A1-03 2 POLE, 10A DC MCB FOR TRIP CIRCUIT, 110V DC. ABB 1
A1-17 4 POLE 4A AC MCB WITH ADD ON BLOCK FOR PT CORE-II CIRCUIT, 110V AC ABB 1
COMBINED SWITCH BOX WITH 3NOS. SWITCHES AND 1NO. 5-PIN SOCKET, 230V AC,
A3-01 ANCHOR/PRESSFIT 1
SW-1 FOR PANEL ILLUMINATION LAMP, SW-2 FOR SPACE HEATER, SW-3 FOR 5-PIN SOCKET.
B10-01 2 POLE, 6A AC MCB FOR MOTOR CIRCUIT, 230V AC. ABB 1
B10-02 2 POLE 16A DC MCB FOR DC CONTROL CIRCUIT, 110V DC. ABB 1
B10-03A 2 POLE 16A AC MCB FOR UPS AC SUPPLY, 230V AC. ABB 1
B10-04 THERMOSTAT, SETTING : 0-75 DEG. CEN. 20A, 230V AC, 50 HZ. APT CONTROLS 1
B10-07 ILLUMININATION LED LAMP 3W, AUX. VOLTAGE: 230V AC. WIPRO/PHILIPS 1
AUXILIARY CONTACTOR WITH CONTACT : 2NO+ 2NC , AUX VOLTAGE : 230V AC , FOR AC CHANGE OVER
B10-08 L&T/SIEMENS/ABB 1
CIRCUIT
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 2 C/O S/R,
B10-09 ABB 1
AUX. VOLTAGE : 110V DC, FOR SPRING CHARGE CIRCUIT.
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 2 C/O S/R,
B10-10 ABB 1
AUX. VOLTAGE : 110V DC, FOR ANTIPUMPING CIRCUIT (94).
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 2 C/O S/R,
B10-11 ABB 1
AUX. VOLTAGE : 110V DC, FOR DC FAIL CIRCUIT (80D).
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 2 C/O S/R,
B10-13 ABB 1
AUX. VOLTAGE : 24V DC, FOR SCADA CLOSE.
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 2 C/O S/R,
B10-14 ABB 1
AUX. VOLTAGE : 24V DC, FOR SCADA TRIP.
B10-16 POWER PACK UNIT INPUT- 230V AC, OUTPUT - 110V DC, BATTERY BACKUP=60MIN ALAN 1
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 4 C/O S/R,
B10-17 ABB 1
AUX. VOLTAGE : 110V DC, FOR (BUCHOLZ) # TRIP (63T).
BILL OF MATERIAL
DRAWN BY: BP
0
CHECKED BY: VT
0 FIRST SUBMISSION 19-01-2022 APPROVD BY: SG
ICOG
LOCATION DESCRIPTION MAKE PANEL
(QTY 1NO.)
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 2 C/O S/R,
B10-18 ABB 1
AUX. VOLTAGE : 110V DC, FOR (BUCHOLZ) # ALARM (63A).
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 4 C/O S/R,
B10-19 ABB 1
AUX. VOLTAGE : 110V DC, FOR (OIL. TEMP. HIGH) # TRIP (26T).
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 2 C/O S/R,
B10-20 ABB 1
AUX. VOLTAGE : 110V DC, FOR (OIL TEMP. HIGH) # ALARM (26A).
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 4 C/O S/R,
B10-21 ABB 1
AUX. VOLTAGE : 110V DC, FOR (WDG TEMP. HIGH) # TRIP (49T).
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 2 C/O S/R,
B10-22 ABB 1
AUX. VOLTAGE : 110V DC, FOR (WDG TEMP. HIGH) # ALARM (49A).
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 4 C/O S/R,
B10-23 ABB 1
AUX. VOLTAGE : 110V DC, FOR (PRV) # TRIP (63X-1).
TYPE: CRM, SINGLE ELEMENT AUX. RELAY WITH CONTACTS: 2 C/O S/R,
B10-24 ABB 1
AUX. VOLTAGE : 110V DC, FOR (MOG) # ALARM (63X-2).
B10-30 RESISTOR, 50 OHM, 200W USED FOR DELTA CONNECTED PT. K2 1
DIGITAL AMMETER WITH BUILT IN SELECTOR SWITCH , CTR PROGRAMMABLE In:1A AUX. VOLTAGE ELEMEASURE/RISHABH/S
D5-21 1
:110VDC,ACC CLASS 0.5 ,SIZE:96X96 ECURE
DIGITAL VOLTMETER WITH BUILT IN SELECTOR SWITCH , CTR PROGRAMMABLE In:1A AUX. VOLTAGE ELEMEASURE/RISHABH/S
D5-22 1
:110VDC,ACC CLASS 0.5 ,SIZE:96X96 ECURE
BILL OF MATERIAL
1
1 REVISED AS PER COMMENTS 22-01-2022 DRAWN BY: BP
D5-42 LED LAMP, GREEN COLOUR LENS, SUITABLE FOR 110V DC BREAKER OFF. TEKNIC/L&T 1
D5-43 LED LAMP, AMBER COLOUR LENS, SUITABLE FOR 110V DC AUTO TRIP. TEKNIC/L&T 1
D5-44 LED LAMP, WHITE COLOUR LENS, SUITABLE FOR 110V DC TRIP CIRCUIT HEALTHY. TEKNIC/L&T 1
D5-47 LED LAMP, RED COLOUR LENS, SUITABLE FOR 63.5V AC R-PHASE HEALTHY. TEKNIC/L&T 1
D5-48 LED LAMP, YELLOW COLOUR LENS, SUITABLE FOR 63.5V AC Y-PHASE HEALTHY. TEKNIC/L&T 1
D5-49 LED LAMP, BLUE COLOUR LENS, SUITABLE FOR 63.5V AC B-PHASE HEALTHY. TEKNIC/L&T 1
D5-50 LED LAMP, BLUE COLOUR LENS, SUITABLE FOR 110V DC SPRING CHARGE. TEKNIC/L&T 1
D5-51 LED LAMP, GREEN COLOUR LENS, SUITABLE FOR 110V DC BREAKER IN TEST. TEKNIC/L&T 1
D5-52 LED LAMP, RED COLOUR LENS, SUITABLE FOR 110V DC BREAKER IN SERVICE. TEKNIC/L&T 1
D5-53 LED LAMP, RED COLOUR LENS, SUITABLE FOR 230V AC, FOR DC FAIL. TEKNIC/L&T 1
PUSH BUTTON, MUSHROOM HEAD TYPE, STAYPUT, RED COLOUR WITH
D5-62 TEKNIC/L&T 1
1NO+1NC ELEMENT FOR EMERGENCY TRIP, PRESS TO LOCK & TWIST TO RELEASE.
12-WINDOW ALARM ANNUNCIATOR WITH DC FAIL FUNCTION (30), FOR BOTH TRIP & NONTRIP ALARM, WITH
D5-71 BUILT IN, ACCEPT, RESET, TEST PUSH BUTTONS, AUX. VOLTAGE: 110V DC, ALAN 1
WITH MODBUS PROTOCOL-RS485 PORT.
D5-72 TWO TONE HOOTER, AUX. VOLTAGE: 110V DC, SIZE 96X96mm. ALAN 1
D5-72A TWO TONE HOOTER, AUX. VOLTAGE: 230V AC, SIZE 96X96mm. ALAN 1
BILL OF MATERIAL
0
DRAWN BY: BP
F02-14 1 PHASE CONTROL TRANSFORMER, RATING: 1000VA, RATIO: 22kV/RT3 /230V AC. PRAGATI/ECS 1
F10-03 SPACE HEATER 230V AC, 100W, (FOR BREAKER COMPARTMENT). APT CONTROLS 1
BILL OF MATERIAL
1
1 REVISED AS PER COMMENTS 24-01-2022 DRAWN BY: BP