Ibusway For Data Center: Catalogue
Ibusway For Data Center: Catalogue
iBusway for
Data Center
Catalogue
2010
Contents
2
Why iBusway for Data Center
Adaptable
The iBusway for Data Centers is designed
for facilities from 150 m2 to more than
5,000 m2, with a power supply ranging
from 150 to more than 10,000 kVA.
Why iBusway for Data Center
Storage room
> Ready-to-install
iBusway for Data Centers, tap-off units.
a solution that is…
Facility monitoring
Flexible
room
Its modular format easily adapts to all types of
> Monitor power distribution
data centers offering easy facility upgrading and
and load status.
equipment replacement while also providing
energy consumption measurements.
Interconnected
The local monitoring system gives you a
clear view of your server room in real time:
measurement of load factors, circuit-breaker
status and power consumption for each
individual rack. The system’s compatibility
allows connection to the data center’s overall
monitoring system.
Easy to install
iBusway is a plug and play solution, with all
components pre-wired and tested for fast,
secure setup and software tools simplify
architecture design. Dedicated services for
installation and start-up are also available.
Why iBusway for Data Center
Communication bus
> Quick, reliable connection to the units.
Local
monitoring
HMI
> Provide real-time
information on each
server rack.
Prefabricated electrical
busbar trunking
> Install either under raised flooring
or above the racks.
Why iBusway for Data Center
A modular solution…
iBusway for Data Centers offers three monitoring levels.
Full pack
Room monitoring
> Power supplies
> PLC M340
> Magelis HMI
> Enclosures
Why iBusway for Data Center
MV Switchboard
Main LV Switchboard
UPS
Main LV Switchboard
Advantages
of the solution
Busway distribution
> Prefabricated busbar trunking > Flexible, scalable solutions for power
distribution, monitoring and control.
> Power monitoring units and protective relays
> Open protocols for monitoring and control.
> Control and monitoring systems
> UPS systems and batteries > Energy efficiency and environmental
conservation.
Presentation Composition of the offer
The solution described in this catalogue satisfies the final electrical distribution needs of the Data Center server racks. It is based on an
architecture consisting of:
b 100A to 400A prefabricated busbar trunking systems,
b 32A to 160A tap-off units,
b An energy monitoring system,
b iBusway for Data Center software.
EN40 / PM9P
Tap-off unit
energy meter
C60 circuit-breaker
iBusway for
Canalis
Data Center software
10
Presentation Composition of the offer
The general principle is to supply the racks by Canalis KS type prefabricated busbar trunking systems, either overhead or via the raised floor.
According to continuity of supply needs, racks are supplied in single or double ways, with supply redundancy in TIER.
Magelis screen
11
Presentation Power distribution
The server racks are supplied with power by Canalis prefabricated busbar trunking
systems.
PD240320
DD230613
A B
This configuration shows a supply with 2 Canalis lines, each line supplying 2 racks
by means of tap-off units.
This type of architecture is recommended for:
b Rack supply safety. Each line distributes at most 50% of the power required for
rack operation. When a supply fault occurs on a Canalis line, the necessary load is
supplied by the remaining line.
Way A Way A Way B
DD230916
DD230917
Way B
DD230614
A B A B
This configuration shows a supply with 4 Canalis lines, each line supplying 2 racks
by means of tap-off units.
This type of architecture is recommended for:
b Rack supply safety. Each line distributes at most 50% of the power required for
rack PDU operation.
b An increased number of tap-off outlets, allowing utilization of tap-off units with
fewer feeders.
12
Presentation Power distribution
Example of electrical distribution with the solution iBusway for Data Center
DD230919
LVHQ (1)
Way A
Way B
LVHQ
13
Presentation Metering
This information is stored and prioritized in the Twido programmed PLC dedicated
to each area (see diagram below).
It is processed by the monitoring module proposed in the Full pack offer or available
in TCP modbus frame exchange format usable by a site global technical
management system.
Consumption is measured directly by EN40 or PM9P energy meters in the tap-off units.
Circuit-breaker status is indicated by SD/OF auxiliaries.
This information is transmitted by the AS-Interface bus to the Twido programmed PLC.
The Canalis lines must be protected by Compact NSX circuit-breakers, allowing measurement of voltage, current, power rate, cos φ and THD.
These data are sent to the Twido programmed PLC by the NSX micrologic module via a modbus protocol.
Block diagram
DD230920
NSX NSX
IFM*
AS-Interface
master modules Twido Programmed PLC
NSX NSX
IFM*
14
Presentation Metering
DD230921
NSX NSX
IFM*
AS-Interface
master modules Twido Programmed
PLC
IFM*
NSX NSX
The above diagram shows two areas, each supplied by 2 Canalis lines. Use of the Twido programmed PLC may be extended to the second
area.
For each area, the information from the tap-off units is stored in a metering module.
This modular organisation allows adaptation to all Data Center sizes and shapes.
15
Presentation Metering
The metering module receives information via the AS-Interface bus. This bus has a
maximum length of 200 metres with a line extension.
Twido programmed PLC
The Twido programmed PLC receives information from:
PD240323
The AS-interface and Modbus buses on the same Canalis line must be connected
to the same Twido programmed PLC.
These AS-Interface input modules are installed in the Canalis tap-off unit.
The number of AS-Interface input modules depends on the number of feeders per
unit (see the tap-off unit choice tables on page 36).
AS-Interface master module
feeder 1L feeder 3L
PD240324
100m Max
16
Presentation Metering
1
1
2 3
2 3
To determine the size of your enclosure, please refer to the product pages to view the overall dimensions of each device.
17
Presentation Monitoring
b Our monitoring software specifically developed for the iBusway for Data Center
PD240325
A area moves to orange when a tap-off unit line or feeder attains a power rate
exceeding the logged alert threshold.
The colour red means that a circuit-breaker protecting a tap-off unit line or feeder
has tripped.
The line circuit-breaker is shown by a square in the left-hand corner of the touch
screen. Each tap-off unit installed is represented by an identified rectangle.
Components move to orange when they have attained their alert threshold.
The colour red means that a circuit-breaker has tripped.
Select a line or unit to find out circuit-breaker status and power rate.
b By phase:
v current,
v power rate,
v cos φ,
v THD,
v maximum current.
b By line:
v circuit-breaker status,
v total power.
18
Presentation Monitoring
b Circuit-breaker status,
b Current,
b Power,
b Power rate,
b Maximum current since resetting,
b Consumption since the last reset.
Data are compatible and easy to use by the Schneider Electric ION-E and ISX central systems.
System configuration
When putting the installation into operation or adding new tap-off units, the
PD240330
19
Presentation Monitoring
NSX NSX
IFM*
Switch
NSX NSX
IFM*
M340 PLC
The M340 is a PLC connected to the switch that converts the information sent by the
Twido and sends it to the Magelis screen. It consists of a CPU, a supply module, a
rack and an Ethernet card.
The M340 can manage:
b 1 to 6 Twido programmed PLCs with 1 switch
b 7 to 12 Twido programmed PLCs with 2 switches
20
Presentation Monitoring
1
0
0: Supply protection
1: Supply
2: M340 PLC
3: Ethernet switch
4: Magelis 15” screen
5: Twido programmed PLC of blue area
6: Twido programmed PLC of orange area
21
Power distribution lines
The aluminium conductors of the Canalis The silver-plated copper contacts based on
prefabricated busbar trunking make it light Copral-inside technology guarantee
weight and easy to handle. The light weight of outstanding life performance.
the Canalis KS simplifies installation and
considerably reduces installation time. You
thus need fewer people and less equipment to
carry out your projects.
22
Power distribution lines Rack supply
Raised floor installation
The power distribution line can be installed either overhead or in a raised floor using a suitable fastening mechanism.
DD230616
If installed in a raised floor, the distribution system is placed in the aisle located between two rows of racks.
The width of this aisle is normally equal to two 60 cm slabs, i.e. 1.2 metres.
DD230618
00
≤ 30
20
00
Whichever installation configuration is chosen, when installing distribution components in a raised floor, allowance must be made for the
overall dimensions of the line and tap-off units making up your installation.
23
Power distribution lines Rack supply
Raised floor installation
Flat configuration
Case 1
PD240333
DD230619
1200
= =
100
500
T2 T2
A B
DD230620 Case 2
1200
= =
100
500
T1 T1 T1 T1
A B A B T1: Small unit
T2: Large unit
The following table shows how tap-off units can be used according to installation of
your network.
KSB32CM55 KSB32CP KSB63SMp8 KSB100SMp8 KSB160SMp24
Case 1 b b b b b
Case 2 b b b b
Edgewise configuration
Case 1
PD240334
DD230621
1200
= =
T2
T2
A B
Case 2
DD230622
1200
= =
T1
T1
A
T1
T1
B
T1: Small unit
T2: Large unit
Caution: when installing the units, allow for the necessary space at the cable
outlets, cable glands and sockets.
24
Power distribution lines Rack supply
DD230623
Overhead installation
In an overhead installation, the distribution system is installed above the racks and only in the edgewise (edgewise) configuration.
Edgewise configuration
PD240335
A B A B
DD230624
T2
T1
T1
T2
T2
T2
PD240336
A A A A
DD230625
T1
T1
T1
T1
T1
T1
B B B B
T1
T1
T1
T1
T1
T1
To validate your choice, refer to the tap-off unit pages to confirm their applications according to the dimensional requirements of your
installation.
Caution: when installing the tap-off units, allow for the necessary space at the cable outlets, cable glands and sockets.
25
Power distribution lines Rack supply
A Data Center consists of racks. Racks contain one or more server servers supplied
PD240337
The rack PDU are supplied simultaneously by 2 lines, each with a maximum load of
50%.
Should one line fail, the entire load is then supported by the other line.
The space available to install the Canalis busbar trunkings may limit use of certain
tap-off units.
Rack PDU
3 racks PDU
2 feeders 6 feeders
1 rack PDU
600
26
Power distribution lines Layout
Feed unit
Allowance must be made for the power pack when installing Canalis lines.
DD230670
310
DD230694
310
DD230671
430
Connector KSB32CM55
According to the direction in which you install the Canalis lines, a minimum centre
distance makes cable outlets possible.
DD230672
310
DD230673
310
27
Power distribution lines Layout
Disconnector KSB●SM●
A minimum centre distance makes cable outlets possible.
DD230674
400
Disconnector KSB160SM●24
A minimum centre distance makes cable outlets possible.
DD230676
500
600
28
Power distribution lines Calibres
DD230667
Canalis KS – 100 to 400A
Standard components
KSA pppED4pppp Polarity Rating Length Number of tap-off Part number Weight
3L + N + PE or 3 L + PEN (A) (mm) outlets (kg)
100 3000 12 KSA 100ED43012 12.10
160 3000 12 KSA 160ED43012 13.40
250 3000 12 KSA 250ED43012 15.70
400 3000 12 KSA 400ED43012 20.40
KSA pppED43012
DD230669
DD230701
DD230679
KSA 400AB4
DD230678
KSA●●●AB4
Cable exit
29
Power distribution lines Protection
Protections
Compact NSX
Breaking unit
Compact NSX100 4P
DD230659
LV431408
Compact NSX400 4P
DD230660
LV432415
+ Trip unit
Distribution protection
Micrologic 5.2 E 4P 3d, 4d, 3d + N/2, 3d +
DD230661
TRV00880
30
Power distribution lines Fastening
Fastening devices
Description Rating Max. load Mounting Sold in Part number Weight
DD230681
KSB 400ZF1 Raised floor fastening kit 600 Floor 4 KSB 400ZFKP2 2.70
500 mm console 600 Edgewise pendant kit 4 KFB CA81500 1.20
DD230685
DD230686
DD230683
DD230684
500
KSB 400ZFKP2
86.4
58.5
DD230688
500
100 140
58.5
100
500
31
The tap-off units
The front face window lets you control and view switchgear status. A transparent
flap guarantees window tightness.
There are two tap-off ratings:
b 63A for 8 modules
b 100A for 12 modules
These units, equipped with 2 Pratika power sockets, have an 8-module capacity.
32
The tap-off units
PD240341
A test button on the front face of the auxiliary contacts simulates faults without needing to use
the circuit-breaker.
PD240345
The energy meters provide you with information on circuit-breaker energy consumption.
This information is then sent to the metering modules.
Four-phase feeder:
b Less than or equal to 40A, use of 3 EN40 energy meters
b Greater than 40A, use of a PM9P energy meter and current transformers
Input module transferring input information on the AS-Interface bus to the Twido programmed
PLCs.
33
The tap-off units Layout and
tap-off capacity
The number of tap-off units presented below corresponds to an installation on a single side of the Canalis prefabricated busbar trunking system.
This number is doubled for installations in which the tap-off units can be mounted on both sides.
KSB63SM●8(1)
DD230628
KSB100SM●12(1)
DD230629
KSB160SM●24(1)
DD230630
KSB160SM●24(1)
DD230632
(1) For more details on tap-off units, refer to the Canalis 20 to 1000 A prefabricated busbar trunking system catalogue.
34
The tap-off units Layout and
tap-off capacity
3P + N + PE 1 x 16 A feeder - -
3P + N + PE 2 x 63 A feeders
2P + PE 4 x 16A feeders or
6 x 32 A feeders 6 x 32 A feeders 6 x 32 A feeders 4 x 32 A feeders or
2 x 63 A feeders
3P + N + PE 2 x 63 A feeders 2 x 63 A feeders 2 x 63 A feeders
3P + N + PE 2 x 16 A feeders or 1 x 16 A feeder ou
1 x 32 A feeder 1 x 32 A feeder
2P + PE 4 x 16A feeders or
6 x 32 A feeders or 6 x 32 A feeders or 6 x 32 A feeders or 4 x 32 A feeders or
2 x 63 A feeders 2 x 63 A feeders 2 x 63 A feeders 2 x 63 A feeders
35
The tap-off units Tap-off unit choice tables
with metering
and residual current protection
DD230643
DD230644
DD230645
DD230646
DD230647
Type Current Nb of Sockets(1) KSB32CM55 KSB32CP KSB63SM48 KSB100SM412 KSB160SM424
(A) feeders 5M 8M 8M 12M 24M
2 poles 16 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■
3 WS ■
PM ■
4 WS ■
PM ■
32 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■
63 A 1 WS ■
PM ■
2 WS ■
PM ■
4 poles 16 A 1 WS ■ ■
PM ■
2 WS ■
PM ■
32 A 1 WS ■ ■
PM ■
2 WS ■
PM ■
63 A 1 WS ■
PM ■
2 WS ■
PM ■
36
The tap-off units Tap-off unit choice tables
with metering
and without residual current protection
DD230643
DD230644
DD230645
DD230646
DD230647
Type Current Nb of Sockets(1) KSB32CM55 KSB32CP KSB63SM48 KSB100SM412 KSB160SM424
(A) feeders 5M 8M 8M 12M 24M
2 poles 16 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■ ■
PM ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
32 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■ ■
PM ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
63 A 1 WS ■
PM ■
2 WS ■
PM ■
4 poles 16 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■
32 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■
63 A 1 WS ■
PM ■
2 WS ■
PM ■
37
The tap-off units Tap-off unit choice tables
without metering
with residual current protection
DD230643
DD230644
DD230645
DD230646
DD230647
Type Current Nb of Sockets(1) KSB32CM55 KSB32CP KSB63SM48 KSB100SM412 KSB160SM424
(A) feeders 5M 8M 8M 12M 24M
2 poles 16 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■
PM ■ ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
32 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■
PM ■ ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
63 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■ ■
PM ■
4 poles 16 A 1 WS ■ ■ ■
PM ■ ■
2 WS ■
PM ■
32 A 1 WS ■ ■ ■
PM ■ ■
2 WS ■
PM ■
63 A 1 WS ■ ■
PM ■
2 WS ■
PM ■
38
The tap-off units Tap-off unit choice tables
without metering
and without residual current protection
DD230643
DD230644
DD230645
DD230646
DD230647
Type Current Nb of Sockets(1) KSB32CM55 KSB32CP KSB63SM48 KSB100SM412 KSB160SM424
(A) feeders 5M 8M 8M 12M 24M
2 poles 16 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■ ■
PM ■ ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
32 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■
PM ■ ■
3 WS ■ ■
PM ■
4 WS ■
PM ■
6 WS ■
PM ■
63 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■ ■
PM ■
4 poles 16 A 1 WS ■ ■ ■ ■
PM ■ ■
2 WS ■ ■ ■
PM ■ ■
32 A 1 WS ■ ■ ■
PM ■ ■
2 WS ■ ■
PM ■
63 A 1 WS ■ ■ ■
PM ■
2 WS ■ ■
PM ■
39
The tap-off units Part numbers
32 to 160 A
Connectors
Disconnection by connector plug-out
Earthing system Busbar trunking TT-TNS-TNC-IT(1)
DD230638
Tap-off TT-TNS-TNS-IT(1)
Tap-off polarity 3L + N + PE(2)
Tap-off diagram
DD230648
(e.g. circuit-breaker protection)
KSB 32CM55 Rating Number Number of Connection Max. cross- Cable gland(4) Part number Weight
(A) of 9mm 18mm(3) section (mm2) (not (kg)
mod. mod. Flexible Rigid supplied)
32 10 5 Pre-wired 6 10 ISO 32 max. KSB 32CM55 0.60
(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system.
(2) Also suitable for 3L + PE tap-off (N not distributed, IT also possible)..
(3) Supplied with blanking plate (1x5 divisible)
(4) Max. diameter for a multipole cable.
KSB 32CM55
DD230649
Cable outlet
Tap-off outlet axis
(5) Surface-mounting dimension
Disconnector units
Disconnection by opening the tap-off unit door
Earthing system Busbar trunking TT-TNS-TNC-IT(1) TNC
DD230639
DD230651
Rating Number Number of Connection Max. cross- Cable gland(4) Part number Part number Weight
KSB 63SMp8, (A) of 9mm 18m(3) mod. section (mm2) (not (kg)
KSB 100SMp12 mod. Flexible Rigid supplied)
63 16 8 Lugs 16 16 ISO 50 max. KSB 63SM48 KSB 63SM58 2.40
(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system.
(2) Also suitable for 3L + PE tap-off (N not distributed).
(3) Supplied with blanking plate 1x5 divisible (8 modules) or 2x5 divisible (12 modules).
(4) Max. diameter for a multipole cable.
KSB 63SMp8, KSB 100SMp12
DD230652
DD230653
40
The tap-off units Part numbers
32 to 160 A
Tap-off TT-TNS-TNS(1)
Tap-off polarity 3L + N + PE
Tap-off diagram The cabling for this
DD230654
(e.g. circuit-breaker protection) tap-off unit
depends on the
power sockets
used
KSB 32CP Rating Number Number of Equipment Current Voltage Part Weight
(A) of 9mm 18mm(2) (A) (V) number (kg)
mod. mod.
32 16 8 Can be equipped with 2 16/32 220/380 KSB 32CP 2.70
Pratika industrial sockets
(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system.
(2) Supplied with blanking plate (1x5 divisible).
KSB 32CPppp
DD230655
Angled socket
Nominal current Nominal voltage Number of Dimensions Part Weight
PD240347
IP67
16 200-250 2P + T 65 x 85 PKY16F723 -
380-415 3P + N + T 90 x 100 PKY16F735 -
32 200-250 2P + T 90 x 100 PKY32F723 -
380-415 3P + N + T 90 x 100 PKY32F735 -
PKYppF7pp 63 200-250 2P + T 100 x 107 81278 -
380-415 3P + N + T 100 x 107 81283 -
Wander socket
Nominal current Nominal voltage Number of Part number Weight
PD240349
16 200-250 2P + T PKY16M723 -
380-415 3P + N + T PKY16M735 -
32 200-250 2P + T PKY32M723 -
380-415 3P + N + T PKY32M735 -
63 200-250 2P + T 81478 -
380-415 3P + N + T 81483 -
Accessory
13137 Equipment Part number Quantity
Socket blanking plate 13137 x1
41
The tap-off units Part numbers
32 to 160 A
Disconnector units
Disconnection by opening the tap-off unit door
Earthing system Busbar trunking TT-TNS-TNC-IT(1) TNC
DD230656
DD230650
DD230651
(e.g. circuit-breaker protection)
Rating Number Number of Connection Max. cross- Cable gland(4) Part number Part number Weight
KSB160SM424 (A) of 9mm 18mm(3) section (mm2) (not (kg)
mod. mod. Flexible Rigid supplied)
160 48 24 Lugs 16² Not ISO 50 max. KSB160SM424 KSB160SM524 10.69
used
(1) The neutral must be protected or not distributed (3L + PE) for the IT earthing system
(2) Also suitable for 3L + PE tap-off (N not distributed).
(3) Supplied with blanking plate 1x5 divisible (8 modules) or 2x5 divisible (12 modules)
(4) Max. diameter for a multipole cable.
KSB160SM424
DD230652
DD230657
303
X = 650
395 177
32 450 230
494 308
Cable outlet
Tap-off outlet axis
42
The tap-off units Modular circuit-breaker
Electrical protection devices
PD240351
24591 24621
(A) (mA)
2 poles 230...400 ≤ 25 30 26733
≤ 40 30 26739
≤ 63 30 26813
4 poles 230...400 ≤ 25 30 26737
≤ 40 30 26811
≤ 63 30 26817
26ppp
43
The tap-off units Modular circuit-breaker
Metering devices
Energy meter
EN40 (1L + N)
PD240353
PD240345
PM9P
Description Voltage Width in 9mm mod. Part number
(V CA)
PM9P 220 to 240 8 15197
Auxiliary contact
SD (fault signal)
PD240354
PD240355
OF (open - closed)
Breaking capacity Width in 9mm mod. Part number
3 A at 415 V AC 1 26924
6 A at 240 V AC
26927 26924
AS-Interface
Asi module with 4 digital inputs
PD240346
DD230658
TCS ATN01N2
44
45
PD240356
Metering and monitoring
The iBusway for Data Center software is an application specifically developed for
management and monitor of IT rooms.
It is used to monitor the tap-off units of the Canalis prefabricated busbar trunking
systems.
46
Metering and monitoring Metering module
KB trunking
Function Sold in Unit part number. Weight
Description
DD230689
indivisible (kg)
quantity
Trunking Width 25 mm, length 3 m 6 KFB 25CD253 1.115
Cable duct support + intermediate support(1) 10 KBB 40ZFG1 0.200
(1) Maximun recommended distance between fixings: 3 meters.
KFB 25CD253 KBB 40ZFG1
KFB 25CD253
DD230690
DD202294
DD210315
KBB 40ZFG1
(kg)
XZCB1●●01 TCSAAR01M
10 Ø 19
DD230693
DD230702
2,5
TCSAAR01M
0,5
4
PD240357
37
46
BU – 3,6 BN +
6,5
M12
TCSATN011F
47
Metering and monitoring Metering module
Twido PLC
Number of Sink/source inputs Part number. Weight
I/O (kg)
PD240358
DD230704
DD230703
TWD LCpAE 40DRF
90
4,5
Programmed card
Description Type Part number Weight
(kg)
Memory card with iBusway for Data Center software EEPROM TWD XCP MFK64S1 0.005
PD240359
AS-Interface master module for 2 M3, V 2.11 62 max. toroid equipment items TWD NOI 10M3 0.085
Twido bases 7 max. analogue equipment
PD240360
items
70 3,8 23,5
DD230705
90
TWD NOI 10M3
9,4
4,5
Accessories
Name Description Part number Weight
(kg)
PD240392
Modbus RS 485 cords 1 min-DIN connector for Twido controller and 1 RJ45 1m long TWD XCA FD010
connector
External backup battery Sold per unit TSX PLP 01
Sold per batch of 10 TSX PLP 101
Setting console Addressing and diagnostic of AS-Interface V2.1 interfaces ASI TERV2 0.500
Live testing of AS-Interface inputs/outputs
Diagnostic of AS-Interface interfaces
Adaptation cord for ASI TERV2 For addressing products with “Jack” socket ASI TERACC2 0.070
terminal
ASI TERV2
48
Metering and monitoring Metering module
The AS-Interface power supply must be protected by a 2 poles C60 B curve circuit-
breaker.
DD230697
ASI ABLB3002
120
54
49
Metering and monitoring Monitoring module
DD230708
100
24 VDC 8-port switch
Description Part number Weight
PD240364
(kg)
RJ45 type 8-port switch 499NES18100 0.230
111 47
DD230817
T
E Telemecanique
499NES08100
1 2
p FAULT
1 2 3 4
DA/STAT
5 6 7 8
0 1
FAULT
LA1
LA2
+24V*
LA3
+24V
LA4
499NES18100
LA5
LA6
LA7
LA8
135
135
1 2
3 4
5 6
7 8
Connecting cord
Description Pre-equipped at ends Length Part number Weight
(kg)
Straight copper cords 2 RJ45 type connectors 2 m 490 NTW 000 02 -
For connection to 5m 490 NTW 000 05 -
terminal equipment
12 m 490 NTW 000 12 -
(DTE)
50
Metering and monitoring Monitoring module
Magelis
Screen type Supply voltage Power Part number Weight
PD240331
kg
60
DD230829
XBGT 7ITRB
383
294
282
5 395
170
DD230813
125 56
12
125
129
143
AUTO MANU
ABL 8RPS24050 + + – –
6
6
51
The tools
52
The tools
For quotation and installation that satisfy your needs, software quotation tools and installation guides have been
specifically developed for the iBusway for Data Center solution.
Note: The iBusway for Data Center solution consists of standard products.
A large quantity of additional information is available in each product catalogue.
53
The sales references
54
ART.837896 © Schneider Electric Industries SAS - All rights reserved
Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask
35, rue Joseph Monier for confirmation of the information given in this publication.
CS 30323
This document has been printed