Relase Date: 2016. 6. / Manual Revision: 1.

01

User's Manual

Copyright © 2016 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
Multi-Way Control Communication Unit (ETR306) Release Note

Release Note :

[April, 2016] Ver1.00


Multi-Way Control Communication Unit ETR306 User's manual is created.

[Jun. 2016] Ver1.01


Modifying tables([Table 4-4] Digital Output Connector, [Table 4-5] Digital Input
Connector Pin(Common Part), [Table 4-6] Digital Input Connector Pin(Circuit
Part))

ii ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Table of Contents

Release Note ii

Table of contents iii

Safety precautions v

1. INTRODUCTION 1
2. TECHNICAL SPECIFICATIONS 2
2.1. Usage Condition 2
2.2. Input & Output 2
2.3. Insulation strength 3
2.4. Communication Port 3
3. DIMENSIONS AND CONSTRUCTION 4
4. SIDE PANEL CONSTRUCTION 5
4.1. Current Input Connector 6
4.2. Voltage Input Connector 7
4.3. Digital Output Connector 8
4.4. Digital Input Connector 9
4.4.1. Common Connector 9
4.4.2. Circuit Connector 9
4.5. Power Input Connector 10
4.6. TD Input Connector 11
4.7. Communication Port (COM PORT) 12
4.7.1. Port for Main Device Communication 12
4.7.2. Maintenance Port 12
4.7.3. RS485 Communication Port 13
4.7.4. Ethernet Port 13
5. USER INTERFACE PANEL 14
5.1. User defined LED Part 15
5.2. Common Control Part 16
5.3. Local Control Part 17
5.4. Open/Close Operation Part 17
5.5. Fault Indication Part 18
5.6. System & LCD Control Part 19
5.6.1. Communication Status Indication Part 20

iii ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

5.6.2. Menu Control Part 20


5.6.3. Other Control Parts 21
6. LCD CONTROL MANUAL 22
6.1. LCD Screen 22
6.2. Control Key 22
6.3. LCD Menu Structure Tree 23
6.3.1. Menu Tree Structure for Switch Part(SW) 23
6.3.2. Menu Tree Structure for Circuit Breaker Part(CB) 24
6.3.3. Common Menu Tree Structure 25
6.4. Initial Screen 26
6.5. Common Main Menu(COM) 28
6.5.1. GLOBAL SETTING 28
6.5.2. EVENT 86
6.5.3. MAINTENANCE 90
6.5.4. TIME 92
6.5.5. STATUS 92
6.5.6. METERING 95
6.6. Circuit Main Menu(CIRCUIT) 97
6.6.1. GROUP SETTING 97
6.6.2. MONITORING 141
6.6.3. EVENT 145
6.6.4. MAINTENANCE 152
6.6.5. STATUS 156
6.6.6. METERING 157

APPENDIX A. TIME CURRENT CURVES 160


APPENDIX B. MENU DESCRIPTION & DEFAULT SETTING 185
APPENDIX C. LOGIC BIT ATTRIBUTES & DESCRIPTION 202

iv ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Safety notice
Safety notice is to operate product safely and
correctly by preventing any accident or danger
before hand.

Safety notice is divided into two kinds, "WARNING"


and "CAUTION" and meanings are as following:

WARNING
Injury or loss of life can happen in case of
violating this sign

CAUTION
Minor injury or product damage can happen in case
of violating this sign

v ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

WARNING
 Do not work on wiring when power is on or
while machine is operating.
It could cause an electric shock. In addition, protection element can be
triggered.

 Avoid any kind of wiring work when bus bar is


live.
Damage or fire due to an electric shock and charging voltage can happen.

 Conduct grounding.
Not conducting grounding might cause electric shock.

 Do not disassemble product even when power is


off.
It could cause electric shock from charging current inside product.

 Do not operate switch with wet hands.


It could cause electric shock.

 Do not use a product that has a damaged cable


cladding.
It could cause electric shock.

 Work on terminal when cable is disconnected.


It could cause electric shock from exposed part of cable.

vi ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

CAUTION
 Approve power of product's P.N power terminal so
that it suits polarity and rating.
Not following rated specification might cause damage or fire in product.

 Do not allow materials such as screw, stone, oil and


etc. inside product.
It could cause damage and fire in product.

 Follow rated load specification of input and output


contact.
It could cause damage and fire in product.

 Confirm terminal number when connecting input and


output terminal.
In case wiring is not connected properly, it could cause product damage or fire.

 When installing or repairing, it shall be performed


by a specialist.
Malfunction or accident can happen due to improper installation.

 Specifications to be checked prior to power


insertion
Check voltage and polarity of control power.
Check connection of input and output terminal.

 Matters that require attention when storing and


treating
Store in a place with no humidity and dust.
Do not apply force or throw when transporting.

vii ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1. INTRODUCTION
ETR306 is installed in 22.9kV-Y/△ multi way of switchgear(combination of circuit
breaker and switch) of distribution line and can be controlled locally or remotely.
It is compact as product is produced as slim type.

ETR306 receives measured signal and status information from each way of
switchgear and its controller. So it can inspect voltage and current flow on
distribution line. It can remotely transmit distribution line status such as FI
detection, single line/phase loss, live/dead line, phase discordance, over current,
direction of tidal flow, direction of fault detection as well as condition of each
way of switchgear and its controller.

Because it can supports to receive remotely control command from each way of
switchgear breaker distribution automation system is perfectly supported. It can
be easily applied for user's communication environment through various
communication method (DNP3.0, MODBUS, IEC60870-5-101/104 option) support.

ETR306 provides various system operation information required by analyzing fault


record, operation record, fault waveform, load record and other event save
functions.

Control switch on front panel can be used to operate manual open/close for each
way of switchgear, and select fault detect/restrain, ground detect normal/restrain,
control select local/remote, and control lock/unlock operation mode.

ETR306 has a PLC (Programmable Logic Control) changed by user. The PLC can
control input and output using information of timer, counter and internal event.

INTERFACE SOFTWARE is easy to use and things such as set value and
operation record can be saved and administered in PC. It is useful for fault
analysis since it has an excellent zoom function and it has a function that
Indicate fault waveform and digital operation factor status together with time.

1 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

2. TECHNICAL SPECIFICATIONS
2.1. Usage Condition
Conditions of use
 Maximum 70℃, minimum -25℃, elevation below 1,000m

2.2. Input & Output


Power
 Input voltage : DC 24V(Normal using range: 19V ~ 29V)
 Power consumption : Below 20W

Current Transformer Input (CT)


 Measurement rating : AC 0.6A nominal, AC 1.2A continuous, AC 20A 1second
 Measurement burden : Below 0.5VA (0.6A)

Voltage Transformer Input (PT)


 Measurement rating : AC 4V(50~150%)
 Measurement burden : 0.002VA

Control Input
 Control Inputs 24 channel
 Nominal Voltages and Operating Range
 250Vdc (-15%, +20%)
 125Vdc (-15%, +20%)
 48Vdc (-15%, +20%)
 24Vdc (-15%, +20%)―standard
 Operating current : < 5mA at Nominal Voltages

Output Contacts
 Outputs 20 Channel
 350Vdc Varistor for differential surge protection
 Make : 30A
 Carry : 6A Continuous Carry
 Break Capacity
- 125V 0.3A L/R=25ms

2 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

2.3. Insulation strength


Power frequency withstand voltage (IEC 60255-27)
 CT input, VT input, control power input & relay output : AC 60㎐, 2㎸/1
minute

Impulse withstand (IEEE 62.45)


 Current(CT sign) : 6㎸(1.2×50㎲)/3㎄(8×20㎲)
 Voltage(PT sign), status contact, control contact : 4㎸(1.2×50㎲)/2㎄(8×20㎲)

Surge Withstand Capability(ANSI/IEEE C37.90.1)


 EFT/BURST test: 4㎸(2.5㎑)
 Oscillation SWC test: 2.5㎸(1㎒)

Insulation resistance test(IEC 60255-27)


 Above 500㏁

Resistance to radio frequency radiation test(ANSI/IEEE C37.90.2)


 35V/m, 25㎒~1000㎒

2.4. Communication Port


[Table 2-1] Communication Port
RS232, 1200~19200bps, None, Odd or Even Parity, 7 or
Front Panel Port1 8 Data bits, 1 or 2 Stop bit
DNP 3.0 Protocol
RS485/422, 1200~19200bps, None, Odd or Even Parity,
Side Panel Port2 7 or 8 Data bits, 1 or 2 Stop bit
DNP 3.0 Protocol
RJ-45, 10BASE-T/100BASE-T
Side Panel Port3
DNP 3.0 Protocol
RS232, 1200~57600bps, No Parity, 8 Data Bits, 1 Stop
Front Panel PortF bit
ETR306 Interface Software

3 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


ENTEC ELECTRIC & ELECTRONIC CO., LTD.
SW

SW

SW
CB

CB

CB

<Figure 3-1> ETR306 Construction and Dimensions


3. DIMENSIONS AND CONSTRUCTION

CONTROL
MON
COM
ENT

RESET
FUN

LAMP

OPEN

OPEN

OPEN

OPEN

OPEN

OPEN
DOWN

CUIT
CIR
UP

RE MOTE/LOCAL

EARTH

EARTH

EARTH

EARTH

EARTH

EARTH
BATT
T EST

CLOSE

CLOSE

CLOSE

CLOSE

CLOSE

CLOSE
AC POW ER OK

CHARGER OK

BATTERY OK

CB BLOCK

DSP LINK

CPU LINK

GROUND
GROUND

GROUND

GROUND

GROUND

GROUND
Multi-Way Control Communication Unit (ETR306)

PROTECTION
PROTECTION

PROTECTION

PROTECTION

PROTECTION

PROTECTION
1 LIVE

2 LIVE

3 LIVE

4 LIVE

5 LIVE

6 LIVE

79RS

79CY

79RS

79CY

79RS

79CY

79RS

79CY

79RS

79CY

79RS

79CY
PORT F

P 1 RTS/CTS

51

50

51

50

51

50

51

50

51

50

51

50
Run/Reset

/DIAG

P 1 RX/TX

P 2 RX/TX

N
1

6
M 2.5

M 2.5
2TX
IN101 103 105 107 108 COM 2RX
OUT101 102 103 104 OUT105 106 107 108 - 1TX
RS232(PORT1) ETHERNET(PORT3)
RS485(PORT2) 1RX
+
M2.5

M2.5
950-8 950-8 950-8 950
A 02 03 04 05 06 07 08 B 02 03 04 05 06 07 08 09 10 C 02 03 04 05 06 07 08 09 10 P N SG
IN201 203 205 207208 COM IN209 211 213 215 216 COM IN217 219 221 223 224 COM
D C1(mA) DC2(mA) DC3(V) DC4(V) OUT201 202 203 204 OUT205 206 207 208 OUT209 210 211 212 - - -
+ + +
950-8 950-8 950-8 950-8 950-8 950-8 950-8
K 02 03 04 05 06 07 08 E 02 03 04 05 06 07 08 F 02 03 04 05 06 07 08 G 02 03 04 05 06 07 08 H 02 03 04 05 06 07 08 09 10 I 02 03 04 05 06 07 08 09 10 J 02 03 04 05 06 07 08 09 10
1IA 1IB 1IC 1IG 2IA 2IB 2IC 2IG 3IA 3IB 3IC 3IG 4IA 4IB 1IC 4IG 1VA V B VC 2VA VB VC 3VA VB VC 4VA VB VC VG
950-8 950-8
R 02 03 04 05 06 S 02 03 04 05 06 T 02 03 04 05 06 U 02 03 04 05 06 V 02 03 04 05 06 07 08 W 02 03 04 05 06 07 08 09 10
POWER IN 5IA 5IB 5IC 5IG 6IA 6IB 6IC 6IG 5VA VB VC 6VA VB VC
+24V 0V +24V 0V ZG FG

M 2.5

M 2.5
950-8
P 02 03 04 05 06 X 02 03 04 05 06 Y 02 03 04 05 06 Z 02 03 04 05 06 07 08

4
Multi-Way Control Communication Unit (ETR306)

4. SIDE PANEL CONSTRUCTION


ETR306 provides connectors for control, modem and its placement is as follows.

M2.5

M2.5
2TX
IN101 103 105 107 108 COM 2RX
OUT101 102 103 104 OUT105 106 107 108 - 1TX
RS232(PORT1) ETHERNET(PORT3)
RS485(PORT2) 1RX
+
M2.5

M2.5
950-8 950-8 950-8 950

A 02 03 04 05 06 07 08 B 02 03 04 05 06 07 08 09 10 C 02 03 04 05 06 07 08 09 10 P N SG
IN201 203 205 207 208 COM IN209 211 213 215 216 COM IN217 219 221 223 224 COM
DC1(mA) DC2(mA) DC3(V) DC4(V) OUT201 202 203 204 OUT205 206 207 208 OUT209 210 211 212 - - -
+ + +
950-8 950-8 950-8 950-8 950-8 950-8 950-8

K 02 03 04 05 06 07 08 E 02 03 04 05 06 07 08 F 02 03 04 05 06 07 08 G 02 03 04 05 06 07 08 H 02 03 04 05 06 07 08 09 10 I 02 03 04 05 06 07 08 09 10 J 02 03 04 05 06 07 08 09 10

1IA 1IB 1IC 1IG 2IA 2IB 2IC 2IG 3IA 3IB 3IC 3IG 4IA 4IB 1IC 4IG 1VA VB VC 2VA VB VC 3VA VB VC 4VA VB VC VG

950-8 9 50-8

R 02 03 04 05 06 S 02 03 04 05 06 T 02 03 04 05 06 U 02 03 04 05 06 V 02 03 04 05 06 07 08 W 02 03 04 05 06 07 08 09 10

POWER IN 5IA 5IB 5IC 5IG 6IA 6IB 6IC 6IG 5VA VB VC 6VA VB VC

+24V 0V +24V 0V ZG FG
M2.5

M2.5
9 50-8

P 02 03 04 05 06 X 02 03 04 05 06 Y 02 03 04 05 06 Z 02 03 04 05 06 07 08

<Figure 4-1> Side Panel

In addition, cable standard for usage connector is as follows.

[Table 4-1] Cable for Connector Usage

Classification Standard( ㎟ ) Plug Type Remarks

Current 1.25 AKZ 960-8P

Power 1.25 AKZ 960-6P


*. Maker:
Digital Input 0.75 AKZ 950-10P Phoenix
Mecano
Digital Output 1.25 AKZ 950-10P,8P

Voltage 0.75 AKZ 950-10P,8P

5 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4.1. Current Input Connector


Current connector is arranged in order of the number for each way of
switchgear. No. 1 connector for each way of switchgear matches with phase A
and goes along in B, C, N current connector order. Near the current connector
part, name of each way of switchgear and phase is stated.

1IA 1IB 1IC 1IG 2IA 2IB 2IC 2IG 3IA 3IB 3IC 3IG 4IA 4IB 1IC 4IG

R 02 03 04 05 06 S 02 03 04 05 06 T 02 03 04 05 06 U 02 03 04 05 06

5IA 5IB 5IC 5IG 6IA 6IB 6IC 6IG

X 02 03 04 05 06 Y 02 03 04 05 06

<Figure 4-2> Current Connector

[Table 4-2] Current Connector Pin


Pin 1IA 1IB 1IC 1IG 2IA 2IB 2IC 2IG
PhaseA PhaseB PhaseC Ground PhaseA PhaseB PhaseC Ground
Description
1 Way 2 Way
Pin 3IA 3IB 3IC 3IG 4IA 4IB 4IC 4IG
PhaseA PhaseB PhaseC Ground PhaseA PhaseB PhaseC Ground
Description
3 Way 4 Way
Pin 5IA 5IB 5IC 5IG 6IA 6IB 6IC 6IG
PhaseA PhaseB PhaseC Ground PhaseA PhaseB PhaseC Ground
Description
5 Way 6 Way
Maker : Phoenix Mecano
Remark
Type : STLZ960/8-7.62

6 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4.2. Voltage Input Connector


Voltage connector is a part of injected 3 phase (A, B, C) voltage and zero
voltage for each way of switchgear and is composed in follows.

1VA VB VC 2VA VB VC 3VA VB VC 4VA VB VC VG

950-8 950-8

V 02 03 04 05 06 07 08 W 02 03 04 05 06 07 08 09 10

5VA VB VC 6VA VB VC

950-8

Z 02 03 04 05 06 07 08

<Figure 4-3> Voltage Connector

[Table 4-3] Voltage Connector Pin


Pin 1VA 1VB 1VC 2VA 2VB 2VC
Phase A Phase B Phase C Phase A Phase B Phase C
Description
1 Way 2 Way
Pin 3VA 3VB 3VC 4VA 4VB 4VC
Phase A Phase B Phase C Phase A Phase B Phase C
Description
3 Way 4 Way
Pin 5VA 5VB 5VC 6VA 6VB 6VC
Phase A Phase B Phase C Phase A Phase B Phase C
Description
5 Way 6 Way
Pin VG
Description Zero Sequence Voltage(V0)
Maker : Phoenix Mecano
Remark
Type : STLZ950/8-5.08, STLZ950/10-5.08

7 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4.3. Digital Output Connector


Digital output(DO) part is composed of a total of 12 relay outputs. Digital output
connector, as a part that outputs command of control part, is composed in
follows.

OUT101 102 103 104 OUT105 106 107 108

950-8 950-8

A 02 03 04 05 06 07 08 B 02 03 04 05 06 07 08 09 10

OUT201 202 203 204 OUT205 206 207 208 OUT209 210 211 212

950-8 950-8 950-8

E 02 03 04 05 06 07 08 F 02 03 04 05 06 07 08 G 02 03 04 05 06 07 08

<Figure 4-4> Digital Output Connector

[Table 4-4] Digital Output Connector Pin


Pin OUT101 OUT102 OUT103 OUT104 OUT105 OUT106 OUT107 OUT108
Batt'
Spare Spare Spare Spare Spare Spare Spare
Description test
COMMON
Pin OUT201 OUT202 OUT203 OUT204 OUT205 OUT206 OUT207 OUT208
Close Open Close Open Close Open Close Open
Description
1 Way 2 Way 3 Way 4 Way
Pin OUT209 OUT210 OUT211 OUT212
Close Open Close Open
Description
5 Way 6 Way
Maker : Phoenix Mecano
Remark
Type : STLZ950/8-5.08, STLZ950/10-5.08
※. NOTE ) This description is applicable to factory default PLC. Following PLC
setting for user’s purpose or specific usage required, above
description can be changed.

8 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4.4. Digital Input Connector


Digital input (DI) part receives 24 status signals in total by using electrically
insulated contacts. At same time of making surge strength in DI part higher, it is
used to insulate signal connection with weak Main Module. Digital input
connector, as a part that receives status input from control part, is composed in
follows.

4.4.1. Common Connector

IN101 103 105 107 108 COM


-
+
950-8

C 02 03 04 05 06 07 08 09 10

<Figure 4-5> Digital Input Connector(Common Part)

[Table 4-5] Digital Input Connector Pin (Common Part)


Pin IN101 IN102 IN103 IN104 IN105 IN106 IN107 IN108 COM
AC DC Door Gas
Description Spare Spare Spare Spare Common
Error Error Open Low
Maker : Phoenix Mecano
Remarks
Type : STLZ950/10-5.08

※. NOTE ) 1. AC Error : Input when AC power is lost.


2. DC Error : Input when AC power is lost and battery over
discharges (input 30 secs before power breaking).
3. This description is applicable to factory default PLC. Following
PLC setting for user’s purpose or specific usage required, above
description can be changed.

4.4.2. Circuit Connector


IN201 203 205 207 208 COM IN209 211 213 215 216 COM IN217 219 221 223 224 COM
- - -
+ + +
950-8 950-8 950-8

H 02 03 04 05 06 07 08 09 10 I 02 03 04 05 06 07 08 09 10 J 02 03 04 05 06 07 08 09 10

<Figure 4-6> Digital Input Connector(Circuit Part)

9 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

[Table 4-6] Digital Input Connector Pin(Circuit Part)


Pin IN201 IN202 IN203 IN204 IN205 IN206 IN207 IN208 COM

Closed Open Ground Aux Closed Open Ground Aux


Description Common
1 Way 2 Way
Pin IN209 IN210 IN211 IN212 IN213 IN214 IN215 IN216 COM

Closed Open Ground Aux Closed Open Ground Aux


Description Common
3 Way 4 Way
Pin IN217 IN218 IN219 IN220 IN221 IN222 IN223 IN224 COM

Closed Open Ground Aux Closed Open Ground Aux


Description Common
5 Way 6 Way
Maker : Phoenix Mecano
Remarks
Type : STLZ950/10-5.08

4.5. Power Input Connector


Power connector is an input terminal to supply operation power for control part
and is composed in follows.

POWER IN [Table 4-7] Power Input Connector Pin


+24V 0V +24V 0V ZG FG
Pin +24V 0V +24V 0V ZG FG
Descriptio Surge Frame
+24V 0V +24V 0V
n ground ground
P 02 03 04 05 06 Maker : Phoenix Mecano
Remarks
Type : STLZ950/6-7.62
<Figure 4-7> Power Connector

10 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4.6. TD Input Connector


TD input connector is a terminal to input DC analog value and is composed in
following way.

DC1(mA) DC2(mA) DC3(V) DC4(V)

950-8

K 02 03 04 05 06 07 08
<Figure 4-8> TD Input Connector

[Table 4-8] TD Input Connector Pin


Pin DC01 DC02 DC03 DC04
Charging circuit
Spare 1 Spare 2 Battery voltage
Description voltage
Current type: 4~20mA Voltage type: 0~35V
Maker : Phoenix Mecano
Remarks
Type : STLZ950/8-5.08
※. NOTE ) DC3 and DC4 is used for measurement of battery voltage and charge
circuit voltage and for determination of faulty battery and charge
circuit during battery test. For related settings and detailed
information, refer to “6.5.6.2 TD MONITORING”.

11 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4.7. Communication Port (COM PORT)


4.7.1. Port for Main Device Communication
Main device communication port is made of D-SUB 9pin Male type and all lines
without 9th RI (Ring Indicator) are connected. This port is for communication
connected with remote central system.

[Table 4-9] Main Device Communication Port Pin


Pin No. Signal Name
RS232(PORT1) 1 DCD : Data Carrier Detect
2 RXD : Receive Data(IN)
3 TXD : Transmit Data(OUT)
4 DTR : Data Terminal Ready(OUT)
5 GND : Ground
6 DSR : Data Set Ready(IN)
<Figure 4-9> Main Devide
Communication Port 7 RTS : Request To Send(OUT)
8 CTS : Clear To Send(IN)
9 RI : Ring Indicator

4.7.2. Maintenance Port


Maintenance port is 9 pin D-SUB Male type that is identical of main device
communication port. The port located in front panel can change setting values
and acquire control and various records by connecting with INTERFACE 
SOFTWARE.
Refer to “[Table 4-9] Main Device Communication Port Pin” since pin
composition and content is identical to main device.

[Table 4-10] Maintenance Port Pin


Pin No. Signal Name
2 RXD : Receive Data(IN)
PORT F 3 TXD : Transmit Data(OUT)
<Figure 4-10> Maintenance 5 GND : Ground
Port

12 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4.7.3. RS485 Communication Port


RS485 communication port has 3pins and the pin composition is in follows.

RS485(PORT2) [Table 4-11] 485 Comm. Port Pin


Pin No.
950
485+

P N SG 485-

<Figure 4-11> 485 Comm. Port SG

4.7.4. Ethernet Port


Ethernet port, as RJ-45, has total 8 pins and is composed in follows.

[Table 4-12] Ethernet Port Pin


Pin No. 10Base-T Signal
ETHERNET(PORT3) 1 Transmit+
2 Transmit-
3 Receive+
4 Unused
5 Unused
6 Receive-
<Figure 4-12> Ethernet Port
7 Unused
8 Unused

13 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

5. USER INTERFACE PANEL

UP FUN

PORT F

Run/Reset

/DIAG

P1 RX/TX
DOWN ENT
P1 RTS/CTS

P2 RX/TX
CIR COM
CUIT MON

1 LIVE AC POWER OK RESET


BATT
2 LIVE CHARGER OK TEST LAMP

3 LIVE BATTERY OK

4 LIVE CB BLOCK

5 LIVE DSP LINK

6 LIVE CPU LINK


REMOTE/LOCAL CONTROL

1
CB
A 51

B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND

2
CB
A 51

B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND

3
CB
A 51

B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND

4
SW
A 51

B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND

5
SW
A 51

B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND

6
SW
A 51

B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND

<Figure 5-1> User Interface Panel

14 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

5.1. User defined LED Part


USER DEFINED LEDs indicate user-defined values on PLC. Detailed description
is in follows.

1 LIVE AC POWER OK

2 LIVE CHARGER OK

3 LIVE BATTERY OK

4 LIVE CB BLOCK

5 LIVE DSP LINK

6 LIVE CPU LINK

<Figure 5-2> User defined LED Part

LIVE LINE Lamp ( ULED1 ~ 6 )


It indicates the live line of each circuit.

AC POWER Lamp ( ULED13 )


It indicates the external power status and turns on when the 220Vac power is in
a supplying status.

CHARGER Lamp ( ULED14 )


The lamp turns on when it is normal voltage(above 21V) when monitoring the
voltage of the charging circuit. Even if the charging circuit is normal, if the
battery voltage is below 21V when charging the battery due to the battery
over-discharge, the 'CHARGER' lamp does not turn on and it turns on when the
battery is charged and its voltage goes above 21V.

BATTERY Lamp ( ULED15 )


The lamp turns on when it is normal voltage(above 21V) when monitoring the
battery voltage.

15 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

CB BLOCK Lamp ( ULED16 )


If the power needed for the CB operation is unsecured, the lamp turns on and at
this time, the CB input operation is restricted. When the control power is ON,
the initial charging time is approximately 20 secs. and in case the close/open are
operated, the charging time is approximately 5 secs.

DSP LINK Lamp ( ULED17 )


It indicates the DSP link with MPU.

CPU LINK Lamp ( ULED18 )


It indicates the CPU link with MPU.

※. NOTE ) This description is applicable to factory default PLC. Following PLC


setting for user’s purpose or specific usage required, above
description can be changed.

5.2. Common Control Part


All indicators show status of control function. The indicators are ON/OFF
continuously when control function is enable/disable. The push-button toggles
Enable/Disable.

REMOTE/LOCAL CONTROL

<Figure 5-3> Local Control Part

REMOTE CONTROL (REMOTE/LOCAL)


- Remote(On) : Remote/local control are both possible.
- Local(Off) : Local control is possible but remote control is not.

CONTROL LOCK (LOCKED/UNLOCKED)


- Unlocked(Off) : Control in remote/local are both possible.
- Locked(On) : All control functions apart from battery tests do not operate in
local and remote.

The control operation lock is irrelevant to protection element.

16 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

5.3. Local Control Part


All indicators show status of Control function. The indicators are continuously ON
when control function is enable and indicators are continuously OFF when control
function is DISABLE. The push-button toggles Enable/Disable.

PROTECTION (ENABLED/DISABLED)
- ENABLED(On) :
All protection elements operate.
- DISABLED(Off) :
All protection elements do not operate.
PROTECTION GROUND

GROUND (ENABLED/DISABLED)
- ENABLED(On) : <Figure 5-4> Local Control Part
Ground protection element operates.
- DISABLED(Off) :
Ground protection element does not operate.

5.4. Open/Close Operation Part


Open/Close Button
CB operates if the button is pressed and the operation status can be checked
with the 'OPEN/CLOSE' lamp.

EARTH
CLOSE OPEN

<Figure 5-5> Operation Part

EARTH Lamp
- The 'EARTH' lamp turns on if the CB inputs to the ground.
- The earth can be operated with a manual operating rod.
- Open/Close control is not possible in the earth input status.

17 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

5.5. Fault Indication Part


A/B/C/N Lamp
1
It indicates the fault phase that occurred when
the fault protection element of each circuit A 51
operated. B 50

C 79RS
51 Lamp
The lamp turns on when the 51 fault element is N 79CY
detected.

50 Lamp
<Figure 5-6> Fault Indication
The lamp turns on when the 50 fault element is Part
detected.

79RS Lamp
The lamp turns on when reclosing(79) reset
element is detected. <Figure 5-7> F.I RESET Button

79CY Lamp
The lamp turns on when reclosing(79) cycle
element is detected

F.I RESET/LAMP Button


This button resets (turns off) the fault indicator.
As button to test lamp, if pressed, all lamps turn
on. RESET lamp does not turn on. The RESET
lamp turns on once when system is booting and
turns off after.

18 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

5.6. System & LCD Control Part

UP FUN

PORT F

Run/Reset

/DIAG

P1 RX/TX
DOWN ENT
P1 RTS/CTS

P2 RX/TX
CIR COM
CUIT MON

<Figure 5-8> System & LCD Control Part

RUN Lamp
It indicates ETR306's operation status. It periodically blinks during normal
operation. In case of system fault, it turns on or off.

RESET Lamp
It turns off after turning on every time system boots and if a system error
occurs during operation, it turns on.

DIAG' Lamp
It turns on if a self diagnosis warning occurs during system operation. Detailed
information can be checked in Common Menu "Diagnosis Event".

19 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

5.6.1. Communication Status Indication Part


PORT1
It is indicated if it is in main device remote communication.
- RX Lamp : It turns on in case of PORT1's data received.
- TX Lamp : It turns on in case of PORT1's data transmitted.
- RTS Lamp : It turns on in case of PORT1's data be possible to transmit.
- CTS Lamp : It turns on in case of PORT1's data required to transmit.

PORT2
It is indicated if it is in 485 communication.
- RX Lamp : It turns on in case of PORT2's data received.
- TX Lamp : It turns on in case of PORT2's data transmitted.

PORT3
It is indicated if it is in Ethernet communication.
- LINK Lamp : It turns on if PORT3 is connected to network.
- ACT Lamp : It turns on if there is data in the LAN when PORT3 is connected
to the network.

5.6.2. Menu Control Part


Measurement and setting, record check and other things can be done in local
when using 20×4 LCD. Refer to "6. LCD CONTROL MANUAL" for more detail.

- 20×4 Character LCD


- 6 Control Keys (UP, DOWN, FUN, ENT, CIRCUIT, COMMON)

20 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

5.6.3. Other Control Parts


BATT TEST Button
Battery test is operated by pushing the Battery Test
[DC MONITORING]
Button. The test is maintained for 5 seconds
BATTERY(V}: 24.5
automatically monitoring battery and charging way of CHARGER(V): 27.5
switchgear. If the button is pushed when AC power is
<Figure 5-9> DC Monitor
in normal, separate charging way of switchgear from
Screen
battery and examinate battery and charging current
by connecting load resistance to battery.
The test result shall be checked in battery lamp and charging way of
switchgear's lamp. In addition, indicate battery voltage and charging way of
switchgear voltage in LCD screen as shown in drawing "<Figure 5-9> DC
Monitor Screen" at above.

- BATTERY : Indicate battery voltage.


- CHARGER : Indicate charging way of switchgear voltage.

21 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6. LCD CONTROL MANUAL


6.1. LCD Screen
20 x 4 character LCD which has back-light support. It is used to operate
conveniently and to check operation status clearly.

6.2. Control Key


LCD control key is composed of 4 basic keys(UP, DOWN, FUN, ENT) and
CIRCUIT and COMMON key. The following is an instruction of key’s function.

[Table 6-1] LCD Control Button

Key Description
From initial screen, it changes to menu selection mode and in the submenu of
each menu it is used as a function to go to the menu before. If pressed in the
Main Menu, it is used to change to the initial screen mode. If this key operates
when setting value is changed, all the changed values will return to the original
[FUN]
value set before.

It is used for selecting menu and changing the set value. In the menu selecting
screen, it operates as a menu selecting function and when the set value is
changed, it changes to menu changing mode in the relevant value's change mode
[ENT] (it operates in toggle method when changing the menu select/setting).

It is used to move the menu up or increase the set value. All the menu is made
as a structure that moves to the bottom location of the menu if in the top location
of the menu since it has a rotation selection function. This function is also applied
when changing set value so the key set value is selected after changing the top
[ UP ] set value. If the button is pressed, it increases one by one and if pressed for
more than 2 seconds, it increases rapidly.

It is used to move the menu to the bottom or decrease the set value. The
rotation selection function is applied for this button too, just like the [UP] key,
when changing the menu/ set value. If the button is pressed, it decreases one by
[DOWN] one and if pressed for more than 2 seconds, it decreases rapidly.

Choose 1 way from the 6 way. If this key is pressed, it changes to the initial
CIR
screen of the chosen circuit.
CUIT
※. NOTE ) The changed value does not get saved if this key is pressed when
[1~6 WAY] changing the set value.

It moves to the common initial screen.


※. NOTE ) The changed value does not get saved if this button is pressed when
changing the set value.
[COMMON]

22 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.3. LCD Menu Structure Tree


 Menu is composed of common menu and circuit menu for each way of
switchgear (CB Part/SW Part).
 The screen structure of each menu is composed of initial screen and menu
screen.
 The initial screen and all menus are composed of rotation method.
 The menu screen is composed of setting, event management and measurement
menu.

6.3.1. Menu Tree Structure for Switch Part(SW)

<Figure 6-1> Circuit Menu Tree Structure for Switch Part(SW)

23 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.3.2. Menu Tree Structure for Circuit Breaker Part(CB)

<Figure 6-2> Circuit Menu Tree Structure for Circuit Breaker Part(CB)

24 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.3.3. Common Menu Tree Structure

<Figure 6-3> Common Menu Tree Structure

25 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.4. Initial Screen


The main information of ETR306 is indicated in initial screen so that user can
easily approach and understand it.

 Initial screen is composed of circuit initial screen and common initial screen.
 It moves to relevant initial screen if [CIRCUIT] or [COMMON] key are
pressed.
 Press [▲][▼] key to move to selected initial screen.
 It moves to main menu if [FUN] key is pressed in initial screen.

[Table 6-2] Initial Screen (1/2)

Initial Screen

MULTI-WAY CONTROL Initial Screen 1 - COMMON


ETR306
When power supply of ETR306 is on, Initial Screen 1 is
ENTEC E&E CO. V1.0
displayed. It displays model name, version and
manufacturer.

Ia: 0A Va: 0.00kV Initial Screen 2 - CIRCUIT


Ib: 0A Vb: 0.00kV
Ic: 0A Vc: 0.00kV
Ia, Ib, Ic, In : Indicate each phase current of selected way
In: 0A <1 SW>
of switchgear.
Va, Vb, Vc : Indicate each phase voltage of selected way
of switchgear.

<1 SW> : Indicate the number of selected way of


switchgear and its control type (SW/CB).

[SEQUENCE ‘V’] Initial Screen 3 - CIRCUIT


V1: 0.00kV ∠ 0˚

V2: 0.00kV 0˚
V1 : Indicate normal voltage and phasor of selected way of
3V0: 0.00kV ∠ 0˚
switchgear.
V2 : Indicate negative phase sequence voltage and
phasor of selected way of switchgear.
V0 : Indicate zero sequence voltage and phasor of
selected way of switchgear.

[SEQUENCE ‘I’] Initial Screen 4 - CIRCUIT


I1: 0A ∠ 0˚
0A ∠
I2: 0˚
I1 : Indicate normal current and phasor of selected way of
3I0: 0A ∠ 0˚
switchgear.
I2 : Indicate negative phase sequence current and
phasor of selected way of switchgear.
I0 : Indicate zero sequence current and phasor of
selected way of switchgear.

26 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

[Table 6-2] Initial Screen (2/2)

Initial Screen

[DEMAND CURRENT] Initial Screen 5 - CIRCUIT


Ia: 0A Ib: 0A
Ic: 0A In: 0A
Ia, Ib, Ic, In : Indicate DEMAND current of each phase
about selected way of switchgear.

Ia: 0˚ Va: 0˚ Initial Screen 6 - CIRCUIT


Ib: 0˚ Vb: 0˚
Ic: 0˚ Vc: 0˚
Ia, Ib, Ic, In : Indicate selected way of switchgear's
In: 0˚ <ANGLE>
current phasor (0~360°).
Va, Vb, Vc : Indicate selected way of switchgear's
voltage phasor (0~360°).

[POWER FACTOR] Initial Screen 7 - CIRCUIT


Pa: 0
Pb: 0 P3: 0
Pa, Pb, Pc : Indicate power factor of each phase about
Pc: 0
selected way of switchgear.
P3 : Indicate power factor of 3 phase about
selected way of switchgear.

[APPARENT POW(KVA)] Initial Screen 8 - CIRCUIT


Pa: 0
Pb: 0 P3: 0
Pa, Pb, Pc : Indicate apparent power of each phase
Pc: 0˚
about selected way of switchgear.
P3 : Indicate 3 phase apparent power about
selected way of switchgear.

[REACTIVE POW(KVAR)] Initial Screen 9 - CIRCUIT


Pa: 0
Pb: 0 P3: 0
Pa, Pb, Pc : Indicate reactive power of each phase
Pc: 0
about selected way of switchgear.
P3 : Indicate 3 phase reactive power about
selected way of switchgear.

[REAL POW(KW)] Initial Screen 10 - CIRCUIT


Pa: 0
Pb: 0 P3: 0
Pa, Pb, Pc : Indicate reactive power of each phase
Pc: 0
about selected way of switchgear.
P3 : Indicate 3 phase reactive power about
selected way of switchgear.

27 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5. Common Main Menu(COM)


When [FUN] key is pressed in common initial screen, it moves to main menu
and if it is pressed in main menu, it moves to initial screen. The main menu has
submenus below.

[ MA I N ME N U ] COM
> 1 . GL OB A L SE T T I NG
2 . E V E NT
3 . MA I N T E N A N C E
4 . T I ME
5 . ST AT UE
6 . ME T E R I N G

[ LCD Screen ] Common Main Menu Screen

6.5.1. GLOBAL SETTING


When [ENT] key is pressed after locating cursor in “1.GLOBAL SETTING” in
main menu, it moves to this screen. The ‘GLOBAL SETTING’ menu has
submenus below.

[ GL OBA L S E T T I N G]
> 1 . S Y S T E M
2 . C OMMU N I C A T I ON
3 . E V E NT R E C ODE R
4 . MON I T OR I N G
5 . P L C
6 . OT HE R S
* . S AV E SE T T I NG

[ LCD Screen ] Global Setting Menu Screen

Caution : Changed set valued must be saved to be applied. When escaping


from "*. SAVE SETTING" menu or moving to high menu, changed
set value is saved by 'Changed set value saved message'.

28 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.1.1. SYSTEM
It moves to this menu if [ENT] key is pressed after locating cursor in “1.
SYSTEM” in ‘GLOBAL SETTING' menu. Various facts related to system are set
in this menu and it has submenus below.

[ S Y S T E M]
> 1 . P O WE R L I NE
2 . CURRE NT S E NSI NG
3 . V OL T A GE S E NSI NG
4 . C ON T R OL T Y P E
5 . CB OP E N I N G T I ME
6 . GA S S E NS OR T Y PE
7 . F I T Y PE S E L E CT

[ LCD Screen ] SYSTEM Setting Menu Screen

Caution : This setting change may influence metering and whole system,
precaution is requested.

(1) POWER LINE


It moves to this menu if [ENT] key is pressed after locating cursor in "1.
POWER LINE" in 'SYSTEM' menu. Set power system information where ETR306
is installed.
The set value alteration procedure is show below;

① Use [▲] and [▼] key and move to items which want to change setting.
② Press [ENT] key to change setting value.
③ Use [▲] and [▼] key to Set new value and press [ENT] key to change
setting value.

[ P O WE R L I NE ]
> F r e q u e n c y : 6 0
Re f . V o l t a g e : A
Ph a s e Ro t a t i o n : ABC
N o mi n a l V o l t : 1 3 2 0 0

[ LCD Screen ] POWER LINE Setting Menu Screen

29 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Frequency

Range 50, 60 ㎐
Default 60
Step 10

 Select nominal power system frequency. This value is used as a


default to set optimal digital sampling rate.
 It is set before product delivery in accordance with specifications.

2) Ref. Voltage

Range A, B, C, NONE
Default A
Step - 0

 Select reference voltage.


 Beside of hard wire connection, phase connection shall be adjusted by
software as well.
※. NOTE ) Depending on settings of 'Reference voltage' and 'Phase
Rotation' bushing connection is changed. Refer to "[Table
6-3] Phase selection according to reference voltage and
phase rotation".

[Table 6-3] Phase selection according to standard voltage and phase rotation

Setting Standard
REF A REF B REF C
voltage
Phase
Terminal ABC ACB ABC ACB ABC ACB
rotation
A body
- A A B B C C
bushing
B body
- B C C A A B
bushing
C body
- C B A C B A
bushing

3) Phase Rotation

Range ABC, ACB


Default ABC
Step -

 Select phase rotation of power system.

30 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4) Nominal Volt

Range 1000 ~ 30000V


Default 13200
Step 10V

 Set power system's rated voltage.

(2) CURRENT SENSING


It moves to this menu if [ENT] key is pressed after locating cursor in "2.
CURRENT SENSING" in 'SYSTEM' menu. Set information of current measuring
device installed in body part using this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ CURRE NT S E NS I NG]
> CT 1 - Ra t i o : 1 0 0 0
GCT 1 - Ra t i o : 1 0 0 0
CT 2 - Ra t i o : 1 0 0 0
GCT 2 - Ra t i o : 1 0 0 0
CT 3 - Ra t i o : 1 0 0 0
GCT 3 - Ra t i o : 1 0 0 0
CT 4 - Ra t i o : 1 0 0 0
GCT 4 - Ra t i o : 1 0 0 0
CT 5 - Ra t i o : 1 0 0 0
GCT 5 - Ra t i o : 1 0 0 0
CT 6 - Ra t i o : 1 0 0 0
GCT 6 - Ra t i o : 1 0 0 0
CT 1 - Po l : F OR
GCT 1 - P o l : F OR
CT 2 - Po l : F OR
GCT 2 - P o l : F OR
CT 3 - Po l : F OR
GCT 3 - P o l : F OR
CT 4 - Po l : F OR
GCT 4 - P o l : F OR
CT 5 - Po l : F OR
GCT 5 - P o l : F OR
CT 6 - Po l : F OR
GCT 6 - P o l : F OR

[ LCD Screen ] CURRENT SENSING Setting Menu Screen

31 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) CT#-Ratio

Range 1 ~ 2000
Default 1000
Step 1

 Set phase CT# ratio (# means the number of switchgear’s way).

2) GCT#-Ratio

Range 1 ~ 5000
Default 1000
Step 1

 Set Ground CT# ratio (# means the number of switchgear’s way).

3) CT# Pol

Range FOR, REV


Default FOR
Step -

 Select phase CT# pole direction (# means the number of switchgear’s


way).

4) GCT# Pol

Range FOR, REV


Default FOR
Step -

 Select ground CT# pole direction (# means the number of switchgear’s


way).

32 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(3) VOLTAGE SENSING


It moves to this menu if [ENT] key is pressed after locating cursor in "3.
VOLTAGE SENSING" in 'SYSTEM' menu. Set information of voltage measuring
device installed in body part using this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ V OL T A GE S E NS I NG]
> V T CON- T y p e : WY E
V T 2 n d ( V ) : 4 . 0 0
V T Ra t i o : 3 3 0 0 . 0

[ LCD Screen ] VOLTAGE SENSING Setting Menu Screen

1) VT CON-Type

Range NONE, WYE, DELTA


Default WYE
Step -

 Select voltage connector.


 NONE : VT non installed. Select NONE if Voltage Sensing item is not used.
 WYE : If Voltage Connect type of 1V is Y type, select WYE.
 DELTA : If Voltage Connect type of 1V is Δ-type, select DELTA.

2) VT 2nd(V)

Range 2.00 ~ 350.00 V


Default 4.00
Step 0.01 V

 Enter second rated voltage(V) of 1V(1st Voltage connector).


 This setting is second rated voltage that entered in relay about line
rated voltage.

3) VT Ratio

Range 10.0 ~ 6500.0


Default 3300.0
Step 0.1

 Enter VT rated rate of 1V(1st Voltage connector).


 The 1st conversion voltage is indicated as multiple of VT Ratio and
2nd VT input voltage.

33 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(4) CONTROL TYPE


It moves to this menu if [ENT] key is pressed after locating cursor in "4.
CONTROL TYPE" in 'SYSTEM' menu. Set control type per way of switchgear of
ETR306 in this menu. At time of product shipment, this menu is set to user's
request and is best to not make any alteration.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ CONT ROL T Y PE ]
> 1 WA Y : CBT Y PE
2 WA Y : CBT Y PE
3 WA Y : CBT Y PE
4 WA Y : CBT Y PE
5 WA Y : CBT Y PE
6 WA Y : CBT Y PE

[ LCD Screen ] CONTROL TYPE Setting Menu Screen

1) 1 WAY ~ 6 WAY

Range NONE, CBTYPE, SWTYPE


Default CBTYPE
Step -

 NONE : Selected when way of switchgear is not used.


 CBTYPE : Circuit breaker uses for selected way of switchgear.
 SWTYPE : Switch uses for selected way of switchgear.

(5) CB OPENING TIME


It moves to this menu if [ENT] key is pressed after locating cursor in "5. CB
OPENING TYPE" in 'SYSTEM' menu. The set value alteration process is identical
to "MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE”.

[ CB OP E N I N G T I ME ]
> T i me : 0 . 0 2 0

[ LCD Screen ] CB OPENING TIME Setting Menu Screen

34 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

The CB Opening Time is set in this menu and time that CB completely opens is
calculated in following way.

Total CB Clearing Time = Relay Release Time + CB Trip Time(CB Opening Time + Arcing Time)

To apply TCC time to complete opening time, CB trip time shall be considered.

1) CB Opening Time

Range 0.000 ~ 1.000 sec


Default 0.020
Step 0.001 sec

※. EXAMPLE ) In case that TCC value applied to ETR306 is 1.00sec and


CB Trip Time is 30msec + 10msec, actual way of switchgear
breaker’s Clearing Time is 1.00 + 30msec + 10msec = 1.04sec. The
difference between TCC value and actual Clearing Time, 40msec
needs to be set for CB Trip Time(40msec). This setting time
compensates CB Trip Time.

(6) GAS SENSOR TYPE


It moves to this menu if [ENT] key is pressed after locating cursor in "6. GAS
SENSOR TYPE" in 'SYSTEM' menu. The purpose of this menu is for
interchangeability of body insulation type and unless body unit has changed,
alteration is forbidden.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ GA S S E NS OR T Y P E ]
> T y p e : NONE

[ LCD Screen ] GAS SENSOR TYPE Setting Menu Screen

35 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Type

Range NONE, TYPE1, TYPE2


Default NONE
Step ~

 This is set in accordance with tank before delivery.


 It is set depending on tank insulation method. If tank is gas insulated
type, it shall take TYPE1 or TYPE2.
 NONE : It means non-gas type. When solid insulated type is used,
select this type.

(7) FI TYPE SELECT


Select type to detect FI(Fault indicator).

[ F I T Y PE S E L E CT ]
> T Y P E SE L E CT : I V

[ LCD Screen ] FI TYPE SELECT Setting Menu Screen

1) TYPE SELECT

Range IV, I
Default IV
Step -

 This setting is only applied to SW type’s way of switchgear.


 IV : If dead line state after experiencing a fault current, FI is
detected.
 I : If fault current maintains during fault delay time(Type I Delay), FI
is detected.

36 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.1.2. COMMUNICATION
It moves to this menu if [ENT] key is pressed after locating cursor in “2.
COMMUNICATION” in ‘GLOBAL SETTING' menu. A variety of matters related to
communication are set here and it has following submenus.

[ C O MMU N I C A T I O N ]
> 1 . P ROT OCOL SE T UP
2 . P OR T SE T UP
3 . DI A L UP MO D E M
4 . A L A L OG E V E NT
5 . F T P F I L E T RANF E R

[ LCD Screen ] COMMUNICATION Setting Menu Screen

(1) PROTOCOL SETUP


It moves to this menu if [ENT] key is pressed after locating cursor in "1.
PROTOCOL SETUP" in 'COMMUNICATION' menu. The DNP3.0 protocol is set
here and set value alteration process is identical to “MAIN MENU(COM)/
GLOBAL SETTING/ SYSTEM / POWER LINE” .

[ P ROT OCOL SE T UP]


> 1 . DNP3
2 . I E C6 0 8 7 0 - 5 - 1 0 1
3 . I E C6 0 8 7 0 - 5 - 1 0 4
4 . MO D B U S

[ LCD Screen ] PROTOCOL SETUP Setting Menu Screen

37 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

A. DNP3
ETR306 can be programmed for communication using DNP3 through
communication port1, port2 or port3.

[ DNP 3 ]
> F u n c t i o n : E NA BL E
COM Po r t : P ORT 1
D/ L C o n f i r m: S OME
D/ L F r a me D l y : 1 0 0
D/ L Re t r i e s : 0
D/ L T i me o u t : 1 0
A/ L T i me o u t : 1 5
Maa s t e r A d d r : 6 0 0 0 0
DNP Ad d r e s s : 1
SBO T i me : 1 5
I n i t Un s o l : E NA BL E
Un s o l T i me : 5
Un s o l T y p e : N OT R I G
Un s o l Re t r i e s : 0
Cl a s s 1 : E NA BL E
Cl a s s 2 : E NA BL E
Cl a s s 3 : E NA BL E
T CP/ UDP Se l e c t : T CP
T CP Po r t : 2 0 0 0 0
UDP Po r t : 2 0 0 0 1
Maa s t e r I P Oc t 1 : 1 9 2
Maa s t e r I P Oc t 2 : 1 6 8
Maa s t e r I P Oc t 3 : 7
Maa s t e r I P Oc t 4 : 2 0 2
K- Al v Ch e c k T m: 4
F r a g me n t S i z e : 2 0 4 8
T i me R e q ( m) : OF F

[ LCD Screen ] DNP3.0 PROTOCOL Setting Menu Screen

1) Function

Range DISABLE, ENABLE


Default ENABLE
Step -

 Select whether DNP3.0 communication is used or not.

38 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

2) COM Port

Range PORT1, PORT2, PORT3


Default PORT1
Step -

 Select communication port to use DNP3.0 communication.

3) D/L Confirm

Range NO, YES, SOME


Default SOME
Step -

 Select whether Data Link Confirm is used or not.


 NO : Data Link Confirm is not used.
 YES : Data Link Confirm is used.
 SOME : Data Link Confirm is used in case of Multi-frame.
 It shall be set as Host setting. If setting is different from Host one,
communication may be failed due to Data Link Reset.

4) D/L FrameDly

Range 10 ~ 5000 msec


Default 100
Step 10 msec

 Set Data Link frame Delay Time.


 In case that D/L Confirm setting is OFF, it means Frame Interval time
when multi-frame occurs.

5) D/L Retries

Range 0 ~ 2
Default 0
Step 1

 Set number of retries that will be issued for a given data link layer.

39 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6) D/L Timeout

Range 1 ~ 255 sec


Default 10
Step 1 sec

 Set waiting time between Data Link Frame transfer till to receive
Data Link Confirm(ACK) of Master. If there is no Data Link Confirm
receiving and Data Link retry is available, ETR306 will send Data Link
Frame again.

7) A/L Timeout

Range 1 ~ 255 sec


Default 15
Step 1 sec

 Set waiting time for Slave Application to receive A/L Confirm(ACK)


from Master Application, in case that Confirm is requested during Data
transfer from Slave Application to Master Application.

8) Master Address

Range 0 ~ 65534
Default 60000
Step 1

 Set master station address. This Address is an address that ETR306


refers to when transmitting unsolicited message.

9) DNP Address

Range 0 ~ 65534
Default 1
Step 1

 Set slave(ETR306) address.

10) SBO Time

Range 1 ~ 255 sec


Default 15
Step 1 sec

 Set time interval between Select Function and Operate Function. If no


operation command during set time, Select command is cancelled.

40 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

11) Init Unsol

Range DISABLE, ENABLE


Default ENABLE
Step -

 Select a use of re-start Initial Unsolicited Response.


 ENABLE : On Power Up, Initial Unsolicited Response Message is
transferred.
 DISABLE : On Power Up, Initial Unsolicited Response Message is not
transferred.

12) Unsol Time

Range 0 ~ 60 sec
Default 5
Step 1 sec

 Set delay time of reporting, in case Unsolicited mode event is


occurred. Reporting is conducted if no new Event is occurred within
time.

13) Unsol Type

Range NOTRIG/PERIOD
Default NOTRIG
Step -

 NOTRIG : If there is no more event occurrence during setting


unsolicited time after last event occurs, event data is transmitted.
 PERIOD : Unsolicited message is sent to a master with whole event
data occurring after setting unsolicited time starting and elapsing when
first event occurs.

14) Unsol Retries

Range 0 ~ 2
Default 0
Step 1

 Set Unsolicited Retries when there is not a confirm about Unsolicited


message from master device.

41 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

15) Class 1

Range DISABLE, ENABLE


Default ENABLE
Step -

 Select whether to send Unsolicited Response or not to master in case


that Event is occurred in Class1.

16) Class 2, Class 3 are also identical to Class1.

17) TCP/UDP Select

Range TCP/UDP
Default TCP
Step -

 Select TCP or UDP communication at use of port3(Ethernet).

18) TCP Port

Range 0 ~ 65535
Default 20000
Step 1

 Set TCP Port number of ETR306 for TCP communication.

19) UDP Port

Range 0 ~ 65535
Default 20001
Step 1

 Set UCP Port number of ETR306 for UDP communication.

20) Master IP Oct1 ~ 4

Range 0 ~ 255
Default IP Oct1 : 192
IP Oct2 : 168
IP Oct3 : 7
IP Oct4 : 202
Step 1

 Select IP Address for DNP3 Communication.


 IP Address: 192.xxx.xxx.xxx
① ② ③ ④

42 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

 Master IP Oct1,2,3,4 stands for ①,②,③,④.


 For example, in case main device IP address is ‘192.168.7.202’, it
shall be set as below.
- Master IP Oct1 : 192
- Master IP Oct2 : 168
- Master IP Oct3 : 7
- Master IP Oct4 : 202

21) K-Alv Check Tm

Range 0(OFF), 1 ~ 600 sec


Default 4
Step 1 sec

 Set time period that check communication connecting status during idle
status.

22) Fragment Size

Range 64 ~ 2048
Default 2048
Step 1

 Set size of DNP fragment.

23) Time Req(m)

Range 0(OFF), 1 ~ 30000


Default OFF
Step 1

 Set Time Synchronization Request Interval(to Master station).

43 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

B. IEC60870-5-101
ETR306 can be programmed for communication using IEC60870-5-101 through
communication port1, port2 or port3.

[ I E C6 0 8 7 0 - 5 - 1 0 1 ]
> F u n c t i o n : DI S ABL E
C OM P o r t : P OR T 1
A d d r e s s : 1
A SDU Ad d r : 0
Cy c l i c Pe r i o d : 6 0
E v e n t P e r i o d : 1 5
Re t r i e s : 0
Co n f . T i me o u t : 1 0
Ma x P o l l T i me : 1 0
A SDU Ad d r S i z e : 2
L i n k C o n f i r m: A L WA Y S
L i n k Ad d r S i z e : 1
Rx F r a me Si z e : 2 6 1
Rx F r a me T O: 1 5
T x F r a me Si z e : 2 6 1
C OT S i z e : 1
I OA S i z e : 2
On e Ch Re s p o n s e : NO
F r a me Re p e t ‘ T O: 3 0
S e l e c t T i me o u t : 5
C MD T e r mi n a t i o n : Y E S
CSE T e r mi n a t i o n : Y E S
Cl o c k S y n c ‘ E v t : Y E S
MS P T i me - T a g : CP 5 6
MI T T i me - T a g : CP 5 6
MME T i me - T a g : CP 5 6
F l t ‘ T i me - T a g : CP 5 6

[ LCD Screen ] IEC60870-5-101 protocol Setting Menu Screen

1) Function

Range DISABLE, ENABLE


Default DISABLE
Step -

 Set use of IEC60870-5-101

44 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

2) COM Port

Range PORT1, PORT2, PORT3


Default PORT1
Step -

 Select a port to use IEC60870-5-101 communication.

3) Address

Range 1 ~ 65535
Default 1
Step 1

 Enter slave(ETR306) address for IEC60870-5-101 communication.

4) ASDU Addr

Range 0 ~ 65535
Default 0
Step 1

 Select Application Service Data Unit Address.

5) Cyclic Period

Range 1 ~ 60000
Default 60
Step 1

 Select Cyclic Period.


 It is to set interval time between Point set for Cyclic.

6) Event Period

Range 0 ~ 255 s
Default 15
Step 1 s

 Select delay time before events are sent.


 Single event or several events occur and then if new event is not
generated during delay time, event(s) already generated is(are) sent to
a Master

45 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

7) Retries

Range 1 ~ 255
Default 0
Step 1

 Set Data retries number.

8) Conf. Timeout

Range 1 ~ 255 s
Default 10
Step 1 s

 Set wait time till receive Data Confirm (ACK) of master after transfer
data.
 If there is not Confirm during this setting time and Data retries is
available, ETR306 transfers Data again.

9) Max Poll Time

Range 1~255 s
Default 10
Step 1 s

 Set Data Polling period time.

10) ASDU Addr Size

Range 1 ~ 2
Default 2
Step 1

 Enter size of cause of transmission.

11) Link Confirm

Range NEVER, ALWAYS


Default ALWAYS
Step -

 Enter Link layer confirm mode.

46 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

12) Link Addr Size

Range 1 ~ 2
Default 1
Step 1

 Enter size of link address.

13) Rx Frame Size

Range 0 ~ 261
Default 261
Step 1

 Enter maximum size of received frame.

14) Rx Frame TO

Range 0(OFF), 0~255 s


Default 15
Step 1 s

 Enter maximum amount of time to wait for a complete frame after


receiving frame sync.

15) Tx Frame Size

Range 0 ~ 261
Default 261
Step 1

 Enter Maximum size of transmitted frame.

16) COT Size

Range 1 ~ 2
Default 1
Step 1

 Enter size of cause of transmission.

47 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

17) IOA Size

Range 1 ~ 3
Default 2
Step 1

 Enter size of information object address.

18) One Ch Response

Range NO, YES


Default NO
Step -

 This allows to send one character response instead of a fixed length


NACK when no response data available.

19) Frame Repet’ TO

Range 0(OFF), 0 ~ 255 s


Default 30
Step 1 s

 Enter time out for repetition of frames(or incremental application layer


timeout).

20) Select Timeout

Range 0(OFF), 0 ~ 255


Default 5
Step 1

 Enter period after a previously received select will timeout.

21) CMD Termination

Range NO, YES


Default YES
Step -

 Select whether to send Activation Termination upon completion of


commands other than set point commands.

48 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

22) CSE Termination

Range NO, YES


Default YES
Step -

 Select whether to send Activation Termination upon completion of set


point command.

23) Clock Sync’ Evt

Range NO/YES
Default YES
Step -

 Select whether to generate spontaneous clock synchronization events.

24) MSP Time-Tag

Range CP56, CP24


Default CP56
Step -

 Select whether a time tag format for single-point.


 CP56 : The time tag format is CP56Time2a.
 CP24 : The time tag format is CP24Time2a.

25) MIT Time-Tag

Range CP56/CP24
Default CP56
Step -
 Select whether a time tag format for integrated totals.
 CP56 : The time tag format is CP56Time2a.
 CP24 : The time tag format is CP24Time2a.

26) MME Time-Tag

Range CP56, CP24


Default CP56
Step -

 Select whether a time tag format for measured value and normalized

49 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

value for general event except for fault current event.


 CP56 : The time tag format is CP56Time2a.
 CP24 : The time tag format is CP24Time2a.

27) Flt' Time-Tag

Range CP56, CP24


Default CP56
Step -

 Select whether a time tag format for integrated totals.


 CP56 : The time tag format is CP56Time2a.
 CP24 : The time tag format is CP24Time2a.

C. IEC60870-5-104
ETR306 can be programmed for communication using IEC60870-5-104 through
communication port3.

[ I E C6 0 8 7 0 - 5 - 1 0 4 ]
> F u n c t i o n : DI S ABL E
C OM P o r t : P OR T 3
A SDU Ad d r : 0
Cy c l i c Pe r i o d : 6 0
T i me o u t ( t 0 ) : 1 2 0
T i me o u t ( t 1 ) : 1 5
T i me o u t ( t 2 ) : 1 0
T i me o u t ( t 3 ) : 2 0
E v e n t P e r i o d : 1 5
T CP P o r t No : 2 4 0 4
Rx F r a me Si z e : 2 5 5
T x F r a me Si z e : 2 5 5
S e l e c t T i me o u t : 5
C MD T e r mi n a t i o n : Y E S
CSE T e r mi n a t i o n : Y E S
Cl o c k S y n c ‘ E v t : Y E S
MS P T i me - T a g : CP 5 6
MI T T i me - T a g : CP 5 6
MME T i me - T a g : CP 5 6
F l t ‘ T i me - T a g : CP 5 6

[ LCD Screen ] IEC60870-5-104 protocol Setting Menu Screen

50 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Function

Range DISABLE, ENABLE


Default DISABLE
Step -

 Set use of IEC60870-5-104 communication.

2) COM Port

Range PORT3
Default PORT3
Step -

 Select a port for IEC60870-5-104 communication.


 It is fixed in PORT3.

3) ASDU Addr

Range 0 ~ 65535
Default 0
Step 1

 Select Application Service Data Unit Address.

4) Cyclic Period

Range 1 ~ 60000
Default 60
Step 1

 Select Cyclic Period.


 It is to set interval time between Point set for Cyclic.

5) Timeout(t0)

Range 1 ~ 255 s
Default 120
Step 1 s

 Select Timeout for connection establishment.

51 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6) Timeout(t1)

Range 1 ~ 255 s
Default 15
Step 1 s

 Select Timeout for sent or test APDUs.

7) Timeout(t2)

Range 1 ~ 255 s
Default 10
Step 1 s

 Select Timeout for acknowledgements in case of no data


message(t2<t1).

8) Timeout(t3)

Range 1 ~ 255 s
Default 20
Step 1 s

 Select Timeout for sending test frame in case of a long idle state.

9) Event Period

Range 0 ~ 255 s
Default 15
Step 1 s

 Select delay time before events are sent.


 Single event or several events occur and then if new event is not
generated during delay time, event(s) already generated is(are) sent to
a Master

10) TCP Port NO

Range 0 ~ 65535
Default 2404
Step 1

 Select TCP/IP Port of ETR306 for IEC60870-5-104 Protocol


communication.

52 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

11) RX Frame Size

Range 0 ~ 255
Default 255
Step 1

 Enter maximum size of received frame.

12) TX Frame Size

Range 0 ~ 255
Default 255
Step 1

 Enter maximum size of transmitted frame.

13) Select Timeout

Range 0(OFF), 0 ~ 255


Default 5
Step 1

 Enter period after a previously received select will timeout.

14) CMD Termination

Range NO, YES


Default YES
Step -

 Select whether to send Activation Termination upon completion of


commands other than set point commands.

15) CSE Termination

Range NO, YES


Default YES
Step -

 Select whether to send Activation Termination upon completion of set


point commands.

53 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

16) Clock Sync’ Evt

Range NO, YES


Default YES
Step -

 Select whether to generate spontaneous clock synchronization events.

17) MSP Time-Tag

Range CP56, CP24


Default CP56
Step -

 Select whether a time tag format for single-point.


 CP56 : The time tag format is CP56Time2a.
 CP24 : The time tag format is CP24Time2a.

18) MIT Time-Tag

Range CP56, CP24


Default CP56
Step -

 Select whether a time tag format for integrated totals.


 CP56 : The time tag format is CP56Time2a.
 CP24 : The time tag format is CP24Time2a.

19) MME Time-Tag

Range CP56, CP24


Default CP56
Step -

 Select whether a time tag format for measured value and normalized
value for general event except for fault current event.
 CP56 : The time tag format is CP56Time2a.
 CP24 : The time tag format is CP24Time2a.

54 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

20) Flt' Time-Tag

Range CP56, CP24


Default CP56
Step -

 Select whether a time tag format for integrated totals.


 CP56 : The time tag format is CP56Time2a.
 CP24 : The time tag format is CP24Time2a.

D. MODBUS
ETR306 can be programmed for communication using MODBUS through
communication port1, port2, port3.

[ MOD B U S ]
> F u n c t i o n : DI S ABL E
C OM P o r t : P OR T 3
T CP / UDP S e l e c t : T CP
T CP P o r t : 5 0 2
UDP P o r t : 2 0 0 0 1
S l a v e A d d r e s s : 1
T x De l a y : 0 . 0 5

[ LCD Screen ] MODBUS protocol Setting Menu Screen

1) Function

Range DISABLE, ENABLE


Default DISABLE
Step -

 Set whether to use MODBUS communication or not.

2) COM Port

Range PORT1, PORT2, PORT3


Default PORT1
Step -

 Select MODBUS communication port.

55 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

3) TCP/UDP Select

Range TCP, UDP


Default TCP
Step -

 Select TCP or UDP communication at use of Port3(Ethernet).

4) TCP Port

Range 1 ~ 65535
Default 502
Step 1

 Set TCP port number of ETR306

5) UDP Port

Range 1 ~ 65535
Default 20001
Step 1

 Set UDP port number of ETR306

6) Slave Address

Range 1 ~ 254
Default 1
Step 1

 Enter MODBUS address.

7) Tx Delay

Range 0.00 ~ 300.00


Default 0.05
Step 0.01

 Delay time of sending Real data after RTS Signal is on.

56 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(2) PORT SETUP


It moves to this menu if [ENT] key is pressed after locating cursor in "2. PORT
SETUP" in 'COMMUNICATION' menu. ETR306 communication port and related
elements are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE” .

[ P OR T SE T UP]
> 1 . P OR T 1 ( 2 3 2 )
2 . P OR T 2 ( 4 8 5 )
3 . P OR T 3 ( E T HE R NE T )
4 . P OR T F ( 2 3 2 )

[ LCD Screen ] COMMUNICATION PORT Setting Menu Screen

A. PORT1(232)

It moves to this menu if [ENT] key is pressed after locating cursor in "1.
PORT1(232)" in 'PORT SETUP' menu. The particulars related to communication
PORT1 located in ETR306 are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ P OR T 1 ( 2 3 2 ) ]
> Ba u d Ra t e : 9 6 0 0
P a r i t y Bi t : NONE
Da t a Bi t : 8
S t o p Bi t : 1
Mo d e m S e l : 4 W
CT S Us a g e : E NABL E
DCD Us a g e : DI S ABL E
RT S Us a g e : AUT O
CT S C h e c k Ou t : 2
DCD C h e c k Ou t : 5 0 0 0
T X Pr e De l a y : 1 0
T X Po s t De l a y : 5 0

[ LCD Screen ] PORT1(232) Setting Menu Screen

57 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Baud Rate

Range 1200, 2400, 4800, 9600, 19200 bps


Default 9600
Step -

 Select baud rate for PORT1.

2) Parity Bit

Range NONE, ODD, EVEN


Default NONE
Step -

 Select whether to use parity bit or not as well as type.

3) Data Bit

Range 7 ~ 8
Default 8
Step 1

 Select number of data bits to be used when communicating.

4) Stop Bit

Range 1 ~ 2
Default 1
Step 1

 Select number of data stop bits to be used when communicating.

5) Modem Sel

Range 2W, 4W, DIAL, NONE


Default 4W
Step -

 Select a modem for communication.


- 2W : 2 wire private line is used and continuously Carrier is
monitored to control data flow by DCD(Data Carrier Detect).
- 4W : 4 wire private line is used and RTS(Request To Send) and
CTS(clear to Send) signal are used to control data flow.
- DIAL : Dial-Up1 modem is used.
- NONE : Not used.

58 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6) CTS Usage

Range DISABLE, ENABLE


Default ENABLE
Step -

 Select whether to use CTS signal or not.


- ENABLE : After confirm CTS signal is Asserted, transfer a data.
- DISABLE : Regardless of CTS signal, transfer a data.

7) DCD Usage

Range DISABLE, ENABLE


Default DISABLE
Step -

 Select whether to use DCD signal.


- ENABLE : After confirming DCD signal is deasserted, transfer a data.
- DISABLE : Regardless of DCD signal, transfer a data.

8) RTS Usage

Range ON, OFF, AUTO


Default AUTO
Step -

 ON : RTS signal of ETR306 is always ON(Assert).


 OFF : RTS signal of ETR306 is always OFF(Deassert).
 AUTO : On requesting data transfer to Modem, after RTS signal of
ETR306 is on and after data transfer completion, RTS signal
of ETR306 is off.

9) CTS CheckOut

Range 1 ~ 255 sec


Default 2
Step 1 sec

 Set waiting time that waits Modems confirmation on RTS signal which
informs that ETR306 is ready to transfer a data. If there is no CTS
response within a set time, RTU confirms CTS Fail and does not
transfer data.
 It is available if ‘CTS Usage’ setting is ON.

59 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

10) DCD CheckOut

Range 10 ~ 30000 msec


Default 5000
Step 10 msec

 Set delay time of DCD signal check which determine modem status
before sending RTS signal in 2 wire communication type. After a set
time, if DCD signal is ON, ETR306 does not transfer data and treat it
as DCD Fail. It is available if ‘DCD Usage’ setting is ON.

11) TX PreDelay

Range 5 ~ 500 msec


Default 10
Step 5 msec

 Set tx pre-delay time. It delayed TX signal after CTS signal check.

12) TX PostDelay

Range 10 ~ 500 msec


Default 50
Step 5 msec

 Set tx post-delay time. It delayed RTS off after TX finished.

B. PORT2(485)

It moves to this menu if [ENT] key is pressed after locating cursor in "2.
PORT2(485)" in 'PORT SETUP' menu. The particulars related to communication
PORT2 located in ETR306 are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ P OR T 2 ( 4 8 5 ) ]
> Ba u d Ra t e : 9 6 0 0
P a r i t y Bi t : NONE
Da t a Bi t : 8
S t o p Bi t : 1
L i n e T y p e : RS4 2 2
CA De l a y : 1 . 0 0

[ LCD Screen ] PORT2(485) Setting Menu Screen

60 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Refer to "6.5.1.2. COMMUNICATION/ (2) PORT SETUP/ A. PORT1(232)"


for Speed, Parity Bit, Data Bit and Stop Bit setting items.

2) Line Type

Range RS422, RS485


Default RS422
Step -

 Selects physical port to be used when communicating.

3) CA Delay

Range 0.00 ~ 240.00 sec


Default 1.00
Step 0.01 sec

 Set lag time until response data is transmitted after receiving data.

C. PORT3(ETHERNET)

It moves to this menu if [ENT] key is pressed after locating cursor in "3.
PORT3(ETHERNET)" in 'PORT SETUP' menu. The particulars related to
communication PORT3 located in ETR306 are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ P OR T 3 ( E T HE R NE T ) ]
> I P Ad d r Oc t 1 : 1 9 2
I P Ad d r Oc t 2 : 1 6 8
I P Ad d r Oc t 3 : 7
I P Ad d r Oc t 4 : 2 1 2
Ga t e wa y Oc t 1 : 1 9 2
Ga t e wa y Oc t 2 : 1 6 8
Ga t e wa y Oc t 3 : 7
Ga t e wa y Oc t 4 : 1
S u b n e t Ma s k Oc t 1 : 2 5 5
S u b n e t Ma s k Oc t 2 : 2 5 5
S u b n e t Ma s k Oc t 3 : 2 5 5
S u b n e t Ma s k Oc t 4 : 0
K - A l v F u n c : E NABL E
K - A l v I d l e T O: 4
K - A l v Re t r y : 3

[ LCD Screen ] PORT3(ETHERNET) Setting Menu Screen

61 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) IP Addr Oct1 ~ 4

Range 0 ~ 255
Default IP Oct1 : 192
IP Oct2 : 168
IP Oct3 : 7
IP Oct4 : 212
Step 1

 Set IP address of ETR306.


 IP Address: 192.xxx.xxx.xxx
① ② ③ ④
 Master IP Oct1,2,3,4 stands for ①,②,③,④.
 For example, in case main device IP address is ‘192.168.7.202’, it
shall be set as below.
- Master IP Oct1 : 192
- Master IP Oct2 : 168
- Master IP Oct3 : 7
- Master IP Oct4 : 212

2) Gateway Oct1 ~ 4

Range 0 ~ 255
Default Gateway Oct1 : 192
Gateway Oct2 : 168
Gateway Oct3 : 7
Gateway Oct4 : 1
Step 1

 Set Gateway address. The setting method is identical to IP address


setting method.

3) Subnet Mask Oct1 ~ 4

Range 0 ~ 255
Default Subnet Mask Oct1 : 192
Subnet Mask Oct2 : 168
Subnet Mask Oct3 : 7
Subnet Mask Oct4 : 212
Step 1

 Set Subnet Mask address. The setting method is identical to IP


address setting method.

62 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4) K-Alv Func

Range DISABLE, ENABLE


Default ENABLE
Step -

 Select whether to use or not Ethernet communication connecting status


check function.

5) K-Alv Idle TO

Range 0(OFF), 1 ~ 600 sec


Default 4
Step 1 sec

 If Idle status is maintained during setting time, check communication


connecting maintenance status.

6) K-Alv Retry

Range 0 ~ 255
Default 3
Step 1

 Check communication connecting maintenance status as much as


setting number. If there isn’t a respond, take as communication fail
and close communication connection.

D. PORTF(232)

It moves to this menu if [ENT] key is pressed after locating cursor in "4.
PORTF(232)" in 'PORT SETUP' menu. The particulars related to communication
PORTF located in ETR306 are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE” .

63 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

[ P OR T F ( 2 3 2 ) ]
> Wi r e l e s s : DI S ABL E
S l a v e A d d r : 1
Ma s t e r Ad d r : 0
Ba u d Ra t e : 3 8 4 0 0
Mo d e m S e l : 4 W
CT S Us a g e : E NABL E
DCD Us a g e : DI S ABL E
RT S Us a g e : AUT O
CT S C h e c k Ou t : 2
DCD C h e c k Ou t : 5 0 0 0
RT S Of f De l a y : 5 0

[ LCD Screen ] PORTF(232) Setting Menu Screen

1) Wireless

Range DISABLE, ENABLE


Default DISABLE
Step -

 Select whether to use wireless communication or not.

2) Slave Address

Range 0 ~ 65534
Default 1
Step 1

 Set Slave(ETR306) address.

3) Master Address

Range 0 ~ 65534
Default 0
Step 1

 Set master device address.

4) Baud Rate

Range 1200,2400,4800,9600,19200,38400,57600,115200 bps


Default 38400
Step -

 Set PORTF's communication speed.

64 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

5) Refer to "6.5.1.2. COMMUNICATION/ (2) PORT SETUP/ A. PORT1(232)”


for Modem Sel, CTS Usage, DCD Usage, RTS Usage, CTS CheckOut, DCD
CheckOut and RTS OffDelay items.

(3) DIALUP MODEM


Place curser on “DIALUP MODEM” in COMMUNICATION menu, press [ENT]
button to move into this menu.
ETR306 supports a Hayes compatible Modem on Port 1(232) for remote dial up
access using DNP 3.0.

[ DI AL UP MOD E M]
> 1 . CAL L I NG S T RI NG
2 . CAL L I NG N U MB E R
3 . I NI T I AL S T RI NG
4 . C ON NE CT I ON

[ LCD Screen ]DIALUP MODEM Setting Menu Screen

1) CALLING STRING

Range !~Z
Default ATD
Step -

 Set to use Dial-Up modem use. Select a dial string one among them.

2) CALLING NUMBER

Range !~Z
Default -
Step -

 Insert call number to call to. [Modem(Master station) phone number].


Total 16 digits shall be used from first digit space and empty space
shall be filled up by ‘X’.

65 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

3) INITIAL STRING

Range SPACE~Z
Default AT&C1 Q1 E0 M0 &D2 + CRM = 129
Step -

 Modem can be initialized by inserting total 30 figures of number,


character, space or special character.
 ETR306 should be reset before making a phone call(connection).

4) CONNECTION

[ CONN E C T I ON ]
> C md Re s ‘ T O: 2
Co n n e c t T O: 3 0
I d l e T i me : 6 0

[ LCD Screen ]DIALUP MODEM>>CONNECTION Setting Menu Screen

① Cmd Res’ TO

Range 0~255 s
Default 2
Step 1 s

 Setting Command response waiting time.


 If there is no response from a modem during setting time, it is
considered as a communication failure after setting time and status of
modem failure is maintained.

② Connect TO

Range 0~255 s
Default 30
Step 1 s

 Setting Modem connection waiting time.


 If there is no connection during setting time, it is considered as a
connection failure after setting time, status of modem failure is
maintained.

66 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

③ Idle Time

Range 0~255 s
Default 60
Step 1 s

 Setting Modem connection close time.


 During setting time, connection is closed after setting time.

(4) ANALOG EVENT


It moves to this menu if [ENT] key is pressed after locating cursor in "4.
ANALOG EVENT" in 'COMMUNICATION' menu. The analog event configuration
related to DNP3.0 protocol is set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ A NA L OG E V E NT ]
> AI E v t Me t h o d : OF F
AE v t S k i p a t F t : NO
Da i l y Ma x I : E NA BL E
F l t ‘I’ E v t : 1 S HOT
Av e r L o a d Ca l c T : 1 5
BI Qu e u e s i z e : 2 5 6
BI E v t Mo d e : AL L
AI Qu e u e s i z e : 2 5 6
AI E v t Mo d e : AL L
CI Qu e u e s i z e : 2 5 6
CI E v t Mo d e : AL L
T i me S y n’ Re f : L OCA L
T i me T a g T y p e : L OCA L

[ LCD Screen ] ANALOG EVENT Setting Menu Screen

1) AI Evt Method

Range OFF, TH, DB, BOTH


Default OFF
Step -

 This setting value is applied only to AI point with vitalized Event


Active : in DNP point map
 OFF : AI point event is not occurred.
 TH : Event is occurred when AI point data is over or less then

67 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Threshold value.
 DB : AI Event is occurred when AI data change value is over
deadband value.
 BOTH : TH and DB all used.
 Use ETR306 interface program to setting “Event Active” activation or
deactivation of AI point, Threshold value and Deadband value.

2) AEvt Skip at Ft

Range NO, YES


Default NO
Step -

 Determine either fault current report or not report.

3) Daily Max I

Range DISABLE, ENABLE


Default ENABLE
Step -

 Select whether to transfer event about daily max. load current.


- DISABLE : Daily Max. Load Current is not recorded as event.
- ENABLE : Daily Max. Load Current is recorded as event.

4) Flt ‘I’ Evt

Range NO, YES, 1SHOT


Default 1SHOT
Step -

 NO : Do not send all Fault Current Sequence to Event.


 YES : Send all Fault Current Sequence to Event.
 1SHOT : Send first Sequence Fault Current of Fault Sequence to
Event.

5) Aver Load Calc

Range 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 min


Default 15
Step -

 Set time interval for calculation of average load current.

68 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6) BI Queue size

Range 32, 64, 128, 256


Default 256
Step -

 Set binary input event queue size.

7) BI Evt Mode

Range ALL, LAST


Default ALL
Step -

 Set binary input event mode.


 ALL : All binary input event is buffed for same point.
 LAST : Only last event is buffed for same point.

8) AI Queue size

Range 32, 64, 128, 256


Default 256
Step -

 Set analog input queue size.

9) AI Evt Mode

Range ALL, LAST


Default ALL
Step -

 Set analog event mode.


 ALL : All analog input event is buffed for same point.
 LAST : Only last event is buffed for same point.

10) CI Queue size

Range 32, 64, 128, 256


Default 256
Step -

 Set counter event queue size.

69 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

11) CI Evt Mode

Range ALL, LAST


Default ALL
Step -

 Set counter event mode.


 ALL : All counter event is buffed for same point.
 LAST : Only last event is buffed for same point.

12) Time Syn’ Ref

Range LOCAL, GMT


Default LOCAL
Step -

 Set reference time type. It signifies the time data type when Time
Synchronizing with the master station.

13) Time Tag Type

Range LOCAL, GMT


Default LOCAL
Step -

 Set the time tag type for event in Communication.

(5) FTP FILE TRANSFER


In this menu, sets about file transfer. These are applied equally to DNP3
Protocol.

[ F T P F I L E T ANSF E R
> F T P Mo d e - R : DNP
F T P M o d e - W: DNP
F T P De v : PA D
F T P De v . No : CB0 0 1
F T P I D: E NT E C
F T P P W: 1 2 3 4
F T P P a s s i v e : DI S ABL E

[ LCD Screen ] FTP FILE TRANSFER Setting Menu Screen

70 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) FTP Mode-R

Range DNP, FTPC, FTPS, USER


Default DNP
Step -

 Select protocol for file transfer.


- DNP : Read file in DNP protocol method.
- FTPC : Read file in FTP Client method.
- FTPS : Read file in FTP Sever method.
- USER : Read file in user’s method.

2) FTP Mode-W

Range DNP, FTPC, FTPS, USER


Default DNP
Step -

 Select protocol for file transfer.


- DNP : Write file in DNP protocol method.
- FTPC : Write file in FTP Client method.
- FTPS : Write file in FTP Sever method.
- USER : Write file in user’s method.

3) FTP Dev

Range SPACE~z
Default PAD
Step -

 Select Device Type for FTP file classification.

4) FTP Dev.NO

Range SPACE~z
Default CB001
Step -

 Select Device Number for FTP file classification.

5) FTP ID

Range SPACE~z
Default ENTEC
Step -

71 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

 Set ID of device used for connection with FTP.

6) FTP PW

Range SPACE~z
Default 1234
Step -

 Set FTP connection password.

7) FTP Passive

Range DISABLE, ENABLE


Default DISABLE
Step -

 Select FTP connecting method.


 ENABLE means to use Passive method.
 DISABLE means to use Active method.

6.5.1.3. EVENT RECORDER


It moves to this menu if [ENT] key is pressed after locating cursor in "3.
EVENT RECORDER" in 'GLOBAL SETTING' menu. The particulars related to
waveform record are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ E V E NT R E C OR DE R ]
> Wa v e Ca p t u r e : ON
Wa v e S/ R: 3 2
Wa v e Pr e - Cy c l e : 5
Wa v e Po s t - Cy c l e : 5
Wa v e He a d - Cy c l e : 5
Wa v e Ca p t u r e Wa y : 1

[ LCD Screen ] EVENT RECORDER Setting Menu Screen

72 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Wave Capture

Range ON, OFF


Default ON
Step -

 Selects whether to record waveform or not.

2) Wave S/R

Range 16, 32 sample


Default 32 sample
Step -

 Select a number of sampling for wave capture.

3) Wave Pre-Cycle

Range 1 ~ 10 cycle
Default 5
Step 1 cycle

 Pre-cycle is to record(capture) a number of wave cycle before trigger


occurring.

4) Wave Post-Cycle

Range 1 ~ 10cycle
Default 5
Step 1 cycle

 The Post-Cycle is number of waveform cycle recorded after trigger is


cleared in case waveform is long.

5) Wave Head-Cycle

Range 1 ~ 10 cycle
Default 5
Step 1 cycle

 The Head-Cycle is number of handled cycle in front of waveform.

73 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.1.4. MONITORING
It moves to this menu if [ENT] key is pressed after locating cursor in "4.
MONITORING" in 'GLOBAL SETTING' menu.

[ MON I T OR I N G]
> 1 . BAT T E RY T E S T
2 . T D MO N I T O R

[ LCD Screen ] MONITORING Setting Menu Screen

(1) BATTERY TEST


It moves to this menu if [ENT] key is pressed after locating cursor in "1.
BATTERY TEST" in 'MONITORING' menu. The set value alteration process is
identical to "MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE” .

[ BA T T E RY T E ST ]
> P e r i o d : 2 4

[ LCD Screen ] BATTERY TEST Setting Menu Screen

1) Period

Range OFF, 1 ~ 720 hour


Default 24
Step 1 hour

 Set time period for automatic battery test.

74 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(2) TD MONITOR
It moves to this menu if the [ENT] key is pressed after locating the cursor in
"2. TD MONITOR" in the 'MONITORING' menu. It sets about the transducer that
can be used as a DC analog input monitoring usage in the menu. The set value
alteration process is identical to "MAIN MENU(COM)/ GLOBAL SETTING/
SYSTEM/ POWER LINE” 's alteration process.

[ T D MO N I T O R ]
> T D1 Ra t e : 4 0
T D1 Ra t i o : 1
T D1 Of f s e t : + 0
T D1 - 1 T y p e : UNDE R
T D1 - 1 P U: 2 3 . 0
T D1 - 1 De l a y : 0 . 5 0
T D1 - 2 T y p e : UNDE R
T D1 - 2 P U: 2 1 . 0
T D1 - 2 De l a y : 0 . 5 0
T D2 Ra t e : 4 0
T D2 Ra t i o : 1
T D2 Of f s e t : + 0
T D2 - 1 T y p e : UNDE R
T D2 - 1 P U: OF F
T D2 - 1 De l a y : 0 . 5 0
.
..

T D4 - 2 T y p e : UNDE R
T D4 - 2 P U: OF F
T D4 - 2 De l a y : 2 . 0 0

[ LCD Screen ] TD MONITOR Setting Menu Screen

 It has a 4 channel transducer and each channel has 2 pickup elements.


 The rating of DC1 of the control device is 20mA and refers to TD3
settings. (it is mapped as TD1 in the DNP Index Map.)
 The rating of DC2 of the control device 20mA and refers to TD4
settings. (it is mapped as TD2 in the DNP Index Map.)
 The rating of the DC3 is 40V and refers to TD1 setting.
 The rating of the DC4 is 40V and refers to TD2 setting.
 DC3 and DC4 are each both fixed by battery voltage and charger voltage.
 The pickup value of TD1-1 is used for battery bad detection.
 The pickup value of TD1-2 is used for overdischarge detection.
 TD2-1 is used for charger bad detection.
 Presently, DC1 and DC2 can be used by the user as spare channel.

75 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) TD1 Rate

Range 1 ~ 200
Default 40
Step -

 Set Transducer 1(TD1) monitoring range.

2) TD1 Ratio

Range 1 ~ 3000
Default 1
Step 1

 Set Transducer 1(TD1) ratio.

3) TD1 Offset

Range -10000 ~ +10000


Default 0
Step 1

 Set an Offset of Transducer 1(TD1).

4) TD1-1 Type

Range UNDER, OVER


Default UNDER
Step -

 Set Transducer 1(TD1) Under or Over. Under setting provides pickup


and alarm when it senses under the pickup value. Over setting
provides pickup and alarm when it senses over the pickup value.

5) TD1-1 PU(V)

Range OFF, 0.0 ~ 6000.0


Default 23.0
Step 0.1

 Set TD1 pickup value.

76 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6) TD1-1 Delay

Range 0.01 ~ 600.00 sec


Default 0.50
Step 0.01 sec

 Set a delay time of TD1.

7) TD1-2 Type

Range UNDER, OVER


Default UNDER
Step -

 Set the 2nd monitoring element of TD1.

8) TD1-2 PU(V)

Range OFF, 0.0 ~ 6000.0


Default 21.0
Step 0.1

 Set the 2nd pickup value of TD1.

9) TD1-2 Delay

Range 0.01 ~ 600.00 sec


Default 0.50
Step 0.01 sec

 Set the 2nd delay time of TD1.

10) TD2~4's setting factor is identical to TD1's.

77 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.1.5. PLC
It moves to this menu if [ENT] key is pressed after locating cursor in "5. PLC"
in 'GLOBAL SETTING' menu.

[ P L C]
> 1 . C OMMO N
2 . DI / DO

[ LCD Screen ] PLC Setting Menu Screen

(1) COMMON
It moves to this menu if [ENT] key is pressed after locating cursor in "1.
COMMON" in 'PLC' menu.

[ C O MMON ]
> 1 . L OGI C T I ME R
2 . P UL SE T I ME R
3 . P UL SE C OU NT E R

[ LCD Screen ] PLC's COMMON Setting Menu Screen

A. LOGIC TIMER
It moves to this menu if [ENT] key is pressed after locating cursor in "1. LOGIC
TIMER" in 'COMMON' menu. The set value alteration process is identical to
"MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE” .

[ L OGI C T I ME R ]
> T M1 - P U : 0 . 0 1
T M1 - D O: 0 . 0 1
T M2 - P U : 0 . 0 1
T M2 - D O: 0 . 0 1
.
..

T M1 6 - P U : 0 . 0 1
T M1 6 - D O : 0 . 0 1

[ LCD Screen ] LOGIC TIMER Setting Menu Screen

78 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

 PLC has 16 logic timer.


 If Input A is occurred in logic timer, X time later, output B becomes 1. If
input A is disappeared, Y time later, output B becomes 0. Please refer
to "<Figure 6-4> Logic Timer Symbol".
 X is Pick-up timer, Y is Dropout timer.
 In PLC, A shall be input at user logic ITM□.
 In PLC, B is output for TM□.

TM□
X
A B
Y
0s/0s
<Figure 6-4> Logic Timer Symbol

1) TM1-PU

Range 0.01 ~ 600.00 sec


Default 0.01
Step 0.01 sec

 Set pickup time of Logic Timer 1.

2) TM1-DO

Range 0.01 ~ 600.00 sec


Default 0.01
Step 0.01 sec

 Set dropout time of Logic Timer 1.

3) Logic Timer 2~16(TM2~16)'s setting factor is identical to Logic Timer 1(TM1).

79 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

B. PULSE TIMER
It moves to this menu if [ENT] key is pressed after locating cursor in "2.
PULSE TIMER" in 'COMMON' menu. The set value alteration process is identical
to "MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE” .

[ P UL SE T I ME R ]
> P T M1 : 0 . 0 1
P T M2 : 0 . 0 1
P T M3 : 0 . 0 1
.
.
.
P T M1 6 : 0 . 0 1

[ LCD Screen ] PULSE TIMER Setting Menu Screen

 PLC has 16 pulse timer.


 When Input A becomes 1 in pulse timer, output B becomes 1, this output
comes for Y time. Please refer to “<Figure 6-5> Pulse Timer Symbol”.
 In PLC, A shall be input at user logic IPTM□.
 In PLC, B is output for PTM□.

PTM□

A B
Y
0s
<Figure 6-5> Pulse Timer Symbol

1) PTM1

Range 0.01 ~ 600.00 sec


Default 0.01
Step 0.01 sec

 Set output time of Pulse Timer 1.

2) Pulse Timer 2~16(PTM2~16)'s setting factor is identical to pulse timer 1(PTM1).

80 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

C. PULSE COUNTER
It moves to this menu if [ENT] key is pressed after locating cursor in "3.
PULSE COUNTER" in 'COMMON' menu. The set value alteration process is
identical to "MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE” .

[ PUL S E COUNT E R]
> P C1 : 1 0 0 0
P C2 : 1 0 0 0
P C3 : 1 0 0 0
.
.
.
P C1 6 : 1 0 0 0

[ LCD Screen ] PULSE COUNTER Setting Menu Screen

 PLC has 16 pulse counter.


 Whenever Input B becomes 0 and Input A becomes 1, pulse counter
increases and, it reaches to set number X, output C becomes 1. If Input
B becomes 1, Output C becomes 0 and increased count becomes 0.
Please refer to "<Figure 6-6> Pulse Counter Symbol".
 In PLC, A shall be input at user logic CLSET□.
 In PLC, B shall be input at user logic CLRST□.
 In PLC, C is output for CLT□

<Figure 6-6> Pulse Counter Symbol

1) PC1

Range 1 ~ 60000
Default 1000
Step 1

 Set output count value of Pulse Counter 1(PC1).

2) Pulse Counter 2~16(PC2~16)'s setting factor is identical to Pulse Counter


1(PC1).

81 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(2) DI/DO
It moves to this menu if [ENT] key is pressed after locating cursor in "2.
DI/DO" in 'PLC' menu.

[ DI / DO]
> 1 . I NP UT DE B OU NC E
2 . OUT P UT PUL S E T I ME

[ LCD Screen ] PLC's DI/DO Setting Menu Screen

A. INPUT DEBOUNCE
It moves to this menu if [ENT] key is pressed after locating cursor in "1.
INPUT DEBOUNCE" n 'DI/DO' menu. The set value alteration process is
identical to "MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE”.

[ I NP UT DE B OU NC E ]
> I N1 0 1 : 0 . 0 2 0
I N1 0 2 : 0 . 0 2 0
I N1 0 3 : 0 . 0 2 0
.
..

I N1 0 8 : 0 . 0 2 0
I N2 0 1 : 0 . 0 0 5
..
.
I N2 2 4 : 0 . 0 2 0

[ LCD Screen ] INPUT DEBOUNCE Setting Menu Screen

 Input debounce timer is individually prepared in Control Input.


 Input debounce timer sets a time to remove Chattering of INPUT signal.
 In Input debounce timer, if Input A becomes 1, X time later, Output B
becomes 1. If Input A is disappeared, X time later, Output B becomes 0.
Please refer to "<Figure 6-7> Input Debounce Timer Symbol".
 In PLC, A is IN101~IN□ of Control Input, B is output for IN□.

82 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

IN□
X
A B
X
0s
<Figure 6-7> Input Debounce Timer Symbol

1) IN101

Range 0.005 ~ 10.000 sec


Default 0.020
Step 0.001 sec

 Set Input Debounce Time of IN101.

2) IN102~108 and IN201~224's set factor are identical to IN101's.


Only, IN201, IN202, IN205 ,IN206, IN209, IN210, IN213, IN214, IN217,
IN218, IN221 and IN222's default values are 0.005sec.

B. OUTPUT PULSE TIME


It moves to this menu if [ENT] key is pressed after locating cursor in "2.
OUTPUT PULSE TIME" in 'DI/DO' menu. The set value alteration process is
identical to "MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE” .

[ OU T P UT P UL SE T I ME ]
> OUT 1 0 1 : 0 . 0 1
OUT 1 0 2 : 0 . 0 1
OUT 1 0 3 : 0 . 0 1
.
.
.
OUT 1 0 8 : 0 . 0 1
OUT 2 0 1 : 0 . 1 0
.
..

OUT 2 1 2 : 0 . 0 3

[ LCD Screen ] OUTPUT PULSE TIME Setting Menu Screen

83 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

 Output Pulse Timer has Control Output individually.


 In output pulse timer, Input B is 0 and, depending on Input A, Output C
becomes 1. When Input A becomes 1, Output C becomes 1 for Y time.
However, if Y time is set for 0, depending on Input A, corresponding
coincidently and if A is 1, C becomes 1, and if A becomes 0 then, C
becomes 0 as buffer. Please refer to "<Figure 6-8> Output Pulse Timer
Symbol".
 In PLC, A shall be input at user logic IOUT□.
 In PLC, B shall be input at user logic BOUT□.
 In PLC, C is output for OUT□ and this output operates RELAY.

OUT□
A
Y C
B R
0s
<Figure 6-8> Output Pulse Timer Symbol

1) OUT101

Range OFF, 0.01 ~ 100.00 sec


Default 0.01
Step 0.01 sec

 Set Output pulse Time of OUT101.

2) OUT102~108 and OUT201~216's set factor is identical to OUT101's.


Only, OUT201, 203, 205, 207, 209 and 211's default value is 0.10sec and
OUT202, 204, 206, 208, 210 and 212's default value is 0.03sec.

84 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.1.6. OTHERS
It moves to this menu if [ENT] key is pressed after locating cursor in "6.
OTHERS" in 'GLOBAL SETTING' menu.

[ OT HE R S ]
> 1 . F A CT ORY DE BUG

[ LCD Screen ] OTHERS Setting Menu Screen

(1) FACTORY DEBUG


This menu is for Manufacture's maintenance purpose.

6.5.1.7. SAVE SETTING

MAIN MANU\ GLOBAL SETTING\ SAVE SETTING

① To save altered GLOBAL SETTING values, press [ENT]


button at screen ①. When value settings have been
SETTING CHANGED
PRESS <ENT> TO SAVE successfully altered, screen ② will be displayed.

② If press [FUN] button at screen ①, screen ③ will be


displayed.
[SAVE SETTING]

* SUCCESS * When there are no altered values and *. SAVE


③ SETTING" menu is selected, screen ④ appears.

[SAVE SETTING]
NOTE )
* ABORT *
The altered values have to be saved to take
④ effect. If saving is cancelled, previous values are
maintained.
* NOTHING CHANGED *

85 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.2. EVENT
It moves to this menu if [ENT] key is pressed after locating cursor in "2.
EVENT RECORDER" in 'MAIN MENU(COM)' menu.
ETR306 periodically checks event that happens during operation and records
events occurred by classifying them into operation event, fault event, system
event, set value alteration event, load event and diagnosis event. All event
record uses circulating record that records events above recording capacity in
oldest event location. Events related to ETR306 system can be checked and
erased in this menu.

[ E V E NT ]
> 1 . S Y S T E M
2 . S E T CHA NGE
3 . DI GNOS T I C
4 . CL E AR S AV E D DAT A

[ LCD Screen ] EVENT Menu Screen

This menu has submenus like following and can move to selected submenu using
[ENT] key.

6.5.2.1. SYSTEM
The system event records up to 2048 events max.

Move to “MAIN MENU(COM)/ EVENT/ SYSTEM” menu to check system event.

[001/2048] CPULINK [002/2048] CPULINK [003/2048] CPULINK


STATUS : HI/ASSERT STATUS : HI/ASSERT STATUS : HI/ASSERT

2008/10/01 00:00:03 2008/10/01 00:00:02 2008/10/01 00:00:01

Can check record using [▼][▲] keys. [001/2048] is latest event recorded.

86 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Trigger Source
 FI detection element
 52A contact point
 Front panel control
 AC power supply
 External control
 External input condition
 System warning

NOTE )
Refer to “APPENDIX C. LOGIC BIT ATTRIBUTES & DESCRIPTION” for
more details about trigger source.

Saving Method
Record in case of event occurrence(HI/ASSERT) or extinction(LO/DEASSERT).

Trigger Time
Every 1/4 cycle

Saving Capacity
Save maximum 2048 events.

6.5.2.2. SET CHANGE


The setting value alteration event saves up to 100 max.

Move to the “MAIN MENU(COM)/ EVENT/ SET CHANGE” menu to check the
setting value alteration event.

[001/100] LOCAL [002/100] LOCAL [001/100] LOCAL


TARGET : GLOBAL TARGET : GLOBAL TARGET : GLOBAL

2008/10/01 00:00:03 2008/10/01 00:00:02 2008/10/01 00:00:01

Can check the record using the [▼][▲] keys. [001/100] is the latest event
recorded.

87 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Trigger Source
 Changed set value menu
- GLOBAL SETTING
- PRIMARY SETTING
- ALTERNATE SETTING

 Alteration method
- LOCAL : Change the set value in local.
- REMOTE : Change the set value in remote.
- PROGRAM : Set value changed using the application program.

Saving Method
Record in case of changing the set value.

Trigger Time
Every 5msec

Saving Capacity
Save up to 100 events max.

6.5.2.3. DIAGNOSTIC EVENT


The diagnostic event records and indicates up to 512 max.

Move to the "MAIN MENU(COM)/ EVENT/ DIAGNOSTIC” menu to check the


diagnostic event.

[001/512] SELFTOK [002/512] SELFTOK [003/512] SELFTOK


STATUS : HI/ASSERT STATUS : HI/ASSERT STATUS : HI/ASSERT

2008/10/01 00:00:03 2008/10/01 00:00:02 2008/10/01 00:00:01

Can check the record using the [▼][▲] keys. [001/512] is the latest event
recorded.

88 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Trigger Source
 System power : AC power, battery, ±12V, +5V(SYSTEM POWER : AC,
Battery, ±12V, +5V)
 A/D conversion : A/D fault, standard voltage 1, standard voltage 2(A/D
Conversion : A/D Fail, Reference Voltage1, Reference Voltage 2)
 SLEEP MODE
 POWER DOWN MODE

NOTE )
Refer to “APPENDIX C. LOGIC BIT ATTRIBUTES & DESCRIPTION” for
more details about trigger source.

Saving Method
Record in case of event occurrence(HI/ASSERT) or extinction(LO/DEASSERT).

Trigger Time
Every 5msec

Saving Capacity
Save up to 512 events max.

89 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.2.3. CLEAR SAVED DATA

MAIN MANU(COM)/ EVENT/ CLEAR SAVED DATA

[CLEAR SAVED DATA]


>1.SYSTEM
Clear Saved Event Data
2.SET CHANGE Press [ENT] key after selecting item to be deleted. If it
3.DIAGNOSTIC
4.ABOVE ALL is successfully deleted, "EVENT CLEAR SUCCESS"
message appears.

[EVENT CLEAR]
4. ABOVE ALL
EVENT CLEAR SUCCESS
Clear all data from item 1 ~ 3.

6.5.3. MAINTENANCE
It moves to this menu if [ENT] key is pressed after locating cursor in "3.
MAINTENANCE" in 'MAIN MENU(COM)' menu.
This menu shows maintenance information of ETR306 and multi-way of
switchgear breaker and this menu shows information about ETR306's common
factor. This menu has following submenus and can move to selected submenu
using [ENT] key.

[ MA I N T E N A N CE ]
> 1 . C OU NT
2 . DAT A RE SE T
3 . CCU I NF O

[ LCD Screen ] MAINTENANCE Menu Screen

6.5.3.1. COUNT
This menu indicates counter information about ETR306's common factors and has
following submenus. Can move to selected submenu using [ENT] key.

[ C OU NT ]
> 1 . CCU

[ LCD Screen ] COUNT Menu Screen

90 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(1) CCU
Move to “MAIN MENU(COM)/ MAINTENANCE/ COUNT/ CCU" menu to check
ETR306 counter.

MAIN MANU(COM)/ MAINTENANCE/ COUNT/ CCU

[CCU] RESTART
RESTART: 30
DIAGNOSTIC: 0 Indicate the number of restarted ETR306.

DIAGNOSTIC
Indicate the number of self diagnosis error detection.

6.5.3.2. DATA RESET


Move to "MAIN MENU(COM)/ MAINTENANCE/ DATA RESET” menu. In this
menu, initial count is 0.

MAIN MANU(COM)/ MAINTENANCE/ DATA RESET

[DATA RESET] Reset saved data


>1.CCU COUNT
2.COUNT ALL Press [ENT] key after selecting item to be initialized.
3.COMM BUFF
4.ABOVE ALL
The "DATA CLEAR SUCCESS” message appears if it
was successfully deleted.
[CLEAR DATA]

DATA CLEAR SUCCESS


4. ABOVE ALL
Reset all data from item 1 ~ 3

6.5.3.3. CCU INFORMATION


To check ETR306 information, move to “MAIN MENU(COM)/ MAINTENANCE/ CCD
INFO” menu.

MAIN MANU(COM)/ MAINTENANCE/ CCU INFO

TYPE:ETR306 Displays present ETR306 information.


01:00000b01 00000020
02:31040000 44800000 Use [▼][▲] keys to move to each page.
03:0000b77d

MPU Ver: 1.0


DSP Ver: 2.26
CPU Ver: 1.01

91 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.4. TIME
It moves to this menu if [ENT] key is pressed after locating cursor in "4. TIME"
in 'MAIN MENU(COM)' menu.

MAIN MANU(COM)/ TIME

[CURRENT TIME] Sets present date and time.


2009/01/01 00:00:00

PRESS <ENT> TO SET


1) Press [ENT] key to select and change set value.
[SETTING TIME] 2) Use [▲][▼] keys to change number and press
2009/01/01 00:00:00
USE [UP/DOWN/ENTER] [ENT] key to move to next item.
PRESS <FUNC> : ABORT 3) Press [ENT] key to save all set values after
[SAVE TIME] altering.
2009/05/05 00:00:00

PRESS <ENT> TO SAVE

6.5.5. STATUS
It moves to this menu if [ENT] key is pressed after locating cursor in "5.
STATUS" in 'MAIN MENU(COM)' menu. This menu has following submenus and
can move to selected submenu using [ENT] key.

[ S T A T US]
> 1 . CCU
2 . I NP UT P OR T S
3 . OUT P UT P ORT S

[ LCD Screen ] Status Menu Screen

92 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.5.1. CCU
Can be checked by moving to “MAIN MANU(COM)/ STATUS/ CCU” menu.

MAIN MANU(COM)/ STATUS/ CCU

[CCU] It can be checked present ETR306’s condition of all factors


>POWER : ON
BATTERY : NORMAL using [▼][▲] key.
BAT’CHARGER : NORMAL
DOOR : CLOSE
DNP ADDRESS : 0
MASTER ADDR : 65534
POWER
GAS : NORMAL External power supply status is displayed. (ON, OFF)

BATTERY
Battery status is displayed. (NORMAL, FAIL)

BAT’ CHARGER
Battery charger status is displayed. (NORMAL, FAIL)

DOOR
Door status is displayed. (OPEN, CLOSE)

DNP ADDRESS
ETR306 DNP set address is displayed(0~65535).

MASTER ADDR
DNP host initial address
(0~65534:65535 is used for Broadcast)

GAS
Circuit breaker gas pressure status is displayed.
(NORMAL, LOW)

93 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.5.2. INPUT PORTS


Can be checked by moving to “MAIN MANU(COM)/ STATUS/ INPUT PORTS”
menu.

MAIN MANU(COM)/ STATUS/ INPUT PORTS

[INPUT PORTS] Display 32 input terminal(IN101 ~ IN108 and IN201 ~


IN 101 : LO/DEASSERT
IN 102 : LO/DEASSERT IN224) status. Depending on input signal, “HI/ASSERT”
:
IN 108 : LO/DEASSERT or “LO/DEASSERT” is displayed.
IN 201 : HI/ASSERT
:
IN 224: HI/ASSERT [▼][▲] key is used to check all input terminal status.

6.5.5.3. OUTPUT PORTS


Can be checked by moving to “MAIN MANU(COM)/ STATUS/ OUTPUT PORTS”
menu.

MAIN MANU(COM)/ STATUS/ OUTPUT PORTS

[INPUT PORTS] Display 20 output terminal(OUT101 ~ OUT108 and


OUT 101: LO/DEASSERT
OUT 102: LO/DEASSERT OUT201 ~ OUT212) status. Depending on output signal,
:
OUT 108: LO/DEASSERT “HI/ASSERT” or “LO/DEASSERT” is displayed.
OUT 201: HI/ASSERT
:
OUT 212: HI/ASSERT [▼][▲] key is used to check all input terminal status.

94 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.6. METERING
It moves to this menu if [ENT] key is pressed after locating cursor in "6.
METERING" in 'MAIN MENU(COM)' menu. In this menu, It indicates present
measurement value about common factors and it has following submenus. Can
move to selected submenu using [ENT] key.

[ ME T E R I N G ]
> 1 . F R E QU E N CY
2 . T D
3 . CCU RE F

[ LCD Screen ] METERING Menu Screen

6.5.6.1. FREQUENCY
Can be checked by moving to “MAIN MANU(COM)/ METERING/ FREQUENCY”
menu.

MAIN MANU(COM)/ METERING/ FREQUENCY

[FREQUENCY] It indicates measurement value of frequency for 1 way.


1 WAY : 0.00Hz

6.5.6.2. TD Monitoring
Can be checked by moving to “MAIN MANU(COM)/ METERING/ TD
MONITORING” menu. It sets about the transducer that can be used as a DC
analog input monitoring usage in the menu.

MAIN MANU(COM)/ METERING/ TD MONITORING

[TD MONITERRING] It indicates TD(transducer) input values.


TD1: 00.0 TD2: 00.0
TD3: 00.0 TD4: 00.0

95 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.5.6.3. CCU Reference


The “MAIN MANU(COM)/ METERING / CCU REF” can be checked by moving to
main menu.

MAIN MANU(COM)/ METERING/ CCD REF

[CCU REFERENCE] It indicates ETR306 reference value.


+5V : 4.9 -5V :-4.9
Ref1:2.5V Ref2:2.5V +5V, -5V : It indicates ±5V reference voltage.
Temp: 37˚
Ref 1,2 : It indicates reference voltage 1,2 of A/D
converter.
Temp : It indicates ETR306's inner temperature.

96 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6. Circuit Main Menu(CIRCUIT)


It moves to main menu if [FUN] key is pressed in initial screen of each way of
switchgear and moves to initial screen if pressed in main menu. The main menu
has following submenus.
The submenus in 'GROUP SETTING' menu for a switch part and for a way of
switchgear breaker part are different in each other. Other menus, however, for a
switch part and for a way of switchgear breaker part consist of same submenus.

[ MA I N ME N U ] 1 W
> 1 . GR OUP SE T T I NG
2 . MON I T OR I N G SE T
3 . E V E NT
4 . MA I N T E N A N C E
5 . ST AT UE
6 . ME T E R I N G

[ LCD screen ] Main Menu Screen

6.6.1. GROUP SETTING


It moves to this menu if [FUN] key is pressed after locating cursor in “1.
GROUP SETTING” in 'MAIN MENU'. The fault detection functions(SW) and
protection elements(CB) are set in this menu and it has following submenus.

[ GR OUP S E T T I NG]
> 1 . P R I MA R Y
2 . AL T E RNAT E
3 . ACT I V E GR OUP

[ LCD screen ] GROUP SETTING screen

The 'GROUP SETTING' menu is divided as PRIMARY group and ALTERNATE


group for user's convenience and set value applied group is selected through
ACTIVE GROUP menu.

97 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

MAIN MANU/ GROUP SETTING/ ACTIVE GROUP

[ACTIVE GROUP] The applied group is chosen according to Active factor's


>Active: PRIMARY
set value.

 PRIMARY : PRIMARY group's set value is applied.


 ALTERNATE : ALTERNATE group's set value is applied.

The set value alternation procedure is identical to "MAIN


MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER
LINE" 's alternation procedure.

6.6.1.1. GROUP SETTING for Switch(SW) Type


The submenu of PRIMARY group and ALTERNATE group are identical, and are
as follows.

[ P R I MA R Y S E T T I NG]
> 1 . P I CKUP CURRE NT
2 . I NRUS H RE ST RA I NT
3 . DI R E C T I ON
4 . F . I S E T T I NG T I ME
5 ON/ OF F L E V E L
6 . P HA S E DI F F
7 . L I V E L I NE
* . S AV E SE T T I NG

[ LCD Screen ] GROUP SETTING Menu Screen

Caution : Changed set valued must be saved to be applied. When escaping


from "*. SAVE SETTING" menu or moving to high menu, changed
set value is saved by 'Changed set value saved message'.

98 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(1) PICKUP CURRENT


It moves to this menu if [ENT] key is pressed after locating cursor in “1.
PICKUP  CURRENT” in group menu. At this menu, fault detection current is set
and has menu as shown below.

[ P I CKUP CURRE NT ]
> P h a s e : 4 0 0
Gr o u n d : 7 0

[ LCD Screen ] PICKUP CURRENT Setting Menu Screen

1) Phase

Range 0(OFF), 10 ~ 1600 A


Default 400
Step 5 A

 Set pickup current of Phase Fault Detection.

2) Ground

Range 0(OFF), 10 ~ 1600 A


Default 70
Step 5 A

 Set pickup current of Ground Fault Detection.

(2) INRUSH RESTRAINT


It moves to this menu if [ENT] key is pressed after locating cursor in “2.
INRUSH RESTRAINT” in group menu. At this menu, inrush restraint settings are
set and has menu as shown below.
Inrush current restraint function is applied when both Source side and Load side
becomes live line status from dead line status and when close the switch. When
transient current is over inrush current level, fault pickup element operates
normally instead of inrush current restraint function. If it is under inrush current
level, restraint during inrush current time and operates the normal fault pickup
element after inrush current time.

99 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

[ I NRUSH RE S T RAI NT ]
> P H A - T i me : 0 . 2
G N D - T i me : 0 . 2
P HA - Mu l t i : 4
GN D - Mu l t i : 4

[ LCD Screen ] INRUSH RESTRAINT Settings Menu Screen

1) PHA-Time

Range 0.0 ~ 180.0 s


Default 0.2
Step 0.1 s

 Set inrush current time of phase.

2) GND-Time

Range 0.0 ~ 180.0 s


Default 0.2
Step 0.1 s

 Set inrush current time of ground.

3) PHA-Multi

Range 1 ~ 20
Default 4
Step 1

4) GND-Multi

Range 1 ~ 20
Default 4
Step 1

100 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(3) DIRECTION
It moves to this menu if [ENT] key is pressed after locating cursor in “3.
DIRECTION” in group menu. At this menu, fault direction detection settings are
set and has menu as shown below.

[ DI R E C T I ON ]
> 1 . P HA S E
2 . GROUND

[ LCD Screen ] FAULT DIRECTION DETECTION Setting Menu Screen

A. PHASE
It moves to this menu if [ENT] key is pressed after locating cursor in “1.
PHASE" in 'DIRECTION' menu. At this menu, direction detection settings of phase
fault are set and has menu as shown below.

[ P HA S E ]
> T y p e : DI S ABL E
M. T . A ( V 1 ) : 6 0
M. P . V : 1 0

[ LCD Screen ] PHASE FAULT DIRECTION DETECTION Setting Menu Screen

The direction distinction of phase fault current use normal voltage(V1) and
normal current(I1) of symmetry, and operation are as following.

 Distinguish in Forward if I1 phase about V1 is within ±90° according M.T.A


basis and if not in Reverse.
 When fault is occurred in Voltage Metering nearby, V1 value can be lost. In
this case, use saved V1 and perform directional detection.
 To operate in direction, V1 detected in fault status shall be bigger than min.
polarizing voltage. If V1 is smaller than this setting value then it does not
detect direction even when fault current is over pickup current.
 To operate in direction, I1 detected in fault status shall be bigger than min.
threshold current. If I1 is smaller than this setting value then it does not
detect direction even when fault current is over pickup current.

101 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Polarizing Referance V1
Voltage:

Typical Fault Angle

Ze
ro
I1 M.T.A= 60˚ Lag

T
orq
e
Lin

ue
e
rqu

Lin
To
m

e
u
xim
Ma

FO
RW
O
RE

RD
VE
RS
E

<Figure 6-9> Phase Directional Detection Element Characteristic

1) Type

Range DISABLE, ENABLE


Default DISABLE
Step -

2) M.T.A(V1)

Range 0 ~ 359 °Lag


Default 60
Step 1 °Lag

102 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

3) M.P.V

Range 0(OFF), 1 ~ 80%


Default 10
Step 1%


B. GROUND
It moves to this menu if [ENT] key is pressed after locating cursor in “2.
GROUND" in 'DIRECTION' menu. At this menu, direction detection settings of
ground fault are set and has menu as shown below.

[ GR OU ND]
> T y p e : DI S ABL E
M. T . A ( - V 0 ) : 6 0
M. P . V : 1 0

[ LCD Screen ] GROUND FAULT DIRECTION DETECTION Setting Menu Screen

 Directional Detection of Ground fault current use Zero Seq. Voltage(V0) and
Zero Seq. Current(I0).
 IF phase angle of I0 about –V0 is within ±90° based on Max. Torque Angle is
Forward, if not is Reverse.
 To operates in direction, 3V0 detected in fault status shall be bigger than min.
polarizing voltage. If 3V0 is smaller than each element setting does not detect
direction, even fault current are over min. pickup current setting value.

1) Type

Range DISABLE, ENABLE


Default DISABLE
Step -

103 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

2) M.T.A(-V0)

Range 0 ~ 359 °Lag


Default 60
Step 1 °Lag

3) M.P.V

Range 0(OFF), 11 ~ 80%


Default 10
Step 1%


Polarizing Referance
-V0
Voltage:

Typical Fault Angle


Ze M.T.A= 45° Lag
ro In
To ne
rq Li
u e ue
Li rq
ne To
um
xim
a
M

FO
R
W
O
R
R D
EV
ER
SE

V0

<Figure 6-10> Ground Directional Detection Element Characteristic

104 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(1) F.I SETTING TIME


It moves to this menu if [FUN] key is pressed after locating cursor in “4. F.I
SETTING TIME" in group menu. At this menu, set permanent fault and temporary
fault time settings and menu is as shown below.

[ F . I SE T T I NG T I ME ]
> P e r ma n e n t : 2 0
T e mp o r a r y : 2
T y p e I d e l a y : 0 . 0 3

[ LCD Screen ] F.I SETTING TIME Setting Menu Screen

Fault Indicator(F.I.) has PERMANENT mode and TEMPORARY mode, it operates


depending upon a fault of Current and Voltage. ‘Type I delay’ mode operates
depending upon a fault of Current only.
After a Line fault(C/B Trip), Fault Indicator is ready to operate. After C/B
connection, if fault disappears, Temporary FI operates after a certain time and
Permanent FI is RESET.
After C/B connection, if fault remains(C/B TRIP), after a certain time, it is
figured as permanent fault, Permanent FI operates and Temporary FI is reset.
PERMANENT mode shall have enough Permanent Set Time considering cycle of
C/B reclosing.
Fault indicator type can be set in "MAIN MENU(COM)/ GLOBAL SETTING/
SYSTEM/ FI TYPE SELECT". Following is fault detection method based on the
fault indicator type.

105 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

A. ‘IV' Type - Permanent FI Detect


It is used for the permanent FI detection of distribution line and it operates
according to following condition.

Voltage

Pickup Level

Current

Temporary
FI SETTING TIME

Permanent
FI SETTING TIME

CLEAR

Temporary FI

Permanent FI
AUTO
FI SET RESET

Permanent Fault

<Figure 6-11> Permanent FI Detection (1)

Occurrence Condition
FI information is set when becomes dead line status after fault current over the
minim. pickup current flowed in live line status, and set the fault type in FI if
dead line status is maintained during setting time (permanent FI Set Time,
1sec~180sec possible to change, Default: 20 second). But, when returns to live
line status by reclosing before the permanent FI Set Time, FI Set Time is
initialized and returned to the first permanent FI occurrence condition.

Clear Condition
It is cleared by Fault indicator reset button or remote FI reset button.

106 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

A,N A,N B,N B,N

P.C
Permanent
N.C FI Set Time

0.6s 2s 15s

① ② ③ ④ ⑤
FI Occurrence(A,N) FI Occurrence(B) Permanent FI Occurrence
Fault Current(A,B,C,N)

<Figure 6-12> Permanent FI Detection (2)

 Fault is experienced in normal status and FI is occurred at no-voltage time


(①②③④ time : additional occurred phase update)
 Fault current size is the max. RMS value which is from the fault detect to the
no-voltage. Event time is handled by the no-voltage detect time
※. When the "Fault 'I' Report - Event Set" setting is "1Shot", fault current
Event is occurred only at the first fault.
 Additional FI is not occurred when fault has detected in the same phase
during Sequence operation. When fault is detected in other phase during
Sequence, FI is occurred in the detected phase(③)
 After Sequence is finished (permanent fault judge time), send the FI occurred
event and fault current to the main device(⑤)
 This is cleared by “FI Reset" command, “Permanent FI occurrence” and “F I
occurrence” event clear.

107 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

B. ‘IV' Type - Temporary FI Detection


It is used for Temporary fault monitoring of distribution line and operates based
on the following condition.

선 VOLTAGE
로 전 압

P IFI
CK PICKPU
UP치

선CURRENT
로 전 류

TEMPORARY
순 간
F I S E T FI
T I SET
N G TIME
T IM E

일 시
PERMANET
F I S E T TFII NSET
G TIME
T IM E

C LEAR

순TEMPORARY
간 FI FI
FI SET

일PERMANENT
시 FI FI

TEMPORARY
순 간 고 FAULT

<Figure 6-13> Temporary FI Detection (1)

Occurrence Condition
When fault current over the setting value flows and then becomes dead line, FI
event is occurred. If it becomes normal current in live line status by reclosing in
source side, after the setting time (Temporary FI Set Time, 1 sec~180sec
variable Default:2sec) Temporary FI is occurred.

Clear Condition
It is cleared by Fault indicator reset button or remote FI reset button.

108 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

A,N B,N Temporary


FI Set Time
P.C
N.C


0.6s 2s Temporary FI
Occurrence
① ②
FI Occurrence(A,N) FI Occurrence(B)
Fault Current(A,B,C,N)

<Figure 6-14> Temporary FI Detection (2)

 Fault is experienced in normal status and FI is occurred at no-voltage time


(①② : additional occurred phase update)
 Fault current size is the max. RMS value which is from the fault detect to the
no-voltage. Event time is handled by the no-voltage detect time
※. If the "Fault 'I' Report - Event Set" setting is "1Shot", Fault current Event
is occurred at first fault only.
 Additional FI is not occurred when fault has detected in the same phase
during Sequence operation. When fault is detected in other phase during
Sequence, FI is occurred in the detected phase(②)
 After several times of line normal status (Temporary FI judge time),
"Temporary fault occurrence" event is sent to the main device (③)
 This is cleared by “FI Reset" command and “Temporary FI occurrence“ and
“FI occurrence” events are cleared

109 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

C. ‘I' Type
Occurrence Condition
In case of I type for TYPE SELECT, FI is occurred regardless of voltage status,
if fault current higher than FI pickup current continues to flow during setting
time (Type I delay Set Time, 0.03 sec~180sec variable Default: 0.03sec).

Clear Condition
It is cleared by Fault indicator reset button or remote FI reset button.

FI PICKUP

NORMAL
CURRENT

FI DELAY TIME

CLEAR

FI

FI SET

<Figure 6-15> I type FI Detection (1)

A,N

P.C
N.C
Type I delay
Set Time

FI Occurrence(A,N)
Fault Current(A,B,C,N)

<Figure 6-16> I type FI Detection (2)

 If fault current keeps during the setting time(Type I delay Set Time), FI is
occurred(①).
 Fault current size is the max. RMS value during the setting time.
※. If the "Fault 'I' Report - Event Set" setting is "1Shot", Fault current Event
is occurred at first fault only.
 This is cleared by “FI Reset" command and “FI occurrence“ events are
cleared.

110 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Permanent

Range 1 ~ 180sec
Default 20
Step 1sec


2) Temporary

Range 1 ~ 180sec
Default 2
Step 1sec


3) Type I delay

Range 0.03 ~ 180sec


Default 0.03
Step 0.01sec


(2) ON/OFF LEVEL


It moves to this menu if [ENT] key is pressed after locating cursor in “5.
ON/OFF LEVEL" in group menu. At this menu, set Phase Open/Loss detection
and menu is as shown below.

[ ON / OF F L E V E L ]
> On L e v e l : 0 . 8 0
Of f L e v e l : 0 . 5 0
De t e c t T i me : 0 . 0

[ LCD Screen ] ON/OFF LEVEL Setting Menu Screen

111 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

For Phase Open/Loss function, if voltage of 1 or 2 of 3 phases is below Off


level, it is judged as Phase Open/Loss and if all 3 phases are above On Level, it
is judged as normal voltage and Phase Open/Loss is cleared. In addition, if all 3
phases are below Off Level, Phase Open/Loss is not indicated since it is judged
as normal(dead line).

1) On Level

Range 0.70 ~ 0.85 pu


Default 0.80
Step 0.1 pu

 Set normal voltage level.


 This setting is applied with multiple of rated voltage.

2) Off Level

Range 0.30 ~ 0.75 pu


Default 0.50
Step 0.01 pu

 Set Phase Open/Loss level.


 This setting is applied with multiple of rated voltage.

3) Detect Time

Range 0.0 ~ 180.0 sec


Default 0.0
Step 0.1 sec

 Set delay time of Phase Open/Loss.

(3) PHASE DIFFERENCE


It moves to this menu if [ENT] key is pressed after locating cursor in “6.
PHASE DIFF" in group menu. At this menu, set Phase Difference(Phase
Synchronism Fail) detection and menu is as shown below.

[ P HA S E DI F F ]
> L e v e l : 3 0
T i me : 1 . 0

[ LCD Screen ] PHASE DIFFERENCE Setting Menu Screen

112 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

If one or two of two way of switchgears that are in a live line condition is
above set angle when voltage phase to phase is compared in an open condition
by them, it is judged as phase difference.
The one that is standard from two way of switchgears is way of switchgear
close to way of switchgear 1 or input way of switchgear. The standard way of
switchgear does not detect(indicate) phase difference. The phase difference
status immediately returns when phase difference gets below set value or one of
two way of switchgears becomes dead line.

1) Level

Range 0(OFF), 5 ~ 80 Deg


Default 30
Step 1 Deg

 Sets detection angle of phase difference element.

2) Time

Range 0.0 ~ 180.0s


Default 1.0
Step 0.1s

 Sets determination time of phase difference element.

(4) LIVE LINE


It moves to this menu if [ENT] key is pressed after locating cursor in “7. LIVE
LINE" in group menu. ETR306 has Live line detection element. If one phase
voltage among three phase maintains over live line detection level during a
constant time, live line is detected. Live line detection setting item is same as
below.

[ L I V E L I NE ]
> L i v e L i n e L v : 0 . 3 0
L i v e L i n e T m: 4 . 0

[ LCD Screen ] LIVE LINE Setting Menu Screen

113 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Live Line Lv

Range 0.10 ~ 0.90 pu


Default 0.1
Step 0.01 pu

 Set live line level and this is set in multiple of previous rating.

2) Live Line Tm

Range 0.0 ~ 180.0 sec


Default 0.0
Step 0.1 sec

 Set delay time of live line detection element.

(5) SAVE SETTING


It has same function and structure with "MAIN MENU(COM)/ GLOBAL SETTING/
*. SAVE SETTING". Refer to "6.5.1.7. SAVE SETTING".

114 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.1.2. GROUP SETTING for Circuit Breaker(CB) Type


The submenu of PRIMARY group and ALTERNATE group are identical, and are
as follows.

[ P R I MA R Y S E T T I NG]
>1 . 5 1 P : T I M E OC - P HA
2 . 5 1 G: T I ME OC - GND
3 . 5 0 P : I NS T ' OC - P HA
4 . 5 0 G: I NS T ' OC - GND
5 . C OL D L OA D P I CKUP
6 . DI R E C T I ON
7 . USE R CURV E
8 . R E CL OS I NG( 7 9 )
9 . ON/ OF F L E V E L
1 0 . PHAS E DI F F
1 1 . L I V E L I NE
* . S AV E SE T T I NG

[ LCD Screen ] GROUP SETTING Menu Screen

Caution : Changed set valued must be saved to be applied. When escaping


from "*. SAVE SETTING" menu or moving to high menu, changed
set value is saved by 'Changed set value saved message'.

(1) Phase Time Overcurrent(51P)


ETR306 has a phase time overcurrent element to set based on CT secondary
current as connected the current inputs. The phase time overcurrent element
provides a time delay versus current for tripping that is used for an inverse time
curve characteristic coordinated with current pickup value, curve type, time dial,
time adder, minimum response time(MRT) and reset method.
This inverse characteristic means that time overcurrent element operates slowly
on small values of current above the pickup value and operates faster when
current increases significantly above the pickup value. The phase time
overcurrent element is enabled in the Primary, Alternate settings and
[PROTECTION] in user interface panel.
Multiple time curves and time dials are available for the phase time overcurrent
element to respectively coordinate with other protection elements in ETR306 and
other external devices on the distribution system. ANSI, IEC, ESB, USER and
non-standard time current curves are included in ETR306. A User Programmable

115 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

curve option is also available allowing the user to create customer time current
curves for more enhanced coordination than the standard curve types.
Two methods of this resetting operation are available, Instantaneous and Linear.
The Instantaneous selection is intended for applications with other relays, such
as most static units, which set the energy capacity directly to zero when the
current falls below the reset threshold. The Linear selection can be used where
the relay must coordinate with electro-mechanical units.

If the circuit breaker is closed by pressing the [CLOSE] button on the front
panel, or by an remote control or via SCADA, the phase time overcurrent
element is prevented from tripping for a period specified by the Cold load pickup
scheme.

The phase time overcurrent element setting factors are as follows. It moves to
this menu if [ENT] key is pressed after locating cursor in “1. 51P:TIME
OC-PHA" in group setting menu.

[ 5 1 P 1 : T I ME OC - P HA ]
> P i c k u p : 4 0 0
Cu r v e : [ N1 ]
T i me Di a l : 1 . 0 0
T i me Ad d r : 0 . 0 0
M. R . T : 0 . 0 0
Re s e t Me t h o d : I NST

[ LCD Screen ] PHASE TIME OVERCURRENT Setting Menu Screen

1) Pickup

Range 0(OFF), 10 ~ 1600 A


Default 400
Step 5 A

116 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

2) Curve

Range A(101), B(117), ... , DEF10


Default N1
Step -





[Table 6-4] ETR306's time-current operation characteristic curve setting range


Setting 1 2 3 4 5 6 7 8 9 10

Curve A(101) B(117) C(133) D(116) E(132) IEC-EI K(162) L(107) M(118) N(104)

Setting 11 12 13 14 15 16 17 18 19 20

Curve IEC-NI P(115) R(105) T(161) V(137) IEC-VI W(138) Y(120) Z(134) 1(102)

Setting 21 22 23 24 25 26 27 28 29 30

Curve 2(135) 3(140) 4(106) 5(114) 6(136) 7(152) 8(113) 8*(111) 9(131) 11(141)

Setting 31 32 33 34 35 36 37 38 39 40

Curve 13(142) 14(119) 15(112) 16(139) 18(151) N1 N2 N3 N4 ANSI-NI

Setting 41 42 43 44 45 46 47 48 49 50

Curve ANSI-VI ANSI-EI ES-NI ES-VI USER-1 USER-2 USER-3 USER-4 DEF-1S DEF-10S

117 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

3) Time Dial

Range 0.05 ~ 15.00


Default 1.00
Step 0.01

4) Time Addr

Range 0.00 ~ 10.00 sec


Default 0.00
Step 0.01 sec


5) M.R.T

Range 0.00 ~ 10.00 sec


Default 0.00
Step 0.01 sec

6) Reset Method

Range INST, LINEAR


Default INST
Step -

118 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(2) Ground Time Overcurrent(51G)


ETR306 has a ground time overcurrent element to set based on CT secondary
current as connected the current inputs. The ground time overcurrent element
provides a time delay versus current for tripping that is used for an inverse time
curve characteristic coordinated with current pickup value, curve type, time dial,
time adder, minimum response time(MRT) and reset method.
This inverse characteristic means that ground time overcurrent element operates
slowly on small values of current above the pickup value and operates faster
when current increases significantly above the pickup value. The ground time
overcurrent element is enabled in the Primary, Alternate settings and
[PROTECTION] and [GROUND] in user interface panel.
Multiple time curves and time dials are available for the ground time overcurrent
element to respectively coordinate with other protection elements in ETR306 and
other external devices on the distribution system. ANSI, IEC, ESB, USER and
non-standard time current curves are included in ETR306. A User Programmable
curve option is also available allowing the user to create customer ground time
current curves for more enhanced coordination than the standard curve types.
Two methods of this resetting operation are available, Instantaneous and Linear.
The Instantaneous selection is intended for applications with other relays, such
as most static units, which set the energy capacity directly to zero when the
current falls below the reset threshold. The Linear selection can be used where
the relay must coordinate with electro-mechanical units.
If the circuit breaker is closed by pressing the [CLOSE] button on the front
panel, or by an remote control or via SCADA, the ground time overcurrent
element is prevented from tripping for a period specified by the Cold load pickup
scheme.
The ground time overcurrent element setting factors are as follows. It moves to
this menu if [ENT] key is pressed after locating cursor in “2. 51G:TIME
OC-GND" in group setting menu.

[ 5 1 G1 : T I ME OC - GND]
> P i c k u p : 7 0
Cu r v e : [ N1 ]
T i me Di a l : 1 . 0 0
T i me Ad d r : 0 . 0 0
M. R . T : 0 . 0 0
Re s e t Me t h o d : I NST

[ LCD Screen ] GROUND TIME OVERCURRENT Setting Menu Screen

119 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Pickup

Range 0(OFF), 10 ~ 1600 A


Default 70
Step 5 A

2) Curve

Range A(101), B(117), ... , DEF10


Default DEF-1S
Step -


3) Time Dial

Range 0.05 ~ 15.00


Default 1.00
Step 0.01

4) Time Addr

Range 0.00 ~ 10.00 sec


Default 0.00
Step 0.01 sec


5) M.R.T

Range 0.00 ~ 10.00 sec


Default 0.00
Step 0.01 sec

120 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6) Reset Method

Range INST, LINEAR


Default INST
Step -

(3) Phase High Current Trip (50P)


ETR306 has a phase high current trip factor that judges whether to trip phase
high current trip or not by using CT secondary current. The phase high current
trip element applies a time delay about phase fault current. In case of phase
fault, delay time(trip time) of phase high current trip element should be set
identically or faster than phase time overcurrent element to immediately block
high current. The phase high current trip element can be used through Primary
and Alternate group setting and front panel [PROTECTION] button control. It
does not get influenced by phase high current trip cold pickup function.

[ 5 0 P 1 : I NS T ' OC - P HA ]
> P i c k u p : 3 5 0 0
T i me De l a y : 0 . 0 0

[ LCD Screen ] PHASE HIGH CURRENT TRIP Setting Menu Screen

The phase high current trip element setting factors is as follows and shall move
to "MAIN MENU/ GROUP SETTING/ PRIMARY or ALTERNATE/ 3. 50P: INST'
OC-PHA" in order to set phase high current trip element.

1) Pickup

Range 0(OFF), 50 ~ 10000 A


Default 3500
Step 1 A


121 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

2) Time Delay

Range 0.00 ~ 1.00 sec


Default 0.00
Step 0.01 sec

(4) Ground High Current Trip (50G)


ETR306 has a ground high current trip factor that judges whether to trip ground
high current trip or not by using CT secondary current. The ground high current
trip element applies a time delay about ground fault current. In case of ground
fault, delay time(trip time) of ground high current trip element should be set
identically or faster than ground time overcurrent element to immediately block
high current. The ground high current trip element can be used through Primary
and Alternate group setting and front panel [PROTECTION] and [GROUND]
button control. It does not get influenced by ground high current trip cold pickup
function.

[ 5 0 G1 : I NS T ' OC - GND]
> P i c k u p : 1 7 5 0
T i me De l a y : 0 . 0 0

[ LCD Screen ] GROUND HIGH CURRENT TRIP Setting Menu Screen

The ground high current trip element setting factors are as follows and shall
move to "MAIN MENU/ GROUP SETTING/ PRIMARY or ALTERNATE/ 4. 50G1:
INST' OC-GND" in order to set ground high current trip element.

1) Pickup

Range 0(OFF), 25 ~ 10000 A


Default 1750
Step 1 A


122 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

2) Time Delay

Range 0.00 ~ 1.00 sec


Default 0.00
Step 0.01 sec

(5) COLD LOAD PICKUP


It moves to this menu if [ENT] key is pressed after locating cursor in “5. COLD
LOAD PICKUP" in group menu. At this menu, set cold load pickup function and
menu is as shown below.

[ COL D L OA D PI CK UP ]
> P H A ( x MT C ) : 4
G N D ( x MT C ) : 6
R MT T i me - P H A : 0 . 3 0
R MT T i me - G N D : 0 . 3 0
RST T i me - P H A : 3 . 0 0
RST T i me - G N D : 3 . 0 0

[ LCD Screen ] COLD LOAD PICKUP Setting Menu Screen

The cold load pickup function is operated to prevent TRIP from overcurrent
elements when an inrush current occurs during manual closing by local/remote
control. The setting values of Cold Load Pickup function for phase, ground
overcurrent elements can be programmed separately.
If pickup level of overcurrent occurring at closing is over cold load pickup
current, trip is done by overcurrent function (Refer Inrush Current 1 in “<Figure
6-17> The Restore Minimum Time Characteristic”).
If overcurrent is below cold load pickup current and overcurrent pickup current,
overcurrent functions are not operated during a period of Restore minimum
Time(RMT)(Refer Inrush Current 2 in “<Figure 6-17> The Restore Minimum
Time Characteristic”). After RMT, overcurrent functions are operated. However,
if current is dropped below overcurrent pickup current during RMT, cold load
pickup function is reset after reset time(Refer Inrush Current 3 in “<Figure
6-17> The Restore Minimum Time Characteristic”).

123 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Current

Outage time Restore Minimum Time

Inrush current 1
CLPU Trip
Pickup Level

Inrush current 2
Trip
Overcurrent
Pickup Level
Inrush current 3

Time

<Figure 6-17> The Restore Minimum Time Characteristic

1) PHA(xMTC)

Range 0(OFF), 1 ~ 10
Default 4
Step 1


2) GND(xMTC)

Range 0(OFF), 1 ~ 10
Default 6
Step 1

124 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

3) RMT Time-PHA

Range 0(OFF), 0.01 ~ 30.00 sec


Default 0.30
Step 0.01 sec


4) RMT Time-GND

Range 0(OFF), 0.01 ~ 30.00 sec


Default 0.30
Step 0.01 sec

5) RST Time-PHA

Range 0.00 ~ 60.00 sec


Default 3.00
Step 0.01 sec


6) RST Time-GND

Range 0.00 ~ 60.00 sec


Default 3.00
Step 0.01 sec

125 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(6) DIRECTION
It moves to this menu if [ENT] key is pressed after locating cursor in “6.
DIRECTION” in group menu.

The directional controls provide overcurrent protection in the direction of power


flow. The directional controls are necessary for the protection of multiple
feeders, when it has the necessity of finding faults in different directions. The
directional controls are composed of phase and ground overcurrent elements.

If directional controls are selected, it will determine whether current flow in each
phase is in forward or reverse direction, as determined by the connection of the
phase CTs, selected Maximum Torque Angle (MTA), voltage and current phasors.
To increase security of all directional controls, add one power frequency cycle of
intentional delay to prevent incorrect operation.

The directional controls have each four settings. The directional controls settings
can be different in the Primary and Alternate settings.

[ DI R E C T I ON ]
> 1 . P HA S E
2 . GROUND

[ LCD Screen ] FAULT DIRECTION DETECTION Setting Menu Screen

A. PHASE
It moves to this menu if the [ENT] key is pressed after locating the cursor in
“1. PHASE" in the 'DIRECTION' menu. This setting is applied in the directivity
phase overcurrent protection element.

[ P HA S E ]
> T y p e : NONE
M. T . A ( V 1 ) : 6 0
M. P . V : 1 0
Bl o c k OC: NO

[ LCD Screen ] PHASE DIRECTION PROTECTION Setting Menu Screen

126 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Whether if the directivity phase overcurrent protection method is going to


operate or not depends on the direction set by differentiating the size and
direction of the fault current. The operation direction can be set in forward
direction or reverse direction and it can also be used with none detection that
operates only with the phase fault current's size(non directivity).
The overcurrent direction judgement uses symmetrical component's normal
voltage(V1) and normal current(I1) and whether operating or not depends on the
following.

 If the I1's phase about V1 is within ±90° with the maximum torque angle as a
reference, it is judged as forward direction and if not, it is judged as reverse
direction.
 The V1 value can be lost in case of fault occurrence in the voltage
measurement rootlet. At that moment, perform the direction differentiation for
a maximum of 1 seconds using the V1 recorded before. After that, it will be
decided whether it will be operated with overcurrent or not according to the
Block OC's set value.
 In order to operate with directivity, the V1 detected in a fault condition
should be above the set minimum polarizing voltage(M.P.V). In other words,
even if the phase fault current is above the pickup current, it will not operate
if V1 is below the set value(M.P.V). Only, it can be operated with only the
overcurrent according to the setting.

Polarizing Referance V1
Voltage:
Ze

Typical Fault Angle


ro

I1 M.T.A= 60° Lag


T
orq

e
Lin
ue

r que
Lin

To
um
e

x i m
Ma
FO
RW
OR
RE

D
VE
RS
E

<Figure 6-18> Phase Directional Protection Characteristic

127 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Setting
Block OC
(No or Yes)

AND
OverCurrent
Direction
Permission
V1 Blocking
-
Setting
+
MPV

Operation Enable
If V1 < MPV, Forward
Memorized V1 is used or
Reverse OR
for maximum 1 second

Update

V1 Memory
AND
Direction Determine
I1 Forward = MTA-90° < Θ <MTA+90°
Reverse = MTA+90° < Θ <MTA-90° Forward
Setting AND
or
MTA
Reverse
Setting None
Direction direction
(Forward or Reverse)
Setting
Direction
(None)

<Figure 6-19> Phase Directional Protection's Logic Diagram

1) Type

Range NONE, FORWARD, REVERSE


Default NONE
Step -

 Selects the phase direction type.


 NONE : It operates the phase overcurrent element only using the
current size regardless with directivity.
 FORWARD : It operates the phase overcurrent element only when it is
in forward direction.
 REVERSE : It operates the phase overcurrent element only when it is
in reverse direction.

2) M.T.A(V1)

Range 0 ~ 359 Deg Lag


Default 60 Deg Lag
Step 1 Deg

128 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

3) M.P.V

Range 0(OFF), 10 ~ 80%


Default 10
Step 1%


4) Block OC

Range NO, YES


Default NO
Step -


B. GROUND
It moves to this menu if the [ENT] key is pressed after locating the cursor in
“2. GROUND" in the 'DIRECTION' menu. This setting is applied in the directivity
ground overcurrent protection element.

[ GR OU ND]
> T y p e : NONE
M. T . A ( - V 0 ) : 6 0
M. P . V : 3 0
Bl o c k OC: NO

[ LCD Screen ] GROUND DIRECTION PROTECTION Setting Menu Screen

129 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Whether if the directivity ground overcurrent protection method is going to


operate or not depends on the direction set by differentiating the size and
direction of the ground fault current. The operation direction can be set in
forward direction or reverse direction and it can also be used with none
detection that operates only with the ground fault current's size(non directivity).
The overcurrent direction judgement uses symmetrical component's zero
sequence voltage(-V0) and zero sequence current(I0) and whether operating or
not depends on the following.

 If the I0's phase about -V0 is within ±90° with the maximum torque angle as
a reference, it is judged as forward direction and if not, it is judged as
reverse direction.
 The 3V0 value can be lost in case of fault occurrence in the voltage
measurement rootlet. At that moment, perform the direction differentiation for
a maximum of 1 seconds using the 3V0 recorded before. After that, it will be
decided whether it will be operated with overcurrent or not according to the
Block OC's set value.
 In order to operate with directivity, the 3V0 detected in a fault condition
should be above the set minimum polarizing voltage(M.P.V). In other words,
even if the ground fault current is above the pickup current, it will not
operate if 3V0 is below the M.P.V set value. Only, it can be operated with
only the overcurrent according to the setting.

Polarizing Referance
-V0
Voltage:

Typical Fault Angle


M.T.A= 45° Lag
Ze

In
ro

ne
To

Li
rq

ue
ue

rq
Li

To
ne

um
im
ax
M

FO
RW
O
RD
RE
VE
RS
E

V0

<Figure 6-20> Ground Directional Protection Characteristic

130 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

1) Type

Range NONE, FORWARD, REVERSE


Default NONE
Step -

 Selects the ground direction type.


 NONE : It operates the ground overcurrent element only using the
current size regardless with directivity.
 FORWARD : It operates the ground overcurrent element only when it
is in forward direction.
 REVERSE : It operates the ground overcurrent element only when it is
in reverse direction.

2) M.T.A(-V0)

Range 0 ~ 359 Deg Lag


Default 60 Deg Lag
Step 1 Deg

 et Maximum Torque Angle of zero sequence current (I0) about zero


sequence voltage(-V0), when detects phase fault.
 -V0 as the standard, set in clock wise direction.

3) M.P.V

Range 0(OFF), 10 ~ 80%


Default 30
Step 1%

 Set a Minimum Polarizing Voltage about zero sequence voltage(3V0) to


distinguish the direction.
 When 3V0 detected is below the set value, direction is not determined.
 Voltage is not applied in the determination of the direction when set as
0(OFF).

131 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4) Block OC

Range NO, YES


Default NO
Step -

 Sets whether the operation is going to be restricted or it is going to


be operated with an ground overcurrent element in case the 3V0 value
measured when failure happens is less than the M.P.V set value.
 NO : Trip due to overcurrent element is allowed.
 YES : It does not trip due to overcurrent element.

(7) USER CURVE


It moves to this menu if [ENT] key is pressed after locating cursor in “7. USER
CURVE” in group menu. The user defined T-C curve can be set in this menu.

[ USE R CURV E ]
> 1 . USE R CURV E 1
2 . USE R CURV E 2
3 . USE R CURV E 3
4 . USE R CURV E 4

[ LCD Screen] User Defined Curve Setting Menu Screen

This menu has submenus like above and moves to submenu selected using
[ENT] key.

A. USER CURVE 1~4


It sets user defined curve. Up to 4 are provided for USER CURVE 1~4 and is
calculated as follows.

USER CURVE SET


Trip Time(sec) = TD×(α/(Mβ-1)+γ) + TA
Reset Time(sec) = TD×(Rt/(1-M2))

132 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

[Table 6-5] Curve measurement


TD Time Dial
TA Time Adder
α, β, γ Characteristic constant
M Multiples of pickup current
Rt Reset characteristic constant

The user curve setting menu is composed of following sub items. Refer to
"APPENDIX A. TIME CURRENT CURVES” for detailed content. The set value
changing step is identical to changing step of "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.

[ USE R CURV E 1 ]
> F a c t o r a : 0 . 0 5 1 5
F a c t o r b : 0 . 0 2 0 0
F a c t o r r : 0. . 1 1 4 0
F a c t o r r t : 4 . 8 5 0 0

[ LCD Screen] User Defined Curve Setting Menu Screen

1) Factor a

Range 0 ~ 150.9999
Default 0.0515
Step 0.0001

 Set user defined curve's factor α value.

2) Factor b

Range 0.0200 ~ 150.9999


Default 2.0000
Step 0.0001

 Set user defined curve's factor β value.

3) Factor r

Range 0 ~ 150.9999
Default 1.8000
Step 0.0001

 Set user defined curve 1's factor γ value.

133 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4) Factor rt

Range 0 ~ 150.9999
Default 59.5000
Step 0.0001

 Set user defined curve's factor Rt value.

The default curve factors for USER CURVE 1~4 match with its IEEE standard
curve; IEEE Moderately Inverse, Very Inverse, Extremely Inverse and Long-Time
Extremely Inverse Curve, respectively. The default curve factors for USER
CURVE 1~4 are described in "[Table 6-6] User defined curve Default value".

[Table 6-6] User defined curve Default value


Curves α β γ Rt
User1 0.0515 0.02 0.114 4.85
User2 19.61 2.0 0.491 21.6
User3 28.2 2.0 0.1217 29.1
User4 5.67 2.0 0.0352 5.67

(8) RECLOSING (79)


It moves to this menu if [ENT] key is pressed after locating cursor in “8.
RECLOSING(79)” in group menu.

[ R E CL OS I NG( 7 9 ) ]
> 1 . F UNCT I ON
2 . OP E R A T I ON S
3 . I NT E RV A L S

[ LCD Screen ] RECLOSING(79) Setting Menu Screen]

134 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

ETR306 has Auto Reclosing(79) function that electrical power system can be
rapidly tripped when line fault is occurred, circuit breaker can be reclosed after
a given interval (reclosing interval). In case of temporary fault caused by
momentary contact of extraneous substance, lightning or loss of insulation and so
on, range of fault and outage time can be minimized by this reclosing function.
After a fault has occurred, the Reclose element closes the recloser when the
programmed reclose interval time expires. The number of operation lockout
setting is programmed one to four, and each reclose shot has its own separate
reclose interval timer.
If the fault is permanent and the recloser continues to trip and reclose, the
Reclose element will continue to increment the operating counter. If this
continues to the maximum number of the operating lockout programmed in the
Reclose element, the reclose logic lockouts. At this moment, if make close
operation remotely or locally, Lockout is released and fault detecting is activated.
Also, if the fault is temporary, the Lockout sequence of the Recloser is Rest by
Reset logic. If the fault is transient, then the reclose logic is reset by the reset
logic.
Auto reclosing sequence operation status is displayed on the LEDs of ‘79 Reset’,
‘79 Cycle’ and ‘79 Lockout’ as follows.

<Figure 6-21> Auto reclosing Sequence operation

135 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

LOCKOUT
Following cases are occurred to lockout. Due to the fact that auto reclosing does
not function in lockout status, circuit breaker should be closed to control locally
or remotely.

 Fault continues to flow, circuit breaker operates to trip as much as preset


operation number. (Permeant Fault)
 Circuit breaker operates manually to open
 Circuit breaker operates to trip fault current is higher than CLPU pickup
current during a period of CLPU operation
 Auto reclosing function is disabled, overcurrent protection trip operates.

Following “<Figure 6-22> Lockout Sequence Operation” describes a typical


protection sequence situation that the fourth trip for overcurrent protection
operates after than lockouts when total number of operation is set to four.

(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC (6) 3rd Reclose Interval Time
(7) 4th Trip - 4th TCC

<Figure 6-22> Lockout Sequence Operation

At the lockout status, if make close operation remotely or locally, Lockout is


released and fault detecting is activated after lockout reset time.

136 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

RESET
RESET is displayed on back to normal status, following cases are occurred to
reset.

 Lockout ➜ Reset : lockout reset time elapses after circuit breaker manually
or remotely operates to trip.
 Cycle ➜ Reset : auto reset time elapses after returning to normal status from
reclosing sequence for temporary fault.

Following “<Figure 6-23> Reset Sequence Operation” describes a typical


temporary fault protection sequence situation that the second trip operates and
after than it comes back to reset status caused by the fault disappears when
total number of operation is set to four.

(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC (6) 3rd Reclose Interval Time

<Figure 6-23> Reset Sequence Operation

If fault occurs again during auto reset time duration, reclosing operation proceeds
to Lockout after remaining operations except count the number of times the
previous operation.

CYCLE
It displays sequence operating. Cycle is activated to trip operation of overcurrent
protection and keeps whenever total trip count reaches to the preset total
number of operation. Cycle performs that the Reclose element closes the

137 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

recloser when the programmed reclose interval time expires. (only the Cycle
condition occurs when Auto Reclosing function is enabled).
At this menu, set reclosing function and its menu is as shown below.

A. FUNCTION
It sets reclosing function is used or not. If the function is disable, general
functions of circuit breaker are applied to CB type for relevant way of
switchgear. If the function is enable, general functions of recloser are applied to
CB type for relevant way of switchgear.

1) Function

Range DISABLE, ENABLE


Default DISABLE
Step -

 Set reclosing function used or not

B. OPERATIONS
This setting is used to change the total number of phase/ground overcurrent
protection trip operation.

1) Lockout

Range 1~4
Default 4
Step 4

 Select the total number of trip operation.

C. INTERVALS
It sets reclose interval for each reclose shot and reset time for auto reclose and
lockout.

1) Reclose 1

Range 0.5~60.0sec
Default 0.6
Step 0.1sec

 This setting is used to change the first reclose interval time between
the first trip operation and the close operation.

138 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

2) Reclose 2

Range 1~60sec
Default 2
Step 1sec

 This setting is used to change the second reclose interval time


between the second trip operation and the close operation.

3) Reclose 3

Range 1~60sec
Default 15
Step 1sec

 This setting is used to change the third reclose interval time between
the third trip operation and the close operation.

4) Reset T(AR)

Range 3~180sec
Default 30
Step 1sec

 This setting is used to change auto reclosing reset time.


 After a temporary fault is removed, ‘Reset T(AR)’ time starts, after
then the number of counter for reclose sequence becomes zero.
 If a fault is detected on ‘Reset T(AR)’ time, Reset timer will be reset.

5) Reset T(LO)

Range 1.00~600.00sec
Default 10.00
Step 0.01sec

 This setting is used to change lockout reset time.


 It is to eliminate reclosing sequence is a fault current is detected after
manual closing and to have waiting time for feeder stabilization.
 After setting time, reclosing function is activated.

139 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6) C/P Wait

Range 1.00~600.00sec
Default 60.00
Step 0.01sec

 C/P wait is Close Power Wait, waiting time to get power supply.
 Power supply is not enough to operate mechanism for reclosing
sequence, it waits for the setting time.
 In a case that power supply is not provided, reclose sequence stops
and goes to lockout status.

(9) ON/OFF LEVEL


It moves to this menu if [ENT] key is pressed after locating cursor in “9.
ON/OFF LEVEL" in group menu. At this menu, set Phase Open/Loss detection.
The "ON/OFF LEVEL" menu of way of switchgear breaker part and switch part
consists of setting items. Refer to "6.6.1.1.(5) ON/OFF LEVEL".

(10) PHASE DIFFERENCE


It moves to this menu if [ENT] key is pressed after locating cursor in “10.
PHASE DIFF" in group menu. At this menu, set Phase Difference(Phase
Synchronism Fail) detection.
The "PHASE DIFFERENCE" menu of way of switchgear breaker part and switch
part consists of setting items. Refer to "6.6.1.1.(6) PHASE DIFFERENCE".

(11) LIVE LINE


It moves to this menu if [ENT] key is pressed after locating cursor in “11. LIVE
LINE" in group menu. At this menu, set live line detection.
The "LIVE LINE" menu of way of switchgear breaker part and switch part
consists of setting items. Refer to "6.6.1.1.(7) LIVE LINE".

(12) SAVE SETTING


It has same function and structure with "MAIN MENU(COM)/ GLOBAL SETTING/
*. SAVE SETTING". Refer to "6.5.1.7. SAVE SETTING".

140 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.2. MONITORING
It moves to menu if [ENT] key is pressed after positioning cursor in "2.
MONITORING" in 'MAIN MENU'.

[ MON I T OR I N G]
> 1 . OP E R A T I ON C OU NT
2 . C ON T A CT WE A R
* . S AV E SE T T I NG

[ LCD Screen ] MONITORING Menu Screen

6.6.2.1. OPERATION COUNT


It moves to this menu if [ENT] key is pressed after locating cursor in "1.
OPERATION COUNT" in 'MONITORING' menu. The monitoring of specifications
related to way of switchgear breaker part operation count per way of switchgear
are set in this menu. The set value alteration process is identical to "MAIN
MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE” .

[ OP E R A T I ON C OU NT ]
> F u n c t i o n : OF F
L i mi t : 1 0 0 0 0
Co u n t s e t : 0

[ LCD Screen ] OPERATION COUNT Setting Menu Screen

1) Function

Range ON, OFF


Default OFF
Step -

 Select whether to use way of switchgear breaker operation count


monitoring.
 If function is activated and operation counter is over Limit, Logic bit
DIGCNT is set. Logic bit can be used for Output or Alarm through
Interface software.

141 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

<Figure 6-24> DIGCNT Diagram

2) Limit

Range 1 ~ 20000
Default 10000
Step 1

 Set number to alarm when way of switchgear breaker operation


number meets this set.

3) Count set

Range 0 ~ 10000
Default 0
Step 1

 It is to set same operation number of way of switchgear breaker. Set


value is available after operation count is reset.
 Count reset refers to “MAINTENANCE/ DATA RESET/ COUNT ALL”.

142 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.2.2. CONTACT WEAR


It moves to this menu if [ENT] key is pressed after locating cursor in "2.
CONTACT WEAR" in 'MONITORING' menu. The monitoring of specifications
related to way of switchgear breaker contact wear per way of switchgear are set
in this menu. The set value alteration process is identical to "MAIN MENU(COM)/
GLOBAL SETTING/ SYSTEM/ POWER LINE” .

[ CONT A CT WE A R ]
> F u n c t i o n : OF F
P i c k u p ( %) : 2 0 . 0
Ra t e d V o l t ( k V ) : 3 8
I n t e r r u p t : 1 2 . 5
N o . Ma x I : 1 0 0
A We a r Se t : 1 0 0 . 0 0
B We a r Se t : 1 0 0 . 0 0
C We a r Se t : 1 0 0 . 0 0

[ LCD Screen ] CONTACT WEAR Setting Menu Screen

1) Function

Range ON, OFF


Default OFF
Step -

 Select whether to use CB contact wear monitoring.

2) Pickup(%)

Range 0.0 ~ 50.0 %


Default 20.0
Step 0.1 %

 Set pickup value to alarm when CB contact wear reaches set value.

3) Rated Volt(kV)

Range 15kV, 27kV, 38kV


Default 38kV
Step -

 Set rated voltage of system.

143 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

4) Interrupt

Range 5.0 ~ 50.0 kA


Default 12.5
Step 0.1 kA

 Set capacity of rated Interrupter.

5) No. Max I

Range 1 ~ 999
Default 100
Step 1

 Set capacity of rated Interrupter.

6) A Wear Set

Range 0.00 ~ 100.00%


Default 100.00
Step 0.01%

 It is to set Circuit breaker phase A contact wear value in ETR306.


 Set value is available after Contact Wear Reset. Contact wear reset
refers to “MAINTENANCE/ DATA RESET/ CONTACT WEAR”.

7) Set item B Wear Set and C Wear Set are also used when coinciding
ETR306 contact wear with body. The Reset method of CONTACT WEAR
B and CONTACT WEAR C is identical to Contact A's.

6.6.2.3. SAVE SETTING


It has same function and structure with "MAIN MENU(COM)/ GLOBAL SETTING/
*. SAVE SETTING". Refer to "6.6.1.7. SAVE SETTING".

144 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.3. EVENT
It moves to this menu when [ENT] key is pressed after placing cursor on
"3.EVENT" in main menu and can check and erase events per way of switchgear
through menu.

[ E V E NT ]
> 1 . OP E R A T I ON
2 . F AUL T
3 . F AUL T CY CL E
4 . A V E R . L OA D / MI N
5 . P E A K . L OA D/ HOU R
6 . P E A K . L OA D/ DA Y
7 . CL E AR S AV E D DAT A

[ LCD Screen ] EVENT Menu Screen

This menu has submenus like following and can move to selected submenu using
[ENT] key.

6.6.3.1. OPERATION EVENT


Operation event records max. 256 events. When Circuit Breaker or Switch
operates(OPEN/CLOSE), operation status and control signal(LOCAL/REMOTE) is
recorded in operation event.

Move to “MAIN MENU/ EVENT/ OPERATION” to confirm operation events.

[001/256] CLOSE [002/256] OPEN [003/256] CLOSE


CONTROL : REMOTE CONTROL : REMOTE CONTROL : REMOTE

2007/10/01 00:00:03 2007/10/01 00:00:02 2007/10/01 00:00:01

Can check the record using the [▼][▲] keys. [001/256] is the latest event
recorded.

Trigger source
 Status
- CLOSE
- OPEN
- EARTH CLOSE(ECLOSE)
- EARTH OPEN(EOPEN)

145 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

 Control
- MANUAL: Manual operation in the CB body
- LOCAL: Manual operation in local
- REMOTE: Manual operation in remote

Saving method
Records when the Circuit Breaker or Switch operates(OPEN/CLOSE)

Trigger time
Every 5msec

Saving capacity
Saves up to 256 events max.

6.6.3.2. FAULT EVENT


Fault event records max. 256 events. It can check the fault occurring time of the
fault event, the fault current size of each phase and the fault event of each
phase.

Move to the “MAIN MENU/ EVENT/ FAULT” menu to check the fault event.

Can check the event using the [▼][▲] keys. If the [ENT] key is pressed in the
current indicating screen, the active and reactive power value of each phase is
indicated and if the [ENT] key is pressed again, it returns to the current
indicating screen. [001/256] is the most recently recorded event.

146 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

Screen Description
1 6

[001/256]FI RESULT:2 2 [002/256] 2 EV 1W 7


Target : A__N R T Target : A__N R
3
2008/10/01 00:02:03 2008/10/01 00:02:00

1 FI RESULT: Final Fault Determination Screen


EV: Fault Information Per Sequence Screen (Function to switch to Fault
Current Screen)
2 Final Sequence
3 T: Temporary Fault
P: Permanent Fault
4 F: Forward Direction Fault
R: Reverse Direction fault
5 Fault Occurrence Target
6 Fault Occurrence Sequence
7 Circuit Identification

Trigger Source
FI Target

Saving Method
Record at time of fault occurrence

Trigger Time
Every 1/4 cycle

Saving capacity
Save up to 256 events max.

147 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.3.3. FAULT CYCLE


The fault waveform records up to 8 waveforms. The fault waveform summary is
indicated in the LCD screen. The captured fault waveform can be checked in the
operating software.
Move to the “MAIN MENU/ EVENT/ FAULT CYCLE” menu to summarize the
fault cycle.

[001/ 8] PU [002/ 8] PU [003/ 8] PU


A: 00000 B: 00000 A: 00000 B: 00000 A: 00000 B: 00000
C: 00000 N: 00000 C: 00000 N: 00000 C: 00000 N: 00000
2008/10/01 03:00:00 2008/10/01 02:00:00 2008/10/01 01:00:00

Can check the record using the [▼][▲] keys. [001/8] is the latest event
recorded.

Trigger source
 Fault waveform capturing point
- PU: Pick up point
- TR: Trip point
- PU&TR: Pickup & Trip point
 Current in case of fault occurrence[A]: Phase A, phase B, phase C, phase N

Saving method
Record the fault waveform capturing point

Trigger time
Every 1/4 cycle

Saving capacity
Save a maximum of 8 events (20cycles×8EA(The sample rate is 32 samples)

148 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.3.4. AVER.LOAD/MIN
Record the average load current per circuit. It can save up to 10 days of event
since it saves a maximum of 1024.

Move to the “MAIN MENU/ EVENT/ AVER. LOAD/MIN” menu to check the
average load event.

[0001/1024] [0002/1024] [0003/1024]


A: 00000 B: 00000 A: 00000 B: 00000 A: 00000 B: 00000
C: 00000 N: 00000 C: 00000 N: 00000 C: 00000 N: 00000
2008/10/01 00:00:45 2008/10/01 00:00:30 2008/10/01 00:00:15

■ ■ ■

P3: 00000/ 00000 P3: 00000/ 00000 P3: 00000/ 00000


PA: 00000/ 00000 PA: 00000/ 00000 PA: 00000/ 00000
PB: 00000/ 00000 PB: 00000/ 00000 PB: 00000/ 00000
PC: 00000/ 00000 PC: 00000/ 00000 PC: 00000/ 00000

Can check the event using the [▼][▲] keys. If the [ENT] key is pressed in the
current indicating screen, the active and reactive power value of each phase is
indicated and if the [ENT] key is pressed again, it returns to the current
indicating screen. [0001/1024] is the most recently recorded event.

Trigger Source
 Measurement current[A]: Phase A, phase B, phase C, phase N
 Active power measurement[kW]: Phase 3, phase A, phase B, phase C
 Reactive power measurement[kVar]: Phase 3, phase A, phase B, phase C

Saving Method
Record when measuring the average load

Trigger Time
Every 15 minutes

Saving Capacity
Save up to 1024 events max.

149 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.3.5. PEAK.LOAD/HOUR
Record the hourly maximum load event per circuit. It can save up to 43 days of
event since it saves a maximum of 1024 hourly maximum load events.

Move to the “MAIN MENU/ EVENT/ PEAK. LOAD/ HOUR” menu to check the
maximum load event per hour.

[0001/1024] [0002/1024] [0003/1024]


A: 00000 B: 00000 A: 00000 B: 00000 A: 00000 B: 00000
C: 00000 N: 00000 C: 00000 N: 00000 C: 00000 N: 00000
2008/10/01 03:00:00 2008/10/01 02:00:00 2008/10/01 01:00:00

■ ■ ■

P3: 00000/ 00000 P3: 00000/ 00000 P3: 00000/ 00000


PA: 00000/ 00000 PA: 00000/ 00000 PA: 00000/ 00000
PB: 00000/ 00000 PB: 00000/ 00000 PB: 00000/ 00000
PC: 00000/ 00000 PC: 00000/ 00000 PC: 00000/ 00000

Can check the event using the [▼][▲] keys. If the [ENT] key is pressed in the
current indicating screen, the active and reactive power value of each phase is
indicated and if the [ENT] key is pressed again, it returns to the current
indicating screen. [0001/1024] is the most recently recorded event.

Trigger Source
 Measurement current[A]: Phase A, phase B, phase C, phase N
 Active power measurement[kW]: Phase 3, phase A, phase B, phase C
 Reactive power measurement[kVar]: Phase 3, phase A, phase B, phase C

Trigger Time
Every hour

Saving Capacity
Save up to 1024 events max.

150 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.3.6. PEAK.LOAD/DAY
Record the daily maximum load event per circuit. It can save up to 1024 events
since it saves a maximum of 1024 daily maximum load events.

Move to the “MAIN MENU/ EVENT/ PEAK. LOAD/ DAY” menu to check the
daily maximum load event.

[0001/1024] [0002/1024] [0003/1024]


A: 00000 B: 00000 A: 00000 B: 00000 A: 00000 B: 00000
C: 00000 N: 00000 C: 00000 N: 00000 C: 00000 N: 00000
2008/10/03 00:00:00 2008/10/02 00:00:00 2008/10/01 00:00:00

■ ■ ■

P3: 00000/ 00000 P3: 00000/ 00000 P3: 00000/ 00000


PA: 00000/ 00000 PA: 00000/ 00000 PA: 00000/ 00000
PB: 00000/ 00000 PB: 00000/ 00000 PB: 00000/ 00000
PC: 00000/ 00000 PC: 00000/ 00000 PC: 00000/ 00000

Can check the event using the [▼][▲] keys. If the [ENT] key is pressed in the
current indicating screen, the active and reactive power value of each phase is
indicated and if the [ENT] key is pressed again, it returns to the current
indicating screen. [0001/1024] is the most recently recorded event.

Trigger Source
 Measurement current[A]: Phase A, phase B, phase C, phase N
 Active power measurement[kW]: Phase 3, phase A, phase B, phase C
 Reactive power measurement[kVar]: Phase 3, phase A, phase B, phase C

Trigger Time
Every day

Saving Capacity
Save up to 1024 events max.

Trigger source
 Measurement current[A]: Phase A, phase B, phase C, phase N
 Active power measurement[kW]: Phase 3, phase A, phase B, phase C
 Reactive power measurement[kVar]: Phase 3, phase A, phase B, phase C

151 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.3.7. CLEAR SAVED DATA

MAIN MANU/ EVENT/ CLEAR SAVED DATA

[CLEAR SAVED DATA] Clearing saved event data


>1.OPERATION
2.FAULT Press the [■] button after choosing the item to be
3.FAULT WAVE
4.LOAD PROFILE cleared. The “EVENT CLEAR SUCCESS” message
5.ABOVE ALL
appears if it is successfully cleared.

[EVENT CLEAR]
5. ABOVE ALL
EVENT CLEAR SUCCESS
Clear all data in article 1 ~ 4.

6.6.4. MAINTENANCE
It moves to the maintenance menu of the [ENT] key is pressed after putting the
cursor in "4. MAINTENANCE" in the main menu. This menu indicates the
information of the maintenance of the CB per circuit. This menu has submenus
as shown below and can move to the chosen submenu by using the [ENT] key.

[ MA I N T E N A N CE ]
> 1 . C OU NT
2 . C ON T A CT WE A R
3 . DAT A RE SE T

[ LCD Screen ] MAINTENANCE Menu Screen

6.6.4.1. COUNT
This menu indicates each circuit's counter information and has a submenu like
shown below. Can move to the chosen submenu by using the [ENT] key.

[ C OU NT ]
> 1 . OP E R A T I ON
2 . F AUL T

[ LCD Screen ] COUNT Menu Screen

152 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

(1) OPERATION
Move to the“MAINTENANCE/ COUNT/ OPERATION” menu to check the CB
operation counter.

MAIN MANU/ MAINTENANCE/ COUNT/ OPERATION

[OPERATION] Indicate the number of CB operation.


COUNT : 0

(2) FAULT
Move to the “MAINTENANCE/ COUNT/ FAULT” menu to check the fault
counter.
Depending on control type for each way of switchgear, FAULT menu contents
displayed on LCD screen are different. LCD screen display for each type is
follows.

A. ‘SW' Type

MAIN MANU/ MAINTENANCE/ COUNT/ FAULT

[FAULT-TOT] 1/3 Indicate the number of CB fault occurred. This COUNT


TOT: 0
A : 0 B : 0 menu is composed of 3 pages and allows to move to
C : 0 N : 0
each page by using the [▼][▲] keys.

FAULT-TOT(1/3)
[FAULT-P] 2/3 Display total number of permanent fault and temporary
TOT: 0
A : 0 B : 0 fault occurrence.
C : 0 N : 0

FAULT-P(2/3)
Display the number of permanent fault occurrence.
[FAULT-T] 3/3
TOT: 0
A : 0 B : 0
C : 0 N : 0
FAULT-T(3/3)
Display the number of temporary fault occurrence.

153 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

B. ‘CB' Type

MAIN MANU/ MAINTENANCE/ COUNT/ FAULT

[FAULT] 1/3 Indicate the number of CB fault occurred. This COUNT


F.I TOTAL : 0
Trip : 0 menu is composed of 3 pages and allows to move to
INST’OC Trip : 0
each page by using the [▼][▲] keys.

FAULT(1/3)
[FAULT-P] 2/3  F.I TOTAL : Display total number of permanent fault
TOT: 0
A : 0 B : 0 and temporary fault occurrence.
C : 0 N : 0
 Trip : Display the number of fault trip.
 INST' OC Trip : Display the number of high current
fault trip.
[FAULT-T] 3/3
TOT: 0
A : 0 B : 0
C : 0 N : 0 FAULT-P(2/3)
Display the number of temporary fault occurrence.

FAULT-T(3/3)
Display the number of instantaneous fault occurrence.

6.6.4.2. CONTACT WEAR


Move to the "MAINTENANCE/ CONTACT WEAR” menu to check the Contact wear.

MAIN MANU/ MAINTENANCE/ CONTACT WEAR

[CONTACT WEAR-%] Show the contact life of the CB part in percentage.


A : 100.0
B : 100.0
C : 100.0

154 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.4.3. DATA RESET


Move to the "MAINTENANCE/ DATA RESET” menu. Reset the count and
maintenance related data in that menu.

MAIN MANU/ MAINTENANCE/ DATA RESET

[DATA RESET] Reset the saved data


>1.OPERATION COUNT
2.FAULT COUNT Press the [ENT] key after choosing the item to be
3.COUNT ALL
4.CONTACT WEAR reset. The “EVENT CLEAR SUCCESS” message appears
5.ENERGY
if it is successfully cleared.
6.ABOVE ALL

[EVENT CLEAR]
※. NOTE )
EVENT CLEAR SUCCESS 1) The ‘OPERATION COUNT’ is reset as the set value
of the ‘MAIN MENU/ MONITORING/ OPERATION
COUNT’ in case it is reset.
2) All other data are reset to 0.

6. ABOVE ALL
Rest all the data in items 1 ~ 4.

155 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.5. STATUS
It moves to the status menu if the [ENT] key is pressed after putting the cursor
in "5. STATUS" in the main menu.

MAIN MANU/ STATUS

[STATUS] Indicate the present CB & ETR306 status.


>SWITCH : TROUBLE
PANEL LOCK : UNLOCK The whole [▼][▲] keys can be checked by using the
CONTROL : LOCAL
EARTH : EARTH
[▼][▲] keys.

SWITCH
Indicate the status of the body.
OPEN, CLOSE, TROUBLE(Device Trouble status)

PANEL LOCK
Indicates the panel lock status.
LOCK, UNLOCK

CONTROL
Indicate the operation control selection status.
REMOTE, LOCAL, TROUBLE(Device Trouble status)

EARTH
Indicate the status of the earth circuit.
EARTH(earthing status), NORMAL(normal status)

156 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.6. METERING
It moves to the measurement menu if the [ENT] key is pressed after putting the
cursor on "6. METERING" in the main menu. In the measurement menu, the
present measurement value is indicated and has submenus like shown below. It is
possible to move to the chosen submenu by pressing the [ENT] key.

[ ME T E R I N G ]
> 1 . CURRE NT
2 . V OL T A GE
3 . P O WE R
4 . E NE RGY
5 . D E MA N D

[ LCD Screen ] Measurement Menu Screen

6.6.6.1. CURRENT
ETR306 measures and displays the following current items;

 CURRENT : Indicate the RMS value and phasor of the measured current per
phase(A, °).
 SEQUENCE 'I' : Indicate the normal/ negative sequence/ zero sequence
current and phasor(A, °).

Can be checked by moving to the“MAIN MENU/ METERING/ CURRENT” menu.

MAIN MANU/ METERING/ CURRENT

[CURRENT] Indicate the measuring value of the phase to phase


IA: 0A ∠ 0˚
current, normal/ negative sequence/ zero sequence
IB: 0A ∠ 0˚
IC: 0A ∠ 0˚ current. Checks the current measurement information by
IN: 0A ∠ 0˚
using the [▼][▲] key.

[SEQUENCE ‘I’]
I1: 0A ∠ 0˚
I2: 0A ∠ 0˚
3I0: 0A ∠ 0˚

157 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.6.2. VOLTAGE
ETR306 indicates the following voltage factors after measuring them;

 VOLTAGE P-N : Indicates the phase voltage and phasor(㎸, °).


 VOLTAGE P-P : Indicates the phase to phase voltage and phasor(㎸, °).
 SEQUENCE 'V' : Indicates the normal/ negative sequence/ zero sequence
voltage and each voltage phasor(㎸, °).

Can be checked by moving to the“MAIN MENU/ METERING/ VOLTAGE” menu.

MAIN MANU/ METERING/ VOLTAGE

[VOLTAGE P-N] [VOLTAGE P-P] [SEQUENCE ‘V’]


A : 0.00kV ∠ 0˚ AB: 0.00kV ∠ 0˚ I1: 0.00kV ∠ 0˚
B : 0.00kV ∠ 0˚ BC: 0.00kV ∠ 0˚ I2: 0.00kV ∠ 0˚
C : 0.00kV ∠ 0˚ CA: 0.00kV ∠ 0˚ 3I0: 0.00kV ∠ 0˚

Indicates the measuring value of the phase to phase voltage and line to line,
voltage, normal/ negative sequence/ zero sequence voltage. Checks the voltage
measurement information by using the [▼][▲] keys.

6.6.6.3. POWER
ETR306 indicates the following power factors after measuring them;

 POWER-KW/KVAR/KVA : Indicates the measurement of the active power/


volt-ampere/reactive power by phase.
 POWER FACTOR : Indicate the power factor by phase.
 3PH POWER-KVA/KW/KVAR/PF : Indicate the measurement of the 3 phase
volt-ampere/ active power/ reactive power/ power factor.

Can be checked by moving to the “MAIN MENU/ METERING/ POWER” menu.

MAIN MANU/ METERING/ POWER

[POWER- KW/KVAR/KVA] [POWER FACTOR] [3PH POWER]


A : 0000 0000 0000 A : 0000 KVA : 0000 PF: 0000
B : 0000 0000 0000 B : 0000 KW : 0000
C : 0000 0000 0000 C : 0000 KVAR: 0000

Indicates the measuring value of the power and power factor by phase. Check
the electricity measurement information by using the [▼][▲] keys.

158 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306)

6.6.6.4. ENERGY
ETR306 measures and displays the following energy items. The base unit
increment is 10k.

 POS’ W/H(10kWh) : Each phase and three phase active power amount of
forward direction are indicated. The indicated power is 10kWh per 1 count.
 POS’ V/H(10kVar) : Each phase and three phase reactive power amount of
forward direction are indicated. The indicated power is 10kVar per 1 count.
 NEG’ W/H(10kWh) : Each phase and three phase active power amount of
reverse direction are indicated. The indicated power is 10kWh per 1 count.
 NEG’ V/H(10kVar) : Each phase and three phase reactive power amount of
reverse direction are indicated. The indicated power is 10kVar per 1 count.

Can be checked by moving to “MAIN MENU/ METERING/ ENERGY” menu.

MAIN MANU/ METERING/ ENERGY

[POS’W/H(10kWh)] [POS’V/H(10kVarh)] [NEG’W/H(10kWh)]


Pa: 0 Pb: 0 Pa: 0 Pb: 0 Pa: 0 Pb: 0
Pc: 0 P3: 0 Pc: 0 P3: 0 Pc: 0 P3: 0
S:08/06/15 12:00:00 S:08/06/15 12:00:00 S:08/06/15 12:00:00

Indicates data related to energy capacity. Check the measurement information


by using the [▼][▲] keys.

6.6.6.5. DEMAND CURRENT


Can be checked by moving to the “METERING/ DEMAND” menu.

MAIN MANU/ METERING/ DEMAND CURRENT

[DEMAND CURRENT] Indicates the measuring value of the load current by


A: 0000 A B: 0000 A
C: 0000 A N: 0000 A phase.

159 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

APPENDIX A. TIME CURRENT CURVES

ETR306 is equipped ANSI, IEEE(User-defined curves' default), IEC, ESB, Definite


Time curves and User-defined curves and all 32 non standard curves are
available. The operation times and reset times refer to ANSI/IEEE C37.112 and
IEC 255-3.

The operation times and reset times are as follows;

ANSI/IEEE
Trip Time(Sec) = TD × ( α / ( Mβ - 1) + γ ) + TA

IEC
Trip Time(Sec) = TD × ( α / (Mβ- 1) ) + TA

ES(KEPCO)
Trip Time(Sec) = TD × ( α / (Mβ - 1) + γ ) + TA

USER-DEFINED
Trip Time(Sec) = TD × ( α / (Mβ - 1) + γ ) + TA
Reset Time(Sec) = TD × ( Rt / (1 – M2) )

[Table A-1] Curve Factor

TD Time dial
TA Time Adder
α, β, γ Characteristic constant
M Multiples of pickup current
Rt Reset characteristic constant

160 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

1. STANDARD CURVES

STANDARD CURVE COEFFICIENTS

[Table A-2] ANSI/IEEE Curves


Curves α β γ Rt
Normally Inverse 5.95 2.0 0.18 5.95
Very Inverse 3.88 2.0 0.0963 3.88
Extremely Inverse 5.67 2.0 0.0352 5.67

[Table A-3] IEC Curves


Curves α β γ Rt
Normally Inverse 0.1400 0.0200 0.0 9.700
Very Inverse 13.500 1.000 0.0 13.500
Extremely Inverse 80.000 2.000 0.0 80.000

[Table A-4] ES(KEPCO) Curves


Curves α β γ Rt
Normally Inverse 0.011 0.02 0.042 9.000
Very Inverse 3.985 1.95 0.1084 3.985

[Table A-5] Definite Time Curves

Curves α β γ Rt
Definite Time 1sec 0.0 - 1.0 1.0
Definite Time 10sec 0.0 - 10.0 10.0

[Table A-6] User-Defined Curves(IEEE Curve)

Curves α β γ Rt
User 1(IEEE Moderately Inverse) 0.0515 0.02 0.1140 4.85
User 2(IEEE Very Inverse) 19.61 2.00 0.4910 21.6
User 3(IEEE Extremely Inverse) 28.2 2.00 0.1217 29.1
User 4(IEEE Long Time Extremely Inverse) 5.67 2.0 0.0352 5.67

*. NOTE ) Default setting values of user-defined curves are identical to IEEE


standard curves; Moderately Inverse, Very Inverse, Extremely
Inverse, Long Time Extremely Inverse, respectively.

161 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

2. NON STANDARD CURVES


2.1. McGraw-Edison Curves
[Table A-7] McGraw-Edison Curves

Phase Ground
Old New Old New
A 101 1 102
B 117 2 135
C 133 3 140
D 116 4 106
E 132 5 114
K 162 6 136
L 107 7 152
M 118 8 113
N 104 8* 111
P 115 9 131
R 105 11 141
T 161 13 142
V 137 14 119
W 138 15 112
Y 120 16 139
Z 134 18 151

2.2. KEPRI Curves


[Table A-8] KEPRI Curves

CURVES
N1, N2, N3, N4

162 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3. CURVES

CURVE CHARACTERISTICS
*. Curve time is Clearing Time.
*. Operation accuracy is +/-10% or +/-10msec.

CURVE LIST
It describes in “[Table A-9] Curves List”.

[Table A-9] Curves List

NO CURVE NO CURVE NO CURVE


1 A(101) 18 Y(120) 35 18(151)
2 B(117) 19 Z(134) 36 N1
3 C(133) 20 1(102) 37 N2
4 D(116) 21 2(135) 38 N3
5 E(132) 22 3(140) 39 N4
6 IEC-EI 23 4(106) 40 ANSI-NI
7 K(162) 24 5(114) 41 ANSI-VI
8 L(107) 25 6(136) 42 ANSI-EI
9 M(118) 26 7(152) 43 ES-NI
10 N(104) 27 8(113) 44 ES-VI
11 IEC-NI 28 8*(111) 45 U1
12 P(115) 29 9(131) 46 U2
13 R(105) 30 11(141) 47 U3
14 T(161) 31 13(142) 48 U4
15 V(137) 32 14(119) 49 DEF-1S
16 IEC-VI 33 15(112) 50 DEF-10S
17 W(138) 34 16(139)

163 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.1. ANSI/IEEE Normally Inverse Curve

100 ANSI NORMALLY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3
15.00
13.00
2 11.00 2
9.00

Time(Second)
Time(Second)

7.00

1 1
0.9 5.00 0.9
0.8 0.8
0.7 4.00 0.7
0.6 0.6
3.00
0.5 0.5
0.4 0.4
2.00
0.3 0.3

0.2 0.2
1.00

0.1 0.1
0.09 0.5 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

164 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.2. ANSI/IEEE Very Inverse Curve

100 ANSI VERY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

15.00
13.00
11.00
1 1
0.9 9.00 0.9
0.8 0.8
0.7 7.00 0.7
0.6 0.6
0.5 5.00 0.5
0.4 4.00 0.4

0.3 3.00 0.3

0.2 2.00 0.2

0.1 1.00 0.1


0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.5 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

165 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.3. ANSI/IEEE Extremely Inverse Curve

100 ANSI EXTREMELY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 15.00 0.6
0.5 13.00 0.5
11.00
0.4 0.4
9.00
0.3 0.3
7.00

0.2 5.00 0.2


4.00

3.00
0.1 0.1
0.09 0.09
0.08 2.00 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 1.00 0.04

0.03 0.03

0.02 0.5 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

166 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.4. IEC Normally Inverse Curve

100 IEC NORMALLY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 1 2

0.8

Time(Second)
Time(Second)

0.7
0.6
1 0.5 1
0.9 0.9
0.8 0.4 0.8
0.7 0.7
0.6 0.3 0.6
0.5 0.5
0.4 0.2 0.4

0.3 0.3

0.2 0.1 0.2

0.1 0.05 0.1


0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

167 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.5. IEC Very Inverse Curve

100 IEC VERY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
1
0.4 0.4
0.8
0.3 0.7 0.3
0.6
0.5
0.2 0.2
0.4

0.3

0.1 0.1
0.09 0.2 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.1
0.04 0.04

0.03 0.03

0.05
0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

168 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.6. IEC Extremely Inverse Curve

100 IEC EXTREMELY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
1,000 1,000
900 900
800 800
700 700
600 600
500 500
400 400
300 300

200 200

100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30

20 20

10 10
9 9
8 8
7 7
6 6

Time(Second)
Time(Second)

5 5
4 4
3 3

2 2

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3

0.2 0.2

0.1 0.1
0.09 1 0.09
0.08 0.08
0.07 0.8 0.07
0.06 0.7 0.06
0.05 0.6 0.05
0.04 0.5 0.04
0.4
0.03 0.03
0.3
0.02 0.02
0.2
0.1
0.05
0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

169 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.7. ESB(ES) Normally Inverse Curve

100 ESB(ES) NORMALLY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 15.00 3
13.00
2 11.00 2
9.00

Time(Second)
Time(Second)

7.00

1 5.00 1
0.9 0.9
0.8 0.8
4.00
0.7 0.7
0.6 3.00 0.6
0.5 0.5
0.4 0.4
2.00
0.3 0.3

0.2 1.00 0.2

0.1 0.5 0.1


0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

170 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.8. ESB(ES) Very Inverse Curves

100 ESB VERY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2
15.00

Time(Second)
Time(Second)

13.00
11.00
1 9.00 1
0.9 0.9
0.8 7.00 0.8
0.7 0.7
0.6 0.6
5.00
0.5 0.5
4.00
0.4 0.4
3.00
0.3 0.3

2.00
0.2 0.2

1.00
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.5
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

171 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.9. IEEE Moderately Inverse Curves

100 IEEE MODERATELY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

15.00

10 13.00 10
9 11.00 9
8 8
7 9.00 7
6 7.00 6
5 5
4 5.00 4
4.00
3 3
3.00
2 2
2.00

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 1.00 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.5 0.4

0.3 0.3

0.2 0.2

0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

172 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.10. IEEE Very Inverse Curves

100 IEEE VERY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 15.00 8
7 7
13.00
6 6
11.00
5 5
9.00
4 4
7.00
3 3
5.00

2 4.00 2

Time(Second)
Time(Second)

3.00

1 2.00 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 1.00 0.5
0.4 0.4

0.3 0.3
0.5
0.2 0.2

0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

173 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.11. IEEE Extremely Inverse Curves

100 IEEE EXTREMELY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

15.00
2 13.00 2
11.00

Time(Second)
Time(Second)

9.00

1 7.00 1
0.9 0.9
0.8 0.8
5.00
0.7 0.7
0.6 4.00 0.6
0.5 0.5
3.00
0.4 0.4

0.3 2.00 0.3

0.2 0.2

1.00

0.1 0.1
0.09 0.09
0.08 0.5 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

174 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.12. IEEE Long Time Extremely Inverse Curves

100 IEEE LONG TIME VERY INVERSE

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
15.00
0.6 0.6
13.00
0.5 0.5
11.00
0.4 0.4
9.00
0.3 7.00 0.3

0.2 5.00 0.2


4.00

3.00
0.1 0.1
0.09 0.09
0.08 2.00 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 1.00 0.04

0.03 0.03

0.02 0.5 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

175 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.13. Definite Time Curve (DEF-1S(D1), DEF-10S(D2))

D1, D2
100

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10
9
D2 10
9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1
0.9
D1 1
0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4

0.3 0.3

0.2 0.2

0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

176 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.14. KEPRI Curve (N1, N2, N3, N4)

100 KEPRI CURVE( N1, N2, N3, N4)

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4

0.3 0.3

0.2 0.2
N4
N2 N3

0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 N1 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

177 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.15. Non-standard Curve (A, B, C, D, E)

100 A, B, C, D, E

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4

0.3 0.3

0.2 0.2

C
0.1 0.1
0.09 0.09
0.08 0.08
0.07 B 0.07
0.06 D 0.06
0.05 E 0.05
0.04
A 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

178 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.16. Non-standard Curve (K, L, M, N)

100 K, L, M, N

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4

0.3 0.3

0.2 0.2

N K
0.1 0.1
0.09 L M 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

179 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.17. Non-standard Curve (P, R, T, V)

100 P, R, T, V

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6
V 0.6
0.5 0.5
0.4 0.4

0.3 0.3

0.2 0.2

T
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05
P R 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

180 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.18. Non-standard Curve (W, Y, Z)

100
W, Y, Z

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4
Z 0.4

0.3 0.3
W
0.2 0.2

0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

181 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.19. Non-standard Curve (1, 2, 3, 4, 5)

100 1, 2, 3, 4, 5

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

10 10
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 3 0.9
0.8 0.8
0.7 0.7
0.6 2 0.6
0.5 0.5
0.4 0.4

0.3 0.3

0.2 0.2

0.1 0.1
0.09 0.09
0.08
0.07
5 0.08
0.07
0.06
1 4 0.06
0.05 0.05
0.04 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

182 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.20. Non-standard Curve (6, 7, 8, 8*, 9)

100 6, 7, 8, 8*, 9

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30
7 30

20 20

10 10
9 9
8 8
7 7
6 6
5 9 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4

0.3 0.3

0.2 0.2
8

0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 8* 0.06
0.05 0.05
0.04
6 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

183 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

3.21. Non-standard Curve (11, 13, 14, 15, 16, 17, 18)

100 11, 13, 14, 15, 16, 17, 18

200

300

400

500

600
700
800
900

10k
1k

2k

3k

4k

5k

6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40

30 30

20 20

11
9 9
8 8
7 7
6 6
5 5
4 4

3 3

2 2

Time(Second)
Time(Second)

1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 18 0.5
14
0.4 0.4

0.3 0.3

0.2 0.2

13
0.09 16 0.09
0.08
0.07
17 0.08
0.07
0.06 0.06
0.05 0.05
0.04 15 0.04

0.03 0.03

0.02 0.02

0.01 0.01
100

200

300

400

500

600
700
800
900
1k

2k

3k

4k

5k

6k
7k
8k
9k
10k

PERCENT OF PICKUP CURRENT

184 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

APPENDIX B. MENU DESCRIPTION & DEFAULT SETTING


[Table B-1] Menu Description & Default Setting(1/17)

FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
MAIN MENU(COM)
1. GLOBAL SETTING
1. SYSTEM
1. POWER LINE
Frequency Power line nominal frequency (50Hz, 60Hz) - 60Hz

Ref. Voltage Reference voltage set (A, B, C) - A

Phase Rotation Power line phase rotation (ABC, ACB) - ABC

Nominal Volt Power line Nominal Voltage (1000~30000V) 10 13200

2. CURRENT SENSING
CT1-Ratio Set phase current transfer ratio (1~2000) 1 1000

GCT1-Ratio Set ground current transfer ratio (1~5000) 1 1000

CT2-Ratio Set phase current transfer ratio (1~2000) 1 1000

GCT2-Ratio Set ground current transfer ratio (1~5000) 1 1000

CT3-Ratio Set phase current transfer ratio (1~2000) 1 1000

GCT3-Ratio Set ground current transfer ratio (1~5000) 1 1000

CT4-Ratio Set phase current transfer ratio (1~2000) 1 1000

GCT4-Ratio Set ground current transfer ratio (1~5000) 1 1000

CT5-Ratio Set phase current transfer ratio (1~2000) 1 1000

GCT5-Ratio Set ground current transfer ratio (1~5000) 1 1000

CT6-Ratio Set phase current transfer ratio (1~2000) 1 1000

GCT6-Ratio Set ground current transfer ratio (1~5000) 1 1000

CT1-Pol Set phase current transfer pole direction (FOR/REV) - Forward


GCT1-Pol Set ground current transfer pole direction (FOR/REV) - Forward
CT2-Pol Set phase current transfer pole direction (FOR/REV) - Forward
GCT2-Pol Set ground current transfer pole direction (FOR/REV) - Forward
CT3-Pol Set phase current transfer pole direction (FOR/REV) - Forward
GCT3-Pol Set ground current transfer pole direction (FOR/REV) - Forward
CT4-Pol Set phase current transfer pole direction (FOR/REV) - Forward
GCT4-Pol Set ground current transfer pole direction (FOR/REV) - Forward
CT5-Pol Set phase current transfer pole direction (FOR/REV) - Forward

GCT5-Pol Set ground current transfer pole direction (FOR/REV) - Forward

CT6-Pol Set phase current transfer pole direction (FOR/REV) - Forward


GCT6-Pol Set ground current transfer pole direction (FOR/REV) - Forward

3. VOLTAGE SENSING
VT CON-Type VT Connector Type (NONE, WYE, DELTA) - WYE

VT 2nd(V) VT 2nd Nominal Voltage (2.00~350.00V) 0.01 4.00

185 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(2/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
VT Ratio VT Nominal Ratio (10.0~6500.0) 0.1 3300.0

4. CONTROL TYPE
1 WAY Control type of 1 way (CBTYPE, SWTYPE, NONE) - CBTYPE

2 WAY Control type of 2 way (CBTYPE, SWTYPE, NONE) - CBTYPE

3 WAY Control type of 3 way (CBTYPE, SWTYPE, NONE) - CBTYPE

4 WAY Control type of 4 way (CBTYPE, SWTYPE, NONE) - CBTYPE

5 WAY Control type of 5 way (CBTYPE, SWTYPE, NONE) - CBTYPE

6 WAY Control type of 6 way (CBTYPE, SWTYPE, NONE) - CBTYPE

5. CB OPENING TIME
Time CB Opening Time (0.000~1.000sec) 0.001 0.020

6. GAS SENSOR TYPE


Type Gas sensor type (NONE, TYPE1, TYPE2) - NONE

7. FI TYPE SELECT
Type Select Select the type of FI(fault indicator) detection. (IV/I) - IV

2. COMMUNICATION
1. PROTOCOL SETUP
1) DNP3
Function Use DNP3.0 protocol or not (DISABLE, ENABLE) - ENABLE

COM Port Set DNP3.0 communication port (PORT1,PORT2,PORT3) - PORT1

D/L Confirm Enable data link layer confirm (NO, YES, SOME) - SOME

D/L FrameDly Set data link frame delay time (10~5000msec) 10 100

D/L Retries Data link layer retries (0~2) 1 0

D/L Timeout Data link layer timeout (1~225sec) 1 10

A/L Timeout Application link layer timeout (1~225sec) 1 15

Master Address Master station address (0~65534) 1 60000

DNP Address ETR306 slave address (0~65534) 1 1

SBO Time Select before operate timeout (1~225sec) 1 15

Init Unsol Set Init Unsol. response or not (DISABLE, ENABLE) - ENABLE

Unsol Time The unsolicited time (0~60sec) 1 5

Unsol Type The unsolicited type(NOTRIG, PERIOD) - NOTRIG

Unsol Retries Unsol' message retries (0 ~2) 1 0

Class 1 Enable Unsolicited Class1 (DISABLE, ENABLE) - ENABLE

Class 2 Enable Unsolicited Class2 (DISABLE, ENABLE) - ENABLE

Class 3 Enable Unsolicited Class3 (DISABLE, ENABLE) - ENABLE

TCP/UDP Select TCP or UDP select. - TCP

TCP Port TCP port number of ETR306 (0~65535) 1 20000

UDP Port UDP port number of ETR306 (0~65535) 1 20001

186 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(3/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
Master IP Oct1 Master IP address 1 (0~225) 1 192

Master IP Oct2 Master IP address 2 (0~225) 1 168

Master IP Oct3 Master IP address 3 (0~225) 1 7

Master IP Oct4 Master IP address 4 (0~225) 1 202

K-Alv Check Tm Keep alive interval (0(OFF), 1~600 sec) 1 4

Fragment Size Fragment size(64~2048) 1 2048


Set interval time for synchronization time
Time Req(m) 1 OFF
(0(OFF), 1~30000min)
2) IEC60870-5-101 Protocol Setup
Use IEC60870-5-101 protocol or not
Function - DISABLE
(DISABLE, ENABLE)
COM Port Select COM Port (PORT1, PORT2, PORT3) - PORT1

Address IEC60870-5-101 Address (1~65535) 1 1

ASDU Addr Application Service Data Unit Address (0~65535) 1 0

Cyclic Period Cyclic Period (1~60000sec) 1 60

Event Period Event Transmission Period(0~255sec) 1 15

Retries Set the Data retries number.(0~255) 1 0

Conf. Timeout The confirm timeout(1~255sec) 1 10

Max Poll Time The max poll delay(1~255sec) 1 10

ASDU Addr Size Size of common address of ASDU(1~2) 1 2

Link Confirm Link layer confirm mode(NEVER, ALWAYS) - ALWAYS

Link Addr Size Link Address Size (1~2) 1 1

Rx Frame Size Maximum size of receive frame(0~261). 1 261


Maximum amount of time to wait for a complete
Rx Frame TO frame after receiving the frame sync 1 15
(0(OFF), 0~255sec)
Tx Frame Size Maximum size of transmit frame (0~261) 1 261

COT Size Size of Cause of transmission.(1~2) 1 1

IOA Size Size of information object address(1~3) 1 2


Allowed to send one character response instead of a
One Ch Response fixed length NACK when on response data available - NO
(NO, YES)
The time out for repetition of frames (0(OFF),
Frame Repet’ TO 1 30
0~255sec)
The period after a previously received select will
Select Timeout 1 5
timeout(0(OFF), 0~255sec)
Whether to send Activation Termination upon
CMD Termination completion of commands other than set point - YES
commands(NO, YES)
Whether to send Activation Termination upon
CSE Termination - YES
completion of set point commands(NO, YES)
Whether to generate spontaneous clock
Clock Sync’ Evt - YES
synchronization events(NO, YES)
MSP Time-Tag Time tag format for single-point(CP56, CP24) - CP56

MIT Time-Tag Time tag format for integrated totals(CP56, CP24) - CP56

187 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(4/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
Time tag format for measured value and
MME Time-Tag normalized value, in case of general event(CP56, - CP56
CP24)
Time tag format for measured value and
Flt Time-Tag normalized value in fault current event (CP56, - CP56
CP24)
3) IEC60870-5-104 Protocol Setup
Use IEC60870-5-104 protocol or not
Function - DISABLE
(DISABLE, ENABLE)
COM Port Select COM Port (PORT1, PORT2, PORT3) - PORT3

ASDU Addr Application Service Data Unit Address (0~65535) 1 0

Cyclic Period Cyclic Period(1~60000sec) 1 60

Time Out(t0) Timeout of Connection(1~255 sec) 1 120

Time Out(t1) Timeout of send(1~255 sec) 1 15


Timeout for acking in case of no data t2<t1(1~255
Time Out(t2) 1 10
sec)
Timeout for sending test frames in case of a long
Time Out(t3) 1 20
idle state (1~255 sec)
Event Period Event Transmission Period(0~255 sec) 1 15

TCP Port No TCP port number(0~65535) 1 2404

Rx Frame Size Maximum size of receive frame(0~255) 1 255

Tx Frame Size Maximum size of transmit frame (0~255) 1 255


The period after a previously received select will
Select Timeout 1 5
timeout(0(OFF), 0~255sec)
Whether to send Activation Termination upon
CMD Termination completion of commands other than set point - YES
commands (NO, YES)
Whether to send Activation Termination upon
CSE Termination - YES
completion of set point commands (NO, YES)
Whether to generate spontaneous clock
Clock Sync’ Evt - YES
synchronization events (NO, YES)
MSP Time-Tag Time tag format for single-point (CP56, CP24) - CP56

MIT Time-Tag Time tag format for integrated totals (CP56, CP24) - CP56
Time tag format for measured value and
MME Time-Tag normalized value, in case of general event (CP56, - CP56
CP24)
Time tag format for measured value and
Flt Time-Tag normalized value in fault current event (CP56, - CP56
CP24)
4) MODBUS Protocol Setup
Function Use MODBUS protocol or not (DISABLE, ENABLE) - DISABLE

COM Port Select COM Port(PORT1, PORT2, PORT3) - PORT3

TCP/UDP Select TCP or UDP select(TCP, UDP) - TCP

TCP Port TCP port number(1~65535) 1 502

UDP Port UDP port number(0~65535) 1 20001

Slave Address Slave Address number(1~254) 1 1

Tx Delay Set Tx Delay Time(0.00(OFF), 0.01~300.00sec) 0.01 0.05

188 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(5/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
2. PORT SETUP
1) PORT1(232)
Select the baud rate for PORT1
Baud Rate - 9600
(1200, 2400, 4800, 9600, 19200bps)
Parity Bit Select whether to use parity bit (NONE, ODD, EVEN) - NONE

Data Bit Select the data bit (7~8) - 8

Stop Bit Select the stop bit (1~2) - 1


Select the type of communication wire
Modem Sel - 4W
(2W, 4W, DIAL, NONE)
Select whether to use CTS signal or not
CTS Usage - ENABLE
(DISABLE, ENABLE)
Select whether to use DCD signal or not
DCD Usage - DISABLE
(DISABLE, ENABLE)
Select whether to use RTS signal or not
RTS Usage - AUTO
(ON, OFF, AUTO)
CTS CheckOut Set CTS check out time (1~255sec) 1 2

DCD CheckOut Set DCD check out time (10~30000msec) 10 5000

TX PreDelay Enter the pre-time delay (5~500ms) 5 10

TX PostDelay Enter the post-time delay (10~500ms) 5 50

2) PORT2(485)
Select the baud rate for PORT2
Baud Rate - 9600
(1200, 2400, 4800, 9600, 19200bps)
Parity Bit Select whether to use parity bit (NONE, ODD, EVEN) - NONE

Data Bit Select the data bit (7~8) - 8

Stop Bit Select the stop bit (1~2) - 1


Select a physical port for communication
Line Type - RS422
(RS422, RS485)
CA Delay Set CA delay time (0.00~240.00sec) 0.01 1.00

3) PORT3(ETHERNET)
IP Addr Oct1 IP address 1 for ETR306 (0~225) 1 192

IP Addr Oct2 IP address 2 for ETR306 (0~225) 1 168

IP Addr Oct3 IP address 3 for ETR306 (0~225) 1 7

IP Addr Oct4 IP address 4 for ETR306 (0~225) 1 212

Gateway Oct1 Gateway address 1 (0~225) 1 192

Gateway Oct2 Gateway address 2 (0~225) 1 168

Gateway Oct3 Gateway address 3 (0~225) 1 7

Gateway Oct4 Gateway address 4 (0~225) 1 1

SubnetMask Oct1 Subnet mask address 1 (0~225) 1 255

SubnetMask Oct2 Subnet mask address 2 (0~225) 1 255

SubnetMask Oct3 Subnet mask address 3 (0~225) 1 255

SubnetMask Oct4 Subnet mask address 4 (0~225) 1 0

K-Alv Fun Keep Alive Function use or not (DISABLE, ENABLE) - ENABLE

189 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(6/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
K-Alv Idele TO Keep Alive Idle Time (0(OFF),1~600sec) 1 4

K-Alv Retry Keep Alive retry (0~255) 1 3

4) PORTF(232)
Select whether to use wireless or not (DISABLE,
Wireless - DISABLE
ENABLE)
Slave Address Slave Address (0~65534) 1 1

Master Address Master Address (0~65534) 1 0


Select the baud rate for PORTF
Baud Rate - 38400
(1200,2400,4800,9600,19200,38400,57600,115200bps)
Select the type of communication wire
Modem Sel - 4W
(2W, 4W, DIAL, NONE)
Select whether to use CTS signal or not
CTS Usage - ENABLE
(DISABLE, ENABLE)
Select whether to use DCD signal or not
DCD Usage - DISABLE
(DISABLE, ENABLE)
Select whether to use RTS signal or not
RTS Usage - AUTO
(ON, OFF, AUTO)
CTS CheckOut Set CTS check out time(1~255sec) 1 2

DCD CheckOut Set DCD check out time(10~30000msec) 10 5000

RTS OffDelay Set RTS off delay time(10~500msec) 5 50

3. DIALUP MODEM
1) CALLING STRING
CS AT command for dial (ATD, ATDT, ATDP) - ATD

2) CALLING NUMBER
CN Modem (Master station)phone number. - -

3) INITIAL STRING
AT&C1 Q1
IS Initial commands for your modem. - E0 M0 &D2
+CRM=129
4) CONNECTION
Cmd Res’ TO Set the cmd Res’ Timeout(0~255sec) 1 2

Connect TO Set the Connection Timeput (0~255sec) 1 30

Idle Time Set the Idle Time (0~255sec) 1 60

4. ANALOG EVENT
AI Evt Method Select the Analog Event Type (OFF, TH, DB, BOTH) - OFF

AEvt Skip at Ft Select DB/TH Event Skip at fault pickup (No, YES) - NO

Daily Max I Daily Max. load current event (DISABLE, ENABLE) - ENABLE

Flt ‘I’ Evt Select the Fault ‘I’ Event(NO, YES, 1SHOT) - 1SHOT
Set the Average Load Calculation Time
Aver.Load Calc T - 15
(1/2/3/4/5/6/10/12/15/20/30min)
BI Queue Size Select the BI Event Queue Size (32, 64, 128, 256) - 256

BI Evt Mode Select the BI Event Mode (ALL, LAST) - ALL

190 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(7/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
AI Queue Size Select the AI Event Queue Size (32, 64, 128, 256) - 256

AI Evt Mode Select the AI Event Mode (ALL, LAST) - ALL

CI Queue Size Select the CI Event Queue Size (32, 64, 128, 256) - 256

CI Evt Mode Select the CI Event Mode (ALL, LAST) - ALL

Time Syn’ Ref Set the time synch type (LOCAL, GMT) - LOCAL

Time Tag Type Set the time tag type (LOCAL, GMT) - LOCAL

5. FTP FILE TRANSFER


Select the protocol for file transfer
FTP Mode-R - DNP
(DNP, FTPC, FTPS, USER)
Select the protocol for file transfer(DNP, FTPC,
FTP Mode-W - DNP
FTPS, USER)
Set the Device type for FTP file classification
FTP Dev - PAD
(space~‘z’)
Set the Device Number of FTP file classification
FTP Dev.No - CB001
(space~‘z’)
Set the ID of the device used for the connection
FTP ID - ENTEC
with FTP(space~‘z’)
FTP PW Set the FTP connection password(space~‘z’) - 1234

FTP Passive Set the FTP connection method(DISABLE, ENABLE) - DISABLE

3. EVENT RECORDER
Select whether to use Wave capture or not
Wave Capture - ON
(ON, OFF)
Select a number of sampling for wave capture
Wave S/R - 32
(16,32sample)
Wave Pre-Cycle Select a number of Pre-Cycle (1~10cycle) 1 5

Wave Post-Cycle Select a number of Post-Cycle (1~10cycle) 1 5

Wave Head-Cycle Select a number of Head-Cycle (1~10cycle) 1 5

4. MONITORING
1. BATTERY TEST
Set time period for automatic battery test
Period 1 24
(OFF, 1~720Hour)
2. TD MONITOR
TD1 Rate Set Transducer 1(TD1) monitoring range (1~200) 1 40

TD1 Ratio Set Transducer 1(TD1) ratio (1~3000) 1 1

TD1 Offset Set Transducer 1(TD1) offset (-10000~+10000) 1 0

TD1-1 Type Set monitoring element of TD1 (UNDER, OVER) - UNDER

TD1-1 PU Set TD1 pickup value (OFF,0.1~6000.0) 0.1 21.0

TD1-1 Delay Set delay time of TD1 (0.01~600.00sec) 0.01 2.00

TD1-2 Type Set 2nd monitoring element of TD1 (UNDER, OVER) - UNDER

TD1-2 PU Set 2nd pickup value of TD1 (OFF,0.1~6000.0) 0.1 19.0

TD1-2 Delay Set 2nd delay time of TD1 (0.01~600.00sec) 0.01 2.00

TD2 Rate Set Transducer 2(TD2) monitoring range (1~200) 1 40

191 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(8/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
TD2 Ratio Set Transducer 2(TD2) ratio (1~3000) 1 1

TD2 Offset Set Transducer 2(TD2) offset (-10000~+10000) 1 0

TD2-1 Type Set monitoring element of TD2 (UNDER, OVER) - UNDER

TD2-1 PU Set TD2 pickup value (OFF,0.1~6000.0) 0.1 23.0

TD2-1 Delay Set delay time of TD2 (0.01~600.00sec) 0.01 2.00

TD2-2 Type Set 2nd monitoring element of TD2 (UNDER, OVER) - UNDER

TD2-2 PU Set 2nd pickup value of TD2 (OFF,0.1~6000.0) 0.1 OFF

TD2-2 Delay Set 2nd delay time of TD2 (0.01~600.00sec) 0.01 2.00

TD3 Rate Set Transducer 3(TD3) monitoring range (1~200) 1 20

TD3 Ratio Set Transducer 3(TD3) ratio (1~3000) 1 1

TD3 Offset Set Transducer 3(TD3) offset (-10000~+10000) 1 0

TD3-1 Type Set monitoring element of TD3 (UNDER, OVER) - UNDER

TD3-1 PU Set TD3 pickup value (OFF,0.1~6000.0) 0.1 OFF

TD3-1 Delay Set delay time of TD3 (0.01~600.00sec) 0.01 2.00

TD3-2 Type Set 2nd monitoring element of TD3 (UNDER, OVER) - UNDER

TD2-2 PU Set 2nd pickup value of TD2 (OFF,0.1~6000.0) 0.1 OFF

TD2-2 Delay Set 2nd delay time of TD2 (0.01~600.00sec) 0.01 2.00

TD3 Rate Set Transducer 3(TD3) monitoring range (1~200) 1 20

TD3 Ratio Set Transducer 3(TD3) ratio (1~3000) 1 1

TD3 Offset Set Transducer 3(TD3) offset (-10000~+10000) 1 0

TD3-1 Type Set monitoring element of TD3 (UNDER, OVER) - UNDER

TD3-1 PU Set TD3 pickup value (OFF,0.1~6000.0) 0.1 OFF

TD3-1 Delay Set delay time of TD3 (0.01~600.00sec) 0.01 2.00

TD3-2 Type Set 2nd monitoring element of TD3 (UNDER, OVER) - UNDER

TD3-2 PU Set 2nd pickup value of TD3 (OFF,0.1~6000.0) 0.1 OFF

TD3-2 Delay Set 2nd delay time of TD3 (0.01~600.00sec) 0.01 2.00

TD4 Rate Set Transducer 4(TD4) monitoring range (1~200) 1 20

TD4 Ratio Set Transducer 4(TD4) ratio (1~3000) 1 1

TD4 Offset Set Transducer 4(TD4) offset (-10000~+10000) 1 0

TD4-1 Type Set monitoring element of TD4 (UNDER, OVER) - UNDER

TD4-1 PU Set TD4 pickup value (OFF,0.1~6000.0) 0.1 OFF

TD4-1 Delay Set delay time of TD4 (0.01~600.00sec) 0.01 2.00

TD4-2 Type Set 2nd monitoring element of TD4 (UNDER, OVER) - UNDER

192 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(9/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
TD4-2 PU Set 2nd pickup value of TD4 (OFF,0.1~6000.0) 0.1 OFF

TD4-2 Delay Set 2nd delay time of TD4 (0.01~600.00sec) 0.01 2.00

5. PLC
1. COMMON
1) LOGIC TIMER
TM1-PU Set pickup time of Logic timer 1 (0.01~600.00sec) 0.01 1.00

TM1-DO Set Dropout Time of Logic timer 1 (0.01~600.00sec) 0.01 0.01

TM2-PU Set pickup time of Logic timer 2 (0.01~600.00sec) 0.01 0.02

TM2-DO Set Dropout Time of Logic timer 2 (0.01~600.00sec) 0.01 0.01

TM3-PU Set pickup time of Logic timer 3 (0.01~600.00sec) 0.01 0.01

TM3-DO Set Dropout Time of Logic timer 3 (0.01~600.00sec) 0.01 0.01

TM4-PU Set pickup time of Logic timer 4 (0.01~600.00sec) 0.01 1.00

TM4-DO Set Dropout Time of Logic timer 4 (0.01~600.00sec) 0.01 0.01

TM5-PU Set pickup time of Logic timer 5 (0.01~600.00sec) 0.01 0.01

TM5-DO Set Dropout Time of Logic timer 5 (0.01~600.00sec) 0.01 0.01

TM6-PU Set pickup time of Logic timer 6 (0.01~600.00sec) 0.01 0.01

TM6-DO Set Dropout Time of Logic timer 6 (0.01~600.00sec) 0.01 0.01

TM7-PU Set pickup time of Logic timer 7 (0.01~600.00sec) 0.01 2.90

TM7-DO Set Dropout Time of Logic timer 7 (0.01~600.00sec) 0.01 0.01

TM8-PU Set pickup time of Logic timer 8 (0.01~600.00sec) 0.01 180.00

TM8-DO Set Dropout Time of Logic timer 8 (0.01~600.00sec) 0.01 0.01

TM9-PU Set pickup time of Logic timer 9 (0.01~600.00sec) 0.01 0.01

TM9-DO Set Dropout Time of Logic timer 9 (0.01~600.00sec) 0.01 0.01

TM10-PU Set pickup time of Logic timer 10 (0.01~600.00sec) 0.01 0.01

TM10-DO Set Dropout Time of Logic timer 10 (0.01~600.00sec) 0.01 0.01

TM11-PU Set pickup time of Logic timer 11 (0.01~600.00sec) 0.01 0.01

TM11-DO Set Dropout Time of Logic timer 11 (0.01~600.00sec) 0.01 0.01

TM12-PU Set pickup time of Logic timer 12 (0.01~600.00sec) 0.01 0.01

TM12-DO Set Dropout Time of Logic timer 12 (0.01~600.00sec) 0.01 0.01

TM13-PU Set pickup time of Logic timer 13 (0.01~600.00sec) 0.01 0.05

TM13-DO Set Dropout Time of Logic timer 13 (0.01~600.00sec) 0.01 0.05

TM14-PU Set pickup time of Logic timer 14 (0.01~600.00sec) 0.01 0.05

TM14-DO Set Dropout Time of Logic timer 14 (0.01~600.00sec) 0.01 0.05

TM15-PU Set pickup time of Logic timer 15 (0.01~600.00sec) 0.01 0.05

193 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(10/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
TM15-DO Set Dropout Time of Logic timer 15 (0.01~600.00sec) 0.01 0.05

TM16-PU Set pickup time of Logic timer 16 (0.01~600.00sec) 0.01 0.05

TM16-DO Set Dropout Time of Logic timer 16 (0.01~600.00sec) 0.01 0.05

2) PULSE TIMER
PTM1 Set output time of pulse timer 1 (0.01~600.00sec) 0.01 0.01

PTM2 Set output time of pulse timer 2 (0.01~600.00sec) 0.01 0.01

PTM3 Set output time of pulse timer 3 (0.01~600.00sec) 0.01 0.01

PTM4 Set output time of pulse timer 4 (0.01~600.00sec) 0.01 0.01

PTM5 Set output time of pulse timer 5 (0.01~600.00sec) 0.01 0.01

PTM6 Set output time of pulse timer 6 (0.01~600.00sec) 0.01 0.01

PTM7 Set output time of pulse timer 7 (0.01~600.00sec) 0.01 0.01

PTM8 Set output time of pulse timer 8 (0.01~600.00sec) 0.01 0.01

PTM9 Set output time of pulse timer 9 (0.01~600.00sec) 0.01 0.01

PTM10 Set output time of pulse timer 10 (0.01~600.00sec) 0.01 0.01

PTM11 Set output time of pulse timer 11 (0.01~600.00sec) 0.01 0.01

PTM12 Set output time of pulse timer 12 (0.01~600.00sec) 0.01 0.01

PTM13 Set output time of pulse timer 13 (0.01~600.00sec) 0.01 0.01

PTM14 Set output time of pulse timer 14 (0.01~600.00sec) 0.01 0.01

PTM15 Set output time of pulse timer 15 (0.01~600.00sec) 0.01 0.01

PTM16 Set output time of pulse timer 16 (0.01~600.00sec) 0.01 0.01

3) PULSE COUNTER
PC1 Set output count value of Pulse counter 1 (1~60000) 1 1000

PC2 Set output count value of Pulse counter 2 (1~60000) 1 1000

PC3 Set output count value of Pulse counter 3 (1~60000) 1 1000

PC4 Set output count value of Pulse counter 4 (1~60000) 1 1000

PC5 Set output count value of Pulse counter 5 (1~60000) 1 1000

PC6 Set output count value of Pulse counter 6 (1~60000) 1 1000

PC7 Set output count value of Pulse counter 7 (1~60000) 1 1000

PC8 Set output count value of Pulse counter 8 (1~60000) 1 1000

PC9 Set output count value of Pulse counter 9 (1~60000) 1 1000

PC10 Set output count value of Pulse counter 10 (1~60000) 1 1000

PC11 Set output count value of Pulse counter 11 (1~60000) 1 1000

194 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(11/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
PC12 Set output count value of Pulse counter 12 (1~60000) 1 1000

PC13 Set output count value of Pulse counter 13 (1~60000) 1 1000

PC14 Set output count value of Pulse counter 14 (1~60000) 1 1000

PC15 Set output count value of Pulse counter 15 (1~60000) 1 1000

PC16 Set output count value of Pulse counter 16 (1~60000) 1 1000

2. DI/DO
1) INPUT DEBOUNCE

IN101 Set Input Debounce Time of IN101 (0.005~10.000sec) 0.001 0.020

IN102 Set Input Debounce Time of IN102 (0.005~10.000sec) 0.001 0.020

IN103 Set Input Debounce Time of IN103 (0.005~10.000sec) 0.001 0.020

IN104 Set Input Debounce Time of IN104 (0.005~10.000sec) 0.001 0.020

IN105 Set Input Debounce Time of IN105 (0.005~10.000sec) 0.001 0.020

IN106 Set Input Debounce Time of IN106 (0.005~10.000sec) 0.001 0.020

IN107 Set Input Debounce Time of IN107 (0.005~10.000sec) 0.001 0.020

IN108 Set Input Debounce Time of IN108 (0.005~10.000sec) 0.001 0.020

IN201 Set Input Debounce Time of IN201 (0.005~10.000sec) 0.001 0.005

IN202 Set Input Debounce Time of IN202 (0.005~10.000sec) 0.001 0.005

IN203 Set Input Debounce Time of IN203 (0.005~10.000sec) 0.001 0.020

IN204 Set Input Debounce Time of IN204 (0.005~10.000sec) 0.001 0.020

IN205 Set Input Debounce Time of IN205 (0.005~10.000sec) 0.001 0.005

IN206 Set Input Debounce Time of IN206 (0.005~10.000sec) 0.001 0.005

IN207 Set Input Debounce Time of IN207 (0.005~10.000sec) 0.001 0.020

IN208 Set Input Debounce Time of IN208 (0.005~10.000sec) 0.001 0.020

IN209 Set Input Debounce Time of IN209 (0.005~10.000sec) 0.001 0.005

IN210 Set Input Debounce Time of IN210 (0.005~10.000sec) 0.001 0.005

IN211 Set Input Debounce Time of IN211 (0.005~10.000sec) 0.001 0.020

IN212 Set Input Debounce Time of IN212 (0.005~10.000sec) 0.001 0.020

IN213 Set Input Debounce Time of IN213 (0.005~10.000sec) 0.001 0.005

IN214 Set Input Debounce Time of IN214 (0.005~10.000sec) 0.001 0.005

IN215 Set Input Debounce Time of IN215 (0.005~10.000sec) 0.001 0.020

IN216 Set Input Debounce Time of IN216 (0.005~10.000sec) 0.001 0.020

195 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(12/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
IN217 Set Input Debounce Time of IN217 (0.005~10.000sec) 0.001 0.005

IN218 Set Input Debounce Time of IN218 (0.005~10.000sec) 0.001 0.005

IN219 Set Input Debounce Time of IN219 (0.005~10.000sec) 0.001 0.020

IN220 Set Input Debounce Time of IN220 (0.005~10.000sec) 0.001 0.020

IN221 Set Input Debounce Time of IN221 (0.005~10.000sec) 0.001 0.005

IN222 Set Input Debounce Time of IN222 (0.005~10.000sec) 0.001 0.005

IN223 Set Input Debounce Time of IN223 (0.005~10.000sec) 0.001 0.020

IN224 Set Input Debounce Time of IN224 (0.005~10.000sec) 0.001 0.020

2) OUTPUT PULSE TIME

OUT101 Set Output pulse time of OUT101 (OFF,0.01~100.00sec) 0.01 0.01

OUT102 Set Output pulse time of OUT102 (OFF,0.01~100.00sec) 0.01 0.01

OUT103 Set Output pulse time of OUT103 (OFF,0.01~100.00sec) 0.01 0.01

OUT104 Set Output pulse time of OUT104 (OFF,0.01~100.00sec) 0.01 0.01

OUT105 Set Output pulse time of OUT105 (OFF,0.01~100.00sec) 0.01 0.01

OUT106 Set Output pulse time of OUT106 (OFF,0.01~100.00sec) 0.01 0.01

OUT107 Set Output pulse time of OUT107 (OFF,0.01~100.00sec) 0.01 3.00

OUT108 Set Output pulse time of OUT108 (OFF,0.01~100.00sec) 0.01 0.01

OUT201 Set Output pulse time of OUT201 (OFF,0.01~100.00sec) 0.01 3.00

OUT202 Set Output pulse time of OUT202 (OFF,0.01~100.00sec) 0.01 3.00

OUT203 Set Output pulse time of OUT203 (OFF,0.01~100.00sec) 0.01 3.00

OUT204 Set Output pulse time of OUT204 (OFF,0.01~100.00sec) 0.01 3.00

OUT205 Set Output pulse time of OUT205 (OFF,0.01~100.00sec) 0.01 0.10

OUT206 Set Output pulse time of OUT206 (OFF,0.01~100.00sec) 0.01 0.03

OUT207 Set Output pulse time of OUT207 (OFF,0.01~100.00sec) 0.01 0.10

OUT208 Set Output pulse time of OUT208 (OFF,0.01~100.00sec) 0.01 0.03

OUT209 Set Output pulse time of OUT209 (OFF,0.01~100.00sec) 0.01 3.00

OUT210 Set Output pulse time of OUT209 (OFF,0.01~100.00sec) 0.01 3.00

OUT211 Set Output pulse time of OUT209 (OFF,0.01~100.00sec) 0.01 3.00

OUT212 Set Output pulse time of OUT210 (OFF,0.01~100.00sec) 0.01 3.00

6. OTHERS
1. FACTORY DEBUG :
This is menu is for Manufacturer's maintenance purpose.

196 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(13/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
MAIN MENU(Circuit)
1. GROUP SETTING(PRIMARY or ALTERNATE)
Switch Part : SW
1. PICKUP CURRENT
Phase Set the pickup current of Phase (OFF, 10~1600 A) 5 400

Ground Set the pickup current of Ground (OFF, 10~1600 A) 5 70

2. INRUSH RESTRAINT
PHA-Time Set the inrush current time of phase (0.0~180.0 sec) 0.1 0.2

GND-Time Set the inrush current time of ground (0.0~180.0 sec) 0.1 0.2

PHA-Multi Set the phase inrush current restraint value (1~20) 1 4

GND-Multi Set the ground inrush current restraint value (1~20) 1 4

3. DIRECTION
1. PHASE
Select whether to use phase direction
Type - DISABLE
(DISABLE, ENABLE)
M.T.A(V1) Set the Maximum Torque Angle (0~359deg) 1 60
Set Minimum Polarizing to check Phase disconnect
M.P.V 1 10
direction (OFF, 1~80%)
2. GROUND
Select whether to use ground direction
Type - DISABLE
(DISABLE, ENABLE)
M.T.A(-V0) Set the maximum torque angle (0~359deg) 1 60
Set Minimum Polarizing Voltage to check ground fault
M.P.V 1 10
direction (OFF, 1~80%)
4. F.I SETTING TIME
Permanent Permanent FI reset time (1~180 sec) 1 20

Transient Transient FI reset time (1~180 sec) 1 2

Type I delay Set the delay time for F.I detection (0.03~180.00sec) 0.01 0.03

5. ON/OFF LEVEL
On Level Set normal voltage level (0.70~0.85pu) 0.01 0.80

Off Level Set phase open/loss level (0.30~0.75pu) 0.01 0.50

Detect Time Set delay time of phase open or loss (0.0~180.0sec) 0.1 4.0

8. PHASE DIFF
Level Set the phase difference level (OFF, 5~80deg) 5 30

Time Set the delay time of phase difference (0.0~180.0sec) 0.1 4.0

9. LIVE LINE
Live Line Lv Set the live line level (0.10~0.90pu) 0.01 0.30

197 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(14/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
Set the delay time of live detect element
Live Line Tm 0.1 4.0
(0.0~180.0sec)

Circuit Breaker Part : CB


1. 51P : TIME OC-PHA
Pickup Set the pickup current of Phase (OFF, 10~1600 A) 5 400
Select the desired curve type
Curve - N1
(A(101),B(117), ... ,DEF-10S: total 50)
Select Time dial and multiply it to selected curve
Time Dial 0.01 1.00
(0.05~15.00)
Select Time adder and add it on the curve
Time Adder 0.01 0.00
(0.00~10.00 sec)
M.R.T Minimum Response Time setting (0.00~10.00 sec) 0.01 0.00
Select the reset method of phase protection
Reset Method - INST
(INST, LINEAR)
2. 51G : TIME OC-GND
Pickup Set the pickup current of Ground (OFF, 10~1600A) 5 70
Select the desired curve type
Curve - N1
(A(101),B(117),...,DEF-10S: total 50)
Select Time dial and multiply it to selected curve
Time Dial 0.01 1.00
(0.05~15.00)
Select Time adder and add it on the curve
Time Adder 0.01 0.00
(0.00~10.00 sec)
M.R.T Minimum Response Time setting (0.00~10.00 sec) 0.01 0.00
Select the reset method of ground protection
Reset Method - INST
(INST, LINEAR)

3. 50P : INST' OC-PHA


Set the pickup current of Phase High current Trip
Pickup 1 3500
(OFF, 50~10000A)
Time Delay Set Time Delay for phase high current trip 1 (0.00~1.00sec) 0.01 0.00

4. 50G : INST' OC-GND


Set the pickup current of Ground High current Trip
Pickup 1 1750
(OFF, 25~10000A)
Set Time Delay for ground high current trip
Time Delay 0.01 0.00
(0.00~1.00sec)

5. COLD LOAD PICKUP


PHA(xMTC) Set phase inrush current restraint value (OFF, 1~10xTMC) 1 4

GND(xMTC) Set ground inrush current restraint value (OFF, 1~10xTMC) 1 6

RMT-PHA Set Restore Minimum Time for phase (OFF, 0.01~30.00sec) 0.01 0.30

RMT-GND Set Restore Minimum Time for ground (OFF, 0.01~30.00sec) 0.01 0.30

RST-PHA Set cold load reset time for phase (OFF, 0.01~60.00sec) 0.01 3.00

RST-GND Set cold load reset time for ground (OFF, 0.01~60.00sec) 0.01 3.00

198 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(15/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
6. DIRECTION
1. PHASE
Type Set phase direction type (NONE,FORWARD,REVERSE) - NONE

M.T.A(V1) Set the Maximum Torque Angle (0~359deg) 1 60

M.P.V Set Minimum Polarizing to check Phase disconnect direction (OFF, 10~80%) 1 10

Block OC Select whether to block the phase polarizing trip (NO, YES) - NO

2. GROUND
Type Set Ground direction type(NONE,FORWARD,REVERSE) - NONE

M.T.A(-V0) Set the maximum torque angle (0~359deg) 1 60

M.P.V Set Minimum Polarizing Voltage to check ground fault direction (OFF, 10~80%) 1 10
Select whether to block the ground polarizing trip
Block OC - NO
(NO, YES)

7. USER CURVE
1. USER CURVE 1
Factor a User defined curve1 factor α (0.0000~150.9999) 0.0001 0.0515

Factor b User defined curve1 factor β (0.0000~150.9999) 0.0001 0.02

Factor r User defined curve1 factor γ (0.0000~150.9999) 0.0001 0.114

Factor rt User defined curve1 factor rt (0.0000~150.9999) 0.0001 4.85

2. USER CURVE 2
Factor a User defined curve2 factor α (0.0000~150.9999) 0.0001 19.61

Factor b User defined curve2 factor β (0.0000~150.9999) 0.0001 2

Factor r User defined curve2 factor γ (0.0000~150.9999) 0.0001 0.491

Factor rt User defined curve2 factor rt (0.0000~150.9999) 0.0001 4.85

3. USER CURVE 3
Factor a User defined curve3 factor α (0.0000~150.9999) 0.0001 28.2

Factor b User defined curve3 factor β (0.0000~150.9999) 0.0001 2

Factor r User defined curve3 factor γ (0.0000~150.9999) 0.0001 0.1217

Factor rt User defined curve3 factor rt (0.0000~150.9999) 0.0001 29.1

4. USER CURVE 4
Factor a User defined curve4 factor α (0.0000~150.9999) 0.0001 5.67

Factor b User defined curve4 factor β (0.0000~150.9999) 0.0001 2

Factor r User defined curve4 factor γ (0.0000~150.9999) 0.0001 0.0352

Factor rt User defined curve4 factor rt (0.0000~150.9999) 0.0001 5.67

199 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(16/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
8. RECLOSING(79)
1. FUNCTION
Set reclosing function used or not
Function - DISABLE
(DISABLE, ENABLE)

2. OPERATIONS
Lockout Set the maximum number of reclosing sequence (1~4) 1 4

3. INTERVALS
Reclose 1 Set the first reclose interval time (0.5~60.0sec) 0.1 0.6

Reclose 2 Set the second reclose interval time (1~60sec) 1 2

Reclose 3 Set the third reclose interval time (1~60sec) 1 15

Reset T(AR) Set the reset time for auto reclosing (3~180sec) 1 30

Reset T(LO) Set the reset time for lockout (0.00~600.00sec) 0.01 10.00

Set waiting time to get power supply


C/P Wait 0.01 60.00
(1.00~600.00sec)
9. ON/OFF LEVEL
On Level Set normal voltage level (0.70~0.85pu) 0.01 0.80

Off Level Set phase open/loss level (0.30~0.75pu) 0.01 0.30

Detect Time Set delay time of phase open or loss (0.0~180.0sec) 0.1 4.0

10. PHASE DIFF


Level Set the phase difference level (OFF, 5~80deg) 5 30

Time Set the delay time of phase difference (0.0~180.0sec) 0.1 4.0

11. LIVE LINE


Live Line Lv Set the live line level (0.10~0.90pu) 0.01 0.30

Live Line Tm Set the delay time of live detect element (0.0~180.0sec) 0.1 4.0

2. MONITORING
1. OPERATION COUNT
Function Select whether to monitor operation count (OFF, ON) - OFF

Limit Set number for Recloser alarming (1~20000) 1 10000

Count set Set same operation count number (0~10000) 1 0

2. CONTACT WEAR
Function Select whether to monitor Recloser contact wear (OFF, ON) - OFF

Pickup(%) Set number for Recloser alarming (0.0~50.0 %) 0.1 20.0

Rated Volt(kV) Set the power line nominal voltage (15kV, 27kV, 38kV) - 38

Interrupt Enter the capacity of rated Interrupter (5.0~50.0 kA) 0.1 12.5

200 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table B-1] Menu Description & Default Setting(17/17)


FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
No. Max I Enter the capacity of rated Interrupter (1~999) 1 100

A Wear Set Set Circuit breaker phase A (0.00~100.00 %) 0.01 100.00

B Wear Set Set Circuit breaker phase B (0.00~100.00 %) 0.01 100.00

C Wear Set Set Circuit breaker phase C (0.00~100.00 %) 0.01 100.00

201 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

APPENDIX C. LOGIC BIT ATTRIBUTES & DESCRIPTION


[Table C-1] LOGIC BIT ATTRIBUTES & DESCRIPTION(1/5)
※. NOTE ) ① SYS : Checked Logic bit can be used with System Event.
② DIG : Checked Logic bit can be used with Diagnostic Event.
③ SCH : Checked Logic bit can be used with Set Change Event.
④ OPE : Checked Logic bit can be used with Operation Event.
⑤ EQ IN : Checked Logic bit can be used with PLC Input.
⑥ EQ OUT : Checked Logic bit can be used with PLC Output.
SC OP EQ EQ
LOGIC BIT SYS DIG DESCRIPTIONS
H E IN OUT
0 ACFAIL √       √   AC POWER FAIL

1 ADBUSY   √     √   AD BUSY ALARM

2 ADCPUERR   √     √   AD CPU ALARM

3 ADREFERR   √     √   AD REF' ALARM

4 BATBAD √       √ √ BATTERY BAD

5 BTCGBAD   √     √ √ BATTERY & CHARGE BAD

6 BTCMD √       √   BATTERY TEST COMMAND

7 BTING √           BATTERY TESTING

8 CF1~6   √     √   RELAY CLOSE FAILO CCURRED : 1~6 WAY

9 CHGBAD √       √ √ CHARGE BOARD BAD

10 CLASS1~3 √       √   CLASS 1~3 ENABLED

11 CLBLK1~6 √       √ √ CLOSE BLOCK STATUS : 1~6 WAY

12 CLCMD1~6 √           CLOSE COMMAND : 1~6 WAY

13 CLOSE1~6 √       √   CLOSE OPERATION : 1~6 WAY

14 CLPGACT1~6 √       √   CLPU ACTIVE-GND : 1~6 WAY

15 CLPPACT1~6 √       √   CLPU ACTIVE-PHA : 1~6 WAY

16 CLST1~6 √       √ √ CLOSE STATUS : 1~6 WAY

17 CPULINK √           CPU MODULE LINK STATUS

18 DACFAIL √       √ √ AC POWER FAIL(REMOTE)

19 DC11T √       √   DC1-1 TIMEOUT

20 DC12T √       √   DC1-2 TIMEOUT

21 DC21T √       √   DC2-1 TIMEOUT

22 DC22T √       √   DC2-2 TIMEOUT

23 DC31T √       √   DC3-1 TIMEOUT

24 DC32T √       √   DC3-2 TIMEOUT

25 DC41T √       √   DC4-1 TIMEOUT

26 DC42T √       √   DC4-2 TIMEOUT

27 DC51T √       √   DC5-1 TIMEOUT

28 DC52T √       √   DC5-2 TIMEOUT

29 DCLBLK1~6 √       √ √ CLOSE BLOCK STATUS(REMOTE) : 1~6 WAY

30 DCTRLK √       √   CONTROL UNLOCK

202 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table C-1] LOGIC BIT ATTRIBUTES & DESCRIPTION(2/5)


EQ EQ
  LOGIC BIT SYS DIG SCH OPE DESCRIPTION
IN OUT
31 DGPROT1~6 √       √   GROUND PROTECTION DISABLED

32 DIGADC   √     √   DIAGNOSTIC ADC

33 DIGALM   √     √ √ DIAGNOSTIC ALARM

34 DIGASET   √     √   DIAGNOSTIC ALTERNATE SETTING

35 DIGCL   √     √   DIAGNOSTIC CLOSE

36 DIGCNT   √     √   DIAGNOSTIC COUNT

37 DIGCPU   √     √   DIAGNOSTIC CPU

38 DIGDO   √     √   DIAGNOSTIC DO

39 DIGERR   √     √ √ DIAGNOSTIC ERROR

40 DIGEVT   √     √   DIAGNOSTIC EVENT

41 DIGFROM   √     √   DIAGNOSTIC FLASH-ROM

42 DIGGSET   √     √   DIAGNOSTIC GLOBAL SETTING

43 DIGLOG   √     √   DIAGNOSTIC PLC

44 DIGMEM   √     √   DIAGNOSTIC MEMORY

45 DIGOP   √     √   DIAGNOSTIC OPEN

46 DIGPSET   √     √   DIAGNOSTIC PRIMARY SETTING

47 DIGRTC   √     √   DIAGNOSTIC RTC

48 DIGSPM5   √     √   SYSTEM POWER(-5V) ALARM

49 DIGSPOW   √     √   DIAGNOSTIC SYSTEM POWER

50 DIGSPP5   √         SYSTEM POWER(+5V) ALARM

51 DIGSPU   √         DIAGNOSTIC DSP

52 DIGTEMP   √     √   CONTROLLER TEMP' ALARM

53 DPROT1~6 √       √   PROTECTION DISABLED : 1~6 WAY

54 DREC1~6 √       √   RECLOSED DISABLED : 1~6 WAY

55 DRMT √       √   REMOTE DISABLED

56 DROPEN √           DOOR OPEN STATUS

57 DSPLINK √       √   DSP MODULE LINK STATUS

58 E52A1~6 √       √ √ CLOSE/OPEN STATUS (52A) : 1~6 WAY

59 EALTSG1~6 √           ALT' SET GROUP ENABLED : 1~6 WAY

60 ECAPW √           EXTERNAL WAVEFORM CAPTURE


61 ECIR1~6 √           CIRCIT ENABLE : 1~6 WAY

62 ECLOSE1~6       √     EARTH CLOSE BY MANUAL : 1~6 WAY

63 ECTRLK √           CONTROL LOCK

64 EFTRIP1~6 √           FAULT TRIP LOGIC : 1~6 WAY

65 EGPROT1~6 √       √   GROUND PROTECTION ENABLED : 1~6 WAY

66 EOPEN1~6       √     EARTH OPEN BY MANUAL : 1~6 WAY

67 EPROT1~6 √           PROTECTION ENABLED : 1~6 WAY

68 EREC1~6 √           RECLOSE ENABLED : 1~6 WAY

203 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table C-1] LOGIC BIT ATTRIBUTES & DESCRIPTION(3/5)


EQ EQ
  LOGIC BIT SYS DIG SCH OPE DESCRIPTION
IN OUT
69 ERMT √       √   REMOTE ENABLED

70 ETST1~6 √       √ √ EARTH STATUS : 1~6 WAY

71 FIFOR1~6 √       √   FAULT FORWARD DIRECTION : 1~6 WAY

72 FIRCMD √       √   FI RESET COMMAND

73 FIREV1~6 √       √   FAULT REVERSE DIRECTION : 1~6 WAY

74 FITING √           FI TESTING

75 FORPF1T~FORPF6T √           FORWARD POWER FLOW : 1~6 WAY

76 FWCCMD √       √   FAULT WAVE CLEAR COMMAND : 1~6 WAY

77 GASHIGH √       √ √ GAS HIGH STATUS

78 GASLOW √       √ √ GAS LOW STATUS

79 IN101~108 √       √   INPUT PORT1-01~08

80 IN201~224 √       √   INPUT PORT2-01~24

81 INRUSH1~6 √       √   INRUSH OCCURRED : 1~6 WAY

82 LASCHG1~6     √       ALT' SETTING CHANGED - LOCAL : 1~6 WAY

83 LCLOSE1~6       √     CLOSE BY LOCAL : 1~6 WAY

84 LGSCHG     √       GLOBAL SETTING CHANGED - LOCAL

85 LKCMD √       √   LOCK COMMAND

86 LOPEN1~6       √     OPEN BY LOCAL : 1~6 WAY

87 LPSCHG1~6     √       PRI' SETTING CHANGED - LOCAL : 1~6 WAY

88 M3PO1T~M2PO6T √           THREE-POLE OPEN TIMEOUT : 1~6 WAY

89 MCLOSE1~6       √     CLOSE BY MANUAL : 1~6 WAY

90 MLOCK1~6 √       √ √ MECHANISM LOCK : 1~6 WAY

91 MOPEN1~6       √     OPEN BY MANUAL : 1~6 WAY

92 NOBATT √       √ √ BATTERY NO EXIST

93 OPCMD1~6 √       √ √ OPEN COMMAND : 1~6 WAY

94 OPST1~6 √       √ √ OPEN STATUS : 1~6 WAY

95 OUT101~108 √           OUTPUT PORT1-01~08

96 OUT201~212 √       √   OUTPUT PORT2-01~12

97 PASCHG1~6     √       ALT' SETTING CHANGED - PROGRAM : 1~6 WAY

98 PFIA1~6 √       √   FI - A PHASE : 1~6 WAY

99 PFIB1~6 √       √   FI - B PHASE : 1~6 WAY

100 PFIC1~6 √       √   FI - C PHASE : 1~6 WAY

101 PFIG1~6 √       √   FI - GROUND : 1~6 WAY

102 PGSCHG     √       GLOBAL SETTING CHANGED - PROGRAM

103 PPSCHG1~6     √       PRI' SETTING CHANGED - PROGRAM : 1~6 WAY

104 PRSFI1~6 √       √   PERMANENT FI RESET : 1~6 WAY

105 PSLEEP √       √ √ PANEL SLEEP MODE

106 PWDOWN √       √ √ POWER DOWN SIGNAL

204 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table C-1] LOGIC BIT ATTRIBUTES & DESCRIPTION(4/5)


EQ EQ
  LOGIC BIT SYS DIG SCH OPE DESCRIPTION
IN OUT
107 RASCHG1~6     √       ALT' SETTING CHANGED - REMOTE : 1~6 WAY

108 RCLOSE1~6       √ √   CLOSE BY REMOTE : 1~6 WAY

109 RECDCMD1~6 √       √ √ RECLOSING DISABLE COMMAND : 1~6 WAY

110 RECECMD1~6 √           RECLOSING ENABLE COMMAND : 1~6 WAY

111 REVPF1T~REVPF6T √       √   REVERSE POWER FLOW : 1~6 WAY

112 RGSCHG     √       GLOBAL SETTING CHANGED - REMOTE

113 ROPEN1~6       √     OPEN BY REMOTE : 1~6 WAY

114 RPSCHG1~6     √       PRI' SETTING CHANGED - REMOTE : 1~6 WAY

115 SELFTERR   √         SELF TEST ERROR

116 SELFTOK   √         SELF TEST OK

117 SGCACMD1~6 √       √ √ ALT' SETTING CHANGE COMMAND : 1~6 WAY

118 SGCPCMD1~6 √       √ √ PRI' SETTING CHANGE COMMAND : 1~6 WAY

119 STTB1~6 √       √ √ TROUBLE STATUS : 1~6 WAY

120 SYSRST   √     √ √ SYSTEM RESTART

121 TFIS1~6 √       √   TEMPORARY FI SET: 1~6 WAY

122 TRF1~6   √     √   RELAY TRIP FAIL OCCURRED : 1~6 WAY

123 TRIP1~6 √       √   TRIP OPERATION : 1~6 WAY

124 TRSFI1~6 √       √   TEMPORARY FI RESET : 1~6 WAY

125 ULKCMD √       √   UNLOCK COMMAND

126 VTFAIL1T~VTFAIL6T   √     √   VT FAIL TIMEOUT : 1~6 WAY

127 WCAPCMD √           WAVE CAPTURE COMMAND

128 Y27LV1~6 √       √   LIVE VOLTAGE PICKUP : 1~6 WAY

129 Y27LV1T~Y27LV6T √       √   LIVE VOLTAGE TIMEOUT : 1~6 WAY

130 Y47A1T~Y47A6T √           OPEN VOLTAGE - A PHA : 1~6 WAY

131 Y47B1T~Y47B6T √       √   OPEN VOLTAGE -B PHA : 1~6 WAY

132 Y47C1T~Y47C6T √       √   OPEN VOLTAGE - C PHA : 1~6 WAY

133 Y79CY1~6 √       √   SEQUENCE CYCLE : 1~6 WAY

134 Y79LO1~6 √       √   SEQUENCE LOCKOUT : 1~6 WAY

135 Y79LOLB1~6 √       √   SEQUENCE LOCKOUT OF LIVE BLOCK: 1~6 WAY

136 Y79RS1~6 √       √   SEQUENCE RESET : 1~6 WAY

137 YIOCTR1~6 √       √   INST' OC TRIP OCCURRED : 1~6 WAY

138 YSH10~13 √       √   RECLOSE SEQUENCE 0~3 : 1 WAY

139 YSH20~23 √       √   RECLOSE SEQUENCE 0~3 : 2 WAY

140 YSH30~33 √       √   RECLOSE SEQUENCE 0~3 : 3 WAY

141 YSH40~43 √       √   RECLOSE SEQUENCE 0~3 : 4 WAY

142 YSH50~53 √       √   RECLOSE SEQUENCE 0~3 : 5 WAY

143 YSH60~63 √       √   RECLOSE SEQUENCE 0~3 : 6 WAY

144 YTMB1A1~6 √       √   CLOSE ON TO FAULT LOCKOUT : 1~6 WAY

205 ENTEC ELECTRIC & ELECTRONIC CO., LTD.


Multi-Way Control Communication Unit (ETR306) Appendix

[Table C-1] LOGIC BIT ATTRIBUTES & DESCRIPTION(5/5)


EQ EQ
  LOGIC BIT SYS DIG SCH OPE DESCRIPTION
IN OUT
145 YTOCTR1~6 √       √   TIME OC TRIP OCCURRED : 1~6 WAY

146 YZSV1T~YZSV6T √       √   ZERO-SEQUENCE VOLTAGE : 1~6 WAY

206 ENTEC ELECTRIC & ELECTRONIC CO., LTD.