ELECTRICAL MAIN LOAD CHART “36M CATAMARAN PASSENGER FERRY”
CONTENTS
1 MAIN PARTICULARS
Main Dimensions
Rule applied
Total KW No. in Opern. SAILING No. in Opern. BEARTH/ UNBEARTH. MODE No. in Opern. HARBOUR
Sl No APPARATUS
Qty. Each Use KW L.F. Cont. Discont. Use KW L.F. Cont. Discont. Use KW L.F. Cont. Discont.
GENARAL MACHINARIES
1 BOW THRUSTER 2 40 2 80 0.8 64
3 SEWAGE TREATMENT PLANT 1 2.96 1 2.96 0.8 2.368 1 2.96 0.8 2.368
4 OILY WATER SEPERATOR 1 2 1 2 0.8 1.6
5 AIR CONDITIONING SYSTEM 1 15 1 15 0.8 12 1 15 0.8 12 1 15 0.8 12
HYD. POWER PACK FOR ANCHOR
6 2 5.5 2 11 0.8 8.8 2 11 0.8 8.8 2 11 0.8 8.8
WINDLASS & RAMP
7 TRANSFORMER RECTIFIRE UNIT 1 1.5 1 1.5 0.8 1.2 1 1.5 0.8 1.2 1 1.5 0.8 1.2
8 LIGHTING LOAD 2 16 1 16 0.8 12.8 2 32 0.8 25.6 2 16 0.8 12.8
9 BOAT DAVIT CRANE 1 7 1 7 0.8 5.6 1 7 0.8 5.6
PUMPS
10 SEWAGE DISCHARGE P/P (3Φ) 1 1.1 1 1.1 0.8 0.88
11 FIRE PUMP 2 5.5 1 5.5 0.8 4.4 2 11 0.8 8.8 2 5.5 0.8 4.4
12 FUEL OIL TRANSFER PUMP 2 1.1 1 1.1 0.8 0.88 2 2.2 0.8 1.76 2 1.1 0.8 0.88
F.W. COOLING PUMP FOR DECK
13 1 2.2 0.8 1.76 1 2.2 0.8 1.76 1 2.2 0.8 1.76
MACHINERY HPU 1 2.2
14 SPRINKLER PUMP 2 22 1 22 0.8 17.6
VENTILATION
15 ENIGINE ROOM/AUX. ER SUPPLY FAN 2 3.3 2 6.6 0.8 5.28 2 6.6 0.8 5.28 1 3.3 0.8 2.64
ENIGINE ROOM/AUX. ER EXHAUST
16 2 2.2 2 4.4 0.8 3.52 2 4.4 0.8 3.52 1 2.2 0.8 1.76
FAN
Maximum
KW 117.52
KVA 146.90
NOTE: -
1. Total no. main generator in this vessel is 2 x 90KW (415Vac. 50Hz, 3ph)
2. During harbour and cruising mode, one generator will be in service, where other generator is in standby mode.
3. During Berthing / un-berthing mode total load is 117.520KW
a) one generator will take 58KW load.
b) second generator will take 58KW load.
4. Manual/Auto synchronizing & load sharing function are equipped in the MSB