Professional Documents
Culture Documents
Communication Module
User’s Manual
03/2005
1743234
2
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3
Warnings - Loss of Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Internal faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4
Safety Information
§
Important Information
NOTICE Read these instructions carefully, and look at the equipment to become familiar with the
device before trying to install, operate, or maintain it. The following special messages
may appear throughout this documentation or on the equipment to warn of potential
hazards or to call attention to information that clarifies or simplifies a procedure.
DANGER
DANGER indicates a hazardous situation, which will result in death, serious injury
or equipment damage.
WARNING
WARNING indicates a situation presenting risks liable to provoke death, serious injury or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which,can result in personal
injury or equipment damage.
03/2005 5
Safety Information
PLEASE NOTE Electrical equipment should be serviced only by qualified personnel. No responsibility is
assumed by Schneider Electric for any consequences arising out of the use of this
material. This document is not intended as an instruction manual for untrained persons.
© 2004 Schneider Electric. All Rights Reserved.
6 03/2005
About the Book
At a Glance
Document Scope This manual describes the setup, functions and operation of the LULC032 Modbus
communication module.
Area of application: mainly control system applications in the Industry and Building
sectors.
Validity Note The data and illustrations in this manual are not contractual. We reserve the right to
modify our products in line with our policy of continuous development. The
information given in this document may be modified without notice and must not be
interpreted as binding on the part of Schneider Electric.
03/2005 7
About the Book
Related
Documents
Title of Documentation Reference Number
LU•B•/LU•S• Model U Starters Quick Reference Guide 1629984
LUTM• Model U Controller Quick Reference Guide 1743236
LUC• Control Units Quick Reference Guide 1629990
LUCM/LUCMT Multifunction Control Unit User’s Manual 1743237
LUTM• Model U Controller User’s Manual 1743233
Internal Communication Variables User’s Manual 1744082
Electromagnetic Compatibility of Industrial Networks and Fieldbuses TSX DG KBL F
Modbus Over Serial Line, Specification & Implementation Guide Modbus_over_serial_
line_V1
Product Related Schneider Electric is in no way liable for any errors in this document. Please contact
Warnings us if you have any suggestions for improvements or modifications, or if you find any
errors in this publication.
No part of this document may be reproduced in any form or by any means
whatsoever (electronic, mechanical or photocopying) without the prior authorization
of Schneider Electric.
All relevant local safety regulations must be followed when installing and using this
product. For safety reasons and to ensure conformity with the documented system
data, only the manufacturer is authorized to repair the components.
User Comments We welcome your comments about this document. You can reach us by e-mail at
techpub@schneider-electric.com
8 03/2005
Hardware Setup
I
Introduction to Hardware Setup
03/2005 9
Hardware Setup
10 03/2005
Installing the LULC032 Modbus
module
1
Introduction to Installation
CAUTION
HAZARDOUS OPERATION
These devices must be installed, configured and used by qualified staff only.
Users must follow all current instructions, standards and regulations.
Check the function settings before starting the motor.
Do not downgrade or modify these devices.
Failure to follow this instruction can result in injury or equipment damage.
CAUTION
PRECAUTIONS WHEN USING COMMUNICATION VARIABLES
Only use the serial link for transmitting data that is not critical to the application.
There is some delay in the transmission of data relating to motor-starter states and
load-current values. This data must not therefore be used in the management of
safety devices and emergency stops.
Data such as Forward, Reverse and Stop must not be used in safety and
emergency-stop circuits.
Failure to follow this instruction can result in injury or equipment damage.
03/2005 11
Installing the LULC032 Modbus module
12 03/2005
Installing the LULC032 Modbus module
Receiving the On opening the box containing the LULC032 Modbus communication module, you
Product should find the following items:
A Quick Reference Guide, providing brief pictorial information on standard
installation of the module
A LULC032 Modbus communication module equipped with connectors
Note: Check that you actually have all the items described above. Make sure that
the Quick Reference Guide is included, along with the correctly inserted
connectors.
Functions The communication module is used to control a motor-starter remotely, via Modbus,
Offered from:
TeSys model U controller-starter LUB••/LU2B••
TeSys model U starter LUS••/LU2S••
TeSys model U controller LUTM••
Note: For information on the Modbus protocol, please refer to the following
website: www.Modbus.org.
DANGER
CONTROL VOLTAGE
The LULC032 Modbus communication module must only be used with 24 V
control units (LUC•••BL).
Failure to follow this instruction will result in death, serious injury, or
equipment damage.
03/2005 13
Installing the LULC032 Modbus module
Data Available The available protection and control data depends on the control unit with which the
LULC032 Modbus communication module is used.
There are 3 types of control unit:
z Standard (reference LUCA)
z Advanced (references LUCB/C/D, LUCBT/DT)
z Multifunction (references LUCM/MT)
The table below can be used to check the data and commands you can access with
each type of control unit:
Control unit
Standard Advanced Multifunction
Data - Commands
(LUCA) (LUCB/C/D, (LUCM/MT)
LUCBT/DT)
Start and stop commands √ √ √
Status (ready, running, fault
√ √ √
condition)
Warning √ √
Automatic reset and remote reset
√ √
via the bus
Indication of the motor load √ √
Differentiation of faults √ √
Remote parameter setting and
√
viewing of all functions
"Log" function √
"Monitoring" function √
14 03/2005
Installing the LULC032 Modbus module
Diagram of the Connectors and indicator lights (LEDs) on the LULC032 Modbus communication module:
Module
Note: The pinout differs from that on the LULC031 Modbus communication module.
03/2005 15
Installing the LULC032 Modbus module
Description of Description of the various states of the indicator lights (light emitting diodes, LEDs)
Indicator Lights on the LULC032 Modbus communication module.
(LEDs)
Light Emitting Diodes (LEDs)
Green "COMM" Green "24V Meaning
Red "ERR" LED
LED " LED
Flashing
Flashing (alternately Bus parameter initialization in
(alternately with On
with the "ERR" LED) progress
the "COMM" LED)
Flashing during
communication with Off On Normal operation
the Module address
Faulty: 24 V DC voltage
missing on the 24 V DC
Off Off terminal. Check the connection
between the power supply and
Off the communication module
Internal fault on the LULC032
On On
Internal faults, p. 68
Loss of communication on the
Flashing On
Modbus network
Note: During startup, because the default fallback mode is "forced stop", if no
communication has previously been established, the red "ERR" LED will flash after
one minute (default timeout value).
16 03/2005
Installing the LULC032 Modbus module
Addressing The Modbus communication module address is defined by switches located on the
Using Switches underside of the module. Simply turn the module over to access them:
On
A
On
B
Note: Addressing is only taken into account when the communication module is
powered up.
03/2005 17
Installing the LULC032 Modbus module
The diagram below illustrates these steps. Installation of the LULC032 Modbus
communication module corresponds to step (2). The numbers indicate both the
order of mounting for the components and their location.
LU2B•• LUB••
LU2S•• LUS•• LUTM•0BL
LUCA••BL
LUCB••BL LUCBT1BL
LUCC••BL LUCDT1BL
LUCD••BL
LUCMT1BL
LUCM••BL
3 3
LULC032
2 2
LU9B N11C
1
LU9M RC
18 03/2005
Installing the LULC032 Modbus module
Electrical Connection
Terminator
LUCM LUCMT
LUCB
LUCBT
LUCC
LUCDT
LUCD
LUCA
A1/A2
LUTM
terminals
LULC032 LULC032
24 V Aux 24 V 24 V 24 V Aux
Internal links
03/2005 19
Installing the LULC032 Modbus module
Note: Both these faults are reset by powering down and then powering up the
LULC032 Modbus communication module (power cycle) and the LUCM control unit.
20 03/2005
Installing the LULC032 Modbus module
Power supply for In order to operate, the LULC032 Modbus communication module must be powered
the LULC032 and by a 24 V source:
Outputs OA1, z With a power base, the module must be powered by an external source.
OA3 and LO1 z With a controller base, it is powered directly.
1 24 V ==: Power-supply terminals for the LUTM and the LULC032 Modbus communication
module via an internal link.
2 The 24 V == power supply for the LULC032 Modbus communication module is only
required when using outputs OA1, OA3 and LO1.
03/2005 21
Installing the LULC032 Modbus module
Power Base: The user has two options for connecting the power base terminals:
Terminal Power z Power supply via the LULC032 Modbus communication module with a prewired
Supply link
z Direct power supply with a wire-to-wire link
Prewired Link
References of the two prewired coils:
Designation With a power base Reference
LUB••/LUS•• LU9B N11C
Prewired coil
LU2B••/LU2S•• LU9M RC
LU2B LUB
LU2S LUS
LULC032 LULC032
LU9B N11C
LU9M RC
22 03/2005
Installing the LULC032 Modbus module
The wire-to-wire link can also be used to insert a local or external stop command,
for example.
03/2005 23
Installing the LULC032 Modbus module
24 03/2005
Installing the LULC032 Modbus module
General There are several ways in which the user can connect the communication module
to the RS 485 bus:
z Direct connection to the bus via a VW3A8306TF•• T-junction box
z Connection to the bus via a splitter box
z Connection to the bus via SCA type junction boxes
Note: For more information, consult the guide TSX DG KBL F: "Electromagnetic
compatibility of industrial networks and fieldbuses".
The new Modbus specification, published in 2002 on the Modbus.org site, defines
all these characteristics precisely. All new Telemecanique devices conform to this
specification.
03/2005 25
Installing the LULC032 Modbus module
Connection to The standard schematic corresponds to the Modbus specification published in 2002
the Bus via a Tee on the Modbus.org site (Modbus_over_serial_line_V1.pdf, Nov 2002) and in
particular to the 2-wire multidrop serial bus schematic.
The LULC032 Modbus communication module conforms to this specification.
The simplified schematic is as follows:
Master
5V
450 -
650 Ω
450 -
650 Ω
D1
150 Ω 150 Ω
D0
Common
LULC032 LULC032
LUB../LUS..
LU2B../LU2S.. LUTM
Slave 1 Slave 2
26 03/2005
Installing the LULC032 Modbus module
03/2005 27
Installing the LULC032 Modbus module
Connection to The schematic for connection to the bus via a splitter box is as follows:
the Bus via a
Splitter Box
IN
5
4 4 4 4
5 6 4 6 4 3 OUT
Note: It is advisable to place a line terminator at each end of the bus to avoid
malfunctions on the communication bus. This means that a tee should not have a free
connector. It is either connected to a slave or to the master, or there is a line terminator.
Note: It is important to connect the bus to the "IN" input (or the screw terminals on the
bottom) of the splitter box. Connection to another splitter box is made via the "OUT" output.
28 03/2005
Installing the LULC032 Modbus module
Note: Ensure that the 470 Ohm resistors are connected to the 0 V and 5 V
polarities correctly.
03/2005 29
Installing the LULC032 Modbus module
Connection between TSX SCY 21601 module (channel 0) and splitter box LU9 GC3 with
TSX SCY CM6030 cable:
25-pin SUB D
Tx - D(A)
Tx + D(B)
Shielding
Connection between PCMCIA card/TSX SCP 114 and splitter box LU9 GC3 with
TSX SCP CX4030 cable:
Tx -
Tx +
Rx -
Rx +
Shielding
2 White/Green 4 Orange/White
30 03/2005
Installing the LULC032 Modbus module
03/2005 31
Installing the LULC032 Modbus module
32 03/2005
Installing the LULC032 Modbus module
Connection to The schematic for connection to the bus via SCA junction boxes is as follows:
the Bus via SCA
Junction Boxes
2 6 7
5 3 4
03/2005 33
Installing the LULC032 Modbus module
34 03/2005
Installing the LULC032 Modbus module
RJ45 Connector The communication module is connected to the Modbus network with an RJ45
Pinout connector in compliance with the following wiring:
Pin no. Signal
1 Do not connect
2 Do not connect
3 Do not connect
4 D(B) or D1
5 D(A) or D0
6 Do not connect
7 Do not connect
1
8 0 V.L
RJ45
8
03/2005 35
Installing the LULC032 Modbus module
36 03/2005
Technical Characteristics
2
Introduction to the Technical Characteristics
03/2005 37
Technical Characteristics
Conditions of The conditions of use for the LULC032 Modbus communication module are as follows:
Use
Certification UL, CSA
Conformity to standards IEC/EN 255-6, UL 508, CSA C22-2 No. 14
European community marking. Satisfies the essential requirements of the low voltage
directives (LV) machinery and electromagnetic compatibility (EMC) directives.
Ambient air temperature Storage °C - 40 ... + 85
around the device Operation °C - 25 ... + 55
24V Power The characteristics of the LULC032 Modbus communication module 24 V power
Supply Circuit supply circuit are as follows:
Unominal V 24V
Supply voltage
Operating range V 20 ... 28
Maximum current drawn A 1
Resistance to microbreaks ms 2
24 V Aux Power- The characteristics of the LULC032 Modbus communication module 24 V Aux
Supply Circuit power supply circuit are as follows:
Unominal V 24V
Supply voltage
Operating range V 20 ... 28
Maximum current drawn mA 30
Resistance to microbreaks ms 3
38 03/2005
Technical Characteristics
Logic Outputs The characteristics of the LULC032 Modbus communication module outputs are as follows:
OA1, OA3 and
Voltage V 24V
LO1 Nominal output values
Current mA 500
Voltage V 20 ... 28
Output limit values
Current mA 500
Coincidence factor of
% 66
the 3 outputs
5 (LUCA/B/C/D)
Output response time (register 704) 15 (LUCM)
(Time between the request start bit and the change in ms 30 (LUCBT/DT)
the output state) 45 (LUCMT)
with stop bit
Against overvoltage Yes
Against inversions Yes
Protection Electronic circuit-
Against short-circuits and
breaker with automatic
overloads
reset
Number of operating
In millions of operating cycles 15
cycles
Maximum rate In operating cycles per hour 3600
Logic Inputs LI1 The characteristics of the LULC032 Modbus communication module inputs are as follows:
and LI2
20 ... 28
Voltage V
Nominal input values (positive logic)
Current mA 7
Voltage V 16
At state 1
Current mA 6
Input limit values
Voltage V 5
At state 0
Current mA 2
Change to state 1 ms 10 +/- 30 %
Response time
Change to state 0 ms 10 +/- 30 %
Type of input Resistive
Protection gl fuse A 1
03/2005 39
Technical Characteristics
* From V1.3 onwards. Previous versions are factory-configured with "No parity".
40 03/2005
Technical Characteristics
Mounting The section below presents the LULC031 and LULC032 module characteristics in
the form of tables.
Mounting the LULC031 and LULC032 in different types of base:
LULC031 LULC032
Starter-controller Starter-controller Controller
LUB••/LU2B•• LUB••/LU2B•• LUTM•0BL
Yes Yes Yes
03/2005 41
Technical Characteristics
42 03/2005
Technical Characteristics
Electrical
Connection The LULC031 and LULC032 module terminals look like this:
LO1 COM + - + -
LULC031
LULC032
03/2005 43
Technical Characteristics
Communication
Configuration The address is selected using switches:
LULC031
LULC032 1
* "Even parity" from V1.3 onwards. Previous versions are factory-configured with
"No parity".
Note: The speed and the parity are calculated automatically by the module. The
speed indicated is a maximum value.
44 03/2005
Technical Characteristics
Software
Configuration Fallback mode on loss of communication (value of default register):
LULC031 LULC032
Starter-controller Starter-controller Controller
LUB••/LU2B•• LUB••/LU2B•• LUTM•0BL
682 = 0
681 = 6000 (timeout = 60 seconds)
No detection of loss of
682 = 2 (fallback mode = forced stop)
communication
03/2005 45
Technical Characteristics
46 03/2005
Software Setup
II
Introduction to Software Setup
03/2005 47
Software Setup
48 03/2005
Starting up the Module via the
Registers
3
Introduction to Start-Up via the Registers
03/2005 49
Starting up the Module via the Registers
Access to The module I/O parameters are set by one of the following three methods:
Parameters z The Modbus RJ45 port, via the application PLC
z The LUCM multifunction control unit’s terminal port
z Locally, via the LUCM multifunction control unit’s keypad
50 03/2005
Starting up the Module via the Registers
Data-Exchange Format
At the end of the initialization phase, the LULC032 Modbus communication module
Time
03/2005 51
Starting up the Module via the Registers
Exception Code The presence of an exception code is indicated by the report from the PLC (refer to
the Modbus master module documentation).
The Modbus exception codes supported are as follows:
Value of the exception code Name Comment
Hexadecimal Decimal
0x01 1 Illegal function Unknown request code
z Register address invalid
z Access to the private memory
zone (address ≥ 20000)
0x02 2 Illegal data address
z Writing to a "read-only" register
The memory zone is prohibited in
both read and write modes
z Invalid value
0x03 3 Illegal data value
The write command is interrupted
* From V1.3 onwards. Previous versions are factory-configured with "No parity".
TSX Micro or Applications for Micro and Premium PLCs are programmed using PL7 software.
Premium READ_VAR or WRITE_VAR requests (see Modbus Requests and Programming
Platform Examples) are used to read or write respectively the value of one or more
consecutive objects of the same type (bit, word), in PL7 language.
52 03/2005
Starting up the Module via the Registers
Factory Configuration
The parameter registers (Modbus protocol) are accessible in read/write mode. The
factory-set values are as follows:
Subject Register Factory value Meaning
Reset mode for thermal overload fault 602.0 1 "Manual" mode
Enable communication between
602.4 1 Communication active
LUCM/MT and LULC032
Forced stop
Fallback mode for control outputs on
682 2 Power base: OA1 and OA3 at 0
loss of communication
Controller base: 13 and 23 at 0
Local operating mode or via the bus Mode for controlling the LUTM controller
683 0
with the LUTM and LULC032 outputs "remotely via the bus"
The state of the outputs corresponds to the
Inversion of the LULC032 outputs 684 0
state of the control bits
Assignment of:
- Output LO1 685 LSB 2 LO1 is the state of control bit 700.0
- Output OA1 686 LSB 12 OA1 is the state of control bit 704.0
- Output OA3 686 MSB 13 OA3 is the state of control bit 704.1
(on controller base)
- Output 13 687 LSB 12 13 is the state of control bit 704.0
- Output 23 687 MSB 13 23 is the state of control bit 704.1
The outputs revert to the state they were in
Restart mode after a power cut 688 0
before the power cut.
Identification of the control unit 690 0 The control unit is identified automatically
Note: For more information, refer to the "Internal Communication Variables" User’s Manual.
03/2005 53
Starting up the Module via the Registers
You can use the factory settings (see Factory Configuration) or customize your
configuration.
The following parameters can be set:
z Control unit configuration
z Control unit ID
z Timeout duration
z Fallback mode
z Control mode with an LUTM controller.
z Inversion of the output states
z Assignment of outputs LO1, OA1, OA3, 13 and 23
z Restart after a power cut
z Control unit forcing
Control Unit Register 602 (accessible in read/write mode) is used to configure the control unit
Configuration (reset mode 602.0-2, and communication 602.4).
(Reg 602)
Reg• Value Comment
602.0 1 Resetting is manual (by default). Bits 1 and 2 are at 0.
0 You have activated either bit 1 (remote reset) or bit 2 (automatic reset)
602.4 1 Communication with the LUCM/MT multifunction control unit has been activated.
0 When forced to 0, this bit inhibits communication between the LUCM/MT
multifunction control unit and the LULC032 Modbus communication module.
Control Unit ID The control unit is identified each time the communication module is powered up.
(Reg 680) However, the multifunction control unit memorizes the reference of the
communication module assembled with it.
To use a multifunction control unit on its own, once it has been used with a
communication module, identification register 680 is reinitialized locally via the
keypad in the menu (Id = 0) or via the remote LUCM Modbus terminal port (value 0
written to register 680).
54 03/2005
Starting up the Module via the Registers
Timeout Register 681 (accessible in read/write mode) is used to set or read the value of the
Duration timeout on loss of communication with the PLC. Following loss of communication,
(Reg 681) the timeout corresponds to the time before switching to fallback mode. Loss of
communication causes an warning, which is signaled by register 460 = 109.
Reg• Value Range Unit Factory value Comment
681 - 0 - 65535 10 ms 6000 Value of timeout
The value 0 represents a time of zero.
Fallback Mode Register 682 (accessible in read/write mode) is used to configure the fallback
(Reg 682) mode in the event of loss of communication with the PLC.
Fallback mode Value Comment
Inhibited (no fallback) 0 No detection of loss of communication
No change in the control states is authorized when
loss of communication is detected
Frozen 1
Any new command will only be taken into account after
acknowledgment of the loss of communication (703.3)
Forced stop (factory value) 2 Outputs OA1 = 0 and OA3 = 0
A change in the control states is authorized when loss
of communication is detected
Unchanged 3
Any new command can be taken into account before
acknowledgment of the loss of communication (703.3)
Forced operation, direction 1 4 Output OA1 = 1 (forward) and (OA3 = 0)
Forced operation, direction 2 5 (OA1 = 0) and output OA3 = 1 (reverse)
Note: The red "ERR" LED flashes to indicate a loss of communication (fault on
timeout).
03/2005 55
Starting up the Module via the Registers
Control Mode Control of outputs 13 and 23 of the LUTM controller depends on the operating
(Local/Bus) With mode selected in register 683.
an LUTM
Value Operation Comment
Controller (Reg
683) "Remote via Outputs 13 and 23 are only controlled by the bus.
0
the bus" mode The state of inputs I.1 and I.2 does not affect outputs 13 and 23.
Outputs 13 and 23 are only controlled by inputs I.1 and I.2.
1 "Local" mode
Commands via the bus are not taken into account.
Outputs 13 and 23 are only controlled
by inputs I.1 and I.2.
"Local" mode if I.10 = 1
Commands via the bus are not taken
"Mixed" mode into account.
2 (input I.10 has
priority) Outputs 13 and 23 are only controlled
"Remote via the bus" by the bus, from the PLC.
mode if I.10 = 0 The state of inputs I.1 and I.2 does not
affect outputs 13 and 23.
Inversion of the Depending on requirements (signaling, run, stop, etc), it is possible to assign NO or
Output State NC behavior to outputs OA1, OA3 and LO1, by configuring register 684.
(Reg 684) To do this, define the output concerned ==> register 684.
Power base Bit
Invert output OA1 _.0 = 1
Invert output OA3 _.1 = 1
Invert output LO1 _.2 = 1
56 03/2005
Starting up the Module via the Registers
Setting the To modify the assignment (factory value), write another value (0 to 45), referring
Parameters of to the "Internal Communication Variables" User’s Manual.
Output LO1 Assignment/control (factory value) of output LO1 of the LULC032 Modbus
(Reg 685 LSB) communication module is as follows:
Reg• Bit Value Factory value Comment
685 0 to 7 0 to 45 2 Output LO1 = state of register 700.0 (control
of output LO1)
Setting the Assignment/control (factory value) of output OA1 of the LULC032 Modbus
Parameters of communication module.
Output OA1
Reg• Bit Value Factory value Comment
(Reg 686 LSB)
686 0 to 7 0 to 45 12 Output OA1 = state of register 704.0 (control
of output OA1)
Setting the Assignment/control (factory value) of output OA3 of the LULC032 Modbus
Parameters of communication module.
Output OA3
Reg• Bit Value Factory value Comment
(Reg 686 MSB)
686 8 to 15 0 to 45 13 Output OA3 = state of register 704.1 (control
of output OA3)
Restart Mode This is a protection against possible unintended equipment operation. Activate it if
After Stopping you do not wish the outputs to go back to the state they were in before the power
(Reg 688) cut, by changing its value to 1.
03/2005 57
Starting up the Module via the Registers
Control Unit The control unit is identified automatically, but identification can be forced.
Forcing
(Reg 690)
Value Comment
0 Default value. The system automatically identifies the type of control unit
connected (standard, advanced, multifunction)
1 If the value is set to 1, this deactivates automatic identification and forces
identification of a standard or advanced control unit.
2 If the value is set to 2, this deactivates automatic identification and forces
identification of a multifunction control unit.
58 03/2005
Starting up the Module via the Registers
Note: The "Broadcast" function is supported. To use it, a write operation (code 6
or 16) to address 00 is necessary.
WARNING
UNEXPECTED OPERATION
Use of this device on a Modbus network that uses the broadcast function should
be considered with caution.
This device has a large number of registers that must not be modified during
normal operation.
Unintended writing of these registers by the broadcast function may cause
unexpected and unwanted product operation.
For more information, refer to the "Internal Communication Variables" User’s
Manual.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.
03/2005 59
Starting up the Module via the Registers
Example of a The example below describes a READ_VAR request, within a TSX Micro or
Read Operation Premium platform, in order to read the motor-starter states at address 4 (slave no. 4)
contained in internal word MW0:
1 Address of the module with which you wish to communicate: 3 (module address), 0
(channel), 4 (module address on the bus)
2 Type of PL7 objects to be read: MW (internal word)
3 Address of the first register to be read: 455
4 Number of consecutive registers to be read: 1
5 Word table containing the value of the objects read: MW0:1
6 Read report: MW100:4
Example of a The example below describes a WRITE_VAR request, within a TSX Micro or
Write Operation Premium platform, in order to control a motor-starter by sending the content of
internal word MW 502:
1 Address of the module with which you wish to communicate: 3 (module address), 0
(channel), 4 (module address on the bus)
2 Type of PL7 objects to be written: MW (internal word)
3 Address of the first register to be written: 704
4 Number of consecutive registers to be written: 1
5 Word table containing the value of the objects to be sent: MW502:1
6 Write report: MW200:4
60 03/2005
Starting up the Module via the Registers
Before setting up a motor-starter, it is useful to know which of the main registers are
invoked, and in what order.
Schematic of The schematic below provides basic setup information, using the following registers:
Register Usage configuration, control and monitoring (system state, measurements, faults and
warnings, acknowledgment). Starting with the factory configuration (predefined),
you will easily be able to follow or anticipate how your system behaves.
03/2005 61
Starting up the Module via the Registers
62 03/2005
Fault and Warning Management
4
Introduction to Faults and Warnings
This chapter shows how to manage the various types of fault and warning that may
occur.
03/2005 63
Fault and Warning Management
Displaying Faults
z Presence of an exception code (report from the PLC). See Exception Code, p. 52.
Note: The warning and the fault are taken into account in the relevant registers. For
more information, refer to the "Internal Communication Variables" User’s Manual: fault
control registers (450 to 454) and warning control registers (460 to 461).
64 03/2005
Fault and Warning Management
Application Faults
The possible application faults are listed below. Their reset (or acknowledgment)
Acknowledgmen method can be: manual/automatic/remote.
t of Application
Faults
Registers LULC032 LUCM• LUTM
451 452
Fault Fault bit Fault
Application faults number acknowledgment
03/2005 65
Fault and Warning Management
Overload Fault Following a thermal overload fault, either the rotary knob or the blue pushbutton on
With LU•B•/LU•S• the front panel can be used, irrespective of which reset mode has been configured.
Power Base
Configuration Reset
Method
register (acknowledgment)
With the rotary knob on LU•B•
direct "manual"
With the blue pushbutton on LU•S•
602.0 = 1
With the LU9 AP•• kit on LU•B•
remote "manual"
With the LU9 •• kit on LU•S•
602.1 = 1 "remote" Acknowledgment by setting bit 704.3 to 1
602.2 = 1 "automatic" Managed by the control unit
Overload Fault Following a thermal overload fault, either the blue pushbutton on the front panel or
With LUTM input I.5 can be used, irrespective of which reset mode has been configured.
Controller Base
Configuration Reset
Method
register (acknowledgment)
local "manual" With the blue pushbutton on the front panel
602.0 = 1 With the reset button on the front of the rack or
remote "manual"
control panel (via Input I.5)
602.1 = 1 "remote" Acknowledgment by setting bit 704.3 to 1
602.2 = 1 "automatic" Managed by the control unit
66 03/2005
Fault and Warning Management
Restart After After acknowledgment by setting bit 703.3 to 1, restarting occurs according to the
Loss of states of control bits 704.0 and 704.1.
Communication
03/2005 67
Fault and Warning Management
Internal faults
68 03/2005
Fault and Warning Management
User’s Manual
_.13 = 1 On -
Power down and
No control unit 206 then power up the
LUTM
03/2005 69
Fault and Warning Management
70 03/2005
Configuration of Predefined
Functions
5
Introduction to the Predefined Functions
03/2005 71
Configuration of Predefined Functions
The reflex stop ensures accurate repeated position control, unhindered by the bus
and PLC scan times.
There are two types of reflex stop function:
z Reflex1: "Reflex stop 1" function
z Reflex2: "Reflex stop 2" function
Description of Sensor no. 1 (logic input LI1) directly controls motor stopping.
Reflex1 After a new run command (stop command then run command), the motor restarts
even if something is still detected (LI1=1).
Note: In the case of a reversing starter, the reflex stop works in both directions.
Data sequence
Time
72 03/2005
Configuration of Predefined Functions
Description of Sensor no. 1 (logic input LI1) controls motor stopping in forward mode.
Reflex2 Sensor no. 2 (logic input LI2) controls motor stopping in reverse mode.
After a new run command (stop command then run command), the motor restarts
even if something is still detected (LI1 or LI2 = 1).
3 2
Note: Sensor no. 2 (LI2) does not affect forward mode and sensor no. 1 (LI1) does
not affect reverse mode.
03/2005 73
Configuration of Predefined Functions
To use a "reflex stop" function, it must be selected in the register of the output to be
monitored.
LUB••/S•• - LU2B••/ LUTM••
2S•• base base
Reflex Value of
Direction of motor rotation Outputs Outputs
function Reg• Output
OA1 13
LO1
OA3 23
Reflex1.Fw = forward 8
Reflex1 Reg686 Reg687
Reflex1.Rev = reverse 9 Reg685
(LSB) (LSB)
Reflex2.Fw = forward 10 (LSB)
Reflex2 (MSB) (MSB)
Reflex2.Rev = reverse 11
Note: Before using the "reflex stop" functions, outputs OA1/OA3 must first be
assigned to the forward/reverse directions. This selection is made in register 686.
By default, OA1 is assigned to forward and OA3 to reverse.
Reflex1.Fw This function is active on a rising edge and not on the level.
LI1 = 1 stops the motor, irrespective of the chosen direction of operation.
.Fw After a new run command (stop command followed by a run command),
even if logic input LI1 = 1,
the motor restarts in the chosen direction.
74 03/2005
Configuration of Predefined Functions
Reflex1.Rev This function is active on a rising edge and not on the level.
LI1 = 1 stops the motor, irrespective of the chosen direction of operation.
.Rev After a new run command (stop command followed by a run command),
even if logic input LI1 = 1,
the motor restarts in the chosen direction.
Reflex2.Fw This function is active on a rising edge and not on the level.
Logic input LI1 = 1 stops the motor in forward mode.
Logic input LI2 = 1 stops the motor in reverse mode.
.Fw
After a new run command (stop command followed by a run command),
even if logic input LI1 = 1,
the motor restarts.
Note: Logic input LI2 does not affect forward mode and logic input LI1 does not
affect reverse mode.
Reflex2.Rev This function is active on a rising edge and not on the level.
Logic input LI2 = 1 stops the motor in reverse mode.
Logic input LI1 = 1 stops the motor in forward mode.
.Rev
After a new run command (stop command followed by a run command),
even if logic input LI2 = 1,
the motor restarts.
Note: Logic input LI2 does not affect forward mode and logic input LI1 does not
affect reverse mode.
03/2005 75
Configuration of Predefined Functions
76 03/2005
Index
B
AC
A Diagram of the Module, 15
Acknowledgment
Alarm, 67 E
Application Fault, 65
Electrical Connection, 19
Internal Fault, 68
Exception Code, 52
Addressing, 17, 44
Alarm, 67
Application Faults, 65 F
Fallback Mode, 55
C Faults, 64
Forcing
Cables, 31, 34
Control Unit, 58
Conductor, 24
Connection, 15
SCA Junction Box, 33 I
Splitter Box, 28
Identification
Tee (Direct), 26
Control Unit, 54
Connectors, 15
Indicator Lights, 15, 16
Control Mode, 56
Input, 39
Control Unit
Input (on Diagram), 15
Configuration, 54
Internal Faults, 68
Forcing, 58
Inversion
Identification, 54
Output State, 56
Control Units (LUC...), 14
Controller Base, 18, 20
J
D Junction Box, 35
Data Exchange
Exception Code, 52
Format, 51
L
Initialization, 51 LEDs, 15, 16
03/2005 77
Index
S
M Speed, 52
Modbus Format, 51 Switches, 17, 44
Modbus Port, 40
Modbus Request, 59
Read, 60 T
Write, 60 Timeout
Module, 29 Duration, 55
Module Functions, 13
O
Order of Mounting, 18
Output, 39
Parameter Setting, 57
Output (on Diagram), 15
Output State
Inversion, 56
P
Parameter Setting
Output, 57
Parameters, 50
Parity, 52
PCMCIA Card, 29
Pinout (RJ45), 35
PL7, 52
Power Base, 18, 20
Power Supply, 19, 21, 22, 38
Power-up, 20
R
Receiving the Product, 13
Reflex Stop, 72
78 03/2005