Professional Documents
Culture Documents
Research Article
E-mail: dramasubramanian@epri.com
Abstract: In this study, modifications are proposed to the state-of-the-art positive sequence generic converter model in order to
capture the small-signal and large-signal oscillatory instabilities associated with converters interfaced at low short circuit
locations. The performance of the positive sequence model is validated against detailed electromagnetic simulations to lend
confidence in this proposed model. Additionally, validation of performance of the model against observed field measurements is
also carried out.
1 Introduction source. This is despite the fact that actually, a converter that is used
for a renewable energy source or battery energy system is truly a
Dynamic simulations using positive sequence models and tools are voltage source converter, where a dc voltage is converted to an ac
the main approach used by transmission planners to evaluate the voltage. In contrast, a current source converter (used widely in
stability behaviour of converter interfaced generation that are either motor drive applications) stores energy in an inductor on the dc
already connected to the bulk power system or are listed in the side, and the dc current is transformed into an ac current. However,
interconnection queue. In the last several years, significant work in a bulk power system connected renewable or battery energy
has been conducted through a broad industry-wide effort for the storage plant, the current output of the voltage source converter is
development of generic and public models for renewable energy strictly controlled to follow the angle of grid and thus, the bulk
systems. The work was done primarily within the Western power system perceives these sources to be as current sources. The
Electricity Coordinating Council (WECC) Renewable Energy state-of-the-art generic positive sequence converter model (named
Modeling Task Force, and the models have been adopted by as REGC_A [3]) reflects this perceived behaviour by modelling the
several of the major commercial software vendors in North inverter as a current source, since this control of the inverter
America. However, these existing state-of-the-art generic positive current is very fast.
sequence mathematical models of converter interfaced generation Generic converter models have a wide variety of use in bulk
have limitations in accurately characterising their stability under power system planning studies. However, due to their nature of
low short circuit grid conditions [1, 2]. The limitations arise being generic, these models also have a set of limitations. The
primarily due to the nature of the mechanism of positive sequence authors of [4, 5] provide an overview of the presently available
simulations. The solution of the differential and algebraic equations generic positive sequence converter models, their region of
in positive sequence simulations are carried out in a sequential accuracy and their limitations. In the state-of-the-art generic
manner. The outputs from the integration of the differential converter model, along with the representation of the behaviour of
equations are used to define the value of the magnitude and phase the converter as a controlled current source, the dynamics of the
of the current to be injected into the network at every generator/ fast inner current control loops of a converter (these control loops
load bus. Subsequently, with this new value of current, the are responsible for the strict control of current in a voltage source
algebraic equations of the network are solved to obtain the value of converter) are simplified to first-order time constants.
bus voltages. These new values of bus voltages are then used in the The speed of response of a controller by itself to a change in
next time step of integration of the differential equations and the reference can be indirectly linked to the magnitude of effort applied
process continues until the end of the simulation. Due to this by the controller, and the time taken to respond to the change in
sequential process, it is important to ensure that at the boundary reference in order to move the plant's output(s) towards the new
bus between the network and the device (usually the bus at which reference value. However, even with a fast controller, for a closed-
the device is connected), the solution of the network equations loop control system to be fast, the feedback from the plant output
converge at every time step. back into the controller input should also occur within a reasonable
When connected to a bus with a low short circuit capacity (large time frame. In other words, if the feedback from the plant back into
perceived impedance), a pure current source model in a positive the controller is quick and positively correlated to the applied effort
sequence simulation platform can experience numerical instability from the controller, then the controller ‘knows’ that it is achieving
because a small change in the injected current can have a large the desired response, and the closed-loop system has a greater
impact on the change in voltage magnitude. Thus, between probability of being stable. However, if there is a large time delay
subsequent time steps of integration, it is possible for the network in the feedback (and consequently phase lag), then, the fast
solution to not converge as the current injections (and thus the controller may assume that it is not applying the right magnitude of
voltage magnitudes) could oscillate between two values. This effort and will consequently either increase or decrease the amount
behaviour is more prominent as the percentage of current sources of effort applied based on the correlation of the feedback with the
increases in the network, as a current source relies on other applied effort. This can lead to the closed system becoming
elements of the network to maintain the voltage. Presently, most unstable. In order to stabilise such a system, the controller element
positive sequence models model the converter interface as a current
always analysed before large-signal disturbances. To this end, four own. Then, the setup of a realistic system is used to show the
different systems are used with the following reasoning: practical use of this proposed model while also observing the
influence of the dynamics of other elements within close electrical
• Section 3.1.1 uses a simple single machine infinite bus (SMIB) proximity. Simultaneously, the aim of the realistic system is to
setup to lay out the concept of the observed performance. Here, show the capability of the model to depict the behaviour that has
there is a single resource that is under study and thus, one can be been captured in measurements. A summary of the various tests
assured that the response provided by the model is not influenced and systems used to demonstrate the validity of the proposed
by the dynamics of any other elements in the system. model is tabulated in Table 1.
• Section 3.1.2 uses the layout of an actual solar plant to further
investigate small-signal events. The system under study is still a 3.1 Small disturbance simulation
small system which is connected in manner which is similar to a
single machine infinite bus setup. However, rather than being In the power system, a lot of converter–weak grid interactions that
single machine, it is a single plant infinite bus setup where the occur can be small-signal interactions. Consider a solar plant
entire solar plant consists of four aggregated energy resources. increasing its power output as the solar irradiation increases. If an
Here, the objective of this section is two-fold: unplanned outage occurs during this change, it can cause the
system strength to change at the solar plant's terminals. Due to this
i. To verify if the small magnitude oscillations observed in reality change in system strength, the increase in power output due to
through measurements can indeed be replicated by the increase in solar irradiation can cause the converter controllers to
proposed model as compared to the existing state-of-the-art exhibit undamped oscillations. To observe the behaviour of the
model. Successful replication of these oscillations is in itself an modified positive sequence model for such a scenario, two system
important result as it serves to highlight the practical use of this setups were considered. The first setup is a fictitious system that
model. was constructed to illustrate the small-signal behaviour, while the
ii. To verify if there would be interactions across the four second setup is representative of an actual solar plant.
aggregated resources within the plant and if the proposed
model would still be numerically robust. Here, the responses 3.1.1 Synthetic system for small-signal behaviour: A synthetic
provided by the proposed model are influenced by the single machine infinite bus setup is shown in Fig. 5. The source at
dynamics of adjacent models. bus 1 was represented by a classical synchronous machine with a
• Section 3.2.1 again uses single machine infinite bus systems. The large MVA and large value of inertia constant. The source at bus 2
first system is the same as used in Section 3.1.1 while the second was represented to be a solar power plant whose electrical controls
system has a more realistic representation of the external system were modelled using the state-of-the-art REEC_A model [3].
rather than just a single Thévenin equivalent. This set-up again The modified positive sequence converter model was used as
allows one to observe the dynamics of the proposed model for the converter interface for the solar plant. Cole and Belmans [15]
large-signal disturbances but uninfluenced by the dynamics of suggest that the dynamics of the PLL can be ‘neglected in power
other elements. system stability studies’ and have accordingly structured their
• Section 3.2.2 uses a portion of the system of an actual North reduced order models. However, the approximate representation of
American utility. The results observed in this section, and its the fast dynamics of the inner current control loop and the PLL for
comparison to detailed electromagnetic results serves to highlight weak-grid (low short circuit strength) connection points can result
the practical use of this proposed model. in an inaccurate representation of the stability of the resources. To
showcase the importance of the dynamics of the inner current
Thus, for each type of disturbance, first a simple fictitious control loop working in tandem with the PLL, two versions of the
system is used to show the behaviour of the individual model on its converter interface model were used. In the first version (called
Version A), the inner current control loop was entirely replaced by
90 IET Gener. Transm. Distrib., 2020, Vol. 14 Iss. 1, pp. 87-97
© The Institution of Engineering and Technology 2019
Fig. 5 Synthetic single machine infinite bus setup
Fig. 6 Active power output of converter for an elliptical change in active power reference. The inset shows the observed response when x = 0.01 pu while the
main figure shows the observed response when x = 0.505 pu. Both figures also compare the behaviour of Version A of the proposed model (with inner current
control loop represented only as first-order time constant) against the behaviour of Version B of the proposed model (with explicit representation of the inner
current control loop dynamics)
a first-order time constant (as is in the present state-of-the-art model. It goes without saying that the presence of the inner
REGC_A model), but the dynamics of the PLL were represented. current control loop does not contribute to the oscillation by
The second version of the model (called Version B) had itself, but rather how it is tuned (values of the control gains)
representation of the dynamics of both the inner current control and the system strength.
loop and the PLL. The second version of the model is the complete ii. The presence of the PLL and the gain settings of the PLL.
model with the block diagram shown in Fig. 4. Note that the iii. The system short-circuit strength as seen by the comparison of
algebraic iterations to enforce the current limits at every time step results when the value of x = 0.01 pu as compared to when the
is incorporated in both versions, since voltage source interfaces are value of x = 0.505 pu.
used. In both versions of the model, the PLL control parameters iv. The system loading which relates to the operation point.
were KPLLi = 1500 and KPLLp = 20.0. In the Version B of the
model, the inner current control loop parameters were KIp = 5.0 Furthermore, the presence of the oscillations is influenced by
and KIi = 70.0 while in Version A of the model, the time constant the initial power output of the plant. To show the impact of the
that represented the characteristics of the inner current control loop initial conditions and also provide a further insight into the impact
was set to a value of 0.07 s. of short circuit strength at the point of interconnection, the
In order to represent the increase in solar irradiation through the behaviour of the converter resource for a 5 MW step change in
day, an elliptical change in active power reference command was power command (both in the positive and negative direction) is
played into the REEC_A model. The performance of the model to shown in Figs. 7 and 8 for an operating point of 90 and 100 MW
two different system short circuit strength scenarios was analysed. respectively. Only the Version B of proposed model which has
The short circuit capacity at the terminal of the solar plant was explicit representation of both the inner current control loops and
varied by changing the reactance X of the transmission line the phase locked loop is used in these results.
highlighted in Fig. 5. A high short circuit rating was represented From these results, the role played by the initial operating
with a value of 0.01 pu while a low short circuit ratio was condition and the direction of change in the power reference
represented with a value of 0.505 pu. The active power output of command can be observed. In a high short circuit scenario
the converter for both the low short circuit and the high short (x = 0.01 pu), there are no oscillations observed. In a low short
circuit scenario is shown in Fig. 6 for the elliptical change in power circuit scenario (x = 0.505 pu), the oscillatory mode is excited after
reference command. the active power output reaches around 95 MW. However, for the
It can be seen for the low short circuit scenario, as the active downward change in step reference (from 95 to 90 MW), the
power output increases, the dynamics of the inner current control presence of positive damping can be seen, because the downward
loop and the PLL give rise to growing oscillations which change returns the plants back below the loading level where
subsequently get damped out as the active power output reduces. oscillations start. However, with an initial operating point of 100
However, these oscillations are not visible in Version A of the MW, the oscillations are present for both an upward and downward
model when the inner current control loop is replaced by the single step, since the plant is already above the power level (95 MW)
first-order time constant. The observed oscillations are not where oscillations start.
‘electromechanical’ even though they have an oscillatory This behaviour can be used to explain the presence of
frequency of around 5 Hz. The oscillations here are purely oscillations in Fig. 6 only during the downward change in active
electrical and are driven by a combination of four factors: power reference. This is because the oscillations only start once
power has exceeded 95 MW, and this happens only around the peak
i. The presence of the inner-current control loop and its of the curve in Fig. 6. Thus, the oscillations start near the peak and
interaction with the dynamics of the PLL as shown by the are observable on the way down, until the damping becomes
difference in results between Version A and Version B of the
Fig. 8 Active power output of the converter for step changes in power reference with operating point of 100 MW. The blue curve is the output observed of the
proposed model with x = 0.01 pu while the red curve is the output observed with x = 0.505 pu
positive once we move below 95 MW and thus eventually damp generation level of the two large solar sources were reduced to 200
out completely. and 190 MW, respectively. For this plant, the generic state-of-the-
Such small-signal oscillations are however not an artefact of art dynamic models supplied to the transmission operator
simulation as they have also been observed in the output of actual comprised of the REGC_A converter interface model, REEC_B
converter plants. The next system setup looks into the ability of the electrical control model and the REPC_A plant controller model.
modified positive sequence model to represent the oscillatory The REGC_A model was replaced with the proposed converter
behaviour observed at a solar plant. model to validate the effectiveness of the proposed model. The
electrical controller and plant controller models were retained. As
3.1.2 In-service solar plant: Recently, an in-frequent small-signal in the synthetic system, an elliptical change in active power
stability issue, shown in Fig. 9, was observed from measurement reference of the REPC_A model was imposed for varying values of
data collected near the terminals of a 500 MW solar plant [16]. An the grid tie impedance. The phase locked loop control parameters
in-depth analysis into the cause of the oscillations revealed that the were KPLLi = 2000 and KPLLp = 20.0 and the inner current control
fast controllers of the converters in the plant were reacting to the loop parameters were KIp = 5.0 and KIi = 70.0. It must be noted
change in output active power level. Additionally, from that these parameters values are not necessarily the actual control
information obtained from the transmission system operator, it was gains of the converters in the plant, but are instead representative
inferred that on that given day, the converter plant was connected generic values. With the original value of the grid tie impedance
to a relatively lower short circuit network. While the converter (high short circuit), Fig. 11 shows the active power output of one of
controllers in the plant have since been re-tuned, the present state- the large generators of the plant.
of-the-art positive sequence generic models supplied to the The blue curve represents the output from the state-of-the-art
transmission system operator were unable to predict this oscillatory REGC_A model while the red curve is the output from the
behaviour as the dynamics of the fast controller loops were not proposed new converter model. It can be seen that for a strong
represented. connection, i.e. high short circuit, the state-of-the-art converter
The layout of the solar plant, with respect to the bulk power models are a good approximation of the fast dynamics of the inner
system is shown in Fig. 10. To model and simulate the same current controller and PLL, and there is no significant difference
approximate operating condition shown in Fig. 9, the active power between the outputs from the two converter models. However, as
Fig. 11 Active power output of solar plant with original grid tie impedance. The blue curve is the output observed while using the state-of-the-art REGC_A
model while the red curve is the output observed with the proposed model
Fig. 12 Active power output of solar plant with low short circuit grid tie impedance. The blue curve is the output observed while using the state-of-the-art
REGC_A model while the red curve is the output observed with the proposed model
to also be evaluated. Two system setups are again chosen for this A more detailed analysis is carried out with another fictitious
exercise. The first setup is a fictitious system, while the second test system shown by the one-line diagram in Fig. 15.
setup is representative of a portion of a utility's bulk power system. The source at bus 2 (at the right side of the diagram) was
represented by a classical machine with an MVA of 1000.0, inertia
3.2.1 Synthetic system for large-signal behaviour: Two of 5.0 s and D = 1.5. For comparison of the behaviour of the
synthetic systems have been used to observe the performance of proposed model against existing state-of-the-art models, the source
the model to large-signal disturbances. The first system studied is at bus 9 (left side of the diagram) was represented by different
the same single machine infinite bus system used in Section 3.1.1. converter interface models, along with the generic REEC_A model
Three scenarios were analysed as described below: in voltage control mode. The impedance of the source at bus 2 was
used to vary the short circuit strength of the system with
i. With x = 0.01 pu, the application of a 6 cycle bolted three- X′′ = 0.0025 pu representing a high short circuit system and
phase fault on bus 2 using the proposed model. The response is X′′ = 3.0 pu representing a low short circuit system.
shown by the blue curve. From a PSCAD® simulation, the response of the converter
ii. With x = 0.505 pu, the application of a 6 cycle bolted three- energy source for a 12 cycle three phase fault at bus 1 is shown in
phase fault on bus 2 using the proposed model. The response is Figs. 16 and 17 for both the high and low short circuit case,
shown by the red curve. respectively, while Table 2 elaborates on the description of the
iii. With x = 0.505 pu, the application of a 6 cycle bolted three- legend in the plot. The representation of the model in PSCAD® is
phase fault on bus 2 using the state-of-the-art REGC_A model. the same representation as used in [2]. A three phase average
The response is shown by the green curve. model of the converter has been used with explicit representation
of all grid side converter control loops. It can clearly be seen that
With a high short circuit strength, the system is able to ride the present state-of-the-art positive sequence current source
through a three-phase fault in a stable manner. However, with a converter model (i.e. REGC_A) is unable to represent the
low short circuit strength, the existing state-of-the-art REGC_A oscillatory behaviour observed in the point on wave simulation for
model shows that the response would be stable while the proposed a low short circuit scenario. With the proposed modified positive
new model shows the possibility of oscillatory instability. This type sequence model, for the same location and duration of the fault,
of oscillatory instability has been observed even in field Figs. 18 and 19 show the performance of the model for high and
measurements. Thus, a model such as that proposed here might low short circuit, respectively. In this model and for this system,
offer a means to further investigate such possibilities. re = 0.0025 pu, xe = 0.1 pu, Imax = 1.2 pu, KIp = 5.0, KIi = 60.0,
5 References
[1] Pourbeik, P., Sanchez-Gasca, J.J., Senthil, J., et al.: ‘Value and limitations of
the positive sequence generic models of renewable energy systems’, [Online]:
Available at https://www.wecc.org/Reliability/White%20Paper%20Generic
%20Model%20Limitations.pdf, accessed December 2015
[2] Wang, W., Huang, G.M., Kansal, P., et al.: ‘Instability of PLL-synchronized
converter-based generators in low short-circuit systems and the limitations of
positive sequence modeling’. 2018 North American Power Symp. (NAPS),
2018, pp. 1–5
[3] WECC Renewable Energy Modeling Task Force: ‘WECC PV power plant
dynamic modeling guide’. Available at https://www.wecc.biz/Reliability/
WECC%20Solar%20Plant%20Dynamic%20Modeling%20Guidelines.pdf,
accessed April 2014
Fig. 24 Comparison of angle output of the PLL of WTG 5 for the stable [4] ‘Model user guide for generic renewable energy system models’. Technical
scenario across positive sequence and point on wave simulation platforms, Report 3002014083, EPRI, Palo Alto, CA, 2018
[5] Pourbeik, P., Sanchez-Gasca, J.J., Senthil, J., et al.: ‘Generic dynamic models
and variation of control gains for modeling wind power plants and other renewable technologies in large-
scale power system studies’, IEEE Trans. Energy Conver., 2017, 32, (3), pp.
1108–1116
[6] ‘Renewable energy systems modeling considerations for weak grid studies -
limitations of positive sequence models in comparison with three-phase
models’. Technical Report 3002010928, EPRI, Palo Alto, CA., 2017
[7] Cai, R., Ruan, J., Huang, X., et al.: ‘Research on grid instability caused by the
interactions in microgrid’. CIRED Workshop 2018, June 2018, pp. 1–4
[8] National Grid: ‘Performance of phase-locked loop based converters’.
Available at https://www.nationalgrideso.com/sites/eso/files/documents/Phase
%20locked%20loop%20FINAL.pdf, accessed December 2017
[9] Ramasubramanian, D., Yu, Z., Ayyanar, R., et al.: ‘Converter model for
representing converter interfaced generation in large scale grid simulations’,
IEEE Trans. Power Syst., 2017, 32, (1), pp. 765–773
[10] Pourbeik, P.: ‘Proposed REGC_B Model’. Available at https://www.wecc.biz/
Administrative/REMTF_REGC_A_and_REGC_B_0317.pdf, accessed March
2017
[11] Ramasubramanian, D., Vittal, V., Farantatos, E.: ‘Enforcing strict current
Fig. 25 Comparison of angle output of the PLL of WTG 5 for the unstable control in controlled voltage source converter model for use in large scale
scenario across positive sequence and point on wave simulation platforms, positive sequence time domain simulations’. 2018 Power Systems
and variation of control gains Computation Conf. (PSCC), Dublin, Ireland, June 2018, pp. 1–8
[12] ‘PSCAD’, Manitoba HVDC Research Centre, 2018. Available at https://
hvdc.ca/pscad/
comparison with the performance of a detailed converter control [13] ‘PSS®E’, Siemens PTI, 2018. Available at https://new.siemens.com/
system in an electromagnetic time-domain simulation. global/en/products/energy/services/transmission-distribution-smart-grid/
However, it must be mentioned that this model does not intend consulting-and-planning/pss-software/pss-e.html
to replace the importance and necessity of detailed point on wave [14] ‘Concorda Positive Sequence Load Flow Software(PSLF)’, General Electric
International, Inc., 2018. Available at http://www.geenergyconsulting.com/
simulations. Positive sequence simulation tools and models, while practice-area/software-products/pslf
being an advantageous and convenient platform to simulate the [15] Cole, S., Belmans, R.: ‘A proposal for standard VSC HVDC dynamic models
bulk power system, still have many limitations. The behaviour of in power system stability studies’, Electr. Pow. Syst. Res., 2011, 81, pp. 967–
converter interfaced generation under every and all circumstances 973
[16] First Solar Inc.: ‘Deploying utility-scale PV power plants in weak grids’.
can only be gleaned from detailed point on wave simulations. 2017 IEEE Power & Energy Society General Meeting, July 2017
However, there is a significant burden involved in running a point [17] NERC Inverter-Based Resource Performance Task Force: ‘Reliability
on wave simulation, and thus, engineering judgment has to be used guideline: BPS-connected inverter-based resource performance’. Technical
in deciding the simulation platform for a particular study. Report, North American Electric Reliability Corporation, September 2018
[18] ‘Integrating inverter-based resources into low short circuit strength systems’.
Unfortunately, industry wide there is no simple answer as of yet to Technical Report, North American Electric Reliability Corporation, December
evaluate the exact scenario or location at which a detailed 2017
simulation study has to be conducted. The proposed positive [19] Working Group B4.62: ‘Connection of wind farms to weak AC networks’.
sequence model described in this paper serves to bridge the gap Technical Report, CIGRE, December 2016