STANDARD FACTORY ACCEPTANCE TEST - PLCC EPAX

Project Name: SCHNEIDER A/C STERILITE SHENDRA PROJECT

Pre-requisite for testing of PLCC EPAX & 2W Telephones:

1. Physical inspection of EPAX / Telephones to be done.


2. EPAX System / Telephones Make, Model & Quantity to be verified per order.
3. EPAX / Telephones functionality to be checked by connecting telephones with EPAX system.

Item / Product Tested:

Project Name : SCHNEIDER A/C STERILITE SHENDRA PROJECT


ABB PO Ref. No.: 5191049008 Dt.15.06.2018
S/n Item Description Qty. Item Serial Number
(nos.)
System PLCC EPAX :
 Make : Matrix
 Model : ETERNITY MENX16SDC
 Consist of: 01 no.
 Eternity ME 48VDC Power Supply Card
 ETERNITY MENX - External Cabinet
SYSTEM - 1  Eternity MENX-LENX Card CPU 0643
Capacity Cards in the System
 ETERNITY ME Card E&M8 01 no.
 ETERNITY ME Card E&M4 01 no.
 ETERNITY ME Card SLT8 01 no.
Redundancy Cards
 Eternity ME 48VDC Power Supply Card 01 no.
 Eternity MENX-LENX Card CPU 01 no.
Telephones Beetel C11 Phones 04 no.

Physical Verification of PLCC EPAX:

S/n Test Criteria Procedure Observation


01 Physical Check Visually Physical inspection for any damages Inspected - OK
02 Make & Model Verification To verify as per order Verified - OK
03 Quantity Verification To verify as per order Verified - OK

Tested By: Witnessed By/Reviewed By:


For Matrix ComSec Pvt. Ltd.

Name:
Company:
Designation:
Name: Mr. Ronakkumar Khant
Designation: Senior Sales Engineer – Projects
STANDARD FACTORY ACCEPTANCE TEST - PLCC EPAX

Project Name: SCHNEIDER A/C STERILITE SHENDRA PROJECT

Physical Verification of Cabinet:


S/n Test Criteria Procedure Observation
01 Color To Check Cabinet color: RAL 7024 (Graphite Grey) Tested & Found OK
02 To check Cabinet Dimension
Dimension Tested & Found OK
805 x 555 x 850.8mm (W x D x H)
03 Door To check proper openings of Door Tested & Found OK

Tested By: Witnessed By/Reviewed By:


For Matrix ComSec Pvt. Ltd.

Name:
Company:
Designation:
Name: Mr. Ronakkumar Khant
Designation: Senior Sales Engineer – Projects
STANDARD FACTORY ACCEPTANCE TEST - PLCC EPAX

Project Name: SCHNEIDER A/C STERILITE SHENDRA PROJECT

Functionality Test:

S/N Functions to Test Testing Procedure Observation


01 Voltage Variation To check system by varying the voltage from 40.8 VDC
Tested & Found OK
48VDC +/- 15% to 55.3 VDC (48VDC +/-15%)
02 EXTENSION TEST
 Flexible Flexible number for extension and Station for 2, 3, 4
Tested & Found OK
Numbering digits checked by programming
Make Extn-A busy and make a call from Extn-B to busy
Extn-A. Extn-B will have busy tone. To set Auto Call
 Auto Call Back back, during the busy tone Give “Command key” at B Tested & Found OK
and hang up. Once Extn-A gets free, A will call back to
Extn-B automatically without human intervention.
Make a call from Extn-A to Extn-B and while B is ringing,
 Call Pick Up press ‘Command key’ from Extn-C and pick up the call Tested & Found OK
to establish the speech between A & C
Make a call from Extn-A to Extn-B. Extn-A activates
conference with C, A puts B on hold by pressing
 Conference ‘FLASH’  Dial Extn-C Speech between A & C Tested & Found OK
From A, Press ‘Command keys’ to bring B in conference
 Conference (Speech) between A,B & C
Extn-A and Extn-B are in speech. If Extn-C need to talk
 Priority to Extn-A, C will use priority feature by pressing ‘Feature Tested & Found OK
Command key’
Make a call from Extn-A to Extn-B. Pick up the call at B.
 Call Transfer Now put A on hold and dial Extn-C and transfer the call Tested & Found OK
to C so Extn-A and Extn-C are in to Speech.
Make a call from Extn-A to Extn-B and hear the ring
 Ringing Tone Tested & Found OK
tone at Extn-B
Make a call from Extn-A to Extn-B and hear ring back
 Ring Back Tone Tested & Found OK
tone at Extn-A
Make a call from Extn-A to Extn-B. While Extn-A & Extn-
 Busy Tone B are in speech, make another call from Extn-C to either Tested & Found OK
Extn-A or Extn-B and hear busy tone at Extn-C
 Tone / Pulse Make a Call from Extn-A to Extn-B in Tone Mode and
Tested & Found OK
Dialing also in Pulse Mode. Speech between A & B
03 TRUNK TEST
Make a call from EPAX-A to EPAX-B. Extension at B
 Out Going Call Tested & Found OK
should ring and speech should be established.
Make a call from EPAX-B to EPAX-A. Extension at A
 Incoming Call Tested & Found OK
should ring and speech should be established.
Make a route from EPAX-A to EPAX-B busy. Call
 Alternate EPAX-B from EPAX-A. System should select another
Tested & Found OK
Routing route automatically. Extension at A should ring and
speech should be established.
Make a call from EPAX-A to EPAX-C via EPAX-B.
 Transit Call Extension at C should ring and speech should be Tested & Found OK
established.

Tested By: Witnessed By/Reviewed By:


For Matrix ComSec Pvt. Ltd.

Name:
Company:
Designation:

Name: Mr. Ronakkumar Khant


Designation: Senior Sales Engineer – Projects