You are on page 1of 10

Doc. No.

APPSIL CHARGING REPORT


3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

1. The cabling from Battery Charger to first, last and tap cell is completed

2. The inter cell connections and cable connections are tightened properly

3. There is no physical damage to any cell and cell terminals

4. Check the cells are correctly numbered


.
5. Check all the cells are connected in correct polarity

6. Check availability of accessories like apron, gloves, hydrometer,


Cell voltage tester, thermometer etc.

7. Check the specific gravity of the electrolyte prior to pouring in the cells

8. Electrolyte is filled upto the level marked in the level indicator

9. Check there is no electrolyte leakage in the cells

10. Check the polarity of the DC connection from Battery charger to Battery

11. Charging is carried out as per the instruction manual

Remarks:

I. Name Plate Details:


Tested By Checked By Witnessed by Witnessed by
M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date
Doc. No.
APPSIL CHARGING REPORT
3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

a) Make : Exide
b) Type : YKP-25 Plante
c) AH rating : 300AH
d) Rated voltage/ cell : ECV 1.85V / Float 2.25 V
e) No. of cells in battery bank : 110
f) Specific gravity : 1205
II. Before Charging Battery Voltage:

Battery Voltage Battery Voltage

Cell
Temperature

Temperature
Cell
Cell Voltage

Cell Voltage
No
Specific

Specific
Gravity

Gravity
No

1 1.98 1140 29’ C 19 1.993 1140 29’ C


2 2.00 1140 29’ C 20 1.995 1140 29’ C
3 2.010 1140 29’ C 21 1.989 1140 29’ C
4 2.002 1140 29’ C 22 1.988 1140 29’ C
5 1.998 1140 29’ C 23 1.994 1140 29’ C
6 2.00 1140 29’ C 24 1.988 1140 29’ C
7 1.983 1140 29’ C 25 2.020 1140 29’ C
8 1.998 1140 29’ C 26 1.984 1140 29’ C
9 1.996 1140 29’ C 27 1.995 1140 29’ C
10 1.995 1140 29’ C 28 1.987 1140 29’ C
11 2.005 1140 29’ C 29 1.997 1140 29’ C
12 2.001 1140 29’ C 30 2.004 1140 29’ C
13 2.002 1140 29’ C 31 1.987 1140 29’ C
14 2.003 1140 29’ C 32 1.985 1140 29’ C
15 2.004 1140 29’ C 33 1.989 1140 29’ C
16 2.003 1140 29’ C 34 1.992 1140 29’ C
17 1.999 1140 29’ C 35 1.992 1140 29’ C
18 1.994 1140 29’ C 36 1.989 1140 29’ C
Cell Battery Voltage
Tested By Checked By Witnessed by Witnessed by
M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date
Doc. No.
APPSIL CHARGING REPORT
3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

Battery Voltage

reTemperatu

Temperatu
Specific Cell No

Specific
Gravity

Gravity
Voltage

Voltage
No
Cell

Cell

re
37 1.993 1140 29’ C 64 1.995 1140 29’ C
38 1.997 1140 29’ C 65 1.996 1140 29’ C
39 1.998 1140 29’ C 66 1.996 1140 29’ C
40 1.989 1140 29’ C 67 1.937 1140 29’ C
41 1.992 1140 29’ C 68 1.990 1140 29’ C
42 1.999 1140 29’ C 69 1.996 1140 29’ C
43 1.998 1140 29’ C 70 1.986 1140 29’ C
44 2.001 1140 29’ C 71 1.990 1140 29’ C
45 2.002 1140 29’ C 72 1.994 1140 29’ C
46 1.997 1140 29’ C 73 2.00 1140 29’ C
47 1.998 1140 29’ C 74 1.999 1140 29’ C
48 2.003 1140 29’ C 75 2.001 1140 29’ C
49 2.002 1140 29’ C 76 1.987 1140 29’ C
50 2.004 1140 29’ C 77 1.994 1140 29’ C
51 1.998 1140 29’ C 78 1.992 1140 29’ C
52 1.996 1140 29’ C 79 1.992 1140 29’ C
53 1.741 1140 29’ C 80 1.981 1140 29’ C
54 1.705 1140 29’ C 81 1.998 1140 29’ C
55 1.994 1140 29’ C 82 1.989 1140 29’ C
56 1.989 1140 29’ C 83 1.984 1140 29’ C
57 1.987 1140 29’ C 84 1.994 1140 29’ C
58 1.990 1140 29’ C 85 1.987 1140 29’ C
59 1.987 1140 29’ C 86 1.986 1140 29’ C
60 1.983 1140 29’ C 87 1.985 1140 29’ C
61 2.001 1140 29’ C 88 1.989 1140 29’ C
62 1.989 1140 29’ C 89 1.989 1140 29’ C
63 1.994 1140 29’ C 90 2.00 1140 29’ C
Cell Battery Voltage

Tested By Checked By Witnessed by Witnessed by


M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date
Doc. No.
APPSIL CHARGING REPORT
3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

Battery Voltage

Cell

Temperature

Temperature
Cell Voltage

Cell Voltage
No
Specific

Specific
Gravity

Gravity
No

91 2.003 1140 29’ C 102 1.995 1140 29’ C


92 2.000 1140 29’ C 103 2.002 1140 29’ C
93 1.994 1140 29’ C 104 2.002 1140 29’ C
94 1.991 1140 29’ C 105 2.006 1140 29’ C
95 2.002 1140 29’ C 106 1.993 1140 29’ C
96 2.002 1140 29’ C 107 2.003 1140 29’ C
97 2.003 1140 29’ C 108 1.986 1140 29’ C
98 2.002 1140 29’ C 109 1.999 1140 29’ C
99 2.002 1140 29’ C 110 1.995 1140 29’ C
100 2.004 1140 29’ C 109 1.996 1140 29’ C
101 2.001 1140 29’ C 110 1.982 1140 29’ C

III. Battery Voltage during Charging & Discharging :

Tested By Checked By Witnessed by Witnessed by


M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date
Doc. No.
APPSIL CHARGING REPORT
3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

During Charging During Discharging


Time 10/11/20 @4.00 Pm Time 14/11/20@11:30 AM
Discharging
Cell Charging Current 21A 30 A
Current
No
Battery Voltage 232.5 Battery Voltage 222.0V
Cell Specific Cell Specific
Temperature Temperature
Voltage Gravity Voltage Gravity
1 2.11 1145 26’C 2.02 1220 23.2’C
2 2.11 1140 26’C 2.02 1220 23.2’C
3 2.12 1145 26’C 2.02 1220 23.2’C
4 2.12 1140 26’C 2.02 1220 23.2’C

Tested By Checked By Witnessed by Witnessed by


M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date
Doc. No.
APPSIL CHARGING REPORT
3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

5 2.11 1140 26’C 2.02 1220 23.2’C


6 2.10 1145 26’C 2.02 1220 23.2’C
7 2.10 1140 26’C 2.02 1220 23.2’C
8 2.11 1140 26’C 2.02 1220 23.2’C
9 2.11 1150 26’C 2.02 1220 23.2’C
10 2.11 1150 26’C 2.02 1220 23.2’C
11 2.11 1145 26’C 2.03 1220 23.2’C
12 2.11 1140 26’C 2.02 1220 23.2’C
13 2.11 1145 26’C 2.02 1220 23.2’C
14 2.11 1140 26’C 2.02 1220 23.2’C
15 2.12 1145 26’C 2.02 1220 23.2’C
16 2.12 1145 26’C 2.02 1220 23.2’C
17 2.11 1140 26’C 2.03 1220 23.2’C
18 2.10 1140 26’C 2.03 1220 23.2’C
19 2.10 1150 26’C 2.03 1220 23.2’C
20 2.10 1145 26’C 2.03 1220 23.2’C
21 2.10 1145 26’C 2.02 1220 23.2’C
22 2.10 1140 26’C 2.03 1220 23.2’C
23 2.10 1145 26’C 2.03 1220 23.2’C
24 2.09 1150 26’C 2.02 1220 23.2’C
25 2.11 1140 26’C 2.02 1220 23.2’C
26 2.09 1140 26’C 2.03 1220 23.2’C
During Charging During Discharging
Time 10/11/20 @4.00 Pm Time 14/11/20@11:30 AM
Discharging
Cell Charging Current 21A 30 A
Current
No
Battery Voltage 232.5 Battery Voltage 222.0V
Cell Specific Cell Specific
Temperature Temperature
Voltage Gravity Voltage Gravity
27 2.11 1145 26’C 2.03 1220 23.2’C
28 2.10 1140 26’C 2.03 1220 23.2’C
29 2.11 1140 26’C 2.02 1220 23.2’C
30 2.09 1145 26’C 2.02 1220 23.2’C
31 2.09 1140 26’C 2.02 1220 23.2’C

Tested By Checked By Witnessed by Witnessed by


M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date
Doc. No.
APPSIL CHARGING REPORT
3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

32 2.09 1140 26’C 2.02 1220 23.2’C


33 2.09 1150 26’C 2.02 1220 23.2’C
34 2.10 1150 26’C 2.02 1220 23.2’C
35 2.09 1140 26’C 2.03 1220 23.2’C
36 2.09 1140 26’C 2.02 1220 23.2’C
37 2.10 1145 26’C 2.03 1220 23.2’C
38 2.09 1145 26’C 2.02 1220 23.2’C
39 2.10 1150 26’C 2.02 1220 23.2’C
40 2.11 1140 26’C 2.02 1220 23.2’C
41 2.11 1145 26’C 2.03 1220 23.2’C
42 2.11 1150 26’C 2.03 1220 23.2’C
43 2.12 1140 26’C 2.02 1220 23.2’C
44 2.13 1140 26’C 2.02 1220 23.2’C
45 2.11 1150 26’C 2.02 1220 23.2’C
46 2.12 1140 26’C 2.02 1220 23.2’C
47 2.13 1150 26’C 2.02 1220 23.2’C
48 2.13 1145 26’C 2.02 1220 23.2’C
49 2.13 1150 26’C 2.02 1220 23.2’C
50 2.11 1140 26’C 2.02 1220 23.2’C
51 2.10 1145 26’C 2.02 1220 23.2’C
52 2.10 1150 26’C 2.02 1220 23.2’C
53 2.04 1140 26’C 2.02 1220 23.2’C
During Charging During Discharging
Time 10/11/20 @4.00 Pm Time 14/11/20@11:30 AM
Discharging
Cell Charging Current 21A 30 A
Current
No
Battery Voltage 232.5 Battery Voltage 222.0V
Cell Specific Cell Specific
Temperature Temperature
Voltage Gravity Voltage Gravity
54 2.013 1140 26’C 2.02 1220 23.2’C
55 2.11 1150 26’C 2.02 1220 23.2’C
56 2.10 1140 26’C 2.02 1220 23.2’C
57 2.10 1145 26’C 2.02 1220 23.2’C
58 2.10 1140 26’C 2.02 1220 23.2’C

Tested By Checked By Witnessed by Witnessed by


M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date
Doc. No.
APPSIL CHARGING REPORT
3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

59 2.09 1150 26’C 2.02 1220 23.2’C


60 2.09 1140 26’C 2.02 1220 23.2’C
61 2.11 1140 26’C 2.02 1220 23.2’C
62 2.10 1140 26’C 2.02 1220 23.2’C
63 2.10 1145 26’C 2.02 1220 23.2’C
64 2.11 1140 26’C 2.02 1220 23.2’C
65 2.11 1140 26’C 2.02 1220 23.2’C
66 2.11 1145 26’C 2.02 1220 23.2’C
67 2.05 1140 26’C 2.02 1220 23.2’C
68 2.10 1145 26’C 2.02 1220 23.2’C
69 2.11 1140 26’C 2.02 1220 23.2’C
70 2.10 1140 26’C 2.02 1220 23.2’C
71 2.09 1145 26’C 2.02 1220 23.2’C
72 2.10 1150 26’C 2.02 1220 23.2’C
73 2.11 1150 26’C 2.02 1220 23.2’C
74 2.11 1140 26’C 2.02 1220 23.2’C
75 2.11 1140 26’C 2.02 1220 23.2’C
76 2.11 1140 26’C 2.02 1220 23.2’C
77 2.10 1145 26’C 2.02 1220 23.2’C
78 2.10 1140 26’C 2.02 1220 23.2’C
79 2.10 1140 26’C 2.02 1220 23.2’C
80 2.09 1145 26’C 2.02 1220 23.2’C
During Charging During Discharging
Time 10/11/20 @4.00 Pm Time 14/11/20@11:30 AM
Discharging
Charging Current 21A 30 A
Current
Battery Voltage 232.5 Battery Voltage 222.0V
Cell Cell Specific Cell Specific
Temperature Temperature
No Voltage Gravity Voltage Gravity
81 2.11 1145 26’C 2.02 1220 23.2’C
82 2.12 1150 26’C 2.02 1220 23.2’C
83 2.09 1140 26’C 2.02 1220 23.2’C
84 2.10 1140 26’C 2.02 1220 23.2’C
85 2.10 1150 26’C 2.02 1220 23.2’C

Tested By Checked By Witnessed by Witnessed by


M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date
Doc. No.
APPSIL CHARGING REPORT
3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

86 2.09 1140 26’C 2.02 1220 23.2’C


87 2.09 1140 26’C 2.02 1220 23.2’C
88 2.09 1150 26’C 2.02 1220 23.2’C
89 2.10 1150 26’C 2.02 1220 23.2’C
90 2.12 1140 26’C 2.02 1220 23.2’C
91 2.13 1140 26’C 2.02 1220 23.2’C
92 2.11 1140 26’C 2.02 1220 23.2’C
93 2.10 1140 26’C 2.02 1220 23.2’C
94 2.09 1145 26’C 2.02 1220 23.2’C
95 2.13 1150 26’C 2.02 1220 23.2’C
96 2.13 1140 26’C 2.02 1220 23.2’C
97 2.13 1140 26’C 2.02 1220 23.2’C
98 2.12 1140 26’C 2.02 1220 23.2’C
99 2.13 1140 26’C 2.03 1220 23.2’C
100 2.12 1145 26’C 2.03 1220 23.2’C
101 2.11 1140 26’C 2.03 1220 23.2’C
102 2.14 1150 26’C 2.02 1220 23.2’C
103 2.12 1150 26’C 2.03 1220 23.2’C
104 2.12 1140 26’C 2.03 1220 23.2’C
105 2.10 1140 26’C 2.03 1220 23.2’C
106 2.13 1150 26’C 2.02 1220 23.2’C
107 2.09 1150 26’C 2.02 1220 23.2’C
During Charging During Discharging
Time 10/11/20 @4.00 Pm Time 14/11/20@11:30 AM
Discharging
Charging Current 21A 30 A
Current
Battery Voltage 232.5 Battery Voltage 222.0V
Cell Cell Specific Cell Specific
Temperature Temperature
No Voltage Gravity Voltage Gravity
108 2.11 1140 26’C 2.03 1220 23.2’C
109 2.10 1140 26’C 2.03 1220 23.2’C
110 2.10 1150 26’C 2.02 1220 23.2’C

 Total Charging Hours : 79 Hours

Tested By Checked By Witnessed by Witnessed by


M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date
Doc. No.
APPSIL CHARGING REPORT
3VIN2226SFQPSTR-SB
Location & Designation
Equipment Rev.
GIS BUILDING/BATTERY Date:10/11/2020
Battery # 1 Nil
ROOM
Customer Project Sheet
M/s BRIGADE TECH 66/11KV GIS BRIGADE TECH Job order No.
GARDEN,BROOKFIELDS,BANGALORE GARDEN
1 of 3

 Total Discharging Hours : 10 Hours

 Recharging Hours : 18 Hours

Tested By Checked By Witnessed by Witnessed by


M/s EXIDE M/S APPSIL M/s KPTCL M/s Brigade Tech
Name

Signature
Date