You are on page 1of 11

IET Generation, Transmission & Distribution

Research Article

Positive sequence voltage source converter ISSN 1751-8687


Received on 4th March 2019

mathematical model for use in low short


Revised 20th September 2019
Accepted on 7th November 2019
E-First on 2nd December 2019
circuit systems doi: 10.1049/iet-gtd.2019.0346
www.ietdl.org

Deepak Ramasubramanian1 , Wenzong Wang1, Pouyan Pourbeik2, Evangelos Farantatos1, Anish


Gaikwad1, Sachin Soni3, Vladimir Chadliev3
1Grid Operations & Planning Group, Electric Power Research Institute, Knoxville, TN 37932, USA
2Power and Energy, Analysis, Consulting and Education, PLLC, Texas, USA
3Grid Integration, First Solar, Inc., Tempe, AZ 85281, USA

E-mail: dramasubramanian@epri.com

Abstract: In this study, modifications are proposed to the state-of-the-art positive sequence generic converter model in order to
capture the small-signal and large-signal oscillatory instabilities associated with converters interfaced at low short circuit
locations. The performance of the positive sequence model is validated against detailed electromagnetic simulations to lend
confidence in this proposed model. Additionally, validation of performance of the model against observed field measurements is
also carried out.

1 Introduction source. This is despite the fact that actually, a converter that is used
for a renewable energy source or battery energy system is truly a
Dynamic simulations using positive sequence models and tools are voltage source converter, where a dc voltage is converted to an ac
the main approach used by transmission planners to evaluate the voltage. In contrast, a current source converter (used widely in
stability behaviour of converter interfaced generation that are either motor drive applications) stores energy in an inductor on the dc
already connected to the bulk power system or are listed in the side, and the dc current is transformed into an ac current. However,
interconnection queue. In the last several years, significant work in a bulk power system connected renewable or battery energy
has been conducted through a broad industry-wide effort for the storage plant, the current output of the voltage source converter is
development of generic and public models for renewable energy strictly controlled to follow the angle of grid and thus, the bulk
systems. The work was done primarily within the Western power system perceives these sources to be as current sources. The
Electricity Coordinating Council (WECC) Renewable Energy state-of-the-art generic positive sequence converter model (named
Modeling Task Force, and the models have been adopted by as REGC_A [3]) reflects this perceived behaviour by modelling the
several of the major commercial software vendors in North inverter as a current source, since this control of the inverter
America. However, these existing state-of-the-art generic positive current is very fast.
sequence mathematical models of converter interfaced generation Generic converter models have a wide variety of use in bulk
have limitations in accurately characterising their stability under power system planning studies. However, due to their nature of
low short circuit grid conditions [1, 2]. The limitations arise being generic, these models also have a set of limitations. The
primarily due to the nature of the mechanism of positive sequence authors of [4, 5] provide an overview of the presently available
simulations. The solution of the differential and algebraic equations generic positive sequence converter models, their region of
in positive sequence simulations are carried out in a sequential accuracy and their limitations. In the state-of-the-art generic
manner. The outputs from the integration of the differential converter model, along with the representation of the behaviour of
equations are used to define the value of the magnitude and phase the converter as a controlled current source, the dynamics of the
of the current to be injected into the network at every generator/ fast inner current control loops of a converter (these control loops
load bus. Subsequently, with this new value of current, the are responsible for the strict control of current in a voltage source
algebraic equations of the network are solved to obtain the value of converter) are simplified to first-order time constants.
bus voltages. These new values of bus voltages are then used in the The speed of response of a controller by itself to a change in
next time step of integration of the differential equations and the reference can be indirectly linked to the magnitude of effort applied
process continues until the end of the simulation. Due to this by the controller, and the time taken to respond to the change in
sequential process, it is important to ensure that at the boundary reference in order to move the plant's output(s) towards the new
bus between the network and the device (usually the bus at which reference value. However, even with a fast controller, for a closed-
the device is connected), the solution of the network equations loop control system to be fast, the feedback from the plant output
converge at every time step. back into the controller input should also occur within a reasonable
When connected to a bus with a low short circuit capacity (large time frame. In other words, if the feedback from the plant back into
perceived impedance), a pure current source model in a positive the controller is quick and positively correlated to the applied effort
sequence simulation platform can experience numerical instability from the controller, then the controller ‘knows’ that it is achieving
because a small change in the injected current can have a large the desired response, and the closed-loop system has a greater
impact on the change in voltage magnitude. Thus, between probability of being stable. However, if there is a large time delay
subsequent time steps of integration, it is possible for the network in the feedback (and consequently phase lag), then, the fast
solution to not converge as the current injections (and thus the controller may assume that it is not applying the right magnitude of
voltage magnitudes) could oscillate between two values. This effort and will consequently either increase or decrease the amount
behaviour is more prominent as the percentage of current sources of effort applied based on the correlation of the feedback with the
increases in the network, as a current source relies on other applied effort. This can lead to the closed system becoming
elements of the network to maintain the voltage. Presently, most unstable. In order to stabilise such a system, the controller element
positive sequence models model the converter interface as a current

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97 87


© The Institution of Engineering and Technology 2019
PLL for low short circuit condition, which is not possible with the
existing positive sequence models. However, this model cannot
replace the need for detailed three-phase point-on-wave
simulations in electromagnetic transient type tools which should be
performed using vendor specific detailed models when considering
actual equipment design and site tuning for facilities in low short
circuit regions. This model can only help bridge the gap between
these two simulation platforms.
The subsequent sections will discuss the modifications made to
the state-of-the-art positive sequence converter model to include
the dynamics of the inner current control loop and the PLL. The
validation of the performance of this positive sequence converter
model is carried out by comparison against the performance of a
detailed point-on-wave simulation representation of a converter.
Simulations on various test systems are used to demonstrate the
efficacy of the proposed model.

Fig. 1 Single line diagram of representation of converter connected to 2 Model description


grid
The improvement in the numerical robustness and performance of
has to be slowed down. An example of application of this concept the state-of-the-art converter model is carried out along four steps.
in power systems is an internal feedback in static excitation The first step in the model improvement was proposed in [9, 10] to
systems. Static excitation systems are predominantly power introduce a voltage source interface positive sequence converter
electronics based, and can thus be a very fast controller. However, model as shown in Fig. 1. This model, named as REGC_B, has
when a large synchronous machine is connected to the network, been tentatively approved by the Western Electricity Coordinating
due to the combined impedance of the field winding of the Council (WECC) Model Validation Working Group (MVWG) and
generator, the loading level of the generator (results in a varying presently, individual commercial software vendors (GE-PSLFTM,
amount of armature reaction), and the external network impedance, Siemens PTI PSS®E, PowerWorld Simulator and Powertech Labs
the static exciter may have to be slowed down in order to stabilise DSA Tools) are developing a beta version of the model. If all
the system. The large impedance of a low short circuit system in controllers in the converter are tuned adequately, then, the voltage
combination with the armature reaction effect brought upon by the source interface of the model will only help ensure numerical
loading of the generator would result in a slower feedback response robustness of the positive sequence simulation.
of the terminal voltage back into the static exciter control loop. However, to have complete observability of the possible
In a converter energy source, the ability of the fast inner current oscillatory behaviour, the REGC_B model is further modified in
control loops to strictly control the value of injected current in a this paper with the proposal of three additional steps. The first
stable manner is linked to the active power output level of the proposed additional step is the introduction of the explicit
converter source, and the network impedance seen by the converter representation of the dynamics of the inner current controller loop
[2, 6]. An increase in both these parameters could often times as opposed to the present state-of-the-art representation of these
require the fast inner current controllers of the converters to be re- dynamics in REGC_A and REGC_B by simplified first-order time
tuned in the field to be slower in order to avoid instability [7]. constants. The representation of these inner current control loops is
Some non-linear controllers may also have adaptive tuning rules to based upon the model described in detail in [11]. A generic
change the control gain values depending on the nature of the proportional–integral controller with a reasonably high gain and
feedback voltage/current signals. However, in either scenario, if the small time constant is used to represent the fast dynamics of the
inner current controller is re-tuned to be slower then transiently, the inner current control loop.
network can no longer perceive the converter to be a current The second proposed additional step is the introduction of an
source. Instead, the converter energy source has to now be algebraic network iteration step between subsequent time steps in
mathematically modelled by its inherent voltage source nature. order to ensure that the current injection from the voltage source
Further, as these inner current controllers are made slower, the interface is within the specified current limits. Due to a Norton
frequency dynamics of these control loops would start aligning equivalent representation of voltage sources in positive sequence
closer to the frequency dynamics of the network and the other simulation software, and the sequential manner in which
slower elements. Thus, the dynamics of the inner current control differential and algebraic equations are solved, the current injected
loop can now no longer be represented by a simple first-order time into the network by this Norton equivalent can at times be greater
constant. It is of course out of scope of the generic positive than the limit specified by the converter control model. In order to
sequence models to have adaptive tuning rules. However, it is limit the current at every time step, an algebraic manipulation of
possible to improve the positive sequence models to be able to the Norton current is carried out at every time step when the
represent the inherent voltage source nature of a converter and the injected current is greater than the limit. The flow chart of this
dynamics of the inner current control loops. algebraic manipulation is shown in Fig. 2.
In addition to the inner current control loops, conventional In a low short circuit situation, a high value of gains of a phased
converter energy sources also have a phase locked loop (PLL) locked loop (a high gain is usually used in applications for high-
controller that tracks the angle of the grid and thereby enables the short circuit strength points of interconnection in order to ensure a
inner current control loops to inject current at the correct phase fast lock onto the grid voltage) can cause converter controllers to
angle. In order to have strict and fast current control by the inner become unstable. The high control gains would push the PLL angle
current control loops, it is imperative that the phase angle of the to change at a fast rate in order to try to synchronise with the grid
grid is known correctly, which is the task of the PLL. Due to the voltage angle, but in a low short circuit situation, the slightest
coupled nature of these two controllers, representation of the change in injected current can cause a large change in the feedback
dynamics of one of the controllers requires representation of the voltage. Thus, this feedback loop of a high gain forward path, and a
dynamics of the other controller as well. A fast PLL in a low short highly sensitive feedback path can lead to an instability. The
circuit system can also introduce undamped oscillations [8]. dynamics of the PLL thus play a crucial role in this process. As a
With this background, this paper proposes modifications to the positive sequence simulation is based upon a phasor simulation
state-of-the-art mathematical modelling of positive sequence approach, traditionally, at every time step of a transient simulation,
converter models. The model presented here allows the user to the angle of the grid voltage is directly obtained from the algebraic
investigate, at a high-level, the potential for controller oscillatory solution of the network solutions. In doing this, the complete
behaviour of the inner-current control loop in combination with the dynamic characteristics of the PLL are ignored. Thus, to include

88 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97


© The Institution of Engineering and Technology 2019
these characteristics, the third proposed additional step introduces The validation of the functionality of this modified model has been
the phased locked loop controller's dynamics as shown in Fig. 3. tested across a few different systems. For each system, the
Here, V treal, V timag, Ireal and Iimag are the real and imaginary behaviour of this positive sequence model has been compared with
components of the terminal voltage and injected current obtained both the behaviour of the same system simulated in positive
from the algebraic solution of the network solution. While the sequence with the present state-of-the-art REGC_A model and
individual components introduced in each step are intuitive from simulated in a point on wave simulation software. The point on
the aspect of a detailed point on wave simulation model of a power wave simulations were conducted in PSCAD® [12], while the
electronic converter, they have not been state of the art for positive positive sequence simulations were conducted in Siemens PTI
sequence simulation of the bulk power system. Their combined PSS®E [13] and GE-PSLFTM [14] with an integration time step of
representation however serves to bridge the gap between the two 1 ms. The modified positive sequence converter model is
simulation platforms without a drastic increase in computation implemented with the ‘user written model’ feature of GE-PSLFTM.
time. The block digram of the proposed converter model is shown Rather than split the results according to the size of the system,
in Fig. 4. it has been chosen to split the results according to size of the
disturbance. This also aligns with the usual process used to analyse
3 Demonstrating simulation results the robustness of controllers wherein, small-signal disturbances are

Fig. 2 Flowchart for algebraic manipulation of Norton current

Fig. 3 PLL implementation in positive sequence

Fig. 4 Complete block diagram of proposed positive sequence converter model

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97 89


© The Institution of Engineering and Technology 2019
Table 1 Summary of various simulation tests and systems used to demonstrate the validity of the proposed model
Disturbance Section of System Models compared Reason for comparison
type paper used
small signal 3.1.1 SMIB-1 proposed model Version A to convey the importance of including the effects of both the PLL
(explicit PLL only) versus and the inner current control loop
proposed model Version B
(explicit PLL and inner current
loop)
3.1.2 in-service REGC_A versus proposed to show the ability of the
solar plant model Version B
proposed model to provide a picture
of the oscillations observed in measurements.
These could not be shown with the state-of-the-art REGC_A model.
large-signal 3.2.1 SMIB-1 REGC_A versus proposed to further highlight the limitation of the existing state-
model Version B
of-the-art REGC_A model for large-signal disturbances in low short
circuit conditions
and the improvement achieved with the proposed model.
SMIB-2 REGC_A versus proposed highlight the limitation of the model against detailed
model Version B versus
PSCAD
EMT simulations and further demonstrate the improvement from the
proposed model.
3.2.2 real system proposed model Version B validation of the robustness of the proposed model for
versus PSCAD
large system and simultaneous comparison of the performance
against detailed EMT simulations

always analysed before large-signal disturbances. To this end, four own. Then, the setup of a realistic system is used to show the
different systems are used with the following reasoning: practical use of this proposed model while also observing the
influence of the dynamics of other elements within close electrical
• Section 3.1.1 uses a simple single machine infinite bus (SMIB) proximity. Simultaneously, the aim of the realistic system is to
setup to lay out the concept of the observed performance. Here, show the capability of the model to depict the behaviour that has
there is a single resource that is under study and thus, one can be been captured in measurements. A summary of the various tests
assured that the response provided by the model is not influenced and systems used to demonstrate the validity of the proposed
by the dynamics of any other elements in the system. model is tabulated in Table 1.
• Section 3.1.2 uses the layout of an actual solar plant to further
investigate small-signal events. The system under study is still a 3.1 Small disturbance simulation
small system which is connected in manner which is similar to a
single machine infinite bus setup. However, rather than being In the power system, a lot of converter–weak grid interactions that
single machine, it is a single plant infinite bus setup where the occur can be small-signal interactions. Consider a solar plant
entire solar plant consists of four aggregated energy resources. increasing its power output as the solar irradiation increases. If an
Here, the objective of this section is two-fold: unplanned outage occurs during this change, it can cause the
system strength to change at the solar plant's terminals. Due to this
i. To verify if the small magnitude oscillations observed in reality change in system strength, the increase in power output due to
through measurements can indeed be replicated by the increase in solar irradiation can cause the converter controllers to
proposed model as compared to the existing state-of-the-art exhibit undamped oscillations. To observe the behaviour of the
model. Successful replication of these oscillations is in itself an modified positive sequence model for such a scenario, two system
important result as it serves to highlight the practical use of this setups were considered. The first setup is a fictitious system that
model. was constructed to illustrate the small-signal behaviour, while the
ii. To verify if there would be interactions across the four second setup is representative of an actual solar plant.
aggregated resources within the plant and if the proposed
model would still be numerically robust. Here, the responses 3.1.1 Synthetic system for small-signal behaviour: A synthetic
provided by the proposed model are influenced by the single machine infinite bus setup is shown in Fig. 5. The source at
dynamics of adjacent models. bus 1 was represented by a classical synchronous machine with a
• Section 3.2.1 again uses single machine infinite bus systems. The large MVA and large value of inertia constant. The source at bus 2
first system is the same as used in Section 3.1.1 while the second was represented to be a solar power plant whose electrical controls
system has a more realistic representation of the external system were modelled using the state-of-the-art REEC_A model [3].
rather than just a single Thévenin equivalent. This set-up again The modified positive sequence converter model was used as
allows one to observe the dynamics of the proposed model for the converter interface for the solar plant. Cole and Belmans [15]
large-signal disturbances but uninfluenced by the dynamics of suggest that the dynamics of the PLL can be ‘neglected in power
other elements. system stability studies’ and have accordingly structured their
• Section 3.2.2 uses a portion of the system of an actual North reduced order models. However, the approximate representation of
American utility. The results observed in this section, and its the fast dynamics of the inner current control loop and the PLL for
comparison to detailed electromagnetic results serves to highlight weak-grid (low short circuit strength) connection points can result
the practical use of this proposed model. in an inaccurate representation of the stability of the resources. To
showcase the importance of the dynamics of the inner current
Thus, for each type of disturbance, first a simple fictitious control loop working in tandem with the PLL, two versions of the
system is used to show the behaviour of the individual model on its converter interface model were used. In the first version (called
Version A), the inner current control loop was entirely replaced by
90 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97
© The Institution of Engineering and Technology 2019
Fig. 5 Synthetic single machine infinite bus setup

Fig. 6 Active power output of converter for an elliptical change in active power reference. The inset shows the observed response when x = 0.01 pu while the
main figure shows the observed response when x = 0.505 pu. Both figures also compare the behaviour of Version A of the proposed model (with inner current
control loop represented only as first-order time constant) against the behaviour of Version B of the proposed model (with explicit representation of the inner
current control loop dynamics)

a first-order time constant (as is in the present state-of-the-art model. It goes without saying that the presence of the inner
REGC_A model), but the dynamics of the PLL were represented. current control loop does not contribute to the oscillation by
The second version of the model (called Version B) had itself, but rather how it is tuned (values of the control gains)
representation of the dynamics of both the inner current control and the system strength.
loop and the PLL. The second version of the model is the complete ii. The presence of the PLL and the gain settings of the PLL.
model with the block diagram shown in Fig. 4. Note that the iii. The system short-circuit strength as seen by the comparison of
algebraic iterations to enforce the current limits at every time step results when the value of x = 0.01 pu as compared to when the
is incorporated in both versions, since voltage source interfaces are value of x = 0.505 pu.
used. In both versions of the model, the PLL control parameters iv. The system loading which relates to the operation point.
were KPLLi = 1500 and KPLLp = 20.0. In the Version B of the
model, the inner current control loop parameters were KIp = 5.0 Furthermore, the presence of the oscillations is influenced by
and KIi = 70.0 while in Version A of the model, the time constant the initial power output of the plant. To show the impact of the
that represented the characteristics of the inner current control loop initial conditions and also provide a further insight into the impact
was set to a value of 0.07 s. of short circuit strength at the point of interconnection, the
In order to represent the increase in solar irradiation through the behaviour of the converter resource for a 5 MW step change in
day, an elliptical change in active power reference command was power command (both in the positive and negative direction) is
played into the REEC_A model. The performance of the model to shown in Figs. 7 and 8 for an operating point of 90 and 100 MW
two different system short circuit strength scenarios was analysed. respectively. Only the Version B of proposed model which has
The short circuit capacity at the terminal of the solar plant was explicit representation of both the inner current control loops and
varied by changing the reactance X of the transmission line the phase locked loop is used in these results.
highlighted in Fig. 5. A high short circuit rating was represented From these results, the role played by the initial operating
with a value of 0.01 pu while a low short circuit ratio was condition and the direction of change in the power reference
represented with a value of 0.505 pu. The active power output of command can be observed. In a high short circuit scenario
the converter for both the low short circuit and the high short (x = 0.01 pu), there are no oscillations observed. In a low short
circuit scenario is shown in Fig. 6 for the elliptical change in power circuit scenario (x = 0.505 pu), the oscillatory mode is excited after
reference command. the active power output reaches around 95 MW. However, for the
It can be seen for the low short circuit scenario, as the active downward change in step reference (from 95 to 90 MW), the
power output increases, the dynamics of the inner current control presence of positive damping can be seen, because the downward
loop and the PLL give rise to growing oscillations which change returns the plants back below the loading level where
subsequently get damped out as the active power output reduces. oscillations start. However, with an initial operating point of 100 
However, these oscillations are not visible in Version A of the MW, the oscillations are present for both an upward and downward
model when the inner current control loop is replaced by the single step, since the plant is already above the power level (95 MW)
first-order time constant. The observed oscillations are not where oscillations start.
‘electromechanical’ even though they have an oscillatory This behaviour can be used to explain the presence of
frequency of around 5 Hz. The oscillations here are purely oscillations in Fig. 6 only during the downward change in active
electrical and are driven by a combination of four factors: power reference. This is because the oscillations only start once
power has exceeded 95 MW, and this happens only around the peak
i. The presence of the inner-current control loop and its of the curve in Fig. 6. Thus, the oscillations start near the peak and
interaction with the dynamics of the PLL as shown by the are observable on the way down, until the damping becomes
difference in results between Version A and Version B of the

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97 91


© The Institution of Engineering and Technology 2019
Fig. 7 Active power output of the converter for step changes in power reference with operating point of 90 MW. The blue curve is the output observed of the
proposed model with x = 0.01 pu while the red curve is the output observed with x = 0.505 pu

Fig. 8 Active power output of the converter for step changes in power reference with operating point of 100 MW. The blue curve is the output observed of the
proposed model with x = 0.01 pu while the red curve is the output observed with x = 0.505 pu

Fig. 9 Small-signal oscillations observed at solar plant [16]

positive once we move below 95 MW and thus eventually damp generation level of the two large solar sources were reduced to 200
out completely. and 190 MW, respectively. For this plant, the generic state-of-the-
Such small-signal oscillations are however not an artefact of art dynamic models supplied to the transmission operator
simulation as they have also been observed in the output of actual comprised of the REGC_A converter interface model, REEC_B
converter plants. The next system setup looks into the ability of the electrical control model and the REPC_A plant controller model.
modified positive sequence model to represent the oscillatory The REGC_A model was replaced with the proposed converter
behaviour observed at a solar plant. model to validate the effectiveness of the proposed model. The
electrical controller and plant controller models were retained. As
3.1.2 In-service solar plant: Recently, an in-frequent small-signal in the synthetic system, an elliptical change in active power
stability issue, shown in Fig. 9, was observed from measurement reference of the REPC_A model was imposed for varying values of
data collected near the terminals of a 500 MW solar plant [16]. An the grid tie impedance. The phase locked loop control parameters
in-depth analysis into the cause of the oscillations revealed that the were KPLLi = 2000 and KPLLp = 20.0 and the inner current control
fast controllers of the converters in the plant were reacting to the loop parameters were KIp = 5.0 and KIi = 70.0. It must be noted
change in output active power level. Additionally, from that these parameters values are not necessarily the actual control
information obtained from the transmission system operator, it was gains of the converters in the plant, but are instead representative
inferred that on that given day, the converter plant was connected generic values. With the original value of the grid tie impedance
to a relatively lower short circuit network. While the converter (high short circuit), Fig. 11 shows the active power output of one of
controllers in the plant have since been re-tuned, the present state- the large generators of the plant.
of-the-art positive sequence generic models supplied to the The blue curve represents the output from the state-of-the-art
transmission system operator were unable to predict this oscillatory REGC_A model while the red curve is the output from the
behaviour as the dynamics of the fast controller loops were not proposed new converter model. It can be seen that for a strong
represented. connection, i.e. high short circuit, the state-of-the-art converter
The layout of the solar plant, with respect to the bulk power models are a good approximation of the fast dynamics of the inner
system is shown in Fig. 10. To model and simulate the same current controller and PLL, and there is no significant difference
approximate operating condition shown in Fig. 9, the active power between the outputs from the two converter models. However, as

92 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97


© The Institution of Engineering and Technology 2019
Fig. 10 Layout of solar plant

Fig. 11 Active power output of solar plant with original grid tie impedance. The blue curve is the output observed while using the state-of-the-art REGC_A
model while the red curve is the output observed with the proposed model

Fig. 12 Active power output of solar plant with low short circuit grid tie impedance. The blue curve is the output observed while using the state-of-the-art
REGC_A model while the red curve is the output observed with the proposed model

frequency that are very much similar to the oscillations observed in


the measurement data shown in Fig. 9. These oscillations can
subsequently be damped by re-tuning the phase locked loop gains.
With a lower value of PLL integral gain, the active power output of
both converter models is shown in Fig. 13 for the same low short
circuit scenario. The results in these two sections serve to validate
the small-signal behaviour of the modified positive sequence
converter model, while also showcasing its importance to a system
planner/operator (Fig. 14).

3.2 Large-signal stability


Fig. 13 Active power output of solar plant with low short circuit grid tie
The fast PLL and inner current controllers of a converter interfaced
impedance and low PLL gain. The blue curve is the output observed while
generation plant are also susceptible to large-signal instability
using the state-of-the-art REGC_A model while the red curve is the output
under low short circuit conditions. The instability usually occurs
observed with the proposed model
upon clearance of the fault and is related to the angular
displacement of the converter currents with respect to the large
the short circuit strength of the grid connection reduces, a
power system. These large-signal oscillations have been observed
significant difference is observed between the outputs of the two
in measurement data [17] and traditionally require point on wave
models as shown in Fig. 12. The short circuit strength of the grid
electromagnetic detail simulations in order to observe and mitigate
tie was reduced by increasing the reactance to 0.065 pu. With the
the phenomena [6, 18, 19]. However, as these oscillations are a
same fast controllers, the proposed positive sequence converter
manifestation of the fast converter controllers, the ability of the
model is able to show small-signal oscillations of around 9 Hz in
modified positive sequence model to capture these oscillations has
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97 93
© The Institution of Engineering and Technology 2019
Fig. 14 Active power output of the converter for a bolted three phase fault on single machine infinite bus system. The blue curve is the output of the proposed
model observed with x = 0.01 pu, the red curve is the output of the proposed model observed with x = 0.505 pu, the green curve is the output of the state-of-
the-art REGC_A model observed with x = 0.505 pu

Fig. 15 One line diagram of the synthetic system

to also be evaluated. Two system setups are again chosen for this A more detailed analysis is carried out with another fictitious
exercise. The first setup is a fictitious system, while the second test system shown by the one-line diagram in Fig. 15.
setup is representative of a portion of a utility's bulk power system. The source at bus 2 (at the right side of the diagram) was
represented by a classical machine with an MVA of 1000.0, inertia
3.2.1 Synthetic system for large-signal behaviour: Two of 5.0 s and D = 1.5. For comparison of the behaviour of the
synthetic systems have been used to observe the performance of proposed model against existing state-of-the-art models, the source
the model to large-signal disturbances. The first system studied is at bus 9 (left side of the diagram) was represented by different
the same single machine infinite bus system used in Section 3.1.1. converter interface models, along with the generic REEC_A model
Three scenarios were analysed as described below: in voltage control mode. The impedance of the source at bus 2 was
used to vary the short circuit strength of the system with
i. With x = 0.01 pu, the application of a 6 cycle bolted three- X′′ = 0.0025 pu representing a high short circuit system and
phase fault on bus 2 using the proposed model. The response is X′′ = 3.0 pu representing a low short circuit system.
shown by the blue curve. From a PSCAD® simulation, the response of the converter
ii. With x = 0.505 pu, the application of a 6 cycle bolted three- energy source for a 12 cycle three phase fault at bus 1 is shown in
phase fault on bus 2 using the proposed model. The response is Figs. 16 and 17 for both the high and low short circuit case,
shown by the red curve. respectively, while Table 2 elaborates on the description of the
iii. With x = 0.505 pu, the application of a 6 cycle bolted three- legend in the plot. The representation of the model in PSCAD® is
phase fault on bus 2 using the state-of-the-art REGC_A model. the same representation as used in [2]. A three phase average
The response is shown by the green curve. model of the converter has been used with explicit representation
of all grid side converter control loops. It can clearly be seen that
With a high short circuit strength, the system is able to ride the present state-of-the-art positive sequence current source
through a three-phase fault in a stable manner. However, with a converter model (i.e. REGC_A) is unable to represent the
low short circuit strength, the existing state-of-the-art REGC_A oscillatory behaviour observed in the point on wave simulation for
model shows that the response would be stable while the proposed a low short circuit scenario. With the proposed modified positive
new model shows the possibility of oscillatory instability. This type sequence model, for the same location and duration of the fault,
of oscillatory instability has been observed even in field Figs. 18 and 19 show the performance of the model for high and
measurements. Thus, a model such as that proposed here might low short circuit, respectively. In this model and for this system,
offer a means to further investigate such possibilities. re = 0.0025 pu, xe = 0.1 pu, Imax = 1.2 pu, KIp = 5.0, KIi = 60.0,

94 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97


© The Institution of Engineering and Technology 2019
capacitances. In contrast, in the positive sequence simulation, the
network is modelled as an algebraic representation of the
fundamental frequency impedance.

3.2.2 Portion of a large utility system: This system is a portion


of the network in a real transmission footprint, with the addition of
several hypothetical renewable energy resources that are in the
interconnection queue. The system has 119 buses, 3 equivalent
sources (representing external system outside the studied area) and
9 renewable power plants. All the renewable power plants are
modelled as Type 4 WTGs in voltage control mode with reactive
power priority during low voltage ride through conditions. Total
renewable generation is 665 MW (total capacity 894 MVA) with
393 MW transferred to the equivalent sources.
In positive sequence, all nine renewable energy sources were
modelled with the proposed modified converter model and the
REEC_A electrical control model in local voltage control mode.
The proportional and integral controller gains for the voltage
Fig. 16 Electromagnetic response of converter plant to a 12 cycle three controller were set as 0.0 and 120.0, respectively. In the proposed
phase fault for high short circuit levels modified converter model, re = 0.0015 pu, xe = 0.15 pu, Imax = 1.1 
pu, KI p = 6.0, KIi = 70.0, KPLLp = 60.0 and KPLLi = 1400.0. The
limits of the PLL (Δωmax and Δωmin) were set at 12 Hz. In point on
wave electromagnetic simulations, the renewable sources were
modelled with the generic converter controller models, but with
inclusion of the fast PLL and inner current control loop.
These fast control loops can withstand a finite duration of fault
at the point of interconnection of the converter plant before going
unstable. Thus, knowledge of the maximum finite duration is
important for a transmission planner to coordinate protection
settings on the transmission system around the point of
interconnection of the converter plant. The ‘critical clearing time’
from both point on wave PSCAD® and positive sequence GE-
PSLFTM simulations were obtained by sequential application of a
three phase bolted fault at the point of interconnection on each
converter plant, until the PLL lost synchronism. By losing
synchronism, the PLL is unable to lock onto the grid angle and
undergoes at least a full 360° rotation before locking onto the
angle. This however causes large transients in the active power,
with the converter consuming active power. In determining this
Fig. 17 Electromagnetic response of converter plant to a 12 cycle three critical clearing time, the aim is to prevent the PLL angle from
phase fault for low short circuit levels losing synchronism with the grid. The critical clearing times
obtained from both positive sequence and point on wave
Table 2 Description of legend for Figs. 16 and 17 simulations are tabulated in Table 3.
Legend Description Modelling details Here, Group 1 and Group 2 are a set of wind turbines that are
colour electrically close to each other, and thus, behave in a coherent
blue generic type 4 wind positive state-of-the-art model manner. The wind turbines numbered 1, 2, 3 and 4 form Group 1,
sequence model while the turbines numbered 7 and 8 form Group B. For these
(REGC_A, REEC_A) in
groups of turbines, the critical clearing time was evaluated by
applying the fault at the coupling bus of these turbines. It can be
Siemens PTI PSS® E seen that the critical clearing time obtained from the modified
green generic type 4 wind model addition of fast inner positive sequence model is very close to that obtained from the
(REGC_A, REEC_A) controllers and point on wave simulation.
in PSCAD® PLL to generic model For one particular wind turbine, WTG 5, the frequency and
red full type 4 wind converter inclusion of dc bus, angle from the PLL from both the positive sequence simulation and
model in PSCAD® rectifier and the point on wave simulation is shown in Fig. 20 when the fault is
cleared 1/8th cycle before the critical clearing time, and in Fig. 21
induction machine
when the fault is cleared 1/8th cycle after the critical clearing time.
dynamics
It can be seen that the fast control loops in the modified positive
sequence model are able to represent the transient behaviour seen
from the detailed point on wave simulations for both the stable and
KPLLp = 40.0 and KPLLi = 3500.0. The limits of the PLL (Δωmax unstable scenario. The active power, reactive power and terminal
and Δωmin) were set at 12 Hz. Additionally, due to the presence of voltage magnitude of the converter resource for both these fault
these fast control loops, the simulation had to be run at a time step clearing times are shown in Figs. 22 and 23.
of 1 ms as opposed to the conventional 4 ms time step. It can be Further sensitivity studies were carried out to obtain the critical
seen that this modified positive sequence model is able to provide clearing time for variation in the controller values of inner current
observability into the oscillatory behaviour that converter control loop and the PLL. The variations were carried out both in
interfaced plants are susceptible to when interfaced to low short point on wave and positive sequence simulations, and angle output
circuit conditions. However, the values of the control gains in the of the PLL is compared across these two simulation platforms in
fast inner current control loops and PLL of the positive sequence Figs. 24 and 25 for WTG 5. The results in this section have thus
model do not directly translate from the point on wave simulation served to increase confidence in the proposed modified positive
model. This is although to be expected as the point on wave sequence converter model and its ability to allow a transmission
simulation has a much smaller time step of integration, while also planner to have observability into the possible oscillatory issues
modelling the network components as inductances and
IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97 95
© The Institution of Engineering and Technology 2019
Fig. 20 Frequency and angle of PLL of WTG 5 from positive sequence
and point on wave simulation when fault is cleared 1/8th cycle before
critical clearing time

Fig. 18 Positive sequence response of converter plant to a 12 cycle three


phase fault for high short circuit levels

Fig. 21 Frequency and angle of PLL of WTG 5 from positive sequence


and point on wave simulation when fault is cleared 1/8th cycle after critical
clearing time

Fig. 19 Positive sequence response of converter plant to a 12 cycle three


phase fault for low short circuit levels

Table 3 Critical clearing time compared across positive


sequence and point on wave simulations
WTG GE-PSLFTM Critical PSCAD® Critical clearing Fig. 22 Active, reactive power and terminal voltage magnitude of WTG 5
clearing
from positive sequence and point on wave simulation when fault is cleared
time (cycles of 60 Hz) time (cycles of 60 Hz) 1/8th cycle before critical clearing time
WTG 9 4.65 3.77
WTG 5 6.95 6.65 ideal current source can experience instability as a small change in
WTG 6 6.45 6.79 the injected current can have a large effect on the voltage
group 2 7.05 7.32 magnitude and angle. The PLL would then try to quickly track this
group 1 7.05 7.47 large change in the angle and in doing so, during the transient,
could provide an erroneous value of angle to the inner current
controller. This could then result in current being injected at the
wrong phase which could further cause the voltage magnitude and
that may arise from converter interfaced generation under low short
angle to change and lead to instability as shown by the results.
circuit conditions.
Stabilisation of the system can be achieved by slowing down the
Observability of the dynamics of the PLL and the inner current
controllers but it could result in degradation of the performance
control loop are crucial when viewed from the perspective that at
and has to be evaluated on a case by case basis. Other approaches
present, in a bulk power system connected inverter based resource,
may also be available for stabilising and optimising these control
the current output of the voltage source converter is strictly
loops, which are used in commercial equipment.
controlled to meet its reference values and thus the bulk power
system perceives these sources to be as current sources. This strict
and near rigid control on current is primarily brought upon by the 4 Conclusion
inner current control loop, with the reference phasor generated by In this paper, modifications to the generic positive sequence
the PLL. The PLL aims to track the network voltage angle quickly converter model have been proposed. These include representation
to minimise the transient in the current output. The inner current of the dynamics of the faster inner current control loops and the
controller uses this value of the angle to ensure that the power and PLL. The explicit inclusion of the dynamics of these control loops,
voltage objectives are met. Simultaneously, the inner current along with a slightly smaller time step of integration allows for
controller also ensures that the magnitude of current is within its observability on the oscillatory behaviour of the converter
limits. When connected to a bus with a low short circuit capacity interfaced resource in low short circuit systems. The performance
(large impedance), a source behaving in a manner similar to an of this mathematical model has been successfully validated by
96 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97
© The Institution of Engineering and Technology 2019
between positive sequence simulation platforms and point on wave
simulation platforms and would now provide a system planner with
an intermediate step to help further screen locations where a
detailed electromagnetic simulation would be required. The model
does require a smaller than typical integration time step to be used
due to the faster dynamics of the inner-current control loops. This
will somewhat reduce the simulation speed for large system
simulations. However, we suspect that this factor alone may not be
a significant barrier for the use of the model, since some other
models (e.g. two-cage induction motor models, some HVDC
models etc.) also use similarly smaller integration time steps within
the model itself, and are still used in large system simulations.
Fig. 23 Active, reactive power and terminal voltage magnitude of WTG 5 Furthermore, this model need not necessarily be used for every
from positive sequence and point on wave simulation when fault is cleared inverter-based generator, but can be used only for those generators
1/8th cycle after critical clearing time located in weak parts of the system. Efficient identification of the
locations of these generators is a topic of future research.

5 References
[1] Pourbeik, P., Sanchez-Gasca, J.J., Senthil, J., et al.: ‘Value and limitations of
the positive sequence generic models of renewable energy systems’, [Online]:
Available at https://www.wecc.org/Reliability/White%20Paper%20Generic
%20Model%20Limitations.pdf, accessed December 2015
[2] Wang, W., Huang, G.M., Kansal, P., et al.: ‘Instability of PLL-synchronized
converter-based generators in low short-circuit systems and the limitations of
positive sequence modeling’. 2018 North American Power Symp. (NAPS),
2018, pp. 1–5
[3] WECC Renewable Energy Modeling Task Force: ‘WECC PV power plant
dynamic modeling guide’. Available at https://www.wecc.biz/Reliability/
WECC%20Solar%20Plant%20Dynamic%20Modeling%20Guidelines.pdf,
accessed April 2014
Fig. 24 Comparison of angle output of the PLL of WTG 5 for the stable [4] ‘Model user guide for generic renewable energy system models’. Technical
scenario across positive sequence and point on wave simulation platforms, Report 3002014083, EPRI, Palo Alto, CA, 2018
[5] Pourbeik, P., Sanchez-Gasca, J.J., Senthil, J., et al.: ‘Generic dynamic models
and variation of control gains for modeling wind power plants and other renewable technologies in large-
scale power system studies’, IEEE Trans. Energy Conver., 2017, 32, (3), pp.
1108–1116
[6] ‘Renewable energy systems modeling considerations for weak grid studies -
limitations of positive sequence models in comparison with three-phase
models’. Technical Report 3002010928, EPRI, Palo Alto, CA., 2017
[7] Cai, R., Ruan, J., Huang, X., et al.: ‘Research on grid instability caused by the
interactions in microgrid’. CIRED Workshop 2018, June 2018, pp. 1–4
[8] National Grid: ‘Performance of phase-locked loop based converters’.
Available at https://www.nationalgrideso.com/sites/eso/files/documents/Phase
%20locked%20loop%20FINAL.pdf, accessed December 2017
[9] Ramasubramanian, D., Yu, Z., Ayyanar, R., et al.: ‘Converter model for
representing converter interfaced generation in large scale grid simulations’,
IEEE Trans. Power Syst., 2017, 32, (1), pp. 765–773
[10] Pourbeik, P.: ‘Proposed REGC_B Model’. Available at https://www.wecc.biz/
Administrative/REMTF_REGC_A_and_REGC_B_0317.pdf, accessed March
2017
[11] Ramasubramanian, D., Vittal, V., Farantatos, E.: ‘Enforcing strict current
Fig. 25 Comparison of angle output of the PLL of WTG 5 for the unstable control in controlled voltage source converter model for use in large scale
scenario across positive sequence and point on wave simulation platforms, positive sequence time domain simulations’. 2018 Power Systems
and variation of control gains Computation Conf. (PSCC), Dublin, Ireland, June 2018, pp. 1–8
[12] ‘PSCAD’, Manitoba HVDC Research Centre, 2018. Available at https://
hvdc.ca/pscad/
comparison with the performance of a detailed converter control [13] ‘PSS®E’, Siemens PTI, 2018. Available at https://new.siemens.com/
system in an electromagnetic time-domain simulation. global/en/products/energy/services/transmission-distribution-smart-grid/
However, it must be mentioned that this model does not intend consulting-and-planning/pss-software/pss-e.html
to replace the importance and necessity of detailed point on wave [14] ‘Concorda Positive Sequence Load Flow Software(PSLF)’, General Electric
International, Inc., 2018. Available at http://www.geenergyconsulting.com/
simulations. Positive sequence simulation tools and models, while practice-area/software-products/pslf
being an advantageous and convenient platform to simulate the [15] Cole, S., Belmans, R.: ‘A proposal for standard VSC HVDC dynamic models
bulk power system, still have many limitations. The behaviour of in power system stability studies’, Electr. Pow. Syst. Res., 2011, 81, pp. 967–
converter interfaced generation under every and all circumstances 973
[16] First Solar Inc.: ‘Deploying utility-scale PV power plants in weak grids’.
can only be gleaned from detailed point on wave simulations. 2017 IEEE Power & Energy Society General Meeting, July 2017
However, there is a significant burden involved in running a point [17] NERC Inverter-Based Resource Performance Task Force: ‘Reliability
on wave simulation, and thus, engineering judgment has to be used guideline: BPS-connected inverter-based resource performance’. Technical
in deciding the simulation platform for a particular study. Report, North American Electric Reliability Corporation, September 2018
[18] ‘Integrating inverter-based resources into low short circuit strength systems’.
Unfortunately, industry wide there is no simple answer as of yet to Technical Report, North American Electric Reliability Corporation, December
evaluate the exact scenario or location at which a detailed 2017
simulation study has to be conducted. The proposed positive [19] Working Group B4.62: ‘Connection of wind farms to weak AC networks’.
sequence model described in this paper serves to bridge the gap Technical Report, CIGRE, December 2016

IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97 97


© The Institution of Engineering and Technology 2019

You might also like