking, immediately indicates flowmeter status.

Weight The weight of the transmitter is as follows:


• 2 lb (1 kg)
• For weight of integrally mounted transmitter and sensor, refer to
sensor specifications.

Dimensions Figure A-1, page 104, and Figure A-2, page 105 show the
transmitter and core processor assembly’s dimensions. For
dimensions of integrally mounted transmitters and sensors, refer to
sensor specifications.

Series 1000 and 2000 Transmitters 103


Specifications continued

Figure A-1. Remote mount transmitter dimensions

Dimensions in inches
(mm)

104 Series 1000 and 2000 Transmitters


Specifications continued

Figure A-2. Remote mount transmitter and core processor assembly dimensions

Dimensions in inches
(mm)

Series 1000 and 2000 Transmitters 105


106 Series 1000 and 2000 Transmitters
Appendix B Using the HART® Communicator

B.1 Overview The instructions in this manual assume that users are already
familiar with the HART Communicator and can perform the
following tasks:
• Turn on the HART Communicator
• Navigate the HART Communicator menus
• Establish communication with HART-compatible devices
• Transmit and receive configuration information between the
HART Communicator and HART-compatible devices
• Use the alpha keys to type information

B.2 Connecting the HART® You can connect the HART Communicator directly to the
Communicator transmitter’s HART/mA terminals or to a point on a HART network.

Connecting to To connect the HART Communicator directly to the transmitter’s


communication terminals communication terminals:
1. Open the cover to the intrinsically safe wiring compartment.
Note: The HART Communicator must be connected across a
resistance of 250–600 Ω . Add resistance to the connection.
2. Connect the HART Communicator leads to transmitter terminals
1 and 2. See Figure B-1.

Figure B-1. Connecting to communication terminals


250–600 Ω resistance

HART Communicator

Series 1000 and 2000 Transmitters 107


Using the HART® Communicator continued

Connecting to a multidrop The HART Communicator can be connected to any point in a


network multidrop network. See Figure B-2.
Note: The HART communicator must be connected across a
resistance of 250–600 Ω . Add resistance to the connection if
necessary.

Figure B-2. Connecting to a multidrop network

Master
device

250–600 Ω
resistance (if
necessary)

Transmitters
HART Communicator

B.3 Conventions used in this All HART Communicator procedures assume that you are starting
manual at the on-line menu. “Online” appears on the top line of the HART
Communicator main menu when the HART Communicator is at the
on-line menu. See Figure B-3.

Figure B-3. HART Communicator on-line menu

B.4 HART® Communicator Users are responsible for responding to safety messages (e.g.,
safety messages and warnings) and notes that appear on the HART Communicator.
notes Safety messages and notes that appear on the HART Communicator
are not discussed in this manual.

B.5 HART® Communicator Figure B-4, page 109, illustrates the HART Communicator menu
menu tree tree for Series 1000 and 2000 transmitters.

108 Series 1000 and 2000 Transmitters


Using the HART® Communicator continued

Figure B-4. HART® Communicator menu tree

1 Process Variables 2 Diag/Services

1 View field dev vars 1 Test/status


2 View output vars 2 Loop test
3 View status 3 Calibration
4 Totalizer cntrl 4 Trim analog out1
5 Scaled AO trim
1 Mass flow 6 Test points
2 Temp
3 Mas totl 1 View status
4 Dens 1 2 Self test
1 5 Mass inventory
6 Vol flo
7 Vol totl 1 Fix analog out1 1 Perform auto zero
2 2 Fix frequency out
8 Vol inventory 2 Mass flo
3 Zero time
1 View PV-analog1 1 Auto zero 4 Zero
2 View SV 1 Value 3
2 Event1 type 2 Density cal
2 3 View TV-frequency 1 Dens pt1 (air)
4 View QV 3 Event1 setpoint 2 Dens pt2 (water)
5 View event1 4 Status alarm1 1 LPO 3 Dens pt3 T-series 1 Perform cal
6 View event2 2 RPO 4 Dens pt4 T-series
1 Value 3 Tube 5 Flowing dens (FD)
2 Event2 type 6
4 Drive
1 Mass totl 3 Event2 setpoint 5 Board temperature
2 Vol totl 4 Status alarm2 6 Live zero flow
3 Start totalizer
4 4 Stop totalizer
5 Reset all totals
6 Reset mass total
7 Reset volume total

3 Basic Setup 4 Detailed Setup 5 Review

1Tag See page 110 1 Device info


2 PV unit 2 Charize sensor
3 Analog1 range vals 3 Fld dev vars
4 Freq scaling 4 Outputs

1 PV URV
3 2 PV LRV

1 FO scale method
4 2 FO scaling 1 TV freq factr
2 TV rate factr

Series 1000 and 2000 Transmitters 109


Using the HART® Communicator continued

Figure B-4. HART® Communicator menu tree (continued)


4 Detailed Setup

1 Charize sensor 1 T-Series


2 Config fld dev var 2 Other
3 Config outputs
4 Device information 1 Flow cal
5 Config events
6 Display setup
1 D1
2 K1
1 Sensor selection 3 D2
2 Flow 4 K2
3 Density 5 Temp coeff
1 4 Temp cal factor 6 FD
5 Meter factors 7 FD cal value

1 Mass factor
1 Flow 2 Vol factor
2 2 Density 3 Dens factor 1 Base mass unit
1 Analog output1 3 Temperature 2 Base mass time
2 Frequency output 1 Mass flo unit 3 Mass flo conv factor
3 HART output 2 Mass flo cutoff 4 Mass flo text
4 RS485 setup 3 Spcl mass units 5 Mass totl text
5 Fault timeout 4 Vol flo unit
1 Tag 5 Vol flo cutoff
2 Descriptor 1 Base vol unit
1 PV is 6 Spcl vol units 2 Base vol time
3 Message 7 Flo direction
2 Range values 3 4 Date 3 Vol flow conv fact
3 PV AO cutoff 8 Flo damp 4 Vol flo text
5 Dev id
4 PV AO added damp 6 Final asmbly num 5 Vol totl text
1 5 AO fault setup 1 AO fault indicator 1 Dens unit
7 Snsr s/n
6 Fix analog out1 2 mA fault value 4 8 Snsr model 2 Dens damping
7 Trim analog out1 9 Output opt brd 3 Slug low limit
8 Scaled AO trim Construction 4 Slug high limit
matls 5 Slug duration
1 TV is 1 TV freq factr Revision #s
2 FO scale method 2 TV rate factr 1 Temp unit
2 3 FO scaling 3 Max pulse width 2 Temp damp
4 FO fault setup
5 Fix frequency out 1 FO fault indicator
2 FO fault value 1 Event1 var
2 Event1 type
1Poll addr 3 Event1 setpoint
2 Num req preams 1 Event1
3 5 2 Event2
3 Burst mode 1 Event2 var
4 Burst option 2 Event2 type
1 Enable/disable 3 Event2 setpoint
1 Protocol 6 2 Display var #s
2 Baudrate 1 Total reset
4 3 Parity 2 Auto scroll
4 Stop bits 3 Offline menu
4 Alarm menu
5 Ack all
6 Offline pswd

110 Series 1000 and 2000 Transmitters


Appendix C Using ProLink II™ Software

C.1 Overview The instructions in this manual assume that users are already
familiar with ProLink II software and can perform the following
tasks:
• Start and navigate in ProLink II software
• Establish communication between ProLink II software and
compatible devices
• Transmit and receive configuration information between
ProLink II software and compatible devices
If you are unable to perform the tasks listed above, consult the
ProLink II software manual before attempting to use the software to
configure a transmitter.

C.2 Connecting to a personal You can connect a personal computer (PC) directly to the
computer transmitter’s HART/Bell 202 terminals, the RS-485 terminals, the
service port, or to a point on a network. Figure C-1 identifies the
transmitter terminals to which a PC can be connected.
Note: You must use a signal converter to convert the
transmitter’s RS-485 or Bell 202 standard to the RS-232
standard used by the PC’s serial port.

Figure C-1. Transmitter terminal identification

HART/Bell 202 terminals (1,2)

RS-485 terminals (5,6)

Service port terminals (7,8)

Series 1000 and 2000 Transmitters 111


Using ProLink II™ Software continued

Connecting to To temporarily connect a PC directly to the HART/Bell 202 or


communication terminals RS-485 terminals:
1. Open the cover to the intrinsically safe wiring compartment.
Note: The signal converter must be connected across a
resistance of 250–600 Ω . Add resistance to the connection.
2. If you are going to temporarily connect to the HART/Bell 202
terminals, then:
a. Connect one end of the signal converter leads to the Bell 202
terminals on the signal converter.
b. Connect the other end of the signal converter leads to the
transmitter terminals labeled “1” and “2.” See Figure C-2.
3. If you are going to temporarily connect to the RS-485 terminals,
then:
a. Connect one end of the signal converter leads to the RS-485
terminals on the signal converter.
b. Connect the other end of the signal converter leads to the
transmitter terminals labeled “5” and “6.” See Figure C-2.

Figure C-2. Connecting to communication terminals

Bell 202 to RS-232


signal converter

250–600Ω resistance added

If connecting to
HART/Bell 202
terminals

If connecting to
RS-485 terminals

25 to 9 pin serial port


adapter (if necessary)
250–600Ω resistance added
RS-485 to RS-232
signal converter

112 Series 1000 and 2000 Transmitters


Using ProLink II™ Software continued

Connecting to a RS-485 or To connect to an RS-485 or HART/Bell 202 standard network:


Bell 202 standard network 1. Identify the communication standard used on the multidrop
network (i.e., Bell 202 or RS-485).
Note:Thesignal convertermust be connected across a resistance of
250–600 Ω . Add resistance if necessary.
2. If the multidrop network uses Bell 202 communication standard,
then:
a. Connect one end of the signal converter leads to the Bell 202
terminals on the signal converter.
b. Connect the other end of the signal converter leads to any point
in the multidrop network. See Figure C-3.
3. If the multidrop network uses RS-485 communication standard,
then:
a. Connect one end of the signal converter leads to the RS-485
terminals on the signal converter.
b. Connect the other end of the signal converter leads to any point
in the multidrop network. See Figure C-3.

Figure C-3. Connecting to a Bell 202 or RS-485 standard network

Distributed
control system If RS-485
or network
programmable
logic controller

25 to 9 pin serial port


adapter (if necessary)

Add 250–1000 Ω RS-485 to RS-232


resistance (if necessary) signal converter

If HART/Bell
202 network

RS-232 to Bell 202


Transmitters signal converter

Series 1000 and 2000 Transmitters 113


Using ProLink II™ Software continued

Connecting to the service To temporarily connect to the service port, which is located in the
port non-intrinsically safe power-supply compartment:
1. Open the cover to the intrinsically safe wiring compartment.

WARNING
Opening the power-supply compartment in explosive
atmospheres while the power is on can cause an
explosion.

Do not open the power-supply compartment in explosive


atmospheres before shutting off the power and waiting the
required delay time as indicated on the transmitter housing.

2. Open the transmitter’s power-supply compartment door.


3. Connect one end of the signal converter leads to the RS-485
terminals on the signal converter.
4. Connect the other end of the signal converter leads to the
service-port terminals. See Figure C-4.

Figure C-4. Connecting to the service port


Series 1000 or 2000 transmitter
terminal compartment

25 to 9 pin serial port


adapter (if necessary)

Service port RS-485 to RS-232


signal converter

114 Series 1000 and 2000 Transmitters


Appendix D Using the Display

D.1 Overview This appendix describes the basic use of the display and provides a
menu tree for the display. You can use the menu tree to locate and
perform display commands quickly.

D.2 Components Figure D-1 illustrates the display components.

Figure D-1. Display components


Current value

Process
variable line Units of
measure
Button-press
indicator

Scroll button
Select button

The Scroll and Select buttons are infrared-sensitive detectors. To


press either button, touch the glass in front of the button or move
your finger close enough over the button to trigger the detector. The
button-press indicator will flash red each time a button is pressed.

Series 1000 and 2000 Transmitters 115


Using the Display continued

D.3 Menu tree Figure D-2 shows the display menu tree for the transmitter. To
perform the functions listed in the menu tree, refer to the
appropriate procedures in sections 2, 3, and 4, and in this appendix.

Figure D-2. Display menu tree

Press SCROLL
and SELECT
simultaneously.

SELECT SELECT Acknowledge


Alarm menu View alarms alarms

SCROLL

SELECT Simulate SCROLL Zero the SCROLL Configure


Off-line menu
outputs flowmeter RS-485

SELECT

Set the
protocol

SCROLL

Set the
baud

SCROLL

Set the
parity

SCROLL

Set the
stop bits

SCROLL

Set the
address

116 Series 1000 and 2000 Transmitters


Appendix E Return Policy

E.1 General guidelines Micro Motion return procedures must be followed for you to meet
the legal requirements of applicable U.S. Department of
Transportation (DOT) regulations. They also help us provide a safe
working environment for our employees. Failure to follow these
requirements will result in your equipment being refused delivery.
To return equipment, contact the Micro Motion Customer Service
Department for return procedures and required documentation:
• In the U.S.A., phone 1-800-522-6277 or 1-303-530-8400 between
6:00 a.m. and 5:30 p.m. (Mountain Standard Time), Monday
through Friday, except holidays.
• In Europe, phone +31 (0) 318 549 549, or contact your local sales
representative.
• In Asia, phone (65) 777-8211, or contact your local sales
representative.
Information on return procedures and forms are also available on
our Web site, at www.micromotion.com.

E.2 New and unused Only equipment that has not been removed from the original
equipment shipping package will be considered new and unused. New and
unused equipment includes sensors, transmitters, or peripheral
devices which:
• Were shipped as requested by the customer but are not needed, or
• Were shipped incorrectly by Micro Motion.

E.3 Used equipment All other equipment is considered used. This equipment must be
completely decontaminated and cleaned before being returned.
Document all foreign substances that have come in contact with the
equipment.

Series 1000 and 2000 Transmitters 117


118 Series 1000 and 2000 Transmitters
Index

A pulse width 67
Acknowledging alarms 27 slug-flow duration 50
Adjusting meter factors 48 slug-flow limits 48
Alarm menu 26 software tag 53
Alarm priorities, status indicator 27 temperature damping 47
Alarms temperature units 41
acknowledging 27 upper range value 59
events volume-flow units 38
high alarm 45 Characterizing 75
low alarm 45 FCF parameter 77
status 91 how to characterize 76
viewing 26 troubleshooting 95
Analog wiring 10 when to characterize 75
with ProLink II 77
B with the HART Communicator 76
Bad pickoff voltage 98 Checking the test points 96
Base mass unit 42 Command tree for the display 116
Base time unit 42 Communication loop, troubleshooting 94
Base unit 42 Components of the transmitter 5
Base volume unit 42 Connecting ProLink II 111, 112, 113, 114
Burst mode 70 Connecting the HART Communicator 107
Contacting customer service 98
C Conventions 108
Calibrating 78 Conversion factor 42
failure 89 Customer service, contacting 98
how to calibrate 78
troubleshooting 96 D
when to calibrate 78 Damping
with ProLink II 83 density damping 47
with the HART Communicator 79 flow damping 46
Changing mA output 62
damping values 46 temperature damping 47
density damping 47 values 46
density units 40 Density
display options 54 meter factor 48
display scroll rate 55 Density calibration 78
display variables 56 Density damping, changing 47
fault output Density units
frequency output 66 changing 40
mA output 62 list 40
flow damping 46 Digital communications 100
flow direction 52 Disabling display parameters 54
high slug-flow limit 49 Display
low slug-flow limit 49 alarm menu 26
lower range value 61 alarms
low-flow cutoff acknowledging 27
mass flow 51 viewing 26
volume flow 51 changing lower range value 61
mA fault output 62 changing output scale 65
mA output damping 62 changing upper range value 60
mass-flow units 37 changing variables 56
meter factors 48 command tree 116
off-line password 55 components 13, 115
output scale 63 enabling/disabling parameters 54

Series 1000 and 2000 Transmitters 119


Index continued

loop test 17 H
mA and frequency range values 73 HART
options 54 burst mode 70
resetting mass totalizer 32 enabling/disabling 70
resetting volume totalizer 33 settings 71
rotating 12 menu tree 108
scroll rate 55 multidrop wiring 11
starting all inventories 31 polling address 95
starting all totalizers 31 single-loop wiring 10
stopping all inventories 31 HART Communicator
stopping all totalizers 31, 32 assigning variables 57, 59
viewing mass inventory 30 burst mode 70, 71
viewing mass totalizer 28 calibrating with 79
viewing process variables 25, 26 changing
viewing volume inventory 30 density damping 47
viewing volume totalizer 29 density units 40
zeroing 21 display scroll rate 55
Drive gain display variables 56
erratic 97 fault timeout 68
flow damping 46
E flow direction 52
Electrical connections 99 frequency fault output 67
EMI effects 101 high slug-flow limit 49
Enabling display parameters 54 low slug-flow limit 49
Environmental effects 101 lower range value 61
Environmental limits 101 mA damping 62
Environmental requirements 1 mA fault output 63
Erratic drive gain 97 mA output damping 62
Events mass low-flow cutoff 51
definition 45 mass-flow units 37
setting 45 off-line password 55
alarm type 45 output scale 63, 64
process variable 45 polling address 72
setpoint 45 pulse width 67
Excessive drive gain 97 RS-485 settings 69
slug-flow duration 50
F software tag 53
Fault conditions 91 temperature damping 47
Fault output, changing temperature units 41
frequency output 66 upper range value 59, 60
mA output 62 volume low-flow cutoff 51
FCF parameter 77 volume-flow units 38
Flow damping, changing 46 characterizing with 76
Flow direction, changing 52 connecting 107
Flowmeter conventions 108
calibrating 78 inventories
Flowmeter, characterizing 75 starting all 31
Frequency output, changing stopping all 31
fault output 66 loop test 16
output scale 63 menu tree 108
pulse width 67 obtaining test points 96
Frequency range values 73 polling address 95
Frequency/pulse output characteristics 100 safety messages 108
Functional specifications 99 setting events 45
Fuse special units
power supply 100 mass-flow unit 43
volume-flow unit 44
totalizers

120 Series 1000 and 2000 Transmitters


Index continued

resetting all 33 density 40


resetting mass totalizer 32, 33 mass flow 37
resetting volume totalizer 32, 33 special
starting all 31 mass-flow unit 43
stopping all 31 volume-flow unit 44
trimming mA output 19 temperature 41
viewing volume flow 39
alarms 26 Menu tree
mass inventory 30 HART 108
mass totalizer 28 Meter factors 48
process variables 25 Milliamp output characteristics 100
volume inventory 30 Milliamp output, changing
volume totalizer 29 damping 62
zeroing with 20 fault output 62
Hazardous area classifications 101 lower range value 61
High alarm 45 upper range value 59
High slug-flow limit 49 Milliamp output, trimming 19, 20
Humidity limits 101 Milliamp range values 73
Mounting
I pipe 3
Input signals 100 wall 3
Inventories Mounting the transmitter 2
definition 28
starting 31 O
stopping 31 Off-line password, changing 55
viewing mass inventory 30 Output scale
viewing volume inventory 30 changing 63
definition 63
L troubleshooting 95
Location, determining appropriate 1 Output signals 100
Loop test 16, 17, 18 Output, troubleshooting
Low alarm 45 analog 90
Low slug-flow limit 49 HART 89
Lower range value
changing 61 P
definition 61 Password, changing 55
troubleshooting 95 Performance specifications 101
Low-flow cutoff Physical specifications 102
mass flow 51 Pickoff voltage 98
volume flow 51 Pipe mounting 3
Point-to-point wiring 11
M Power supply 100
Mass flow Power supply, troubleshooting 94
meter factor 48 Power, applying to transmitter 16
Mass inventory, viewing 30 Process variables
Mass-flow units assigning to analog outputs 57
changing 37 viewing 25
list 37 ProLink II
Mating connector 6 assigning variables 58, 59
Measurement range, changing burst mode 70, 71
lower range value 61 calibrating 83
upper range value 59 changing
Measurement units density damping 47
changing density units 40
density units 40 display scroll rate 55
mass-flow units 37 display variables 57
temperature units 41 fault timeout 68
volume-flow units 38 flow damping 46

Series 1000 and 2000 Transmitters 121


Index continued

flow direction 52 definition 55


frequency fault output 67 Sensor
high slug-flow limit 49 pickoff values 97
low slug-flow limit 49 Sensor, characterizing for 75
lower range value 62 Service port 111
mA damping 62 Setpoint 45
mA fault output 63 Slug flow
mass low-flow cutoff 51 duration 50
mass-flow units 38 limits 48
off-line password 56 Slugs 48
output scale 66 Software tag 53
polling address 72 Special units
pulse width 67 base mass unit 42
RS-485 settings 69 base time unit 42
slug-flow duration 50 base unit 42
software tag 53 base volume unit 42
temperature damping 47 conversion factor 42
temperature units 41 mass-flow unit 43
upper range value 60 volume-flow unit 44
volume low-flow cutoff 51 Specifications
volume-flow units 38 functional 99
characterizing with 77 performance 101
connecting 111, 112, 113, 114 physical 102
display parameters 54 Status alarm indicator 27
loop test 18 Status alarms 91
resetting totalizers 33
setting events 46 T
special units Tables
mass-flow unit 43 flowing density calibration minimum flow rates 81
volume-flow unit 44 sensor pickoff values 97
starting all inventories 31 Tag, software 53
starting all totalizers 31 Temperature damping, changing 47
stopping all inventories 32 Temperature effect 101
test points 96 Temperature limits 101
trimming the mA output 20 Temperature units
viewing changing 41
alarms 27 list 41
viewing mass inventory 30 Terminals
viewing mass totalizer 29 communication 111
viewing process variables 26 Test points
viewing volume inventory 30 checking 96
viewing volume totalizer 29 obtaining with a HART Communicator 96
zeroing with 22 obtaining with ProLink II 96
Pulse width Totalizers
changing 67 definition 28
definition 67 resetting all 33
resetting mass totalizer 32
R resetting volume totalizer 32
Receiving device, troubleshooting 95 starting 31
Return policy 117 stopping 31
Rotating the display 12 viewing mass totalizer 28
Rotating the transmitter 8 viewing volume totalizer 29
Transmitter
S changing settings 35
Safety messages 1 components 5
HART Communicator 108 environmental requirements 1
Scroll rate installing 1
changing 55 mounting 2

122 Series 1000 and 2000 Transmitters


Index continued

rotating 8 Z
troubleshooting Zeroing 20
no communication 89 failure 89
no operation 89 with ProLink II 22
wiring 9 with the display 21
Trimming mA output 19 with the HART Communicator 20
Trimming the mA output 19, 20
Troubleshooting
alarms 91
analog output 90
bad pickoff voltage 98
calibration 89, 96
characterization 95
checking test points 96
communication loop 94
core module to transmitter wiring 94
customer service telephone number 98
erratic drive gain 97
excessive drive gain 97
fault conditions 91
frequency output scale and method 95
HART output 89
HART polling address 95
measurement range 95
power supply wiring 94
receiving device 95
transmitter does not communicate 89
transmitter does not operate 89
wiring problems 94
zero failure 89

U
Upper range value
changing 59
definition 59
troubleshooting 95

V
Viewing
alarms 26
mass inventory 30
mass totalizer 28
process variables 25
volume inventory 30
volume totalizer 29
Volume flow
meter factor 48
Volume inventory, viewing 30
Volume-flow units
changing 38
list 39

W
Wall mounting 3
Wire distances 2
Wiring problems 94
Wiring the transmitter 9

Series 1000 and 2000 Transmitters 123


124 Series 1000 and 2000 Transmitters
Visit us on the Internet at www.micromotion.com

Micro Motion Europe Micro Motion Asia


Groeneveldselaan 8 1 Pandan Crescent
3903 AZ Veenendaal Singapore 128461
The Netherlands Republic of Singapore
Tel +31 (0) 318 549 549 Tel (65) 777-8211
Fax +31 (0) 318 549 559 Fax (65) 770-8003

Micro Motion Inc. USA Micro Motion Japan


Worldwide Headquarters Shinagawa NF Bldg. 5F
7070 Winchester Circle 1-2-5, Higashi Shinagawa
Boulder, Colorado 80301 Shinagawa-ku
Tel (303) 530-8400 Tokyo 140-0002 Japan
(800) 522-6277 Tel (81) 3 5769-6803
Fax (303) 530-8459 Fax (81) 3 5769-6843

© 2001 Micro Motion, Inc.


All rights reserved
P/N 3600204, Rev. B

recycled paper

You might also like