Professional Documents
Culture Documents
0-7803-5843-0/00/$10.0002000 IEEE
119
I
UtilayImpdaaoe
The general solution for the arc current is:
MainFeeder I -a ( t - r a ) (2)
(%-sin(ota- 0)). I.
120
3
substituted for the impedance at the panel or 178.30 + solved using a Runge-Kutta numerical method. The first
j18.43 m were substituted for the impedance at the model incorporates a currentdependent arc voltage based
branch. The ground impedance is assumed to be zero. The on an equation formulated by Stokes and Oppedander [7]
system impedance seen at the main distribution panel is for instantaneous arc voltage. By Kirchhoff s voltage law,
typically highly inductive and much smaller in magnitude the following equation holds:
than the highly resistive branch circuits that typically have
dim,
much larger impedancevalues. ,,V sin(ot) = Rim +L-dt
+ (20 + 0.534 -
25.4 g)i,, .
0.12
-100 -
-300 -
-400 - ResMke Voltage/
1 . 1 . a . i .
O.OOOO0 0.00417 0.00833 0.01250 0.01667
O.OOOO0 0.00417 0.00833 0.01250 0.01667
"e in Seconds TTme in Seconds
-
Figure 3 Arc Current & Voltages at MDP Figure 5 - Arc Current & Voltages at Branch
121
4
-
Table 2 Short-circuit Ratio and Arc Duration produced sustained arcing for rms supply voltages as low
as 146 V (206 V peak) [SI. The exact voltage required
Power
depends on many factors. These include: the surface
Factor Duration condition of the cathode and the presence of conductive
9.950 0.576 0.827 dusts (or other conductive material) to help bridge the gap
0.2 4.899 0.53 1 0.799 [l]. The exact voltage also depends on the time of arc
extinction since arcing last occurred [113. Since voltages
I 0.3 I 3.180 I 0.495 I 0.774 I less than about 350 V are not capable of initiating arcs at
I 0.4
I
I 2.291 I 0.468 I 0.751 I
I
room temperature and atmospheric pressure [12], a 350 V
10.5
I
I 1.732 I 0.448 I 0.728 I
I
restrike voltage has been adopted for the new models.
The Merentid equations in (4) and (5) produce fairly
I 0.6
I
I 1.333
I
I 0.433
I
I 0.704
I
I
I
similar arc current and voltage waveforms. Since the arc
0.7 1.020 0.424 0.678 voltage expression developed by Stokes and Oppenlander
was determined from over 200 digitally sampled arc tests
0.8 0.750 0.422 0.647 with more than two million arc current and voltage data
0.9 0.484 0.43 1 0.605 points [7], the arc current and arc voltage will be predicted
by (4). Figure 6 shows the relative Waveform shapes and
0.95 0.329 0.444 0.571 current magnitudes for arcing faults at the main
0.995 0.100 0.474 0.508 distributionpanel, a sub-panel, and a branch circuit for the
electrical system illustrated in Figure 1. The predicted arc
current and voltage waveforms at the main distribution
panel, sub-panel, and branch circuit are shown in Figures
The second model incorporates an arc voltage based on the 7,8, and 9, reWstiVelY.
product of arc current and Fisher's equation for arc The arc Voltage is now a function Of arc current;
resistance [SI. ~y Kirchhoffs voltage law, the following therefore, it increases and decreases with the magnitude of
equation holds: the arc current. Neglecting the fluctuations associated with
the random and dynamic nature of arcing, the arc current
and arc voltage feach peak values simul&wusly because
V- ~in(ot)
= Rim +L G
dt
+ (25-.&)itt5. (5)
-30000 m
122
5
f140000
-100 -
-400 - Restlikevoltage
-40000
0.00000 0.00417 0.00833 0.01250 0.01667
Time in Seconds O.OOOOO 0.00417 0.00833 0.01250 0.01667
Time in Seconds
-
Figure 7 Arc Current & Voltages at MDP
-
Figure 9 Arc Current & Voltages at Branch
13000 When the arc voltage is greater than the source voltage, the
magnetic energy stored in the system begins dissipating.
Once the magnetic energy has dissipated, the arc becomes
extinct.
In addition to the current magnitude and not addressed
by the Matthews model, a close relationship exists between
the arc voltage and the distance from the cathode to the
anode (gap width). The arc length is often longer than the
gap width, and the difference tends to increase with
increasing gap width. Unlike the flat 140 V arc voltages
shown in Figures 3, 4, and 5, the arc voltages shown in
Figures 7,8, and 9 have significantly different peak values
of 209.8 V, 143.0 V, and 82.1 V which correspond to 3-
inch, 2-inch, and 1-inch gap widths, respectively.
-400 - Restrike Voltage
. . .
- -11000
I I m m *
-13000 V. COMPARISON OW SYSTEM RESULTS
0.00000 0.00417 0.00833 0.01250 0.01667
Time in Seconds A summary of system calculations predicted by the
Figure 8 - Arc Current & Voltages at Panel Matthews 140 V arc model and the new arc model
incorporating the voltage expression based on the work of
Stokes and Oppenlander are listed in Table 3. At the MDP,
an arc can be considered a purely resistive component. the Matthews model predicts a larger arc current and a
However, the arc resistance is highly nonlinear; large smaller arc voltage. An overcurrent device would react to a
increases in current magnitude produce much smaller larger current magnitude more quickly. The overcurrent
corresponding increases in arc voltage. One improvement device would take longer to react to the smaller arc current
associated with the currentdependent arc voltage is that predicted by the new model. Consequently, the arc is likely
after the arc current has reached its peak value and is to propagate for a longer period of time than indicated by
decreasing, the arc voltage is also decreasing. Unlike the the Matthews model. Arcing is typically extremely
Matthews model, the decreasing arc voltage delays the dangerous and explosive at the MDP because of the high
moment that the arc voltage exceeds the source voltage. level of current magnitudes involved. At both the MDP and
123
6
the panel, the new model predicts that more energy has Fisher. Peak arc currents were used to assess the models’
been released through the arc than the Matthews model ability to predict arc currents, since the true rms currents
predicts. were not measured at the time. Table 4 lists the average
In general, the models predict more congruous results deviation of the peak currents predicted by Matthews
at the panel. h4atthews’ 140 volt arc voltage is only slightly model and the new models with the peak arc currents
lower than the new model’s peak 143.0 V, but the new measured by Stanback and Fisher. Although the model
model predicts a larger arc current and a longer arc based on Fisher’s work more accurately predicted arc
duration. The arc duration contributes to the likelihood currents for the test data, the model based on the work of
that the arc will remain self-sustaining; the longer arc Stokes and Oppenlander is preferred at this point in the
duration predicted by the new model more strongly research because Fisher’s test data is limited and arcing-
indicates that a self-sustaining arc will be produced at the fault data from Fisher, as well as Stanback, was used to
panel than the Matthews model suggests. validate the models. In addition, an: voltages were also
The results of the models deviate widely at the branch. validated in [13], and the new models are better able to
The rms arc current and peak arc voltage predicted by the predict arc voltage [131.
new model are at least 34% higher and lower, respectively,
than those values predicted by the Matthews model. The
new model also predia a longer arc duration than the
Wtthews model. Although arcing is not as critical and Model Stanback’s Data Fisher’s Data
hazardous at the branch, the magnitude of the arc current Matthews 19.82 % 30.61 %
and the duration of arcing contributesto the likelihood that
New #1 (*) 6.59 % 14.81%
the arc will restrike and that it will initiate a fire.
The models were validated in [13]. Arcing-fault test New #2 (**) 5.39 % 12.04 %
data published in [8] and [9] were used to validate the
models. The rms shortcircuit currents for the test systems
ranged from 650 to 41,600 A, power factors ranged from
0.09 to 0.44 lagging, and gap widths ranged from 0.5 to 4
inches [8,9]. Predicted peak arc currents were compared
with the data from 24 self-sustaining tests performed by VI. HARMONICS
Stanback and from 10 self-sustaining tests performed by
At the present time, arcing-fault currents in building
systems are detected through a ground-fault protective
Table 3 - Summary of System Cal ulations system, which detects current flowing to ground. The arc-
fault circuit interrupter (AFCI) cau detect arcing faults in
I MDP residential 20 A circuits [4]. Since much interest has been
20.98 179.25 generated about arcing-fault detection from harmonic
9.272 0.810 components, the harmonic contents of the arc currents at
the MDP, panel, and branch for the typical building system
Isc (A) 42,290 13,205
have been identified from the arc currents calculated with
2 the new model based on the work of Stokes and
Matthews’ model: Oppenlander. The coefficient, c, of the Fourier Transform
IarCASC 0.572 0.421 0.473 was calculatedby the following quation [141:
24,206 5,565 731
140 140
KW 2,771.4 572.9 66.8
0.655 0.509
New model:
0.482 0.658 In equation (6), n is the harmonic number and N is the
total number of discrete current data. The third, fifth,
6,370 1,017
seventh, ninth, eleventh, and thirteenth harmonic
143.0 82.1 percentages at the MDP, panel, and branch are graphed in
679.4 58.7 Figures 10, 11, and 12, respectively. The harmonic
ArcDuration I 0.795 0.723 0.627 percentageswere found by the following equation:
124
7
I MDP h, = 2IC. 1I 0 0 % .
IC1 I
(7)
I Harmonics
-
Figure 10 MDP Harmonic Percentages
I Branch
Va CONCLUSIONS
Instantaneousarc current models have been explored in
this work. Arc currents predicted by the Matthews model
are independent of the gap width, since the arc voltage is a
constant value. The Matthews model has been used to
generate a table for predicting rms arc currents based on
the X/R ratio. Although the new models are more
laborious, they can more accuately predict arc currents
since the arc voltage is a currentdependent function.
Harmonics are also calculated for the arc currents
predicted by one of the new models to show the harmonic
I Harmonics contents of the arc currents. Eventually harmonic analysis
may be a viable method for arcing-fault detection in
Figure 12 - Branch Harmonic Percentages
125
8
126