You are on page 1of 9

String Report for: Telmex | Metro | Culh 01f | Bb3alpha on 02/02/2022 10:29:45 Page: 1

02/02/2022 14:19:34

String Information Test Information


Site Name: Telmex | Metro | Culh 01f Test Start Date: 02/02/2022 10:29:45
String ID: Bb3alpha Operator:
# of Batteries: 24 Float Voltage:
Float Current:

String Specific Battery Details Battery Definition Test Settings


# of Straps: 0 Manufacturer: Gnb Noise Filtering: Auto
Float: On Model: 100G33 Polarity Correction: On
Voltage Reference/Cell: 2.230 Cell Type: Lead Acid (AGM) Battery Test Start: Auto
Voltage Reference/Battery: 2.230 Capacity: 1600.0 (Ah) Strap Test Start: Auto
# of Cells/Battery: 1 Auto Start Delay: 1
Test Level: Battery

Baseline Information Test Parameters Hardware Settings


Impedance Reference: 0.201 (mΩ) Impedance Serial Number: EC2000-1103496
ACF: 1.268 Voltage MAC Address: 00:0D:15:00:A8:5E
Baseline Type: Auto Generated in EC2000 CELScan Hardware Version: 19333301
(Sulfation/Dryout)
Baselined from Test Date: 02/02/2022 10:29:45 Firmware Version: 2.1.8
Data Origin: EC2000

Applied Alarms

Impedance (%) Voltage (V/Cell) Sulfation (%) Dryout (%) Strap (%)
High Fail 125.0 2.35 20 20 Undefined
High Warn 117.0 2.30 15 15 Undefined
Low Warn 70.0 2.20
Low Fail 50.0 2.15
String Report for: Telmex | Metro | Culh 01f | Bb3alpha on 02/02/2022 10:29:45 Page: 2
02/02/2022 14:19:34

Impedance (mΩ)
Healthy High Fail: 125.0% High Warn: 117.0% Low Warn: 70.0% Low Fail: 50.0%

26
24
22
20
Impedance (mΩ)

18
16
14
12
10
8
6
4
2
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb3alpha on 02/02/2022 10:29:45 Page: 3
02/02/2022 14:19:34

Voltage (V)
Healthy High Fail: 2.35 V/Cell High Warn: 2.30 V/Cell Low Warn: 2.20 V/Cell Low Fail: 2.15 V/Cell

3.6
3.4
Voltage (V/Battery)

3.2
3
2.8
2.6
2.4
2.2
2
1.8
1.6
1.4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb3alpha on 02/02/2022 10:29:45 Page: 4
02/02/2022 14:19:34

Sulfation (%)
Healthy High Fail: 20% High Warn: 15%

90
80
70
Sulfation (%)

60
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb3alpha on 02/02/2022 10:29:45 Page: 5
02/02/2022 14:19:34

Dryout (%)
Healthy High Fail: 20% High Warn: 15%
200
180
160
140
Dryout (%)

120
100
80
60
40
20
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb3alpha on 02/02/2022 10:29:45 Page: 6
02/02/2022 14:19:34

Temperature (°C)

100
90
80
Temperature (°C)

70
60
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb3alpha on 02/02/2022 10:29:45 Page: 7
02/02/2022 14:19:34

Battery # Result Impedance Impedance (%) Voltage Sulfation Dryout Temperature


(mΩ) (Population Ref.) (V) (%) (%) (°C)
1 Fail 13.700 6801.8 2.983 0 100 26.8
2 Pass 0.206 102.5 2.210 0 0 26.8
3 Fail 0.501 248.6 2.227 0 30 26.8
4 Fail 0.326 161.6 2.213 20 0 26.8
5 Pass 0.203 101.0 2.208 0 0 26.8
6 Fail 0.391 194.3 2.214 29 0 26.8
7 Fail 0.496 246.3 2.216 46 25 26.8
8 Warning 0.246 122.0 2.215 5 0 26.8
9 Pass 0.222 110.3 2.220 0 0 26.8
10 Pass 0.232 115.0 2.212 1 0 26.8
11 Fail 0.463 229.8 2.222 39 0 26.8
12 Warning 0.243 120.6 2.219 3 0 26.8
13 Pass 0.235 116.5 2.216 2 0 26.8
14 Pass 0.232 115.2 2.219 2 0 26.8
15 Warning 0.236 117.1 2.214 1 0 26.8
16 Pass 0.186 92.2 2.223 0 0 26.8
17 Pass 0.201 100.0 2.222 0 0 26.8
18 Pass 0.234 116.4 2.219 2 0 26.8
19 Fail 0.481 238.7 2.224 41 0 26.8
20 Warning 0.245 121.7 2.215 3 0 26.8
21 Fail 0.366 181.6 2.213 22 0 26.8
22 Fail 6.338 3146.7 2.207 0 100 26.8
23 Fail 0.654 324.5 2.221 0 40 26.8
24 Fail 1.162 577.1 2.219 0 87 26.8
String Report for: Telmex | Metro | Culh 01f | Bb3alpha on 02/02/2022 10:29:45 Page: 8
02/02/2022 14:19:34

Battery # Installation Manufactured Replaced


Date Date
1 No
2 No
3 No
4 No
5 No
6 No
7 No
8 No
9 No
10 No
11 No
12 No
13 No
14 No
15 No
16 No
17 No
18 No
19 No
20 No
21 No
22 No
23 No
24 No
String Report for: Telmex | Metro | Culh 01f | Bb3alpha on 02/02/2022 10:29:45 Page: 9
02/02/2022 14:19:34

Summary
Test Summary
Test Start Date & Time: 02/02/2022 10:29:45
Test End Date & Time: 02/02/2022 10:40:40
Total Number of Batteries Tested: 24
Number of Batteries Passed: 9
Number of Batteries Failed: 11
Number of Batteries Warned: 4

Test Statistics

Coefficient of
Maximum Minimum Mean Std. Deviation Variation %
Impedance (mΩ): 13.700 0.186 1.158 2.883 248.9
Impedance (%) (Population-referenced): 6801.8 92.2 575.1 1431.2 248.9
Voltage (V): 2.983 2.207 2.249 0.153 6.8
Temperature (°C): 26.8 26.8 26.8 0.0 0.0
Sulfation (%): 46 0
Dryout (%): 100 0