You are on page 1of 43

FIRE PROTECTION

DESIGN COURSE

AYMAN HASSAN
MECHANICAL ENGINEER
2013
FOURTH LECTURE CONTENTS

 Revision on Hydraulic Calculation Method.

1. Fire Elite Hydraulic Calculation program & Example.

2. Calculation of Fire Water Tank Capacity.

3. Introduction to Fire Alarm System.

11/5/2013 2
1. FIRE ELITE SOFTWARE
HYDRAULIC CALCULATION

11/5/2013 3
1. INSIDE& OUTSIDE
HOSE STREAM ALLOWANCE

11/5/2013 4
(2&4)DEFAULT K-FACTOR&
SPRINKLER SIZE

11/5/2013 5
3. TEMPERATURE RATING

11/5/2013 6
(5&7)MINIMUM DESIRED DENSIT Y&
AREA OF SPRINKLER OPERATION

11/5/2013 7
(8)MAXIMUM AREA PER SPRINKLER

11/5/2013 8
MINIMUM OPERATING PRESSURE
FOR SPRINKLER

11/5/2013 9
WATER VELOCIT Y THROUGH PIPES

 FOR PUMP SUCTION& DISCHARGE LINE:


 V Suction = 10ft/sec = 3 m/s
 V Discharge = 13.33ft/sec = 4 m/s

 FOR NET WORK VELOCIT Y NOT TO EXCEED 2.5m/s(8.2ft/sec)

11/5/2013 10
HYDRAULIC JUNCTION POINT
(NODE PRESSURE)

11/5/2013 11
DAMPING FACTOR

11/5/2013 12
2. CALCULATION OF FIRE
WATER TANK CAPACIT Y
 After determination of pump capacity, according to occupancy
hazard type the amount of firefighting water tank shall be
calculated.

 The fire pumps should operate for a specific minimum


duration according to the type and hazard of the occupancy.

 Fire water tank should be calculated according to the highest


hazard at the project being designed.

11/5/2013 13
EXAMPLE

 Calculated pump capacity=750 gpm.


 Hazard Type= Ordinary Hazard. (60-90 minutes).
Or 30 Minutes(NFPA -14)
 Fire Water Tank Capacity=750*60=45,000 gallons= 170m 3

Fire water tank should consist of ( 2 compartments) of 170m 3


water reserve for firefighting purposes.

11/5/2013 14
MINIMUM WATER SUPPLY TIME

11/5/2013 15
WATER TANK

11/5/2013 16
3. INTRODUCTION TO
FIRE ALARM SYSTEM

11/5/2013 17
FIRE ALARM SYSTEM

 A fire alarm system is designed to detect the unwanted


presence of fire by monitoring environmental changes
associated with combustion .(automatically or manually
actuated or both)

 Automatic fire alarm systems are intended to notify the


building occupants to evacuate in the event of a fire or other
emergency, report the event to the responsible authorities for
emergency services, and to prepare the structure and
associated systems to control the spread of fire and smoke.

11/5/2013 18
FIRE ALARM SYSTEM COMPONENTS

1. Initiating Devices.

2. Control Panel.

3. Power Supply.

11/5/2013 19
1. INITIATING DEVICES

 This component acts as an input to the fire alarm control unit


and are either manually or automatically actuated.

 Examples would be devices pull stations, heat detectors, or


smoke detectors.

 Heat and smoke detectors have dif ferent categories of both


kinds.

11/5/2013 20
MANUAL INITIATING DEVICES

Manually actuated devices ; also known as fire alarm boxes,


are installed to be readily located (near the exits), identified,
and operated.

 manual pull stations

 Break glass stations.

 call points or Buttons.

11/5/2013 21
MANUAL CALL POINTS

 A Manual Call Point is a device which enables personnel to


raise an alarm in the event of a fire incident by pressing a
frangible element to activate the alarm system .

 Manual Call Point should be installed at a height of 1 .2m


above floor level at easily accessible positions , on exit routes,
at the entry floor landings of staircases and at all exits to the
open air.

11/5/2013 22
MANUAL CALL POINTS

 Manual Call Points should be spaced so that one may always


be found within a maximum distance of 45m apart or 25m for
disabled person.

11/5/2013 23
FIRE ALARM SOUNDERS

 Fire Alarm Sounders should be installed throughout the


building with an even distribution, to generally provide a
minimum sound level of 65dB(A) or 5dB(A) above any
background noise which is likely to persist for more than 30
seconds.

 Where the alarm may have to arouse sleeping persons e.g.


Hotel bedrooms, nursing homes, etc, a minimum sound level
of 75dB(A) is required, at the bed head with all the doors
shut.

11/5/2013 24
FIRE ALARM SOUNDERS

11/5/2013 25
1.2 AUTOMATIC INITIATING DEVICES

 Automatically actuated devices can take many forms intended


to respond to any number of detectable physical changes
associated with fire:
 Heat detector.
 Smoke detectors.
 Flame detector.
 Fire gas detector, and release of extinguishing agents.
 The newest innovations can use cameras and computer
algorithms to analyze the visible ef fects of fire and movement
in applications inappropriate for or hostile to other detection
methods.

11/5/2013 26
FIRE ALARM DETECTOR

 A device suitable for connection to a circuit that has a sensor


that responds to a physical stimulus such as heat or smoke .

Types of Detectors:
1. Smoke Detector.

2. Heat Detector.

3. Beam Detector.

4. Combined Detector(Smoke + Heat).

11/5/2013 27
SMOKE DETECTOR

 Smoke detectors are preferred since it senses fire existence


fir st(SMOKE).
 It includes a light source (infrared LED-Light-Emitting Diode) and a
photodiode or other photoelectric sensor at an angle to the beam as
a light detector. In the absence of smoke, the light passes in front
of the detector in a straight line. When smoke enters the optical
chamber across the path of the light beam, some light is scattered
by the smoke par ticles, directing it at the sensor and thus triggering
the alarm.

11/5/2013 28
SMOKE DETECTOR

 In open spaces under flat horizontal ceilings, every point


should lie within 7.5m of a smoke detector.
Smoke detection should be generally avoided in the following
areas to avoid unwanted alarms:
 Contamination in dusty areas may cause unwanted alarms and
reduce the life of the detector.
 Humid conditions such as showers, bathrooms and external areas
should be avoided as the water vapor may cause unwanted alarms
and reduce the life of the detector.
 Detectors should never be used at low temperature where ice or
condensation can affect detector sensitivity.
 Kitchens, garages, welding shops and boiler houses should generally
be avoided.

11/5/2013 29
SMOKE DETECTOR

11/5/2013 30
HEAT DETECTOR

 A heat detector is a fire alarm device designed to respond


when the convected thermal energy of a fire increases the
temperature of a heat sensitive element.
 The most common fixed temperature point for electrically
connected heat detectors is 136.4°F (58°C). Technological
developments have enabled the perfection of detectors that
activate at a temperature of 117°F (47°C), increasing the
available reaction time and margin of safety.

11/5/2013 31
HEAT DETECTOR

 In open spaces under flat horizontal ceilings, every point


should lie within 5.3m of a heat detector.

 Heat detectors are designed to either detect a rapid rise in


temperature or to operate at a fixed temperature. Although
they provide a slower response time than smoke detectors
they do provide a method of protection for areas where smoke
detectors cannot be used .

11/5/2013 32
HEAT DETECTOR

11/5/2013 33
BEAM DETECTOR

 A type of photoelectric light obscuration smoke detector


wherein the beam spans the protected area.
 Used for places which its height is higher than 10 meters.
 L=50 meters or 100 meters & installed each 15 meters.

11/5/2013 34
2. FIRE ALARM CONTROL UNIT (PANEL)

 A system component that receives inputs from automatic and


manual fire alarm devices and might supply power to
detection devices.

11/5/2013 35
ADDRESSABLE CONTROL PANEL

11/5/2013 36
ADDRESSABLE CONTROL PANEL

11/5/2013 37
ADDRESSABLE CONTROL PANEL

 Allowed range of fire detectors to be connected to one loop


is( 126 – 200) detector.

 Maximum number of loops to be connected to an addressable


control panel is 10 loops ( 2- 4 – 6 – 8 - 10).

11/5/2013 38
CONVENTIONAL CONTROL PANEL

11/5/2013 39
CONVENTIONAL CONTROL PANEL

 Allowed range of fire detectors to be connected to one loop


is( 20 - 30) detectors.

 Maximum number of zones to be connected to a conventional


control panel is 8 zones ( 2- 4 – 6 – 8 ).

11/5/2013 40
3. POWER SUPPLY SOURCE

 Primary Power supply: Commonly the non-switched 120 or


240 Volt Alternating Current source supplied from a
commercial power utility. In non-residential applications, a
branch circuit is dedicated to the fire alarm system and its
constituents. "Dedicated branch circuits" should not be
confused with "Individual branch circuits" which supply energy
to a single appliance.

 Secondary (backup) Power supplies : This component,


commonly consisting of sealed lead -acid storage batteries or
other emergency sources including generators, is used to
supply energy in the event of a primary power failure.

11/5/2013 41
NOTIFICATION APPLIANCES

 This component uses energy supplied from the fire alarm


system or other stored energy source, to inform the proximate
persons of the need to take action, usually to evacuate.

This is done by means of :


 flashing light.
 strobe light.
 electromechanical horn .
 Bell.
 Speaker.

 OR a combination of these devices which makes a beeping


sound and electromechanical sound together.

11/5/2013 42
EXIT DOORS

11/5/2013 43

You might also like