Professional Documents
Culture Documents
Operating Manual
Page
SAFETY……… ............................................................................................................... 1
SERVICE…….. ............................................................................................................... 5
INTRODUCTION .......................................................................................................... 7
Helium Compressor, Model FA-70H ................................................................... 7
PRINCIPLES of OPERATION ........................................................................................ 9
DESCRIPTION ........................................................................................................... 11
Components ..................................................................................................... 11
SPECIFICATIONS ....................................................................................................... 13
FA-70H Compressor (high voltage model)......................................................... 13
Electrical Characteristics ................................................................................. 13
Compressor Control ........................................................................................ 14
Right Front Panel Connections on the Outdoor Unit .......................................... 14
Front and Rear Panel Connections on the Indoor Unit....................................... 15
Front Panel Mounted Items on the Indoor Unit .................................................. 15
Environmental Requirements ............................................................................ 15
Mounting Position .............................................................................................. 15
Helium Gas Pressures ..................................................................................... 16
Refrigerant Quality ........................................................................................... 16
Maintenance Intervals ....................................................................................... 16
Noise Level ....................................................................................................... 16
Weight .............................................................................................................. 16
General Operating Conditions ........................................................................... 16
Supplier Name and Address .............................................................................. 17
Regulatory Compliance ..................................................................................... 18
Parts Identification ............................................................................................. 21
INSTALLATION .......................................................................................................... 27
Introduction ....................................................................................................... 27
Receipt Inspection Instructions .......................................................................... 27
System Configuration ........................................................................................ 28
Compressor Location ....................................................................................... 29
Interconnecting Electrical Cables Installation ..................................................... 34
Electrical Supply Connection (Indoor Unit) ........................................................ 40
Transformer Voltage Tap Selection for FA-70H ................................................. 41
SCAI Recommendations for Wiring an FA-70 According to the US National
Electric Code ..................................................................................................... 42
Compressor Checkout ..................................................................................... 44
Install the Gas Lines ......................................................................................... 45
Install the Cold Head Cable(s) .......................................................................... 46
Compressor Control Preparation – Control Input Selection................................ 46
Compressor Control Preparation – Outdoor Unit Type Selection ....................... 47
Prestart Check................................................................................................... 47
Operation of FA-70 and CNA-61 Combinations ................................................. 48
i
Table Of Contents
Page
OPERATION ............................................................................................................. 51
Starting ............................................................................................................ 51
Stopping .......................................................................................................... 51
Cold Head Only Run ........................................................................................ 51
Cold Start ........................................................................................................ 51
Restarting After a Power Failure ...................................................................... 53
Automatic Restarting After a Helium High Temperature Shutdown Error ......... 53
System Status Display (LCD) ............................................................................ 53
Check System Lamp ......................................................................................... 54
MAINTENANCE ......................................................................................................... 55
Adsorber Replacement ...................................................................................... 55
Adsorber Removal ............................................................................................. 55
Adsorber Installation .......................................................................................... 57
Register New Adsorber ................................................................................... 58
Used Adsorber Venting and Disposal .............................................................. 58
Replace Fuses ................................................................................................ 59
Heat Exchanger Cleaning .................................................................................. 59
TROUBLESHOOTING ................................................................................................ 61
Error/Warning Conditions .................................................................................. 61
Clearing Error/Warning Conditions .................................................................... 62
Restarting after an Error Condition .................................................................... 62
Troubleshooting Guide .................................................................................... 62
Diagnostic Interface Connector Pin Functions ................................................... 69
SERIAL PROTOCOL AND PIN-OUTS ....................................................................... 71
General Information ........................................................................................... 71
Serial Command List ......................................................................................... 71
Command Structure .......................................................................................... 72
Command Set ................................................................................................. 73
CRC Generation ................................................................................................ 77
PARTS ........................................................................................................................ 79
Ordering ............................................................................................................ 79
ii
Table Of Contents
Page
ILLUSTRATIONS LIST
Figure 1 Compressor Flow Diagram .................................................................. 9
Figure 2 FA-70H Compressor Indoor Unit, Front View .................................... 19
Figure 3 FA-70H Compressor, Indoor Unit, Dimensions .................................. 20
Figure 4 FA-70H Compressor, Outdoor Unit, Dimensions............................... 21
Figure 5 FA-70H Compressor, Indoor Unit, Parts Identification ........................ 22
Figure 6 FA-70H Compressor, Outdoor Unit, Parts Identification ..................... 23
Figure 7 Fuse Locations in the FA-70 Indoor Unit Electrical Chassis ............... 26
Figure 8 Compressor System Configuration .................................................... 29
Figure 9 Anchor Bolt Pitch for Affixing Outdoor Unit......................................... 30
Figure 10 Sling Hanging the Outdoor Unit ....................................................... 30
Figure 11 Required Space for Outdoor Unit ..................................................... 31
Figure 12 Required Space for Multiple Outdoor Units ...................................... 32
Figure 13 Required Space for Indoor Unit ........................................................ 33
Figure 14 Electrical Connection Diagram ......................................................... 34
Figure 15 Outdoor Unit Electrical Panel ........................................................... 35
Figure 16 Indoor Unit Selection Connectors..................................................... 36
Figure 17 Insert Interconnecting Electrical Cables Through Side Panel ........... 36
Figure 18 Connect Cables to Outdoor Unit Terminal Board ............................. 37
Figure 19 Indoor Unit Side Electrical Panel ...................................................... 38
Figure 20 Connect Cables to Indoor Unit Terminal Board ................................ 39
Figure 21 Connect Field Wiring to Mains Terminal Block and PE Connector ... 40
Figure 22 Voltage Selection Connectors .......................................................... 41
Figure 23 SCAI Wiring Recommendations Diagram ........................................ 42
Figure 24 Connect Gas Line to Compressor or Cold Head .............................. 46
Figure 25 Disconnect Self-Sealing Coupling .................................................... 56
Figure 26 Disconnect Adsorber from Base ...................................................... 56
Figure 27 Disconnect Adsorber from Rear Panel ............................................. 57
Figure 28 FA-70H Indoor Compressor Unit Wiring Schematic ......................... 66
Figure 29 FA-70H Outdoor Compressor Unit Wiring Schematic....................... 67
Figure 30 FA-70H Compressor D-sub Adapter Wiring Diagram ....................... 68
TABLES
Table 1 Diagnostic Interface Connector Pin Functions, Configuration Mode 1 69
SJM P/N 268854A
iii
(This page is intentionally blank.)
iv
SAFETY
GENERAL
SCAI equipment is designed to operate safely when the installation, operation and servicing are
performed in accordance with the instructions in this technical manual. For Service Center
locations, see the Service section of this manual.
SPECIAL NOTICES
Three types of special notices -- WARNINGS, CAUTIONS and NOTES are used in this
technical manual.
WARNINGS call attention to actions or conditions that can result in serious injury or death.
CAUTIONS call attention to actions or conditions that can result in damage to the equipment or
in abnormal performance.
NOTE
WARNINGS and CAUTIONS, like other safety instructions, appear within rectangles in the text
where they are applicable. Because of their importance, they are summarized in this Safety
section and in the General Technical Manual, and should be read first.
NOTE
Changes to this manual since the previous issue are identified by parallel
lines (||) in the right margins.
1
Safety
WARNINGS
AVOID ELECTRIC SHOCK. All electrical supply equipment must meet applicable codes and
be installed by qualified personnel.
Disconnect the power to the compressor before troubleshooting the electrical components.
Permit only qualified electrical technicians to open electrical enclosures, to perform electrical
checks or to perform tests with the power supply connected and wiring exposed. Failure to
observe this warning can result in serious injury or death.
AVOID INJURY. Never use compressed helium gas from a cylinder without a proper regulator.
Overpressure can cause serious injury if the system equipment ruptures.
During operation, some surfaces under the compressor’s cover become hot. Allow the
compressor to cool for 1/2 hour after shutdown before removing the cover for maintenance.
Always wear eye protection when handling pressurized gas lines and other pressurized
equipment. Never apply heat to a pressurized gas line or other pressurized components.
Disconnect gas lines only when the compressor is stopped. Disconnecting the cold head while
it is cold can create excessively high internal pressure as the gas warms. Material failure and
uncontrolled pressure release can cause serious injury.
Use two wrenches when disconnecting a gas line coupling to avoid loosening the cold head or
compressor coupling. Gas pressure can project the coupling with enough force to cause
serious injury.
The compressor is charged with helium gas. Except when disconnecting the adsorber or the
gas lines, vent both supply and return Aeroquip couplings to atmospheric pressure before
disassembly. Uncontrolled pressure release can cause serious injury.
Always vent a gas-charged component before beginning to disassemble its couplings. Gas
pressure can launch a loose coupling with enough force to cause serious injury.
The adsorber is charged with helium gas. Follow the used adsorber venting procedure for safe
disposal of the used adsorber.
The Outdoor Unit has a venting fan. Do not insert foreign substances from the exhaust port
under any circumstances. Failing to observe this precaution may result in serious injury or
malfunction.
Do not touch the Outdoor Unit’s cooler fin during fin cleaning. Touching the sharp edges of the
fin may result in serious injury.
CAUTIONS
PRESERVE YOUR WARRANTY. Modification to equipment without the consent of the
manufacturer will void the warranty.
Specifications require the use of 99.999% pure helium gas. Using a lesser quality of helium can
damage the system and void the warranty.
2
Safety
CAUTIONS (continued)
AVOID GAS LEAKS. Check the condition of the gasket face seal on the male half of each
Aeroquip coupling. Be sure the gasket face seal is in place and the sealing surfaces on both the
male and female halves are clean before connecting. Replace the gasket face seal if it is
damaged or missing.
Keep the gas line couplings aligned when making or breaking a coupling connection. Leaks can
occur due to the weight of the gas line or due to a sharp bend near the connection.
AVOID CONTAMINATION. When checking the compressor for shipping damage, do not
connect the gas lines and the cold head. The components may become contaminated with
compressor oil.
Follow the charging or venting procedures to prevent reverse flow of system gas. Do not charge
through the supply coupling. Do not vent through the return coupling. Reverse flow can
contaminate the system with compressor oil.
A leaking coupling on an adsorber should not be repaired in the field. Consult a Service Center.
Venting the adsorber will introduce contaminants to the system, which cannot be removed in the
field.
PREVENT EQUIPMENT DAMAGE. Damage to gas lines can result from crimping by repeated
bending and repositioning.
The Outdoor Unit is designed for connection to an FA-70 or CNA-61 Indoor Unit only. Do not
connect the Outdoor Unit to any other equipment or electrical supply.
If the compressor is wired for 380/400/415 (±10%) V3~ electrical service, connecting to a higher
voltage may damage the control circuit. Similarly, if it is wired for 480 V3~, 60 Hz, (460-480 ±10%
V3~) it can be damaged by connecting to 380/400/415 V3~.
Never pull a vacuum on the compressor or on the cold head. The motors will short circuit if
started.
Operating the cold head without gas flow may cause heat buildup that will damage the cold head.
Do not place yourself or any objects on top of the compressor units. Failing to observe this
precaution may prevent the equipment from operating normally or cause injury.
Connect and Operate Only High Voltage IDU’s with High Voltage ODU’s. Connect and Operate
Only Low Voltage IDU’s with Low Voltage ODU’s. DO NOT MIX VOLTAGES.
AVOID A MALFUNCTION. Repeatedly charging the system with helium gas rather than locating
and repairing gas leaks can cause a malfunction. Impurities are introduced at an abnormal rate
and can freeze in the cold head.
Do not allow air to get into the helium gas refrigerant of the system. Moisture from the
atmosphere can seriously degrade cold head performance.
AVOID EQUIPMENT FAILURE OR CONTAMINATION. Use SHIG adsorber P/N 00218 only.
Use of non-SHIG spare parts will void the warranty.
3
(This page is intentionally blank.)
4
SERVICE
HEADQUARTERS
Sumitomo (SHI) Cryogenics of America, Inc.
1833 Vultee Street
Allentown, PA 18103-4783
Sales and Parts
TEL: (800) 525-3072
or
(610) 791-6700
FAX: (610) 791-0440
Service
TEL: (800) 525-3071
or
TEL: (610) 791-6750
SERVICE CENTERS
Eastern Sumitomo (SHI) Cryogenics of America, Inc. Central U.S.A.
U.S.A 1833 Vultee Street
Allentown, PA 18103-4783 Sumitomo (SHI) Cryogenics of America, Inc.
1500-C Higgins Road
TEL: (800) 525-3071
Elk Grove Village, IL 60007
or
(610) 791-6750 TEL: (847) 290-5801
FAX: (610) 791-3904 FAX: (847) 290-1984
Europe Sumitomo (SHI) Cryogenics of Europe, Ltd. Sumitomo (SHI) Cryogenics of Europe, GmbH
3 Hamilton Close Daimlerweg 5a
Houndmills Industrial Estate D-64293 Darmstadt
Basingstoke Germany
Hampshire RG21 6YT
TEL: +49 6151 860 610
United Kingdom
FAX: +49 6151 800 252
TEL: +44 1256 853333
FAX: +44 1256 471507
Asia Sumitomo Heavy Industries, Ltd. Sumitomo (SHI) Cryogenics Korea, Co., Ltd.
Service Section Room 619-620, Venture Valley
Cryogenics Division #958 Goseck-Dong, Kwonsun-Gu
2-1-1 Yato-Cho Nishitokyo-City Suwon-City, Gyeonggi-Do
Tokyo 188-8585 South Korea
Japan
TEL: +82 31 278 3050
TEL: +81 424 68 4265 FAX: +82 31 278 3053
FAX: +81 424 68 4462
Sumitomo Heavy Industries (Shanghai) Sumitomo (SHI) Cryogenics Taiwan Co., Ltd.
Management, Ltd. 4th Floor, No.3
Room 107-110, Building 5 Lane 216, Gongyuan Rd.
No. 100, Zixiu Road Hsinchu City 300
Shanghai 201103 Taiwan ROC
People’s Republic of China
Phone: +886 3 561 2557/2101
TEL: +86 21-6070-5200 Fax: +886 3 562 3400
FAX: +86 21-6070-5086
5
(This page is intentionally blank.)
6
INTRODUCTION
7
(This page is intentionally blank.)
8
PRINCIPLES OF OPERATION
Key
ARV Atmospheric relief valve
F Filter
FCT Fan control thermistor
FM Fan motor
GSV Gas solenoid valve
HTR Oil Heater
HTS Gas temperature switch for use with CNA-61 Indoor Unit
HTT Helium temperature thermistor for use with FA-70 Indoor Unit
IRV Internal relief valve
OBV Oil Bypass Valve
OTS Oil-out temperature switch for use with CNA-61 Indoor Unit
OTT Oil-out temperature thermistor for use with FA-70 Indoor Unit
PG Pressure gauge
PS Pressure switch for use with CNA-61 Indoor Unit
PT Pressure transducer for use with FA-70 Indoor Unit
SOBV Solenoid Oil Bypass Valve
The compressor continuously draws low-pressure helium from the system return line. It
compresses, cools and cleans the gas, then delivers it through the system gas supply line to the
cold head. See Figure 1.
9
Principles of Operation
When helium gas leaves the compressor capsule, the gas contains heat and compressor
lubricant (oil). Both must be removed. From the compressor capsule, the hot gas with its
entrained oil flows out of the shell and through the bulk oil separator. The gas next flows
through one circuit of a two-circuit, air-cooled, heat exchanger, where it is cooled. Next, the gas
passes through the final oil separator and the adsorber for oil and moisture removal. From the
adsorber, the high-pressure helium gas flows to the cold head through the gas lines.
Through the system gas return line, low-pressure gas from the cold head flows into the
compressor.
A gas line containing an internal relief valve (IRV) connects the high-pressure line to the low-
pressure line. The relief valve will open to prevent overloading the motor when the system gas
lines are not connected to the compressor. The IRV also will open during cooldown of the cold
head, bypassing gas until the cold head cools the gas to a sufficient temperature to accept all of
the compressor flow.
Oil is separated from the gas in three stages. The first stage is by gravity when the oil/gas
stream passes through the bulk oil separator. The second stage is in the final oil separator
whose element collects oil mist from the gas; oil is agglomerated and returned to the
compressor. The third stage is the adsorber that removes any remaining oil the gas is carrying.
Oil collected in the oil separators flows back to the compressor capsule through capillary tubes
and orifices. The differential gas pressure across the system is the moving force, and the
restriction size limits the amount of gas bypassed. The small amount of oil collected in the
adsorber remains there and is removed only by replacing the adsorber.
Before being returned to the compressor capsule, the oil separated in the bulk oil separator
flows through the heat exchanger where it is cooled. It is then injected into the low pressure
side of the compressor capsule to absorb heat and lubricate the compressor capsule.
For starting in cold weather, a heater maintains minimum oil temperature, and bypass valves
divert oil until proper operating temperatures are reached.
10
DESCRIPTION
Components
Adsorber - The adsorber removes any oil and moisture the gas is carrying which did not drop
out in the final oil separator. The adsorber has a finite life and must be replaced at regular
intervals.
Atmosphere Relief Valve [ARV] – The pressure relief valve prevents the compressor from
operating at an unsafe pressure by venting to the atmosphere.
Bulk Oil Separator - Removes much of the entrained oil from the gas stream. This unit needs
no servicing or replacement
Cold Head Power Receptacle - Mounted on the front panel of the indoor unit for connecting a
cable to supply electrical power from the compressor to the cold head.
Compressor Capsule - Helium, scroll compressor with a hermetically sealed motor.
Compressor High Temperature Motor Protector Switch - Located inside the compressor
motor, the switch senses compressor motor temperature and stops the motor if the temperature
is too high. The switch resets after cool down.
Final Oil Separator - Removes most of the remaining entrained oil from the gas stream. This
unit needs no servicing or replacement.
Fuses – Three (3) time delay, class CC fuses, located inside the electrical chassis box in the
indoor unit, protect the transformer. Six (6) time delay, 5x20 mm fuses, located in the front
panel recess of the indoor unit, protect the cold head supply circuit and outdoor unit 200 V
circuits.
Heat Exchanger - Uses air to cool the high-pressure helium refrigerant and the compressor’s
lubricating oil.
Heater [HTR] – Maintains minimum oil temperature in cold weather.
Helium Charge - A size 4, male (4M) Aeroquip coupling located on the front of the indoor unit is
used for charging or venting helium gas refrigerant.
Helium Supply and Helium Return Pressure Couplings (for connections to gas lines)
Outdoor Unit – Supply (high pressure) and return (low pressure) couplings are self-sealing,
size 8, male (8M) Aeroquip, bulkhead couplings and are the points of connection on the right
panel.
Indoor Unit – Helium port (high pressure from Outdoor Unit) is a self-sealing, size 8, female
(8F) Aeroquip coupling. Helium port (high pressure to cold head), is a self-sealing, size 8,
male (8M) Aeroquip bulkhead connector. Both are located on the rear panel.
Helium Temperature Thermistor [HTT] and Helium Temperature Switch [HTS] - Sense
discharge gas temperature. They cause the compressor to shut down if the temperature of the
high-pressure helium from the compressor is too high.
11
Description
Hour Meters – Additional battery-driven hour meters are provided in both the IDU and ODU for
servicing:
IDU – located on the side panel next to Cable 1-3 terminal strip. See Figure 20.
ODU – Located next to the IDU selection connectors. See Figure 16.
Indoor Unit [IDU] – Portion of compressor located indoors. It contains the electrical controls
and the gas adsorber. It is connected to the Outdoor Unit by three (3) electrical cables and the
supply gas line.
Internal Relief Valve [IRV] - The internal relief valve opens to allow the compressor to be
operated in the stand-alone mode or when the system gas lines are disconnected, to avoid
overloading the motor.
Mains Power Switch - Mounted on the front panel of the indoor unit, it provides a means to
disconnect power and it protects the compressor from electrical overload. This device is labeled
Main Power.
Oil Bypass Valve [OBV] – Thermally-actuated valve open during cold weather start and closed
when unit has reached operating temperature.
Oil Capillary - The capillary returns oil collected in the oil separator sump to the compressor for
recycling.
Oil Filter - Filters in the oil lines protect the oil return capillary and the orifices.
Oil Injection Orifices - These orifices are installed in the oil return lines and control the flow
rate of oil returned to the compressor.
Oil Out Temperature Thermistor [OTT], Oil Out Temperature Switch [OTS] and Fan
Control Thermistor [FCT] - Sense temperature of oil leaving the heat exchanger. They control
the fan, oil heater and solenoid oil bypass valve.
Outdoor Unit [ODU] - Portion of compressor located outdoors. It contains the compressor
capsule, heat exchanger and oil separators. It is connected to the Indoor Unit by three (3)
electrical cables and the supply gas line.
Pressure Gauge - Indicates gas pressure in the supply line of the indoor unit. When the
compressor is not running, the gauge located on the compressor’s front panel shows the
equalization pressure.
Pressure Transducer [PT] and Pressure Switch [PS] – Sense helium pressure at suction of
compressor. They cause the system to shut down when the suction pressure is too low
(<1 bar – switch and transducer) or too high (>9.7 bar – transducer only).
Solenoid Oil Bypass Valve [SOBV] – Solenoid-actuated valve open during cold weather start
and closed when unit has reached operating temperature.
12
SPECIFICATIONS
Electrical Characteristics
Service required: Delta connected, 4 wires (3 phase plus protective ground or earth.)
Power Connection:
Field wiring terminals are provided. Use only copper conductors.
FA-70H (high voltage model) Transformer Voltage Tap Selection: The proper
transformer voltage tap must be selected to match the incoming supply voltage by
proper position of the transformer supply connector located behind the voltage
selection access panel on the electrical front panel of the indoor unit. See the
section Transformer Voltage Tap Selection.
Power consumption: Operation Startup
6.9 – 7.2 kW @ 50 Hz <8.0 kW @ 50 Hz
7.9 – 8.2 kW @ 60 Hz <9.0 kW @ 60 Hz
Compressor rated load current: 13 amperes
Locked rotor current: 75 amperes at 50/60 Hz
Fan motor FLA (200 V Secondary Circuit): 0.92 amperes
Minimum required circuit ampacity: 20 amperes
Maximum circuit protection: 30 amperes
Internal circuit protection
Transformer - (3) 1.0 ampere, time delay, class CC fuses (FU-1, 2 and 3)
Cold head motor/200 V Control circuit: (3) 0.63 ampere, time delay, 5x20 mm fuses
(FU-4, 5 and 6)
Heater/Fan - (3) 1.25 ampere, time delay, 5x20 mm fuses (FU-7, 8 and 9)
24 V Control circuit: (2) 0.75 ampere, resettable, poly fuses (not replaceable).
Fuses are located inside the Indoor Unit electrical compartment (Fuses1-3) and on the
Indoor Unit Front Panel (Fuses 4-9). Fuses 1-3 are to be serviced by a qualified
electrical technician only. See Figure 7.
Cold head power requirement: 200 V3~, 0.4 amperes, supplied from the compressor.
Cold head power supply: A cable connects the cold head to the indoor unit.
Class I: Grounded equipment
Ingress Protection: Indoor Unit - IP4X; Outdoor Unit – IP23
See the Compressor Wiring Schematics, Figures 28 and 29.
13
Specifications
Compressor Control
Control options
1. Front Panel ON and OFF buttons
2. Control through the Diagnostic Interface
3. Control through the Serial Interface (RS232 protocol on RS485 physical layer)
Control functions
• System ON and OFF
• Front panel LCD display of elapsed time and system status.
• (2) Push buttons, up and down arrows, to scroll the LCD display
• Cold head only run (front panel control only)
• Compressor only run (Diagnostic Interface and RS485 control only)
• Interlock to prevent starting the compressor and the cold head if the main power
phase sequence is incorrect.
• Automatic restart after power interruption.
• Automatic shutoff for the following system faults. Operator correction is required
before restart. Reset is required to clear the alarm lamp and error message on the
display. See Clearing Error / Warning Conditions in Troubleshooting Section.
• High gas discharge temperature, when thermistor reads between 88-102° C
(190-216° F).
(5 automatic restarts at 20 minute intervals before operator correction required.)
• High compressor motor windings temperature, switch opens at 145° C (293° F),
resets at 61° C (142° F).
• High return pressure (>140 psig)
• High equalization pressure (>255 psig)
• High compressor motor current draw: trips at 16 amperes.
• Open cold head (valve motor) fuse(s)
• Low gas return pressure, < 1.03 bar (15 psig)
• Warning displayed for the following system faults: Operator investigation is required.
Reset is required to clear the alarm lamp and warning message on the display. See
Clearing Error / Warning Conditions in Troubleshooting Section.
• High gas discharge temperature when thermistor reads > 83° C (181° F)
• Check system lamp to show:
• Cold Head Only Run
• Sensor Failure – Disconnected sensor or wrong electronic ODU selection
• Error condition
• Warning condition
14
Specifications
Front Panel Mounted Items on the Indoor Unit (See Figure 2.)
• Supply pressure gauge (0-40 bar, 0-600 psig, 0-4000 kPa)
• LCD display (Elapsed time meter display is the default position)
• ON and OFF buttons
• (2) Display buttons (to scroll the LCD display)
• Main power switch
• Check system lamp
Environmental Requirements
Outdoor unit Indoor unit
Operating Storage Operating Storage
Ambient -30° C to 45° C -30° C to 65° 4° C to 40° C -20° C to 65°
Temperature (-22° F to 112° F) C (40° F to 104° F) C
(-22° F to (-4° F to 150°
150° F) F)
Relative 20% to 95% 10% to 90% 30% to 70% 10% to 90%
Humidity (non- (non-
condensing) condensing)
Magnetic Field ≤ 150 Gauss ≤ 150 Gauss ≤ 150 Gauss ≤ 150 Gauss
Limits
Atmospheric 70 kPa to 110 kPa 20 kPa to 110 70 kPa to 110 kPa 20 kPa to 110
Pressure kPa kPa
NOTE
Operating the equipment out of specifications may void the warranty.
Mounting Position
Indoor and outdoor compressor units must be mounted base down and level within 5 degrees of
horizontal.
15
Specifications
*The operating pressure varies according to the heat load of cold head, operating Hz, total gas
line length and ambient temperature.
Refrigerant Quality
Refrigerant is 99.999% pure helium gas with a dew point temperature less than -50° C (-58° F)
at 20.7 bar (300 psig).
Maintenance Intervals
Compressor adsorber: 30,000 operating hours
Clean Outdoor Unit heat exchanger: Twice every year, minimum
Noise Level
Outdoor Unit: < 75 dB(A) at 1m
Weight (approximate)
Outdoor Unit: 142 kg (312 lbs.)
Indoor Unit: 46 kg (102 lbs.)
16
Specifications
(610) 791-6700
17
Specifications
Regulatory Compliance
Declaration of Conformity
I, the undersigned, hereby declare that the equipment specified above conforms to the above Directives.
18
Specifications
19
Specifications
20
Specifications
21
Specifications
Parts Identification
2
3
15
14
4
13
5 12
6
11
7
10
8 9
22
Specifications
16 26
25
24
23
17 22
18
19
21
20
27
35
28
29 34
30
33
31
32
23
Specifications
Indoor Unit
1 Adsorber
2 Control Boards
3 Front Panel Board
4 Alarm Lamp
7 Motor Contactor
8 Fuses FU-1 – FU-3
9 Transformer
10 Voltage Connection Selector (not shown)
16 Cooling Fan
17 Low Pressure Switch and Transducer
18 Compressor Capsule
22 Relief Valve
23 Terminals R, S, T, PE (Cable 1-1)
24 Terminals 1 – 9 (Cable 1-2)
25 Terminals 10 –1 9 (Cable 1-3)
26 ODU Type Connector
24
Specifications
25
Specifications
Fuses
FU-1, 2 and 3
Fuses Fuses
FU-4, 5 and 6 FU-7, 8 and 9
26
INSTALLATION
Introduction
Install the FA-70H Compressor, Gas Lines and Cold Head Cable, and configure the
Compressor Control according to the following procedures.
The following installation procedures are based on standard arrangements of equipment, using
SCAI standard components.
To prevent contaminating the components or the system, it is important to follow the procedures
in this manual step by step.
NOTE
Be sure to have 99.999% pure helium gas available for installation of the system.
See Refrigerant Quality in Specifications.
1. Upon receipt, inspect the shipping containers and the compressor units for damage.
1.1. If there is any evidence of external damage to the container(s), be sure the carrier’s
driver sees the damage. Note it on the shipping documents and have the driver
acknowledge it by his initials on the delivery receipt.
1.2. Remove the compressor units from their shipping containers and inspect for damage. If
there is external damage to the compressor unit(s), remove the covers and check for
internal damage. Notify the carrier immediately and take photographs of the damage to
document your claim to the carrier. Keep the damaged shipping container(s).
NOTE
Retain the shipping containers, if reusable, for returning the components to the
factory if reconditioning is required. If internal damage is suspected, retain the
shipping container(s) for proof to the carrier.
2. Inspect for Proper Charge Pressure (Indoor Unit only)
2.1 View the pressure gauge on the Indoor Compressor Unit front panel. The pressure
gauge should indicate 200 – 207 PSIG at 68°F (13.8 – 14.3 bar at 20°C).
2.2 If the gauge indicates 0 PSIG (0 MPa), the Indoor Compressor Unit cannot be used.
Contact the nearest SHIG Service Center.
27
Installation
3. If the equalization pressure is outside the specified range or there is physical damage to
the compressor enclosure or the compressor has been on its side or upside down for an
extended period of time (more than one hour), contact the nearest Service Center and
notify the delivering carrier of the damage.
NOTE
When checking the compressor for shipping damage, do not connect gas lines and
cold head. The components may become contaminated with compressor oil.
4.1 Inspect the exterior panels of the Compressor Units for evidence of damage.
4.2 If there was external damage to the compressor, remove the compressor unit panels
and check for internal damage. Notify the carrier immediately and take photographs
of the damage to document your claim to the carrier.
4.3 If any irrecoverable damage is found (e.g. oil leakage, panel deformation), contact
the nearest Service Center.
System Configuration
The FA-70 compressor consists of an Outdoor Unit, Indoor Unit, and interconnecting hoses and
electrical cables. It is normally installed as part of a cryogenic refrigeration system additionally
consisting of a Cold Head and interconnecting electrical cables and gas lines. See figure 8. All
of the system components will be shipped in separate shipping containers i.e. Outdoor Unit,
Indoor Unit, Accessories and Cold Head.
NOTE
The FA-70 is a split indoor/outdoor system with components out of sight of each
other and with electrical connections through exterior walls. Installation must
comply with local electrical codes and regulations.
UL Type SOOW/SEOOW/SEOW cords available from SCAI for electrical
connection between the Outdoor and Indoor units are fit for purpose. Where
local codes require alternate wiring methods or devices (such as disconnecting
switches), it is the responsibility of the installer to ensure electrical wiring and
devices are properly selected based on the equipment rating.
Recommendations for installing the system according to the United States
National Electric Code are provided below at the end of this section.
28
Installation
CH Power Cable
Compressor Location
Outdoor Unit
The compressor must be installed base down, within 5 degrees of horizontal. Do not tilt more
than 30 degrees at any time. Using the four (4) anchor bolts, affix the outdoor unit to a level,
concrete or structural steel support base that is suitable for the weight of the unit and is at least
5 cm (2”) in height and well drained. See Figures 9 and 10.
29
Installation
BASE
(concrete,etc.)
360mm
646mm
ANCHOR-BOLT
(M10 x4)
ANCHOR BOLT
(M10 x 4 PLACES)
max. 3cm
min. 5cm
30
Installation
The location should be well-ventilated with an ambient temperature range of -30° C to 45° C
(-22° F to 113° F).
Allow a 30 cm (12”) space behind the unit for air suction, and a 100 cm (39”) space in front of
the unit for air discharge. Allow a 15 cm (6”) space on the left side (when facing the unit) and a
50 cm (20”) space on the right side. Make sure discharge air does not reenter the unit. See
Figure 11 for spacing of a single unit and Figure 12 for spacing of multiple units.
31
Installation
NOTE
Do not position objects or obstacles near the ventilation fan or heat exchanger.
Do not place heat sensitive or flammable objects near the Outdoor Unit.
NOTE
The Outdoor Unit should be installed in an area free from dirt or oil mist to avoid
frequent cleaning of the heat exchanger.
NOTE
Install a snow guard over the Outdoor Unit if it will be exposed to heavy snowfall.
Indoor Unit
Place the compressor indoor unit in a location that is protected from the elements and where the
ambient temperature will always be within the range of 4° C to 40° C (40° F to 104° F).
The indoor compressor unit must be installed base down, within 5 degrees of horizontal, and
preferably at a height convenient for making connections and reading the pressure gauge.
Allow a 60 cm (24”) space in the front and rear of the indoor compressor unit for access to
electrical and gas connections. Allow 60 cm (24”) on the left side (when facing the front) of the
indoor compressor unit for maintenance of the adsorber. See Figure 13 for spacing of the
indoor unit.
32
Installation
33
Installation
19 19
18 18
17 17
16 16
15 CABLE1-3 15
14 14
13 13
12 12
11 11
10 10
9 9
8 8
7 7
6 6
5 CABLE1-2 5
4 4
3 3
2 2
1 1
T T
S S
R CABLE1-1 R
G/PE G/PE
34
Installation
Outdoor Unit
1. Disconnect the mains power supply to the Indoor Compressor Unit (if connected).
2. Remove the Outdoor Compressor Unit’s electrical panel. See Figure 15.
Electrical
Panel
3. At the top of the terminal panel, select the indoor unit type by moving the exposed connector
half to the Indoor Unit Type connector labeled for the correct indoor model. Make sure the
connector latches in place. See Figure 16.
35
Installation
4. Insert Cable1-1, Cable1-2 and Cable1-3 through the holes in the side panel and affix the
cable bushings to the side panel. See Figure 17.
NOTE
It is important that all cables have feed thru bushings that will seal off the opening
from the environment. This is important to keep out insects and animals in
addition to providing a seal against moisture and other environmental elements.
36
Installation
5. Connect the ring terminals of Cable1-1 (R, S, T, PE), Cable1-2 (1-9) and Cable1-3 (10-19)
to the terminal screws provided. Match the wire marking with the screw terminal marking.
The green-colored wire (G/PE) of Cable1-1 is for the ground. Connect it to the screw
marked “PE” at the bottom of the terminal panel near terminal “R”. See Figure 18.
Terminals 10-19
Terminals 1-9
Terminals R, S, T, PE
6. Secure the cables with the internal clamp located at the bottom of the terminal panel
7. Reattach the electrical panel.
37
Installation
Indoor Unit
Side Electrical
Panel
3. Insert Cable1-1, Cable1-2 and Cable1-3 through the holes in the rear panel and affix the
cable bushing to the side panel.
NOTE
It is important that all cables have feed thru bushings that will seal off the opening
from the environment. This is important to keep out insects and animals in
addition to providing a seal against moisture and other environmental elements.
38
Installation
4. At the top of the terminal board, select the outdoor unit type by moving the exposed
connector half to the Outdoor Unit Type connector labeled for the correct outdoor model.
Make sure the connector latches in place.
NOTE
The electronic controller also must be set for outdoor unit type after power is
connected to the unit. See Compressor Control Preparation sections below.
5. Connect the ring terminals of Cable1-1 (R, S, T), Cable1-2 (1-9) and Cable1-3 (10-19) to the
terminal screws provided. Match the wire marking with the screw terminal marking. The
green-colored wire (G/PE) of Cable1-1 is for the ground. Connect it to the screw of the
terminal panel under the “R” terminal. See Figure 20.
Recommended Tightening Torque: R, S, T – 3.0 Nm
1-19 – 0.9 Nm
PE – 3.0 Nm
Cable1-3(10-19)
Cable1-2(1-9)
Cable1-1(R, S, T, PE)
39
Installation
1. Install conduit or cable gland of wiring method approved by local codes and secure to rear
panel.
NOTE
It is important that all cables and conduits have feed thru bushings that will seal
off the opening from the environment. This is important to keep out insects and
animals in addition to providing a seal against moisture and other environmental
elements.
2. Connect field wiring to the mains terminal block and the protective earth connector. See
Figure 21.
Recommended Tightening Torque: L1, L2, L3 Terminal Block – 4.0 N·m (35 in·lbs)
Protective Earth – 2.3 N·m (20 in·lbs)
Figure 21 Connect Field Wiring to Mains Terminal Block and Protective Earth Connector
40
Installation
NOTE
The 480V tap should be used for both 460V and 480V applications.
Before power is supplied, the following procedure must be applied only if the wires need
to be changed to another supply voltage.
SCAI Recommendations for Wiring an FA-70 According to the US National Electric Code
NOTE
Additional local code requirements may apply. Contact a local inspector for any
additional requirements beyond those of the NEC
Male Conector
Female Conector
CH Power Cable
42
Installation
Notes:
Wiring shall be Type THHN or THWN or THHW for commercial type installations rated for
600V. The wiring can be color coded to match existing terminals as well as terminated with
ring terminal connections.
Liquid-tight or rigid conduit connections will need to be installed on the Outdoor Unit, the
Indoor Unit, and Disconnect Housings.
Make sure that the connection between the conduit and the outdoor component housing is
water tight.
43
Installation
Compressor Checkout
After all electrical interconnect cables and power wiring are connected, the compressor should
be operated before the gas lines are connected to the Outdoor Unit.
1. Be sure that the transformer voltage taps are correctly selected to match the supply voltage.
2. Supply power to the compressor. Set the compressor’s Main Power switch to on.
3. Scroll the LCD to show the return pressure. With the compressor off, the pressure should
be the equalization pressure.
4. Push the ON button. Scroll the LCD to show the return pressure. With the compressor
running, but no gas lines connected, the pressure should be between 1.3 and 3.5 bar (20
and 50 psig). Run the compressor for ten (10) minutes and then stop.
NOTE
The compressor has reverse-phase protection to prevent it from running in reverse.
If it does not start and the LCD displays “Phase/Fuse– ERR”, disconnect the power
and interchange any two mains supply wires (except ground). Refer to the
Troubleshooting section in this manual.
NOTE
If the compressor starts but return pressure does not decrease, turn it off
immediately. It could be running in reverse despite the above-mentioned reverse-
phase protection. Contact a Service Center if this occurs.
This completes the checkout of the compressor.
44
Installation
AVOID INJURY. Always wear eye protection when handling pressurized gas
lines and other pressurized equipment. Never apply heat to a pressurized gas
line or other pressurized components.
NOTE
Be sure to have 99.999% pure helium gas available at the installation site in case
gas needs to be added to the system. See Refrigerant Quality in Specifications
in this manual.
1. Arrange the system components so that the gas lines will be protected from stress and
traffic. Observe the minimum bend radius of 180 mm (7") when routing gas lines. Provide
supports where needed.
2. Remove the dust caps from the gas line and gas couplings.
3. Connect the gas lines at the Outdoor Unit, Indoor Unit, indoor helium return line and Cold
Head, using two wrenches to tighten the coupling. Torque all couplings to 47 ± 7 Nm (35 ±
5 ft. lbs.) See Figure 24. Tighten each coupling before proceeding to the next one.
45
Installation
AVOID GAS LEAKS. Check the condition of the gasket seal on the male half of
each Aeroquip coupling. Be sure the gasket seal is in place and the sealing
surfaces on both the male and female halves are clean before connecting.
Replace the gasket seal if it is damaged or missing.
Keep the gas line couplings aligned when making or breaking a coupling
connection. Leaks can occur due to the weight of the gas line or due to a sharp
bend near the connection.
NOTE
Retain the dust caps and plugs to re-cover the couplings when they are not in
use. They protect the couplings from damage and prevent the entry of
contaminants.
5. Using two wrenches, connect the RETURN gas line to the RETURN coupling on the cold
head. Tighten the coupling to 47 ± 7 Nm (35 ± 5 ft. lbs.).
6. Using two wrenches, connect the SUPPLY gas line to the SUPPLY coupling on the cold
head. Tighten the coupling to 47 ± 7 Nm (35 ± 5 ft. lbs.).
The system equalization pressure, shown by the pressure gauge on the indoor unit after all
components have been connected, will determine if charging or venting is required. System
equalization pressure should equal the value provided in the system level manual or the
Specification section of this manual.
Error/warning and data reporting is available simultaneously through the front panel display, the
Diagnostic Interface connection, and the Serial Interface connection.
46
Installation
3. Press the ON front panel control button to change from CNA-61 to FA-70 or from FA-70 to
CNA-61 outdoor unit type.
4. Turn the main power switch off.
Prestart Check
1. Check that all electric connections are made:
a. Interconnecting cables 1-1, 1-2 and 1-3
b. Power to the compressor
c. Cold head cable
d. Diagnostic interface cable or serial cable (if used).
2. Check that the electrical power supply is switched on.
3. Scroll the LCD display up and check the software version display shows the correct outdoor
unit type. (e.g. “FA-70 V3.3” or “CNA61 V3.3”).
4. Check that the equalization pressure is as specified when the compressor is at room
temperature, 20° C (68° F). A change in temperature, higher or lower, will cause a small
change, higher or lower, in the equalization pressure. If the pressure is far from the
specified equalization pressure, the gas charge is incorrect and may indicate a leak or
incorrect filling.
47
Installation
48
Installation
1. In the FA-70 IDU electrical compartment (see Figure 19) the Outdoor Unit Type connector
must be plugged into the plug labeled CNA-61 (see Figure 20).
2. Connect the interconnecting electrical cables per the instructions in this manual. See
Interconnecting Electrical Cables Installation section.
3. Connect the interconnecting helium hoses per the instructions in this manual. See Install
the Gas Lines section.
4. Connect the electrical power per the instructions in this manual. See Electrical Supply
Connection (Indoor Unit) section.
5. Connect electrical cold head cable per the instructions in this manual. See Install the Cold
Head Cable(s) section.
6. Install the CNA-61 ODU per the relevant operating manuals below:
6.1 Service Manual; CD32ZZ-076S
6.2 Technical Instructions; CD32ZZ-078S (for CNA-61D)
6.3 Technical Instructions; CD32ZZ-077S (for CNA-61C)
7. Operate the system per the FA-70 operating instructions. See Operation section.
49
(This page is intentionally blank.)
50
OPERATION
Starting
Supply power to the compressor, turn the knob of the main power switch on the front of the
Indoor Unit to ON, then:
For Front Panel Button Control: Press the ON button located on the front panel under the
LCD. The compressor and cold head will start.
For Diagnostic Interface Control: Provide the necessary run signal as identified in Table 1
in the Troubleshooting section of this manual. The compressor and cold head will start.
For Serial Interface Control: Provide the ON command as identified in the Serial Protocol
and Pin-Outs section of this manual. The compressor and cold head will start.
Stopping
For Front Panel Button Control: Press the OFF button located on the front panel under
the LCD. The compressor and cold head will stop.
For Diagnostic Interface Control: Remove the run signal as identified in Table 1 in the
Troubleshooting section of this manual. The compressor and cold head will stop.
For Serial Interface Control: Provide the OFF command as identified in the Serial Protocol
and Pin-Outs section of this manual. The compressor and cold head will stop.
As desired, turn the main power switch on the front of the compressor to OFF and remove
power to the compressor.
PREVENT EQUIPMENT DAMAGE. Operating the cold head without gas flow may
cause heat buildup that will damage the cold head.
Cold Start
Components
The FA-70 is designed to start at temperatures down to -30°C. The following components are
part of the cold start functionality:
1. Solenoid Oil Bypass Valve (SOBV)
2. Oil Bypass Valves (OBV)
51
Operation
NOTE
See component descriptions in the Introduction section.
Description of Operation
FA-70 with Firmware Version 3.3
If the outdoor unit is located in an environment where the temperature can fall below -5C the
following will occur:
1. If system power is available and the system power switch is turned on and the ambient
temperature is below -5°C, then the SOBV and BOS heater will be energized. This will
provide heat to the oil in the BOS and to the connecting components (i.e. tubing, SOBV,
compressor capsule, etc.) via conduction heat transfer of the oil and metal components.
1.1 The system power must be on for at least 4 hours to allow for the oil and components to
become fully heated.
1.2 If the system power switch is not on or if power to the system is not available these
components will remain de-energized and the components will not receive any heat. The
compressor system can use the auto restart feature to start under these conditions. One
or more compressor auto restarts are needed and should be expected.
2. When the compressor is started and the ambient temperature is below -5°C the SOBV,
OBV’s and BOS heater are employed to direct the heat generated by the heater and the
compressor to the oil in the heat exchanger and to the compressor bearings. This cold start
functionality usually takes about 20 minutes before the compressor system is running
normally for the ambient temperature conditions.
2.1 The fan control system does not allow the fan to operate until the cold start functionality
has completed the cold start sequence
3. The fan control system will then operate in three different modes depending on the ambient
air temperature which is used as the coolant.
3.1 Fan off mode: This is used during cold start and during very cold ambient air conditions.
3.2 Low speed fan: This is used when ambient air conditions are in the cool to normal range.
52
Operation
3.3 High speed fan: This is used when the ambient air conditions are normal to hot.
NOTE
Fan cycling is normal and should be expected.
4. Auto restart feature: As stated in 1.2 above the auto restart feature can be used if the
system power is not on and a cold start is required. In this scenario the operator will activate
the system on and immediately start the compressor. Since the heater has not been on to
provide heat to the oil and components the compressor will start and shutdown on the first
attempt. The auto restart feature will wait 20 minutes and attempt another compressor start.
This will occur up to five times in order to start the compressor system. Depending on
conditions the compressor system will start and remain on after one to five restarts.
The CNA-61 IDU does not support the auto restart feature
53
Operation
54
MAINTENANCE
AVOID INJURY. The Outdoor Unit has a venting fan. Do not insert foreign
substances from the exhaust port under any circumstances. Failing to observe
this precaution may result in serious injury or malfunction.
AVOID INJURY. Do not touch the Outdoor Unit’s cooler fin during fin cleaning.
Touching the sharp edges of the fin may result in serious injury.
Adsorber Replacement
Part required: Adsorber, P/N 00218
Tools required: Open-end wrenches, 1", 1 1/8", 1 3/16", ½”
Snoop®
The compressor’s adsorber should be replaced every 30,000 operating hours (40 months).
The used adsorber has no salvage or repair value. Venting the compressor is not required
when replacing the adsorber because the gas couplings are self-sealing.
Adsorber Removal
1. Stop the compressor and disconnect the power to the Indoor Unit.
2. Disconnect the high pressure (supply) gas line from the helium high pressure coupling on
the Indoor Unit rear panel. Screw a dust plug into the disconnected gas line. Use two
wrenches.
NOTE
Always hold the stationary nut on the gas line coupling with one wrench while
turning the moveable coupling with the other wrench.
3. Remove the Indoor Unit’s cover panel.
55
Maintenance
4. Disconnect the self-sealing coupling on the inlet side of the adsorber. Use two wrenches.
See Figure 25.
5. Use a ½” wrench to remove the nut, lock washer and spacer holding the adsorber to the
base. See Figure 26.
6. Remove the locknut, spacer washer and nylon washer on the Aeroquip supply coupling on
the rear panel. See Figure 27.
56
Maintenance
7. Pull the adsorber back until the supply coupling clears the back panel. Remove the
adsorber. Retain all hardware to reuse with the new adsorber.
AVOID INJURY. The adsorber is charged with helium gas. Follow the used
adsorber venting procedure for safe disposal of the used adsorber.
Adsorber Installation
1. Remove the caps from the gas lines of the new adsorber. Do not vent the new adsorber.
2. Insert the supply coupling through the rear panel and position the adsorber.
3. Insert and tighten the nut, lock washer and spacer to secure the new adsorber to the base.
4. Install the nylon washer and the locknut on the supply coupling. Torque the locknut to 54
Nm (40-ft. lbs.).
5. Connect the adsorber’s self-sealing coupling on its inlet side to the coupling that is
connected to the tubing leading to the helium inlet from the Outdoor Unit. With two
wrenches, torque the Aeroquip coupling to 47 ± 7 Nm (35 ± 5 ft. lbs.).
6. Reconnect the supply (red) gas line to the supply coupling on the Indoor Unit rear panel.
Torque the coupling to 47 ± 7 Nm (35 ± 5-ft. lbs.).
7. Using Snoop®, leak check all Aeroquip couplings just completed. Wipe off the Snoop® to
prevent rusting.
8. Check the equalization pressure. See Specifications section.
9. Reinstall the Indoor Unit’s cover panel.
This completes the procedure for replacing an adsorber.
57
Maintenance
Register New Adsorber (30,000 hour life) (for firmware versions 1.7 or later)
When a new adsorber is installed, the adsorber timer must be reset to 30,000 hours so that the
correct remaining adsorber life will be displayed on the LCD.
The timer can be reset either through the front panel control buttons or through the RS232
terminal interface.
Through the front panel control buttons:
1. With the Main Power switch turned off, press and hold all four control buttons below the
LCD window.
2. Keep these buttons held and turn the Main Power Switch ON to enter “Service Level”
mode. Release the buttons.
3. Scroll using the arrow control buttons until display shows “NEW ADS? ON=Yes.”
4. Press the ON control button. Display will show “SAVE? Y-ON N-OFF.”
5. Press the ON control button again to complete. (Press the OFF control button to back
out of the function.) When ON is pressed, display will show: “Saving New ADS”. When
function is complete, display will again show “NEW ADS? ON=Yes.”
6. Turn the main power switch to OFF to leave Service Level.
Through the RS232 Terminal Communication Interface
1. Turn the compressor main power switch ON.
2. Connect the terminal interface computer to the compressor serial port .
3. Send a “g” to the compressor to register a new adsorber (or, alternately, send an “m” to
the compressor to return the menu of available functions and then send a “g”).
4. Compressor will return “Are you sure? Y/N” Send a “Y” to complete the function. (“N”
will back out of the function with compressor returning “Aborted”.)
5. When the function is complete, the compressor will return “Adsorber change registered.”
58
Maintenance
Replace Fuses
Parts required: Internal fuse kit, FA-70H (high volt only), SCAI P/N 268874A, including
(3) Power fuses, 1.0 ampere, 600 V, class CC, SCAI P/N 34162
(3) Control Power fuses, 1.25 ampere, 250 V, IEC 60127 Type T SCAI
P/N 34175, and
(3) Control Power fuses, 0.63 ampere, 250 V, IEC 60127 Type T, SCAI
P/N 34687
Three (3) 1.0 AT Class CC time delay fuses, FU-1, FU-2 and FU-3, are located in the Indoor
Unit’s electrical chassis box. See Figure 7.
Three (3) 0.63 AT fuses, FU-4, FU-5 and FU6, and three (3) 1.25 AT fuses, FU-7, FU-8 and
FU-9, are located on the Indoor Unit’s front panel. See Figure 7.
If the LCD display reads Phase Seq-ERR, check all fuses FU-1 through FU-9. If no phase
sequence error is indicated but the diagnostic interface connection signals are behaving
erratically or the compressor will not run or build pressure, check fuses FU-1 through FU-3.
1. Disconnect the power to the Indoor Unit.
For fuses FU-1, FU-2 and FU-3:
2. Remove the Indoor Unit’s electrical panel cover.
3. Remove, inspect or check each fuse to find a blown fuse(s). Replace the defective fuse(s).
4. Reinstall the Indoor Unit’s cover.
For fuses FU-4 through FU-9:
5. Remove each fuse from the Indoor Unit’s front panel and inspect to find a blown fuse.
Replace the defective fuse(s).
6. Reconnect the power to the compressor.
59
Maintenance
A soft brush or soft brush attachment may be used to help remove dust.
60
TROUBLESHOOTING
Error/Warning Conditions
An error condition will cause the alarm lamp to illuminate, an “ERR” message and a shutdown.
A warning condition will cause the alarm lamp to illuminate and a “Warn” message. The
following table lists the alarm and the alarm/shutdown errors that are monitored. Overload trip
of the Mains Power switch (described below) is not monitored or reported.
Return Pressure- Alarm/ Loss of gas charge Return pressure < 15 psig.
ERR Shutdown
If the compressor has been shut down by one of these interlocks, do not restart until the
problem has been found and corrected. Refer to the Troubleshooting Guide to identify the
problem.
In the event of a shutdown error, the compressor motor and cold head valve motor are
turned off. The controller will communicate the error condition via signals at the System
Diagnostics Connector, via the LCD Display/Alarm Lamp and via the Serial interface. See
Figure 2, Table 1 and the Serial Protocol and Pin-Outs section.
The Mains Power switch trips when steady-state current exceeds 1.2 x the front panel set
point. When tripped, the switch knob locates halfway between the on and off positions.
61
Troubleshooting
Troubleshooting Guide
The Troubleshooting Guide that follows lists problems that can occur in the system and
suggests causes and corrective actions.
Problem Possible Cause Corrective Action
System shutdown LCD reads Low oil level or blocked oil Try five times to restart the
Helium Temp-ERR or circulation. compressor. If it does not
Helium Temp-Warn start, consult a Service
Center.
Ambient air temperature is too Operate compressor when
high. outdoor air temperature is
between -30 and 45° C.
Outdoor unit air flow is Clean heat exchanger or
blocked or restricted. remove restriction.
Faulty gas thermistor or Contact a Service Center.
control board.
62
Troubleshooting
LCD reads FAIL instead of Sensor is disconnected. Wrong outdoor unit or indoor
ERR. unit type is selected. Select
correct unit type. (See
Installation section.)
Compressor and cold head No electrical power. Check that the power source
motor do not start when the is on and connected.
start switch on the
compressor is pushed.
Wrong voltage. Compare customer’s electric
service with system
specifications.
Main power phase sequence Interchange any two- (2)
is wrong. incoming power leads (except
ground.
63
Troubleshooting
System starts but gas Wrong equalization pressure. Refer to Specifications and
pressure is abnormally high or the section on Charging or
low. Venting.
Gas line couplings are not Be sure that all gas couplings
fully engaged. are fully engaged and
torqued.
Gas lines are connected Reconnect gas lines at correct
wrong. connection.
Cold head motor does not Cold head cable is not Stop the compressor.
start when the compressor connected. Connect the cable. Check
starts. connections at the cold head
and at the compressor.
Open circuit in the cold head Disconnect the cable. Check
cable. each conductor for continuity.
Replace the cable if
necessary.
FU-4, FU-5 or FU-6 fuse is Contact a Service Center to
blown. have a qualified electrical
technician replace the fuse
inside the electrical enclosure.
Cold head motor hums but Open circuit in the cold head Disconnect the cable. Check
does not start. cable. each conductor for continuity.
Replace the cable if
necessary
Valve disc stalled on the valve Check the system
stem. equalization pressure.
Consult a Service Center.
FU-4, FU-5 or FU-6 fuse is Contact a Service Center to
blown. have a qualified electrical
technician replace the fuse
inside the electrical enclosure
64
Troubleshooting
Compressor shuts down, LCD FU-1, FU-2, or FU-3 fuse is Have a qualified electrical
display is blank blown. technician replace the fuse
inside the electrical enclosure.
Malfunctioning control boards. Contact a Service Center.
65
Troubleshooting
66
Troubleshooting
67
Troubleshooting
68
Troubleshooting
Pin # Function
1 Alternate +485
2 Alternate -485
3 Reset. System error/warning conditions are cleared by momentary application of a
+24VDC, 2 mA signal to this pin.
4 Cold head pause. The cold head only will turn off while a +24VDC, 2 mA signal is
applied to this pin if the system was turned on remotely (pin 6). The cold head will
restart when the signal is removed.
6 System ON/OFF. The compressor and cold head will turn on when +24VDC, 2 mA
signal is applied to this pin. They will turn off when the signal is removed.
7 Cable configuration fault high. When electrical continuity (< 20 ohms) is applied
between pins 7 and 8, system will turn off in fault condition.
8 Cable configuration fault low. See Pin 7 description.
10 Compressor return pressure analog value, 0.5-4.5 VDC linear relative to pin 24: PSI
Absolute = 125 x (volts) – 47.8
11 Not active. 0 VDC, 20 mA max. signal.
12 Protective earth ground
13 Protective earth ground
14 Not active.
15 Not active.
16 Low pressure shutdown. On a compressor return low pressure error (<15 psig) this pin
will carry a +24 VDC, 20 mA max. signal.
17 Power error. On a phase or fuse error, this pin will carry a +24VDC, 20 mA max. signal.
18 Gas temp error. On a high helium gas discharge temperature error, this pin will carry a
+24VDC, 20 mA max. signal.
19 Run status. When the compressor and cold head are running or the compressor is
running with the cold head paused, this pin will carry a +24VDC, 20 mA max. signal.
20 Motor winding temperature error. On a high compressor motor winding temperature
error, this pin will carry a +24VDC, 20 mA max. signal.
24 0 VDC, 100 mA signal power source. (Connected to earth ground)
25 +24VDC, 100mA signal power source.
69
(This page is intentionally blank.)
70
SERIAL PROTOCOL AND PIN-OUTS
General Information
This section describes the FA-70 compressor serial interface only. It does not describe overall
operation or safety of the FA-70 compressor. Please refer to the operating manual for operating
instructions and warnings. The information in this section should be used only after safe
operation of the FA-70 compressor is understood.
The FA-70 sends no unsolicited messages. It only responds to commands from a host
computer.
NOTE
Serial commands that change operation of the FA-70 compressor (on, off, reset,
cold head run, cold head pause and pause off) have equal value as front panel
key press control. The FA-70 will respond equally to either source of control
input in the order in which it is received.
NOTE
There are no error routines or checks to prevent possible conflicts if a
compressor is both connected to a diagnostic interface (Dsub 25) control
element and a serial control element. Active Dsub 25 operating signals (+24V
applied) will take priority over front panel key press and serial control.
Serial Command List (See the Command Set section below for command descriptions
and examples)
1. Information Commands
$TEA: Read all temperatures $TEn: Read temperature n (n = 1, 2 ,3, or 4)
$PRA: Read all pressures $PRn: Read pressure n (n = 1 or 2)
$STA: Read status bits $ID1: Read firmware version and elapsed operating hours
2. Operating Commands
$ON1: On $OFF: Off
$RS1: Reset $CHR: Cold head run
$CHP: Cold head pause $POF: Cold head pause off
71
Serial Protocol and Pin-Outs
Command Structure
The individual bytes of any communication packet (frame) are restricted to the ASCII domain of
0x20 (20H, space) through 0x7E (7EH, tilde), plus 0x0D (carriage return).
The basic communication frame from the host computer to the FA-70 compressor is comprised
of a start character, a command mnemonic, data (if required), checksum, and a message end
character.
START
END
COMMAND DA TA CRC-16
IF REQUI RED
End of message: This is always 0x0D (0DH carriage return). This assures that the end of
message character falls outside the standard text domain and will not
be incorporated in commands, data, or checksums.
The response frame from the FA-70 compressor is similar to the command frame, but includes
delimiters between the various fields.
COMMA
COMMA
COMMA
START
END
72
Serial Protocol and Pin-Outs
End of message: This is always 0x0D (0DH carriage return). This assures that the end of
message character falls outside the standard text domain and will not
be incorporated in commands, data, or checksums.
Command Set
$TEA: Read all temperatures
Command with checksum and carriage return = $TEAA4B9<cr>
Response: $TEA,T1,T2,T3,T4,<crc-16><cr>
The temperature fields are always 3 characters long and are rounded to the nearest
degree. Temperatures less than 100 °C have leading zeroes.
73
Serial Protocol and Pin-Outs
P1 is the compressor return pressure in PSIG. P2 is inactive (returns “000”) for most
FA-70 variants.
The pressure fields are always 3 characters long and are rounded to the nearest whole
number. Pressures less than 100 psig have leading zeroes.
The status bits are contained in a four character field that is the ASCII hex equivalent of
a 16 bit word. For example, a status bit field of "0301" is equivalent to a binary
'0000001100000001". The left most character is the MSbit. Bits are defined as follows:
Bit 14 - spare.
Bit 13 - spare.
Bit 12 - spare.
Bit 9 - LSbit of state number. The state number reflects the state of operation:
74
Serial Protocol and Pin-Outs
NOTE
Remote ON and OFF are states accessed exclusively with the Dsub 25
Diagnostic Interface connector. Serial on, off, and reset commands operate as
Local states.
Bit 4 - 1 = Outdoor Unit Temperature alarm. 0 = no alarm. (CNA-61 Outdoor Unit only)
The version number is a three character text field corresponding to the firmware version.
The elapsed hours are an eight character text field corresponding to elapsed operating
hours (including tenths) with preceding 0’s.
$ON1: On
Command with checksum and carriage return = $ON177CF<cr>
Response: $ON1,<crc-16><cr>
When the compressor is off and without active fault, this will turn the compressor and
cold head on. If the command is sent while the compressor is in other states, the
response will be returned, but no action will occur.
$OFF: Off
Command with checksum and carriage return = $OFF9188<cr>
Response: $OFF,<crc-16><cr>
75
Serial Protocol and Pin-Outs
When the compressor and/or cold head is on, this will turn either or both off. If the
command is sent while the compressor and cold head are off, the response will be
returned, but no action will occur.
$RS1: Reset
Command with checksum and carriage return = $RS12156<cr>
Response: $RS1,<crc-16><cr>
Clears fault indications from the serial status response, Dsub 25 diagnostic interface,
and LCD display, and, if the compressor is in Fault Off state (off because of fault),
compressor will go to OFF state. If the command is sent while no faults are indicated or
not in Fault Off state, the response will be returned, but no action will occur.
When the compressor is off, this will turn on the cold head only. If no subsequent off
command is received, the cold head will turn off automatically after 30 minutes. If the
command is sent while the compressor is not in an Off state, the response will be
returned, but no action will occur.
When the compressor and cold head are on, this will turn off the cold head only. If the
command is sent while the compressor is not in an On state, the response will be
returned, but no action will occur.
When the compressor is on with the cold head off (Cold Head Pause state), this will turn
the cold head back on (return to normal ON state). If the command is sent while the
compressor is not in Cold Head Pause state, the response will be returned, but no action
will occur.
Every time the controller receives an end of message character (carriage return), it
checks the preceding message for errors. These include: lack of a message start
character, unrecognized mnemonic, incorrect message length, invalid checksum. If
any of these fail the check, then the controller responds with the above "error"
message.
76
Serial Protocol and Pin-Outs
CRC Generation
1. CRC-16 ANSI (also MODBUS) is used. The CRC-16 is first started by pre-loading a 16 bit
register with all 1's. The process begins by applying successive 8-bit bytes of the message
to the current contents of the register. Only the eight bits of the data in each character are
used for generating the CRC. Start, stop, and parity bits do not apply to the CRC.
During generation of the CRC, each 8-bit character is Exclusive-ORed (XORed) with the
register contents. Then the result is shifted in the direction of the least significant bit (LSB),
with a zero filling the most significant bit (MSB). The LSB is then examined. If the LSB is a
1, the register is XORed with a preset fixed value (A001h). If the LSB is a 0, then no XOR
takes place.
This process is repeated until eight shifts have been performed. After the last shift, then the
next 8-bit message byte is XORed with the 16-bit register. The eight-shift processes above
are repeated.
After all of the message bytes have been XORed and shifted, the result is the CRC.
2. A pre-formatted indexed table of read-only values can be XORed with the 16 bit register as
a substitute for the iterative shift-and-XOR-with-A001h process described above. Example
C code for this method is given here:
77
Serial Protocol and Pin-Outs
78
PARTS
Ordering
The nameplate fastened to the compressor identifies the components as follows:
Model Number
Part Number
Customer’s Part Number (when applicable)
Serial Number
Date of Manufacture
Furnish this complete information when ordering parts. Also, order parts by part number and
name.
NOTE
Be sure to have 99.999% pure helium gas available for servicing the system.
79
(This page is intentionally blank.)
80