You are on page 1of 27

 

 
Position
Tracking
Systems  

 
Posi-­‐Stop  Troubleshooting  Guide  
 

January  2014  

Version  1.0.0  

   
 
   
 
Table  of  Contents  
1   Introduction  ...........................................................................................................................................  4  
2   Posi-­‐Stop  User  Interface  and  Connection  Locations  ..............................................................................  5  
3   Posi-­‐Stop  Circuit  Board  ..........................................................................................................................  6  
4   Posi-­‐Stop  Stationary  Test  .......................................................................................................................  7  
5   Posi-­‐Stop  Does  Not  Power  Up  ...............................................................................................................  8  
5.1   Check  Incoming  Power  On  Terminal  Block  ......................................................................................  8  
5.2   Check  Battery  Voltage  .....................................................................................................................  9  
5.3   Check  Continuity  Of  Fuse  .................................................................................................................  9  
5.4   Check  Voltage  To  Pin  Of  On/Off  Switch  .........................................................................................  10  
5.5   Check  Voltage  Located  At  TB  Top  Of  Main  Board  Above  Fuse  ......................................................  12  
5.6   Check  Voltage  Readings  On  7805  At  Top  Of  Main  Board  ..............................................................  13  
6   Posi-­‐Stop  Powers  Up,  LED  Displays  Do  Not  Function  ...........................................................................  14  
6.1   Check  voltage  on  LED  board  ..........................................................................................................  14  
6.2   Check  The  7805  On  The  LED  Board  ................................................................................................  15  
6.3   Check  12  Volt  TB  Coming  From  Main  Board  ..................................................................................  15  
7   Solenoid  Does  Not  Function  Correctly  .................................................................................................  16  
7.1   Check  Voltage  To  Solenoid  ............................................................................................................  16  
7.2   Check  Connection  In  Junction  Box  On  Solenoid  .............................................................................  17  
7.3   New  Style  Solenoid  Valve  Functional  Test  .....................................................................................  18  
8   Proximity  Switch  or  Encoder  Does  Not  Function  Correctly   .................................................................  19  
8.1   Check  Continuity  Of  Encoder/Proximity  Switch  Cable  ...................................................................  19  
8.2   Proximity  Switch  Installation/Tests  ...............................................................................................  20  
8.2.1  Check  Sensor  Installation  ..........................................................................................................................  20  
8.2.2  Test  Proximity  Switch  Sensors  ...................................................................................................................  21  
8.2.3  Test  Proximity  Switch  Sensor  LEDs  ............................................................................................................  22  
8.2.4  Test  Proximity  Switch  Circuit  Board  ..........................................................................................................  23  
8.2.5  Test  Proximity  Switch  Sensors  Through  Circuit  Board  ...............................................................................  25  

8.3   Check  Voltage  at  Encoder/Proximity  Switch  Input  Terminal  on  Main  Board  ................................  26  

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   3  


 

1 Introduction  
This  Troubleshooting  Guide  covers  the  most  common  issues  that  prevent  the  proper  function  of  
the  system.  This  is  a  living  document,  and  as  new  issues  arise,  better  identification  procedures  or  
better  corrective  actions  are  developed.  This  guide  will  be  updated  and  available  on  our  web  page  
www.posi-­‐stop.com.  Please  ensure  all  personnel  involved  in  operation,  maintenance  and  
management  of  the  rig  operations  read  the  warning  below,  in  the  Operations  Manual  and  on  
every  Posi-­‐Stop  Console  on  the  right  panel.  Prior  to  starting  a  shift  or  change  in  Operator  the  
attached  Pre-­‐Shift  Checklist  should  be  followed  and  if  any  of  the  checklist  items  does  not  pass  this  
Guide  will  have  the  most  common  issues  and  corrective  actions  to  correct  the  problem  and  have  
proper  operation  of  the  Posi-­‐Stop  System.  

4   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 

2 Posi-­‐Stop  User  Interface  and  Connection  Locations  

 
Figure  1  –  Posi-­‐Stop—Front  View  

 
Figure  2  –  Posi-­‐Stop—Bottom  View  

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   5  


 

3 Posi-­‐Stop  Circuit  Board  

 
Figure  3  –  Posi-­‐Stop  Circuit  Boards  

6   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 

4 Posi-­‐Stop  Stationary  Test  


a) Connect  encoder  and  solenoid  cables  
b) If  there  is  a  power  supply,  connect  the  110  VAC  and  use  the  meter  to  check  if  output  is  at  
12.5  VDC.  Turn  adjustment  potentiometer  to  get  12.5  VDC  
c) Turn  power  switch  to  ON  and  ensure  the  block  position  LED  tracks  from  25  to  75,  up  and  
down—if  it  does  not,  refer  to  section  6  
d) Turn  power  switch  to  SET.  Block  position  LED’s  top  and  bottom  bars  should  blink,  and  
Percent  of  Travel  LED  should  show  00  
e) Turn  power  switch  to  ON  
f) The  block  position  LED  top  bar  should  be  on,  and  the  percent  of  travel  should  show  -­‐01  
g) Solenoid  should  be  on—if  not,  refer  to  section  7  
h) Red  limit  light  should  be  on  
i) Press  red  limit  light  bypass  button  
j) Red  limit  light  should  blink,  and  solenoid  should  release—if  not,  refer  to  section  7  

 
Figure  4  –  Posi-­‐Stop  Performing  a  Stationary  Test  

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   7  


 

5 Posi-­‐Stop  Does  Not  Power  Up  

5.1 Check  Incoming  Power  On  Terminal  Block  

a) Connect  meter  red  lead  to  the  red  wire  


b) Connect  meter  black  lead  to  black  wire  
c) If  meter  reads  12  volts,  go  to  section  5.2  
d) If  meter  reads  less  than  12V,  check  connection  from  rig  external  power  source    

   
Figure  5  –  Checking  Incoming  Power  Voltage   Figure  6  –  Position  of  Terminal  Block  in  Posi-­‐Stop  

 
Note:  Ground  wire  must  go  to  rig  battery.  Do  not  ground  to  box.  

   

8   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 
5.2 Check  Battery  Voltage  

a) Connect  meter  red  lead  to  +  side  of  battery  


b) Connect  meter  black  lead  to  –  side  of  battery  
c) Meter  should  read  at  least  +12V  DC  
d) If  voltage  is  below  12V,  replace  or  recharge  battery  
e) If  voltage  is  12V  or  greater,  go  to  section  5.3  

 
Figure  7  –  Checking  Battery  Voltage  

5.3 Check  Continuity  Of  Fuse  

a) Set  meter  to  ohms  


b) Connect  leads  to  each  side  of  fuse  
c) Meter  should  read  zero  and/or  beep  out  
d) If  fuse  is  good,  go  to  section  5.4  
e) If  not,  replace  fuse  

   
Figure  8  –  Checking  Fuse  Continuity   Figure  9  –  Fuse  Location  on  Main  Board  

   

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   9  


 
5.4 Check  Voltage  To  Pin  Of  On/Off  Switch  

a) Connect  meter  black  lead  to  ground  (pin  4)  of  OFF/ON/SET  switch  contact  block  
b) Connect  meter  red  lead  to  pin  2  of  contact  block  
c) Meter  should  read  +12V  DC  
d) Remove  lead  from  pin  2  on  contact  block  and  connect  to  pin  1  
e) Meter  should  read  zero  
f) Turn  Posi-­‐Stop  On  
g) Meter  should  read  +12V  DC  
h) If  meter  reads  12V,  go  to  section  5.5  
i) If  meter  does  not  read  12V,  return  Posi-­‐Stop  to  Position  Tracking  Systems  for  repair  

(see  next  page  for  images)  

10   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 

   
Figure  10  –  Location  of  On/Off  Switch  Contact  Block   Figure  11  –  Pin  Locations  on  Contact  Block  

   
Figure  12  –  Black  Lead  To  Ground,  Pin  4,  Red  to  Pin  2,   Figure  13  –  Black  Lead  to  Ground,  Pin  4,  Red  to  Pin  1,  
Showing  12  Volts   Showing  0  Volts  

 
Figure  14  –  After  Turning  Box  On,  Meter  Reads  12  Volts  

   

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   11  


 
5.5 Check  Voltage  Located  At  TB  Top  Of  Main  Board  Above  Fuse  

a) Connect  meter  red  lead  to  red  wire  


b) Connect  meter  black  lead  to  black  wire  
c) Meter  should  read  +12V  DC  
d) If  meter  reads  12V,  skip  to  section  5.6  
e) If  meter  does  not  read  12V,  return  Posi-­‐Stop  to  Position  Tracking  Systems  for  repair  

   
Figure  15  –  Checking  TB  Voltage   Figure  16  –  TB  Location  on  Main  Board  

12   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 
5.6 Check  Voltage  Readings  On  7805  At  Top  Of  Main  Board    

a) Connect  black  lead  to  metal  top  of  7805  


b) Connect  red  lead  to  left  leg  of  7805  
c) Meter  should  read  +12V  DC  
d) Connect  red  lead  to  right  leg  of  7805  
e) Meter  should  read  +5V  DC  
f) If  above  test  fails,  return  Posi-­‐Stop  to  Position  Tracking  Systems  for  repair  

   
Figure  17  –  Red  Lead  to  Left  Leg   Figure  18  –  Red  Lead  to  Right  Leg  

 
Figure  19  –  Location  of  7805  on  Main  Board  

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   13  


 

6 Posi-­‐Stop  Powers  Up,  LED  Displays  Do  Not  Function  

6.1 Check  voltage  on  LED  board  

a) Connect  meter  red  lead  to  red  wire  on  terminal  block  located  at  top  of  LED  board  
b) Connect  meter  black  lead  to  black  wire  
c) Meter  should  read  +12V  DC  
d) If  meter  reads  12V,  go  to  section  6.2  
e) If  no  voltage,  perform  steps  in  section  5.5  
f) If  still  not  getting  12V,  return  Posi-­‐Stop  to  Position  Tracking  Systems  for  repair  

   
Figure  20  –  Checking  Voltage  on  LED  Board   Figure  21  –  TB  Location  on  LED  Board  

 
   

14   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 
6.2 Check  The  7805  On  The  LED  Board  

a) Connect  meter  black  lead  to  metal  top  of  7805  


b) Connect  meter  red  lead  to  left  leg  of  7805  
c) Meter  should  read  +12V  DC  
d) Connect  meter  red  lead  to  right  leg  of  7805  
e) Meter  should  read  +5V  DC  
f) If  meter  reads  correctly,  go  to  section  6.3  
g) If  above  test  fails,  return  Posi-­‐Stop  to  Position  Tracking  Systems  for  repair  

   
Figure  22  –  Steps  a-­‐c   Figure  23  –  Steps  d-­‐f  

6.3 Check  12  Volt  TB  Coming  From  Main  Board  

a) Connect  meter  red  lead  to  12v  terminal  block  on  main  board  
b) Connect  meter  black  lead  to  ground  terminal  block  on  main  board  
c) If  meter  reads  12  volts,  and  display  still  does  not  function,  return  Posi-­‐Stop  to  Position  
Tracking  Systems  for  repair  

   
Figure  24  –  Steps  a-­‐b   Figure  25  –  Location  of  TB  on  Main  Board  

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   15  


 

7 Solenoid  Does  Not  Function  Correctly    

7.1 Check  Voltage  To  Solenoid    

a) Turn  Posi-­‐Stop  on    


b) Turn  switch  to  SET    
c) Turn  switch  back  to  ON  
d) When  solenoid  activates,  red  limit  light  should  come  on  (Solenoid  should  make  an  audible  
“click”)  
e) Connect  red  lead  of  meter  to  white  wire  located  on  right  side  of  main  board  
f) Connect  black  lead  of  meter  to  black  wire    
g) Meter  should  read  +12V  DC  
h) Press  red  limit  light  Bypass  button,  solenoid  should  release  (Solenoid  should  make  an  
audible  “click”)  
i) Voltage  should  go  to  0V  DC  
j) Red  limit  light  should  flash  
k) If  bullets  a)  through  j)  function  as  specified,  go  to  section  7.2  

   
Figure  26  –  Steps  e-­‐g   Figure  27  –  Steps  i-­‐j  

 
Figure  28  –  Flashing  Limit  Light  on  Posi-­‐Stop  

   
16   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  
GUIDE  
 
7.2 Check  Connection  In  Junction  Box  On  Solenoid  

a) Remove  solenoid  junction  box  cover  


b) Ensure  the  two  black  wires  from  the  solenoid  have  good  connection  with  the  black  and  
white  wires  in  the  yellow  cable  from  the  Posi-­‐Stop  
c) Connect  the  cable  to  the  Posi-­‐Stop  (Yellow  three  conductor  cable  marked  “solenoid”)  
d) Turn  Posi-­‐Stop  to  ON,  then  SET,  then  ON  
e) Solenoid  should  activate,  red  limit  light  should  turn  on  (Solenoid  should  make  audible  
“click”)  
f) Connect  red  lead  from  meter  to  white  wire.  Connect  black  lead  from  meter  to  black  wire.    
g) Meter  should  read  12V  DC.  If  less  than  10V  solenoid  will  not  operate.  
h) Press  red  limit  light  Bypass  button  
i) Solenoid  should  release,  red  limit  light  should  blink  (Solenoid  should  make  audible  “click”)  
j) Voltage  reading  should  be  0  
k) Repeat  steps  a)  through  g)  in  section  7.1  
l) If  solenoid  does  not  activate,  replace  solenoid  
 

   
Figure  29  –  Voltage  Check  Between  White  +  Black   Figure  30  –Voltage  Check  After  Pressing  Bypass  

 
Figure  31  –  Location  of  Wires  in  Solenoid  

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   17  


 

7.3 New  Style  Solenoid  Valve  Functional  Test  

a) Connect  new  style  solenoid  to  Posi-­‐Stop  (Yellow  three  conductor  cable  marked  
“solenoid”)  
b) Turn  Posi-­‐Stop  to  ON  –  then  SET  –  then  back  to  ON  
c) Solenoid  should  activate  and  air  cylinder  should  operate  
d) LED  light  on  top  of  solenoid  should  be  on  
e) Press  red  limit  light  Bypass  button  –  solenoid  should  release  and  air  cylinder  should  
exhaust  
f) Solenoid  LED  light  should  go  off  
g) If  LED  and  solenoid  do  not  function  as  specified  in  steps  c),  d),  e),  and  f),  replace  solenoid  

   
Figure  32  –  Solenoid  LED  On   Figure  33  –  Solenoid  LED  Off  

18   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 

8 Proximity  Switch  or  Encoder  Does  Not  Function  Correctly  

8.1 Check  Continuity  Of  Encoder/Proximity  Switch  Cable  

a) Perform  continuity  test  on  corresponding  pins  on  each  end  of  cable  
b) If  cable  does  not  test  correctly,  replace  or  return  cable  to  Position  Tracking  Systems  for  
repairs  
c) If  cable  does  test  correctly,  for  an  encoder  system,  send  encoder  to  Position  Tracking  
Systems  for  repairs  
d) If  cable  does  test  correctly,  for  a  proximity  switch  system,  go  to  section  8.2  

 
Figure  34  –  Checking  Continuity  of  Cable  

   

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   19  


 
8.2 Proximity  Switch  Installation/Tests  

8.2.1 Check  Sensor  Installation  

a) Hopper  rig  installation:  


1) Ensure  the  16  targets  are  4”  apart  and  ¼”  below  the  flange  edge  
2) Ensure  that  sensor  is  properly  mounted.  A  sturdy  location  limits  vibrations  that  
may  impact  the  encoder’s  ability  to  accurately  sense  the  targets.  Add  gussets  or  
additional  support  if  needed.  The  sensor  bracket  must  be  positioned  such  that  the  
tips  of  the  sensors  are  ¼”  away  from  the  targets  and  1/8”  from  the  outside  edge  
of  the  target  (away  from  the  flange).  
b) Franks  rig  installation:  
1) Mount  target  wheel  on  bearing  carrier  housing  as  shown  in  Figure  36  
2) Proximity  switch  bracket  needs  to  be  positioned  so  that  the  switches  are  located  
on  the  target  center  line  (centered  over  target  holes),  and  the  tips  of  the  switches  
need  to  be  ¼”  away  from  the  target  wheel  
c) Ensure  the  black  encoder  cable  is  connected  to  the  Posi-­‐Stop  
d) Ensure  cables  are  protected  from  moving  parts  or  accidental  contact  by  rig  personnel    
e) Check  yellow  end  of  sensor  to  ensure  it  has  not  scraped  the  end  by  contacting  target  
f) If  sensors  are  damaged,  contact  Position  Tracking  Systems  for  replacement  
g) If  sensors  are  good,  and  installation  is  correct,  go  to  section  8.2.2  

 
Figure  35  –  Sensor  Installation  Location  On  Hopper  Rig  

 
Figure  36  –  Sensor  Installation  On  Franks  Rig  

   

20   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 
8.2.2 Test  Proximity  Switch  Sensors  

a) Connect  proximity  switch  assembly  to  Posi-­‐Stop  with  encoder  cable  


b) Turn  switch  to  “Set”  
c) Touch  sensor  1  to  metal  object  
d) A  reading  of  “+01”  should  be  displayed  on  Posi-­‐Stop  
e) Touch  sensor  2  to  metal  object  
f) A  reading  of  “+155”  should  be  displayed  on  Posi-­‐Stop  
g) If  readings  are  not  as  specified  in  d),  and  f),  go  to  section  8.2.3  
h) If  readings  are  as  specified  in  d),  and  f),  and  proximity  switch  still  does  not  work  correctly,  
repeat  steps  in  section  8.2.1  

   
Figure  37  –  Sensor  1  Making  Contact   Figure  38  –  Sensor  2  Making  Contact  

 
   

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   21  


 
8.2.3 Test  Proximity  Switch  Sensor  LEDs  

a) Remove  cover  from  proximity  switch  assembly  


b) Connect  proximity  switch  encoder  cable  to  Posi-­‐Stop  
c) Turn  Posi-­‐Stop  On  
d) The  two  LED  lights  on  proximity  switch  circuit  board  will  illuminate  
e) Touch  one  sensor  to  a  metal  surface  –  one  LED  will  turn  off  
f) Touch  the  other  sensor  to  a  metal  surface  –  the  other  LED  will  turn  off  
g) If  steps  e)  and  f)  function  as  specified,  the  LED  board  and  sensors  are  operational,  go  to  
section  8.2.4  
h) If  steps  e)  and  f)  do  not  function  as  specified,  send  proximity  switch  assembly  to  Position  
Tracking  Systems  for  repairs  

   
Figure  39  –  One  Sensor  Light  Off   Figure  40  –  Other  Sensor  Light  Off  

 
   

22   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 
8.2.4 Test  Proximity  Switch  Circuit  Board  

NOTE:      Targets  need  to  be  moving  very  slowly  past  proximity  switches  to  get  accurate  readings.  

a) Ensure  12  volts  is  available  to  proximity  switch  assembly  by  connecting  red  lead  from  
meter  to  red  wire  and  black  lead  from  meter  to  green  wire  
b) Read  3.3V  (positive  or  negative)  by  connecting  meter  leads  to  blue  and  orange  wires  
c) Also  read  3.3V  (positive  or  negative)  by  connecting  meter  leads  to  black  and  white  wires  
d) When  proximity  switch  detects  target,  voltage  should  change  from  negative  to  positive  
(or  vice  versa)    
e) LED  Lights  on  circuit  board  and  proximity  switch  should  alternate  when  proximity  switch  
detects  target  
f) Ensure  voltage  is  going  through  circuit  board  to  proximity  switch  by  connecting  meter  
leads  to  brown  and  blue  wires  –  should  read  12  volts  
g) Read  3.3V  (positive  or  negative)  by  connecting  meter  leads  to  blue  and  black  proximity  
switch  wires  
h) When  proximity  switch  detects  target,  voltage  should  change  from  negative  to  positive  
(or  vice  versa)  
i) Connect  black  lead  from  meter  to  metal  top  of  7805  
j) Connect  red  lead  from  meter  to  left  leg  of  7805  
k) Meter  should  read  +12V  DC  
l) Connect  red  lead  from  meter  to  right  leg  of  7805  
m) Meter  should  read  +5V  DC  
n) If  steps  a)  through  m)  are  as  specified,  go  to  section  8.2.5  
o) If  voltage  is  not  as  specified,  return  proximity  switch  assembly  to  Position  Tracking  
Systems  for  repairs.  

   
Figure  41  –  12V  Coming  Into  Proximity  Switch   Figure  42  –  Negative  3.3V  On  Blue  and  Orange  

(see  next  page  for  more  images)  

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   23  


 

   
Figure  43  –  Positive  3.3V  When  Sensor  On  Target   Figure  44  –  Negative  3.3V  On  Black  and  White  

   
Figure  45  –  Positive  3.3V  When  Sensor  on  Target   Figure  46  –  Negative  3.3V  on  Blue  and  Black  

   
Figure  47  -­‐  Positive  3.3V  When  Sensor  On  Target   Figure  48  –  7805  Location  in  Proximity  Switch  

   
Figure  49  -­‐  Red  Lead  to  Left  Leg  of  7805   Figure  50  -­‐  Red  Lead  to  Right  Leg  of  7805  

24   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 
8.2.5 Test  Proximity  Switch  Sensors  Through  Circuit  Board  

a) Turn  Posi-­‐Stop  on  


b) Connect  meter  black  lead  to  black  wire,  meter  red  lead  to  white  wire  on  proximity  switch  
board  
c) Meter  should  read  3.3V  
d) Touch  corresponding  sensor  to  metal  –  voltage  will  change  to  negative  3.3V  
e) Connect  meter  black  lead  to  blue  wire,  meter  red  lead  to  orange  wire  on  proximity  switch  
board  
f) Meter  should  read  3.3V  
g) Touch  corresponding  sensor  to  metal  –  voltage  will  change  to  negative  3.3V  
h) If  steps  a)  through  g)  are  not  as  specified,  go  to  section  8.3  
i) If  steps  a)  through  g)  are  as  specified,  perform  steps  f)  through  m)  in  section  8.2.4    

   
Figure  51  –  Black  Meter  Lead  To  Black,  Red  Meter  Lead   Figure  52  –  Touching  Sensor  To  Metal  Produces  Negative  
to  White   Voltage  

   
Figure  53  -­‐  Black  Meter  Lead  To  Blue,  Red  Meter  Lead  to   Figure  54  -­‐  Touching  Sensor  To  Metal  Produces  Negative  
Orange   Voltage  

   

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   25  


 
8.3 Check  Voltage  at  Encoder/Proximity  Switch  Input  Terminal  on  Main  Board  

a) Connect  encoder/proximity  switch  assembly  to  Posi-­‐Stop  with  encoder  cable  


b) Turn  on  Posi-­‐Stop  
c) Connect  meter  red  lead  to  pin  1  and  meter  black  lead  to  pin  2  on  terminal  block  at  left  
side  of  main  board  
d) Turn  encoder/proximity  switch  target  (slowly)  
e) Meter  should  change  from  +3V  to  -­‐3V  while  encoder/proximity  switch  target  is  turning  
slowly  
f) Connect  meter  red  lead  to  pin  3  and  meter  black  lead  to  pin  4  on  terminal  block  at  left  
side  of  main  board  
g) Turn  encoder/proximity  switch  target  (slowly)  
h) Meter  should  change  from  +3V  DC  to  -­‐3V  DC  while  encoder/proximity  switch  target  is  
turning  slowly  

(see  next  page  for  images)  

26   POSI-­‐STOP  PLUS  TROUBLESHOOTING   Version  1.0.0  


GUIDE  
 

   
Figure  55  –  Positive  3.3V  on  Pins  1  and  2   Figure  56  –  Negative  3.3V  on  Encoder  turn  

   
Figure  57  –  Positive  3.3V  on  Pins  3  and  4   Figure  58  –  Negative  3.3V  on  Encoder  turn  

 
Figure  59  –  Location  of  TB  on  Main  Board,  With  Pins  Labeled  1  through  4  

Version  1.0.0   POSI-­‐STOP  PLUS  TROUBLESHOOTING  GUIDE   27  

You might also like