On Sunday, March 24, 2019, 3:08:58 PM GMT+2, SORIANO Leonardo <Leonardo.

SORIANO-
int@egis.fr> wrote:

Dear Sir,

We have prepared a comparison table of street lighting pole in the Drawing as compared to BOQ.

As an example please clarify in IC1 KSR where there are 2 types of poles - 8 meter and 16 meter high.

 In BOQ there are 300 poles while in the drawing there are 381 poles.

 In BOQ there are 80 poles where there are (0)none in the drawings.

 Please indicate in your drawing the location of the 16meter poles for IC1

The table attached indicating missing poles should match between BOQ and Drawing.
Dear Sir,

We have received some clarification on the Road Lighting drawings attached.

Please clarify :

Details of Drawing below on Lighting Pole:

 Foundation Dimension as shown in all the drawings for IC1 IC2 and IC3 where the
dimension is 0.25 as scale of sheet

Foundation dimensions ,and reinforcement of pole must be checked by contractor at execution


based on soil report,pole weight, wind intensity.
the sheet is not to scale, foundation width shall be not less than 0.7 m ,whoever it must checked
by contractor as explained above.
details plan attached again after update this dimension to use it for all ic.

 Number of Bolts especially for 16 meter height as shown in the Detail Design Drawing for
IC1 IC2 and IC3. Please confirm only 4 bolts for 16 meter high pole.
4 plots are sufficient, but plots sizes must be checked by contractor according to pole weight,
wind intensity.

 Location of 16 meter street lighting pole in the Road Lighting Drawings especially in IC1
because there are none in the drawings.
16 m pole are used for bridges lighting at midan area only (middle zone of bridge) , this is for all
IC as we agreed before.

 In the Drawing Detail the height of the poles was 10 meter and 7 meter of lighting pole
detail for road and sub-road.

While in the Road Lighting Drawing in the plan indicate 8 meter and 6 meter disputing the
Lighting Pole Detail.
After our revise of dwgs we confirm the used poles in both of detail drawings and lighting
drawings are:-
7 meter for sub roads
10 meter for main roads
16 m for middle zone of bridge at midan area.

and you should update boq based on this values.

 Earthing Diagram symbol is not indicated in the Legend.


we added it in general detail plan,and you can add it in master drawings of each ic.
. Details and works for Chambers
shop drawings issue.