Professional Documents
Culture Documents
REV 1.0
Presentation
Thank you for choosing high-tech Enpower33 C SERIES™ UPS. This unit is
produced with advanced technological equipment in accordance with ISO9001
quality system.
Please read this manual thoroughly and keep it for a fruitful and safer use. For
further information, visit our website www.allsai.com or contact with the nearest
sales and technical support centre.
1/62
ENPOWER33 C SERIES USER MANUAL rev1.0
PREFACE ...................................................................................................................... 3
INTRODUCTION.......................................................................................................... 4
INSTALLATION ........................................................................................................... 5
FRONT PANEL............................................................................................................14
COMMUNICATION ....................................................................................................45
TROUBLESHOOTING................................................................................................53
TECHNICAL PROPERTIES.......................................................................................56
2/62
ENPOWER33 C SERIES USER MANUAL rev1.0
PREFACE
This user manual provides all the instructions about the installation and the
operations of Enpower33 C Series UPS in the power range of 10-40 kVA.
Please read this user manual before operating your UPS.
Be cautious to the warnings stated in this user manual.
Apply the instructions step by step.
In case you face any problem while applying the instructions as per stated in
this manual, please inform our head-office through telephone or e-mail
printed at the back-cover of this manual.
INTRODUCTION
Enpower33 C Series UPS is a high technology product manufactured to be used
in industrial fields, hospitals, schools, banks, business centers (offices), computer
and communication systems and in any other places where the hi-tech devices are
used. Besides being an on-line system it also provides a by-pass system, contains
all the protection systems and able to feed all kinds of loads.
As it is constructed with Double Conversion (Online) methodology, the system
feeds the loads with stable voltage (frequency and amplitude). In the case of mains
blackout or back to the normal mains, there is no transfer time in question in an on-
line structure.
With a view to provide stable operation of the load, responsive microprocessor
control mechanism is implemented in UPS design thus ensuring quality output,
especially needed for the devices sensitive to minor voltage changes.
The static by-pass unit of the UPS continuously keeps the mains as a stand-by
supply. In an overload case, UPS transfers the load to the mains to protect itself
from damage. As soon as the load conditions returns to the normal, with static by-
pass system the UPS starts to provide pre-defined, stable frequency and voltage.
In an UPS fault case, the static by-pass unit behaves the same as it was
mentioned above and protects the load from energy interruption.
During the mains failure, UPS feeds the load from the batteries. During that
autonomy time, depending on the capacity and number of batteries, UPS is run by
the batteries. In that time, if mains come back again, UPS passes to Normal Mode
and continues to feed the load. Meanwhile charging of the batteries begins.
While the UPS is connected to a PC system by RS232, with compatible software
program all the functions of UPS can be monitored. By means of a Modem,
connecting to a remote device (UPS), the device related functions and problems
could be acquired in PC. Moreover, it is possible to make suitable changes in the
parameters of UPS from the connected PC.
The system in Enpower33 C Series UPS is shown as a block diagram below in
Figure-1.
INSTALLATION
SITE SELECTION
The UPS system should be installed in a cool and dry place where the
temperature is maintained at required ambient temperature range. There
should be enough ventilation. If necessary, in order to provide air circulation
in the room, fanning system should be installed and suitable air-filters should
be used.
The floor on which the UPS is to be placed should be flat-leveled, plastic
coated and strong enogh to sustain the weight of the UPS.
Ensure that the installation should not have extreme dusty and oily
surroundings.
Ambient humidity should be in range of recommended values.
The selected place should not be under direct sunlight and should be far from
any heat source.
UNPACKING
If the unit is kept for a long time in warehouse, please do not unpack till
the installation.
Cut the circles wrapped up at the front and back sides of the UPS.
Cut the protective nylon wrapped up the UPS.
Take out the cardboard box.
Take out other protective stuff if available like wedge.
Cut the second protective nylon wrapped up the UPS and take it out.
Examine the UPS system carefully for any equipment damage that may
occur during the shipment. If you find any peculiarity with the equipment,
please contact your supplier without delay.
Check the auxiliary stuff such as control program, communication cable, user
manual and the warranty. If any, please check the extra hardware.
LOCATING THE UPS
Carry the UPS with its palette to the installation place on a forklift.
Take apart the front and back fixer parts.
Bring down the UPS over the palette carefully.
It is suggested to keep a space at the backside of the UPS for ventilating.
Enough places should be kept open around the UPS so that a man can pass
by its sides.
5/62
ENPOWER33 C SERIES USER MANUAL rev1.0
There are four pcs battery trays inside Enpower33 C Series UPS. Please see the
following table to learn the battery types and numbers to be connected into the
trays. The cross-sectional areas in the table are for the inner connecting cables.
If the battery type or quantity are different from the values in the table,
you have to use battery cubicle(s).
Before performing the steps below, be sure that all the circuit breakers
must be OFF
Please pay attention to the following points while making the connections.
Take out the top and left side covers of the UPS.
Dismount the fixing parts of battery trays.
Draw the trays and dismount the battery side and top tightening parts.
Put and locate the batteries onto the lowest tray.
Mount the battery side tightening part.
Fill up the free space on the tray with a material such as sponge wedge.
Mount the battery top tightening parts.
Make the inner connections of the tray.
Push the tray and mount it to the UPS by means of fixing part.
Make the necessary socket connections of the tray.
Carry out the same steps for the other battery trays.
Put the top and left side covers of the UPS again.
6/62
ENPOWER33 C SERIES USER MANUAL rev1.0
7/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Take out the protective cover of terminals. The detailed appearance of terminals is
shown below. That detailed appearance is also found as a picture under the
terminals.
You can use the open space located under side of the UPS while connecting the
power cables.
8/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Before making the cable connections, all the circuit breakers must be
OFF.
The cross-sectional areas of the cables are given in the table below . For
a safer operation, please use the recommended ones.
The cross-sectional areas of battery cable stated in the table above are
for the cable between UPS and battery cubicle.
For a safer operation, the earth connection must be done. Before
making the other connections, please make the appropriate earth
connection carefully.
Connect the input neutral cable to the terminal marked as ‘INPUT’ (N1).
Connect the output / load three phase cables to the terminals marked as
‘OUTPUT’ (L1), (L2), (L3) sequentially.
Connect the output neutral cable to the terminal marked as ‘OUTPUT’ (N2).
9/62
ENPOWER33 C SERIES USER MANUAL rev1.0
If there are two battery cubicles, both of them must have the same type
and number of batteries.
If the distance between the UPS and the battery cubicle(s) is more than
3 m, please connect the battery cubicle cables twisted to each other.
10/62
ENPOWER33 C SERIES USER MANUAL rev1.0
11/62
ENPOWER33 C SERIES USER MANUAL rev1.0
12/62
ENPOWER33 C SERIES USER MANUAL rev1.0
After turning off the UPS, there may be still dangerous high voltage
inside the UPS. If needed to service and maintain, please wait for at
least five minutes.
13/62
ENPOWER33 C SERIES USER MANUAL rev1.0
FRONT PANEL
The following sections are found on the front panel.
1. LED Bar
It gives information about the operational mode of the UPS by using different colors
and forms of warning leds.
2. LCD Screen
This display is used for monitoring. It shows operational mode of the UPS, input,
output and battery data, active failure warnings, date, time and internal temperature.
3. Keypad
The keypad is used for starting and stopping the UPS, also for monitoring and -if
needed- adjusting the data by going through the menus.
LCD SCREEN
There are two windows which can be shifted sequentially by the user on the LCD
screen.
Mimic Diagram Window
This window consists of two subwindows. Mimic diagram and alarm information
window.
14/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Mimic Diagram
Mimic diagram shows the icons of input, output, battery, rectifier and inverter stages
and lines expressing the operational modes. There is also a bar inside the battery
icon showing the battery level and one more bar inside the output icon showing the
load level. By this way, it becomes very easy to understand the status of the UPS at
first glance.
Active failure (alarm) warnings of the UPS can be observed by following this alarm
information window below the mimic diagram on the LCD. As long as the failure
case continues, the warning of the failure is seen on that window. If there are more
than two warnings, these are seen on the window alternately.
15/62
ENPOWER33 C SERIES USER MANUAL rev1.0
16/62
ENPOWER33 C SERIES USER MANUAL rev1.0
MENU CONFIGURATION
DEFINITION AND FEATURES
A menu configuration is formed in Data Monitoring Window to allow user to access
the menus easily. Thus user can observe and change the related data of the UPS.
Configuration comprises three menus named “Main Menu”, “Inter Menu” and “Sub-
Menu”. By using the keypad, user can go through the menus and make changes.
17/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Access to the menu level where the list of all main menus
are seen by using ‘ESC’ button. There are special icons
Going through the Main
for each main menu. Then use ‘down arrow’ or ‘up arrow’
Menus
to go the main menu that you prefer. Press ‘ENTER’ to
access this menu.
Access to the menu level where the list of all inter menus
Going through the is seen by using ‘ESC’ button. Use ‘down arrow’ or ‘up
Inter Menus arrow’ to go the inter menu that you prefer. Press
‘ENTER’ to access this menu.
18/62
ENPOWER33 C SERIES USER MANUAL rev1.0
MAIN MENUS
Displays
This Main Menu is used to observe the data of mains, output, battery, bypass,
inverter and general information of UPS. To go through the menu, use the keypad.
Sub-Menus are seen in a page format. Inter Menus forming that Main Menu are
explained below.
Mains The mains supply voltages (phase-neutral), currents drawn from mains,
apparent and active powers drawn from mains, power factor, crest
factors of drawn currents and the mains voltage frequency can be
observed.
Battery Battery voltage and current, capacity (%), elapsed time (resets in every
battery operation) and remaining time during the discharging can be
observed. While charging, remaining time is seen as zero. Moreover,
battery test functions are also observed here. Please see the “Battery
Test” section.
Device In this Inter Menu, UPS model, serial number, power rating, program
name, program date, total operating time and the guarantee status can
be observed. There are three options under the Guarantee Status Sub-
Menu. If guarantee time is set and does not expire, guarantee finishing
time is seen. If guarantee time expires, ‘expired’ warning is seen. If
guarantee time is not set, ‘not set’ warning is seen.
19/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Ups Status
This menu is also used for observing. It gives information about essential parts of
UPS. In this Main Menu, there are no Inter Menus. Sub-Menus are seen in a page
format.
Input It shows the mains voltage status. If the mains voltages are between the
defined limits, seen ‘normal’. If they are under the minimum limit seen
‘low’ and if they are over the maximum limit seen ‘high’. If there is phase
sequence fault, ‘phase sequence fault’ warning is seen. If the mains
frequency is out of the certain limits, “Mains Frequency Fault” warning is
seen. In that case rectifier stage of UPS does not work but inverter stage
of UPS is able to work.
Bypass It shows the bypass voltage status. If the bypass voltages are between
the defined limits, seen ‘normal’. If they are under the minimum limit seen
‘low’ and if they are over the maximum limit seen ‘high’. If there is phase
sequence fault in bypass voltages, ‘Phase Sequence Fault’ warning is
seen. In that case bypass static switch stage of UPS does not work.
When bypass frequceny is out of limit, ‘Freq. Outside Limit’ warning is
seen.
Output It shows that which source is feeding the output. Please see the following
warnings to see how the output is fed.
Fan It shows failure and speed (%) of the fans mounted on the heatsink unit.
Depending on the load and temperature of heatsink, the velocity of fans
controlled by the microprocessor dynamicly. When the load increases,
fans rotate faster and when it decreases, they rotate slower. In case of a
failure in any fans, ‘failure’ warning is seen instead of the velocity.
Fuse It shows the status of fast fuses placed on power stages. In case any of
the fuses blows, a warning is seen. This warning states which unit’s fuse
has blown. Those units are ‘input’, ‘bypass’, ‘rectifier’, and ‘battery’. If all
of the fuses are OK, ‘normal’ warning is seen.
Heatsink It shows the temperature status of the heatsink that cools the system.
Power semiconductors are mounted on that heatsink. When the
temperature of the heatsink exceeds 80 °C, ‘over heat shutdown’ warning
20/62
ENPOWER33 C SERIES USER MANUAL rev1.0
is seen and the UPS stops running in Normal Mode and passes to Stop
Mode.
SCR It shows the status of thyristors (SCR) placed on the power stages. They
are used as static switches. In case any of the thyristors blows, “failure”
warning is seen. Otherwise “normal” warning is seen.
IGBT It shows the status of IGBTs placed on the power stage. They have
switching function in rectifier and inverter stages. In case any of the
IGBTs blows, a warning is seen. This warning shows which unit’s IGBT
has blown. Those units are ‘rectifier’ and ‘inverter’. If all of the IGBTs are
OK, ‘normal’ warning is seen.
Warnings
The past warnings of failures and operational modes are observed. UPS gives user
the opportunity to observe 512 messages with date and time. By using keypad, you
can go through in warnings and get information about the past failures of UPS.
Warnings are seen in a page format. The last warning is seen in the first line. In
date part, you can see only time and date. You can access to the following page by
using “down arrow”, the previous page by using “up arrow”.
The list of all the possible warnings in Warnings Main Menu are given in Table-4.
Name Explanation
Stop Mode The UPS has been stopped and it is in Stop Mode.
21/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Battery Test The manual or periodical battery test mode of the UPS.
Mains voltage is below the defined limit and the UPS begins
Mains Low
to run by battery.
Mains voltage is above the defined limit and the UPS begins
Mains High
to run by battery.
22/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Emergency Stop The UPS is stopped by EPO (Emergency Power Off) button.
23/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Choose the parameter that you would like to change by using ‘Up arrow’ and
‘down arrow’ buttons. The chosen line is showed with a graphical bar.
24/62
ENPOWER33 C SERIES USER MANUAL rev1.0
With ‘Up arrow’ and ‘down arrow’ buttons, set the value that you prefer.
By pressing ‘Enter’ button, save the new value and exit from the Change
Mode. Meanwhile the graphical bar shifts to the following line.
The parameters in this Main Menu and their functions are showed below.
25/62
ENPOWER33 C SERIES USER MANUAL rev1.0
‘CALIBRATIONS’, ‘SET VALUES’ and ‘TEST SETTINGS’ Main Menus are not
explained in this user manual. Since those menus can only be used by authorised
technical personnel. Careless and unconscious changes that made by end users
26/62
ENPOWER33 C SERIES USER MANUAL rev1.0
may cause harm to the UPS. If done so, in that case manufacturer does not take
any responsibility.
27/62
ENPOWER33 C SERIES USER MANUAL rev1.0
BASIC FEATURES
OPERATIONAL MODES
In case the following conditions occur, the UPS stops running in this mode.
28/62
ENPOWER33 C SERIES USER MANUAL rev1.0
In case the following conditions occur, the UPS passes to Stop Mode.
After the UPS is turned on
Cases of overheat shutdown, overload shutdown or overcurrent inverter
Stopping the UPS manually by pressing “EXT” button
Stopping the UPS by remote bypass switch
While activating the manual bypass
Any failures in rectifier and/or inverter stages
System Off Mode
All power stages including the static bypass line do not run. There is no voltage at
the output. The mimic diagram of the mode is shown in figure below. In this mode
LED bar does not light.
29/62
ENPOWER33 C SERIES USER MANUAL rev1.0
In case the following conditions occur, the UPS passes to System Off Mode.
When the reason that makes the siren system active disappears, the system
becomes inactive automatically. For instance when there is overload, the siren
begins to sound. And when the overloading finishes, the siren system stops.
In case of any failures, when the UPS is stopped by pressing “EXT” button, the siren
system becomes inactive.
Please push (press and leave) “EXT” button to make the siren system silent
temporarily without stopping the UPS.
30/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Press “EXT” button for a while. UPS passes to Stop Mode. The load is
transferred to static bypass line without interrupting.
Switch the output circuit breaker into ‘MBYP’ position.
With the siren sound, ‘Maintenance Switch On’ warning is seen in both Alarm
Information Window and Warnings Main Menu. ‘Service’ message is seen in
Output Menu of UPS Status Main Menu. The mimic diagram is seen as
showed in figure below.
After switching the output circuit breaker into ‘MBYP’ position, the load is
fed without interrupting as long as the mains voltage exists.
During manual bypass operation, there are still dangerous voltage at the
terminals of input, battery and output terminals. Do not take out the
protective cover of terminals. This operation should only be made by
authorized personnel.
31/62
ENPOWER33 C SERIES USER MANUAL rev1.0
During manual bypass operation and the UPS is OFF, do not switch the
output circuit breaker into ‘UPS’ or ‘OFF’ position. Otherwise your load will
be dropped. For a safer transfer, execute the following steps stated below.
After passing to Running by Battery Mode, the battery voltage begins to drop
depending on the load and the capacity of the batteries. The battery voltage is
compared with the reference values defined in SET VALUES/Battery Menu.
According the result of this comparison, the periodic siren system changes as
shown in table below.
Battery Voltage Periodic Siren Warning Message
Twice in every four
Higher than ‘Nominal Voltage’ Mains Low
minutes
Twice in every two
Higher than ‘Low Voltage’ Battery On
minutes
Three times in
Higher than ‘Shutdown Voltage’ Battery Low
every ten seconds
Lower than ‘Shutdown Voltage’ Four times in every Battery Depleted
five seconds
Table-6 Change in siren system and warning messages depending on the
battery voltage
32/62
ENPOWER33 C SERIES USER MANUAL rev1.0
During Running by Battery Mode, if the mains come back, the UPS passes to
Normal Mode uninterruptingly.
In case the batteries deplete completely, ‘battery depleted’ warning is given and four
minutes later both the rectifier and inverter stages are shut. Meanwhile no energy is
transferred to the load. After depleting, if mains come back, the UPS is restarted
and passes to Normal Mode.
If you want the UPS to be started automatically when the mains come
back after shutting entirely, do not turn off the any circuit breakers.
Otherwise you will have to start it manually.
After executing EPO, UPS can not be started. To do this, please turn off
all the circuit breakers of the UPS and turn them on again.
If EPO option not preferred, select “off” under TEST SETTINGS/ Hardware/
Emergency Power Off menu.
REMOTE START/STOP PROCEDURE (REMOTE BYPASS)
The UPS can be remotely stopped and started again by means of an external
switch. Tips of the external swich must be connected 1 and 2. pins of CUSTOM
CONTACTS (DSUB-9F) female socket on the communication unit. While the UPS is
working, if external switch is turned OFF, it passes to Stop Mode. Both the rectifier
and inverter stages are shut. Load is fed by bypass line. When the switch is turned
ON, the UPS is restarted and after a while it passes to Normal Mode.
33/62
ENPOWER33 C SERIES USER MANUAL rev1.0
To make the remote start/stop procedure option active, please select “on” in TEST
SETTINGS/ Hardware/ UPS Shutdown.
RUNNING BY GENERATOR
When the UPS is fed by generator instead of mains, battery charge feature of UPS
can be made passive to operate the generator more productive. To do this, a
contact data from generator must be given to the UPS. The tips of that contact must
be connected 3 and 4.pins of CUSTOM CONTACTS (DSUB-9F) female socket on
the communication unit. When the generator begins to run, the UPS passes to
Normal Mode but the batteries are not charged. Thus the generator is not
overloaded. Furthermore, while passing from running by battery to Normal Mode,
the genarator is loaded softly. The generator does not fall down because of loading.
When the mains is back and running by generator stops, the batteries will be
charged again. To make that option active, please select “on” in TEST SETTINGS/
Hardware/ Generator Active.
BATTERY TEST
The batteries can be tested in two different ways. Manual ve Periodical Test. Battery
test can only be executed while the UPS in Normal Mode.
Manual Test
In this way, end users test the batteries manually whenever they want. Test
procedure is explained in steps below.
In this page, when the battery test is not made, there exists information belongs to
the previous test. Here is the information that can be observed in that page.
34/62
ENPOWER33 C SERIES USER MANUAL rev1.0
‘Test Time’ : It shows the date and time of the previous test. If any tests have not
been made so far, this information is not seen.
Press ‘ENTER’ button. The UPS passes to running by battery mode and it
stays at this mode during the determined test period. Meanwhile running by
battery mode figure is seen on the mimic diagram.
In this page, during the battery test, there exists information belongs to the present
test. Here is the information that can be observed in that page:
‘Test Time’ : It shows the time and date when the test has started.
‘Test Result’ : While on progress, since the result is not certain, ‘xxx’ is seen.
‘Test Monitoring’ : The battery test voltage and the remaining test time are seen
here. During the battery test, if the battery voltage decreases under the reference
battery test voltage, it is understood that there is a problem in batteries. When that
time finishes and battery test stops, the UPS passes to Normal Mode again.
During the battery test, if ‘ENTER’ button is pressed, test is cancelled and the UPS
passes to Normal Mode again.
35/62
ENPOWER33 C SERIES USER MANUAL rev1.0
During the battery test, if any problems are determined, the UPS stops the test and
passes to Normal Mode. Battery failure is notified by means of periodic siren.
“failure” message is seen on the “Test Result” part of Test Monitoring page.
36/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Periodical Test
In this way, batteries can be tested automatically at determined period intervals. In
CUSTOM SETTINGS/Battery/Test Period menu, test period can be determined as
time of days. Factory default value for test period is 7 days. If you do not want to
use the periodical test, please select the “off” under CUSTOM
SETTINGS/Battery/Test Period menu. Test procedure is the same as in the manual
test.
OVERLOAD
If there is an overload case at the output of the UPS, the operation of the UPS
changes as explained below.
If the overload case is still going on at the end of the overload time, the UPS
transfers the load to the static bypass line. Both the rectifier and inverter stages are
shut. ‘Overload Shutdown’ warning is seen in both Alarm Information Window and
Warnings Main Menu. It’s waited for approximately 4 minutes to allow the UPS to
get cool.
37/62
ENPOWER33 C SERIES USER MANUAL rev1.0
If the load percentage drops under nominal load value at the end of that time, the
UPS restarts and passes to Normal Mode. If overload is going on, the UPS does not
restart.
If overload case stops before overload time expires, periodic siren system becomes
silent. The value of overload counter begins to decrease. Overload warning
disappears in the Alarm Information Window.
ECO-MOD OPERATION
In eco-mode, the load is fed by bypass source instead of inverter voltage. In this
mode, both the rectifier and inverter stages run different from Stop Mode. Bypass
voltage, its frequency and waveform are continuously observed. Inverter voltage is
kept ready by synchronizing with bypass voltage. When the bypass voltage and/or
frequency is beyond the defined limits or the waveform is corrupted, the load is
automatically transferrred to the inverter line. When the bypass source comes back
into the range of defined limits, the load is automatically transferrred to the static
bypass line.
In this mode, the batteries are continuously kept charged. When the mains fail, the
rectifier stage is shut and the batteries begin to feed the inverter. The batteries pass
to discharging state. When the mains come back, the rectifier stage is operated
again and the batteries begin to be charged. The LED bar lights in red winkly.
Activating Eco-Mod
Stop the UPS and verify that it is in Stop Mode.
Select the ‘eco-mod’ under TEST SETTINGS/General/Operating Mode
menu.
Press EXT button on the front panel for a while.
Wait for the recitifier and inverter stages to run.
After they begin to run, ‘Eco Mod’ warning is seen in Warnings Main Menu.
From that moment Eco-Mod is active.
38/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Deactivating Eco-Mod
Press EXT button on the front panel for a while and verify that it is in Stop
Mode.
Select the ‘normal’ under TEST SETTINGS/General/Operating Mode menu.
Press EXT button on the front panel for a while again.
Wait for the recitifier and inverter stages to run.
After both of them begin to run, the UPS passes to Normal Mode.
PARALLEL OPERATION
Definition and Features
The failure probability in a parallel system is comparatively less than that of the
single unit because of the under capacity operation. Thus it provides more reliable
operation.
In case all the units go out of order, the system switches the load to bypass
automatically and when they return to normal condition they start operating
automatically in parallel mode. In a parallel configuration, the units feed the total
load together and share it equally.
That’s to say, they equally distribute the necessary load current. There can also be a
unit remains as stand-by. The stand-by unit is a passive one that begins to feed the
load in case of failure one of the active units or in case of an increase in the total
load. When the failured active unit is OK or the load is decreased, the stand-by unit
is taken out of circuit automatically. This system is generally named as (N+1). N,
the active units feeding the load together and +1, the unit remains stand-by.
39/62
ENPOWER33 C SERIES USER MANUAL rev1.0
In C SERIES, a new control technology is used for paralleling that increases the
reliability and flexibility.
Installation
While connecting the output phase cables to the common output bus
on the panel, pay attention to phase sequences.
A load disconnector should be used between the common output bus and
the load system on the load distribution panel.
Use a separate battery cubicle for each unit. Do not use a common battery
cubicle.
Use a separate earth cable for each unit.
The cooling system of the UPS room must be designed according to the total
power of the parallel configuration.
Finally, connect the parallel cables provided with the UPS to the parallel DSUB-9M
port of the communication unit of the UPS and tighten the screws.
Settings
Please carry out the following steps for each unit in the same way.
KPRO4: 040
KINT4: 010
40/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Please carry out the following steps for each unit depending on the UPS’ status in
the parallel configuration.
Commissioning
Please execute the following steps for each unit to start the parallel operation.
After all the units start, carry out the following points.
41/62
ENPOWER33 C SERIES USER MANUAL rev1.0
It can be reached to the voltage free contacts of the relays through the RELAY
OUTPUTS (DSUB-25F) female socket on the communication unit. Positions of the
contacts in the socket are given in Table-8 below.
42/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Remote monitoring panel is connected to the UPS by means of a CAT-5 cable. The
cable must be put on the REMOTE (DSUB-9F) female socket on the communication
unit. To active the remote monitoring panel, please select the choice ‘on’ in the
TEST SETTINGS/Communication/Remote Monitoring menu.
43/62
ENPOWER33 C SERIES USER MANUAL rev1.0
For more detailed information, please see the User Manual of Remote Monitoring
Panel.
44/62
ENPOWER33 C SERIES USER MANUAL rev1.0
COMMUNICATION
Standard
RS232
RS422 / RS485
MOD BUS (RTU)
JBUS (RTU)
CAN BUS
Optional
SNMP
USB
GPRS
SMS
45/62
ENPOWER33 C SERIES USER MANUAL rev1.0
RS232
It is used to communicate the UPS with a
computer that is located near to the UPS Pin Signal Explanation
(max 20 m) upon through the RS232
1 DCD Data Carrier Detect
protocol. For connection, RS232 socket is
used. To active that feature, please select 2 TX Transmit Data
the choice ‘rs232’ in the TESTSETTINGS /
Communication / Hardware Protocol. 3 RX Receive Data
46/62
ENPOWER33 C SERIES USER MANUAL rev1.0
RS485
RS232 standard is desinged to be
effective in short distances. In case it is Pin Signal Explanation
exceeded the limits of distances, RS485
1 B
protocol can be used to get the facilities of Receive Signals
RS232 softwares. Thus the same 2 A
softwares can be used in long distances
with the same efficiency. 3 Z
Transmit Signals
RS485 communication is a kind of signal 4 Y
converting process. So a converter is
needed at the side of the computer to 5 GND Signal Ground
make the signals suitable for the
computer. This converter (RS485 adapter)
Table-12 Inner structure of the
is presented optionally with C SERIES
RS485 socket
UPS’ and it supports a number of
industrial standards.
RS485 socket situated on the communication unit is used for connection. To active
that feature, please select the choice ‘rs485’ in the TEST
SETTINGS/Communication/Hardware Protocol menu. Communication speed can
be chosen in TESTSETTINGS/Communication/Baudrate menu.
MODBUS
It is a standard communication protocol that allows the UPS to transfer data to
industrial systems such as PLC. It provides mutual data flowing in these systems.
47/62
ENPOWER33 C SERIES USER MANUAL rev1.0
48/62
ENPOWER33 C SERIES USER MANUAL rev1.0
49/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Making Connections
In order to connect the UPS to a network environment at first an SNMP adaptor is
needed. For this reason you have to obtain an SNMP adaptor packet. It is put on the
communication unit as a internal card. So this connection must be done by a
qualified and authorized technical personnel.
50/62
ENPOWER33 C SERIES USER MANUAL rev1.0
Most of the information (except Start / Stop operation and such) in this user manual
is written for those who have technical educational background. Only those who are
expert and knowledgeable about the system and all the parts inside it, are
authorized to deal with it.
They are allowed to open the case of the UPS to maintain or for repairing or to do
the tasks of these sorts.
Only experienced and specialist persons in this field are supposed to be involved in
fault detection and trouble-shooting. The experts are those who do not need a
detailed analysis of the problems. All these warnings, rules and regulations are only
to protect the user against any sort of fatalities.
When the case of the UPS is kept open, there remains a probability to touch the
high voltage carrying points accidentally. Consequently, in this condition, the
personnel dealing with it should be concerned and should not touch the points with
bare-hand. So, when the UPS runs, the enclosures should be kept closed.
51/62
ENPOWER33 C SERIES USER MANUAL rev1.0
PERIODICAL SERVICE
C SERIES UPS is designed in such a way that a little maintenance is necessary. In
order to guarantee healthy condition of UPS system for a long time the following
cares should be taken.
At first the UPS should be shutdown and then all the voltage connections (at
input and output) should be disconnected from the UPS by turning off the
circuit breakers.
Then wait for at least 5 minutes before any other tasks (so that the
capacitors are discharged by this period of time).
Clean the case of the UPS with a piece of wet cloth in every two months.
Clean the dust deposited on the front panel with a piece of cotton cloth in
every three months. It is recommended to replace the display illumination
unit in every three years.
The fans should be checked and cleaned once in every three months.
Lifespans of the fans depend on the ambient temperature and the usage
method. It is recommended to replace the fans in every four years.
It is recommended to replace the AC and DC capacitors in the system in
every five years.
Lifespans of the batteries depend on the ambient temperature, number of
charging-discharging process and the amount of deep discharging. It is
recommended to replace the batteries in every five years maximumly.
FAULT
Since there are fatal (dangerous) parts inside the unit, only the authorized, trained
and qualified technicians are allowed to provide services to the UPS.
BEFORE CALLING THE TECHNICAL SERVICE
Before you call the technical service please be sure to check the following.
52/62
ENPOWER33 C SERIES USER MANUAL rev1.0
TROUBLESHOOTING
The following information is for frequently met problems. It is aimed to make the
troubleshooting easier with such information. For more details, please see the
Service Manual.
53/62
ENPOWER33 C SERIES USER MANUAL rev1.0
54/62
ENPOWER33 C SERIES USER MANUAL rev1.0
55/62
ENPOWER33 C SERIES USER MANUAL rev1.0
TECHNICAL PROPERTIES
GENERAL PROPERTIES
POWER - KVA 10 15 20 30 40
UPS topology On-line – Double Conversion, transformerless
Efficiency (AC AC) -
> 92
%
Heat dissipation at
nominal load
56/62
ENPOWER33 C SERIES USER MANUAL rev1.0
RECTIFIER
POWER - KVA 10 15 20 30 40
Topology Vector controlled IGBT technology
Nominal input voltage -
220/380, 230/400
Vac
Input voltage range ±25%
Nominal input frequency -
50 / 60
Hz
Input frequency range 10%
Maximum input current (At
nominal input voltage) - 15 22 30 45 60
Amper
Input current harmonic
< %5
(THD)
Input power factor > 0.99
DC output voltage stability ±1%
DC output voltage ripple 1%
Maximum charging current
1.2 2.0 2.5 3.5 4.5
(At nominal load) – Amper
Input protection Fast fuse
BATTERY
POWER - KVA 10 15 20 30 40
Standard battery type Dry, maintenance free
Battery ambient
(0) / (+25)
temperature - °C
Battery storage
(-10) / (+60)
temperature - °C
Battery storage period (At
3 Months
+25°C)
Numbers of cells 384
Floating voltage (At +25C°)
864
– V DC
Minimum discharge voltage
665
– V DC
Battery protection Fast fuse
Battery test property Manual and periodical (adjustible)
57/62
ENPOWER33 C SERIES USER MANUAL rev1.0
INVERTER
POWER – KVA 10 15 20 30 40
Topology Vector controlled IGBT technology
Nominal output voltage -Vac 220/380, 230/400 (optional)
Output Voltage Stability
kVA 10 15 20 30 40
kW 8 12 16 24 32
Output power factor 0,8
Overload capacity
58/62
ENPOWER33 C SERIES USER MANUAL rev1.0
BYPASS
POWER - KVA 10 15 20 30 40
Nominal voltage - Vac 220/380,230/400
Voltage range %15
Nominal frequency - Hz 50 / 60
Frequency range %10
Overload capacity
59/62
AUTHORISED TECHNICAL SERVICE