3.0 Responsibility
Unit Head / Regional managers:
Unit heads / Regional managers have overall responsibility for health and safety management and role
includes:
Planning and scheduling of activities with a view to execute the project
Identify significant health and safety and eliminate or minimize them
Maintaining all legal and statutory requirement
Assist the safety team to conduct the safety training and audit at sites
Ensure all safety rules and regulations are followed at work sites
Site Engineers:
Site engineers are responsible for all aspects of health and safety on site and are accountable to the Unit
head / Regional manager. Their roles include:
Report any issue affecting health and safety issues at the work sites to the regional manager / unit
head / safety team
Coordinate with end customer / client for the taking work permit and returning work permit
Communicating the work content / hazard involved to working group through the medium of
Toolbox meeting before commencement of work every day
Initiating proactive measures to minimize / eliminate accidents
Reporting in detail in the event of incident
Ensure effective use of appropriate PPE
Ensure the quality of job at all times without any compromise on safety
“Stop Work” in the event of any serious safety violation
Prepared by Approved by
Doc No: VEPL /OHSAS/D11 Rev.No:00 Page 1 of 8
VOLTECH ENGINEERS PRIVATE LIMITED.
OPERATIONAL CONTROL PROCEDURE
OCP NO: 08
Prepared by Approved by
Doc No: VEPL /OHSAS/D11 Rev.No:00 Page 2 of 8
VOLTECH ENGINEERS PRIVATE LIMITED.
OPERATIONAL CONTROL PROCEDURE
OCP NO: 08
Prepared by Approved by
Doc No: VEPL /OHSAS/D11 Rev.No:00 Page 3 of 8
VOLTECH ENGINEERS PRIVATE LIMITED.
OPERATIONAL CONTROL PROCEDURE
OCP NO: 08
Y
MEGGER
Prepared by Approved by
Doc No: VEPL /OHSAS/D11 Rev.No:00 Page 4 of 8
VOLTECH ENGINEERS PRIVATE LIMITED.
OPERATIONAL CONTROL PROCEDURE
OCP NO: 08
IR TEST BETWEEN PHASE TO PHASE (BUS BAR):
MEGGER Y
Prepared by Approved by
Doc No: VEPL /OHSAS/D11 Rev.No:00 Page 5 of 8
VOLTECH ENGINEERS PRIVATE LIMITED.
OPERATIONAL CONTROL PROCEDURE
OCP NO: 08
Looped (Shorted) the other conductors (BØ & YØ) and connect it to the earth
Switch “ON” the test kit and apply voltage to the Bus bar and after taking the reading
Switch “OFF” the test kit
Use discharge rod to discharge the potential from the Bus bar
Repeat the above steps for measuring the other phases (YØ & BØ)
HI – POT Y
TRANSFORMER
OUTPUT
Prepared by Approved by
Doc No: VEPL /OHSAS/D11 Rev.No:00 Page 6 of 8
VOLTECH ENGINEERS PRIVATE LIMITED.
OPERATIONAL CONTROL PROCEDURE
OCP NO: 08
OCP for IR and Hi-Pot test for Bus bar is available with testing engineers
Ensure PTW system in place for the particular Panel
Ensure all supply to the equipment is dead
Unauthorized persons should not be allowed to enter Testing area
Barricade the testing area with warning tape
Proper supervision, conduct job specific toolbox meeting and barricading the entire area
Calibrated equipment shall be used
Insulated hand tools shall be used
Avoid joints for power cable and supply has to be taken via ELCB
Avoid Lone working
Use arc flash suits and shied for Hi-Pot test
Use appropriate insulated hand gloves
5.0 Final Checks & Restoration of work area after completion of work:
Prepared by Approved by
Doc No: VEPL /OHSAS/D11 Rev.No:00 Page 7 of 8
VOLTECH ENGINEERS PRIVATE LIMITED.
OPERATIONAL CONTROL PROCEDURE
OCP NO: 08
Personal
Protective
Equipment
Personal
Protective
Equipment
Prepared by Approved by
Doc No: VEPL /OHSAS/D11 Rev.No:00 Page 8 of 8