You are on page 1of 1

FROM NO OF CURRENT

No PANEL TO PANEL/CIRCUIT CABLES PER TOTAL CURRENT PER CABLE CROSS SECTION TOTAL MV VOLTAGE VOLTAGE VOLTAGE ACCEPTABLE
NAME LENGTH DROP DROP (V) DROP (V)
NAME PHASE CABLE
(VA) (A) (A) (M) (V) UP LEVEL SOURCE
2(3x240+120)
1 TR MDB/TR 1 300000 455.82 455.82 10 0.11 0.50 0.13% 0.13% ACCEPTED
CU, XLPE/STA/PVC
(3x95+50)
2 MDB DB-BR 1 9400 14.28 11.00 300 0.6 1.98 0.52% 0.65% ACCEPTED
AL, XLPE/STA/PVC
(4x25)
3 DB-BR L1,3,5/DB-BR 1 2400 3.65 3.65 400 1.3 1.90 0.50% 0.63% ACCEPTED
CU, XLPE/STA/PVC
(4x25)
3 DB-BR L2,4,6/DB-BR 1 2100 3.19 3.19 400 1.3 1.66 0.44% 0.57% ACCEPTED
CU, XLPE/STA/PVC
(4x25)
3 DB-BR L7,9,11/DB-BR 1 3000 4.56 4.56 600 1.3 3.56 0.94% 1.59% ACCEPTED
CU, XLPE/STA/PVC