You are on page 1of 1

INTERNAL TEST REPORT

Client : KPTCL
Contractor : Asa Bhanu Technical Services Limited
Project : Construction of 2x10MVA 110/11KV, Substation for ESIC
Medical College, Gulbarga
Manufacturer : Exide Industries Limited
Lot Qty : 110V 100Ah Plante battery set (YKP9) -01 set(55 Cells)
Test Report Date : 30.10.2019
No. of Samples drawn for Testing : 03 Nos. Cells of 100Ah (As per IS 8320:2000)

ROUTINE TEST :

Parameter Checked Observations


Visual Inspections : Found Satisfactory
Cleanliness : Found Satisfactory
Markings : MAX
MIN
EXIDE
INDUSTRIAL
Low Maintenance
P 100 P HDP ,
YKP 9
C10 Capacity : 100Ah at ECV- 1.85 V
Float Voltage : 2.25±0.02 at 27˚C
Made in India
2019
EXIDE INDUSTRIES LIMITED
Polarity Tests : Found Satisfactory
Dimensional Verifications : : Found Satisfactory
ACCEPTANCE TESTS CONDUCTED. (As per Specification No. IS 1652 :2013)
Markings : Checked and Found O.K.
Verification of Dimensions : Checked and Found O.K.

iii) ELECTRICAL PERFORMANCE REPORT (C10 Capacity)

Sample Discharge duration up Delivered Ah Delivered Ah at % Capacity at Remarks


No. to 1.85 V/ Cell at 26.5°C 27°C 27°C
01 11Hrs 10 Min 111.67 112.23 112.23 Accepted
02 11Hrs 08 Min 111.33 111.89 111.89 Accepted
03 11Hrs 12 Min 112.00 112.56 112.56 Accepted

Remarks: Accepted. For EXIDE Industries Ltd