Professional Documents
Culture Documents
VOLUME 2
System Operation
Publication ref GED00230017
Revision No. 1
October 2014
VOLUME 2, October 2014
For the latest updates to all technical documentation please register at www.energymanager-online.com
Chapter 1
OVERVIEW
CHAPTER CONTENTS
MASTER SEQUENCES 1
OVERVIEW
OVERVIEW
OVERVIEW
1 MASTER SEQUENCES
(1) The master sequence c ontrol is st arted from the p ackage control system
(PCS). It controls the co-ordinated start-up and sh utdown of the plant as
specified in the Plant S tate and operator selected configuration
requirements. It is the control interf ace for the plant for permitted changes
of operation instructions.
Each sequence operates drives (valves, pumps etc.) through lower level control
and protection systems as necessary . The control for a drive must be switched
to remote at its control station at the MCC to operate that drive.
(1) Make sure the GT fire suppression system, the site fire detection/protection
system, and all rela ted safety equipment are fully operat ional during plant
operation. Remove or isolate any fire hazards or potentially hazardous
conditions as soon as possible to prevent injury or equipment damage.
(2) When maintenance work is done with cutting or welding equipment, put fire
watchers, with fire extinguishers ready, at necessary locations.
(3) Do not smoke or use equipment that can cause fire near to a fuel which
gives off flammable vapor. Drain (including vapors) all systems that contain
such a fuel or remove unwanted materi als and test before work is st arted.
Make sure that the maintenance area stays sufficiently ventilated. Refer to
the plant's safety instructions for more detailed data.
OVERVIEW
(4) Make sure that all maintenance wo rk is complete and that all st art-up
danger notices are cleared and remo ved from equipment befo re start-up.
Before start-up, do an analysis of maintenance done during shut down to
make sure that all system functions are now available.
(5) Monitor the normal operational condi tions of each system, it s equipment
and component s to find variations fr om those conditions and fun ction.
Report unusual conditions or malfunctions as soon as possible. Equipment
failures frequently occur in the firs t 30 minutes of operation. Do several
checks during this time to make sure that operation is satisfactory.
(6) If at any time during an operations procedure, the necessary effect for a
given action does not occur, inform the operations engineer in charge.
(7) Safety boot s, safety glasses, lumi nous vest s and overalls must be wo rn
when you move around the equipment.
(8) Clean up lubricating fluids deposited on the floors of the plant as a result of
leaks or spills as soon as possible to prevent personnel injury.
(9) Isolate the equipment correctly before all maintenance work is started. Put
warning notices on the relevant breakers, switches, valves etc. as specified
by plant safety instructions.
(10) Refer to the plant safety instru ctions before you work with hazardous
materials. Make sure that emerg ency shower and eyewash st ations a re
available before you touch or work with stored chemicals, or feed systems.
Use the correct PPE equipment when you work with industrial chemicals.
(11) Refer to the plant safety instructi ons before you enter an isolated t ank or
empty space.
(12) Do not byp ass safety sequences and interlocks unless authorized by a
particular work or test procedure. This is very important for the GT fuel
management programmes.
(13) Use the plant drainage systems only for their correct purpose. They should
receive only those liquids for which they are applicable.
(1) Be careful when you work near to rotating equipment such as engines, fans,
motors, turbines, etc. to make sure clothing is not caught in the rot ating
equipment. These precautions also applywhen you work near moving drive
belts and operating linkages.
OVERVIEW
(2) Wear protective clothing when you work near to hot surfaces, pipework and
equipment that could cause burns and dangerous inju ry to operating
personnel.
(3) Slowly open isolation valves in a pressurized and heated system to prevent
thermal shock to pipework and tanks, unless operating instructions specify
differently.
(4) Slowly open vent and drain valves to prevent injury to personnel from high
pressure fluids. Make sure all pressure is released from a particular system
or component before you start work on that system or component.
(5) Before you operate the valves, make sure you understand the type of valve
used, such as ball valve or butterfl y valve, and the subsequent ef fects the
operation of the valve may have on the system.
(6) Make sure the fluid in heated fluid systems is cooled correctly before you
start work on that syst em. This includes wate r systems and systems that
have lubricants and anti-freeze and water systems.
(7) Take care when you oper ate large manual valves. This is very import ant
when operation of the va lve is not easy because of location. If necessary ,
get assistance to operate large valves , to avoid possible back or muscle
injury.
(8) In fuel systems, specially those using gas, tighten valve packing at regular
intervals and check the co ndition of the packing with a leak detector. Take
the same precautions with pipework systems that carry chemicals.
(9) When you do work on a system that hasinterlocks or safety protection, use
correct work procedures that include special instructions on re-testing. This
includes relief/safety valves.
(10) Keep pressurized air systems free of contaminants such as oil and other
flammable liquids. Fast compression of such cont aminants can cause an
explosion due to heat gener ated from compression. This effect, known as
'diesel effect', can cause dangerous personnel and equipment hazards.
OVERVIEW
(12) When using a valve sp anner, make sure that the 'thumb' of the sp anner
points in the direction of rotation.
(1) Close the doors of all electric al p anels and switch-gear and engage
fasteners, unless working in the panel.
(2) Do not open or close electrical disconnect switch es while on load unless
specially made for operations on load. Open the correct isolation breaker(s)
before you start to operate the disconnect switch.
(3) Make sure that earth switches are open before you close the related
disconnect(s). Do not let interlocks be the only precaution.
(4) Always examine the switch-gear bef ore it is energized. The inspection
steps that follow should include, but are not necessarily limited to:
(b) All covers are correctly installed and all doors are closed.
(e) Safety barriers are in place to prevent personnel access to the area of
switch-gear to be energized.
(5) Do not reset a tripped break er or controller before the fault is corrected or
isolated, unless in low volt age cond itions. In low volt age con ditions
(415V AC or lower), reset a tripped breaker or controller once only. If a fault
condition causes another trip, isolate the component and correct the fault.
(6) Take care when you work on uninter ruptible power supply (UPS) systems
and their battery chargers. Only qualified personnel,with special knowledge
of the system, must work on or oper ate these systems. This is very
important to the multiple power sources (AC and DC) connected with UPS
systems.
OVERVIEW
(7) A fully operational eyew ash must be inst alled near areas where work with
liquid batteries will be done. The PPE that follows must be used:
(8) Make sure that the batteries are kept clean, the cells are covered, and the
battery box covers are in positi on. Use only recommended cables and
connections. Make sure that suf ficient ventilation exist s before you st art
battery charging operations.
(9) Do not disconnect a chargi ng unit circuit or battery circuit cab les from a
battery when the charger is in operation.
OVERVIEW
OVERVIEW
Chapter 2
GAS TURBINE
CHAPTER CONTENTS
PRE-START CHECKS 2
GT Installation Checks 2.1
Electric Starter Motor Commissioning 2.2
Electric Starter Motor Lube Oil System 2.3
GT Lubrication Oil System 2.4
Hydraulic Control Oil System 2.5
START-UP 3
Start Sequence 3.1
Electric Starter Motor Lube Oil System 3.2
GT Lubrication Oil System 3.3
Hydraulic Control Oil System 3.4
NORMAL OPERATIONS 4
Normal Running 4.1
Operational Checks 4.2
Electric Starter Motor Lube Oil System 4.3
GT Lubrication Oil System 4.4
Hydraulic Control Oil System 4.5
SHUTDOWN 5
Normal Shutdown Sequence 5.1
Electric Starter Motor Lube Oil System 5.2
GT Lubrication Oil System 5.3
Hydraulic Control Oil System 5.4
UNSCHEDULED SHUTDOWN 6
Introduction 6.1
GAS TURBINE
GAS TURBINE
GAS TURBINE
1.1 Introduction
(1) This chapter specifies the operating limit s of the Industrial T rent GT .
Rolls-Royce will not accept respo nsibility for damage or malfunction that
could occur.
(2) You must operate the equ ipment to the commissi oning limit s that are
specified i n t he Mast er Applications, Inst allation, and Commissioning
Schedule for this project.
Before the gas turbine (GT) can st art, the p ackage control system (PCS) will
automatically do a number of pre-start checks as part of the start sequence. The
start sequence will not start if a condition that follows occurs:
(4) The fuel and vent valves are not set to their correct positions.
(5) The water injection and metering system skid (WIMS) discharge valve is in
bypass and the water injection drain valve is opened.
(7) The temperature of the GT lubricat ion oil in the reservoir is less than
15 deg.C. (59 deg.F.).
(8) The oil level is not in the range specified in the alarm trip matrix.
GAS TURBINE
1.4 GT Instrumentation
2 PRE-START CHECKS
CAUTION YOU MUST DO THE CHE CKS AND INSPE CTIONS THA T
FOLLOW BEFORE YOU TRY TO START THE GT.
(1) Make sure that the GT is clean and that it is correctly att ached to the
mountings. Make sure that the air inlet system is correctly attached.
(2) Examine the GT components, tubes, pipes and electrical connections (also
those electrical connections on the battery plates). Make sure that they are
assembled and attached correctly.
(3) Make sure that the oil levels are correct and that only approved lubricants
are used.
(4) Make sure that the gas detection system is fully serviceable and is correctly
calibrated.
(5) Make sure that the fire detec tion and extinguishing systems are fully
serviceable and are correctly calibrated.
(6) Examine the gas detec tion, and the fire detec tion and extinguishing
systems at the intervals specified by the system manufacturers.
GAS TURBINE
Before the first operation of the electric starter motor af ter the st arter motor or
gearbox is replaced, flush the electric starter motor lube oil system to remove all
unwanted material. Refer to Customer Support for more data.
3 START-UP
The start sequence is started by the PCS and is controlled by the engine control
system (ECS) when the start conditions are satisfactory. (Refer to Chapter 4 for
system start details).
GAS TURBINE
(2) The ECS will start the engine start sequence as follows:
(b) Energize the igniters and open the primary metering valve.
(c) Detect light-up and sc hedule the fuel flow to sub synchronized idle
speed.
4 NORMAL OPERATIONS
(1) Power limit (58 to 64 MW if fuel type and use of WIMS and/or ISI).
(2) TGT limit (based on a function of the T20 te mperature and if the water
injection is on or off).
GAS TURBINE
4.2.1 Introduction
This data gives the usual performance values for the GT when it operates in the
limits of operation. Adjustment of the GT to corr ect performance is usually only
necessary when components are replaced.
4.2.2 Record of GT check run to sub synchronized and synchronized idle speed
(1) Station.
(2) GT No.
(3) Date.
(11) Run-down time from sub synchronized and synchronized idle speed.
GAS TURBINE
(7) TGT.
The performance of the GT is related to, and changes with ambient temperature
and atmospheric pressure. Thus, it is necessary to correct the performance limits
back to those recorded at standard atmospheric conditions. The standard (ISO)
conditions are a temperature of 15 deg.C. (59 deg.F .) and an atmospheric
pressure of 760 mm of mercury (14.7 psi).
A compressor wash must be done before you do the performance comp arison.
The performance point s from the performance comp arison must be comp ared
with the performance curve that was done during the commissioning of the GT.
GAS TURBINE
5 SHUTDOWN
(2) When the PCS receives a signal to shutdown or stop, the PCS st arts the
shutdown sequence by unloading the AC generator package.
(3) When the AC generator load is less than 0.5 to 1 MW the generator circuit
breaker is opened automatica lly by the PCS, or manu ally by the operator.
The PCS will then send a shut down signal to the ECS to tell it to st art its
own shutdown sequence.
(i) Let the GT engine cool while still running at sync speed.
(ii) Close the fuel valve, metering valve and open vent valves.
(4) When the ECS shutdown sequence is complete and the fuel is stopped, the
PCS will st art the GT enclosure cool down and shut down the auxiliary
systems.
GAS TURBINE
6 UNSCHEDULED SHUTDOWN
6.1 Introduction
(1) If a condition is sensed by the PCS or the ECS t hat will cause damage to
the GT engine, then the PCS or t he ECS will st art an unscheduled
shutdown.
(2) There are two types of unschedul ed shut down, the CSD (Controlled
Shutdown) and the ESD (Emergency Shutdown).
(1) When a condition is sensed, the PCS and/or the ECS will unload the GT.
(j) Gas fuel system pressure measurement or fuel metering valve (FMV)
minor fault.
(1) When a failure in the auxiliary systems or GT is sensed, the PCS or SIS will
start an ESD. This closes the high speed shut-off valve (HSSOV) and opens
the vent valves. The double block and bl eed valves will only operate for a
fire or gas trip.
GAS TURBINE
(g) Turbines disc temperature upper limi t too high o r sensor failure (T42
and T44 thermocouples).
(p) IP compressor inlet and gas fuel skid inlet and outlet pressure
measurement not sensed.
(q) Failure sensed in the IP variable stator vane (VSV) control system.
(v) Overspeed.
GAS TURBINE
GAS TURBINE
Chapter 3
AC GENERATOR
CHAPTER CONTENTS
AC GENERATOR
AC GENERATOR
AC GENERATOR
Plant shutdown.
1.2 References
(1) Make sure that the starter isolators for the AC motor, driven oil pumps are
in the closed position, and that the Hand-Off-Auto (HOA) switch is set to the
‘Auto’ position.
(2) Make sure that the st arter isolator for the jacking oil pump is in the closed
position, and that the HOA switch is set to the ‘Auto’ position.
(3) Make sure that the starter isolator for the air/oil extractor, vent fan is in the
closed position, and that the HOA switch is set to the ‘Auto’ position.
(4) Make sure that the isol ator for the oil reservoir heater is in the closed
position.
(5) Make sure that all the motor and generator heater isolators are in the closed
positions.
Make sure that the isolat or fo r th e DC mo tor, driven oil pump is in the closed
position.
(1) Make sure that the isolat or valve for the oil reserv oir drain is in the closed
position.
AC GENERATOR
(2) Look at the oil level gauge. Make sure that the oil level is more than 3/4 full
reservoir.
(4) Make sure that the isolator valve for the AC motor oil pump No.1 (pressure
side) is locked in the open position.
(5) Make sure that the isolator valve for the AC motor oil pump No.2 (pressure
side) is locked in the open position.
(6) Make sure that the isolator valve for the DC motor oil pump (pressure side)
is locked in the open position.
(7) At the pressure differential transmitter (PDT) for the duplex oil filter:
(a) Make sure that the isolator valves are in the open position.
(b) Make sure that the equalizer valves are in the closed position.
(c) Make sure that the vent valve is in the closed position.
(8) At the pressure transmitter for the generator bearing oil supply:
(a) Make sure that the isolator valve is in the open position.
(b) Make sure that the vent valve bleed is in the closed position.
(c) Make sure that the starter isolator for the DC motor, driven oil pump is
in the closed position, and that the Hands-Off-Auto (HOA) switch is set
to the ‘Auto’ position.
(d) Make sure that the drain and vent valves for the duplex oil filter are all
in the closed positions.
Make sure that the isolator valve for the jacking oil pump (suction side) is in the
open position.
(1) Make sure that all the alarms and tr ips are cancelled and set back to their
usual condition. Do a check that t he generator lubricat ion oil levels and
temperatures are satisfactory.
(2) Make sure that the alar m for the fire protection sy stem is not in operation,
and that the system is satisfactory.
AC GENERATOR
(3) Make sure that the generator lo ckout relays are se t to their normal
serviceable condition.
(4) Make sure that the generator sy nchronizing and control equipment is
available to start. Move the selector switches to the positions that follow:
(5) Make sure that the gen erator shaft ground brush is in good condition and
that the spring applies a good load to the brush.
(6) Make sure that the exciter breather installed on the top of the exciter casing
is not blocked.
(7) Make sure that all the exciter covers are in position and correctly attached.
(8) Do a check that the water coolant system is available before start.
(1) Make sure the area around the generator is free of unwanted material and
oil/coolant leaks that could cause a fire or be dangerous to personnel.
(2) Make sure that the guards for the generator shaft coupling are in position
and correctly attached.
JOB COMPLETE
Plant shutdown.
2.2 References
AC GENERATOR
2.4 Pre-Start Checks from the Station Control Human/Machine Interface (HMI)
(1) Use the lubrication oil system displayon the station control HMI. Look at the
indications that follow and make sure that they are correct:
(a) Lubrication oil reservoir level is above the necessary minimum level.
The start sequence will not start if the temperature of the generator lubrication oil
in the reservoir is less than 22 deg.C. (72 deg.F.). Also, the unit will not st art if
there is no lubrication oil system pressure.
2.6 Start-Up
(1) Use the lubrication oil system displayon the station control HMI. Look at the
indications that follow and make sure that they are correct:
(a) Differential pressure across the oil filter must not be more than
200 kPa (29 psi). Thus, the display graphic shows that the filter is not
blocked.
(b) Lubrication oil supply pressure must increase from zero to 160 kPa
(23.2 psi).
(c) Lubrication oil reservoir level must not decrease below the 677mm
(26.65 in.) minimum necessary level.
AC GENERATOR
(f) The AC motor-driven oil pump st arts and the oil supply pressure
increases from zero to approximately 200 kPa (29 psi).
(g) The jacking oil pump and the AC motor-driven oi l pump will supply a
jacking pressure of not more than 9500 kPa (1377 psi) to the
generator pedestal.
(i) When the generator rotor shaft starts to turn, the jacking oil pump will
continue to operate and deliver a holding pressure of 7000 kPa (1015
psi) until it is automatically st opped as the generator shaf t speed
increases to more than 130 rpm.
(1) GT started and operates to the synchronous speed (NL 3000 rpm).
(6) When the generator output is synchronized to the specified limit s, the
generator circuit breaker is automatically closed.
(7) When the generator is connected to the grid, the generator load is
automatically increased to minimum power.
JOB COMPLETE
AC GENERATOR
Plant in operation.
3.2 References
(a) GT synchronized.
JOB COMPLETE
Plant in operation.
4.2 References
AC GENERATOR
Use the lubrication oil system displa y on the st ation control HMI. During
GT shutdown, make sure that the differential pressure across the lubrication oil
filter decreases to zero.
(1) When the automatic shutdown sequence is started, the shutdown sequence
that follows will occur automatically:
(e) When the GT has fully stopped, the generator lubrication oil pump
continues to operate for 30 minutes and shuts down.
(2) At 1 MW, the generator circuit br eaker can be opened from the st ation
control HMI or from the generator cont rol and protection panel in the unit
control cabin as follows:
(i) Make a selection of the GTgen. control graphic screen and push
the ‘open generator CB’ button.
(i) Operate the hard wi red switch to man ually open the generator
circuit breaker.
AC GENERATOR
(1) Do the checks that follow to prepare the unit for a subsequent start-up.
(a) Make sure that the lubrication oil level at the HMI is above the
necessary minimum level for operation.
(b) Make sure that the temperature of the lubrication oil in the reservoir at
the HMI is in the specified limits.
JOB COMPLETE
AC GENERATOR
Chapter 4
CHAPTER CONTENTS
Plant Shutdown.
1.2 References
1.4 Start-Up
(a) Make sure that all trips are reset and that there are no fault indications
on the HMI.
(b) The Package Control System (PCS) Human Machine Interface (HMI).
(b) The conditions that follow must be met in 30 seconds to satisfy this
sequence step:
(b) The conditions that follow must be met in 30 seconds to satisfy this
sequence step:
(ii) Generator lube oil supply pressure >low alarm setting 80 kPa
(11.6 psi).
(b) The conditions that follow must be met in 300 seconds to satisfy this
sequence step:
(i) DE Jacking oil pressure >low alarm setting 5000 kPa (725 psi).
(ii) NDE Jacking oil pressure >low alarm setting 5000 kPa (725 psi).
(b) The conditions that follow must be met in 80 seconds to satisfy this
sequence step:
(b) The conditions that follow must be met in 60 seconds to satisfy this
sequence step:
(ii) GT enclosure dif ferential pre ssure >low alarm setting. 0.6 kPa
(0.08 psi).
(a) The condition that follows must be met to satisfy this sequence step:
(8) Step 4 - Request permission from ECS to initiate the GT starter sequence:
(b) The condition that follows must be met in 10 seconds to satisfy this
sequence step:
(a) The condition that follows must be met in 60 seconds to satisfy this
sequence step:
(a) The condition that follows must be met in four minutes to satisfy this
sequence step:
(a) The condition that follows must be met in 71 seconds to satisfy this
sequence step:
(a) The conditions that follow must be met to satisfy this sequence step:
(c) The following condition must be met to satisfy this sequence step:
(a) The con ditions th at follow must be met in 80 se conds to satisfy this
sequence step:
(a) The con ditions th at follow must be met in 60 se conds to satisfy this
sequence step:
(a) The conditions that follow must be met to satisfy this sequence step:.
(b) The conditions that follow must be met in 24 0 seconds to satisfy this
sequence step:
JOB COMPLETE
Plant in Operation.
2.2 References
(1) The normal stop sequence is initiated when a signal is received from one of
these sources:
(b) A sto p unit signal from the dist ributed control s ystem (operator
controlled shutdown).
(c) A stop unit s ignal from the p ackage co ntrol HMI (operator controlled
shutdown).
A signal that the GT n ormal shut down sequenc e is active is sent to the st art
sequence.
(b) The conditions that follow must be met to satisfy this sequence step:
(b) The condition that follows must be met to satisfy this sequence step:
(b) The conditions that follow must be met to satisfy this sequence step:
(iv) The stop sequence complete signal is received from the ECS.
(b) The condition that follows must be met to satisfy this sequence step:
(b) The conditions that follow must be met to satisfy this sequence step:
(b) The condition that follows must be met to satisfy this sequence step:
(b) The condition that follows must be met to satisfy this sequence step:
JOB COMPLETE
Chapter 5
CHAPTER CONTENTS
Plant Shutdown.
1.2 References
(e) ESM oil pump motor , st arter isolator is closed and HOA switch
selected to ‘Auto’.
(f) Hydraulic oil reservoir heater isolator is closed and HOA switch
selected to ‘Auto’.
(1) Make sure that the ESM system valves are in position as follows:
(c) HV0702 demister drain sample isolating valve Closed and locked.
(g) HV0708, HV0709, HV 0716 and HV0717dupl ex filter (FIL TER 070 1)
bleed valves are all closed.
(h) FILTER 0702 duplex filter, make sure filter selection lever is switched
to the filter to be used for 100% duty. Check bleed valves HV0710,
HV0711, HV0712, HV0713, HV 0718, HV0719, HV0720 and HV0721
in the closed position.
(1) Make sure that the motor is correctly in position and covers attached.
(2) Make sure that all cables are free from external damage and deformity.
(3) Make sure the area around and below the motor is free of oil/coolant leaks
and unwanted materials that can cause a fire or personnel hazard.
Make sure that the ESM hydraulic system supply and return flexible hoses are
free from external damage and defect.
(1) Make sure the area around the system is free of oil leaks and unwanted
materials that could cause a fire or personnel hazard.
(4) Make sure that the enc losure lighting is switch ed of f when you exit the
enclosure.
JOB COMPLETE
Plant Shutdown.
2.2 References
2.4 Pre-requisites
(2) Start-up of the electric start system is linked to the start of the gas turbine.
When the operator st arts the gas turb ine, the electric st art system is
activated.
2.5 Start-Up
The plant start up sequence causes operation of the electric start sequence.
(1) During start-up, the control room operator must monitor these electric start
systems indications:
(g) Differential pressure across filters must not set off an alarm.
(h) Oil reservoir level must not decrease below the minimum operational
level.
(2) A description of the start sequence and the steps of operation during engine
start up are in V olume 1 Chapter 5, Pa ra 3 - Ele ctric S tart System,
Operation.
JOB COMPLETE
Plant in operation.
3.2 References
(a) On power-up the turbine will accelerate to 500 rpm in 60 seconds and
watchdog timer sequence fail will not occur.
(b) As the turbine accelerates to 3000rpm, the purge cycle will be started.
(d) After ignition stop s, the turbine will accele rate to approximately
6100 rpm and start motor will be cut.
JOB COMPLETE
Plant in operation.
4.2 References
4.4 Shutdown
Shutdown of the electric start system occurs automatically when the gas turbine
gets to approximately 6100 rpm.
(1) At shutdown, the control room operator can monitor these electrical control
system indications:
JOB COMPLETE
Chapter 6
CHAPTER CONTENTS
Plant Shutdown.
1.2 References
(1) Make sure that No.1 hydraulic cont rol pump st arter isolator is closed and
HOA switch selected to ‘Auto’.
(2) Make sure that No.2 hydraulic control pump starter isolator is closed.
(3) Make sure that the oil t ank heater cont actor isolator is closed and HOA
switch selected to ‘Auto’.
(1) Make sure that the GT Hydraulic oil t ank external drain valve HV0701 is
Closed.
(2) Make sure that the GT Hydraulic oil t ank exte rnal sample point valve
HV0700 is Closed.
(3) Make sure the area around the Mechanical Enclosure is free of oil/coolant
leaks and unwanted materials that could cause a fire or personnel hazard.
(1) Make sure that the GT Hydraulic oil isolat ing valves HV0703 and HV0704
are Open.
(2) Make sure that the Demister drain line sample valve HV0702 is Closed and
locked.
(3) Make sure the area around the oil syst em is free of oil/coolant leaks and
unwanted materials that could cause a fire or personnel hazard.
(4) At the duplex filter, make sure bleed valves HV0710, HV0711, HV0720 and
HV0721 are all closed.
(5) At the duplex filter, make sure filter selection lever is switched to the filter to
be used for 100% duty. Make sure the bleed valve is in the closed position.
(6) Make sure that the hydraulic c ontrol system valves are positioned as
follows:
(a) PDT0703 Control oil fi lter differential pressure transmitter block and
bleed:
(1) Make sure the area around the system is free of oil leaks and unwanted
materials that could cause a fire or personnel hazard.
(2) Make sure that the ac cumulator precharge pressu re is at 5000 kPa (725
psi).
(4) Make sure the enclosu re lighting is switched of f when you exit the
enclosure.
JOB COMPLETE
Plant Shutdown.
2.2 References
2.4 Prerequisites
(2) Use the hydraulic control oil gra phic screen on the st ation console, to
monitor:
(e) There is no differential pressure across the duplex filter assembly and
the supply pressure is zero.
The starting sequence will not proceed if there is a trip or alarm fault or if one is
shown.
2.6 Start-Up
After a st art has been init ialized in the PCS, then the pump selected as duty
automatically starts. The pump can also be started if you select the hand position
on the Hand/Of f/Auto switch on the moto r control ce nter and push the st art
button.
(1) During start-up the control room operator must monitor the hydraulic control
oil system indications as follows:
(c) During the st art-up, the dif ferential pressure across the filters will be
high, but it will decrease to norma l whe n it get s to o perational
pressure.
(d) The oil reservoir level must not fall below the alarm level.
JOB COMPLETE
Plant in operation.
3.2 References
(1) As the normal operation is fully automatic, the operator can only monitor the
system graphic display.
(2) Refer to step 3.5 for normal operational status, and to step 3.6 for necessary
parameters, alarms and limits related to the system.
(1) Duty hydraulic control pump discharge pressure 7600 kPa (1102 psi).
(2) Hydraulic control oil supply manifold pressure 7600 kPa (1102 psi).
(3) Stand-by hydraulic control pump will start automatically on the failure of the
duty pump at a decreased supply pressure of 6720 kPa (974.6 psi) or at a
decrease electric start supply pressure of 1050 kPa (152.3 psi).
(1) Hydraulic control oil low supply pressure 7240 kPa (1050 psi)
(2) Hydraulic control oil high supply pressure 7930 kPa (1150 psi).
(3) Hydraulic con trol o il d uplex filt er high dif ferential pressure 100 kPa
(14.5 psi).
(4) Duty hydraulic control pump discharge pressure 6720 kPa (974.6 psi).
(1) Hydraulic control oil low supply manifold pressure 6380 kPa (925 psi).
(a) Hydraulic control oil duplex filter dif ferential pressure maximum
100 kPa (14.5 psi).
(b) Duty hydraulic oil pump disc harge pressure maximum 2900 kPa
(420 psi).
(d) The hydraulic oil tank level should not decrease below the alarm level.
(e) At regular intervals, and just befor e shutdown, record the dif ferential
pressure across the filter . If the differential pressure approaches the
maximum 100 kPa (14.5 psi) the duplex filter must be changed.
JOB COMPLETE
Plant in operation.
4.2 References
(1) At shutdown, monitor the hydraulic control oil system indications as follows:
(b) Hydraulic control supply pressure will be high until the accumulator is
empty.
(c) Both hydraulic pump status indication must display ‘OFF’ in the HMI -
(GT lube oil).
JOB COMPLETE
Chapter 7
CHAPTER CONTENTS
Plant Shutdown.
1.2 References
1.4 Pre-requisites
(2) At the MCC panel make sure that the oil reservoir heater contactor isolator
is closed.
(3) Make sure that the lube oil demister drain to oil reservoir pipe sample drain
valve HV0702 is closed.
1.5 Make Sure the Lubricating Oil System Valves are Positioned correctly
(4) Do a check at the duplex filter , make sure bleed valves HV0708, HV0709,
HV0716 and HV0717 are all closed.
(5) Do a check at the duplexfilter, make sure filter selection lever is switched to
the filter to be used for 100% duty . Check bleed valve is in the closed
position.
(9) PT0702A and PT0702B GT lube oil bearing vent pressure transmitters:
(10) PT0701 GT lube oil scavenge bet ween pump and cooler pressu re
transmitter:
(1) Make sure the area around the GT enclosure is free of oil/coolant leaks or
loose debris that can cause a fire or personnel hazard.
(2) Make sure fire and gas sensors are not covered.
(3) Make sure that the package enclosure doors are closed.
(4) Make sure the GT enclosure light s are switched of f when you exit the
enclosure.
JOB COMPLETE
Plant Shutdown.
2.2 References
(1) Utilizing the GT Lube oil graphic screen on the station console, the operator
must monitor these indications:
(a) Make sure that the lube oil reservoir level is above the minimum level
necessary.
The start sequence will not occur if gas turbine oil reservoir temperature is below
15 deg.C. (59 deg.F.).
2.6 Start-Up
When the GT is st arted the GT lube oil is supplied and scavenge d by the
on-engine pumps.
(1) During st art-up, the control room o perator must monitor these lube oil
system indications:
(a) Differential pressure across t he filter must not exceed 100 kPa
(14.5 psi). A clean filter will indicate a dif ferential pressure of 50 kPa
(7.25 psi), i.e. graphic shows an unblocked filter.
JOB COMPLETE
Plant in operation.
3.2 References
3.4 Pre-requisites
In operation.
(1) As the normal operation of the lube oil system is fully automatic, the
operator can only monitor the system graphic display.
(2) Normal operational st atus, necessa ry p arameters, alarms and limit ations
related to the system are listed in Paras 3.6, 3.7, 3.8 and 3.9.
(1) GT lube oil reservoir level 441mm to 496mm (17.4 in. to 19.5 in.).
(4) GT lube oil scavenge return temperature ISO day 138 deg.C. (280.4 deg.F.).
(5) GT lube oil duplex filter differential pressure <100 kPa (14.5 psi) maximum.
(3) GT lube oil supply pressure high alarm 2900 kPa (420.6 psi).
(4) GT lube oil supply pressure low 200 kPa (29 psi).
(5) GT lube oil high scavenge return temperature varies with engine speed and
oil supply temperature.
(7) GT lube oil duplex supply filter differential pressure >100 kPa (14.5 psi).
(8) GT lube oil internal gearbox differential pressure, 63QGJIGB1, (differs with
engine speed).
(a) One litre of lube oi l is consumed each minute for three consecutive
minutes.
(b) Sixteen litres of lube oil is consumed over a period of four hours.
(2) GT lube oil high supply pressure 300 kPa (43.5 psi).
(3) GT lube oil low supply pressure 170 kPa (24.65 psi).
(4) GT lube oil high scavenge temperature changes with engine speed and oil
supply temperature.
(6) GT lube oil simplex supply filter differential pressure >160 kPa (23.2 psi).
(7) GT lube oil internal gearbox differential pressure, 63QGJIGB1, (differs with
engine speed).
(1) GT lube oil high scavenge temperature trip changes with engine speed and
oil supply temperature.
(2) GT lube oil low supply pressure 150 kPa (21.75 psi).
(3) GT lube oil internal gearbox differential pressure, 63QGJIGB1, (differs with
engine speed).
JOB COMPLETE
Plant in operation.
4.2 References
4.4 Shutdown
(1) Make sure that the oilreservoir level on the HMI is above the minimum level
necessary for operation (in preparation for next start-up).
NOTE If the reservoir level shown is below the necessary level on the
HMI, then new lube oil must be added to the reservoir as
specified in the related Maintenance Chapter.
JOB COMPLETE
Chapter 8
CHAPTER CONTENTS
Plant Shutdown.
1.2 References
1.4 Pre-requisites
(1) Make sure that the 24V DC power supply is available to all the instruments
in the unit.
(1) IP inlet pressure P24 pressure transmitter PT0224A isolating valve Open.
(2) IP inlet pressure P24 pressure transmitter PT0224A vent valve Closed.
(3) IP inlet pressure P24 pressure transmitter PT0224B isolating valve Open.
(4) IP inlet pressure P24 pressure transmitter PT0224B vent valve Closed.
(1) Make sure there are no oil/coolant leaks or loose debris that could cause a
fire or personnel hazard.
(3) Make sure the enclosu re lighting is switched of f when you exit the
enclosure.
(5) Make sure that all permits to work on the system have been cancelled and
padlocks removed.
JOB COMPLETE
Plant Shutdown.
2.2 References
Make sure that the 24V DC power supply is on at all the necessary equipment in
the complete unit.
JOB COMPLETE
Plant in operation.
3.2 References
As normal operation of the unit is fully automatic, the operator can only mon itor
the HMI.
3.5 Normal Operational Status, Alarms and Limitations Related to the System are as
follows:
Power is reduced if the WCAC temperature is morethan 260 deg.C. (500 deg.F.).
The power reduction is stopped if the WCAC outlet temperature goes below 257
deg.C. (494.6 deg.F.).
Chapter 9
CHAPTER CONTENTS
Plant Shutdown.
1.2 References
Monitor the GT enclosure graphic screen to make sure the indicators that follow
are shown:
(1) The gas turbine (GT) enclosure ventilation inlet and exhaust extinguishant
retention dampers are open.
At the MCC panel inside the control room make sure that:
(1) The No.1 GT vent exhaust fan mo tor isolator is Closed and the HOA
selector switch is selected to ‘Auto’.
(2) The No.2 GT vent exhaust fan mo tor isolator is Closed and the HOA
selector switch is selected to ‘Auto’.
(3) The No.3 GT vent exhaust fan mo tor isolator is Closed and the HOA
selector switch is selected to ‘Auto’.
(1) Make sure all air intake louvres and related actuating mechanisms are free
from obstruction(s).
(2) Make sure all int ake louvres and related actuating mechanisms have no
signs of visible damage.
(3) Make sure HV0101 and HV0102 are both in the open position and locked.
JOB COMPLETE
Plant Shutdown.
2.2 References
2.4 Start-Up
(1) During unit st art-up s equence, the enclosure ventilation systems are
started.
(3) The second duty ventilation fan will start if the GT enclosure temperature is
>15 deg.C. (59 deg.F.), GT enclosure DP is >0.08 kPa (0.012 psi), or GT
synch idle is reached.
(4) If the GT enclosure DP is less than that set in the Safety Integrated System
(SIS), the GT will be tripped and the gas fuel system depressurized.
(5) If at any time the fire and gas prot ection indicates a gas concentration in
excess of 3% LEL, the stand-by fan will be started.
(6) If at any time the GT enclosure temperature is >65 deg.C. (149 deg.F.) the
stand-by fan will be started.
(7) If either duty fan fails during GT operation, the stand-by fan will be started.
(8) If a fire is detected, all fans will be stopped and fire dampers will close.
JOB COMPLETED
Plant in operation.
3.2 References
3.4 Pre-requisites
Make sure that there is anunrestricted flow of ventilation/cooling air and to permit
rapid isolation if the fire protection systemis activated, the air intake louvres must
not be obstructed.
(1) As the normal operation of the Genset is fully automatic, the operator can
only monitor the HMI.
(3) Exhaust fans No.1, No.2 and No.3, two out of the three in operation.
(4) Back draught dampers No .1, No.2 and No.3, d amper open automatically
when its related fan is in operation.
(3) GT enclosure gas detection >3% of LEL (alarm) which puts 3rd fan on.
JOB COMPLETE
Plant in operation.
4.2 References
4.4 Shutdown
(2) After gas turbine shut down, the enclosure ventil ation fans will run for
30 minutes.
(3) If the GT temperature is <10 deg.C. (50 deg.F.) the ventilation fans will run
for one minute, then shut down.
NOTE The standby fan will st art during and after the shutdown for the
conditions that follow:
JOB COMPLETE
Plant Shutdown.
5.2 References
(1) Inspect the 'clean side' maintenance hatch at the rear end of the filter
housing above the plat form level, and make sure that the rubber sealing
joint is installed and that all the cover fastenings are tightened down to give
a good air tight seal.
(2) Do a check around the two levels of the filter housing enclosure to make
sure that all filters are seated and correctly attached to the division plate.
(1) Unlock and open up the 'dirty side' filter housing access door.
(2) Do a check around the two levels of the filter housing enclosure to make
sure that all filters are seated and correctly attached to the division plate.
(3) Make sure that there are no loose or unwanted items that can cause fire,
filter damage, personnel injury or reduced filter efficiency.
(4) Make sure that the house enclosure lights are switched of f at the con trol
panel before you leave the building.
(5) Lock the filter housing access door andgo to the ground level, by use of the
vertical ladder.
(a) Make sure drain valves HV010 1, HV0102, HV0105 and HV0106 a re
closed.
JOB COMPLETE
Plant Shutdown.
6.2 References
6.4 Pre-requisites
(1) Make sure that all permits to work on the system have been cancelled and
padlocks removed.
(1) The air inlet system will operate automatically on st art-up unless one of
these systems/instruments is in alarm:
JOB COMPLETE
Plant in operation.
7.2 References
As the normal operation of the Trent package is fully automatic, the operator can
only monitor the HMI.
(1) Inlet filter (atmospheric) differential pressure alarm 1 kPa (0.145 psi).
(1) High inlet filter differential pressure trip 1.5 kPa (0.218 psi).
JOB COMPLETE
Chapter 10
CHAPTER CONTENTS
Plant Shutdown.
1.2 References
Go to the unit gas fuel system graphic screen and do these checks:
(1) The header vent valve (HVV) and manifold vent valve (MVV) indicate Open.
(1) Make sure that the gas fuel system valves are in position as follows:
(1) Make sure that the P30 purge air system valves are as follows:
(1) Make sure that there are no oil/coolant leaks or unwanted materials that can
cause a fire or personnel hazard.
(3) Make sure that enclosure light s are switched of f when you exit the
enclosure.
JOB COMPLETE
Plant Shutdown.
2.2 References
2.4 Start-Up
(a) On instruction from the ECS, the vent valve wil l go from fully open to
closed.
(b) Position switches on the HSSOV and FMV will do a check for correct
operation. A shut down wil l be initiated if one valve fails this check.
After this check, these valves will go back to their shutdown state and
stay there until the end of the 41 second GT purge cycle.
(i) The ECS will cycle t he Fuel Metering V alve (FMV) three times
during the ramp up to 3000 rpm.
(ii) The manifold vent valve is cycled (closed and re-opened) two
times.
(iii) The header vent is cycled tw o times but remains open for GT
purge (it will close when the GT is ready to light up).
(c) Before ignition, the ECS will do a leak check on the gas fuel system.
If the check fails, the start sequence will be stopped and an indication
will be displayed on the HMI.
(i) The HSSOV leak check is done with the HSSOV, FMV and HVV
closed. The rate of change of the FMV inlet pressure is
monitored for 10 seconds to make sure there is no leakage from
the HSSOV.
(ii) The FMV and HVV leak che ck is done with the FMV and HVV
closed. The rate of change of the FMV inlet pressure is
monitored for 10 seconds to make sure there is no leakage from
the HVV and FMV.
(e) Two seconds in to the igniti on sequence the HSSOV opens and the
fuel gas is available up to the fuel gas metering valve.
(h) The ignition system ignites the gas in the GT annular combustion
system.
(i) When ignition is detected, the fuel metering valve is set to increase the
GT fuel flow rate from start up to sub synch idle speed.
(j) When you have synchronisation of t he generator to the grid, the fuel
metering valve is set to increase the GT fuel flow up to the Customer
target load requirements.
(k) When you get the correct t arget load, the ECS wi ll adjust the gas
metering valve as necessary to match the Customertarget load or grid
changes.
JOB COMPLETE
Plant Running.
3.2 References
(1) The engine control system (ECS) controls fuel flow supplied to the gas fuel
manifold to control engine speed, power and load.
(2) Gas enters the system through the high speed shut-off valve (HSSOV) and
is available for use in ht e manifold. The gas is regulated in the line as normal
operational loads change. Pressure transducers in the system send signals
to the (ECS) for correct fuel pressure regulation by the fuel metering valve
in the fuel line. Vent valves in the fuel line and the high speed shut-off vent
valve (HSSOV), are connected into a common manifold fo r venting of the
system to atmosphere during engine shutdown.
As the normal operation of the genset is fully automa tic, the operator can only
monitor the system graphic display.
GT in Operation.
JOB COMPLETE
Plant Running.
4.2 References
(1) With the HMI start sequence screen, shutdown processes are as follows:
(a) Below the main panel, click on the UNIT STOP button.
JOB COMPLETE
Plant Running.
5.2 References
(1) The engine control system (ECS) contro ls fuel flow supplied to the liquid
fuel and gas fuel manifolds to control engine speed, power and load.
(2) When the change over is started, the liquid FMV closes and the position
switch shows the valve is closed for one second.
(3) The P30 air purge system on the liquid manifold side will stop if in gas fuel
dry operation. If in gas fu el wet operation, water from the WIMS will stop.
The liquid fuel system will then prime ready for use.
(4) When the liquid fuel syst em is ready , the change over will begin. Af ter
completion of the fuels cross over, the liquid fuel system high speed shut-off
valve will open and the gas fuel high speed shut-off valve will close.
(5) When the gas fuel system high speed shut-off valve is fully closed and the
gas fuel system is shutdown and shown as off, P30 purge air for the gas fuel
manifold will start.
(6) P30 air purge for the ga s fuel manifold st ays on while the system is
operational on liquid fuel.
As the normal operation of the Genset is fully automatic, t he operator can only
monitor the system graphic display.
GT Running.
JOB COMPLETE
Chapter 11
CHAPTER CONTENTS
Plant Shutdown.
1.2 References
Monitor the unit liquid fuel system graphi c screen to make sure that these
indications are shown:
(1) Make sure that the liquid fuel system valves are set as follows:
(1) Make sure that the liquid fuel system valves are as follows:
(1) Make sure that the P30 Purge Air system valves are as follows:
(1) Make sure that there are no oil/coolant leaks orunwanted materials that can
cause a fire or personnel hazard.
(3) Make sure that enclosure lighting is switched o ff when you exit the
enclosure.
JOB COMPLETE
Plant Shutdown.
2.2 References
2.4 Start-Up
(iv) The fuel metering valve is set to the priming flow position.
(c) When you get the correct priming volume, the FMV will open to the
main light-up fuel flow.
(d) When ignition is detected, the FMV is set to increase the GT fuel flow
rate from start-up to sub sync idle speed.
(f) When you get the correct target load, the ECS will adjust the FMV as
necessary to match the Customer target load or grid changes.
JOB COMPLETE
Plant in operation.
3.2 References
(1) The ECS controls the liquid fuel metering valve using position based on
pre-determined liquid fuel flow and monitors position feedback.
(2) The liquid fuel metering valve returns the liquid fuel that is not required by
the GT to maintain a constant pressure drop across the metering valve.
As the normal operation of the genset is fully automat ic, the operator can only
monitor the system graphic display.
GT in operation.
JOB COMPLETE
Plant in operation.
4.2 References
JOB COMPLETE
(1) With the HMI start sequence screen, shutdown processes are as follows:
(a) Below the main panel, click on the UNIT STOP button.
NOTE The sequence below starts after the breaker opens and the
GT cooldown is complete as given in Chapter 2.
(b) The valves that follow are operated at the same time:
(i) The downstream HSSOV closes and stops flow to the manifold.
(ii) The upstream 3-way HSSOV diverts fuel to the spill line.
(v) When the liquid fuel is shut off, the liquid PAPS and liquid SAS
purge the liquid fuel m anifold, pig tails, and injectors for seven
minutes with the liquid fuel drain valve open for the first two
minutes.
JOB COMPLETE
Plant Shutdown.
5.2 References
Go to the unit liquid fuel system graphic screen and check as follows:
(1) Make sure that the water flush system valves are as follows:
(1) Make sure that there are no oil/coolant leaks orunwanted materials that can
cause a fire or personnel hazard.
(3) Make sure that encl osure light s are switched off when you leave the
enclosure.
JOB COMPLETE
Plant Shutdown.
6.2 References
6.4 Start-Up
(1) The water flush system will st art automatically during a liquid to gas fuel
transfer as follows:
(a) On instruction from the ECS, the shut-off valve will go from closed to
open.
(b) The ECS will then start the pump motor to supply demineralized water
through the liquid fuel manifold when the liquid fuel supply is stopped.
JOB COMPLETE
Plant in operation.
7.2 References
(1) The ECS controls the water flow supply to the liquid fuel manifold to control
the amount of water supplied to the engine.
(2) Demineralized water goes into the system through the HSSOV for use in the
manifold. The water flush system is sequenced with the liqu id fuel to gas
fuel change over.
As the normal operation of the genset is fully automat ic, the operator can only
monitor the system graphic display.
GT in operation.
JOB COMPLETE
Plant Operational.
8.2 References
(1) The water flush system is controll ed by the ECS so the operator can only
monitor the HMI to make sure that:
JOB COMPLETE
Plant in operation.
9.2 References
(1) The ECS controls fuel flow supply to the liquid fu el and gas fuel manifolds
to control engine speed, power and load.
(2) When the change over has occurred, the P30 air purge system on the gas
manifold side will stop.
(3) The gas system HSSOV will open and the liquid fuel high speed shut-of f
valve will close, at 50 % of change over the wate r flush system will st art.
After the fuels cross over is comple ted, the liquid fu el system will then
completely shut down.
(4) When the flush sequence is completed, the water flush system will stop and
P30 purge air will start.
NOTE For dry operation only, at the same time the liquid fuel manifold
valve will open for a duration of 40 seconds, and then close.
(5) P30 air purge for the liquid fuel manifold stays on while the system runs on
gas fuel.
As the normal operation of the genset is fully automat ic, the operator can only
monitor the system graphic display.
GT in operation.
JOB COMPLETE
Chapter 12
CHAPTER CONTENTS
Plant shutdown.
1.2 References
1.4 Pre-requisites
Make sure that the customers demineralized water supply pressure is available.
(1) The water injection and metering system skid (WIMS) discharge valve is in
bypass.
(1) Make sure that the water injection system valves are positioned as follows:
(1) Make sure that the water inject ion and metering system valves are
positioned as follows:
(1) Make sure that there are no leaks or unwanted materials that can cause a
fire or personnel hazard.
(3) Make sure that enclosu re lighting is switched of f when you exit the
enclosure.
JOB COMPLETE
Plant Shutdown.
2.2 References
2.4 Prerequisites
(2) Use the water injection graphic scr een on the st ation console, to observe
that:
(b) The water injection and metering system has a stop indication.
2.5 Start-Up
(1) The water injection and metering system must be enabled on the HMI.
(2) The first pump starts to operate when the GT is at 36% power (23 MW) and
simultaneously the water injection and metering skid discharge valve opens
and the water injection drain valve is closed.
(3) The second pump starts to operate when the rpm demand of the first pump
exceeds 1800 rpm. The rpm demand is calculated using kg/h to rpm factor.
(4) As the second pump is st arted, it will rot ate to minimum speed (750 rpm)
and then the first pump will decelerate from 1800 rpm to 1025 rpm.
(5) The third pump starts to operate when the rpm demand exceeds 3100 rpm.
(6) As the third pump is st arted, the pumps will be at approximately 1025 rpm
and 1275 rpm.
(7) Any increase in water demand is equally divided between the three pumps.
NOTE If one of the three pumps fails, the water injection and metering
system will do an immediate shutdown.
(1) During start-up the control room operator must monitor these indications:
JOB COMPLETE
Plant in operation.
3.2 References
(2) The nominal water demand can be corr ected on the water injection HMI
screen with the raise/lower buttons to adjust the water bias up to 10%.
JOB COMPLETE
Plant in operation.
4.2 References
(1) At shutdown, the control room operator must monitor these water injection
and metering system indications:
(2) There are two types of shut down, W ater Injection and Me tering System
Immediate and Water Injection and Metering System Normal.
(a) For a normal shutdown, the rpm demand will decelerate to 3000 rpm.
Pumps 1, 2 and 3 will decelerate equal ly to meet this demand. At
3000 rpm demand, the third pump wi ll shut down. Similarly , at
1750 rpm demand, Pump 2 will shut down and at 763 rpm demand,
Pump 1 will shut down. At this point the water injection and metering
skid discharge valve is commanded cl osed, and the GT continues to
run without water injection.
(b) Immediate shutdown, the water injection and metering skid discharge
valve is immediately closed and all pumps are shut down at the same
time, and the GT continues to run without water injection.
(c) A normal shut down occurs when the unit d ecelerates below the
normal threshold of 36% power (23 MW), or if there is a WIMS high or
low alarm that results in a WIMS shutdown.
(d) A water injection and metering system immediate shut down occurs
when there is a fault on the water injection and metering system skid
(water supply temperature or pressure outside their normal ranges).
JOB COMPLETE
Chapter 13
CHAPTER CONTENTS
Plant shutdown.
1.2 References
1.4 Pre-requisites
Make sure that the customers demineralized water supply pressure is available.
(1) Make sure that the ISI and inlet fo gging system valves are in position as
follows:
(2) Make sure that the wet compressi on system valves are in position as
follows:
(1) Make sure that there are no leaks or unwanted material that could cause a
fire or personnel hazard.
(3) Make sure that enclosure lighting is switched o ff when you exit the
enclosure.
JOB COMPLETE
Plant shutdown.
2.2 References
2.4 Pre-requisites
(2) Use the inlet fogging graphic screen on the station console, to monitor:
(9) The TGT margin (TGT limit - TGTCACT) is less than 18 deg.C. (32.4deg.F.)
OR the T30 margin (T30 limit - T 30CACT) is less than 18 deg.C.
(32.4 deg.F.).
(1) When the fogging system is enabled on the inlet fogging HMI screen, the
pump starts to operate for two seconds and stops to prime the system and
purge the system of air and the steps that follow occur:
(a) During minimum flow situations where the fogging demand is less
than the flow rate supplied by the pump, the recycle valve opens to
divert the excess flow by byp assing water back to the plant water
supply.
(b) The flow is then sent to the three fogging arrays where the scheduling
valves control the flow through each array.
(c) The fogging demand will vary as the ambient wet bulb temperatu re
changes and is calculated by the Fogging Control System.
2.6 Start-Up
(1) When the fogging system is enabled on the inlet fogging HMI screen, the
pump starts to operate.
(2) During minimum situations where the fogging demand is less than the flow
rate supplied by the pump, the recyclevalve opens to divert the excess flow
by bypassing water back to the plant water supply.
(3) The flow is then sent to the th ree fogging arrays where the scheduling
valves control the flow through each array.
(4) The fogging demand will vary as theambient wet bulb temperature changes
and is calculated by the Fogging Control System.
(1) During start-up the control room operator must monitor these indications:
(b) Pressure builds up to the flow rate of water set by the ECS to meet the
necessary power level.
JOB COMPLETE
Plant in operation.
3.2 References
As the normal operation is fully automati c, the operator can only monitor the
system graphic display.
JOB COMPLETE
Plant in operation.
4.2 References
(1) The inlet fogging system on the ISI skid will shut down when the system is
disabled on the HMI, a fault occurs on the inlet fogging system, during
controlled engine shut downs, or if the ambient wet bulb temperature is
10 deg.C. (50 deg.F.) or less and the steps that follow occur:
(a) The pump is de-energized and the recycle valve opens at the
minimum fogging flow threshold to di vert the flow ba ck to th e pl ant
water supply.
(b) After 15 seconds, the applicable scheduling valve(s) will close and the
recycle valve opens to divert the flow back to the plant water supply.
(1) At shut down, the control room opera tor must monitor the se inl et fogg ing
system indications:
JOB COMPLETE
Plant shutdown.
5.2 References
5.4 Pre-requisites
Make sure that the customers demineralized water supply pressure is available.
(1) Make sure that the wet compressi on system valves are in position as
follows:
(1) Make sure that there are no leaks or unwanted material that could cause a
fire or personnel hazard.
(3) Make sure that the enc losure lighting is switch ed of f when you exit the
enclosure.
JOB COMPLETE
Plant shutdown.
6.2 References
6.4 Pre-requisites
(2) Use the wet compression graphic screen on the station console, to monitor:
(9) The TGT margin (TGT limit - TGTCACT) is less than 18 deg.C. (32.4deg.F.)
OR the T 30 margin (T 30 limit - T30CACT) is less than 18 deg.C.
(32.4 deg.F.).
6.5 Start-Up
(1) When the ISI is enabled on the inlet spray HMI screen, the three pump s
prime the system for seven seconds and then turn off.
(3) Based on the power demand the number of duty pumps are determined, for
the initial water demand (2800 pph to 4025 pph) the first small pump will be
used.
(4) The scheduling valve for the Pump 1 regulates the flow of water to the wet
compression ring spray manifold.
(5) When the water demand is above 5600 pph, the second small pump starts
or the first small pump is shut-off and the large pump starts. The associated
scheduling valve regulates the flow of water to the wet compression ring
spray manifold.
(6) When the water demand is above 8400 pph, a small pump starts back up,
if previously shut of f, and provides flow along with the large pump or the
large pump st arts and one of the small pump s shuts off. The associated
scheduling valve regulates the flow of water to the wet compression ring
spray manifold.
(7) When the water demand is above 12075 pph, a small pump starts back up
if previously shut of f, and provides flow along with the large pump or the
large pump st arts and one of the small pump s shuts off. The associated
scheduling valve regulates the flow of water to the wet compression ring
spray manifold.
(1) During start-up the control room operator must monitor these indications:
(b) Pressure builds up to the flow rateof water set by the ECS to meet the
necessary power level.
JOB COMPLETE
Plant in operation.
7.2 References
As the normal operation is fully automatic, the operator can only monitor the
system graphic display. Refer to Volume 1, Chapter 13 for operating guidelines.
JOB COMPLETE
Plant Running.
8.2 References
8.4 Shutdown
(1) The inlet spray system on the ISI ski d will shut down when the system is
disabled on the HMI, a fault occurs on the inlet spray system, or if the TGT
and T30 margin is greater than 65 deg.C. (117 deg.F.) and the step s that
follow occur:
(a) As the water demand is ramped down, the lanes will turn of f. The
associated pump will hold its rpm for six seconds and then ramp down
to zero.
(b) When the pump is less than 10 rpm, the scheduling valve diverts the
water flow back to the plant water supply and the drain stays closed.
(c) When all pump s have been turned of f, the drains open and the wet
compression manifold purge scheduling valves supply instrument air
to purge the drains for 60 seconds.
(d) The wet compression manifold purge scheduling valv es then supply
instrument air to purge the manifolds of water for 300 seconds.
(2) The inlet spray system on the ISI skid will shut down when controlled and
emergency engine shut downs occur , if the T1 temperature drop s below
7 deg.C. (44.6 deg.F.) or if one inle t spray lane has been inactive for a
period of five days and the steps that follow occur:
(a) As the water demand is ramped down , the lanes will turn of f. The
associated pump will hold its rpm for six seconds and then ramp down
to zero.
(b) When the pump is less than 10 rpm, the scheduling valve divert s the
water flow back to the plant water supply and the drain stays closed.
(c) When all pump s have been turned off, the drains open and the wet
compression manifold purge scheduling valves supply instrument air
to purge the drains for 100 minutes.
(1) At shutdown, the contro l room operator must m onitor these inlet fogging
system indications:
JOB COMPLETE
Chapter 14
CHAPTER CONTENTS
Plant Shutdown.
1.2 References
(2) GED00162924 Diagram - Trent 60 WLE G.T. Fire and Gas System.
1.4 Pre-requisites
(1) Do a check on all the T rent p ackage enclosures to make sure that no
personnel are present. Cl ose and lock each enclosure d oor(s) when work
is complete.
(b) CO2 manual discharge push button co ver is in position and fully
operational.
(1) Make sure that the weight of each CO2 cylinder is a minimum of 90% of its
CO2 charge weight. The required maintenance schedule and procedure for
weighing the CO2 cylinders can be found in Chapter 16.
(2) Check CO 2 discharge hoses and con nections between the CO 2 cylin der
actuators and their rela ted manifolds are in good order and correctly
attached.
Make sure that the gr een AC power LED is illu minated. The alpha numeric
display will show the time and date and will change between a user programmed
text message and a system status.
JOB COMPLETE
Plant Shutdown.
2.2 References
(2) GED00162924 Diagram - Trent 60 WLE G.T. Fire and Gas System.
2.4 Start-Up
(2) The fire detection system is inst alled to automatically sense a fire in the
protected area (zone) by an electrical detection system and to extinguish
the fire by th e supply of CO 2 gas to the necessary zone. The operation of
the CO 2 system is automatic, but can be manually discharged in an
emergency. Gas detectors automatically sense if gas levels get to unsafe
LEL levels. When the gas LEL level get to the alarm threshold as specified
in the Alarm and T rip Matrix, the st andby fan will turn on and the unit will
CSD or ESD depending on the LEL level.
(3) The detection system has automatic fire and gas detectors, manual CO 2
discharge push buttons, alarm sounders and beacons, CO 2 status units,
and valve limit/pressure switches al l monitored by t he main unit F&G
(Fire and Gas) Panel.
JOB COMPLETE
Plant in operation.
3.2 References
(2) GED00162924 Diagram - Trent 60 WLE G.T. Fire and Gas System.
(1) These events will occur when the system is set in automatic and a single
detector circuit goes into an alarm condition:
(a) Unit F&G Controller gives a vi sual and audible alarm indication to
identify a fire, immediately and then at the station F&G controller.
(b) Local alarm sounders and beacons are started through the Unit F&G
Controller. The sounders give a continuous warning.
(2) These events occur when the system is set in automatic as a result of both
detector circuits going into an alarm in a zone (confirmed fire):
(a) Unit and station F&G controller gives an immediate visual and audible
alarm indication to identify a confirmed fire in a zone.
(a) If a fire is detected in one of theenclosures, at the same time the F&G
controller starts a number of different steps:
(iii) A pre-discharge warning horn goes off before the release of fire
extinguishant. Audible and visual warnings (horn/beacon) go off
when the fire extinguishant is released. Fire extinguishant is
supplied into the correct zone of the enclosure.
(b) The zonal discharge pipework pressure switch monitored by the F&G
detection system, signals that the main CO 2 bank has been
discharged in the zone where the fire was detected.
In the event of a fire re-strikeat time >90 seconds after main CO2 bank
is discharged, the reserve CO2 bank is automatically released.
(1) These events will occur when the system is on and asingle sensor goes into
an alarm condition:
(a) The standby fan is turned on to help lower the LEL level.
(b) After 10 minutes, the GT will CSD. When the gas level is below the
alarm threshold, the st andby fan wi ll stop and the duty fans will run
until the post cooldown requirement is com plete. If any of the gas
detectors touch the trip threshold, the control system will execute and
ESD and the standby fan will stop and the duty fans will run until the
post cool down requirement is complete. T he ESD is st arted by the
F&G controller to the Tripline, which will depressurize and turn off the
fuel supply in the GT enclosure independently of any UCP sof tware
function.
Plant running.
4.2 References
(2) GED00162924 Diagram - Trent 60 WLE G.T. Fire and Gas System.
4.4 Shutdown
JOB COMPLETE
NOTE This procedure effects the safe operation of the equipment, and it is
important that the user obeys its instructions.
(1) Make sure all personnel in the area are notified that the fire and gas system
has been discharged and are aware of the potential hazards such as:
(2) Make sure no personnel have been affected by CO2 discharge such as:
(2) Make sure the manual isolation valve inside the CO2 enclosure is closed for
safe entry.
(3) From HMI or Control room “ACTIVATE” the enclosure ventilation fans for at
least 10 minutes to make sure sufficient air change.
(4) If the Fire Brigade or any Fire Protection authorities are present, make sure
you get approval that the environment is safe and personnel can enter the
enclosure.
(5) If you are not sure if it is safe to enter, test the atmosphere in the enclosure
with a port able CO 2 “sniffer” and correct br eathing app aratus before
personnel can enter the enclosure. Thework must be checked by a method
statement and risk assessment.
(6) When the enclosure atmosphere is safefor entry, open the enclosure doors.
The type of incident and the extent of damage inside the enclosure could make
it necessary to recommission the equipm ent in accordance with it s original
documentation.
The fire extinguishing system must be recharged and armed, the EQP is reset
(reference the Det-T ronics Operati ng Manual), and the Fire and Gas and
Ventilation safe settings checked before the start of more unit runs.
Chapter 15
CHAPTER CONTENTS
Shutdown.
1.2 References
1.4 Prerequisites
(1) Make sure that the GT electric start system is aligned and available.
(2) Make sure that the GT hydraulic control system is aligned and available.
(3) Make sure that the GT lube oil system is aligned and available.
(4) Make sure that the generator lube oil system is aligned and available.
(5) Make sure that the generator jacking oil system is aligned and available.
(6) Make sure that the cleaning system is aligned and available.
(7) Make sure that the GT & generator cooling water system is online and
available.
(8) Make sure that there is suf ficient sp ace in the drains collecting t ank to
contain the waste water from the compressor wash.
(9) Remove the combusto r plug (located approx imately 15 degrees from
bottom dead center).
(2) Make sure that the water wash system valves are in position as follows:
(1) Make sure the area around the compressor wash module is free of oil leaks
or loose debris that can cause a fire or personnel hazard.
(2) Make sure that the 20 ‘Of f line’ sp ray nozzle flexible hoses are free from
external damage and deformity.
(3) Make sure that the GT drains pi pework and drain mani fold are free from
external damage and that all unions and connections are tight.
(4) Make sure the area aroundand below the GT is freeof oil/coolant leaks and
unwanted material that can cause a fire or personnel hazard.
(6) Make sure the enclosu re lighting is switched off when you exit the
enclosure.
JOB COMPLETE
Shutdown.
2.2 References
(1) With the water wash HMI screen on th e station console, the control room
operator must make sure that all criteria are me t before a crank st art is
started.
NOTE 1 The frequency of the wash procedure will be site specific, in line with
operational requirements, filtration effectiveness, and local pollutants.
This interval sh ould not be greater than 1000 hours unle ss
Rolls-Royce has agreed.
NOTE 3 Refer to the Utility Consumption List for approval wash fluids and
anti-freeze solutions and the corre ct mixing of these for optimal
washing.
(1) Stop the GT and make sure that the average TGT is below 100 deg.C.
(212 deg.F.) before you st art the wa sh procedure. TGT temperature is
displayed on the HMI.
(2) The GT must be shut down for a mini mum of two hours before you st art a
compressor wash cycle. Alternatively, two three minute dry cranks, the firs
tone 15 minutes after shutdown, the second one 15 minutes later, will make
sure that the turbine gas temperature is below 100 deg.C. (212 deg.F.).
2.6 Start-Up
(1) On the HMI control function screen, select the ‘wash’ operating mode.
NOTE In wash mode, the ECS will autom atically set the flow con trol
actuators to an optimum positi on for an ef fective wash and
ensure the fuel pump remains off.
(2) On the HMI water wash screen, press the crank start icon to start the wash.
JOB COMPLETE
Shutdown.
3.2 References
As the operation of the co mpressor wash system is m anual, the Operator must
control the introduction of water wash fluidfrom the manual valves located on the
water wash cart.
(2) Crank the engine to achieve a HP purge speed of 3000 rpm for at least one
minute or until the LP spool speed hasstabilised. Confirm that the LP spool
is rotating. Stop the wash if the LP system is not rotating, report this to your
Rolls-Royce representative.
(3) The wash sequence starts. Manually open the valve HV1109 to introduce a
water wash fluid into the GT, the aim is to inject 41 litres (10.83 US gallons)
of cleaning fluid into the compressor. Sixty seconds after injection st arts,
stop the st arter and let the remaining fl uid to be injected a s the unit runs
down. The wash skid outlet valve (HV1104) must be adjusted, to make sure
the tank is emptied in approximately 240 seconds, nominal flow rate of 10
litres/min (2.64 US gal/min).
(4) Let the engine soak/drain for a minimum of 15 minutes. Collection of a fluid
sample from the LPC drai n (D2) will give an indi cation of how dirty the
compressor wash and how clean it is at the end of the sequence. Up to ten,
250ml translucent sample bottles will be required.
(5) Do operations (2), (3) and (4) until the sample recovered from the LPC drain
shows the fluid to be acceptably clean. A dirty compressor may require two
solvent washes before rinsing. S tubborn dirt is more easily removed by
using a warm solvent/water mix in t he tank (40 to 60 deg.C. (104 to 140
deg.F.)).
(3) Manually close the valv e HV1109 on the water wash cart stop valve af ter
30 seconds to shut-off the rinse fluid. Stop the crank on the HMI.
(4) Drain all detergent remaining in the tank, open valve HV1105.
(5) Rinse the tank with rinse solution. The tank can contain two cycles of rinse
solution.
(6) A 15 minute delay will now start for the engine to run down and soak.
(1) Make sure the tank drain ball valve HV1105 is closed.
(2) Crank the engine to achieve a HP purge speed of 3000 rpm for at least one
minute or until the LP spool speed has stabilized. Make sure that the LP
spool is rotating. Stop the wash if the LP system is not ro tating, report this
to your Rolls-Royce representative.
(3) The rinse sequence st arts. Manually open the valve HV1 109 to introduce
the water wash fluid into the GT , the aim is to inject 41 litres
(10.83 US gallons) of rinse fluid into the compressor. Sixty seconds af ter
injection starts, stop the starter and allow the remaining fluid to be injected
as the unit runs down. The wash skid outlet valve (HV1 104) must be
adjusted, to make sure the tank is emptied in approximately 240 seconds,
nominal flow rate of 10 litres/min (2.64 US gal/min).
(4) Let the engine soak/drain for a minimum of 15 minutes. Collection of a fluid
sample from the LPC drai n (D2) will give an indica tion of how dirty the
compressor was and how clean it is at the end of the sequence. Up to ten,
250ml translucent sample bottles will be required.
(5) Do steps (2), (3) and (4) again using a rinse fluid, water or water/anti-freeze
mix as necessary. Two rises are nece ssary as a minimum. If soapy water
continues to drain, an additional rinse is recommended.
(6) Manually close the valve HV1 109 on the water wash cart stop valve af ter
30 seconds to shut-off the rinse fluid. Stop the crank on the HMI.
JOB COMPLETE
Shutdown.
4.2 References
(1) Close the exhaust drain valve HV1108 and ‘D2’ drain valve HV1110.
(4) Make sure that no oil/ coolant leaks or loose debris are present that could
cause a fire or personnel hazard.
(6) Make sure that enclosure lighting is switched OFF when you exit.
(8) Start the gas turbine and run to synchronous idle for at least 15 minutes.
Make sure that the completion of a wash is recorded and advi sed to your local
Rolls-Royce representative, noting any difficulties with completing the procedure
or starting the engine post wash.
JOB COMPLETE
Chapter 16
MAINTENANCE SCHEDULE
CHAPTER CONTENTS
MAINTENANCE SCHEDULE 1
MAINTENANCE SCHEDULE
EXAMINE THE FLEXIBLE BELLOWS ON THE ENGINE INLET AND ICD DUCT IN THE
GT ENCLOSURE 7
Frequency 7.1
References 7.2
Consumables/Spare Parts 7.3
Special Tools 7.4
Plant State 7.5
General Instructions 7.6
Maintenance Task 7.7
MAINTENANCE SCHEDULE
EXAMINE THE SCAVENGE GT, ESM, AND HYDRAULIC OIL BASKET STRAINERS FOR
UNWANTED MATERIALS 12
Frequency 12.1
References 12.2
Consumables/Spare Parts 12.3
Special Tools 12.4
Plant State 12.5
General Instructions 12.6
Maintenance Task 12.7
MAINTENANCE SCHEDULE
EXAMINE THE DRAIN PIPE OF THE COMBUSTION AIR SYSTEM IN THE FILTER
HOUSING 17
Frequency 17.1
References 17.2
Consumables/Spare Parts 17.3
Special Tools 17.4
Plant State 17.5
General Instructions 17.6
Maintenance Task 17.7
MAINTENANCE SCHEDULE
References 18.2
Consumables/Spare Parts 18.3
Special Tools 18.4
Plant State 18.5
General Instructions 18.6
Maintenance Task 18.7
MAINTENANCE SCHEDULE
MAINTENANCE SCHEDULE
MAINTENANCE SCHEDULE
DO A CRANK/SOAK WASH 31
Frequency 31.1
References 31.2
Consumables/Spare Parts 31.3
Special Tools 31.4
Plant State 31.5
General Instructions 31.6
Maintenance Task 31.7
Procedure 31.8
CHECK FOR EXCESSIVE NOISE OUTSIDE EACH ENCLOSURE DOOR WHEN THE
UNIT IS RUNNING 35
Frequency 35.1
MAINTENANCE SCHEDULE
References 35.2
Consumables/Spare Parts 35.3
Special Tools 35.4
Plant State 35.5
General Instructions 35.6
Maintenance Task 35.7
MAINTENANCE SCHEDULE
FILL THE GT, ELECTRIC START AND HYDRAULIC OIL CONTROL OIL RESERVOIR40
Frequency 40.1
References 40.2
Consumables/Spare Parts 40.3
Special Tools 40.4
Plant State 40.5
General Instructions 40.6
Maintenance Task 40.7
MAINTENANCE SCHEDULE
MAINTENANCE SCHEDULE
1 MAINTENANCE SCHEDULE
MAINTENANCE SCHEDULE
MAINTENANCE SCHEDULE
2.1 Frequency
Daily.
2.2 References
None.
None.
None.
Plant in operation.
MAINTENANCE SCHEDULE
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(a) Tell the duty , approved person that it is necessary for you to walk
around the package.
(2) Procedure.
(a) Walk around the p ackage. Listen for unusual sounds and look for
damage or leaks.
(b) Examine the liquid fuel/water flus h skid or gas fuel skid, depending
upon unit operation. Listen for unusua l sounds and look for damage
or leaks.
(c) Examine the ISI skid. Listen for unusual sounds and look for damage
or leaks.
(d) Examine the WIMS skid. List en for unusual sounds and look for
damage or leaks.
(e) Comply with any local document ation requirements for maintenance
task approval.
(b) Remove all loosely adhering coatings, rust, scale etc, by chipping and
scraping until a sound substrate has been achieved.
(c) Power tool clean ex posed metal surfaces to ST.3 minimum standard
(ISO 8501-1, ST .3); en-sure that the resulting surface is suit ably
profiled to yield good coating key , feathering back sound coating by
50mm.
MAINTENANCE SCHEDULE
(d) Use paint color matched to original part and paint system (Please refer
to paint manufacturers product data sheet). Build thickness to match
original surface.
END OF PROCEDURE
3.1 Frequency
One year.
3.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure the permit to work is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
MAINTENANCE SCHEDULE
(b) Tell the duty , approved person that it is necessary for you to do a
functional test of the E-stop button.
(2) Procedure.
(a) During a usual shutdown, let the GT speed decrease to idle speed and
push the E-stop button to shutdown the unit.
(b) Look at the control p anel/HMI di splay and make su re that a stop
command is shown.
(c) Examine the E-stop button to make sure that it remains in the pushed
down (stop) position.
(f) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
4.1 Frequency
One year.
4.2 References
None.
None.
None.
Plant shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to examine
the exhaust transition seal.
(2) Procedure.
(a) Examine the exhaust transition se als for cracks, de-lamination and
general deterioration of the material around the exhaust transition.
(c) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
MAINTENANCE SCHEDULE
5.1 Frequency
5.2 References
None.
None.
Shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
MAINTENANCE SCHEDULE
(e) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(f) Tell the duty, approved person that it is necessary for you to examine
the ductwork silencers from in the GT enclosure.
(2) Procedure.
(b) Examine the ductwork flexible sections for signs of damage and
deterioration.
(c) Examine for signs of heat dama ge on the ductwork and flexible
sections.
(d) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
6.1 Frequency
6.2 References
None.
None.
None.
MAINTENANCE SCHEDULE
Shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to examine
the GT enclosure door seals.
(2) Procedure.
(a) Examine all access door seals for wear and correct attachment.
(c) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
MAINTENANCE SCHEDULE
7 EXAMINE THE FLEXIBLE BELLOWS ONTHE ENGINE INLET AND ICD DUCT
IN THE GT ENCLOSURE
7.1 Frequency
7.2 References
None.
None.
Shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
MAINTENANCE SCHEDULE
(c) Tell the duty, approved person that it is necessary for you to examine
the flexible bellows on the engine inlet and ICD duct in the GT
enclosure.
(2) Procedure.
(a) Examine the external side of flex ible bellows on the engine inlet and
ICD duct in the GT enclosure for deterioration, cracks, de-lamination
and signs of leakage.
(c) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
8.1 Frequency
One year.
8.2 References
None.
None.
None.
Shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to examine
and do a functional test of the door hinges of the GT enclosure.
(2) Procedure.
(a) Check of the condition and operat ion of the door hinges of the GT
enclosure.
(b) If necessary, lubricate all the door hinges with light machine oil.
(c) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
MAINTENANCE SCHEDULE
9.1 Frequency
One year.
9.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
MAINTENANCE SCHEDULE
(c) Tell the duty, approved person that it is necessary for you to examine
the emergency light covers in the GT enclosure.
(2) Procedure.
(a) Examine the GT emergency light covers for signs of dirt or unwanted
materials.
(b) Remove all dirt or unwanted materials with a clean, dry lint free cloth.
(c) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
10.1 Frequency
12 months or as required.
10.2 References
None.
None.
Plant shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to use the
control p anel/HMI display to record and tr end dif ferential pressu re
across filter 0701.
(2) Procedure.
(iv) Wait two minutes and rotate transfer valve to stand-by filter.
MAINTENANCE SCHEDULE
(c) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
11.1 Frequency
2000 running hours or at the same interval as the oil filter replacement.
11.2 References
None.
None.
None.
Shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty , approved person that it is necessary fo r you to get
samples of oil from the GT lubrication oil reservoir.
(2) Procedure.
(a) Find the GT lubrication oil reservoir and the sample point.
(b) If the lubrication oil system is shutdown, start one of the auxiliary motor
driven lubrication oil pump s. Leav e the pump in operation for 30
minutes or more before you take samples.
(c) Remove the cap from the sample point valve and half fill a clean
marked up ‘Sample No 1’ 250 ml bottlewith oil from the GT lubrication
oil reservoir sample point.
(d) Put the fluid from the bottle into a clean container.
(e) Do steps (c) and (d) two or three times to flush the system before you
take the last sample.
MAINTENANCE SCHEDULE
(g) Use ‘Sample No 2’ 250 ml bottle and do steps (c) to (f) again.
(h) Install the cap on the GT lubrication oil reservoir sample point.
(i) Clean up oil spills with oil absorbentpads or clean lint free rags. When
complete, put the oily rags/pads into an approved disposal container.
(j) Make sure that the 250 ml sample bottles are correctly identified and
dated and give them to the duty approved person for dispatch.
(k) The duty, approved person will send the samples for analysis to the
approved laboratory for tests.
(m) If the GT is not operational, stop the hydraulic control oil pump motor
locally. When complete, set the H ands-Off-Auto (HOA) switch to the
‘Auto’ position.
(n) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
MAINTENANCE SCHEDULE
12.1 Frequency
8000 hours.
12.2 References
None.
Plant shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
MAINTENANCE SCHEDULE
(d) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(e) Tell the duty, approved person that it is necessary for you to examine
the scavenge basket strainer.
(2) Procedure.
(b) Remove strainer cover and collect all oil in an approved container.
(d) Clean the strainer element and install. Replace the strainer if
necessary.
(f) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
13.1 Frequency
Six months.
13.2 References
None.
MAINTENANCE SCHEDULE
Plant shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty , approved person that it is necessary for you to weigh
each of the CO2 bottles.
(2) Procedure.
(b) Take the approved charged weight of each cylinder (this is st amped
on the cylinder neck).
MAINTENANCE SCHEDULE
(d) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
14.1 Frequency
One year.
14.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
MAINTENANCE SCHEDULE
(b) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to examine
the fire extinguisher nozzles.
(2) Procedure.
(a) Examine the fire extinguisher nozzles for damage and correct
attachment. Replace or repair all damaged or blocked nozzles.
(b) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
15.1 Frequency
15.2 References
None.
Ladder or scaffolding.
Plant shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(c) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(d) Tell the duty, approved person that it is necessary for you to examine
the combustion air filters.
(2) Procedure.
(b) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
16.1 Frequency
One year.
MAINTENANCE SCHEDULE
16.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to do a check
of the structure bolts for the combustion air filter.
(2) Procedure.
MAINTENANCE SCHEDULE
(a) Examine the combustion air f ilter support structure and support
steelwork for signs of failure. Do a check externally for cracks, loose
or missing bolts, and other signs ofdeterioration or damage which can
cause a failure during operation.
(b) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
17.1 Frequency
One year.
17.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
MAINTENANCE SCHEDULE
(1) Preparation.
(c) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(d) Tell the duty, approved person that it is necessary for you to do a check
of the combustion air system drain pipe in the filter house.
(2) Procedure.
(a) Make sure the drain valve is open and no water has collected in the
filter house.
(b) Put water down the drain and make sure that the water goes out at the
drain outlet.
(c) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
18.1 Frequency
Before it is used.
18.2 References
None.
MAINTENANCE SCHEDULE
None.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty, approved person that it is necessary for you to examine
the water wash system hoses.
(2) Procedure.
(a) Do a check on the water wash system hoses for signs of damage,
splits, kinks or blockage and the condition of connections to engine
and air system.
(c) Comply with any local docume ntation requirements for maintenance
task approval.
MAINTENANCE SCHEDULE
END OF PROCEDURE
19.1 Frequency
Before it is used.
19.2 References
None.
None.
None.
Shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty, approved person that it is necessary for you to do a check
of the water wash system reservoir for surface damage.
(2) Procedure.
MAINTENANCE SCHEDULE
(a) Examine the water wash system reservoir for signs of surface damage
such as dents etc.
(b) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
20.1 Frequency
Before it is used.
20.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
MAINTENANCE SCHEDULE
(a) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty , approved person that it is necessary for you to do a
functional test of the brake for the water wash trolley.
(2) Procedure.
(a) Do a functional test of the brak e for the water wash sy stem tr olley.
Report defective brake operation to a senior approved person.
(b) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
21.1 Frequency
One year.
21.2 References
None.
None.
None.
Plant shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to examine
the package seal between the generator and the GT.
(2) Procedure.
(a) Examine the seal for damage. It isvery important that damage caused
by de-lamination, cracks or other surface deformity is found.
(b) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
22.1 Frequency
Continuous.
22.2 References
None.
MAINTENANCE SCHEDULE
None.
None.
Plant shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty, approved per son that it is necessa ry for you to mon itor
the generator air inlet temperat ure and outlet temperature and the
stator winding temperat ure in all three phases and to look for
increased trend.
(2) Procedure.
(a) Read the air temperature in t he generator and the st ator winding
temperatures and look for an incr eased trend. Note also the out side
ambient temperature at the time these are read.
(b) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
MAINTENANCE SCHEDULE
23.1 Frequency
One year.
23.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(2) Record all defect s in complia nce with the local document ation
requirements.
(1) Preparation.
(b) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to use the
control p anel/HMI display to do a check, record and trend of the
generator lubrication oil system di fferential pressure across filter
1250.
(2) Procedure.
MAINTENANCE SCHEDULE
(a) Do a check of the display indica tions from the control p anel/HMI
against the alarm level which has been set.
(iii) Install new filter element with new seals and gaskets.
(d) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
24.1 Frequency
24.2 References
None.
None.
Plant shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to examine
the generator lubrication oil suction strainer.
(2) Procedure.
(a) For pump handling and removal in structions, refer to the Siemens
Manual Volume 2.
(b) Remove strainer cover and collect all spilled oil in an app roved
container.
(d) Clean the stra iner el ement and inst all. Re place the element s if
necessary.
(e) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
25.1 Frequency
6 months.
MAINTENANCE SCHEDULE
25.2 References
Clean 250 ml Sample bottle: Mark ed up: ‘Generator lubric ation oil re servoir
Sample No.1, T ime and Date’. 250 ml Sample bottle: Marked up: ‘Generator
lubrication oil reservoir Sample No.2, Time and Date’. 1 litre container.
None.
Plant In Operation/Shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty, approved person that it is necessary for you to examine
the condition of the generator lubrication oil.
(c) Put absorbent p ads on the gener ator enclosure floor below the
generator oil reservoir sample point.
(2) Procedure.
MAINTENANCE SCHEDULE
END OF PROCEDURE
26.1 Frequency
monthly.
26.2 References
Nothing Found
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
MAINTENANCE SCHEDULE
(c) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(d) Tell the duty, approved person that it is necessary for you to examine
the start pump suction strainer of the generator lubrication oil system.
(2) Procedure.
(a) Make sure the nitrogen bottle is shut off with hose attached.
(b) Using appropriate valve in the GT lube oil system, di scharge all oil
from the accumulator.
(c) With ‘T’ handle backed all the way out, remove valve cap, att ach the
charging kit to the accumulator, and close the bleed valve.
(d) Turn ‘T’ handle until the gauge starts showing accumulator pressure.
(e) Open valve on nitrogen bottle and slowly fill accumulator to the
pre-charged pressure of 50 bar (725 psi).
(f) When finished, back the ‘T’ handle all the way out and close the bleed
valve.
(g) Remove the charging kit and replace the valve cap on the
accumulator.
(h) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
MAINTENANCE SCHEDULE
27.1 Frequency
27.2 References
SB No. 0055.
None.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
MAINTENANCE SCHEDULE
(c) Tell the duty, approved person that it is necessary for you to examine
the start pump suction strainer of the generator lubrication oil system.
(2) Procedure.
(a) Inspect the routing of the gas fuel pigtails.There should be no contact
between the pigt ails. look for any signs of cont act or damage. If
damaged, please t ake a phot ograph and cont act Rolls-Royce
Technical Support for sentencing.
(b) If there is any contact, then alter the orientation of the pigtails so there
is no contact. If this cannot be achieved, phot ograph the pigtails and
contact Rolls-Royce Technical Support for advice.
(c) Comply with any local document ation requirements for maintenance
task approval.
(d) Contact your local Rolls-Royce Technical Support office should further
information be required.
END OF PROCEDURE
28.1 Frequency
One year.
28.2 References
None.
None.
None.
Plant shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure that the permit to wo rk is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to check the
load capacity of the generator enclosure hoist.
(2) Procedure.
(a) Do a visual examinati on of the hoist block, trolley and permanen tly
installed runway beam.
NOTE Load tests and certification of the hoist block must be done
by an approved test house.
(b) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
MAINTENANCE SCHEDULE
29.1 Frequency
Monthly.
29.2 References
None.
None.
None.
Plant In Operation/Shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure the permit to work is correct and obey all th e safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty, approved person that it is necessary for you to use the
control panel/HMI display to check, record and trend the main liquid
fuel forwarding system differential pressure across filter FIL1000.
(2) Procedure.
MAINTENANCE SCHEDULE
(a) Check of display indications from HMI against a larm level which has
been set.
(c) If indication is near or above alarm level, ch ange the filter at next
opportunity.
(iv) Install new filter element with new seals and gaskets.
(d) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
30.1 Frequency
Monthly.
30.2 References
None.
None.
None.
MAINTENANCE SCHEDULE
Plant In Operation/Shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure the permit to work is correct and obey all th e safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty, approved person that it is necessary for you to use the
control p anel/HMI disp lay to check, record and trend dif ferential
pressure across the main water flush filter.
(2) Procedure.
(a) Check of display indications from HMI against alarm level which has
been set.
(iv) Install new filter element with new seals and gaskets.
MAINTENANCE SCHEDULE
(d) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
31 DO A CRANK/SOAK WASH
31.1 Frequency
31.2 References
Cleaning fluids and anti-freeze as specified in the Utility Consumption List. If the
recorded ambient temperatur e is below or near freezin g, 0 d eg.C. (32 deg.F.),
glycol is required in accordance with the manufacturer’s guidelines.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
MAINTENANCE SCHEDULE
(1) Preparation.
(b) Make sure that the pe rmit to work is correc t and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is nece ssary for you to remove
and examine the strainer for the GT lubrication oil system.
31.8 Procedure
END OF PROCEDURE
32.1 Frequency
One year.
32.2 References
None.
None.
Plant shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure the permit to work is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty , approved person that it is necessary for you to do a
functional test of the fire and gas system.
(2) Procedure.
(a) Perform a complete fire and gas test to the OEM instructions.
(b) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
33.1 Frequency
Two monthly.
MAINTENANCE SCHEDULE
33.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure the permit to work is correct and obey all th e safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty , approved person that it is necessary for you to do a
back-up of data on the control system.
(2) Procedure.
(b) Comply with any local document ation requirements for maintenance
task approval.
MAINTENANCE SCHEDULE
END OF PROCEDURE
34.1 Frequency
Every 2 months.
34.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure the permit to work is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty , approved person that it is necessary for you to do a
back-up of data on the hard disk.
(2) Procedure.
MAINTENANCE SCHEDULE
(f) Comply with any local document ation requirements for maintenance
task approval.
END OF PROCEDURE
35.1 Frequency
Weekly.
35.2 References
None.
None.
None.
Plant running.
MAINTENANCE SCHEDULE
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(b) Make sure the permit to work is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty , approved person that it is necessary for you to check
excessive noise outside each enclosure door when the unit is running.
(2) Procedure.
(a) Check for excessive noise outside each enclosure door when the unit
is running.
(b) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
36.1 Frequency
Weekly.
MAINTENANCE SCHEDULE
36.2 References
None.
None.
None.
Plant running.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(a) Make sure the permit to work is correct and obey all th e safety
precautions. Do only the task specified on the permit to work.
(b) Tell the duty, approved person that it is necessary for you to check the
ventilation system seals by listening for excessive audible noise from
ground level.
(2) Procedure.
(b) Comply with any local document ation requirements for maintenance
task approval.
MAINTENANCE SCHEDULE
END OF PROCEDURE
37.1 Frequency
Five years.
37.2 References
None.
None.
None.
Plant shutdown.
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
MAINTENANCE SCHEDULE
(b) Make sure the permit to work is correct and obey all th e safety
precautions. Do only the task specified on the permit to work.
(c) Tell the duty, approved person that it is necessary for you to check the
operation of the door position switch.
(2) Procedure.
(b) Make sure that the position of the door is displayed on the HMI.
(c) Give the keys back and sign off the permit to work.
END OF PROCEDURE
38.1 Frequency
One year.
38.2 References
None.
None.
Plant shutdown.
MAINTENANCE SCHEDULE
(1) If you find something unusual or defective in this procedure, tell the
supervisor.
(1) Preparation.
(c) Make sure the permit to work is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(d) Tell the duty, approved person that it is necessary for you to visu ally
check the drive belts on the ventilation fans.
(2) Procedure.
(a) Check drive belt s to OEM inst ructions, record and report any
problems.
(b) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
MAINTENANCE SCHEDULE
39.1 Frequency
Every 5060 hours for 25 deg.C. (77 deg.F). For every 15 deg.C (27 deg.F.) above
25 deg.C. (77 deg.F), reduce the frequency by half.
39.2 References
None.
Plant shutdown.
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
MAINTENANCE SCHEDULE
(c) Make sure the permit to work is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(d) Tell the duty, approved person that it is necessary for you to g rease
the ventilation fan bearings.
(2) Procedure.
(b) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
40 FILL THE GT, ELECTRIC START AND HYDRAULIC OIL CONTROL OIL
RESERVOIR
40.1 Frequency
As required.
40.2 References
None.
MAINTENANCE SCHEDULE
(1) If you find something unus ual or defective in th is procedure, tell the
supervisor.
(1) Preparation.
(d) Allow enough time for the GT to cool down after a shutdown.
(e) Ensure the permit to work is correct and obey all the safety
precautions. Do only the task specified on the permit to work.
(f) Tell the duty, approved person that it is necessary for you to fill the GT
and hydraulic control oil reservoir.
(2) Procedure.
(a) With the plant shut down, verify that the GT and hydraulic control oil
reservoir level is below the rundo wn level marked on the re servoir
sight level gauge and the GT lube oil graphics screen in the HMI.
(b) Connect oil transfer pump to re servoir fill connection using the
supplied quick connector.
MAINTENANCE SCHEDULE
(c) While the GT and hydraulic reserv oir oil level is below the Rundown
level, fill the reservoir with approv ed oil from the Utility Consu mption
List.
NOTE The oil must meet the cleanliness standard ISO 4406 14/12
or NAS 1638 Class 5.
NOTE Filling the t ank level abov e the max rundo wn le vel will
prevent the unit from starting.
(e) Comply with any local docume ntation requirements for maintenance
task approval.
END OF PROCEDURE
(1) Additional required maintenance tasks are located in the OEM manuals as
follows:
(e) Doc No. 1003795 - Ultra Electronics, Handbook for the Electric S tart
System for the Industrial Trent 60 and RB211 Gas Turbines.
MAINTENANCE SCHEDULE
MAINTENANCE SCHEDULE
Chapter 17
TROUBLESHOOTING
CHAPTER CONTENTS
TROUBLESHOOTING PROCESS 1
General Information 1.1
Troubleshooting Process 1.2
Record 1.3
Identify 1.4
Find 1.5
Solve 1.6
GAS TURBINE 2
DRIVEN EQUIPMENT 3
OIL SYSTEMS 5
COMBUSTION AIR 6
TABLES
Table 1 - GT Front, Centre and Rear Vibration Transducer 39GTI, 39GTC, 39GTT
Table 2 - Gas Turbine LP (NL) Speed Sensor 99GTNL1-3
Table 3 - Gas Turbine IP (NI) Speed Sensor 99GTNI1-3
Table 4 - Gas Turbine HP (NH) Speed Sensor 99GTNH1-3
Table 5 - GT IP Turbine Inlet Temperature Thermocouple 26GT42A & B
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
1 TROUBLESHOOTING PROCESS
To locate the current alarm and shutdown settings, refer to the HMI digital meter
module, or the ladder logi c program on the PC S. Settings are listed by device
code on the Table of Action on each diagram.
The est ablished limit s protect the equipment. Never operate the equ ipment
above or below it s limit s. When an alarm or shut down occurs, correct the
situation before attempting to continue operation.
To minimize shut down times and to keep all devices connected and properly
maintained, perform periodic maintenance. In addition to procedures listed here,
read and follow instructions in “Preventive Maintenance (chapter 16).”
In the vast majority of cases wher e Rolls-Royce st ates 'Cont act Customer
Support' this is at a point where a corrective action is required.
TROUBLESHOOTING
Due to the complex natur e of the equipment and the associated control and
protection systems, and to minimise any Health and Safety risks associated with
resolving the problem and in t aking co rrective actions, Rolls-Royce st andard
approach is to advise the operator to contact the supplier (OEM).
This approach minimises the risks of harm to personnel and/or damage to the
equipment in circumst ances where s pecialist training and competencies a re
required. W e therefore re strict access to cert ain corrective maintenance
procedures to those Rolls-Royce E ngineers who are qualif ied and trained to
perform these activities.
(1) Record.
(2) Identify.
(3) Find.
(4) Solve.
1.3 Record
1.4 Identify
Use your senses (sight, hearing, touch, and smell) and operating data records to
identify problems. Identifying a problem may be difficult. Problem indicators vary
from oil on the ground to a triggered unit shut down. Use records and frequent
inspections to look for possible problem areas. Alwa ys be alert for equipment
changes (drastic or subtle) such as temperature rises, temperature drop s,
pressure rises, pressure drops, unusual sounds, etc.
TROUBLESHOOTING
1.5 Find
Find probable causes for the malfunction. Study diagrams and OEM information
to find logical causes for the problem. The causes vary as much as the problem
indicators - anything from a faulty monitoring device to a wiped bearing. Cre ate
a work plan - think of as many probabl e causes to the problem as you can, and
then eliminate causes one by one. Rememb er, the alarm or indicator that alerts
you to a problem ma y be only the obvious problem, with other problems harder
to find. With this equipment, one problem can trigger several different indicators
and alarms.
1.6 Solve
Follow your plan. Solving the problem includes examining probable causes and
correcting them one by one. Once you el iminate a probable cause, see if the
problem is solved. If not, check and correct the next probable cause. This can be
a lengthy and frustrating process. Re member that even though servicing an
indicator or alarm may seem simple, t he actual cause of the problem and it s
solution may be more complicated.
2 GAS TURBINE
3 DRIVEN EQUIPMENT
NOTE Any connection to the gasturbine has the possibility of being filled with
liquids at low point s in the lines. Th is can cause erratic or erroneous
readings on instrumentation.
TROUBLESHOOTING
Table 1 - GT Front, Centre and Rear Vibration Transducer 39GTI, 39GTC, 39GTT
Trouble Sources Malfunction Corrective Action
Transducer Faulty transducer Remove and replace
the transducer. Refer
to the transducer
OEM instructions.
TROUBLESHOOTING
High NL speed alarm GT fuel Fuel pressure high Check fuel gas
pressure. Refer to
the Rolls-Royce
manual
Alarm condition not - Determine and fix
corrected the cause of the
shutdown. Start the
equipment again
High NL speed
shutdown
Contact your local
Rolls-Royce
Technical Support
Department
TROUBLESHOOTING
TROUBLESHOOTING
High NH speed alarm GT fuel Fuel pressure high Check fuel gas
pressure. Refer to
the Rolls-Royce
manual
TROUBLESHOOTING
Contact RRESI. Do
not re-start the
engine if there is
indication that a fire
has occured
TROUBLESHOOTING
Contact RRESI. Do
not re-start the
engine if there is
indication that a fire
has occured
TROUBLESHOOTING
TROUBLESHOOTING
5 OIL SYSTEMS
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
Table 14 - Electric Start Motor Cooling Oil Supply Pressure Transmitter 63SRMC
Trouble Sources Malfunction Corrective Action
Pressure transmitter Faulty transmitter Remove and replace
the transmitter. Refer
to the transmitter
OEM instructions.
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
6 COMBUSTION AIR
TROUBLESHOOTING
Refer to the fire and gas detection and suppression system OEM literature for
information.
Refer to the Siemens O & M manual for troubleshooting in formation for the
generator for the following devices:
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
Table 29 - Water Injection and Metering Skid Supply Temperature RTD 26WISA
Trouble Sources Malfunction Corrective Action
RTD Faulty RTD Remove and replace
the RTD. Refer to the
RTD OEM
instructions.
TROUBLESHOOTING
TROUBLESHOOTING
Table 30 - Water Injection and Metering Skid Supply Pressure Transmitter 63WIS
Trouble Sources Malfunction Corrective Action
Pressure transmitter Faulty transmitter Remove and replace
the transmitter. Refer
to the transmitter
OEM instructions.
TROUBLESHOOTING
TROUBLESHOOTING
Table 31 - Water Injection and Metering Skid Inlet Filter DP transmitter 63WIJF
Trouble Sources Malfunction Corrective Action
DP transmitter Faulty DP Remove and replace
transmitter the DP transmitter.
Refer to the DP
transmitter OEM
instructions.
TROUBLESHOOTING
Table 32 - Water Injection and Metering Skid Inlet Discharge Pressure Transmitter 63WIR
Trouble Sources Malfunction Corrective Action
Pressure transmitter Faulty transmitter Remove and replace
the transmitter. Refer
to the transmitter
OEM instructions.
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING