User's Manual
Copyright © 2016 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
Multi-Way Control Communication Unit (ETR306) Release Note
Release Note :
Table of Contents
Release Note ii
Safety precautions v
1. INTRODUCTION 1
2. TECHNICAL SPECIFICATIONS 2
2.1. Usage Condition 2
2.2. Input & Output 2
2.3. Insulation strength 3
2.4. Communication Port 3
3. DIMENSIONS AND CONSTRUCTION 4
4. SIDE PANEL CONSTRUCTION 5
4.1. Current Input Connector 6
4.2. Voltage Input Connector 7
4.3. Digital Output Connector 8
4.4. Digital Input Connector 9
4.4.1. Common Connector 9
4.4.2. Circuit Connector 9
4.5. Power Input Connector 10
4.6. TD Input Connector 11
4.7. Communication Port (COM PORT) 12
4.7.1. Port for Main Device Communication 12
4.7.2. Maintenance Port 12
4.7.3. RS485 Communication Port 13
4.7.4. Ethernet Port 13
5. USER INTERFACE PANEL 14
5.1. User defined LED Part 15
5.2. Common Control Part 16
5.3. Local Control Part 17
5.4. Open/Close Operation Part 17
5.5. Fault Indication Part 18
5.6. System & LCD Control Part 19
5.6.1. Communication Status Indication Part 20
Safety notice
Safety notice is to operate product safely and
correctly by preventing any accident or danger
before hand.
WARNING
Injury or loss of life can happen in case of
violating this sign
CAUTION
Minor injury or product damage can happen in case
of violating this sign
WARNING
Do not work on wiring when power is on or
while machine is operating.
It could cause an electric shock. In addition, protection element can be
triggered.
Conduct grounding.
Not conducting grounding might cause electric shock.
CAUTION
Approve power of product's P.N power terminal so
that it suits polarity and rating.
Not following rated specification might cause damage or fire in product.
1. INTRODUCTION
ETR306 is installed in 22.9kV-Y/△ multi way of switchgear(combination of circuit
breaker and switch) of distribution line and can be controlled locally or remotely.
It is compact as product is produced as slim type.
ETR306 receives measured signal and status information from each way of
switchgear and its controller. So it can inspect voltage and current flow on
distribution line. It can remotely transmit distribution line status such as FI
detection, single line/phase loss, live/dead line, phase discordance, over current,
direction of tidal flow, direction of fault detection as well as condition of each
way of switchgear and its controller.
Because it can supports to receive remotely control command from each way of
switchgear breaker distribution automation system is perfectly supported. It can
be easily applied for user's communication environment through various
communication method (DNP3.0, MODBUS, IEC60870-5-101/104 option) support.
Control switch on front panel can be used to operate manual open/close for each
way of switchgear, and select fault detect/restrain, ground detect normal/restrain,
control select local/remote, and control lock/unlock operation mode.
ETR306 has a PLC (Programmable Logic Control) changed by user. The PLC can
control input and output using information of timer, counter and internal event.
INTERFACE SOFTWARE is easy to use and things such as set value and
operation record can be saved and administered in PC. It is useful for fault
analysis since it has an excellent zoom function and it has a function that
Indicate fault waveform and digital operation factor status together with time.
2. TECHNICAL SPECIFICATIONS
2.1. Usage Condition
Conditions of use
Maximum 70℃, minimum -25℃, elevation below 1,000m
Control Input
Control Inputs 24 channel
Nominal Voltages and Operating Range
250Vdc (-15%, +20%)
125Vdc (-15%, +20%)
48Vdc (-15%, +20%)
24Vdc (-15%, +20%)―standard
Operating current : < 5mA at Nominal Voltages
Output Contacts
Outputs 20 Channel
350Vdc Varistor for differential surge protection
Make : 30A
Carry : 6A Continuous Carry
Break Capacity
- 125V 0.3A L/R=25ms
SW
SW
CB
CB
CB
CONTROL
MON
COM
ENT
RESET
FUN
LAMP
OPEN
OPEN
OPEN
OPEN
OPEN
OPEN
DOWN
CUIT
CIR
UP
RE MOTE/LOCAL
EARTH
EARTH
EARTH
EARTH
EARTH
EARTH
BATT
T EST
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
AC POW ER OK
CHARGER OK
BATTERY OK
CB BLOCK
DSP LINK
CPU LINK
GROUND
GROUND
GROUND
GROUND
GROUND
GROUND
Multi-Way Control Communication Unit (ETR306)
PROTECTION
PROTECTION
PROTECTION
PROTECTION
PROTECTION
PROTECTION
1 LIVE
2 LIVE
3 LIVE
4 LIVE
5 LIVE
6 LIVE
79RS
79CY
79RS
79CY
79RS
79CY
79RS
79CY
79RS
79CY
79RS
79CY
PORT F
P 1 RTS/CTS
51
50
51
50
51
50
51
50
51
50
51
50
Run/Reset
/DIAG
P 1 RX/TX
P 2 RX/TX
N
1
6
M 2.5
M 2.5
2TX
IN101 103 105 107 108 COM 2RX
OUT101 102 103 104 OUT105 106 107 108 - 1TX
RS232(PORT1) ETHERNET(PORT3)
RS485(PORT2) 1RX
+
M2.5
M2.5
950-8 950-8 950-8 950
A 02 03 04 05 06 07 08 B 02 03 04 05 06 07 08 09 10 C 02 03 04 05 06 07 08 09 10 P N SG
IN201 203 205 207208 COM IN209 211 213 215 216 COM IN217 219 221 223 224 COM
D C1(mA) DC2(mA) DC3(V) DC4(V) OUT201 202 203 204 OUT205 206 207 208 OUT209 210 211 212 - - -
+ + +
950-8 950-8 950-8 950-8 950-8 950-8 950-8
K 02 03 04 05 06 07 08 E 02 03 04 05 06 07 08 F 02 03 04 05 06 07 08 G 02 03 04 05 06 07 08 H 02 03 04 05 06 07 08 09 10 I 02 03 04 05 06 07 08 09 10 J 02 03 04 05 06 07 08 09 10
1IA 1IB 1IC 1IG 2IA 2IB 2IC 2IG 3IA 3IB 3IC 3IG 4IA 4IB 1IC 4IG 1VA V B VC 2VA VB VC 3VA VB VC 4VA VB VC VG
950-8 950-8
R 02 03 04 05 06 S 02 03 04 05 06 T 02 03 04 05 06 U 02 03 04 05 06 V 02 03 04 05 06 07 08 W 02 03 04 05 06 07 08 09 10
POWER IN 5IA 5IB 5IC 5IG 6IA 6IB 6IC 6IG 5VA VB VC 6VA VB VC
+24V 0V +24V 0V ZG FG
M 2.5
M 2.5
950-8
P 02 03 04 05 06 X 02 03 04 05 06 Y 02 03 04 05 06 Z 02 03 04 05 06 07 08
4
Multi-Way Control Communication Unit (ETR306)
M2.5
M2.5
2TX
IN101 103 105 107 108 COM 2RX
OUT101 102 103 104 OUT105 106 107 108 - 1TX
RS232(PORT1) ETHERNET(PORT3)
RS485(PORT2) 1RX
+
M2.5
M2.5
950-8 950-8 950-8 950
A 02 03 04 05 06 07 08 B 02 03 04 05 06 07 08 09 10 C 02 03 04 05 06 07 08 09 10 P N SG
IN201 203 205 207 208 COM IN209 211 213 215 216 COM IN217 219 221 223 224 COM
DC1(mA) DC2(mA) DC3(V) DC4(V) OUT201 202 203 204 OUT205 206 207 208 OUT209 210 211 212 - - -
+ + +
950-8 950-8 950-8 950-8 950-8 950-8 950-8
K 02 03 04 05 06 07 08 E 02 03 04 05 06 07 08 F 02 03 04 05 06 07 08 G 02 03 04 05 06 07 08 H 02 03 04 05 06 07 08 09 10 I 02 03 04 05 06 07 08 09 10 J 02 03 04 05 06 07 08 09 10
1IA 1IB 1IC 1IG 2IA 2IB 2IC 2IG 3IA 3IB 3IC 3IG 4IA 4IB 1IC 4IG 1VA VB VC 2VA VB VC 3VA VB VC 4VA VB VC VG
950-8 9 50-8
R 02 03 04 05 06 S 02 03 04 05 06 T 02 03 04 05 06 U 02 03 04 05 06 V 02 03 04 05 06 07 08 W 02 03 04 05 06 07 08 09 10
POWER IN 5IA 5IB 5IC 5IG 6IA 6IB 6IC 6IG 5VA VB VC 6VA VB VC
+24V 0V +24V 0V ZG FG
M2.5
M2.5
9 50-8
P 02 03 04 05 06 X 02 03 04 05 06 Y 02 03 04 05 06 Z 02 03 04 05 06 07 08
1IA 1IB 1IC 1IG 2IA 2IB 2IC 2IG 3IA 3IB 3IC 3IG 4IA 4IB 1IC 4IG
R 02 03 04 05 06 S 02 03 04 05 06 T 02 03 04 05 06 U 02 03 04 05 06
X 02 03 04 05 06 Y 02 03 04 05 06
950-8 950-8
V 02 03 04 05 06 07 08 W 02 03 04 05 06 07 08 09 10
5VA VB VC 6VA VB VC
950-8
Z 02 03 04 05 06 07 08
950-8 950-8
A 02 03 04 05 06 07 08 B 02 03 04 05 06 07 08 09 10
OUT201 202 203 204 OUT205 206 207 208 OUT209 210 211 212
E 02 03 04 05 06 07 08 F 02 03 04 05 06 07 08 G 02 03 04 05 06 07 08
C 02 03 04 05 06 07 08 09 10
H 02 03 04 05 06 07 08 09 10 I 02 03 04 05 06 07 08 09 10 J 02 03 04 05 06 07 08 09 10
950-8
K 02 03 04 05 06 07 08
<Figure 4-8> TD Input Connector
P N SG 485-
UP FUN
PORT F
Run/Reset
/DIAG
P1 RX/TX
DOWN ENT
P1 RTS/CTS
P2 RX/TX
CIR COM
CUIT MON
3 LIVE BATTERY OK
4 LIVE CB BLOCK
1
CB
A 51
B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND
2
CB
A 51
B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND
3
CB
A 51
B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND
4
SW
A 51
B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND
5
SW
A 51
B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND
6
SW
A 51
B 50 EARTH
C 79RS CLOSE OPEN
N 79CY
PROTECTION GROUND
1 LIVE AC POWER OK
2 LIVE CHARGER OK
3 LIVE BATTERY OK
4 LIVE CB BLOCK
REMOTE/LOCAL CONTROL
PROTECTION (ENABLED/DISABLED)
- ENABLED(On) :
All protection elements operate.
- DISABLED(Off) :
All protection elements do not operate.
PROTECTION GROUND
GROUND (ENABLED/DISABLED)
- ENABLED(On) : <Figure 5-4> Local Control Part
Ground protection element operates.
- DISABLED(Off) :
Ground protection element does not operate.
EARTH
CLOSE OPEN
EARTH Lamp
- The 'EARTH' lamp turns on if the CB inputs to the ground.
- The earth can be operated with a manual operating rod.
- Open/Close control is not possible in the earth input status.
C 79RS
51 Lamp
The lamp turns on when the 51 fault element is N 79CY
detected.
50 Lamp
<Figure 5-6> Fault Indication
The lamp turns on when the 50 fault element is Part
detected.
79RS Lamp
The lamp turns on when reclosing(79) reset
element is detected. <Figure 5-7> F.I RESET Button
79CY Lamp
The lamp turns on when reclosing(79) cycle
element is detected
UP FUN
PORT F
Run/Reset
/DIAG
P1 RX/TX
DOWN ENT
P1 RTS/CTS
P2 RX/TX
CIR COM
CUIT MON
RUN Lamp
It indicates ETR306's operation status. It periodically blinks during normal
operation. In case of system fault, it turns on or off.
RESET Lamp
It turns off after turning on every time system boots and if a system error
occurs during operation, it turns on.
DIAG' Lamp
It turns on if a self diagnosis warning occurs during system operation. Detailed
information can be checked in Common Menu "Diagnosis Event".
PORT2
It is indicated if it is in 485 communication.
- RX Lamp : It turns on in case of PORT2's data received.
- TX Lamp : It turns on in case of PORT2's data transmitted.
PORT3
It is indicated if it is in Ethernet communication.
- LINK Lamp : It turns on if PORT3 is connected to network.
- ACT Lamp : It turns on if there is data in the LAN when PORT3 is connected
to the network.
Key Description
From initial screen, it changes to menu selection mode and in the submenu of
each menu it is used as a function to go to the menu before. If pressed in the
Main Menu, it is used to change to the initial screen mode. If this key operates
when setting value is changed, all the changed values will return to the original
[FUN]
value set before.
It is used for selecting menu and changing the set value. In the menu selecting
screen, it operates as a menu selecting function and when the set value is
changed, it changes to menu changing mode in the relevant value's change mode
[ENT] (it operates in toggle method when changing the menu select/setting).
It is used to move the menu up or increase the set value. All the menu is made
as a structure that moves to the bottom location of the menu if in the top location
of the menu since it has a rotation selection function. This function is also applied
when changing set value so the key set value is selected after changing the top
[ UP ] set value. If the button is pressed, it increases one by one and if pressed for
more than 2 seconds, it increases rapidly.
It is used to move the menu to the bottom or decrease the set value. The
rotation selection function is applied for this button too, just like the [UP] key,
when changing the menu/ set value. If the button is pressed, it decreases one by
[DOWN] one and if pressed for more than 2 seconds, it decreases rapidly.
Choose 1 way from the 6 way. If this key is pressed, it changes to the initial
CIR
screen of the chosen circuit.
CUIT
※. NOTE ) The changed value does not get saved if this key is pressed when
[1~6 WAY] changing the set value.
<Figure 6-2> Circuit Menu Tree Structure for Circuit Breaker Part(CB)
Initial screen is composed of circuit initial screen and common initial screen.
It moves to relevant initial screen if [CIRCUIT] or [COMMON] key are
pressed.
Press [▲][▼] key to move to selected initial screen.
It moves to main menu if [FUN] key is pressed in initial screen.
Initial Screen
Initial Screen
[ MA I N ME N U ] COM
> 1 . GL OB A L SE T T I NG
2 . E V E NT
3 . MA I N T E N A N C E
4 . T I ME
5 . ST AT UE
6 . ME T E R I N G
[ GL OBA L S E T T I N G]
> 1 . S Y S T E M
2 . C OMMU N I C A T I ON
3 . E V E NT R E C ODE R
4 . MON I T OR I N G
5 . P L C
6 . OT HE R S
* . S AV E SE T T I NG
6.5.1.1. SYSTEM
It moves to this menu if [ENT] key is pressed after locating cursor in “1.
SYSTEM” in ‘GLOBAL SETTING' menu. Various facts related to system are set
in this menu and it has submenus below.
[ S Y S T E M]
> 1 . P O WE R L I NE
2 . CURRE NT S E NSI NG
3 . V OL T A GE S E NSI NG
4 . C ON T R OL T Y P E
5 . CB OP E N I N G T I ME
6 . GA S S E NS OR T Y PE
7 . F I T Y PE S E L E CT
Caution : This setting change may influence metering and whole system,
precaution is requested.
① Use [▲] and [▼] key and move to items which want to change setting.
② Press [ENT] key to change setting value.
③ Use [▲] and [▼] key to Set new value and press [ENT] key to change
setting value.
[ P O WE R L I NE ]
> F r e q u e n c y : 6 0
Re f . V o l t a g e : A
Ph a s e Ro t a t i o n : ABC
N o mi n a l V o l t : 1 3 2 0 0
1) Frequency
Range 50, 60 ㎐
Default 60
Step 10
2) Ref. Voltage
Range A, B, C, NONE
Default A
Step - 0
[Table 6-3] Phase selection according to standard voltage and phase rotation
Setting Standard
REF A REF B REF C
voltage
Phase
Terminal ABC ACB ABC ACB ABC ACB
rotation
A body
- A A B B C C
bushing
B body
- B C C A A B
bushing
C body
- C B A C B A
bushing
3) Phase Rotation
4) Nominal Volt
[ CURRE NT S E NS I NG]
> CT 1 - Ra t i o : 1 0 0 0
GCT 1 - Ra t i o : 1 0 0 0
CT 2 - Ra t i o : 1 0 0 0
GCT 2 - Ra t i o : 1 0 0 0
CT 3 - Ra t i o : 1 0 0 0
GCT 3 - Ra t i o : 1 0 0 0
CT 4 - Ra t i o : 1 0 0 0
GCT 4 - Ra t i o : 1 0 0 0
CT 5 - Ra t i o : 1 0 0 0
GCT 5 - Ra t i o : 1 0 0 0
CT 6 - Ra t i o : 1 0 0 0
GCT 6 - Ra t i o : 1 0 0 0
CT 1 - Po l : F OR
GCT 1 - P o l : F OR
CT 2 - Po l : F OR
GCT 2 - P o l : F OR
CT 3 - Po l : F OR
GCT 3 - P o l : F OR
CT 4 - Po l : F OR
GCT 4 - P o l : F OR
CT 5 - Po l : F OR
GCT 5 - P o l : F OR
CT 6 - Po l : F OR
GCT 6 - P o l : F OR
1) CT#-Ratio
Range 1 ~ 2000
Default 1000
Step 1
2) GCT#-Ratio
Range 1 ~ 5000
Default 1000
Step 1
3) CT# Pol
4) GCT# Pol
[ V OL T A GE S E NS I NG]
> V T CON- T y p e : WY E
V T 2 n d ( V ) : 4 . 0 0
V T Ra t i o : 3 3 0 0 . 0
1) VT CON-Type
2) VT 2nd(V)
3) VT Ratio
[ CONT ROL T Y PE ]
> 1 WA Y : CBT Y PE
2 WA Y : CBT Y PE
3 WA Y : CBT Y PE
4 WA Y : CBT Y PE
5 WA Y : CBT Y PE
6 WA Y : CBT Y PE
1) 1 WAY ~ 6 WAY
[ CB OP E N I N G T I ME ]
> T i me : 0 . 0 2 0
The CB Opening Time is set in this menu and time that CB completely opens is
calculated in following way.
Total CB Clearing Time = Relay Release Time + CB Trip Time(CB Opening Time + Arcing Time)
To apply TCC time to complete opening time, CB trip time shall be considered.
1) CB Opening Time
[ GA S S E NS OR T Y P E ]
> T y p e : NONE
1) Type
[ F I T Y PE S E L E CT ]
> T Y P E SE L E CT : I V
1) TYPE SELECT
Range IV, I
Default IV
Step -
6.5.1.2. COMMUNICATION
It moves to this menu if [ENT] key is pressed after locating cursor in “2.
COMMUNICATION” in ‘GLOBAL SETTING' menu. A variety of matters related to
communication are set here and it has following submenus.
[ C O MMU N I C A T I O N ]
> 1 . P ROT OCOL SE T UP
2 . P OR T SE T UP
3 . DI A L UP MO D E M
4 . A L A L OG E V E NT
5 . F T P F I L E T RANF E R
A. DNP3
ETR306 can be programmed for communication using DNP3 through
communication port1, port2 or port3.
[ DNP 3 ]
> F u n c t i o n : E NA BL E
COM Po r t : P ORT 1
D/ L C o n f i r m: S OME
D/ L F r a me D l y : 1 0 0
D/ L Re t r i e s : 0
D/ L T i me o u t : 1 0
A/ L T i me o u t : 1 5
Maa s t e r A d d r : 6 0 0 0 0
DNP Ad d r e s s : 1
SBO T i me : 1 5
I n i t Un s o l : E NA BL E
Un s o l T i me : 5
Un s o l T y p e : N OT R I G
Un s o l Re t r i e s : 0
Cl a s s 1 : E NA BL E
Cl a s s 2 : E NA BL E
Cl a s s 3 : E NA BL E
T CP/ UDP Se l e c t : T CP
T CP Po r t : 2 0 0 0 0
UDP Po r t : 2 0 0 0 1
Maa s t e r I P Oc t 1 : 1 9 2
Maa s t e r I P Oc t 2 : 1 6 8
Maa s t e r I P Oc t 3 : 7
Maa s t e r I P Oc t 4 : 2 0 2
K- Al v Ch e c k T m: 4
F r a g me n t S i z e : 2 0 4 8
T i me R e q ( m) : OF F
1) Function
2) COM Port
3) D/L Confirm
4) D/L FrameDly
5) D/L Retries
Range 0 ~ 2
Default 0
Step 1
Set number of retries that will be issued for a given data link layer.
6) D/L Timeout
Set waiting time between Data Link Frame transfer till to receive
Data Link Confirm(ACK) of Master. If there is no Data Link Confirm
receiving and Data Link retry is available, ETR306 will send Data Link
Frame again.
7) A/L Timeout
8) Master Address
Range 0 ~ 65534
Default 60000
Step 1
9) DNP Address
Range 0 ~ 65534
Default 1
Step 1
Range 0 ~ 60 sec
Default 5
Step 1 sec
Range NOTRIG/PERIOD
Default NOTRIG
Step -
Range 0 ~ 2
Default 0
Step 1
15) Class 1
Range TCP/UDP
Default TCP
Step -
Range 0 ~ 65535
Default 20000
Step 1
Range 0 ~ 65535
Default 20001
Step 1
Range 0 ~ 255
Default IP Oct1 : 192
IP Oct2 : 168
IP Oct3 : 7
IP Oct4 : 202
Step 1
Set time period that check communication connecting status during idle
status.
Range 64 ~ 2048
Default 2048
Step 1
B. IEC60870-5-101
ETR306 can be programmed for communication using IEC60870-5-101 through
communication port1, port2 or port3.
[ I E C6 0 8 7 0 - 5 - 1 0 1 ]
> F u n c t i o n : DI S ABL E
C OM P o r t : P OR T 1
A d d r e s s : 1
A SDU Ad d r : 0
Cy c l i c Pe r i o d : 6 0
E v e n t P e r i o d : 1 5
Re t r i e s : 0
Co n f . T i me o u t : 1 0
Ma x P o l l T i me : 1 0
A SDU Ad d r S i z e : 2
L i n k C o n f i r m: A L WA Y S
L i n k Ad d r S i z e : 1
Rx F r a me Si z e : 2 6 1
Rx F r a me T O: 1 5
T x F r a me Si z e : 2 6 1
C OT S i z e : 1
I OA S i z e : 2
On e Ch Re s p o n s e : NO
F r a me Re p e t ‘ T O: 3 0
S e l e c t T i me o u t : 5
C MD T e r mi n a t i o n : Y E S
CSE T e r mi n a t i o n : Y E S
Cl o c k S y n c ‘ E v t : Y E S
MS P T i me - T a g : CP 5 6
MI T T i me - T a g : CP 5 6
MME T i me - T a g : CP 5 6
F l t ‘ T i me - T a g : CP 5 6
1) Function
2) COM Port
3) Address
Range 1 ~ 65535
Default 1
Step 1
4) ASDU Addr
Range 0 ~ 65535
Default 0
Step 1
5) Cyclic Period
Range 1 ~ 60000
Default 60
Step 1
6) Event Period
Range 0 ~ 255 s
Default 15
Step 1 s
7) Retries
Range 1 ~ 255
Default 0
Step 1
8) Conf. Timeout
Range 1 ~ 255 s
Default 10
Step 1 s
Set wait time till receive Data Confirm (ACK) of master after transfer
data.
If there is not Confirm during this setting time and Data retries is
available, ETR306 transfers Data again.
Range 1~255 s
Default 10
Step 1 s
Range 1 ~ 2
Default 2
Step 1
Range 1 ~ 2
Default 1
Step 1
Range 0 ~ 261
Default 261
Step 1
14) Rx Frame TO
Range 0 ~ 261
Default 261
Step 1
Range 1 ~ 2
Default 1
Step 1
Range 1 ~ 3
Default 2
Step 1
Range NO/YES
Default YES
Step -
Range CP56/CP24
Default CP56
Step -
Select whether a time tag format for integrated totals.
CP56 : The time tag format is CP56Time2a.
CP24 : The time tag format is CP24Time2a.
Select whether a time tag format for measured value and normalized
C. IEC60870-5-104
ETR306 can be programmed for communication using IEC60870-5-104 through
communication port3.
[ I E C6 0 8 7 0 - 5 - 1 0 4 ]
> F u n c t i o n : DI S ABL E
C OM P o r t : P OR T 3
A SDU Ad d r : 0
Cy c l i c Pe r i o d : 6 0
T i me o u t ( t 0 ) : 1 2 0
T i me o u t ( t 1 ) : 1 5
T i me o u t ( t 2 ) : 1 0
T i me o u t ( t 3 ) : 2 0
E v e n t P e r i o d : 1 5
T CP P o r t No : 2 4 0 4
Rx F r a me Si z e : 2 5 5
T x F r a me Si z e : 2 5 5
S e l e c t T i me o u t : 5
C MD T e r mi n a t i o n : Y E S
CSE T e r mi n a t i o n : Y E S
Cl o c k S y n c ‘ E v t : Y E S
MS P T i me - T a g : CP 5 6
MI T T i me - T a g : CP 5 6
MME T i me - T a g : CP 5 6
F l t ‘ T i me - T a g : CP 5 6
1) Function
2) COM Port
Range PORT3
Default PORT3
Step -
3) ASDU Addr
Range 0 ~ 65535
Default 0
Step 1
4) Cyclic Period
Range 1 ~ 60000
Default 60
Step 1
5) Timeout(t0)
Range 1 ~ 255 s
Default 120
Step 1 s
6) Timeout(t1)
Range 1 ~ 255 s
Default 15
Step 1 s
7) Timeout(t2)
Range 1 ~ 255 s
Default 10
Step 1 s
8) Timeout(t3)
Range 1 ~ 255 s
Default 20
Step 1 s
Select Timeout for sending test frame in case of a long idle state.
9) Event Period
Range 0 ~ 255 s
Default 15
Step 1 s
Range 0 ~ 65535
Default 2404
Step 1
Range 0 ~ 255
Default 255
Step 1
Range 0 ~ 255
Default 255
Step 1
Select whether a time tag format for measured value and normalized
value for general event except for fault current event.
CP56 : The time tag format is CP56Time2a.
CP24 : The time tag format is CP24Time2a.
D. MODBUS
ETR306 can be programmed for communication using MODBUS through
communication port1, port2, port3.
[ MOD B U S ]
> F u n c t i o n : DI S ABL E
C OM P o r t : P OR T 3
T CP / UDP S e l e c t : T CP
T CP P o r t : 5 0 2
UDP P o r t : 2 0 0 0 1
S l a v e A d d r e s s : 1
T x De l a y : 0 . 0 5
1) Function
2) COM Port
3) TCP/UDP Select
4) TCP Port
Range 1 ~ 65535
Default 502
Step 1
5) UDP Port
Range 1 ~ 65535
Default 20001
Step 1
6) Slave Address
Range 1 ~ 254
Default 1
Step 1
7) Tx Delay
[ P OR T SE T UP]
> 1 . P OR T 1 ( 2 3 2 )
2 . P OR T 2 ( 4 8 5 )
3 . P OR T 3 ( E T HE R NE T )
4 . P OR T F ( 2 3 2 )
A. PORT1(232)
It moves to this menu if [ENT] key is pressed after locating cursor in "1.
PORT1(232)" in 'PORT SETUP' menu. The particulars related to communication
PORT1 located in ETR306 are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.
[ P OR T 1 ( 2 3 2 ) ]
> Ba u d Ra t e : 9 6 0 0
P a r i t y Bi t : NONE
Da t a Bi t : 8
S t o p Bi t : 1
Mo d e m S e l : 4 W
CT S Us a g e : E NABL E
DCD Us a g e : DI S ABL E
RT S Us a g e : AUT O
CT S C h e c k Ou t : 2
DCD C h e c k Ou t : 5 0 0 0
T X Pr e De l a y : 1 0
T X Po s t De l a y : 5 0
1) Baud Rate
2) Parity Bit
3) Data Bit
Range 7 ~ 8
Default 8
Step 1
4) Stop Bit
Range 1 ~ 2
Default 1
Step 1
5) Modem Sel
6) CTS Usage
7) DCD Usage
8) RTS Usage
9) CTS CheckOut
Set waiting time that waits Modems confirmation on RTS signal which
informs that ETR306 is ready to transfer a data. If there is no CTS
response within a set time, RTU confirms CTS Fail and does not
transfer data.
It is available if ‘CTS Usage’ setting is ON.
Set delay time of DCD signal check which determine modem status
before sending RTS signal in 2 wire communication type. After a set
time, if DCD signal is ON, ETR306 does not transfer data and treat it
as DCD Fail. It is available if ‘DCD Usage’ setting is ON.
11) TX PreDelay
12) TX PostDelay
B. PORT2(485)
It moves to this menu if [ENT] key is pressed after locating cursor in "2.
PORT2(485)" in 'PORT SETUP' menu. The particulars related to communication
PORT2 located in ETR306 are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.
[ P OR T 2 ( 4 8 5 ) ]
> Ba u d Ra t e : 9 6 0 0
P a r i t y Bi t : NONE
Da t a Bi t : 8
S t o p Bi t : 1
L i n e T y p e : RS4 2 2
CA De l a y : 1 . 0 0
2) Line Type
3) CA Delay
Set lag time until response data is transmitted after receiving data.
C. PORT3(ETHERNET)
It moves to this menu if [ENT] key is pressed after locating cursor in "3.
PORT3(ETHERNET)" in 'PORT SETUP' menu. The particulars related to
communication PORT3 located in ETR306 are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.
[ P OR T 3 ( E T HE R NE T ) ]
> I P Ad d r Oc t 1 : 1 9 2
I P Ad d r Oc t 2 : 1 6 8
I P Ad d r Oc t 3 : 7
I P Ad d r Oc t 4 : 2 1 2
Ga t e wa y Oc t 1 : 1 9 2
Ga t e wa y Oc t 2 : 1 6 8
Ga t e wa y Oc t 3 : 7
Ga t e wa y Oc t 4 : 1
S u b n e t Ma s k Oc t 1 : 2 5 5
S u b n e t Ma s k Oc t 2 : 2 5 5
S u b n e t Ma s k Oc t 3 : 2 5 5
S u b n e t Ma s k Oc t 4 : 0
K - A l v F u n c : E NABL E
K - A l v I d l e T O: 4
K - A l v Re t r y : 3
1) IP Addr Oct1 ~ 4
Range 0 ~ 255
Default IP Oct1 : 192
IP Oct2 : 168
IP Oct3 : 7
IP Oct4 : 212
Step 1
2) Gateway Oct1 ~ 4
Range 0 ~ 255
Default Gateway Oct1 : 192
Gateway Oct2 : 168
Gateway Oct3 : 7
Gateway Oct4 : 1
Step 1
Range 0 ~ 255
Default Subnet Mask Oct1 : 192
Subnet Mask Oct2 : 168
Subnet Mask Oct3 : 7
Subnet Mask Oct4 : 212
Step 1
4) K-Alv Func
5) K-Alv Idle TO
6) K-Alv Retry
Range 0 ~ 255
Default 3
Step 1
D. PORTF(232)
It moves to this menu if [ENT] key is pressed after locating cursor in "4.
PORTF(232)" in 'PORT SETUP' menu. The particulars related to communication
PORTF located in ETR306 are set in this menu.
The set value alteration process is identical to "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE” .
[ P OR T F ( 2 3 2 ) ]
> Wi r e l e s s : DI S ABL E
S l a v e A d d r : 1
Ma s t e r Ad d r : 0
Ba u d Ra t e : 3 8 4 0 0
Mo d e m S e l : 4 W
CT S Us a g e : E NABL E
DCD Us a g e : DI S ABL E
RT S Us a g e : AUT O
CT S C h e c k Ou t : 2
DCD C h e c k Ou t : 5 0 0 0
RT S Of f De l a y : 5 0
1) Wireless
2) Slave Address
Range 0 ~ 65534
Default 1
Step 1
3) Master Address
Range 0 ~ 65534
Default 0
Step 1
4) Baud Rate
[ DI AL UP MOD E M]
> 1 . CAL L I NG S T RI NG
2 . CAL L I NG N U MB E R
3 . I NI T I AL S T RI NG
4 . C ON NE CT I ON
1) CALLING STRING
Range !~Z
Default ATD
Step -
Set to use Dial-Up modem use. Select a dial string one among them.
2) CALLING NUMBER
Range !~Z
Default -
Step -
3) INITIAL STRING
Range SPACE~Z
Default AT&C1 Q1 E0 M0 &D2 + CRM = 129
Step -
4) CONNECTION
[ CONN E C T I ON ]
> C md Re s ‘ T O: 2
Co n n e c t T O: 3 0
I d l e T i me : 6 0
① Cmd Res’ TO
Range 0~255 s
Default 2
Step 1 s
② Connect TO
Range 0~255 s
Default 30
Step 1 s
③ Idle Time
Range 0~255 s
Default 60
Step 1 s
[ A NA L OG E V E NT ]
> AI E v t Me t h o d : OF F
AE v t S k i p a t F t : NO
Da i l y Ma x I : E NA BL E
F l t ‘I’ E v t : 1 S HOT
Av e r L o a d Ca l c T : 1 5
BI Qu e u e s i z e : 2 5 6
BI E v t Mo d e : AL L
AI Qu e u e s i z e : 2 5 6
AI E v t Mo d e : AL L
CI Qu e u e s i z e : 2 5 6
CI E v t Mo d e : AL L
T i me S y n’ Re f : L OCA L
T i me T a g T y p e : L OCA L
1) AI Evt Method
Threshold value.
DB : AI Event is occurred when AI data change value is over
deadband value.
BOTH : TH and DB all used.
Use ETR306 interface program to setting “Event Active” activation or
deactivation of AI point, Threshold value and Deadband value.
2) AEvt Skip at Ft
3) Daily Max I
6) BI Queue size
7) BI Evt Mode
8) AI Queue size
9) AI Evt Mode
Set reference time type. It signifies the time data type when Time
Synchronizing with the master station.
[ F T P F I L E T ANSF E R
> F T P Mo d e - R : DNP
F T P M o d e - W: DNP
F T P De v : PA D
F T P De v . No : CB0 0 1
F T P I D: E NT E C
F T P P W: 1 2 3 4
F T P P a s s i v e : DI S ABL E
1) FTP Mode-R
2) FTP Mode-W
3) FTP Dev
Range SPACE~z
Default PAD
Step -
4) FTP Dev.NO
Range SPACE~z
Default CB001
Step -
5) FTP ID
Range SPACE~z
Default ENTEC
Step -
6) FTP PW
Range SPACE~z
Default 1234
Step -
7) FTP Passive
[ E V E NT R E C OR DE R ]
> Wa v e Ca p t u r e : ON
Wa v e S/ R: 3 2
Wa v e Pr e - Cy c l e : 5
Wa v e Po s t - Cy c l e : 5
Wa v e He a d - Cy c l e : 5
Wa v e Ca p t u r e Wa y : 1
1) Wave Capture
2) Wave S/R
3) Wave Pre-Cycle
Range 1 ~ 10 cycle
Default 5
Step 1 cycle
4) Wave Post-Cycle
Range 1 ~ 10cycle
Default 5
Step 1 cycle
5) Wave Head-Cycle
Range 1 ~ 10 cycle
Default 5
Step 1 cycle
6.5.1.4. MONITORING
It moves to this menu if [ENT] key is pressed after locating cursor in "4.
MONITORING" in 'GLOBAL SETTING' menu.
[ MON I T OR I N G]
> 1 . BAT T E RY T E S T
2 . T D MO N I T O R
[ BA T T E RY T E ST ]
> P e r i o d : 2 4
1) Period
(2) TD MONITOR
It moves to this menu if the [ENT] key is pressed after locating the cursor in
"2. TD MONITOR" in the 'MONITORING' menu. It sets about the transducer that
can be used as a DC analog input monitoring usage in the menu. The set value
alteration process is identical to "MAIN MENU(COM)/ GLOBAL SETTING/
SYSTEM/ POWER LINE” 's alteration process.
[ T D MO N I T O R ]
> T D1 Ra t e : 4 0
T D1 Ra t i o : 1
T D1 Of f s e t : + 0
T D1 - 1 T y p e : UNDE R
T D1 - 1 P U: 2 3 . 0
T D1 - 1 De l a y : 0 . 5 0
T D1 - 2 T y p e : UNDE R
T D1 - 2 P U: 2 1 . 0
T D1 - 2 De l a y : 0 . 5 0
T D2 Ra t e : 4 0
T D2 Ra t i o : 1
T D2 Of f s e t : + 0
T D2 - 1 T y p e : UNDE R
T D2 - 1 P U: OF F
T D2 - 1 De l a y : 0 . 5 0
.
..
T D4 - 2 T y p e : UNDE R
T D4 - 2 P U: OF F
T D4 - 2 De l a y : 2 . 0 0
1) TD1 Rate
Range 1 ~ 200
Default 40
Step -
2) TD1 Ratio
Range 1 ~ 3000
Default 1
Step 1
3) TD1 Offset
4) TD1-1 Type
5) TD1-1 PU(V)
6) TD1-1 Delay
7) TD1-2 Type
8) TD1-2 PU(V)
9) TD1-2 Delay
6.5.1.5. PLC
It moves to this menu if [ENT] key is pressed after locating cursor in "5. PLC"
in 'GLOBAL SETTING' menu.
[ P L C]
> 1 . C OMMO N
2 . DI / DO
(1) COMMON
It moves to this menu if [ENT] key is pressed after locating cursor in "1.
COMMON" in 'PLC' menu.
[ C O MMON ]
> 1 . L OGI C T I ME R
2 . P UL SE T I ME R
3 . P UL SE C OU NT E R
A. LOGIC TIMER
It moves to this menu if [ENT] key is pressed after locating cursor in "1. LOGIC
TIMER" in 'COMMON' menu. The set value alteration process is identical to
"MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE” .
[ L OGI C T I ME R ]
> T M1 - P U : 0 . 0 1
T M1 - D O: 0 . 0 1
T M2 - P U : 0 . 0 1
T M2 - D O: 0 . 0 1
.
..
T M1 6 - P U : 0 . 0 1
T M1 6 - D O : 0 . 0 1
TM□
X
A B
Y
0s/0s
<Figure 6-4> Logic Timer Symbol
1) TM1-PU
2) TM1-DO
B. PULSE TIMER
It moves to this menu if [ENT] key is pressed after locating cursor in "2.
PULSE TIMER" in 'COMMON' menu. The set value alteration process is identical
to "MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE” .
[ P UL SE T I ME R ]
> P T M1 : 0 . 0 1
P T M2 : 0 . 0 1
P T M3 : 0 . 0 1
.
.
.
P T M1 6 : 0 . 0 1
PTM□
A B
Y
0s
<Figure 6-5> Pulse Timer Symbol
1) PTM1
C. PULSE COUNTER
It moves to this menu if [ENT] key is pressed after locating cursor in "3.
PULSE COUNTER" in 'COMMON' menu. The set value alteration process is
identical to "MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE” .
[ PUL S E COUNT E R]
> P C1 : 1 0 0 0
P C2 : 1 0 0 0
P C3 : 1 0 0 0
.
.
.
P C1 6 : 1 0 0 0
1) PC1
Range 1 ~ 60000
Default 1000
Step 1
(2) DI/DO
It moves to this menu if [ENT] key is pressed after locating cursor in "2.
DI/DO" in 'PLC' menu.
[ DI / DO]
> 1 . I NP UT DE B OU NC E
2 . OUT P UT PUL S E T I ME
A. INPUT DEBOUNCE
It moves to this menu if [ENT] key is pressed after locating cursor in "1.
INPUT DEBOUNCE" n 'DI/DO' menu. The set value alteration process is
identical to "MAIN MENU(COM)/ GLOBAL SETTING/ SYSTEM/ POWER LINE”.
[ I NP UT DE B OU NC E ]
> I N1 0 1 : 0 . 0 2 0
I N1 0 2 : 0 . 0 2 0
I N1 0 3 : 0 . 0 2 0
.
..
I N1 0 8 : 0 . 0 2 0
I N2 0 1 : 0 . 0 0 5
..
.
I N2 2 4 : 0 . 0 2 0
IN□
X
A B
X
0s
<Figure 6-7> Input Debounce Timer Symbol
1) IN101
[ OU T P UT P UL SE T I ME ]
> OUT 1 0 1 : 0 . 0 1
OUT 1 0 2 : 0 . 0 1
OUT 1 0 3 : 0 . 0 1
.
.
.
OUT 1 0 8 : 0 . 0 1
OUT 2 0 1 : 0 . 1 0
.
..
OUT 2 1 2 : 0 . 0 3
OUT□
A
Y C
B R
0s
<Figure 6-8> Output Pulse Timer Symbol
1) OUT101
6.5.1.6. OTHERS
It moves to this menu if [ENT] key is pressed after locating cursor in "6.
OTHERS" in 'GLOBAL SETTING' menu.
[ OT HE R S ]
> 1 . F A CT ORY DE BUG
[SAVE SETTING]
NOTE )
* ABORT *
The altered values have to be saved to take
④ effect. If saving is cancelled, previous values are
maintained.
* NOTHING CHANGED *
6.5.2. EVENT
It moves to this menu if [ENT] key is pressed after locating cursor in "2.
EVENT RECORDER" in 'MAIN MENU(COM)' menu.
ETR306 periodically checks event that happens during operation and records
events occurred by classifying them into operation event, fault event, system
event, set value alteration event, load event and diagnosis event. All event
record uses circulating record that records events above recording capacity in
oldest event location. Events related to ETR306 system can be checked and
erased in this menu.
[ E V E NT ]
> 1 . S Y S T E M
2 . S E T CHA NGE
3 . DI GNOS T I C
4 . CL E AR S AV E D DAT A
This menu has submenus like following and can move to selected submenu using
[ENT] key.
6.5.2.1. SYSTEM
The system event records up to 2048 events max.
Can check record using [▼][▲] keys. [001/2048] is latest event recorded.
Trigger Source
FI detection element
52A contact point
Front panel control
AC power supply
External control
External input condition
System warning
NOTE )
Refer to “APPENDIX C. LOGIC BIT ATTRIBUTES & DESCRIPTION” for
more details about trigger source.
Saving Method
Record in case of event occurrence(HI/ASSERT) or extinction(LO/DEASSERT).
Trigger Time
Every 1/4 cycle
Saving Capacity
Save maximum 2048 events.
Move to the “MAIN MENU(COM)/ EVENT/ SET CHANGE” menu to check the
setting value alteration event.
Can check the record using the [▼][▲] keys. [001/100] is the latest event
recorded.
Trigger Source
Changed set value menu
- GLOBAL SETTING
- PRIMARY SETTING
- ALTERNATE SETTING
Alteration method
- LOCAL : Change the set value in local.
- REMOTE : Change the set value in remote.
- PROGRAM : Set value changed using the application program.
Saving Method
Record in case of changing the set value.
Trigger Time
Every 5msec
Saving Capacity
Save up to 100 events max.
Can check the record using the [▼][▲] keys. [001/512] is the latest event
recorded.
Trigger Source
System power : AC power, battery, ±12V, +5V(SYSTEM POWER : AC,
Battery, ±12V, +5V)
A/D conversion : A/D fault, standard voltage 1, standard voltage 2(A/D
Conversion : A/D Fail, Reference Voltage1, Reference Voltage 2)
SLEEP MODE
POWER DOWN MODE
NOTE )
Refer to “APPENDIX C. LOGIC BIT ATTRIBUTES & DESCRIPTION” for
more details about trigger source.
Saving Method
Record in case of event occurrence(HI/ASSERT) or extinction(LO/DEASSERT).
Trigger Time
Every 5msec
Saving Capacity
Save up to 512 events max.
[EVENT CLEAR]
4. ABOVE ALL
EVENT CLEAR SUCCESS
Clear all data from item 1 ~ 3.
6.5.3. MAINTENANCE
It moves to this menu if [ENT] key is pressed after locating cursor in "3.
MAINTENANCE" in 'MAIN MENU(COM)' menu.
This menu shows maintenance information of ETR306 and multi-way of
switchgear breaker and this menu shows information about ETR306's common
factor. This menu has following submenus and can move to selected submenu
using [ENT] key.
[ MA I N T E N A N CE ]
> 1 . C OU NT
2 . DAT A RE SE T
3 . CCU I NF O
6.5.3.1. COUNT
This menu indicates counter information about ETR306's common factors and has
following submenus. Can move to selected submenu using [ENT] key.
[ C OU NT ]
> 1 . CCU
(1) CCU
Move to “MAIN MENU(COM)/ MAINTENANCE/ COUNT/ CCU" menu to check
ETR306 counter.
[CCU] RESTART
RESTART: 30
DIAGNOSTIC: 0 Indicate the number of restarted ETR306.
DIAGNOSTIC
Indicate the number of self diagnosis error detection.
6.5.4. TIME
It moves to this menu if [ENT] key is pressed after locating cursor in "4. TIME"
in 'MAIN MENU(COM)' menu.
6.5.5. STATUS
It moves to this menu if [ENT] key is pressed after locating cursor in "5.
STATUS" in 'MAIN MENU(COM)' menu. This menu has following submenus and
can move to selected submenu using [ENT] key.
[ S T A T US]
> 1 . CCU
2 . I NP UT P OR T S
3 . OUT P UT P ORT S
6.5.5.1. CCU
Can be checked by moving to “MAIN MANU(COM)/ STATUS/ CCU” menu.
BATTERY
Battery status is displayed. (NORMAL, FAIL)
BAT’ CHARGER
Battery charger status is displayed. (NORMAL, FAIL)
DOOR
Door status is displayed. (OPEN, CLOSE)
DNP ADDRESS
ETR306 DNP set address is displayed(0~65535).
MASTER ADDR
DNP host initial address
(0~65534:65535 is used for Broadcast)
GAS
Circuit breaker gas pressure status is displayed.
(NORMAL, LOW)
6.5.6. METERING
It moves to this menu if [ENT] key is pressed after locating cursor in "6.
METERING" in 'MAIN MENU(COM)' menu. In this menu, It indicates present
measurement value about common factors and it has following submenus. Can
move to selected submenu using [ENT] key.
[ ME T E R I N G ]
> 1 . F R E QU E N CY
2 . T D
3 . CCU RE F
6.5.6.1. FREQUENCY
Can be checked by moving to “MAIN MANU(COM)/ METERING/ FREQUENCY”
menu.
6.5.6.2. TD Monitoring
Can be checked by moving to “MAIN MANU(COM)/ METERING/ TD
MONITORING” menu. It sets about the transducer that can be used as a DC
analog input monitoring usage in the menu.
[ MA I N ME N U ] 1 W
> 1 . GR OUP SE T T I NG
2 . MON I T OR I N G SE T
3 . E V E NT
4 . MA I N T E N A N C E
5 . ST AT UE
6 . ME T E R I N G
[ GR OUP S E T T I NG]
> 1 . P R I MA R Y
2 . AL T E RNAT E
3 . ACT I V E GR OUP
[ P R I MA R Y S E T T I NG]
> 1 . P I CKUP CURRE NT
2 . I NRUS H RE ST RA I NT
3 . DI R E C T I ON
4 . F . I S E T T I NG T I ME
5 ON/ OF F L E V E L
6 . P HA S E DI F F
7 . L I V E L I NE
* . S AV E SE T T I NG
[ P I CKUP CURRE NT ]
> P h a s e : 4 0 0
Gr o u n d : 7 0
1) Phase
2) Ground
[ I NRUSH RE S T RAI NT ]
> P H A - T i me : 0 . 2
G N D - T i me : 0 . 2
P HA - Mu l t i : 4
GN D - Mu l t i : 4
1) PHA-Time
2) GND-Time
3) PHA-Multi
Range 1 ~ 20
Default 4
Step 1
4) GND-Multi
Range 1 ~ 20
Default 4
Step 1
(3) DIRECTION
It moves to this menu if [ENT] key is pressed after locating cursor in “3.
DIRECTION” in group menu. At this menu, fault direction detection settings are
set and has menu as shown below.
[ DI R E C T I ON ]
> 1 . P HA S E
2 . GROUND
A. PHASE
It moves to this menu if [ENT] key is pressed after locating cursor in “1.
PHASE" in 'DIRECTION' menu. At this menu, direction detection settings of phase
fault are set and has menu as shown below.
[ P HA S E ]
> T y p e : DI S ABL E
M. T . A ( V 1 ) : 6 0
M. P . V : 1 0
The direction distinction of phase fault current use normal voltage(V1) and
normal current(I1) of symmetry, and operation are as following.
Polarizing Referance V1
Voltage:
Ze
ro
I1 M.T.A= 60˚ Lag
T
orq
e
Lin
ue
e
rqu
Lin
To
m
e
u
xim
Ma
FO
RW
O
RE
RD
VE
RS
E
1) Type
2) M.T.A(V1)
3) M.P.V
B. GROUND
It moves to this menu if [ENT] key is pressed after locating cursor in “2.
GROUND" in 'DIRECTION' menu. At this menu, direction detection settings of
ground fault are set and has menu as shown below.
[ GR OU ND]
> T y p e : DI S ABL E
M. T . A ( - V 0 ) : 6 0
M. P . V : 1 0
Directional Detection of Ground fault current use Zero Seq. Voltage(V0) and
Zero Seq. Current(I0).
IF phase angle of I0 about –V0 is within ±90° based on Max. Torque Angle is
Forward, if not is Reverse.
To operates in direction, 3V0 detected in fault status shall be bigger than min.
polarizing voltage. If 3V0 is smaller than each element setting does not detect
direction, even fault current are over min. pickup current setting value.
1) Type
2) M.T.A(-V0)
3) M.P.V
Polarizing Referance
-V0
Voltage:
FO
R
W
O
R
R D
EV
ER
SE
V0
[ F . I SE T T I NG T I ME ]
> P e r ma n e n t : 2 0
T e mp o r a r y : 2
T y p e I d e l a y : 0 . 0 3
Voltage
Pickup Level
Current
Temporary
FI SETTING TIME
Permanent
FI SETTING TIME
CLEAR
Temporary FI
Permanent FI
AUTO
FI SET RESET
Permanent Fault
Occurrence Condition
FI information is set when becomes dead line status after fault current over the
minim. pickup current flowed in live line status, and set the fault type in FI if
dead line status is maintained during setting time (permanent FI Set Time,
1sec~180sec possible to change, Default: 20 second). But, when returns to live
line status by reclosing before the permanent FI Set Time, FI Set Time is
initialized and returned to the first permanent FI occurrence condition.
Clear Condition
It is cleared by Fault indicator reset button or remote FI reset button.
P.C
Permanent
N.C FI Set Time
0.6s 2s 15s
① ② ③ ④ ⑤
FI Occurrence(A,N) FI Occurrence(B) Permanent FI Occurrence
Fault Current(A,B,C,N)
선 VOLTAGE
로 전 압
P IFI
CK PICKPU
UP치
선CURRENT
로 전 류
TEMPORARY
순 간
F I S E T FI
T I SET
N G TIME
T IM E
일 시
PERMANET
F I S E T TFII NSET
G TIME
T IM E
C LEAR
순TEMPORARY
간 FI FI
FI SET
일PERMANENT
시 FI FI
TEMPORARY
순 간 고 FAULT
장
Occurrence Condition
When fault current over the setting value flows and then becomes dead line, FI
event is occurred. If it becomes normal current in live line status by reclosing in
source side, after the setting time (Temporary FI Set Time, 1 sec~180sec
variable Default:2sec) Temporary FI is occurred.
Clear Condition
It is cleared by Fault indicator reset button or remote FI reset button.
③
0.6s 2s Temporary FI
Occurrence
① ②
FI Occurrence(A,N) FI Occurrence(B)
Fault Current(A,B,C,N)
C. ‘I' Type
Occurrence Condition
In case of I type for TYPE SELECT, FI is occurred regardless of voltage status,
if fault current higher than FI pickup current continues to flow during setting
time (Type I delay Set Time, 0.03 sec~180sec variable Default: 0.03sec).
Clear Condition
It is cleared by Fault indicator reset button or remote FI reset button.
FI PICKUP
NORMAL
CURRENT
FI DELAY TIME
CLEAR
FI
FI SET
A,N
P.C
N.C
Type I delay
Set Time
①
FI Occurrence(A,N)
Fault Current(A,B,C,N)
If fault current keeps during the setting time(Type I delay Set Time), FI is
occurred(①).
Fault current size is the max. RMS value during the setting time.
※. If the "Fault 'I' Report - Event Set" setting is "1Shot", Fault current Event
is occurred at first fault only.
This is cleared by “FI Reset" command and “FI occurrence“ events are
cleared.
1) Permanent
Range 1 ~ 180sec
Default 20
Step 1sec
2) Temporary
Range 1 ~ 180sec
Default 2
Step 1sec
3) Type I delay
[ ON / OF F L E V E L ]
> On L e v e l : 0 . 8 0
Of f L e v e l : 0 . 5 0
De t e c t T i me : 0 . 0
1) On Level
2) Off Level
3) Detect Time
[ P HA S E DI F F ]
> L e v e l : 3 0
T i me : 1 . 0
If one or two of two way of switchgears that are in a live line condition is
above set angle when voltage phase to phase is compared in an open condition
by them, it is judged as phase difference.
The one that is standard from two way of switchgears is way of switchgear
close to way of switchgear 1 or input way of switchgear. The standard way of
switchgear does not detect(indicate) phase difference. The phase difference
status immediately returns when phase difference gets below set value or one of
two way of switchgears becomes dead line.
1) Level
2) Time
[ L I V E L I NE ]
> L i v e L i n e L v : 0 . 3 0
L i v e L i n e T m: 4 . 0
1) Live Line Lv
Set live line level and this is set in multiple of previous rating.
2) Live Line Tm
[ P R I MA R Y S E T T I NG]
>1 . 5 1 P : T I M E OC - P HA
2 . 5 1 G: T I ME OC - GND
3 . 5 0 P : I NS T ' OC - P HA
4 . 5 0 G: I NS T ' OC - GND
5 . C OL D L OA D P I CKUP
6 . DI R E C T I ON
7 . USE R CURV E
8 . R E CL OS I NG( 7 9 )
9 . ON/ OF F L E V E L
1 0 . PHAS E DI F F
1 1 . L I V E L I NE
* . S AV E SE T T I NG
curve option is also available allowing the user to create customer time current
curves for more enhanced coordination than the standard curve types.
Two methods of this resetting operation are available, Instantaneous and Linear.
The Instantaneous selection is intended for applications with other relays, such
as most static units, which set the energy capacity directly to zero when the
current falls below the reset threshold. The Linear selection can be used where
the relay must coordinate with electro-mechanical units.
If the circuit breaker is closed by pressing the [CLOSE] button on the front
panel, or by an remote control or via SCADA, the phase time overcurrent
element is prevented from tripping for a period specified by the Cold load pickup
scheme.
The phase time overcurrent element setting factors are as follows. It moves to
this menu if [ENT] key is pressed after locating cursor in “1. 51P:TIME
OC-PHA" in group setting menu.
[ 5 1 P 1 : T I ME OC - P HA ]
> P i c k u p : 4 0 0
Cu r v e : [ N1 ]
T i me Di a l : 1 . 0 0
T i me Ad d r : 0 . 0 0
M. R . T : 0 . 0 0
Re s e t Me t h o d : I NST
1) Pickup
2) Curve
Curve A(101) B(117) C(133) D(116) E(132) IEC-EI K(162) L(107) M(118) N(104)
Setting 11 12 13 14 15 16 17 18 19 20
Curve IEC-NI P(115) R(105) T(161) V(137) IEC-VI W(138) Y(120) Z(134) 1(102)
Setting 21 22 23 24 25 26 27 28 29 30
Curve 2(135) 3(140) 4(106) 5(114) 6(136) 7(152) 8(113) 8*(111) 9(131) 11(141)
Setting 31 32 33 34 35 36 37 38 39 40
Setting 41 42 43 44 45 46 47 48 49 50
Curve ANSI-VI ANSI-EI ES-NI ES-VI USER-1 USER-2 USER-3 USER-4 DEF-1S DEF-10S
3) Time Dial
4) Time Addr
5) M.R.T
6) Reset Method
[ 5 1 G1 : T I ME OC - GND]
> P i c k u p : 7 0
Cu r v e : [ N1 ]
T i me Di a l : 1 . 0 0
T i me Ad d r : 0 . 0 0
M. R . T : 0 . 0 0
Re s e t Me t h o d : I NST
1) Pickup
2) Curve
3) Time Dial
4) Time Addr
5) M.R.T
6) Reset Method
[ 5 0 P 1 : I NS T ' OC - P HA ]
> P i c k u p : 3 5 0 0
T i me De l a y : 0 . 0 0
The phase high current trip element setting factors is as follows and shall move
to "MAIN MENU/ GROUP SETTING/ PRIMARY or ALTERNATE/ 3. 50P: INST'
OC-PHA" in order to set phase high current trip element.
1) Pickup
2) Time Delay
[ 5 0 G1 : I NS T ' OC - GND]
> P i c k u p : 1 7 5 0
T i me De l a y : 0 . 0 0
The ground high current trip element setting factors are as follows and shall
move to "MAIN MENU/ GROUP SETTING/ PRIMARY or ALTERNATE/ 4. 50G1:
INST' OC-GND" in order to set ground high current trip element.
1) Pickup
2) Time Delay
[ COL D L OA D PI CK UP ]
> P H A ( x MT C ) : 4
G N D ( x MT C ) : 6
R MT T i me - P H A : 0 . 3 0
R MT T i me - G N D : 0 . 3 0
RST T i me - P H A : 3 . 0 0
RST T i me - G N D : 3 . 0 0
The cold load pickup function is operated to prevent TRIP from overcurrent
elements when an inrush current occurs during manual closing by local/remote
control. The setting values of Cold Load Pickup function for phase, ground
overcurrent elements can be programmed separately.
If pickup level of overcurrent occurring at closing is over cold load pickup
current, trip is done by overcurrent function (Refer Inrush Current 1 in “<Figure
6-17> The Restore Minimum Time Characteristic”).
If overcurrent is below cold load pickup current and overcurrent pickup current,
overcurrent functions are not operated during a period of Restore minimum
Time(RMT)(Refer Inrush Current 2 in “<Figure 6-17> The Restore Minimum
Time Characteristic”). After RMT, overcurrent functions are operated. However,
if current is dropped below overcurrent pickup current during RMT, cold load
pickup function is reset after reset time(Refer Inrush Current 3 in “<Figure
6-17> The Restore Minimum Time Characteristic”).
Current
Inrush current 1
CLPU Trip
Pickup Level
Inrush current 2
Trip
Overcurrent
Pickup Level
Inrush current 3
Time
1) PHA(xMTC)
Range 0(OFF), 1 ~ 10
Default 4
Step 1
2) GND(xMTC)
Range 0(OFF), 1 ~ 10
Default 6
Step 1
3) RMT Time-PHA
4) RMT Time-GND
5) RST Time-PHA
6) RST Time-GND
(6) DIRECTION
It moves to this menu if [ENT] key is pressed after locating cursor in “6.
DIRECTION” in group menu.
If directional controls are selected, it will determine whether current flow in each
phase is in forward or reverse direction, as determined by the connection of the
phase CTs, selected Maximum Torque Angle (MTA), voltage and current phasors.
To increase security of all directional controls, add one power frequency cycle of
intentional delay to prevent incorrect operation.
The directional controls have each four settings. The directional controls settings
can be different in the Primary and Alternate settings.
[ DI R E C T I ON ]
> 1 . P HA S E
2 . GROUND
A. PHASE
It moves to this menu if the [ENT] key is pressed after locating the cursor in
“1. PHASE" in the 'DIRECTION' menu. This setting is applied in the directivity
phase overcurrent protection element.
[ P HA S E ]
> T y p e : NONE
M. T . A ( V 1 ) : 6 0
M. P . V : 1 0
Bl o c k OC: NO
If the I1's phase about V1 is within ±90° with the maximum torque angle as a
reference, it is judged as forward direction and if not, it is judged as reverse
direction.
The V1 value can be lost in case of fault occurrence in the voltage
measurement rootlet. At that moment, perform the direction differentiation for
a maximum of 1 seconds using the V1 recorded before. After that, it will be
decided whether it will be operated with overcurrent or not according to the
Block OC's set value.
In order to operate with directivity, the V1 detected in a fault condition
should be above the set minimum polarizing voltage(M.P.V). In other words,
even if the phase fault current is above the pickup current, it will not operate
if V1 is below the set value(M.P.V). Only, it can be operated with only the
overcurrent according to the setting.
Polarizing Referance V1
Voltage:
Ze
e
Lin
ue
r que
Lin
To
um
e
x i m
Ma
FO
RW
OR
RE
D
VE
RS
E
Setting
Block OC
(No or Yes)
AND
OverCurrent
Direction
Permission
V1 Blocking
-
Setting
+
MPV
Operation Enable
If V1 < MPV, Forward
Memorized V1 is used or
Reverse OR
for maximum 1 second
Update
V1 Memory
AND
Direction Determine
I1 Forward = MTA-90° < Θ <MTA+90°
Reverse = MTA+90° < Θ <MTA-90° Forward
Setting AND
or
MTA
Reverse
Setting None
Direction direction
(Forward or Reverse)
Setting
Direction
(None)
1) Type
2) M.T.A(V1)
3) M.P.V
4) Block OC
B. GROUND
It moves to this menu if the [ENT] key is pressed after locating the cursor in
“2. GROUND" in the 'DIRECTION' menu. This setting is applied in the directivity
ground overcurrent protection element.
[ GR OU ND]
> T y p e : NONE
M. T . A ( - V 0 ) : 6 0
M. P . V : 3 0
Bl o c k OC: NO
If the I0's phase about -V0 is within ±90° with the maximum torque angle as
a reference, it is judged as forward direction and if not, it is judged as
reverse direction.
The 3V0 value can be lost in case of fault occurrence in the voltage
measurement rootlet. At that moment, perform the direction differentiation for
a maximum of 1 seconds using the 3V0 recorded before. After that, it will be
decided whether it will be operated with overcurrent or not according to the
Block OC's set value.
In order to operate with directivity, the 3V0 detected in a fault condition
should be above the set minimum polarizing voltage(M.P.V). In other words,
even if the ground fault current is above the pickup current, it will not
operate if 3V0 is below the M.P.V set value. Only, it can be operated with
only the overcurrent according to the setting.
Polarizing Referance
-V0
Voltage:
In
ro
ne
To
Li
rq
ue
ue
rq
Li
To
ne
um
im
ax
M
FO
RW
O
RD
RE
VE
RS
E
V0
1) Type
2) M.T.A(-V0)
3) M.P.V
4) Block OC
[ USE R CURV E ]
> 1 . USE R CURV E 1
2 . USE R CURV E 2
3 . USE R CURV E 3
4 . USE R CURV E 4
This menu has submenus like above and moves to submenu selected using
[ENT] key.
The user curve setting menu is composed of following sub items. Refer to
"APPENDIX A. TIME CURRENT CURVES” for detailed content. The set value
changing step is identical to changing step of "MAIN MENU(COM)/ GLOBAL
SETTING/ SYSTEM/ POWER LINE”.
[ USE R CURV E 1 ]
> F a c t o r a : 0 . 0 5 1 5
F a c t o r b : 0 . 0 2 0 0
F a c t o r r : 0. . 1 1 4 0
F a c t o r r t : 4 . 8 5 0 0
1) Factor a
Range 0 ~ 150.9999
Default 0.0515
Step 0.0001
2) Factor b
3) Factor r
Range 0 ~ 150.9999
Default 1.8000
Step 0.0001
4) Factor rt
Range 0 ~ 150.9999
Default 59.5000
Step 0.0001
The default curve factors for USER CURVE 1~4 match with its IEEE standard
curve; IEEE Moderately Inverse, Very Inverse, Extremely Inverse and Long-Time
Extremely Inverse Curve, respectively. The default curve factors for USER
CURVE 1~4 are described in "[Table 6-6] User defined curve Default value".
[ R E CL OS I NG( 7 9 ) ]
> 1 . F UNCT I ON
2 . OP E R A T I ON S
3 . I NT E RV A L S
ETR306 has Auto Reclosing(79) function that electrical power system can be
rapidly tripped when line fault is occurred, circuit breaker can be reclosed after
a given interval (reclosing interval). In case of temporary fault caused by
momentary contact of extraneous substance, lightning or loss of insulation and so
on, range of fault and outage time can be minimized by this reclosing function.
After a fault has occurred, the Reclose element closes the recloser when the
programmed reclose interval time expires. The number of operation lockout
setting is programmed one to four, and each reclose shot has its own separate
reclose interval timer.
If the fault is permanent and the recloser continues to trip and reclose, the
Reclose element will continue to increment the operating counter. If this
continues to the maximum number of the operating lockout programmed in the
Reclose element, the reclose logic lockouts. At this moment, if make close
operation remotely or locally, Lockout is released and fault detecting is activated.
Also, if the fault is temporary, the Lockout sequence of the Recloser is Rest by
Reset logic. If the fault is transient, then the reclose logic is reset by the reset
logic.
Auto reclosing sequence operation status is displayed on the LEDs of ‘79 Reset’,
‘79 Cycle’ and ‘79 Lockout’ as follows.
LOCKOUT
Following cases are occurred to lockout. Due to the fact that auto reclosing does
not function in lockout status, circuit breaker should be closed to control locally
or remotely.
(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC (6) 3rd Reclose Interval Time
(7) 4th Trip - 4th TCC
RESET
RESET is displayed on back to normal status, following cases are occurred to
reset.
Lockout ➜ Reset : lockout reset time elapses after circuit breaker manually
or remotely operates to trip.
Cycle ➜ Reset : auto reset time elapses after returning to normal status from
reclosing sequence for temporary fault.
(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC (6) 3rd Reclose Interval Time
If fault occurs again during auto reset time duration, reclosing operation proceeds
to Lockout after remaining operations except count the number of times the
previous operation.
CYCLE
It displays sequence operating. Cycle is activated to trip operation of overcurrent
protection and keeps whenever total trip count reaches to the preset total
number of operation. Cycle performs that the Reclose element closes the
recloser when the programmed reclose interval time expires. (only the Cycle
condition occurs when Auto Reclosing function is enabled).
At this menu, set reclosing function and its menu is as shown below.
A. FUNCTION
It sets reclosing function is used or not. If the function is disable, general
functions of circuit breaker are applied to CB type for relevant way of
switchgear. If the function is enable, general functions of recloser are applied to
CB type for relevant way of switchgear.
1) Function
B. OPERATIONS
This setting is used to change the total number of phase/ground overcurrent
protection trip operation.
1) Lockout
Range 1~4
Default 4
Step 4
C. INTERVALS
It sets reclose interval for each reclose shot and reset time for auto reclose and
lockout.
1) Reclose 1
Range 0.5~60.0sec
Default 0.6
Step 0.1sec
This setting is used to change the first reclose interval time between
the first trip operation and the close operation.
2) Reclose 2
Range 1~60sec
Default 2
Step 1sec
3) Reclose 3
Range 1~60sec
Default 15
Step 1sec
This setting is used to change the third reclose interval time between
the third trip operation and the close operation.
4) Reset T(AR)
Range 3~180sec
Default 30
Step 1sec
5) Reset T(LO)
Range 1.00~600.00sec
Default 10.00
Step 0.01sec
6) C/P Wait
Range 1.00~600.00sec
Default 60.00
Step 0.01sec
C/P wait is Close Power Wait, waiting time to get power supply.
Power supply is not enough to operate mechanism for reclosing
sequence, it waits for the setting time.
In a case that power supply is not provided, reclose sequence stops
and goes to lockout status.
6.6.2. MONITORING
It moves to menu if [ENT] key is pressed after positioning cursor in "2.
MONITORING" in 'MAIN MENU'.
[ MON I T OR I N G]
> 1 . OP E R A T I ON C OU NT
2 . C ON T A CT WE A R
* . S AV E SE T T I NG
[ OP E R A T I ON C OU NT ]
> F u n c t i o n : OF F
L i mi t : 1 0 0 0 0
Co u n t s e t : 0
1) Function
2) Limit
Range 1 ~ 20000
Default 10000
Step 1
3) Count set
Range 0 ~ 10000
Default 0
Step 1
[ CONT A CT WE A R ]
> F u n c t i o n : OF F
P i c k u p ( %) : 2 0 . 0
Ra t e d V o l t ( k V ) : 3 8
I n t e r r u p t : 1 2 . 5
N o . Ma x I : 1 0 0
A We a r Se t : 1 0 0 . 0 0
B We a r Se t : 1 0 0 . 0 0
C We a r Se t : 1 0 0 . 0 0
1) Function
2) Pickup(%)
Set pickup value to alarm when CB contact wear reaches set value.
3) Rated Volt(kV)
4) Interrupt
5) No. Max I
Range 1 ~ 999
Default 100
Step 1
6) A Wear Set
7) Set item B Wear Set and C Wear Set are also used when coinciding
ETR306 contact wear with body. The Reset method of CONTACT WEAR
B and CONTACT WEAR C is identical to Contact A's.
6.6.3. EVENT
It moves to this menu when [ENT] key is pressed after placing cursor on
"3.EVENT" in main menu and can check and erase events per way of switchgear
through menu.
[ E V E NT ]
> 1 . OP E R A T I ON
2 . F AUL T
3 . F AUL T CY CL E
4 . A V E R . L OA D / MI N
5 . P E A K . L OA D/ HOU R
6 . P E A K . L OA D/ DA Y
7 . CL E AR S AV E D DAT A
This menu has submenus like following and can move to selected submenu using
[ENT] key.
Can check the record using the [▼][▲] keys. [001/256] is the latest event
recorded.
Trigger source
Status
- CLOSE
- OPEN
- EARTH CLOSE(ECLOSE)
- EARTH OPEN(EOPEN)
Control
- MANUAL: Manual operation in the CB body
- LOCAL: Manual operation in local
- REMOTE: Manual operation in remote
Saving method
Records when the Circuit Breaker or Switch operates(OPEN/CLOSE)
Trigger time
Every 5msec
Saving capacity
Saves up to 256 events max.
Move to the “MAIN MENU/ EVENT/ FAULT” menu to check the fault event.
Can check the event using the [▼][▲] keys. If the [ENT] key is pressed in the
current indicating screen, the active and reactive power value of each phase is
indicated and if the [ENT] key is pressed again, it returns to the current
indicating screen. [001/256] is the most recently recorded event.
Screen Description
1 6
Trigger Source
FI Target
Saving Method
Record at time of fault occurrence
Trigger Time
Every 1/4 cycle
Saving capacity
Save up to 256 events max.
Can check the record using the [▼][▲] keys. [001/8] is the latest event
recorded.
Trigger source
Fault waveform capturing point
- PU: Pick up point
- TR: Trip point
- PU&TR: Pickup & Trip point
Current in case of fault occurrence[A]: Phase A, phase B, phase C, phase N
Saving method
Record the fault waveform capturing point
Trigger time
Every 1/4 cycle
Saving capacity
Save a maximum of 8 events (20cycles×8EA(The sample rate is 32 samples)
6.6.3.4. AVER.LOAD/MIN
Record the average load current per circuit. It can save up to 10 days of event
since it saves a maximum of 1024.
Move to the “MAIN MENU/ EVENT/ AVER. LOAD/MIN” menu to check the
average load event.
■ ■ ■
Can check the event using the [▼][▲] keys. If the [ENT] key is pressed in the
current indicating screen, the active and reactive power value of each phase is
indicated and if the [ENT] key is pressed again, it returns to the current
indicating screen. [0001/1024] is the most recently recorded event.
Trigger Source
Measurement current[A]: Phase A, phase B, phase C, phase N
Active power measurement[kW]: Phase 3, phase A, phase B, phase C
Reactive power measurement[kVar]: Phase 3, phase A, phase B, phase C
Saving Method
Record when measuring the average load
Trigger Time
Every 15 minutes
Saving Capacity
Save up to 1024 events max.
6.6.3.5. PEAK.LOAD/HOUR
Record the hourly maximum load event per circuit. It can save up to 43 days of
event since it saves a maximum of 1024 hourly maximum load events.
Move to the “MAIN MENU/ EVENT/ PEAK. LOAD/ HOUR” menu to check the
maximum load event per hour.
■ ■ ■
Can check the event using the [▼][▲] keys. If the [ENT] key is pressed in the
current indicating screen, the active and reactive power value of each phase is
indicated and if the [ENT] key is pressed again, it returns to the current
indicating screen. [0001/1024] is the most recently recorded event.
Trigger Source
Measurement current[A]: Phase A, phase B, phase C, phase N
Active power measurement[kW]: Phase 3, phase A, phase B, phase C
Reactive power measurement[kVar]: Phase 3, phase A, phase B, phase C
Trigger Time
Every hour
Saving Capacity
Save up to 1024 events max.
6.6.3.6. PEAK.LOAD/DAY
Record the daily maximum load event per circuit. It can save up to 1024 events
since it saves a maximum of 1024 daily maximum load events.
Move to the “MAIN MENU/ EVENT/ PEAK. LOAD/ DAY” menu to check the
daily maximum load event.
■ ■ ■
Can check the event using the [▼][▲] keys. If the [ENT] key is pressed in the
current indicating screen, the active and reactive power value of each phase is
indicated and if the [ENT] key is pressed again, it returns to the current
indicating screen. [0001/1024] is the most recently recorded event.
Trigger Source
Measurement current[A]: Phase A, phase B, phase C, phase N
Active power measurement[kW]: Phase 3, phase A, phase B, phase C
Reactive power measurement[kVar]: Phase 3, phase A, phase B, phase C
Trigger Time
Every day
Saving Capacity
Save up to 1024 events max.
Trigger source
Measurement current[A]: Phase A, phase B, phase C, phase N
Active power measurement[kW]: Phase 3, phase A, phase B, phase C
Reactive power measurement[kVar]: Phase 3, phase A, phase B, phase C
[EVENT CLEAR]
5. ABOVE ALL
EVENT CLEAR SUCCESS
Clear all data in article 1 ~ 4.
6.6.4. MAINTENANCE
It moves to the maintenance menu of the [ENT] key is pressed after putting the
cursor in "4. MAINTENANCE" in the main menu. This menu indicates the
information of the maintenance of the CB per circuit. This menu has submenus
as shown below and can move to the chosen submenu by using the [ENT] key.
[ MA I N T E N A N CE ]
> 1 . C OU NT
2 . C ON T A CT WE A R
3 . DAT A RE SE T
6.6.4.1. COUNT
This menu indicates each circuit's counter information and has a submenu like
shown below. Can move to the chosen submenu by using the [ENT] key.
[ C OU NT ]
> 1 . OP E R A T I ON
2 . F AUL T
(1) OPERATION
Move to the“MAINTENANCE/ COUNT/ OPERATION” menu to check the CB
operation counter.
(2) FAULT
Move to the “MAINTENANCE/ COUNT/ FAULT” menu to check the fault
counter.
Depending on control type for each way of switchgear, FAULT menu contents
displayed on LCD screen are different. LCD screen display for each type is
follows.
A. ‘SW' Type
FAULT-TOT(1/3)
[FAULT-P] 2/3 Display total number of permanent fault and temporary
TOT: 0
A : 0 B : 0 fault occurrence.
C : 0 N : 0
FAULT-P(2/3)
Display the number of permanent fault occurrence.
[FAULT-T] 3/3
TOT: 0
A : 0 B : 0
C : 0 N : 0
FAULT-T(3/3)
Display the number of temporary fault occurrence.
B. ‘CB' Type
FAULT(1/3)
[FAULT-P] 2/3 F.I TOTAL : Display total number of permanent fault
TOT: 0
A : 0 B : 0 and temporary fault occurrence.
C : 0 N : 0
Trip : Display the number of fault trip.
INST' OC Trip : Display the number of high current
fault trip.
[FAULT-T] 3/3
TOT: 0
A : 0 B : 0
C : 0 N : 0 FAULT-P(2/3)
Display the number of temporary fault occurrence.
FAULT-T(3/3)
Display the number of instantaneous fault occurrence.
[EVENT CLEAR]
※. NOTE )
EVENT CLEAR SUCCESS 1) The ‘OPERATION COUNT’ is reset as the set value
of the ‘MAIN MENU/ MONITORING/ OPERATION
COUNT’ in case it is reset.
2) All other data are reset to 0.
6. ABOVE ALL
Rest all the data in items 1 ~ 4.
6.6.5. STATUS
It moves to the status menu if the [ENT] key is pressed after putting the cursor
in "5. STATUS" in the main menu.
SWITCH
Indicate the status of the body.
OPEN, CLOSE, TROUBLE(Device Trouble status)
PANEL LOCK
Indicates the panel lock status.
LOCK, UNLOCK
CONTROL
Indicate the operation control selection status.
REMOTE, LOCAL, TROUBLE(Device Trouble status)
EARTH
Indicate the status of the earth circuit.
EARTH(earthing status), NORMAL(normal status)
6.6.6. METERING
It moves to the measurement menu if the [ENT] key is pressed after putting the
cursor on "6. METERING" in the main menu. In the measurement menu, the
present measurement value is indicated and has submenus like shown below. It is
possible to move to the chosen submenu by pressing the [ENT] key.
[ ME T E R I N G ]
> 1 . CURRE NT
2 . V OL T A GE
3 . P O WE R
4 . E NE RGY
5 . D E MA N D
6.6.6.1. CURRENT
ETR306 measures and displays the following current items;
CURRENT : Indicate the RMS value and phasor of the measured current per
phase(A, °).
SEQUENCE 'I' : Indicate the normal/ negative sequence/ zero sequence
current and phasor(A, °).
[SEQUENCE ‘I’]
I1: 0A ∠ 0˚
I2: 0A ∠ 0˚
3I0: 0A ∠ 0˚
6.6.6.2. VOLTAGE
ETR306 indicates the following voltage factors after measuring them;
Indicates the measuring value of the phase to phase voltage and line to line,
voltage, normal/ negative sequence/ zero sequence voltage. Checks the voltage
measurement information by using the [▼][▲] keys.
6.6.6.3. POWER
ETR306 indicates the following power factors after measuring them;
Indicates the measuring value of the power and power factor by phase. Check
the electricity measurement information by using the [▼][▲] keys.
6.6.6.4. ENERGY
ETR306 measures and displays the following energy items. The base unit
increment is 10k.
POS’ W/H(10kWh) : Each phase and three phase active power amount of
forward direction are indicated. The indicated power is 10kWh per 1 count.
POS’ V/H(10kVar) : Each phase and three phase reactive power amount of
forward direction are indicated. The indicated power is 10kVar per 1 count.
NEG’ W/H(10kWh) : Each phase and three phase active power amount of
reverse direction are indicated. The indicated power is 10kWh per 1 count.
NEG’ V/H(10kVar) : Each phase and three phase reactive power amount of
reverse direction are indicated. The indicated power is 10kVar per 1 count.
ANSI/IEEE
Trip Time(Sec) = TD × ( α / ( Mβ - 1) + γ ) + TA
IEC
Trip Time(Sec) = TD × ( α / (Mβ- 1) ) + TA
ES(KEPCO)
Trip Time(Sec) = TD × ( α / (Mβ - 1) + γ ) + TA
USER-DEFINED
Trip Time(Sec) = TD × ( α / (Mβ - 1) + γ ) + TA
Reset Time(Sec) = TD × ( Rt / (1 – M2) )
TD Time dial
TA Time Adder
α, β, γ Characteristic constant
M Multiples of pickup current
Rt Reset characteristic constant
1. STANDARD CURVES
Curves α β γ Rt
Definite Time 1sec 0.0 - 1.0 1.0
Definite Time 10sec 0.0 - 10.0 10.0
Curves α β γ Rt
User 1(IEEE Moderately Inverse) 0.0515 0.02 0.1140 4.85
User 2(IEEE Very Inverse) 19.61 2.00 0.4910 21.6
User 3(IEEE Extremely Inverse) 28.2 2.00 0.1217 29.1
User 4(IEEE Long Time Extremely Inverse) 5.67 2.0 0.0352 5.67
Phase Ground
Old New Old New
A 101 1 102
B 117 2 135
C 133 3 140
D 116 4 106
E 132 5 114
K 162 6 136
L 107 7 152
M 118 8 113
N 104 8* 111
P 115 9 131
R 105 11 141
T 161 13 142
V 137 14 119
W 138 15 112
Y 120 16 139
Z 134 18 151
CURVES
N1, N2, N3, N4
3. CURVES
CURVE CHARACTERISTICS
*. Curve time is Clearing Time.
*. Operation accuracy is +/-10% or +/-10msec.
CURVE LIST
It describes in “[Table A-9] Curves List”.
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
15.00
13.00
2 11.00 2
9.00
Time(Second)
Time(Second)
7.00
1 1
0.9 5.00 0.9
0.8 0.8
0.7 4.00 0.7
0.6 0.6
3.00
0.5 0.5
0.4 0.4
2.00
0.3 0.3
0.2 0.2
1.00
0.1 0.1
0.09 0.5 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
15.00
13.00
11.00
1 1
0.9 9.00 0.9
0.8 0.8
0.7 7.00 0.7
0.6 0.6
0.5 5.00 0.5
0.4 4.00 0.4
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 15.00 0.6
0.5 13.00 0.5
11.00
0.4 0.4
9.00
0.3 0.3
7.00
3.00
0.1 0.1
0.09 0.09
0.08 2.00 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 1.00 0.04
0.03 0.03
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 1 2
0.8
Time(Second)
Time(Second)
0.7
0.6
1 0.5 1
0.9 0.9
0.8 0.4 0.8
0.7 0.7
0.6 0.3 0.6
0.5 0.5
0.4 0.2 0.4
0.3 0.3
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
1
0.4 0.4
0.8
0.3 0.7 0.3
0.6
0.5
0.2 0.2
0.4
0.3
0.1 0.1
0.09 0.2 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.1
0.04 0.04
0.03 0.03
0.05
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
1,000 1,000
900 900
800 800
700 700
600 600
500 500
400 400
300 300
200 200
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
Time(Second)
Time(Second)
5 5
4 4
3 3
2 2
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 1 0.09
0.08 0.08
0.07 0.8 0.07
0.06 0.7 0.06
0.05 0.6 0.05
0.04 0.5 0.04
0.4
0.03 0.03
0.3
0.02 0.02
0.2
0.1
0.05
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 15.00 3
13.00
2 11.00 2
9.00
Time(Second)
Time(Second)
7.00
1 5.00 1
0.9 0.9
0.8 0.8
4.00
0.7 0.7
0.6 3.00 0.6
0.5 0.5
0.4 0.4
2.00
0.3 0.3
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
15.00
Time(Second)
Time(Second)
13.00
11.00
1 9.00 1
0.9 0.9
0.8 7.00 0.8
0.7 0.7
0.6 0.6
5.00
0.5 0.5
4.00
0.4 0.4
3.00
0.3 0.3
2.00
0.2 0.2
1.00
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.5
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
15.00
10 13.00 10
9 11.00 9
8 8
7 9.00 7
6 7.00 6
5 5
4 5.00 4
4.00
3 3
3.00
2 2
2.00
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 1.00 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.5 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 15.00 8
7 7
13.00
6 6
11.00
5 5
9.00
4 4
7.00
3 3
5.00
2 4.00 2
Time(Second)
Time(Second)
3.00
1 2.00 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 1.00 0.5
0.4 0.4
0.3 0.3
0.5
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
15.00
2 13.00 2
11.00
Time(Second)
Time(Second)
9.00
1 7.00 1
0.9 0.9
0.8 0.8
5.00
0.7 0.7
0.6 4.00 0.6
0.5 0.5
3.00
0.4 0.4
0.2 0.2
1.00
0.1 0.1
0.09 0.09
0.08 0.5 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
15.00
0.6 0.6
13.00
0.5 0.5
11.00
0.4 0.4
9.00
0.3 7.00 0.3
3.00
0.1 0.1
0.09 0.09
0.08 2.00 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 1.00 0.04
0.03 0.03
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
D1, D2
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10
9
D2 10
9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1
0.9
D1 1
0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
N4
N2 N3
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 N1 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100 A, B, C, D, E
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
C
0.1 0.1
0.09 0.09
0.08 0.08
0.07 B 0.07
0.06 D 0.06
0.05 E 0.05
0.04
A 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100 K, L, M, N
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
N K
0.1 0.1
0.09 L M 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100 P, R, T, V
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6
V 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
T
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05
P R 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
W, Y, Z
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4
Z 0.4
0.3 0.3
W
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100 1, 2, 3, 4, 5
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 3 0.9
0.8 0.8
0.7 0.7
0.6 2 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08
0.07
5 0.08
0.07
0.06
1 4 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100 6, 7, 8, 8*, 9
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30
7 30
20 20
10 10
9 9
8 8
7 7
6 6
5 9 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
8
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 8* 0.06
0.05 0.05
0.04
6 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
3.21. Non-standard Curve (11, 13, 14, 15, 16, 17, 18)
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
11
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 18 0.5
14
0.4 0.4
0.3 0.3
0.2 0.2
13
0.09 16 0.09
0.08
0.07
17 0.08
0.07
0.06 0.06
0.05 0.05
0.04 15 0.04
0.03 0.03
0.02 0.02
0.01 0.01
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
FACTORY
MENU NAME DESCRIPTION STEP
DEFAULT
MAIN MENU(COM)
1. GLOBAL SETTING
1. SYSTEM
1. POWER LINE
Frequency Power line nominal frequency (50Hz, 60Hz) - 60Hz
2. CURRENT SENSING
CT1-Ratio Set phase current transfer ratio (1~2000) 1 1000
3. VOLTAGE SENSING
VT CON-Type VT Connector Type (NONE, WYE, DELTA) - WYE
4. CONTROL TYPE
1 WAY Control type of 1 way (CBTYPE, SWTYPE, NONE) - CBTYPE
5. CB OPENING TIME
Time CB Opening Time (0.000~1.000sec) 0.001 0.020
7. FI TYPE SELECT
Type Select Select the type of FI(fault indicator) detection. (IV/I) - IV
2. COMMUNICATION
1. PROTOCOL SETUP
1) DNP3
Function Use DNP3.0 protocol or not (DISABLE, ENABLE) - ENABLE
D/L Confirm Enable data link layer confirm (NO, YES, SOME) - SOME
D/L FrameDly Set data link frame delay time (10~5000msec) 10 100
Init Unsol Set Init Unsol. response or not (DISABLE, ENABLE) - ENABLE
MIT Time-Tag Time tag format for integrated totals(CP56, CP24) - CP56
MIT Time-Tag Time tag format for integrated totals (CP56, CP24) - CP56
Time tag format for measured value and
MME Time-Tag normalized value, in case of general event (CP56, - CP56
CP24)
Time tag format for measured value and
Flt Time-Tag normalized value in fault current event (CP56, - CP56
CP24)
4) MODBUS Protocol Setup
Function Use MODBUS protocol or not (DISABLE, ENABLE) - DISABLE
2) PORT2(485)
Select the baud rate for PORT2
Baud Rate - 9600
(1200, 2400, 4800, 9600, 19200bps)
Parity Bit Select whether to use parity bit (NONE, ODD, EVEN) - NONE
3) PORT3(ETHERNET)
IP Addr Oct1 IP address 1 for ETR306 (0~225) 1 192
K-Alv Fun Keep Alive Function use or not (DISABLE, ENABLE) - ENABLE
4) PORTF(232)
Select whether to use wireless or not (DISABLE,
Wireless - DISABLE
ENABLE)
Slave Address Slave Address (0~65534) 1 1
3. DIALUP MODEM
1) CALLING STRING
CS AT command for dial (ATD, ATDT, ATDP) - ATD
2) CALLING NUMBER
CN Modem (Master station)phone number. - -
3) INITIAL STRING
AT&C1 Q1
IS Initial commands for your modem. - E0 M0 &D2
+CRM=129
4) CONNECTION
Cmd Res’ TO Set the cmd Res’ Timeout(0~255sec) 1 2
4. ANALOG EVENT
AI Evt Method Select the Analog Event Type (OFF, TH, DB, BOTH) - OFF
AEvt Skip at Ft Select DB/TH Event Skip at fault pickup (No, YES) - NO
Daily Max I Daily Max. load current event (DISABLE, ENABLE) - ENABLE
Flt ‘I’ Evt Select the Fault ‘I’ Event(NO, YES, 1SHOT) - 1SHOT
Set the Average Load Calculation Time
Aver.Load Calc T - 15
(1/2/3/4/5/6/10/12/15/20/30min)
BI Queue Size Select the BI Event Queue Size (32, 64, 128, 256) - 256
CI Queue Size Select the CI Event Queue Size (32, 64, 128, 256) - 256
Time Syn’ Ref Set the time synch type (LOCAL, GMT) - LOCAL
Time Tag Type Set the time tag type (LOCAL, GMT) - LOCAL
3. EVENT RECORDER
Select whether to use Wave capture or not
Wave Capture - ON
(ON, OFF)
Select a number of sampling for wave capture
Wave S/R - 32
(16,32sample)
Wave Pre-Cycle Select a number of Pre-Cycle (1~10cycle) 1 5
4. MONITORING
1. BATTERY TEST
Set time period for automatic battery test
Period 1 24
(OFF, 1~720Hour)
2. TD MONITOR
TD1 Rate Set Transducer 1(TD1) monitoring range (1~200) 1 40
TD1-2 Type Set 2nd monitoring element of TD1 (UNDER, OVER) - UNDER
TD1-2 Delay Set 2nd delay time of TD1 (0.01~600.00sec) 0.01 2.00
TD2-2 Type Set 2nd monitoring element of TD2 (UNDER, OVER) - UNDER
TD2-2 Delay Set 2nd delay time of TD2 (0.01~600.00sec) 0.01 2.00
TD3-2 Type Set 2nd monitoring element of TD3 (UNDER, OVER) - UNDER
TD2-2 Delay Set 2nd delay time of TD2 (0.01~600.00sec) 0.01 2.00
TD3-2 Type Set 2nd monitoring element of TD3 (UNDER, OVER) - UNDER
TD3-2 Delay Set 2nd delay time of TD3 (0.01~600.00sec) 0.01 2.00
TD4-2 Type Set 2nd monitoring element of TD4 (UNDER, OVER) - UNDER
TD4-2 Delay Set 2nd delay time of TD4 (0.01~600.00sec) 0.01 2.00
5. PLC
1. COMMON
1) LOGIC TIMER
TM1-PU Set pickup time of Logic timer 1 (0.01~600.00sec) 0.01 1.00
2) PULSE TIMER
PTM1 Set output time of pulse timer 1 (0.01~600.00sec) 0.01 0.01
3) PULSE COUNTER
PC1 Set output count value of Pulse counter 1 (1~60000) 1 1000
2. DI/DO
1) INPUT DEBOUNCE
6. OTHERS
1. FACTORY DEBUG :
This is menu is for Manufacturer's maintenance purpose.
2. INRUSH RESTRAINT
PHA-Time Set the inrush current time of phase (0.0~180.0 sec) 0.1 0.2
GND-Time Set the inrush current time of ground (0.0~180.0 sec) 0.1 0.2
3. DIRECTION
1. PHASE
Select whether to use phase direction
Type - DISABLE
(DISABLE, ENABLE)
M.T.A(V1) Set the Maximum Torque Angle (0~359deg) 1 60
Set Minimum Polarizing to check Phase disconnect
M.P.V 1 10
direction (OFF, 1~80%)
2. GROUND
Select whether to use ground direction
Type - DISABLE
(DISABLE, ENABLE)
M.T.A(-V0) Set the maximum torque angle (0~359deg) 1 60
Set Minimum Polarizing Voltage to check ground fault
M.P.V 1 10
direction (OFF, 1~80%)
4. F.I SETTING TIME
Permanent Permanent FI reset time (1~180 sec) 1 20
Type I delay Set the delay time for F.I detection (0.03~180.00sec) 0.01 0.03
5. ON/OFF LEVEL
On Level Set normal voltage level (0.70~0.85pu) 0.01 0.80
Detect Time Set delay time of phase open or loss (0.0~180.0sec) 0.1 4.0
8. PHASE DIFF
Level Set the phase difference level (OFF, 5~80deg) 5 30
Time Set the delay time of phase difference (0.0~180.0sec) 0.1 4.0
9. LIVE LINE
Live Line Lv Set the live line level (0.10~0.90pu) 0.01 0.30
RMT-PHA Set Restore Minimum Time for phase (OFF, 0.01~30.00sec) 0.01 0.30
RMT-GND Set Restore Minimum Time for ground (OFF, 0.01~30.00sec) 0.01 0.30
RST-PHA Set cold load reset time for phase (OFF, 0.01~60.00sec) 0.01 3.00
RST-GND Set cold load reset time for ground (OFF, 0.01~60.00sec) 0.01 3.00
M.P.V Set Minimum Polarizing to check Phase disconnect direction (OFF, 10~80%) 1 10
Block OC Select whether to block the phase polarizing trip (NO, YES) - NO
2. GROUND
Type Set Ground direction type(NONE,FORWARD,REVERSE) - NONE
M.P.V Set Minimum Polarizing Voltage to check ground fault direction (OFF, 10~80%) 1 10
Select whether to block the ground polarizing trip
Block OC - NO
(NO, YES)
7. USER CURVE
1. USER CURVE 1
Factor a User defined curve1 factor α (0.0000~150.9999) 0.0001 0.0515
2. USER CURVE 2
Factor a User defined curve2 factor α (0.0000~150.9999) 0.0001 19.61
3. USER CURVE 3
Factor a User defined curve3 factor α (0.0000~150.9999) 0.0001 28.2
4. USER CURVE 4
Factor a User defined curve4 factor α (0.0000~150.9999) 0.0001 5.67
2. OPERATIONS
Lockout Set the maximum number of reclosing sequence (1~4) 1 4
3. INTERVALS
Reclose 1 Set the first reclose interval time (0.5~60.0sec) 0.1 0.6
Reset T(AR) Set the reset time for auto reclosing (3~180sec) 1 30
Reset T(LO) Set the reset time for lockout (0.00~600.00sec) 0.01 10.00
Detect Time Set delay time of phase open or loss (0.0~180.0sec) 0.1 4.0
Time Set the delay time of phase difference (0.0~180.0sec) 0.1 4.0
Live Line Tm Set the delay time of live detect element (0.0~180.0sec) 0.1 4.0
2. MONITORING
1. OPERATION COUNT
Function Select whether to monitor operation count (OFF, ON) - OFF
2. CONTACT WEAR
Function Select whether to monitor Recloser contact wear (OFF, ON) - OFF
Rated Volt(kV) Set the power line nominal voltage (15kV, 27kV, 38kV) - 38
Interrupt Enter the capacity of rated Interrupter (5.0~50.0 kA) 0.1 12.5
38 DIGDO √ √ DIAGNOSTIC DO
74 FITING √ FI TESTING