Professional Documents
Culture Documents
ABSTRACT
This paper illustrates the use of electric field computation to optimize the design of gas
filled high voltage composite bushings. The United States Navy employs these bushings
in high power very low frequency/low frequency transmitting stations. Commercially
available 2D and 3D computational packages based on the boundary element method
were employed to analyze the electric fields. The optimized design uses both internal
and external elements for electric stress grading at critical parts of the bushing. It has
been shown that the location and magnitude of the maximum electric field have been
optimized which should result in a substantially higher corona free operating voltage.
Index Terms — High voltage, bushing, boundary element method, corona ring,
electric field grading, voltage contour, corona inception voltage
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO PARA. Downloaded on January 07,2022 at 14:43:57 UTC from IEEE Xplore. Restrictions apply.
1218 S. Monga et al.: Design Optimization of High Voltage Bushing Using Electric Field Computations
operating voltage and range of transmission. While it is 2.1 CONFIGURATION 1: NO FIELD SHAPER
entirely possible that the use of uniform field profile electrodes The 2-D model of the bushing geometry, without the field
(such as the Rogowski profile) could achieve the same goal of shaper is shown in Figure 2. The housing was considered as a
reducing the electric field in critical areas, the manufacturers uniform diameter sleeve and the shed projections were
of the bushing deemed that this was not an economically eliminated to reduce modeling complexity. This is justified
feasible solution. Hence basic bushing configuration shown in because the highest values of the electric field occur on the
Figure 1 was used as the starting point and the goal of the shank region, which is represented in the simplified geometry.
present project was to design optimum grading hardware for The removal of sheds has a minimal effect on the electric field.
the larger bushing tubes. A voltage of 1 per unit was used for analysis. The electric field
As the first step, a 2-D model of the bushing was developed. profile along the segment AB (silicone rubber surface) is
Then various electric field grading elements like external shown in Figure 3. The magnitude of the surface electric field
corona rings and internal electric field shaper were added to at the HV end and the ground end of the bushing is given in
the initial geometry to obtain an optimum model of the Table 1. The maximum electric field occurs at the triple point
bushing. Repeated analysis was done with each element in interface of the HV electrode, housing and air media. This
different positions to obtain the optimum location giving the triple point location is known be a weak point in insulating
minimum value of electric field on the external surface of the systems. The high field can give rise to corona and cause
bushing. As more elements were added there is interaction flashover. Permanent damage to the housing material is a
between elements and the position of all elements had to be distinct possibility.
adjusted. Thus the optimization process involved hundreds of
iterations. In the discussion below only the final results for
each configuration are given. Finally using the optimum 2-D
model as an input, a 3-D model of the bushing was developed.
For the 2-D and 3-D models, the number of elements used
typically was 2000 and 8500 respectively. For the 3-D model
rectangular shaped elements were employed. For the 2-D
model the shape of the element is not relevant as surfaces are
represented by lines and the package divides the lines into
smaller segments. The distribution of the elements over the
modeling region was done by the package. The above number
of elements was needed in order to ensure that the modeling
error in the electric field was less than 5%. The program
requires the identification of the electrodes and their voltages
(can be expressed in per unit), permittivity and/or conductivity
of the various dielectric components. In the present project the
dielectric materials were assumed to have a very low
conductivity, hence the electric field and voltage distribution is
determined by the various capacitances and not the resistances.
For each configuration the surface electric field at HV end, Figure 2. 2-D bushing model without field shaper.
ground end and the location and magnitude of the maximum
electric field was determined and are listed in Table 1.
Figure 1. Schematic of the bushing. Figure 3. Electric field profile along segment AB, configuration 1.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO PARA. Downloaded on January 07,2022 at 14:43:57 UTC from IEEE Xplore. Restrictions apply.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 13, No. 6; December 2006 1219
Figure 6. Equipotential plot near the ground end showing improvement in field distribution with the addition of field shaper (left) compared to the
Configuration 1 without field shaper (right). The ground electrode is at 0.0 potential and HV electrode is at 1.0 potential.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO PARA. Downloaded on January 07,2022 at 14:43:57 UTC from IEEE Xplore. Restrictions apply.
1220 S. Monga et al.: Design Optimization of High Voltage Bushing Using Electric Field Computations
2.4 CONFIGURATION 4: WITH FIELD SHAPER, AB is shown in Figure 11. The addition of the external
TOP AND BOTTOM EXTERNAL CORONA RING bottom corona ring reduces the electric field at the ground
In an attempt to further reduce the electric field, an external end because the field lines are pushed away from the bottom
corona ring was added near the ground end shown in Figure silicone surface (segment AB).
10. The corresponding electric field profile along segment
Table 1. Results obtained during the optimization process
E-field
E-field
(V/cm) Max E field Location of Max E Field
Configuration, Geometry (V/cm)
Ground (V/cm)
HV end
end
1.675 x 10- Triple junction of HV
1. Without field shaper 2 3.01 x 10-2 3.01 x 10-2
electrode-air-housing
2. With field shaper 5.06 x 10-3 3.01 x 10-2 3.01 x 10-2 Same as above
3. With field shaper, top outer ring 6.61 x 10-3 5.30 x 10-3 6.8 x 10-3 70 cm from ground end
Figure 7. Dimensions of the top external corona ring. Figure 8. Electric field profile along segment AB, configuration 3
Figure 9. Equipotential plot near the HV end showing improvement in field distribution with the addition of the top external corona ring (left)
compared to the Configuration 1 without the corona ring (right). The HV electrode is at 1.0 potential and ground electrode is at 0.0 potential.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO PARA. Downloaded on January 07,2022 at 14:43:57 UTC from IEEE Xplore. Restrictions apply.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 13, No. 6; December 2006 1221
Figure 10. Dimensions of external bottom corona ring. Figure 13. Electric field profile along segment AB, configuration 5
Figure 12. Dimensions of internal top corona ring Figure 14. Dimensions of second external top corona ring
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO PARA. Downloaded on January 07,2022 at 14:43:57 UTC from IEEE Xplore. Restrictions apply.
1222 S. Monga et al.: Design Optimization of High Voltage Bushing Using Electric Field Computations
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO PARA. Downloaded on January 07,2022 at 14:43:57 UTC from IEEE Xplore. Restrictions apply.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 13, No. 6; December 2006 1223
actual application) was covered by a tarp to keep it dry Predicting the corona inception voltage from the
during the wet test for the top part of the bushing. The computational analysis is not straightforward due to various
corona inception voltage under dry conditions exceeded 240 factors such as the nonuniform field distribution, the effect
kVrms and the test was stopped as there is no intention of of water droplets on electric field enhancement, the unclear
operating the bushing above this voltage. Under wet relationship between corona at 30 kHz when compared with
conditions corona was detected (by ultraviolet corona 60 Hz for which there is a large body of information
cameras) on water drops dripping from the sheds at about available. For this reason laboratory and field testing is
180 kV. This type of corona is not expected to cause any absolutely essential prior to placing new designs in service.
problem as the water droplet does not stay in one location Despite these unknowns it has been shown that optimizing
for any length of time. Corona from water droplets on the design using electric field calculations is indeed a worthy
shank was observed only at about 230 kV. Corona was first exercise.
observed on the surface about 1/3 of the distance from the
bottom electrode. This was concurrent with the location of 3 CONCLUSIONS
the highest electric field in Fig. 8. Corona was not seen at (1) It has been demonstrated that the use of the 2-D model
the critical triple point junctions at the top or ground can be used effectively for optimizing the design of HV
electrode, and this was again in agreement with the model bushings. The optimum design consists of one corona ring
predictions. Based on these tests, it appears that a voltage of at the top and an internal metal electric field shaper. Adding
200 kV would be a safe operating voltage. additional internal or external corona rings did not
significantly change the magnitude or the location of the
maximum electric field when compared to the optimized
design.
(2) Laboratory testing indicates good agreement with model
prediction in so far as critical parameters are concerned, i.e.,
a corona free operation at the critical triple junction of
electrode-air-dielectric is possible by internal and external
grading.
4 REFERENCES
[1] P. M. Hansen and A. D. Watt, “VLF/LF High Voltage Design and
Testing”, SPAWAR Systems Center San Diego, TR 1904,
Septermber 2003.
[2] R. S. Gorur, E. A. Cherney and J. T. Burnham, “Outdoor insulators”,
Ravi S. Gorur Inc., Phoenix, Arizona, USA, 1999.
[3] E. Kufel and W. S. Zaengel, High Voltage Engineering
Fundamentals, Pergamon press, 1988.
Figure 18. Electric field profile along segment AB, configuration 7 (3-D [4] A. H. Cookson, “Role of electrical insulation in the design and
model) operation of high voltage equipment”, IEEE 5th International
Conference on Properties and Applications of Dielectric Materials,
Korea, Vol. 1, pp. 1-5, 1997.
[5] T. N. Judge and J. L. Roldan, “Optimization of high voltage
equipment design using boundary element method based
electromagnetic analysis tools”, IEE High Voltage Engineering
Symposium, No. 467, 1999.
[6] C. Trinitis, “Field optimization of three dimensional high voltage
equipment”, IEE High Voltage Engineering Symposium, No. 467,
1999.
[7] P. B. Zhou, Numerical Analysis of Electromagnetic Fields”,
Springer-Verlag, Berlin, 1993.
[8] S. S. Bamji, A. T. Bulinski and K. M. Prasad, “Electric field
calculations with the boundary element method”, IEEE Trans. Electr.
Insul., Vol. 28, pp. 420-424, 1993.
[9] H. Steinbigler, D. Haller and A. Wolf, “Comparative analysis of
methods for computing 2-D and 3-D electric fields”, IEEE Trans.
Electr. Insul., Vol. 26, pp. 529-537, June 1991.
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO PARA. Downloaded on January 07,2022 at 14:43:57 UTC from IEEE Xplore. Restrictions apply.
1224 S. Monga et al.: Design Optimization of High Voltage Bushing Using Electric Field Computations
Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO PARA. Downloaded on January 07,2022 at 14:43:57 UTC from IEEE Xplore. Restrictions apply.