You are on page 1of 56

Low voltage distribution

iBusway for
Data Center

Catalogue
2010
Contents

Why iBusway for Data Center 5


Presentation 10
Composition of the offer 10
Power distribution 12
Metering 14
Monitoring 18

Power distribution lines 22


Rack supply 23
Layout 27
Ratings 39
Protections 30
Fastening 31

The tap-off units 32


Layout and tap-off capacity 34
Tap-off unit choice tables 36
Part numbers 40
Modular circuit-breaker 43

Metering and monitoring 46


Metering module 47
Monitoring module 50

The tools 53


The sales references 54


2
Why iBusway for Data Center

Optimize your investment


and reduce your power
consumption
Information technology undergoes constant change. What
will future servers be like? What technical, environmental and
economic constraints will determine their maximum capacity
within safe operating limits? All these questions are hard to
answer, but they influence your decisions today.

How can you plan ahead


for these changes?
> The Schneider Electric iBusway for > The iBusway solution helps improve the
Data Centers is a power distribution system continuity of service in your data center, optimize
for server racks, meeting your requirements for site energy efficiency, and reduce the long-term
electrical power availability, energy savings and impact on the environment by reducing cabling
return on investment, while still allowing you to and the waste generated during traditional
flexibly adapt to changing needs. retrofits.

This flexible, scalable and


sustainable solution lets you invest
for today’s needs while preparing
for tomorrow’s possibilities.

Adaptable
The iBusway for Data Centers is designed
for facilities from 150 m2 to more than
5,000 m2, with a power supply ranging
from 150 to more than 10,000 kVA.


Why iBusway for Data Center

A simple, secure solution


The Schneider Electric iBusway for Data Centers is the key component for high
availability power distribution to all server racks in your data center. Based on
the Canalis KS prefabricated busbar trunking system, with plug-in tap-off units,
monitoring and a specific control and monitoring system, iBusway for Data Centers
is a "plug-&-play" solution for quickly installing or upgrading an IT facility.

Storage room
> Ready-to-install
iBusway for Data Centers, tap-off units.
a solution that is…
Facility monitoring
Flexible
room
Its modular format easily adapts to all types of
> Monitor power distribution
data centers offering easy facility upgrading and
and load status.
equipment replacement while also providing
energy consumption measurements.

Interconnected
The local monitoring system gives you a
clear view of your server room in real time:
measurement of load factors, circuit-breaker
status and power consumption for each
individual rack. The system’s compatibility
allows connection to the data center’s overall
monitoring system.

Easy to install
iBusway is a plug and play solution, with all
components pre-wired and tested for fast,
secure setup and software tools simplify
architecture design. Dedicated services for
installation and start-up are also available.

Zero foot print


The iBusway solution takes up no floor space
and offers more efficient use of dedicated rack
areas. Electrical
distribution
switchboards
> Conforms to
international
Remote monitoring room standards; equipped
> Centralized information to optimizes overall with Compact NSX
operation of the facilities. intelligent and
interconnected circuit
breakers.


Why iBusway for Data Center

Communication bus
> Quick, reliable connection to the units.

Local
monitoring
HMI
> Provide real-time
information on each
server rack.

Plug-in tap-off units


> Pre-equipped and prewired
with circuit breakers and measurement
and communication equipment.

Prefabricated electrical
busbar trunking
> Install either under raised flooring
or above the racks.


Why iBusway for Data Center

A modular solution…
iBusway for Data Centers offers three monitoring levels.

Full pack

Room monitoring & tap-off unit configuration on Magelis


Global
Advanced pack management
system
Measurement of rack power, power rate and circuit- by Schneider
breaker status data available on Twido Electric (ION
Enterprise,
Classic pack
ISX central)
or other
Power distribution to racks by Canalis

… With the best products


from Schneider Electric
Power distribution to the rack
> Canalis KS length & feed units
> Canalis KS plug-in units
> MCB, RCB, Auxiliary (Multi 9 range)
> MCCB Compact NSX breakers

Measurement on the rack


> Energy meters (EN40, PM9-P)
> AS interface (4I Module, bus)
> KBA trunking
> Twido PLCs & power supplies
> MicroLogic (Compact NSX) breakers &
connexions

Room monitoring
> Power supplies
> PLC M340
> Magelis HMI
> Enclosures


Why iBusway for Data Center

iBusway is a key element


of our comprehensive
data centers solution
Schneider Electric is world leader in integrated solutions for data centers:
power distribution, secure power, cooling, pre-wired busbar trunking,
control and monitoring.

MV Switchboard

Main LV Switchboard

UPS

Main LV Switchboard

Advantages
of the solution
Busway distribution

Racks > Optimization of investment: coherent design


Lighting

from the electricity supplier through to the


Racks servers, without need for overbuilding to obtain
PDU
required availability levels.
> Perfect coordination between redundancy
levels, equipment configuration and maintenance
constraints.
> Tested and reliable solutions: complete
technical architectures for operating
dependability, on-site feedback, continual
process improvement, and solution
The comprehensive offering includes: standardization.

> MV and LV switchboards > Map solutions to quantified characteristics:


> Switching and paralleling systems availability, scalability, capital and operating costs.

> Prefabricated busbar trunking > Flexible, scalable solutions for power
distribution, monitoring and control.
> Power monitoring units and protective relays
> Open protocols for monitoring and control.
> Control and monitoring systems
> UPS systems and batteries > Energy efficiency and environmental
conservation.


Presentation Composition of the offer

The solution described in this catalogue satisfies the final electrical distribution needs of the Data Center server racks. It is based on an
architecture consisting of:
b 100A to 400A prefabricated busbar trunking systems,
b 32A to 160A tap-off units,
b An energy monitoring system,
b iBusway for Data Center software.

The scope covered by the solution is the server room.

EN40 / PM9P
Tap-off unit
energy meter

C60 circuit-breaker

iBusway for
Canalis
Data Center software

10
Presentation Composition of the offer

The general principle is to supply the racks by Canalis KS type prefabricated busbar trunking systems, either overhead or via the raised floor.
According to continuity of supply needs, racks are supplied in single or double ways, with supply redundancy in TIER.

Compact NSX Twido PLC +


circuit-breaker AS-Interface system

Magelis screen

Switch M340 PLC

11
Presentation Power distribution

The server racks are supplied with power by Canalis prefabricated busbar trunking
systems.
PD240320

We offer a variety of installation types to meet your needs.


Supply example with 2 Canalis lines

DD230613

A B

This configuration shows a supply with 2 Canalis lines, each line supplying 2 racks
by means of tap-off units.
This type of architecture is recommended for:
b Rack supply safety. Each line distributes at most 50% of the power required for
rack operation. When a supply fault occurs on a Canalis line, the necessary load is
supplied by the remaining line.
Way A Way A Way B
DD230916

DD230917

Way B

Supply with 4 Canalis lines


Way A Way B
DD230918

DD230614

A B A B

This configuration shows a supply with 4 Canalis lines, each line supplying 2 racks
by means of tap-off units.
This type of architecture is recommended for:
b Rack supply safety. Each line distributes at most 50% of the power required for
rack PDU operation.
b An increased number of tap-off outlets, allowing utilization of tap-off units with
fewer feeders.

12
Presentation Power distribution

Example of electrical distribution with the solution iBusway for Data Center
DD230919

LVHQ (1)
Way A

Way B
LVHQ

LVHQ : electrical switchboard (1) : automation enclosure

13
Presentation Metering

b For each rack, the solution allows acquisition of the following:


PD240321

b Consumption, current and power rate of each feeder,


b Status of circuit-breakers of each feeder,
b Current, power rate, voltage, cos φ and total harmonic distortion (THD) of each
line,
b Status of line protection circuit-breakers.

This information is stored and prioritized in the Twido programmed PLC dedicated
to each area (see diagram below).
It is processed by the monitoring module proposed in the Full pack offer or available
in TCP modbus frame exchange format usable by a site global technical
management system.

Consumption is measured directly by EN40 or PM9P energy meters in the tap-off units.
Circuit-breaker status is indicated by SD/OF auxiliaries.
This information is transmitted by the AS-Interface bus to the Twido programmed PLC.

The Canalis lines must be protected by Compact NSX circuit-breakers, allowing measurement of voltage, current, power rate, cos φ and THD.
These data are sent to the Twido programmed PLC by the NSX micrologic module via a modbus protocol.

Block diagram
DD230920

NSX NSX
IFM*

AS-Interface
master modules Twido Programmed PLC

NSX NSX
IFM*

The above diagram shows a area supplied by 4 Canalis lines.

* IFM : MODBUS communication port of the Compact NSX circuit-breaker

14
Presentation Metering
DD230921

NSX NSX
IFM*

AS-Interface
master modules Twido Programmed
PLC

IFM*
NSX NSX

The above diagram shows two areas, each supplied by 2 Canalis lines. Use of the Twido programmed PLC may be extended to the second
area.

* IFM : MODBUS communication port of the Compact NSX circuit-breaker

AS-Interface Modbus Area


bus

A Data Center structure consists of several areas.

A area is made up of two rows of racks separated by an aisle.

For each area, the information from the tap-off units is stored in a metering module.

The metering modules are concentrated in an automation enclosure.

This modular organisation allows adaptation to all Data Center sizes and shapes.

15
Presentation Metering

Composition of the metering module


The metering module consists of:
PD240322

b A Twido programmed PLC,


b An iBusway for Data Center metering software,
b Two AS-Interface master modules,
b One power supply per AS-Interface bus.

The metering module receives information via the AS-Interface bus. This bus has a
maximum length of 200 metres with a line extension.
Twido programmed PLC
The Twido programmed PLC receives information from:
PD240323

b The AS-Interface bus from the tap-off units.


b The Modbus bus from Compact NSX circuit-breakers.
The Twido programmed PLC manages up to 8 Compact NSX circuit-breakers.

The AS-interface and Modbus buses on the same Canalis line must be connected
to the same Twido programmed PLC.

Each Twido programmed PLC can manage up to 2 x 58 AS-Interface input modules.

These AS-Interface input modules are installed in the Canalis tap-off unit.
The number of AS-Interface input modules depends on the number of feeders per
unit (see the tap-off unit choice tables on page 36).
AS-Interface master module

feeder 1L feeder 3L
PD240324

≤40A 1 to 3 feeders 1 AS-Interface module 1 feeder 1 AS-Interface module


≤40A 4 to 6 feeders 2 AS-Interface modules 2 feeders 2 AS-Interface modules

AS-Interface 4-input module


DD230922

100m Max

Line 200m Max


extension

Canalis tap-off unit: feeder protection and metering

16
Presentation Metering

Layout of the metering module


The metering module components are multiplied by the number of areas to be
measured.
DD230635

1
1

2 3

2 3

0: Protection (for a Twido programmed PLC + 2 AS-Interface power supplies)


1: Supply for AS-Interface bus
2: Twido programmed PLC
3: AS-Interface master modules

To determine the size of your enclosure, please refer to the product pages to view the overall dimensions of each device.

17
Presentation Monitoring

b Our monitoring software specifically developed for the iBusway for Data Center
PD240325

solution guarantees a clear vision in real time of your server room:


b Power rate measurement,
b Circuit-breaker status,
b Rack individual consumption,
b Alarm localization.

IT room viewing screen


Use this screen to view your entire IT room divided up into areas, thus ensuring
PD240326

prompt localization and action in event of an alert.

A area moves to orange when a tap-off unit line or feeder attains a power rate
exceeding the logged alert threshold.

The colour red means that a circuit-breaker protecting a tap-off unit line or feeder
has tripped.

Select a area to access the detail of its component parts.

Area viewing screen


Use this screen to view the lines and tap-off units in this area.
PD240327

The line circuit-breaker is shown by a square in the left-hand corner of the touch
screen. Each tap-off unit installed is represented by an identified rectangle.

Components move to orange when they have attained their alert threshold.
The colour red means that a circuit-breaker has tripped.
Select a line or unit to find out circuit-breaker status and power rate.

Line viewing screen


Use this screen to view:
PD240328

b By phase:
v current,
v power rate,
v cos φ,
v THD,
v maximum current.
b By line:
v circuit-breaker status,
v total power.

18
Presentation Monitoring

Feeder viewing screen


Use this screen to view:
PD240329

b Circuit-breaker status,
b Current,
b Power,
b Power rate,
b Maximum current since resetting,
b Consumption since the last reset.

Data are compatible and easy to use by the Schneider Electric ION-E and ISX central systems.

System configuration
When putting the installation into operation or adding new tap-off units, the
PD240330

monitoring system can be configured simply by parameter setting on the touch


screen and requires no specific programming skills.

19
Presentation Monitoring

Solution block diagram


DD230923

NSX NSX
IFM*

MAGELIS touch screen


M340 PLC

AS-Interface Twido Programmed


master modules PLC

Switch

NSX NSX
IFM*

* IFM = MODBUS communication port of the Compact NSX circuit-breaker


AS-Interface Modbus Area Ethernet
bus

The monitoring module can control a server room of up to 12 Twido programmed


PLCs, i.e. approximately 1400 racks.
It consists of:
b A Magelis 15” touch screen with the iBusway for Data Center software,
b An M340 PLC with the iBusway for Data Center software:
v a rack,
v a supply module,
v a CPU,
v two Ethernet cards, including one reserved for the upstream monitoring system.
b Communication accessories,
all contained in the automation enclosure.

The Magelis screen


b Magelis screen = 1 room = 12 Twido PLCs = approximately 1400 racks.
PD240331

M340 PLC
The M340 is a PLC connected to the switch that converts the information sent by the
Twido and sends it to the Magelis screen. It consists of a CPU, a supply module, a
rack and an Ethernet card.
The M340 can manage:
b 1 to 6 Twido programmed PLCs with 1 switch
b 7 to 12 Twido programmed PLCs with 2 switches

20
Presentation Monitoring

Layout of the monitoring components


DD230637

1
0

0: Supply protection
1: Supply
2: M340 PLC
3: Ethernet switch
4: Magelis 15” screen
5: Twido programmed PLC of blue area
6: Twido programmed PLC of orange area

21
Power distribution lines

The aluminium conductors of the Canalis The silver-plated copper contacts based on
prefabricated busbar trunking make it light Copral-inside technology guarantee
weight and easy to handle. The light weight of outstanding life performance.
the Canalis KS simplifies installation and
considerably reduces installation time. You
thus need fewer people and less equipment to
carry out your projects.

22
Power distribution lines Rack supply
Raised floor installation

The power distribution line can be installed either overhead or in a raised floor using a suitable fastening mechanism.
DD230616

If installed in a raised floor, the distribution system is placed in the aisle located between two rows of racks.

The width of this aisle is normally equal to two 60 cm slabs, i.e. 1.2 metres.

In this configuration, the busbar trunking can be installed:


b Flat
b Edgewise.

Example of flat installation Example of edgewise installation


DD230617

DD230618

00
≤ 30
20
00

Whichever installation configuration is chosen, when installing distribution components in a raised floor, allowance must be made for the
overall dimensions of the line and tap-off units making up your installation.

23
Power distribution lines Rack supply
Raised floor installation

Flat configuration
Case 1
PD240333

DD230619
1200
= =

100

500
T2 T2
A B

DD230620 Case 2

1200
= =

100
500

T1 T1 T1 T1
A B A B T1: Small unit
T2: Large unit

The following table shows how tap-off units can be used according to installation of
your network.
KSB32CM55 KSB32CP KSB63SMp8 KSB100SMp8 KSB160SMp24
Case 1 b b b b b
Case 2 b b b b

For more details on tap-off units, refer to page 36

Edgewise configuration
Case 1
PD240334

DD230621

1200
= =
T2

T2

A B

Case 2
DD230622

1200
= =
T1
T1

A
T1
T1

B
T1: Small unit
T2: Large unit

Caution: when installing the units, allow for the necessary space at the cable
outlets, cable glands and sockets.

24
Power distribution lines Rack supply
DD230623
Overhead installation

In an overhead installation, the distribution system is installed above the racks and only in the edgewise (edgewise) configuration.
Edgewise configuration
PD240335

A B A B
DD230624

T2

T1
T1

T2
T2
T2
PD240336

A A A A
DD230625

T1

T1

T1
T1

T1
T1

B B B B
T1

T1

T1
T1

T1
T1

To validate your choice, refer to the tap-off unit pages to confirm their applications according to the dimensional requirements of your
installation.

Caution: when installing the tap-off units, allow for the necessary space at the cable outlets, cable glands and sockets.

25
Power distribution lines Rack supply

A Data Center consists of racks. Racks contain one or more server servers supplied
PD240337

by one or more rack Power Distribution Unit (rack PDU).

The rack PDU are supplied simultaneously by 2 lines, each with a maximum load of
50%.
Should one line fail, the entire load is then supported by the other line.

The size of the tap-off units used depends on several criteria:


b The number of feeders
Server b Feeder power
b Need for residual current protection
PD240338

b Whether or not metering is required

The space available to install the Canalis busbar trunkings may limit use of certain
tap-off units.

Rack PDU

Rack supply example


1 rack PDU
DD230924

3 racks PDU

2 feeders 6 feeders

1 rack PDU

600

26
Power distribution lines Layout

Feed unit
Allowance must be made for the power pack when installing Canalis lines.

There are two possible configurations for flat installation:


b Opposite direction installation,
b Same direction installation.

DD230670

310
DD230694

310
DD230671

430

Connector KSB32CM55
According to the direction in which you install the Canalis lines, a minimum centre
distance makes cable outlets possible.
DD230672

310
DD230673

310

27
Power distribution lines Layout

Disconnector KSB●SM●
A minimum centre distance makes cable outlets possible.

DD230674

400
Disconnector KSB160SM●24
A minimum centre distance makes cable outlets possible.

There are two possible configurations:


b With panel mountings,
b With wander sockets.
DD230675

DD230676

500
600

Panel mountings Wander sockets

28
Power distribution lines Calibres
DD230667
Canalis KS – 100 to 400A

Standard components
KSA pppED4pppp Polarity Rating Length Number of tap-off Part number Weight
3L + N + PE or 3 L + PEN (A) (mm) outlets (kg)
100 3000 12 KSA 100ED43012 12.10
160 3000 12 KSA 160ED43012 13.40
250 3000 12 KSA 250ED43012 15.70
400 3000 12 KSA 400ED43012 20.40

KSA pppED43012
DD230669

Feed unit (supplied with end cover)


Rating Mounting Connection Max. cross- Part number Weight
DD230700

(A) section (mm2) (kg)


Flexible or rigid
100 To right or left Terminals 5 x 16 KSA 100AB4 1.85
100 to To right or left By lugs 240 KSA 250AB4 7.20
250 (M10 screw)
KSA 100AB4 400 To right or left By lugs 2 x 240 KSA 400AB4 8.80
(M10 screw)
KSA 100AB4 KSA 250AB4
DD230677

DD230701

DD230679

KSA 400AB4
DD230678

KSA●●●AB4

Cable exit

29
Power distribution lines Protection
Protections
Compact NSX

Breaking unit
Compact NSX100 4P
DD230659

NSX100F (36 kA 380/415 V LV429008


Compact NSX160 4P
NSX160F (36 kA 380/415 V) LV430408
Compact NSX250 4P
NSX250F (36 kA 380/415 V) LV431408

LV431408
Compact NSX400 4P
DD230660

NSX400F (36 kA 380/415 V) LV432415

LV432415
+ Trip unit
Distribution protection
Micrologic 5.2 E 4P 3d, 4d, 3d + N/2, 3d +
DD230661

(LSI protection, energy metering) OSN


Micrologic 5.2 E 100 A LV429105
Micrologic 5.2 E 160 A LV430496
Micrologic 5.2 E 250 A LV431496
LV432100
Micrologic 5.3 E 4P 3d, 4d, 3d + N/2, 3d +
(LSI protection, energy metering) OSN
Micrologic 6.3 E 400 A LV432100

For 3-pole protection, consult Schneider Electric

Monitoring and control (remote operation)


Circuit-breaker accessory
DD230662

BSCM “Breaker Status and Control” module LV434205

LV434205 ULP communication module


Modbus SL communication interface module TRV00210
DD230663

For DC power supply, see page 51.

TRV00210 ULP cabling accessory


NSX cables, wiring length L = 0.35 m LV434200
DD230664

NSX cables, wiring length L = 1.3 m LV434201

LV434200 NSX cables, wiring length L = 3 m LV434202

10 Modbus communication interface coupling connectors TRV00217


DD230665

10 ULP line caps TRV00880


TRV00217
DD230666

TRV00880

30
Power distribution lines Fastening

Fastening devices
Description Rating Max. load Mounting Sold in Part number Weight
DD230681

(A) (kg) indivisible (kg)


quantity

Fixing bracket(1) 100 to 400 70 Wall or suspended by 10 KSB 400ZF1 0.3


threaded rod
Pendant kit 100 to 400 80 Under ceiling or IPN(1) 4 KSB 400ZFKP1 2.70
Flat fastening All Floor 5 KSA 80EZ5 0.70

KSB 400ZF1 Raised floor fastening kit 600 Floor 4 KSB 400ZFKP2 2.70
500 mm console 600 Edgewise pendant kit 4 KFB CA81500 1.20
DD230685

(1) Maximum recommended fastening centre distance: 3 metres

KSB 400ZF1 KSA 80EZ5


DD210301

DD230686

KSB 400ZFKP1 KSB 400ZFKP2 KSB 400ZFKP1


DD230682

DD230683

DD230684
500

KSB 400ZFKP2
86.4
58.5
DD230688

500

KFB CA81500 KFB CA81500


17
DD230687

100 140
58.5

100
500

31
The tap-off units

Exemple d'un coffret équipé


PD240339

Coffret sectionneur 63 A équipé avec des éléments de protection et de mesure.

b Auxiliary contact SD/OF


b Disjoncteur C60
b Energy meter EN40
b Module 4 entrée AS-Interface

32A connectors for modular circuit-breaker


DD230902

This connector allows mounting of modular devices with up to 5 modules.


Its front face window lets you control and view switchgear status. A transparent flap
guarantees window tightness.

Disconnector units for modular circuit-breaker


DD230903

The front face window lets you control and view switchgear status. A transparent
flap guarantees window tightness.
There are two tap-off ratings:
b 63A for 8 modules
b 100A for 12 modules

32A connector with power sockets


DD230904

These units, equipped with 2 Pratika power sockets, have an 8-module capacity.

160A disconnector unit


DD230905

This unit can be equipped with moving or panel mountings.

It consists of a moving support, accommodating the modular circuit-breaker with up


to 24 modules.

32
The tap-off units

The Canalis tap-off unit consists of:

SD/OF auxiliary contact


PD240340

PD240341

The auxiliary contacts allow remote indication of circuit-breaker status.

b SD auxiliary contact: indicates tripping on circuit-breaker fault


b OF auxiliary contact: indicates circuit-breaker open or closed position.

A test button on the front face of the auxiliary contacts simulates faults without needing to use
the circuit-breaker.

C60 circuit-breaker, C and D curves


PD240342

Circuit overcurrent protection and control (general applications).


The magnetic releases act between 5 and 10 ln in C curve and between 10 and 20 ln in D curve.

A si type Vigi C60 residual current module


PD240343

Ideally suited for operation in environments with:


b High nuisance tripping risks: lightning strokes at close intervals, IT earthing system, presence
of electronic ballasts, presence of switchgear incorporating interference suppression filters of
the lighting, micro-computing type, etc.
b Blinding sources
v presence of harmonics or rejection of high frequencies
v presence of DC components: diodes, diode bridges, switch mode power supplies, etc.

Its use depends on applicable legislation in your country.

EN40 or PM9P energy meter


PD240344

PD240345

The energy meters provide you with information on circuit-breaker energy consumption.
This information is then sent to the metering modules.

Single-phase feeder: use of the EN40 energy meter.

Four-phase feeder:
b Less than or equal to 40A, use of 3 EN40 energy meters
b Greater than 40A, use of a PM9P energy meter and current transformers

AS-Interface 4-input module


PD240346

Input module transferring input information on the AS-Interface bus to the Twido programmed
PLCs.

33
The tap-off units Layout and
tap-off capacity

The number of tap-off units presented below corresponds to an installation on a single side of the Canalis prefabricated busbar trunking system.
This number is doubled for installations in which the tap-off units can be mounted on both sides.

Tap-off units with wander sockets


KSB32CM55(1)
DD230627

KSB63SM●8(1)
DD230628

KSB100SM●12(1)
DD230629

KSB160SM●24(1)
DD230630

Tap-off units with panel mountings


KSB32CP(1)
DD230631

KSB160SM●24(1)
DD230632

(1) For more details on tap-off units, refer to the Canalis 20 to 1000 A prefabricated busbar trunking system catalogue.

: Tapdoors not usable for the type of tap-off.

34
The tap-off units Layout and
tap-off capacity

Without metering With metering


Without vigi With vigi Without vigi With vigi
2P + PE 1 x 32 A feeder 1 x 32 A feeder - -

3P + N + PE 1 x 16 A feeder - -

2P + PE 2 x 63 A feeders 2 x 63 A feeders 2 x 32 A feeders 1 x 32 A feeder

3P + N + PE 2 x 16 A feeders or 1 x 32 A feeder 1 x 32 A feeder -


1 x 63 A feeder

2P + PE 3 x 32 A feeders 3 x 32 A feeders 3 x 32 A feeders 2 x 32 A feeders

3P + N + PE 2 x 63 A feeders

2P + PE 4 x 16A feeders or
6 x 32 A feeders 6 x 32 A feeders 6 x 32 A feeders 4 x 32 A feeders or
2 x 63 A feeders
3P + N + PE 2 x 63 A feeders 2 x 63 A feeders 2 x 63 A feeders

Without metering With metering


Without vigi With vigi Without vigi With vigi
2P + PE 2 x 32 A feeders 2 x 32 A feeders - -

3P + N + PE 2 x 16 A feeders or 1 x 16 A feeder ou
1 x 32 A feeder 1 x 32 A feeder

2P + PE 4 x 16A feeders or
6 x 32 A feeders or 6 x 32 A feeders or 6 x 32 A feeders or 4 x 32 A feeders or
2 x 63 A feeders 2 x 63 A feeders 2 x 63 A feeders 2 x 63 A feeders

3P + N + PE 2 x 32 A feeders or 2 x 32 A feeders or 2 x 32 A feeders or 2 x 32 A feeders or

2 x 63 A feeders 2 x 63 A feeders 2 x 63 A feeders 2 x 63 A feeders

35
The tap-off units Tap-off unit choice tables
with metering
and residual current protection

DD230643

DD230644

DD230645

DD230646

DD230647
Type Current Nb of Sockets(1) KSB32CM55 KSB32CP KSB63SM48 KSB100SM412 KSB160SM424
(A) feeders 5M 8M 8M 12M 24M
2 poles 16 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■
3 WS ■
PM ■
4 WS ■
PM ■
32 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■
63 A 1 WS ■
PM ■
2 WS ■
PM ■
4 poles 16 A 1 WS ■ ■
PM ■
2 WS ■
PM ■
32 A 1 WS ■ ■
PM ■
2 WS ■
PM ■
63 A 1 WS ■
PM ■
2 WS ■
PM ■

36
The tap-off units Tap-off unit choice tables
with metering
and without residual current protection

DD230643

DD230644

DD230645

DD230646

DD230647
Type Current Nb of Sockets(1) KSB32CM55 KSB32CP KSB63SM48 KSB100SM412 KSB160SM424
(A) feeders 5M 8M 8M 12M 24M
2 poles 16 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■ ■
PM ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
32 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■ ■
PM ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
63 A 1 WS ■
PM ■
2 WS ■
PM ■
4 poles 16 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■
32 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■
63 A 1 WS ■
PM ■
2 WS ■
PM ■

37
The tap-off units Tap-off unit choice tables
without metering
with residual current protection

DD230643

DD230644

DD230645

DD230646

DD230647
Type Current Nb of Sockets(1) KSB32CM55 KSB32CP KSB63SM48 KSB100SM412 KSB160SM424
(A) feeders 5M 8M 8M 12M 24M
2 poles 16 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■
PM ■ ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
32 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■
PM ■ ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
63 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■ ■
PM ■
4 poles 16 A 1 WS ■ ■ ■
PM ■ ■
2 WS ■
PM ■
32 A 1 WS ■ ■ ■
PM ■ ■
2 WS ■
PM ■
63 A 1 WS ■ ■
PM ■
2 WS ■
PM ■

38
The tap-off units Tap-off unit choice tables
without metering
and without residual current protection

DD230643

DD230644

DD230645

DD230646

DD230647
Type Current Nb of Sockets(1) KSB32CM55 KSB32CP KSB63SM48 KSB100SM412 KSB160SM424
(A) feeders 5M 8M 8M 12M 24M
2 poles 16 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■ ■
PM ■ ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
32 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■
PM ■ ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
63 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■ ■
PM ■
4 poles 16 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■
PM ■ ■
32 A 1 WS ■ ■ ■
PM ■ ■
2 WS ■ ■
PM ■
63 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■

39
The tap-off units Part numbers
32 to 160 A

Connectors
Disconnection by connector plug-out
Earthing system Busbar trunking TT-TNS-TNC-IT(1)
DD230638

Tap-off TT-TNS-TNS-IT(1)
Tap-off polarity 3L + N + PE(2)
Tap-off diagram

DD230648
(e.g. circuit-breaker protection)

KSB 32CM55 Rating Number Number of Connection Max. cross- Cable gland(4) Part number Weight
(A) of 9mm 18mm(3) section (mm2) (not (kg)
mod. mod. Flexible Rigid supplied)
32 10 5 Pre-wired 6 10 ISO 32 max. KSB 32CM55 0.60

(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system.
(2) Also suitable for 3L + PE tap-off (N not distributed, IT also possible)..
(3) Supplied with blanking plate (1x5 divisible)
(4) Max. diameter for a multipole cable.
KSB 32CM55
DD230649

Cable outlet
Tap-off outlet axis
(5) Surface-mounting dimension

Disconnector units
Disconnection by opening the tap-off unit door
Earthing system Busbar trunking TT-TNS-TNC-IT(1) TNC
DD230639

Tap-off TT-TNS-TNS-IT(1) TNC

Tap-off polarity 3L + N + PE(2) 3L + PEN


Tap-off diagram
DD230650

DD230651

(e.g. circuit-breaker protection)

Rating Number Number of Connection Max. cross- Cable gland(4) Part number Part number Weight
KSB 63SMp8, (A) of 9mm 18m(3) mod. section (mm2) (not (kg)
KSB 100SMp12 mod. Flexible Rigid supplied)
63 16 8 Lugs 16 16 ISO 50 max. KSB 63SM48 KSB 63SM58 2.40

100 24 12 Lugs 35 35 ISO 63 max. KSB 100SM412 KSB 100SM512 5.00

(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system.
(2) Also suitable for 3L + PE tap-off (N not distributed).
(3) Supplied with blanking plate 1x5 divisible (8 modules) or 2x5 divisible (12 modules).
(4) Max. diameter for a multipole cable.
KSB 63SMp8, KSB 100SMp12
DD230652

DD230653

Dim. 63A 100A


A 357 444
B 158 183
C 167 202
D 309 397
E 108 133
F 202 220
X = 432,5 (KSB 63SMp8)
X = 545,5 (KSB 100SM 12)
Cable outlet (5) Surface-mounting dimension
Tap-off outlet axis

40
The tap-off units Part numbers
32 to 160 A

Connector for power sockets


Disconnection by plug-out
Earthing system Busbar trunking TT-TNS-TNC(1)
DD230640

Tap-off TT-TNS-TNS(1)
Tap-off polarity 3L + N + PE
Tap-off diagram The cabling for this

DD230654
(e.g. circuit-breaker protection) tap-off unit
depends on the
power sockets
used

KSB 32CP Rating Number Number of Equipment Current Voltage Part Weight
(A) of 9mm 18mm(2) (A) (V) number (kg)
mod. mod.
32 16 8 Can be equipped with 2 16/32 220/380 KSB 32CP 2.70
Pratika industrial sockets
(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system.
(2) Supplied with blanking plate (1x5 divisible).

KSB 32CPppp
DD230655

Tap-off outlet axis (3) Surface-mounting dimension

Angled socket
Nominal current Nominal voltage Number of Dimensions Part Weight
PD240347

(A) (V CA) poles (l x h in mm) number (kg)


IP44
16 200-250 2P + T 65 x 85 PKY16F423 -
380-415 3P + N + T 90 x 100 PKY16F435 -
PKYppF4pp 32 200-250 2P + T 90 x 100 PKY32F423 -
380-415 3P + N + T 90 x 100 PKY32F435 -
PD240348

IP67
16 200-250 2P + T 65 x 85 PKY16F723 -
380-415 3P + N + T 90 x 100 PKY16F735 -
32 200-250 2P + T 90 x 100 PKY32F723 -
380-415 3P + N + T 90 x 100 PKY32F735 -
PKYppF7pp 63 200-250 2P + T 100 x 107 81278 -
380-415 3P + N + T 100 x 107 81283 -
Wander socket
Nominal current Nominal voltage Number of Part number Weight
PD240349

(A) (V CA) poles (kg)


IP44
16 200-250 2P + T PKY16M423 -
380-415 3P + N + T PKY16M435 -
PKYppFppp 32 200-250 2P + T PKY32M423 -
380-415 3P + N + T PKY32M435 -
IP67
PD240397

16 200-250 2P + T PKY16M723 -
380-415 3P + N + T PKY16M735 -
32 200-250 2P + T PKY32M723 -
380-415 3P + N + T PKY32M735 -
63 200-250 2P + T 81478 -
380-415 3P + N + T 81483 -
Accessory
13137 Equipment Part number Quantity
Socket blanking plate 13137 x1

41
The tap-off units Part numbers
32 to 160 A

Disconnector units
Disconnection by opening the tap-off unit door
Earthing system Busbar trunking TT-TNS-TNC-IT(1) TNC
DD230656

Tap-off TT-TNS-TNS-IT(1) TNC


Tap-off polarity 3L + N + PE(2) 3L + PEN
Tap-off diagram

DD230650

DD230651
(e.g. circuit-breaker protection)

Rating Number Number of Connection Max. cross- Cable gland(4) Part number Part number Weight
KSB160SM424 (A) of 9mm 18mm(3) section (mm2) (not (kg)
mod. mod. Flexible Rigid supplied)
160 48 24 Lugs 16² Not ISO 50 max. KSB160SM424 KSB160SM524 10.69
used

(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system
(2) Also suitable for 3L + PE tap-off (N not distributed).
(3) Supplied with blanking plate 1x5 divisible (8 modules) or 2x5 divisible (12 modules)
(4) Max. diameter for a multipole cable.

KSB160SM424
DD230652

DD230657

303

X = 650

395 177
32 450 230
494 308

Cable outlet
Tap-off outlet axis

42
The tap-off units Modular circuit-breaker
Electrical protection devices

C60 circuit-breakers, C and D curves


16 A, 32 A, 63 A circuit-breakers
PD240350

PD240351

Compliance with standards IEC 60898, IEC 60947-2


Number of poles 2 poles 4 poles
Number of 9mm modules 4 8

24591 24621

Asi Vigi C60 residual current module


Number of poles Voltage (V CA) Rating Sensitivity Part number
PD240350

(A) (mA)
2 poles 230...400 ≤ 25 30 26733
≤ 40 30 26739
≤ 63 30 26813
4 poles 230...400 ≤ 25 30 26737
≤ 40 30 26811
≤ 63 30 26817

26ppp

43
The tap-off units Modular circuit-breaker
Metering devices

Energy meter
EN40 (1L + N)
PD240353

PD240345

Voltage (V Current Tolerance Width in 9mm mod. Part number


CA) (A) (V CA)
230 40 +-20 2 15239

PM9P
Description Voltage Width in 9mm mod. Part number
(V CA)
PM9P 220 to 240 8 15197

15239 15197 Description Current (A) Ratio Part number

Current transformer (toroid) 75 75/5 16452

Description Number of Width in 9mm mod. Part number


poles
C60N circuit-breaker 2 4 24197
2A C curve

Auxiliary contact
SD (fault signal)
PD240354

PD240355

Breaking capacity Width in 9mm mod. Part number


3 A at 415 V AC 1 26927
6 A at 240 V AC

OF (open - closed)
Breaking capacity Width in 9mm mod. Part number
3 A at 415 V AC 1 26924
6 A at 240 V AC

26927 26924
AS-Interface
Asi module with 4 digital inputs
PD240346

DD230658

Addressing type Number of inputs Number and type of Part number


outputs
XZ CE40 Extended A/B 4 - ASI20MT4IE

Description Use Part number


Gland plate seal For flat cable mounting XZ CE40
Sold per batch of 10 tightness in an 11 mm
gland plate (DIN Pg 11)

Description Connection to the AS- Cord Fastening Part number


Interface component length

ASI20MT4IE Tap-off for connection to By stripped wires for 2m To be TCS ATN01N2


a flat cable for terminal block screwed on
AS-Interface (yellow). 2 x 0.34 mm cable
2

Degree of protection Brown wire: AS-Interface+


IP 67 Blue wire: AS-Interface-
DD230699

TCS ATN01N2

44
45
PD240356
Metering and monitoring

The iBusway for Data Center software is an application specifically developed for
management and monitor of IT rooms.

It is used to monitor the tap-off units of the Canalis prefabricated busbar trunking
systems.

46
Metering and monitoring Metering module

KB trunking
Function Sold in Unit part number. Weight
Description
DD230689

indivisible (kg)
quantity
Trunking Width 25 mm, length 3 m 6 KFB 25CD253 1.115
Cable duct support + intermediate support(1) 10 KBB 40ZFG1 0.200
(1) Maximun recommended distance between fixings: 3 meters.
KFB 25CD253 KBB 40ZFG1

KFB 25CD253

DD230690

DD202294
DD210315

KBB 40ZFG1

AS-Interface flat bus and accessories


Description Duct colour IP Length Cable type Part number. Weight
DD230692

(kg)

2 x 1.5mm² flat cables Yellow 67 20 m Standard XZ CB10201 1.400


Ue ≤ 48 V (for AS-Interface) 50 m Standard XZ CB10501 3.500
100 m Standard XZ CB11001 7.000
XZCB1●●01 Sold in Part number Weight
indivisible (Kg)
quantity
Thermo Shrink cable To maintain IP67 degree of tightness at the end 10 ASI 67FACC2 0.002
DD230691

end cover of the AS-Interface cable


Fastening Part number Weight
(Kg)
Line extension To extend segment length by 100 m TCS AAR011M 0.047
ASI67FACC2 Connection by 5-pin socket straight M12 remote To be screwed TCS ATN011F 0.090
connector on
Tap-off for connection to a Tapp-off for AS-Interface cable TCSATN02V
flat cable for AS-Interface
PD240356

XZCB1●●01 TCSAAR01M
10 Ø 19
DD230693

DD230702

2,5
TCSAAR01M
0,5
4
PD240357

37
46

BU – 3,6 BN +
6,5

M12
TCSATN011F

47
Metering and monitoring Metering module

Twido PLC
Number of Sink/source inputs Part number. Weight
I/O (kg)
PD240358

40 E/S a 100…240 V TWD LCAE 40DRF 0.525


- 15 %, + 10 %, 50/60 Hz
2,03 70 157

DD230704

DD230703
TWD LCpAE 40DRF

90
4,5

Programmed card
Description Type Part number Weight
(kg)

Memory card with iBusway for Data Center software EEPROM TWD XCP MFK64S1 0.005
PD240359

AS-Interface master module


TWD XCP MFK64S1 Description Nb modules AS-Interface Number of I/Os Part number Weight
per base profile (kg)

AS-Interface master module for 2 M3, V 2.11 62 max. toroid equipment items TWD NOI 10M3 0.085
Twido bases 7 max. analogue equipment
PD240360

items
70 3,8 23,5
DD230705

90
TWD NOI 10M3

9,4
4,5

Accessories
Name Description Part number Weight
(kg)
PD240392

Modbus RS 485 cords 1 min-DIN connector for Twido controller and 1 RJ45 1m long TWD XCA FD010
connector
External backup battery Sold per unit TSX PLP 01
Sold per batch of 10 TSX PLP 101
Setting console Addressing and diagnostic of AS-Interface V2.1 interfaces ASI TERV2 0.500
Live testing of AS-Interface inputs/outputs
Diagnostic of AS-Interface interfaces

Adaptation cord for ASI TERV2 For addressing products with “Jack” socket ASI TERACC2 0.070
terminal

ASI TERV2

48
Metering and monitoring Metering module

AS-Interface power supply


AS-Interface range Phaseo regulated switch mode power supply
Input voltage Secondary Resetting Earth Reference Weight
PD240361

Output Nominal Nominal auto- fault (kg)


voltage power current protection detection
Single-phase (N-L1) or two-phase (L1-L2) connection
a 100…240 V c 30 V 72 W 2,4 A Auto No ASI ABLB3002 0.800
- 15 %, + 10 %
50/60 Hz

The AS-Interface power supply must be protected by a 2 poles C60 B curve circuit-
breaker.

DD230697
ASI ABLB3002

120
54

49
Metering and monitoring Monitoring module

M340 programmed PLC


Description Part number Weight
(kg)
PD240362

Rack BMXXBP0400 0.630

Description Part number Weight


(kg)
Supply module BMXCPS3500 0.360

Description Part number Weight


(kg)
PD240363

CPU programmed with iBusway BMXP3420ITRB 0.205


for Data Center application

Description Speed Transparent ready Part number Weight


class (kg)
Modbus/TCP Ethernet 10/100 Mbits/s B30 BMXNOE0100 0.200
network module

BMXP3420ITRB 140 242,4


DD230709

DD230708

100
24 VDC 8-port switch
Description Part number Weight
PD240364

(kg)
RJ45 type 8-port switch 499NES18100 0.230

111 47
DD230817

T
E Telemecanique
499NES08100

1 2
p FAULT
1 2 3 4
DA/STAT
5 6 7 8

0 1
FAULT

LA1
LA2
+24V*

LA3
+24V

LA4

499NES18100
LA5
LA6
LA7
LA8
135

135

1 2

3 4

5 6

7 8

Connecting cord
Description Pre-equipped at ends Length Part number Weight
(kg)
Straight copper cords 2 RJ45 type connectors 2 m 490 NTW 000 02 -
For connection to 5m 490 NTW 000 05 -
terminal equipment
12 m 490 NTW 000 12 -
(DTE)

50
Metering and monitoring Monitoring module

Magelis
Screen type Supply voltage Power Part number Weight
PD240331

kg

15” screen multifunction


Touch screen programmed with 24 V c 90W XBGT 7ITRB 5.6
the iBusway for Data Center
application

60
DD230829
XBGT 7ITRB
383

294
282
5 395

Power supply for DC monitoring circuits


Optimum range Phaseo regulated switch-mode power supplies
Input voltage Secondary Reset Conforms to Part number Weight
PD240365

Output Nominal Nominal standard EN (kg)


voltage power current 61000-3-2

Single-phase (N-L1) or two-phase (L1-L2) connection


100...240 V a 24 V c  120 W 5 A Auto No ABL 8RPS24050 1.000
- 15%, + 10%
50/60 Hz
The AS-Interface power supply must be protected by a C60 C curve 5A circuit-breaker.

170
DD230813

125 56
12
125

129

143

AUTO MANU

ABL 8RPS24050 + + – –

6
6

51
The tools

52
The tools

For quotation and installation that satisfy your needs, software quotation tools and installation guides have been
specifically developed for the iBusway for Data Center solution.

The installation guide


This document, to be ordered when carrying
out a project, explains the installation
procedure.
> Installation of lines
> Cabling of tap-off units
> Cabling of the automation enclosure
> Configuration of the iBusway
for Data Center application
> Commissioning

This guide is intended for:


> the panel-builder equipping the tap-off
units,
> the contractor installing,
> the contractor configuring,
> the Data Center operator who will use it to manage his site,
> the maintenance department for site management (adding/modifying tap-off units).

The CanBrass and CanCad applications


These tools, used to design the installation, allow graphic representation of
the Canalis lines and tap-off units. You can use the CanCad application to
represent the layout of the Canalis lines in an AutoCad environment and thus
validate project conformity.

These tools are intended for:


> electrical consultants,
> the Schneider Electric sales agencies accompanying you throughout your
projects.

The iBusway for Data Center quotation


software (Product Selector)
Use this software to calculate solution cost and place your order
with our sales department.

This software is intended for:


> Schneider Electric sales representatives,
> electrical consultants.

Note: The iBusway for Data Center solution consists of standard products.
A large quantity of additional information is available in each product catalogue.

53
The sales references

> Banco Commercial Portugues - Portugal


> BSCH Ciudad Financiera - Spain
> Bahrti, Noida and Pune Data Center, Telecoms - India
> Colt, Telecom & Internet provider - Belgium
> Digiplex Colocation facility - Sweden
> IBM, head quater - Spain, Italy
> MCI-Worldcom, Telecom & Internet provider - UK, Italy
> Interxion, Colocation - Spain, Belgium
> Station switch - Belgium
> Fujitsu - Netherlands
> Pink Roccade SSII IT services - Netherlands
> Reuters World Wide new - Switzerland
> Euroclear transaction bank - Belgium
> ST MicroElectronics semiconductor manufacturer - France
> Kuusitunturi - Finland
> Peugeot, Car manufacturer - France
> Belgacom, Telecom & Internet provider - Belgium
> Safehost colocation - Switzerland
> Eurobank - Greece
> Française Des Jeux - France
> Linxtelecom, Telecom - Russia
> Telenet, Data Center - Belgium
> IBM, Project XIV - Israel
> EMC2, Data Center - India
> La poste, Telecom & internet provider - Luxembourg

54
  ART.837896 © Schneider Electric Industries SAS - All rights reserved

Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask
35, rue Joseph Monier for confirmation of the information given in this publication.
CS 30323
This document has been printed