Professional Documents
Culture Documents
GAS REFERENCE
PACKAGE
1
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
Visual inspection
The main reasons for incomplete combustion
1. Lack of oxygen (soft yellow flames)
2. Incorrect burner pressure (over gassed / under gassed)
3. Flame impingement (flame chilling)
A good pre-aerated flame should be bright blue with a strong inner and outer cone,
and above all will have a roar. If there is any yellow in the flame then it is incorrect.
(Do not mistake yellow for orange, as orange flames are usually dust being burnt.)
Procedure for carrying out a service with the aid of a Combustion Analyser.
If unacceptable:
If possible rectify fault(s) then re test
If not possible follow the unsafe situations guidelines.
At Risk for flued appliances
Immediately Dangerous for Flueless appliances.
2
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
BS 7967-3
APPLIANCE TYPE CO/CO2 RATIO
Back boiler unit Boiler 0.008
In combination with fire 0.020
Central heating boiler 0.008
Hot water circulator 0.010
Flued space heater 0.020 (check man instructions)
Flueless space heater 0.001
Water heater flued and Flueless 0.020
Warm air heater 0.008
Flueless cooker Oven 0.008
Hob Visual inspection of flames
Grill (CE marked) 0.010
Grill (No CE mark) 0.020
Range oven flued 0.020
Refrigerator (LPG) 0.007
Tumble drier Flued 0.010
flueless 0.001
Gas lights (LPG) 0.020
Any ratios above these readings maybe through, misuse, lack of maintenance, damage
or aging.
3
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
Carrying out a room test for carbon monoxide with a Combustion Analyser.
General
1. Position an open ended sampling probe approximately 2 m above floor level in
the centre of the room and at least 1 m away from any suspect appliance
installation.
2. Close all external doors, windows and customer adjustable ventilation.
3. Record the level of CO over a 15 min period. If the indoor level of CO starts
to rise during this period, check for CO migration from other sources.
4. If there is no rise then proceed to test the appliance.
Room Operate the appliance at full rate until the CO reading stabilizes or begins to fall,
sealed and whichever occurs first.
open flued
appliances
Cookers Ensure that all permanent ventilation to the space in which the appliance is situated is
unobstructed.
Place a saucepan on each of the pan-supports above the two largest hotplate burners
and put approximately a litre of water in each and cover with a lid. Use a saucepan
with a flat base and a base diameter of between 160 mm and 220 mm.
Place the grill pan in its highest position under the grill.
Open/operate the customer adjustable ventilation in accordance with the cooker
manufacturer’s instructions, e.g. window or extractor fan.
Light the grill, oven and the two hotplate burners at their maximum setting. Turn the
oven down to gas mark 5 (or mid-range if not calibrated in gas mark numbers).
Record the CO levels at 1 min intervals.
Turn the hotplate burners down to simmer when the water boils. Turn the grill off
after 30 min.
If during the test the CO reading:
begins to fall without exceeding 30 ppm, stop the test; the installation and cooker are
satisfactory;
does not exceed 30 ppm for longer than 20 min and begins to fall and does not exceed
90 ppm at any time, stop the test; the installation and cooker are satisfactory;
Exceeds 90 ppm at any time, stop the test, ventilate the room, identify the cause,
rectify and repeat the test.
Flueless Ensure that all permanent ventilation to the space in which the appliance is situated is
water unobstructed.
heaters Close all customer adjustable ventilation to the space in which the appliance is
situated.
Light the appliance and operate it at maximum gas rate for 5 min recording the CO
levels at 1 min intervals.
Flueless Ensure that all permanent ventilation to the space in which the appliance is situated is
space unobstructed.
heaters
Close all customer adjustable ventilation to the space in which the appliance is
situated.
Light the appliance and operate it at maximum gas rate for 30 min recording the CO
levels at 1 min intervals.
4
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
Purge the remaining sections of the installation (light and detect method)
Re-light each appliance in turn checking that all user controls are
working satisfactorily
Check all open flued appliances for spillage
Inform customer on appliance use and gas safety
5
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
The test pressure must never be greater than 23mb as the governor may lock up,
if so you will have to spray all the inlet pipework to check for leaks.
Air testing
Connect a zeroed manometer to the TEST TEE and start the test procedure.
Test name Reason Test pressure Test time
Stabilisation to allow for temp. differences 20mb 1 min
Soundness test (record any drops here) 20mb 2 min
Air test would be used for pipework in new installations
NO DISCERNABLE DROP ALLOWED -(max 0.25mb or 0.2mb with a digital)
6
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
U16 meter 1mb over 2 min* even if the pipe is greater than 28 mm
7
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
The test pressure must never be greater than 19mb as the governor
may lock up,
Because the inlet pipework is subjected to pressures up to 2 bar you
must spray all the inlet pipework to check for leaks.
U16 meter 1mb over 2 min* even if the pipe is greater than 28 mm
8
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
Ventilation
“When checking ventilation requirements always observe manufacturers instructions”
Calculate MAX NET heat input Take MAX GROSS heat input from the
appliance DATA BADGE and by 1.1
TWO Open flued appliance in a room ADD two heat inputs together and
MAX net heat input calculate as above
TWO Open flued appliance in a ADD two heat inputs together and
compartment MAX net heat input calculate as above
TWO Open flued GAS FIRES in the additional ventilation may not be
same room (less than 14kW) required
TWO Open flued GAS FIRES in the Add heat inputs together and calculate as
same room (greater than 14kW) for one open flued appliance in a room
IF flue or spillage test fails additional ventilation is required
TUMBLE DRIER YES 100 CM² 100 CM² 0 CM² 0 CM² 0 CM²
* IF THE ROOM CONTAINS A DOOR TO OUTSIDE THEN A VENT IS NOT REQUIRED
Measuring ventilators Calculate the free air area (measure the holes) the hole
MUST be from 5 to 10 mm and not closeable.
if answer is in MM² 100 to get CM²
9
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
Pressure testing
STANDING PRESSURE at the meter (APPROX. 25mb)
Test method (see below)
WORKING PRESSURE (must be 21± 2 mb) AT THE METER
Test method (see below) Multifunction control
BURNER
Burner pressure
This test is to prove that the appliance is burning within the limitations set by the
manufacturer.
1. Connect a zeroed manometer to the boiler BURNER PRESSURE test point.
2. Turn on the appliance and record the reading (compare the reading against the
appliance data badge. The reading must be within the range)
**To read the manometer correctly add both legs together and divide by 2**
10
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
The purpose of these tests is to prove how much gas is being burnt by the appliance
IMPERIAL METER (ft³): E.G. U6
1. Make sure only the appliance to be tested is on (turn up full)
2. Got to the gas meter and time one complete revolution of the red dial on the meter.
3. Convert the time into seconds and apply into the calculation.
Flame supervision devices or F.S.D s Purpose : To avoid unlit gas entering the appliance
1 Thermoelectric FSD Recognise because it has a push button and
thermocouple
Found in every type of gas appliance
Test 1. Light pilot and establish.
2. Turn gas off time until click
12
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
9 Lid safety device Purpose To turn off the burners, when the
lid drops
Mechanical safety Found Cookers, (hotplates)
cut off Test 1. Turn on gas tap to hotplate.
2. Lower lid and gas should turn
off
13
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
14
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
yes no
15
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
Cooker Controls
See www.gb-gas.co.uk for more details.
FSD
Vapour pressure
Test procedure
Light the oven burner, it should light on the low flame
After approx. 30 seconds it should rise to the high flame
Turn oven gas tap off
After 90 seconds re-light the oven burner, it should light on low flame
If it lights on the high flame then the FSD is faulty
OR
Thermoelectric
Test procedure
Oven thermostat
Test Procedure
16
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
Unsafe situations
To find out if a situation is NCS AR or ID consult the unsafe situations document
Category Action taken Label used Notice used
N.C.S. Inform responsible person, and repair fault if None Fill in the NCS
NOT TO possible. Fill in (notice) and give copy to section of
CURRENT responsible person warning notice
STANDARDS
form
A.R. Inform responsible person, and repair fault if Warning label do Fill in the A.R.
AT RISK possible. If not turn appliance off attach not use section of
(label) and fill in (notice) and give copy to warning notice
responsible person. form
I.D. Inform responsible person, and repair fault if Warning label do Fill in the I.D.
IMEDIATELY possible. If not DISCONNECT appliance not use section of
DANGEROUSE
and attach (label) and fill in (notice) and warning notice
give copy to responsible person. form
Flue inspection
When visually inspecting a flue start at one end and work methodically to the other
end making a note of all the problem areas
Common faults to look for are
Open flues
Catchment area too Catchment area not Catchment area has Incorrect flue for
small sealed letterbox opening appliance
Flue not sealed to the Flue damaged Flue upside down Signs of spillage
appliance
Joints leaking Joints not sealed Flues not clipped Minimum of 600mm
between draught
diverter and first bend
Bend no greater than Flue too small for To close to Incorrect terminal
45 appliance. combustible material.
Terminal not high Copex liner not fixed Copex not sealed to Incorrect material or
enough through the at the top or bottom appliance methods used.
roof.
17
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
FLUE TESTING
See www.gb-gas.co.uk for more details.
The purpose of a flue test is to prove a few points about the flue:
1. Flue draws all the products of combustion up the flue.
2. The flue does not leak from any joints or connections.
3. The flue terminates in the correct position.
4. The flue does not leak through any other flue system.
↓ ↓ ↗ ↓
OK Test with a Pre-test with a → CONDEMN
smoke pellet smoke match
FAIL
↓ ↓ ↗
If heating the flue with a blow torch, it OK Test with a
may require as much as 30 min to heat smoke pellet
properly
↓
OK
18
gb-gas.co.uk GAS REFERENCE PACKAGE 2010v2 Aim To Pass With Gb-Gas
SPILLAGE TESTING
See www.gb-gas.co.uk for more details.
The purpose of a spillage test is to prove a few points about the appliance:
1. The appliance draws all the products of combustion into the flue.
2. The appliance and flue design are working correctly.
3. The appliance has no fumes entering the room
4. The appliance is safe to use
↓ ↗ ↓
Is all the
smoke drawn
Leave the
appliance on and → CONDEMN
place smoke
into the match in the FAIL
appliance desired area
↓ ↓ ↗
OK Is all the If the appliance fails then
smoke drawn further investigation may be
into the required
appliance The appliance may be;
1. Over gassed.
↓ 2. Sooted up.
3. Blocked flue or flue ways.
OK 4. Bad flue design.
5. Faulty appliance.
19
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
20
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
POSSIBLE
EXTENSION
21
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
Signs Of Spillage
Sooting in or around the appliance or appliance seals
Pattern staining from the draught diverter
Inoperative Thermostats
Inoperative operating thermostats giving temperature problems (to hot or to
cold)
If operating thermostat fails on a system boiler. The high limit stat will lock
the boiler out (requires to be manually reset)
If high limit stat also fails steaming hot water will discharge from the pressure
relief valve. This will drop the pressure from the boiler. (requires to be
manually reset)
22
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
Signs Of Spillage
Sooting in or around the appliance or appliance seals
Pattern staining from the draught diverter
Inoperative Thermostats
Inoperative operating thermostats giving temperature problems (to hot or to
cold)
If operating thermostat fails on a system boiler. The high limit stat will lock
the boiler out (requires to be manually reset)
If high limit stat also fails steaming hot water will discharge from the pressure
relief valve. This will drop the pressure from the boiler. (requires to be
manually reset)
23
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
24
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
Signs Of Spillage
Sooting in or around the appliance or appliance seals
Pattern staining from the draught diverter
Flame impingement
Incomplete combustion
In either case the burner will not operate correctly, with the appliance
becoming sooted
25
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
Signs Of Spillage
Sooting in or around the appliance or appliance seals
Pattelkj ;oinern staining from the draught diverter
Inoperative Thermostats
Warm air units have a low temperature thermostat this lets the burner turn on
and heat, the heat exchanger before the fan unit turns on.
and a high temperature thermostat this turns the burner off when the heat
exchanger gets too hot, but lets the fan keep running.
If it does not operate in this sequence then the thermostat(s) may be faulty.
26
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
Signs Of Spillage
Sooting in or around the appliance or appliance seals
Pattern staining from the draught diverter
Defective Diaphragm
Blocked Venturi
Failure of the mechanism (push rod sticking)
27
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
Meter type
LENGTH 15mm
LENGTH 22mm
LENGTH 28mm
LENGTH 35mm
28
gb-gas.co.uk GAS REFERENCE PACKAGE 2008.1 Aim To Pass With Gb-Gas
Resistance table:
Discharge in straight horizontal table x copper tube with 1.0 mb differential
pressure between the ends, for gas of relative density 0.6 (air = 1).
When estimating the gas flow rate in pipework of a known length this length
must be increased by 0.5 m for each elbow and tee branch fitted.
Draw a plan of your pipe routs SPLIT THE PIPE WORK INTO SECTIONS and number them 1,2,3,4
etc. details on the plan the number of actual or estimated elbows and tees required.
Appliance / appliances 1 2 3 4 5 6
Pipework
G PRESSURE DROP mb
Chart allowable length D divided by
the actual length F. if this is greater
than one you have divided the wrong
number first.
Total Pressure drop
Adding the pressure drops from the meter to the appliances and all pipework it passes must total less
than one to pass eg. (From the meter to the first tee). + (From the tee to the appliance) = must equal less
than 1mb. See www.gb-gas.co.uk for more details.
Meter to appliance 1 Meter to appliance 2 Meter to appliance 3 Meter to appliance 3
29