You are on page 1of 4

916 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 36, NO.

3, MAY/JUNE 2000

A Perspective of Low-Voltage Circuit


Breaker Interrupting Rating
Raymond D. Valentine, Life Senior Member, IEEE

Abstract—This paper reviews application of all three types of the available fault current could be pessimistic or optimistic de-
low-voltage circuit breakers for three-phase fault interrupting duty pending upon the point of view, and it could lead to an improper
by reference to the circuit breaker’s interrupting requirement and conclusion [10].
rating. After a discussion of the rating process for circuit breaker
design and the fault-current evaluation process for circuit breaker A related aspect of conductor protection is that the circuit
application, it then considers the effect of the erroneous assump- breaker must be terminated with conductor of rated wire size
tion that the load-side bolted fault interrupting let-through current to properly heat sink the circuit breaker. This is 60  C or 75  C
of all circuit breakers is equal to the calculated line-side prospec- wire, not the smaller 90  C wire that is sometimes used in cir-
tive fault current. cuits. This also means that the connectors at the circuit breaker
Index Terms—Circuit breaker, interrupting, let-through, low must be large enough and of the correct type to properly ac-
voltage, rating. commodate the size and material of the wire. Connectors for
copper and aluminum conductors are marked to indicate their
I. BASIC INTERRUPTING RATING OVERVIEW suitability for use with these materials.
Consistent with their primary purpose of protecting the phase
HE one-word qualifier that should be the focus of atten-
T tion in application is the word “rating.” However, rating
may not mean exactly what we think it means at first thought.
wire, circuit breakers are tested with rated wire to prove their
ability to perform the function. The amount of let-through cur-
rent allowed by the circuit breaker is not a significant factor as
For example, under “interrupting rating,” the National Electrical long as protection is provided.
Code (NEC) statement is that circuit breakers “...shall have an
interrupting rating sufficient for the nominal circuit voltage and
current that is available at the line terminals of the equipment” II. TEST BASIS FORSHORT-CIRCUIT INTERRUPTING
[1], [9]. Interrupting rating should, therefore, be specified by CURRENT RATING
reference to the available fault current at the terminals of the
circuit breaker and it is. However, failure to account for the A specific set of current interrupting ratings has been agreed
differences in the process of interruption can lead to problems upon by manufacturers and users and all standard circuit
in application. The circuit breaker interrupting requirement is breakers utilize these standard interrupting ratings. The stan-
for sufficiency and there can be a wide range in the amount of dards also specify the different test voltage and test circuit X/R
let-through current that different circuit breakers allow. requirements that must be used to establish these ratings. Power
The function of a circuit breaker is to provide switching and circuit breaker short-circuit interrupting tests, for example,
overcurrent protection functions. They are to protect phase con- are performed per IEEE Standards C37.13 and C37.50 at
ductors downstream from damage due to current in excess of maximum voltage [4], [14]. Molded-case circuit breaker and
their ratings [2], [3]. They are not in the circuit primarily to pro- insulated-case circuit breaker short-circuit interrupting tests
tect the ultimate load device. They may provide a measure of are performed per UL-489 Standard at rated voltage [13].
backup protection for other devices, but, generally, that is not The required X/R ratios of the test circuits are specified in
their primary function. More sensitive specific-purpose devices these standards and, for molded-case and insulated-case circuit
like overloads and motor circuit protectors are usually used to breakers, they are related to the interrupting ratings being
provide the load protection. sought. They are as listed in Table I.
When the circuit breaker interrupts fault current flow, the Knowing the value of X/R at which the circuit breaker proof
amount of current it interrupts does not have to be equal to test was made makes evaluation of the circuit breaker for in-
the available fault current. An assumption that it is equal to terrupting rating a simple comparison of the evaluated prospec-
tive interrupting current for the application to the circuit breaker
nameplate interrupting current rating as long as the prospective
Paper IPCSD98–37, presented at the 1998 Industry Applications Society An- circuit X/R ratio is less than or equal to the test value. This is the
nual Meeting, St. Louis, MO, October 12–16, and approved for publication in major benefit of the change from total current rating to symmet-
the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS by the Power Systems
Protection Committee of the IEEE Industry Applications Society. Manuscript rical current rating for circuit breakers which is used now. That
submitted for review October 16, 1998 and released for publication January 29, is, with the change to symmetrical current rating, asymmetry
2000. during fault inception and interruption is accounted for in the
The author is at 3216 Brison Court, Murrysville, PA 15668-1214 USA
(e-mail: rdmcval@nb.net). symmetrical current interrupting rating for all values of X/R up
Publisher Item Identifier S 0093-9994(00)04389-9. to the test value, and the test values are high enough to eliminate
0093–9994/00$10.00 © 2000 IEEE
VALENTINE: A PERSPECTIVE OF LOW-VOLTAGE CIRCUIT BREAKER INTERRUPTING RATING 917

TABLE I circuit breaker which would reduce the fault current at the load
RANGES OF TEST CIRCUIT X/R RATIO FOR DEVELOPMENT OF
terminals of that circuit breaker from the value calculated as
LOW-VOLTAGE CIRCUIT BREAKERS
prospective. However, this fact is neglected for the purpose
of circuit breaker application. This is because proof tests for
circuit breakers is done from a calibrated source bus and, in the
tests, the circuit breaker actually interrupts the resulting real
fault current that flows from the prospective current source.
For molded-case circuit breakers, the real interrupted current
is essentially never equal to the prospective fault current
calculated because of the rapid rate at which molded-case
circuit breakers can respond to overcurrent and introduce
dynamic impedance into the circuit [7]. Some molded-case
circuit breakers can limit the current in interruption enough to
satisfy the definition of “current limiting” and can, therefore,
be listed as special-purpose current-limiting circuit breakers.
However, even when they are not fast enough to satisfy the
definition, essentially, all molded-case circuit breakers limit
fault current to some degree in interruption. The net result
is that molded-case and most insulated-case circuit breakers
essentially never let through prospective fault current [11].
the necessity to do a separate engineering evaluation in a large In contrast, power circuit breakers essentially do not affect the
number of practical cases. This is true for power circuit breaker first cycle of fault let-through current because it takes a period
as well as for molded-case and insulated-case circuit breaker ap- of time on the order of that of one power system cycle to do the
plications. decision making and implementing of a mechanism trip. After
that, the circuit breaker interrupts the current.
III. CIRCUIT BREAKER EVALUATION With this perspective, the following sections examine a few
of the consequences of these different actions.
When circuit X/R ratio exceeds the test value of X/R ratio, it
is necessary to evaluate the circuit breaker for interrupting capa-
bility. The process of evaluation is the same for molded-case and V. A PERSPECTIVE OF POWER CIRCUIT
insulated-case circuit breakers as it is for power circuit breakers. BREAKER APPLICATIONS
One multiplies the calculated symmetrical fault current of the
application circuit by a multiplying factor which is a function A question that might be asked about power circuit breaker
of the X/R ratio of the application circuit to get an evaluated applications is: “Is let-through current equal to the calculated
short-circuit current. Then, the circuit breaker interrupting cur- symmetrical fault current at the point of application?” In light of
rent rating is compared to the evaluated prospective short-circuit the preceding discussion, for a fault very near the load side ter-
current. If the evaluated short-circuit current is greater than the minals the answer is: “Yes, until the protective relaying senses
circuit breaker interrupting rating, then the circuit breaker may the fault, initiates a trip, and the circuit breaker interrupts the
not have the capability to interrupt current in that circuit and fault.” This answer suggests consideration of the definition of
may not be applied. the word “instantaneous” as applied to circuit breaker tripping.
Since the test X/R ratios differ, the multiplying factors for dif- If there is no intentional delay, then it is instantaneous. It prob-
ferent circuit breaker types and interrupting ratings also differ, ably should also suggest consideration of the “O and CO” tests
but they are applied in the same manner. One important obser- performed on power circuit breakers during proof testing and,
vation is that all fault-current multiplying factors are of magni- in particular, the requirement of a power circuit breaker to be
tude 1.0 or greater. This correctly indicates that the application able to “make” under fault conditions. The “O” test means the
prospective current can never be evaluated to be less than its cal- circuit breaker is initially closed and it is required to open upon
culated symmetrical value and, conversely, the interrupting cur- inception of a fault. The “CO” test means the circuit breaker
rent rating of a circuit breaker may never be made greater than its is initially open and it is required to close into a fault and then
nameplate rating on the basis of an evaluation calculation. IEEE open. To “make” means that the circuit breaker must be able to
Std 1015-1997, the Blue Book, [5] lists multiplying factors for close and latch against the forces of the fault current. Then, sub-
power circuit breakers taken from IEEE Std C37.13-1990, Table sequently, it opens and interrupts [14].
3 and multiplying factors for molded-case and insulated-case Note that molded-case and insulated-case circuit breakers do
circuit breakers in Table 3-25. not have a “make” requirement. The power circuit breaker, be-
cause of its method of sensing current, its stored energy oper-
ating system mechanism design, and its general massiveness
IV. SOME PRACTICAL CONSIDERATIONS OF FAULT CURRENT
is relatively slow to respond to an overcurrent trip relative to
Obviously, one of the realities of the actual physical system power system cycle time. This is one of the primary differ-
is that, when any circuit breaker is connected to a point in ences between smaller molded-case and insulated-case circuit
the system, some additional impedance is added through the breakers and typically larger power circuit breakers. Because of
918 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 36, NO. 3, MAY/JUNE 2000

its relative slowness, a power circuit breaker tends to let cur- has an interrupting rating less than that which is required for full
rent through for a longer time during an instantaneous overcur- rating, then, obviously, the combination must be series rated. If
rent trip condition, but this delay is not intentional, and it must the molded-case circuit breaker’s interrupting rating is sufficient
still protect its downstream circuit conductors, and it does so as for its position in the circuit, then there is no question about its
proved by test. ability to interrupt because, in that case, it is fully rated. The
Therefore, we might think of a power circuit breaker as being only question then arises with series rating.
more representative of a solid piece of bus for a short time which There seems to be a strong temptation for some engineers
is usually longer than 1/2 cycle before it introduces any dynamic to attempt to calculate the requirements of an upstream series
impedance into the circuit during interruption. This also means fuse based on an estimate of the downstream molded-case
that a current-limiting fuse or a circuit breaker in series with circuit breaker’s i2 t interrupting let-through. However, even if
it upstream would likely have ample time to operate in its cur- the downstream molded-case circuit breaker i2 t interrupting
rent-limiting mode before the power circuit breaker could begin let-through is known, the dynamics of interruption is not
to open. Fused power circuit breakers work in this mode, but quantified. There is just not enough information normally avail-
at the expense of the loss of circuit breaker capability under able to do it. The result is that, in many cases, the calculated
high-level faults. The fuses are used to protect downstream con- performance of a proposed series combination is not obtained
ductors at a level lower than the circuit breaker alone can pro- in practice. At this time, the only way to know how a series
vide under certain severe fault conditions. For faults below that combination will work is by testing it.
limiting level, the circuit breaker operates in its normal mode to The up-over-and-down method for fuses of estimating an
protect the circuit. The ranges of interrupting protection for the equivalent required short-circuit interrupting rating based on
power circuit breaker and the fuses or limiters are shown on the current-limited fuse let-through may work very well when
coordination curve for the fuse being used. the fuse is operating into a bolted short circuit, but it is not
generally applicable to the case where the fuse is separated
from the bolted fault by a molded-case circuit breaker. One
VI. A PERSPECTIVE OF INSULATED-CASE AND MOLDED-CASE
fallacy in this method is that one cannot be sure that the
CIRCUIT BREAKER APPLICATIONS
fuse will have enough time to interrupt in its current-limiting
Asking the same question as was asked for the power circuit mode because of the speed of operation of the downstream
breaker case above, the answer for molded-case circuit breakers molded-case circuit breaker in interruption. Another is that the
in general would be: “No, the let-through current is not equal to current limiting characteristic shown may not be valid for the
the prospective fault current, except in the very early lower cur- X/R ratio of the application circuit. This can result in a change
rent stage of buildup. The typical molded-case circuit breaker in the fuse interrupting response [12]. At this time, there is
will generally blow open, limiting even the first half-cycle of no mathematical procedure known which is easy enough to
fault current.” For insulated-case circuit breakers, because of be employed conveniently and accurate enough in result to be
their larger size and the similarity of some of their operating used in place of a series test [8], [11].
mechanisms to those of power circuit breakers, the “no” is not as Another consequence of the “no” answer for molded-case cir-
sure. It could be true in some cases and false in others. Those in- cuit breakers is that the actual fault current flow is further re-
sulated-case circuit breakers whose operating mechanisms will duced from the prospective value. This is a beneficial side effect,
permit a blow-open will behave in that manner if fault current since, in the ideal case, it would be desirable to allow no current
is large enough. Others will tend to hold closed more like a flow into a fault. Although the actual interrupting let-through
power circuit breaker. Therefore, because insulated-case circuit current is not required by the Standards to be published for stan-
breakers as a type span the gap between typical molded-case dard (not current-limiting) circuit breakers, if it was, it could
circuit breakers and power circuit breakers, their behavior in in- vary considerably from manufacturer to manufacturer and from
terrupting fault current cannot be as readily generalized. Insu- case to case while still being satisfactorily low enough (or suffi-
lated-case circuit breakers are usually certified to UL-489 like cient) to protect downstream conductor. Interrupting let-through
molded-case circuit breakers, but could be certified to ANSI like current is required to be published only for those low-voltage
power circuit breakers. molded-case circuit breakers that are rated “current-limiting”
In the case of molded-case circuit breakers, one immediate and the circuit condition for that measurement must be that of
consequence of the “no” answer is that molded-case circuit a bolted short circuit downstream of the circuit breaker when
breakers should not to be expected to be representative of a the test is made. The bolted short circuit assures that the circuit
solid piece of bus for a time sufficient for another current-lim- breaker is operating in its current-limiting mode.
iting device in series to operate. They introduce dynamic In light of these considerations, the conservative worst case
impedance into the circuit so quickly that there is danger that assumption that a molded-case circuit breaker with a 100-kA in-
a current-limiting fuse or a current-limiting circuit breaker in terrupting rating, for example, will let anywhere near this value
series would not be exposed to its required current-limiting of current flow into the fault from a 100-kA prospective system
operational condition long enough to be able to follow through is incorrect. The let-through current on test is more likely be
and interrupt in that mode. a fraction of the value of the 100-kA prospective peak and, in
When other molded-case circuit breakers or fuses are chosen practice, it will probably be at even a more reduced level as
to operate upstream in series with a molded-case circuit breaker, a result of practical fault impedance [6]. However, a bolted-
then a special situation exists. If the downstream circuit breaker fault condition can occur downstream of a molded-case circuit
VALENTINE: A PERSPECTIVE OF LOW-VOLTAGE CIRCUIT BREAKER INTERRUPTING RATING 919

breaker, especially at startup where a wiring error is a possi- by the circuit breaker is generally false. It is an optimum as-
bility. sumption when used to apply the circuit breaker by its inter-
The conservative most optimistic assumption from the cir- rupting rating and it should be used in that case, but it is pes-
cuit breaker point of view, that molded-case circuit breakers simistic when used to postulate the circuit breaker’s effect on
as a class of circuit breaker generally “blow open” under the other circuit devices connected in series.
influence of heavy fault current, would be closer to the truth.
Molded-case circuit breakers generally do not wait for sensors REFERENCES
to detect severe faults and for the sensors to send a signal to a trip [1] Interrupting Rating, National Electrical Code, Article 110-9, 1993.
unit to initiate opening and then wait for interruption to occur. [2] Circuit Impedance and Other Characteristics, National Electrical Code,
They “blow open,” which means that, by design, they use force Article 110-10, 1993.
[3] NEMA Circuit Breaker Section, “What is the purpose of a circuit
produced by the fault current flow itself to drive the contact arms breaker?,” EC&M, July 1994.
open so quickly that the terminology “blow open” has been ap- [4] IEEE Standard for Low-Voltage AC Power Circuit Breakers Used in En-
plied. Due to this driving force, to some degree and over some closures, IEEE/ANSI Std C37.13, 1990.
[5] IEEE Recommended Practice for Applying Low-Voltage Circuit
range below maximum interrupting rating, some molded-case Breakers Used in Industrial and Commercial Power Systems,
circuit breakers operate even faster, the higher the prospective IEEE/ANSI Std 1015-1997 (IEEE Blue Book), 1997.
fault current level. Their interrupting characteristic curves slope [6] IEEE Recommended Practice for Electric Power Distribution for Indus-
trial Plants, IEEE/ANSI Std 141-1993 (IEEE Red Book, ch. 5), 1993.
downward in time with increasing current. The nature of dy- [7] Y. K. Chien and F. D. Graham, “Molded-case circuit breaker systems:
namic impedance complicates desktop analysis [7], [8]. Testing with conductors,” in Conf. Rec. IEEE-IAS Annu. Meeting, 1993,
pp. 1536–1539.
[8] B. DiMarco and S. Hansen, “Interplay of energy in circuit breaker and
VII. SUMMARY fuse combination,” in Conf. Rec. IEEE-IAS Annual Meeting, 1991, pp.
1765–1769.
Actual fault current let-through of a low-voltage circuit [9] J. A. DeDad, “Roundtable discussion on circuit breaker testing, applica-
breaker is not always equal to the available fault current. It can tion and operation,” EC&M, pp. 35–49, October 1992.
vary widely depending upon the circuit characteristics and the [10] A. J. Smith III, “Short circuit ratings, labels and fault withstandability of
molded-case and insulated-case circuit breakers and combination motor
specific circuit breaker being considered. Interrupting current starters,” in Proc. IEEE PCIC, 1991, pp. 1830–1838.
let-through measurements are only published for current-lim- [11] G. D. Gregory and W. M. Hall, “Predicting molded-case circuit breaker
iting circuit breakers because current-limiting performance is performance during short-circuit conditions in an electrical system,” in
Conf. Rec. IEEE-IAS Annu. Meeting, 1991, pp. 1754–1764.
measured relative to an i2 t criterion and an i2 t performance [12] S. Schaffer, “Current-limiting effect charts a valuable engineering tool,”
measurement is most appropriate for showing that compliance. in Conf. Rec. IEEE-IAS Annu. Meeting, 1991, pp. 1776–1779.
Interrupting current let-through for noncurrent-limiting circuit [13] Molded-Case Circuit Breakers, Molded-Case Switches, and Cir-
cuit-Breaker Enclosures, UL 489 Standard For Safety.
breakers is inconsequential for phase conductor protection and [14] American National Standard Test Procedures for Low-Voltage AC Power
can vary considerably between circuit breakers. Therefore, a Circuit Breakers Used in Enclosures, ANSI C37.50-1981, 1981.
qualitative evaluation of a circuit breaker’s ability to protect
standard size wire is made during proof testing. In practice, a
circuit breaker’s ability to protect conductors is shown by its Raymond D. Valentine (S’60–M’61–SM’82–
time–current characteristic being below and to the left of its LS’99) is a Consulting Engineer in private practice.
cable damage curve on a coordination diagram. He retired as a Fellow Engineer from Westinghouse
in 1994 after 39 years of service. From 1988 to 1994,
he worked in the Applications and Standards De-
VIII. CONCLUSIONS partment of the company’s Distribution and Control
Business Unit’s Technical Center, Pittsburgh, PA.
Different types of circuit breakers interrupt fault current dif- During this period, he worked on applications and
ferent ways. The differences are insignificant with respect to the development of molded-case, insulated-case, and
low-voltage power circuit breakers and accessories.
circuit breaker’s primary function of interrupting fault current Mr. Valentine has been an active participant in the
and protecting downstream phase conductors. However, the dif- Low-Voltage Protection Subcommittee of the I&CPS Power Systems Protec-
ferences can be very significant to other functions. tion Committee of the IEEE Industry Applications Society since 1988. He cur-
rently serves as Chair of both the Low-Voltage Protection Subcommittee and its
The assumption that total available fault current flows in a Molded-Case Circuit Breaker Working Group and is Vice-Chair of the Power
bolted load-side fault and that this level of current is interrupted Systems Protection Committee.

You might also like