Set No Lift 

  (cm) Water     ∆P Actuator     ∆P


flow rate (manom P (manom
(LPH) eter) (kg/cm²) eter)
(mm (bar)    Cv (max)
H₂o)   

1 0 515 109.4 0 0.010728 1.82388


2 4 435 119.4 0.36 0.011709 1.474636
3 8 310 126.8 0.56 0.012435 1.019764
4 12 200 132.2 0.7 0.012964 0.644335
5 16 130 135.2 0.85 0.013259 0.414145
6 20 85 136.6 0.95 0.013396 0.285452
7 24 50 137.2 1.1 0.013455 0.158121
8 20 90 136.4 0.9 0.013376
9 16 130 135.8 0.8 0.013317
10 12 190 133.4 0.65 0.013082
11 8 290 128 0.5 0.012553
12 4 420 118.2 0.4 0.011591
13 0 510 108.4 0 0.01063

Installed Character
600

500

400
Flowrate (LPH)

300

200

100

0
0 5 10 15
Lift (cm)
Lift   (cm)

Cv (min) Cv (max) Inherent Ch


2
Hysteresis 1.8
1.814484 0.515165 0 1.82388 1.6
1.430995 2.959442 4 1.474636 1.4

Valve Coefficient
0.949491 6.891104 8 1.019764 1.2
0.609359 5.428232 12 0.644335 1
16 0.8
0.413229 0.221179 0.414145
0.6
0.269396 5.624764 20 0.285452
0.4
0.158121 0 24 0.158121
0.2
0
0 5 10

Installed Characteristics

Actuator
P Cv (max) Cv (min)
(kg/cm²)
0 1.82388 1.814484
0.36 1.474636 1.430995
0.56 1.019764 0.949491
0.7 0.644335 0.609359
5 10 15 20 25 30 0.85 0.414145 0.413229
Lift (cm) 0.95 0.285452 0.269396
1.1 0.158121 0.158121
Inherent Characterisitics

0 5 10 15 20 25 30
Lift (cm)

Hysteresis Characteristics
2
1.8
1.6
1.4
Valve Coefficient

1.2
1
0.8
0.6
0.4
0.2
0
0 0.2 0.4 0.6 0.8 1 1.2
Actuator Pressure (kg/cm2)

Cv (max) Cv (min)