You are on page 1of 1

FM 200 FIRE SUPPRESSION SYSTEM

Smoke Detector
Max. Area covered = 150ft²

Fire Hazard Classes

Class A – Fire in ordinary combustible materials such as wood, cloth, paper, rubber, and plastics.
Class B – Fire in flammable liquids
Class C – Fire involves energized electrical equipment

Volumetric Design Concentration & Safety Factor

Fire Hazard Classes Design Concentration Safety Factor

Class A 6.70 % 1.2


Class B 8.97% 1.3
Class C 7.20% 1.2

Amount of FM – 200 required

W = V/S * (C /100 - C)

W = Weight (FM200) in lbs.


V = Protected space volume (L * W * H)
C = FM200 Volumetric Design Concentration
S = Specific vapor volume in ft³/lbs;
S = 1.885 + (0.0046 * T) – English System
S = 0.1269 + (0.005*T) – SI unit
Where T = minimum Temperature

Final Design Concentration


C = Design Concentration * Safety Factor

Number of Discharge Nozzle


Protected Area
No . of nozzles=
Area covered per nozzle